400kv protection presentation
DESCRIPTION
400kv Protection presentationTRANSCRIPT
400KV PROTECTION400KV PROTECTION400KV PROTECTION400KV PROTECTIONPREPARED BYPREPARED BY
GOPALA KRISHNA PALEPUGOPALA KRISHNA PALEPUADE/APTRANSCOADE/APTRANSCO
[email protected], [email protected], Mobile:9440336984Mobile:9440336984
BASICS BASICS OF OF OF OF
ONE AND HALF ONE AND HALF CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER
SCHEMESCHEMEPREPARED BY
GOPALA KRISHNA PALEPUADE/MRT(PROTECTION)
ONE & HALF BREAKER DESCRIPTIONONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-1 BUS-2
1. IN THIS TWO BUSES ARE PRIOVIDED.
BUS-1 BUS-2
BUS-2
ONE & HALF BREAKER DESCRIPTIONONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-1 BUS-2
2. THESE TWO BUSES ARE INTER-CONNECTED BY THREE CIRCUIT BREAKERS.
BUS-1 BUS-2
BUS-2
ONE & HALF BREAKER DESCRIPTIONONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-1 BUS-2
1-52 CB
3. THEY ARE DESIGNATED AS 1-52 CB, 2-52 CB, 3-52 CB.
BUS-1 BUS-2
2-52 CB
1-52 CB 3-52 CB
BUS-2
3-52 CB
2-52 CB
ONE & HALF BREAKER DESCRIPTIONONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-1 BUS-2
1-52 CB
4. LINE - 1 IS CONNECTED IN BETWEEN 1-52 CB & 2-52 CB.
5. LINE - 2 IS CONNECTED IN BETWEEN 3-52 CB & 2-52 CB.
BUS-1 BUS-2
2-52 CB
1-52 CB 3-52 CB
LINE-1
BUS-2
3-52 CB
2-52 CB
LINE-2
LINE-1 LINE-2
ONE & HALF BREAKER DESCRIPTIONONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-1 BUS-2
1-52 CB
6. LINE-1 HAVING TWO FEEDING PATHS i.eA. VIA BUS-1 & 1-52 CBB. VIA BUS-2, 3-52 CB & 2-52 CB
7. LINE-2 HAVING TWO FEEDING PATHS i.eA. VIA BUS-2 & 3-52 CBB. VIA BUS-1, 1-52 CB & 2-52 CB
BUS-1 BUS-2
2-52 CB
1-52 CB 3-52 CB
LINE-1
BUS-2
3-52 CB
2-52 CBLINE-2
LINE-1 LINE-2
ONE & HALF BREAKER DESCRIPTIONONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-1 BUS-2
1-52 CB
8. FOR INTURUPTING LINE-1 THE 1-52CB AND 2-52CB IS TO BE TRIPPED.
9. FOR INTURUPTING LINE-2 THE 3-52CB AND 2-52CB IS TO BE TRIPPED.
BUS-1 BUS-2
2-52 CB
1-52 CB 3-52 CB
LINE-1
BUS-2
3-52 CB
2-52 CB
LINE-2
LINE-1 LINE-2
ONE & HALF BREAKER DESCRIPTIONONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-1 BUS-2
1-52 CB
10. FOR ANY PROBLEM IN LINE-1 OR LINE-2 ALONG WITH MAIN BREAKER THE MIDDLE BREAKER OR SAY TIE BREAKER (2-52 CB) MUST TRIP.
BUS-1 BUS-2
2-52 CB
1-52 CB 3-52 CB
LINE-1
BUS-2
3-52 CB
2-52 CB
LINE-2
LINE-1 LINE-2
ONE & HALF BREAKER DESCRIPTIONONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-1 BUS-2
1-52 CB13. SO THESE TWO FEEDERS CONTROLLED BY THREE CIRCUIT BREAKERS
IT IS CALLED ONE & HALF BREAKER SYSTEM.
11. NORMALLY IN ALL TYPES OF BUSBAR CONFIGUARATIONS ONE BREAKER IS SUFFICIENT FOR ONE FEEDER.
12. HERE TWO FEEDERS ARE CONTROLED BY THREE BREAKERS.
BUS-1 BUS-2
2-52 CB
1-52 CB 3-52 CB
LINE-1
BUS-2
3-52 CB
2-52 CB
LINE-2
LINE-1 LINE-2
ONE & HALF BREAKER DESCRIPTIONONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-1 BUS-2
1-52 CB
14. THE BAY BETWEEN BUS-1 & LINE-1 IS CALLED MAIN BAY FOR FEEDER-1.
MA
IN B
AY
(1S
TB
AY
) F
OR
FE
ED
ER
-1
BUS-1 BUS-2
2-52 CB
1-52 CB 3-52 CB
LINE-1
MA
IN B
AY
(1
BA
Y)
FO
R F
EE
DE
R-1
BUS-2
3-52 CB
2-52 CB
LINE-2
LINE-1 LINE-2
MA
IN B
AY
(1S
TB
AY
) F
OR
FE
ED
ER
ONE & HALF BREAKER DESCRIPTIONONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-1 BUS-2
1-52 CB
MA
IN B
AY
(1S
TB
AY
) F
OR
FE
ED
ER
-1 15. THE BAY BETWEEN LINE-1 & LINE-2 IS CALLED TIE BAY FOR FEEDER-1 & 2.
BUS-1 BUS-2
2-52 CB
1-52 CB 3-52 CB
LINE-1
MA
IN B
AY
(1
BA
Y)
FO
R F
EE
DE
R-1
TIE
BA
Y (
2N
DB
AY
) F
OR
FE
ED
ER
-1 &
2
BUS-2
3-52 CB
2-52 CB
LINE-2
LINE-1 LINE-2
MA
IN B
AY
(1S
TB
AY
) F
OR
FE
ED
ER
TIE
BA
Y (
2
TIE BAY (2ND BAY ) FOR FEEDER-1 & 2.
ONE & HALF BREAKER DESCRIPTIONONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-1 BUS-2
1-52 CB
MA
IN B
AY
(1S
TB
AY
) F
OR
FE
ED
ER
-1 16. THE BAY BETWEEN BUS-2 & LINE-2 IS CALLED MAIN BAY FOR FEEDER-2.
BUS-1 BUS-2
2-52 CB
1-52 CB 3-52 CB
LINE-1
MA
IN B
AY
(1
BA
Y)
FO
R F
EE
DE
R-1
TIE
BA
Y (
2N
DB
AY
) F
OR
FE
ED
ER
-1 &
2
BA
Y)
FO
R F
EE
DE
R-2
BUS-2
3-52 CB
2-52 CB
LINE-2
LINE-1 LINE-2
MA
IN B
AY
(1S
TB
AY
) F
OR
FE
ED
ER
TIE
BA
Y (
2
TIE BAY (2ND BAY ) FOR FEEDER-1 & 2.
MA
IN B
AY
(3R
DB
AY
) F
OR
FE
ED
ER
-2
MA
IN B
AY
(3R
D
ONE & HALF BREAKER DESCRIPTIONONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-1 BUS-2
1-52 CB
MA
IN B
AY
(1S
TB
AY
) F
OR
FE
ED
ER
-1
17. IN THIS SYSTEM FULL DIA MEANS 2 FEEDERS CONTROLLED BY 3 CBs.18. HALF DIA MEANS 1 FEEDER CONTROLLED BY 2 CBs.
(Nothing but Double CB System)
BUS-1 BUS-2
2-52 CB
1-52 CB 3-52 CB
LINE-1
MA
IN B
AY
(1
BA
Y)
FO
R F
EE
DE
R-1
TIE
BA
Y (
2N
DB
AY
) F
OR
FE
ED
ER
-1 &
2
BA
Y)
FO
R F
EE
DE
R-2
BUS-2
3-52 CB
2-52 CB
LINE-2
LINE-1 LINE-2
MA
IN B
AY
(1S
TB
AY
) F
OR
FE
ED
ER
TIE
BA
Y (
2
TIE BAY (2ND BAY ) FOR FEEDER-1 & 2.
MA
IN B
AY
(3R
DB
AY
) F
OR
FE
ED
ER
-2
MA
IN B
AY
(3R
D
ONE & HALF BREAKER DESCRIPTIONONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-1 BUS-2
1-52 CB
MA
IN B
AY
(1S
TB
AY
) F
OR
FE
ED
ER
-1
GOPALA KRISHNA PALEPU ADE/MRT/ T&C/400KV SS/
O/O CE/400KV / L&SS/ VSAPTRANSCO, [email protected]
Mobile: 9440336984
BUS-1 BUS-2
2-52 CB
1-52 CB 3-52 CB
LINE-1
MA
IN B
AY
(1
BA
Y)
FO
R F
EE
DE
R-1
TIE
BA
Y (
2N
DB
AY
) F
OR
FE
ED
ER
-1 &
2
BA
Y)
FO
R F
EE
DE
R-2
BUS-2
3-52 CB
2-52 CB
LINE-2
LINE-1 LINE-2
MA
IN B
AY
(1S
TB
AY
) F
OR
FE
ED
ER
TIE
BA
Y (
2
TIE BAY (2ND BAY ) FOR FEEDER-1 & 2.
MA
IN B
AY
(3R
DB
AY
) F
OR
FE
ED
ER
-2
MA
IN B
AY
(3R
D
SUBSTATION DESIGN/LAYOUT SUBSTATION DESIGN/LAYOUT (I(I--CONFIGUARATION)CONFIGUARATION)
FEEDER1 FEEDER3 FEEDER5 FEEDER7 FEEDER9 FEEDER11
BUSBUS--11 DIA1 DIA2 DIA3 DIA4 DIA5 DIA6
BA
Y1
BA
Y2
BA
Y4
BA
Y5
BA
Y7
BA
Y8
BA
Y10
BA
Y11
BA
Y13
BA
Y14
BA
Y16
BA
Y17
FEEDER2 FEEDER4 FEEDER6 FEEDER8 FEEDER10 FEEDER12
BUSBUS--22
BA
Y3
BA
Y6
BA
Y9
BA
Y12
BA
Y15
BA
Y18
SUBSTATION DESIGN/LAYOUTSUBSTATION DESIGN/LAYOUT(D(D--CONFIGUARATION)CONFIGUARATION)
FEEDER1 FEEDER2 FEEDER5 FEEDER6 FEEDER9 FEEDER10
BAY2 BAY8 BAY14
BUSBUS--22
BUSBUS--11
BA
Y1
BA
Y3
BA
Y4
BA
Y6
BA
Y7
BA
Y9
BA
Y10
BA
Y12
BA
Y13
BA
Y15
BA
Y16
BA
Y18
DIA1 DIA3 DIA5
DIA6
FEEDER3 FEEDER4 FEEDER7 FEEDER8 FEEDER11 FEEDER12
BA
Y4
BAY5
BA
Y6
BA
Y10
BAY11
BA
Y12
BA
Y16
BAY17
BA
Y18
DIA2 DIA4 DIA6
CT METHODS CT METHODS IN IN IN IN
ONE AND HALF ONE AND HALF CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER
SCHEMESCHEMEPREPARED BY
GOPALA KRISHNA PALEPUADE/MRT(PROTECTION)
DIFFERENT CT METHODS OF ONE & HALF BREAKER SYSTEMDIFFERENT CT METHODS OF ONE & HALF BREAKER SYSTEM
3 CT METHOD3 CT METHOD
4 CT METHOD4 CT METHOD
LINE
LINE
CB CB CB
CB CB CB
AT/F
AT/FCB CB CB
6 CT METHOD6 CT METHOD
6 CT METHOD6 CT METHOD
LINE
LINECB CB CB
CB CB CB
AT/F
AT/F
5 CT METHOD5 CT METHODLINE
CB CB CB
AT/F
6 CT METHOD6 CT METHOD
LINE
AT/F
6 CT METHOD6 CT METHOD
LINECB CB CB
AT/F
LINE8 CT METHOD8 CT METHOD
AT/F
CB CB CB
SINGLE BUS SYSTEMSINGLE BUS SYSTEM
11--52CB52CB1-89 1-89L
1-CT
P2 P1
BUS
1-CVTBB-EVT / CVT
BU
SB
AR
MA
IN1
PR
OT
BU
SB
AR
MA
IN1
PR
OT
BU
SB
AR
MA
IN2
PR
OT
BU
SB
AR
MA
IN2
PR
OT
BC
U +
EN
ER
GY
ME
TE
RB
CU
+ E
NE
RG
Y M
ET
ER
1 P
RO
TE
CT
ION
1 P
RO
TE
CT
ION
FO
R L
INE
(2
1L
1/8
7L
1)
FO
R L
INE
(2
1L
1/8
7L
1)
PR
OT
EC
TIO
NP
RO
TE
CT
ION
FO
R L
INE
(2
1L
2/8
7L
2)
FO
R L
INE
(2
1L
2/8
7L
2)
12345
1
BU
SB
AR
MA
IN1
PR
OT
BU
SB
AR
MA
IN1
PR
OT
(87
BB
M1
+ L
BB
)(8
7B
BM
1+
LB
B)
BU
SB
AR
MA
IN2
PR
OT
BU
SB
AR
MA
IN2
PR
OT
(87
BB
M2
+ L
BB
)(8
7B
BM
2+
LB
B)
BC
U +
EN
ER
GY
ME
TE
RB
CU
+ E
NE
RG
Y M
ET
ER
FO
R L
INE
FO
R L
INE
MA
INM
AIN
--1 P
RO
TE
CT
ION
1 P
RO
TE
CT
ION
FO
R L
INE
(2
1L
1/8
7L
1)
FO
R L
INE
(2
1L
1/8
7L
1)
MA
INM
AIN
--22P
RO
TE
CT
ION
PR
OT
EC
TIO
NF
OR
LIN
E (
21
L2
/87
L2
)F
OR
LIN
E (
21
L2
/87
L2
)
1 2 3
1
2
3
LATEST CONCEPT
REDUNDANT LINE PROTECTION, REDUNDANT ICT PROTECTION, REDUNDANT BUSBAR
PROTECTION, LBB IS IN BUILT FUNCTION OF BUSBAR
400KV C.T. INFORMATION400KV C.T. INFORMATIONP1 P2
P1 P2
PRIMARY CONNECTIONS : P1 – P2
CURRENT RATING : 2000 AMPS
CORES CLASS PURPOSE
SECONDARY CONNECTIONS
CURRENT RATING : 1A
HAIRHAIR
CORES CLASS PURPOSE CURRENT RATING : 1A
2000/ 1A 1000/ 1A 500/ 1A
CORE-1 PSBUSBAR
PROTECTION1S1 – 1S3
1S1 – 1S2
1S2 – 1S3
__
CORE-2 PS
BUSBAR
CHECKUP
PROTECTION
2S1 – 2S32S1 – 2S2
2S2 – 2S3__
1
2
3
4
5
1 5
EYE BOLT EYE BOLT DESIGNDESIGN
HAIRHAIRPIN / PIN /
U SHAPE U SHAPE DESIGNDESIGN
DEAD TANK DESIGNDEAD TANK DESIGN
CORE-3 0.2 METERING 3S1 – 3S43S1 – 3S3
3S4 – 3S2
3S1 – 3S2
3S4 – 3S3
CORE-4 PSMAIN-2
PROTECTION4S1 – 4S4
4S1 – 4S3
4S4 – 4S2
4S1 – 4S2
4S4 – 4S3
CORE-5 PSMAIN-1
PROTECTION5S1 – 5S4
5S1 – 5S3
5S4 – 5S2
5S1 – 5S2
5S4 – 5S3
1
2
3
4
5
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM
1-89 3-89
BUS-1 BUS-2
(3CT METHOD)(3CT METHOD)
1-89A
11--52CB52CB
3-89A
33--52CB52CB
1-CT
P1
P2
3-CTP1
P2
2-CT
P1 P2
LINE 1
22--52CB52CB2-89A 2-89B
1-89L 3-89T
T/F-1
CT CONNECTIONS IN 3CT METHODCT CONNECTIONS IN 3CT METHOD
CORECORE 1 1 –– CTCT 2 2 –– CTCT 3 3 –– CTCT
CORE CORE –– 11( PS)( PS)
MAIN1 BUSBARMAIN1 BUSBAR--1 1
PROTECTION LBB IN BUILTPROTECTION LBB IN BUILT
(87BB1M1)(87BB1M1)
MAIN1 DIFFFERENTIAL MAIN1 DIFFFERENTIAL
PROTECTION FOR PROTECTION FOR
TRANSFORMER (87T1)TRANSFORMER (87T1)
MAIN1 BUSBARMAIN1 BUSBAR--2 2
PROTECTION LBB IN BUILTPROTECTION LBB IN BUILT
(87BB2M1)(87BB2M1)(87BB1M1)(87BB1M1) TRANSFORMER (87T1)TRANSFORMER (87T1) (87BB2M1)(87BB2M1)
CORE CORE –– 2 2 ( PS)( PS)
MAIN2 BUSBARMAIN2 BUSBAR--1 1
PROTECTION LBB INBUILT PROTECTION LBB INBUILT
(87BB1M2)(87BB1M2)
BACKUP PROTECTION FOR BACKUP PROTECTION FOR
TRANSFORMER (67 HV)TRANSFORMER (67 HV)
MAIN2 BUSBARMAIN2 BUSBAR--2 2
PROTECTION LBB IN BUILT PROTECTION LBB IN BUILT
(87BB2M2)(87BB2M2)
CORE CORE –– 3 3 ( 0.2)( 0.2)
SPARESPAREHV BCU + HV ENERGY HV BCU + HV ENERGY
METER FOR AT/F HVMETER FOR AT/F HVSPARESPARE
CORE CORE –– 4 4 BCU + ENERGY METER BCU + ENERGY METER BCU + ENERGY METER BCU + ENERGY METER HV BCU + HV ENERGY HV BCU + HV ENERGY CORE CORE –– 4 4 (0.2)(0.2) FOR FEEDERFOR FEEDER FOR FEEDERFOR FEEDER METER FOR AT/F HVMETER FOR AT/F HV
CORE CORE –– 5 5 ( PS)( PS)
MAINMAIN--2 LINE PROTECTION 2 LINE PROTECTION
FOR FEEDER (21 L2 / 87L2)FOR FEEDER (21 L2 / 87L2)
MAINMAIN--2 LINE PROTECTION 2 LINE PROTECTION
FOR FEEDER (21 L2 / 87L2)FOR FEEDER (21 L2 / 87L2)
BACKUP PROTECTION FOR BACKUP PROTECTION FOR
TRANSFORMER (67 HV)TRANSFORMER (67 HV)
CORE CORE –– 6 6 ( PS)( PS)
MAINMAIN--1 LINE PROTECTION1 LINE PROTECTION
FOR FEEDER (21L1/87L1)FOR FEEDER (21L1/87L1)
MAINMAIN--1 LINE PROTECTION1 LINE PROTECTION
FOR FEEDER (21L1/87L1)FOR FEEDER (21L1/87L1)
MAIN1 DIFFFERENTIAL MAIN1 DIFFFERENTIAL
PROTECTION FOR PROTECTION FOR
TRANSFORMER (87T1)TRANSFORMER (87T1)
CT CONNECTIONS IN 3CT METHODCT CONNECTIONS IN 3CT METHOD
CORECORE 1 1 –– CTCT 2 2 –– CTCT 3 3 –– CTCT
CORE CORE –– 11( PS)( PS)
MAIN1 BUSBARMAIN1 BUSBAR--1 1
PROTECTION LBB IN BUILTPROTECTION LBB IN BUILT
(87BB1M1)(87BB1M1)
MAIN1 DIFFFERENTIAL MAIN1 DIFFFERENTIAL
PROTECTION FOR PROTECTION FOR
TRANSFORMER (87T1)TRANSFORMER (87T1)
MAIN1 BUSBARMAIN1 BUSBAR--2 2
PROTECTION LBB IN BUILTPROTECTION LBB IN BUILT
(87BB2M1)(87BB2M1)(87BB1M1)(87BB1M1) TRANSFORMER (87T1)TRANSFORMER (87T1) (87BB2M1)(87BB2M1)
CORE CORE –– 2 2 ( PS)( PS)
MAIN2 BUSBARMAIN2 BUSBAR--1 1
PROTECTION LBB INBUILT PROTECTION LBB INBUILT
(87BB1M2)(87BB1M2)
BACKUP PROTECTION FOR BACKUP PROTECTION FOR
TRANSFORMER (67 HV)TRANSFORMER (67 HV)
MAIN2 BUSBARMAIN2 BUSBAR--2 2
PROTECTION LBB IN BUILT PROTECTION LBB IN BUILT
(87BB2M2)(87BB2M2)
CORE CORE –– 3 3 (0.2)(0.2)
BCU + ENERGY METER BCU + ENERGY METER
FOR FEEDERFOR FEEDER
BCU + ENERGY METER BCU + ENERGY METER
FOR FEEDERFOR FEEDERSPARESPARE
CORE CORE –– 4 4 MAINMAIN--2 LINE PROTECTION 2 LINE PROTECTION MAINMAIN--2 LINE PROTECTION 2 LINE PROTECTION BACKUP PROTECTION FOR BACKUP PROTECTION FOR CORE CORE –– 4 4 ( PS)( PS) FOR FEEDER (21 L2 / 87L2)FOR FEEDER (21 L2 / 87L2) FOR FEEDER (21 L2 / 87L2)FOR FEEDER (21 L2 / 87L2) TRANSFORMER (67 HV)TRANSFORMER (67 HV)
CORE CORE –– 5 5 ( PS)( PS)
MAINMAIN--1 LINE PROTECTION1 LINE PROTECTION
FOR FEEDER (21L1/87L1)FOR FEEDER (21L1/87L1)
MAINMAIN--1 LINE PROTECTION1 LINE PROTECTION
FOR FEEDER (21L1/87L1)FOR FEEDER (21L1/87L1)
MAIN1 DIFFFERENTIAL MAIN1 DIFFFERENTIAL
PROTECTION FOR PROTECTION FOR
TRANSFORMER (87T1)TRANSFORMER (87T1)
BUSHING CT BUSHING CT
METERING CORE METERING CORE (0.2)(0.2)
NORMALLY THIS SYTEM ADOPTS, WHEN ONE SIDE LINE, OTHER SIDE AUTO NORMALLY THIS SYTEM ADOPTS, WHEN ONE SIDE LINE, OTHER SIDE AUTO
TRANSFORMER OR BUS REACTOR IS PROVIDED IN A DIA OF ONE AND HALF BREAKER TRANSFORMER OR BUS REACTOR IS PROVIDED IN A DIA OF ONE AND HALF BREAKER
SYSTEM, IF BUSHING CT METERING CORE IS AVAILABLE, THEN IT IS USED FOR HV BCU SYSTEM, IF BUSHING CT METERING CORE IS AVAILABLE, THEN IT IS USED FOR HV BCU
+ HV ENERGY METER FOR AT/F HV OR BUS REACTOR+ HV ENERGY METER FOR AT/F HV OR BUS REACTOR
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM
BUS-1 BUS-2
(3CT METHOD)(3CT METHOD)
79+25(BCU)
79+25(BCU)
VBB1
VL1/VL2OR VBB2
VBB2
VL2/VL1OR VBB1
87BB1M1BU
87BB1M2BU
BCU+EM (L)
MAIN1:21L1 / 87L1
MAIN2: 21L2/87L2
87BB2M1BU
87BB2M2BU
SPARE
MAIN1:87T1
B/U: 67HV
BC
U+
EM
(H
V)
MA
IN1:8
7T
1
B/U
: 67LV
79+25(BCU)
OR VBB2 OR VBB1
VBB1/VL1
VBB2/VL2
LINE 1
ICT
BC
U+
EM
(L)
MA
IN1:2
1L
1 / 8
7L
1
MA
IN2: 2
1L
2/8
7L
2
MA
IN1:8
7T
1
B/U
: 67H
V
BC
U+
EM
(H
V)
MA
IN2:8
7T
2
MA
IN1:8
7T
1
B/U
: 67LVVBB2/VL2
LB
B
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM(3CT METHOD) (3CT METHOD) –– LINE PROTECTIONLINE PROTECTION
BU
S-1
BCU+EMBCU+EM
MAIN2: 21L2MAIN2: 21L2
FIBER
MAIN1: 87BB1MAIN1: 87BB1
MAIN2 :87BB1MAIN2 :87BB1
MAIN1: 21L1MAIN1: 21L1
LINE FIBEROPTIC
OPTIC
C
E
50Z +87BBCENTRAL UNITLBB IS INBUILT
BUSBAR
ABB Network Partner AG
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ABB Network Partner AG REL 316*4
C
E
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM(3CT METHOD) (3CT METHOD) –– ICT PROTECTIONICT PROTECTION
BU
S-2
TIE LBBTIE LBB
MAIN1: 87BB2MAIN1: 87BB2
MAIN2 :87BB2MAIN2 :87BB2
BCU+EMBCU+EM
MAIN2: 87T2MAIN2: 87T2
B/U: 67HVB/U: 67HV
50Z +87BB
ABB Network Partner AG
1
2
9
10
ABB Network Partner AG REL 316*4
ICT
MAIN1: 87T1MAIN1: 87T1
C
E
50Z +87BBCENTRAL UNITLBB IS INBUILT
BUSBAR
3
4
5
6
7
8
11
12
13
14
15
16
C
E
B/U: 67LVB/U: 67LV
ONE & HALF BREAKER ( 3 CT METHOD) WITH PROTECTION SCHEMEONE & HALF BREAKER ( 3 CT METHOD) WITH PROTECTION SCHEME
87BB1
CVT
VBB1
79
25
BF
VL1 / VL2
OR VBB2
VBB1
87L 21M2 CVT VL1VL1
BUSBARBUSBAR--11
21M1 VL1
79
25
FEEDER1 / LINE1
FEEDER2 / LINE2
BF
VL1 / VBB1
VL2 / VBB2
87BB2
CVT
VBB279
25VBB2
BF
VL2 / VL1
OR VBB1
FEEDER2 / LINE2
CVT VL2
BUSBARBUSBAR--22
MAIN-1
MAIN-2PROTECTION OF LINE2
(OR TRANSFORMER, IF APPLICABLE)
FOR TRANSFORMER PROTECTION & METERING VOLTAGE SELECTION RELAYS FOR BUS-1, BUS-2& LINE ARE PROVIDED .
BU
S-I
BU
S-I
I
MA
IN-1
MA
IN-2
ME
T+
SY
N
MA
IN-1
MA
IN-2
ME
T+
SY
N87 B
B M
1 B
US
BA
R P
RO
TN
MA
IN-1
87 B
B M
1 B
US
BA
R P
RO
TN
MA
IN-1
87 B
B M
2 B
US
BA
R P
RO
TN
MA
IN-2
87 B
B M
2 B
US
BA
R P
RO
TN
MA
IN-2
21L1
-LI
NE
DIS
T P
RO
T1
21L2
-LI
NE
DIS
T P
RO
T2
87T
1-IC
T D
IFF
PR
OT
1
67H
V-
ICT
DIR
O/C
,E/F
ONE & HALF BREAKER ( 3 CT METHOD) WITH PROTECTION SCHEMEONE & HALF BREAKER ( 3 CT METHOD) WITH PROTECTION SCHEME
BU
S
BU
S
1-52
CB
2-52
CB
3-52
CB
MAIN-1MAIN-2
MET+SYN
ME
T+
SY
N
ME
T+
SY
N
DISTURBANCE RECORDER,
EVENT RECORDER, FAULT LOCATOR
ARE IN BUILT FUNCTIONS IN BOTH
DISTURBANCE RECORDER,
EVENT RECORDER,
ARE IN BUILT FUNCTIONS IN BOTH
NUMERICAL DIFF PROT RELAYS
87T2- ICT DIFF PROT2
ARE IN BUILT FUNCTIONS IN BOTH
NUMERICAL DIST PROT RELAYS
21L1 & 21L2
NUMERICAL DIFF PROT RELAYS
87T1 & 87T2
FOR ICT CVT IS NOT AVAILABLE.
ACCORDING TO CONDITION IT IS SELECTED
BUS-1 CVT OR BUS-2 CVT OR LINE CVT
HV & LV OVER FLUX PROT ARE IN BUILT.
ICT HV METERING IS BUSHING CT
LATEST CONCEPT
REDUNDANT LINE PROTECTION
REDUNDANT ICT PROTECTION
REDUNDANT DISTRIBUTED BUSBAR PROTECTION
LBB IS IN BUILT FUNCTION OF BUSBAR
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM
1-89 3-89
BUS-1 BUS-2
(4CT METHOD)(4CT METHOD)
1-89A
11--52CB52CB
3-89A
33--52CB52CB
1-CTP1
P2
3-CTP1
P2
2-ACTP1P2
2-BCT
P1 P2
LINE 1
22--52CB52CB2-89A 2-89B
1-89L 3-89T
T/F-1
CORECORE 11-- CTCT 22--BCTBCT 22--ACTACT 33--CTCT
CORECORE--1 1 (PS)(PS)
MAIN1 BUSBARMAIN1 BUSBAR--1 1
PROTECTION PROTECTION
LBB IN BUILTLBB IN BUILT
(87BB1M1)(87BB1M1)
SPARESPARE SPARESPARE
MAIN1 BUSBARMAIN1 BUSBAR--2 2
PROTECTION PROTECTION
LBB IN BUILTLBB IN BUILT
(87BB2M1)(87BB2M1)
CT CONNECTIONS IN 4CT METHODCT CONNECTIONS IN 4CT METHOD
(87BB1M1)(87BB1M1) (87BB2M1)(87BB2M1)
CORECORE--2 2 (PS)(PS)
MAIN2 BUSBARMAIN2 BUSBAR--1 1
PROTECTION PROTECTION
LBB INBUILT LBB INBUILT
(87BB1M2)(87BB1M2)
TIE LBBTIE LBB SPARESPARE
MAIN2 BUSBARMAIN2 BUSBAR--2 2
PROTECTION PROTECTION
LBB INBUILT LBB INBUILT
(87BB2M2)(87BB2M2)
CORECORE--3 3 (0.2)(0.2)
BCU + ENERGY BCU + ENERGY
METER METER
FOR FEEDERFOR FEEDER
BCU + ENERGY BCU + ENERGY
METER METER
FOR FEEDERFOR FEEDER
HV BCU + HV HV BCU + HV
ENERGY METER ENERGY METER
FOR ICT HVFOR ICT HV
HV BCU + HV HV BCU + HV
ENERGY METER ENERGY METER
FOR ICT HVFOR ICT HV
MAINMAIN--2 LINE 2 LINE MAINMAIN--2 LINE 2 LINE BACKUP BACKUP BACKUP BACKUP
CORECORE--4 4 (PS)(PS)
MAINMAIN--2 LINE 2 LINE
PROTECTION FOR PROTECTION FOR
FEEDERFEEDER
(21 L2 / 87L2)(21 L2 / 87L2)
MAINMAIN--2 LINE 2 LINE
PROTECTION FOR PROTECTION FOR
FEEDER FEEDER
(21 L2 / 87L2)(21 L2 / 87L2)
BACKUP BACKUP
PROTECTION FOR PROTECTION FOR
TRANSFORMER TRANSFORMER
(67 HV)(67 HV)
BACKUP BACKUP
PROTECTION FOR PROTECTION FOR
TRANSFORMERTRANSFORMER
(67 HV)(67 HV)
CORECORE--5 5 (PS)(PS)
MAINMAIN--1 LINE 1 LINE
PROTECTIONPROTECTION FOR FOR
FEEDER FEEDER
(21L1/87L1)(21L1/87L1)
MAINMAIN--1 LINE 1 LINE
PROTECTIONPROTECTION FOR FOR
FEEDER FEEDER
(21L1/87L1)(21L1/87L1)
MAIN1MAIN1--ICT ICT
DIFFFERENTIAL DIFFFERENTIAL
PROTECTION FOR PROTECTION FOR
TRANSFORMER TRANSFORMER
(87T1)(87T1)
MAIN1 MAIN1 ––ICT ICT
DIFFFERENTIAL DIFFFERENTIAL
PROTECTION FOR PROTECTION FOR
TRANSFORMER TRANSFORMER
(87T1)(87T1)
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM
BUS-1 BUS-2
(4 CT METHOD)(4 CT METHOD)
79+25(BCU)
79+25(BCU)
VBB1
VL1/VL2OR VBB2
VBB2
VL2/VL1OR VBB1
87BB1M1BU
87BB1M2BU
BCU+EM (L)
MAIN1:21L1 / 87L1
MAIN2: 21L2/87L2
87BB2M1BU
87BB2M2BU
MAIN1:87T1
B/U: 67HV
BCU+EM (HV)
MA
IN1:8
7T
1
B/U
: 67LV
79+25(BCU)
OR VBB2 OR VBB1
VBB1/VL1
VBB2/VL2
LINE 1
ICT
BC
U+
EM
(HV
)
MA
IN1:2
1L
1 / 8
7L
1
MA
IN2: 2
1L
2/8
7L
2
MA
IN1:8
7T
1
B/U
: 67H
V
MA
IN2:8
7T
2
MA
IN1:8
7T
1
B/U
: 67LV
TIE
LB
B
BC
U+
EM
(L)
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM(4CT METHOD) (4CT METHOD) –– LINE PROTECTIONLINE PROTECTION
BU
S-1
BCU+EM(L)BCU+EM(L)
MAIN2: 21L2MAIN2: 21L2
FIBER
MAIN1: 87BB1MAIN1: 87BB1
MAIN2 :87BB1MAIN2 :87BB1
MAIN1: 21L1MAIN1: 21L1
TIE LBB
LINE FIBEROPTIC
OPTIC
C
E
50Z +87BBCENTRAL UNITLBB IS INBUILT
BUSBAR
ABB Network Partner AG
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ABB Network Partner AG REL 316*4
C
E
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM(4CT METHOD) (4CT METHOD) –– ICT PROTECTIONICT PROTECTION
BU
S-2
MAIN1: 87BB2MAIN1: 87BB2
MAIN2 :87BB2MAIN2 :87BB2
BCU+EM (HV)BCU+EM (HV)
MAIN2: 87T2MAIN2: 87T2
B/U: 67HVB/U: 67HV
50Z +87BB
ABB Network Partner AG
1
2
9
10
ABB Network Partner AG REL 316*4
ICT
MAIN1: 87T1MAIN1: 87T1
C
E
50Z +87BBCENTRAL UNITLBB IS INBUILT
BUSBAR
3
4
5
6
7
8
11
12
13
14
15
16
C
E
B/U: 67LVB/U: 67LV
ONE & HALF BREAKER ( 4 CT METHOD) WITH PROTECTION SCHEMEONE & HALF BREAKER ( 4 CT METHOD) WITH PROTECTION SCHEME
87BB1
CVT
VBB1
79
25
BF
VL1 / VL2
OR VBB2
VBB1
87L 21M2 CVT VL1VL1
BUSBARBUSBAR--11
21M1 VL1
FEEDER1 / LINE1
FEEDER2 / LINE2
BF
79
25VL1 / VBB1
VL2 / VBB2
87BB2
CVT
VBB279
25VBB2
BF
VL2 / VL1
OR VBB1
FEEDER2 / LINE2
CVT VL2
BUSBARBUSBAR--22
MAIN-1
MAIN-2PROTECTION OF LINE2
(OR TRANSFORMER, IF APPLICABLE)
FOR TRANSFORMER PROTECTION & METERING VOLTAGE SELECTION RELAYS FOR BUS-1, BUS-2& LINE ARE PROVIDED .
BU
S-I
BU
S-I
I
MA
IN-1
MA
IN-2
ME
T+
SY
N
MA
IN-1
MA
IN-2
ME
T+
SY
N87 B
B M
1 B
US
BA
R P
RO
TN
MA
IN-1
87 B
B M
1 B
US
BA
R P
RO
TN
MA
IN-1
87 B
B M
2 B
US
BA
R P
RO
TN
MA
IN-2
87 B
B M
2 B
US
BA
R P
RO
TN
MA
IN-2
21L1
-LI
NE
DIS
T P
RO
T1
21L2
-LI
NE
DIS
T P
RO
T2
87T
1-IC
T D
IFF
PR
OT
1
67H
V-
ICT
DIR
O/C
,E/F
ONE & HALF BREAKER ( 4 CT METHOD) WITH PROTECTION SCHEMEONE & HALF BREAKER ( 4 CT METHOD) WITH PROTECTION SCHEME
BU
S
BU
S
1-52
CB
2-52
CB
3-52
CB
MAIN-1MAIN-2
MET+SYN
ME
T+
SY
N
ME
T+
SY
N
DISTURBANCE RECORDER,
EVENT RECORDER, FAULT LOCATOR
ARE IN BUILT FUNCTIONS IN BOTH
NUMERICAL DIST PROT RELAYS
DISTURBANCE RECORDER,
EVENT RECORDER,
ARE IN BUILT FUNCTIONS IN BOTH
NUMERICAL DIFF PROT RELAYS
87T2- ICT DIFF PROT2
NUMERICAL DIST PROT RELAYS
21L1 & 21L2
NUMERICAL DIFF PROT RELAYS
87T1 & 87T2
FOR ICT CVT IS NOT AVAILABLE.
ACCORDING TO CONDITION IT IS SELECTED
BUS-1 CVT OR BUS-2 CVT OR LINE CVT
HV & LV OVER FLUX PROT ARE IN BUILT
LATEST CONCEPT
REDUNDANT LINE PROTECTION
REDUNDANT ICT PROTECTION
REDUNDANT DISTRIBUTED BUSBAR PROTECTION
LBB IS IN BUILT FUNCTION OF BUSBAR
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM
3-89
BUS-1 BUS-2
1-89P1P1
1A-CT 3A-CT
(6CT METHOD)(6CT METHOD)
1-89A
11--52CB52CB
1B-CT
3-89A
33--52CB52CB
3B-CT
2B-CT
P2
P1
P2
P1
P2 P1P1 P2
P2
P1
P21A-CT
2A-CT
3A-CT
LINE 1
22--52CB52CB2-89A 2-89B
1-89L 3-89T
T/F-1
CURRENT TRANSFORMERCURRENT TRANSFORMER
CONNECTIONS IN 6CT METHODCONNECTIONS IN 6CT METHOD(GIS or AIS with DEAD TANK CBs) (GIS or AIS with DEAD TANK CBs)
1B1B--CTCT 1A1A--CTCT 2B2B--CTCT 2A2A--CTCT 3A3A--CTCT 3B3B--CTCT
CORECORE--1 1 MAIN1 MAIN1 2CT’s SECONDARIES 2CT’s SECONDARIES 2CT’s SECONDARIES 2CT’s SECONDARIES MAIN1 MAIN1 CORECORE--1 1
(PS)(PS)
MAIN1 MAIN1 BUSBARBUSBAR--1 1
PROTN PROTN LBB IN BUILT LBB IN BUILT
(87BB1M1)(87BB1M1)
2CT’s SECONDARIES 2CT’s SECONDARIES ARE CONNECTED ARE CONNECTED IN PARALLEL AND IN PARALLEL AND CONNECTED TO CONNECTED TO
MAINMAIN--1 PROTECTION1 PROTECTION
2CT’s SECONDARIES 2CT’s SECONDARIES ARE CONNECTED ARE CONNECTED CONNECTED TO CONNECTED TO
MAINMAIN--1 PROTECTION1 PROTECTION
MAIN1 MAIN1 BUSBARBUSBAR--22
PROTN LBB IN PROTN LBB IN BUILTBUILT
(87BB2M1)(87BB2M1)
CORECORE--2 2
(PS)(PS)
MAIN2 MAIN2 BUSBARBUSBAR--1 1
PROTN PROTN LBB INBUILT LBB INBUILT (87BB1M2)(87BB1M2)
2CT’s SECONDARIES 2CT’s SECONDARIES ARE CONNECTED INARE CONNECTED IN
PARALLEL AND PARALLEL AND CONNECTED TOCONNECTED TO
MAINMAIN--2 PROTECTION 2 PROTECTION
2CT’s SECONDARIES 2CT’s SECONDARIES ARE CONNECTED INARE CONNECTED IN
PARALLEL AND PARALLEL AND CONNECTED TO CONNECTED TO
BACKUP PROTECTION BACKUP PROTECTION
MAIN2 MAIN2 BUSBARBUSBAR--2 2
PROTN LBB PROTN LBB INBUILT INBUILT
(87BB2M2)(87BB2M2)
CORECORE--3 3
(0.2)(0.2)
SPARESPARE 2CT’s SECONDARIES 2CT’s SECONDARIES ARE CONNECTED INARE CONNECTED IN
PARALLEL AND PARALLEL AND CONNECTED TO CONNECTED TO
BCU + ENERGY BCU + ENERGY METER FOR METER FOR
FEEDERFEEDER
2CT’s SECONDARIES 2CT’s SECONDARIES ARE CONNECTED INARE CONNECTED IN
PARALLEL AND PARALLEL AND CONNECTED TO CONNECTED TO
HV BCU + HV HV BCU + HV ENERGY METER FOR ENERGY METER FOR
ICT HVICT HV
SPARESPARE
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM
BUS-1 BUS-2
(6CT METHOD)(6CT METHOD)
MAIN1:21L1 / 87L1
MAIN2: 21L2/87L2
MAIN1:87T1
B/U: 67HV
87BB1M1BU
87BB1M2BU
BCU+EM (L)
MAIN2: 21L2/87L2
87BB2M1BU
87BB2M2BU
B/U: 67HV
BCU+EM (HV)
MA
IN1:8
7T
1
B/U
: 67LV
79+25(BCU)
79+25(BCU)
79+25(BCU)
VBB1
VL1/VL2OR VBB2
VBB2
VL2/VL1OR VBB1
VB
B1/V
L1
VB
B2/V
L2
LINE 1
ICT
BC
U+
EM
(HV
)
MA
IN1:2
1L
1 / 8
7L
1
MA
IN2: 2
1L
2/8
7L
2
MA
IN1:8
7T
1
B/U
: 67H
V
MA
IN2:8
7T
2
MA
IN1:8
7T
1
B/U
: 67LV
TIE
LB
B
BC
U+
EM
(L)
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM(6CT METHOD) (6CT METHOD) –– LINE PROTECTIONLINE PROTECTION
BU
S-1
BCU+EM(L)BCU+EM(L)
MAIN2: 21L2MAIN2: 21L2
FIBER
MAIN1: 87BB1MAIN1: 87BB1
MAIN2 :87BB1MAIN2 :87BB1
MAIN1: 21L1MAIN1: 21L1
TIE LBB
LINE FIBEROPTIC
OPTIC
C
E
50Z +87BBCENTRAL UNITLBB IS INBUILT
BUSBAR
ABB Network Partner AG
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ABB Network Partner AG REL 316*4
C
E
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM(6CT METHOD) (6CT METHOD) –– ICT PROTECTIONICT PROTECTION
BU
S-2
MAIN1: 87BB2MAIN1: 87BB2
MAIN2 :87BB2MAIN2 :87BB2
BCU+EM (HV)BCU+EM (HV)
MAIN2: 87T2MAIN2: 87T2
B/U: 67HVB/U: 67HV
50Z +87BB
ABB Network Partner AG
1
2
9
10
ABB Network Partner AG REL 316*4
ICT
MAIN1: 87T1MAIN1: 87T1
C
E
50Z +87BBCENTRAL UNITLBB IS INBUILT
BUSBAR
3
4
5
6
7
8
11
12
13
14
15
16
C
E
B/U: 67LVB/U: 67LV
ONE & HALF BREAKER ( 6 CT METHOD) WITH PROTECTION SCHEMEONE & HALF BREAKER ( 6 CT METHOD) WITH PROTECTION SCHEME
87BB1
CVT
VBB1
BF
79
25
VL1 / VL2
VBB187L 21M2 CVT VL1
VL1
BUSBARBUSBAR--11
21M1 VL1
VL1 / VL2
OR VBB2 FEEDER1 / LINE1
FEEDER2 / LINE2
BF
79
25VL1 / VBB1
VL2 / VBB2
87BB2
CVT
VBB279
25VBB2
VL2 / VL1
OR VBB1
FEEDER2 / LINE2
CVT VL2
BUSBARBUSBAR--22
MAIN-1
MAIN-2
PROTECTION OF LINE2(OR TRANSFORMER, IF APPLICABLE)
FOR TRANSFORMER PROTECTION & METERING VOLTAGE SELECTION RELAYS FOR BUS-1, BUS-2& LINE ARE PROVIDED .
BF
TYPICAL ONE & HALF BREAKER TYPICAL ONE & HALF BREAKER SYSTEM ADOPTED IN GISSYSTEM ADOPTED IN GIS
DS : DISCONNECTOR SWITCH, GS: GROUNDING SWITCH, CT: CURRENT TRANSFORMER, VD: VOLTAGE DIVIDER
TYPICAL ONE & HALF BREAKER TYPICAL ONE & HALF BREAKER SYSTEM ADOPTED IN GISSYSTEM ADOPTED IN GIS
1-1/2 CB SYSTEM (SIEMENS VATECH)
VDVD
VDVD
DS : DISCONNECTOR SWITCH, GS: GROUNDING SWITCH, CT: CURRENT TRANSFORMER, VD: VOLTAGE DIVIDER
CT CT CT CT CT CT
VDVD
DSDSDSDSDSDS
GS
GS
GS
GS
GS
GS
GS
GS
CB CB CB
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM
3-89
BUS-1 BUS-2
1-89
(5CT METHOD)(5CT METHOD)
1-89A
11--52CB52CB
1-CT
3-89A
33--52CB52CB
3-CT
2-CT
P2
P1
P2
P1
P1 P2
LINE 1
22--52CB52CB
1L-CT
2-89A 2-89B
1-89L 3-89T
T/F-1
3T-CTP2
P1
P2
P1
CORECORE 11--CTCT 11--LCTLCT 22--CTCT 33--TCTTCT 33--CTCT
CORECORE--1 1
(PS)(PS)
MAIN1 BUSBARMAIN1 BUSBAR--1 1
PROTECTION PROTECTION
LBB IN BUILTLBB IN BUILT
(87BB1M1)(87BB1M1)
TEED PROTTEED PROT--11(BAY 1&2)(BAY 1&2)
TEED PROTTEED PROT--11(BAY 2&3)(BAY 2&3)
TEED PROTTEED PROT--11(BAY 2&3)(BAY 2&3)
MAIN1 BUSBARMAIN1 BUSBAR--2 2
PROTECTION PROTECTION
LBB IN BUILTLBB IN BUILT
(87BB2M1)(87BB2M1)
CT CONNECTIONS IN 5CT METHODCT CONNECTIONS IN 5CT METHOD
CORECORE--2 2
(PS)(PS)
MAIN2 BUSBARMAIN2 BUSBAR--1 1
PROTECTION PROTECTION
LBB INBUILT LBB INBUILT
(87BB1M2)(87BB1M2)
TEED PROTTEED PROT--22(BAY 1&2)(BAY 1&2)
TEED PROTTEED PROT--22(BAY 2&3)(BAY 2&3)
TEED PROTTEED PROT--22(BAY 2&3)(BAY 2&3)
MAIN2 BUSBARMAIN2 BUSBAR--2 2
PROTECTION PROTECTION
LBB INBUILT LBB INBUILT
(87BB2M2)(87BB2M2)
CORECORE--3 3
(0.2)(0.2)BCU (L)BCU (L)
ENERGY ENERGY METER (L)METER (L)
BCU (L)BCU (L)ENERGY ENERGY
METER (HV)METER (HV)
SPARE SPARE
BCU (HV) BCU (HV) Bushing CTBushing CT
CORECORE--4 4 TEED PROTTEED PROT--22MAINMAIN--22
PROTECTIONPROTECTIONTEED PROTTEED PROT--22(BAY 1&2) +(BAY 1&2) +
BACKUPBACKUP--ICTICTPROTECTIONPROTECTION
TEED PROTTEED PROT--22CORECORE--4 4
(PS)(PS)TEED PROTTEED PROT--22
(BAY 1&2)(BAY 1&2)PROTECTIONPROTECTION(21 L2 / 87L2)(21 L2 / 87L2)
(BAY 1&2) +(BAY 1&2) +TIE LBBTIE LBB
PROTECTIONPROTECTION(67 HV)(67 HV)
TEED PROTTEED PROT--22(BAY 2&3)(BAY 2&3)
CORECORE--5 5
(PS)(PS)TEED PROTTEED PROT--11
(BAY 1&2)(BAY 1&2)
MAINMAIN--11PROTECTIONPROTECTION
(21L1/87L1)(21L1/87L1)
TEED PROTTEED PROT--11(BAY 1&2)(BAY 1&2)
MAIN1MAIN1--ICT ICT
DIFFFERENTIAL DIFFFERENTIAL
PROTECTION PROTECTION
(87T1)(87T1)
TEED PROTTEED PROT--11(BAY 2&3)(BAY 2&3)
Paralleling of 2Nos CTs to the Main-1/Main-2/Backup line protection is not required. This gives better transient response. Separate STUB protection can be connected (Nothing BUT TEED Protection).
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM(5CT METHOD)(5CT METHOD)
87B
B1M
1B
U
87B
B1M
2B
U
87 T
EE
D
87 T
EE
D
87 T
EE
D
87 T
EE
D
87 T
EE
D
87 T
EE
D
87 T
EE
D
87 T
EE
D87B
B2M
1B
U
87B
B2M
2B
U
BU
S-1
BU
S-2
LBB
87B
B1M
1
87B
B1M
2
BC
U (L
)
87 T
EE
D-1
(1&
2)
87 T
EE
D-2
(1&
2)
87 T
EE
D-1
(2&
3)
87 T
EE
D-2
(2&
3)
87 T
EE
D-1
(1&
2)
87 T
EE
D-2
(1&
2)
87 T
EE
D-1
(2&
3)
87 T
EE
D-2
(2&
3)
BC
U (L
)
SP
AR
E
87B
B2M
1
87B
B2M
2
87 TEED-2 (1&2)
EM (L)
87 TEED-2 (3&2)
EM (HV)
MAIN1:87T1
B/U: 67HV
MA
IN1:8
7T
1
B/U
: 67LV
MAIN1:21L1 / 87L1
MAIN2: 21L2/87L2
ICT
MA
IN2:8
7T
2
87 TEED-1 (1&2)
87 TEED-2 (1&2)
87 TEED-1 (3&2)
87 TEED-2 (3&2)
MA
IN1:8
7T
1
B/U
: 67LV
BC
U (
HV
)
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM(5CT METHOD) (5CT METHOD) –– LINE PROTECTIONLINE PROTECTION
BU
S-1
BCUBCU
ABB Network Partner AG REL 316*4
87 TEED1 (BAY 1&2)87 TEED1 (BAY 1&2)
TIE LBB
MAIN1: 87BB1MAIN1: 87BB1
MAIN2 :87BB1MAIN2 :87BB1 MAIN1: 21L1MAIN1: 21L1
MAIN2: 21L2MAIN2: 21L2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
C
E
87 TEED2 (BAY 1&2)87 TEED2 (BAY 1&2)
LINE C
E
50Z +87BBCENTRAL UNITLBB IS INBUILT
BUSBAR
ABB Network Partner AG
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ABB Network Partner AG REL 316*4
C
E
EMEM
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM(5CT METHOD) (5CT METHOD) –– ICT PROTECTIONICT PROTECTION
BU
S-2
87 TEED1 (BAY 2&3)87 TEED1 (BAY 2&3)
87 TEED2 (BAY 2&3)87 TEED2 (BAY 2&3)
MAIN1: 87BB2MAIN1: 87BB2
MAIN2 :87BB2MAIN2 :87BB2
EMEM
B/U: 67HVB/U: 67HV
50Z +87BB
ABB Network Partner AG
1
2
9
10
ABB Network Partner AG REL 316*4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ABB Network Partner AG REL 316*4
C
E
ICT
MAIN1: 87T1MAIN1: 87T1
C
E
50Z +87BBCENTRAL UNITLBB IS INBUILT
BUSBAR
3
4
5
6
7
8
11
12
13
14
15
16
C
E
B/U: 67LVB/U: 67LV
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM(5CT METHOD) (5CT METHOD) –– ICT ICT –– BUSHING CT PROTECTIONBUSHING CT PROTECTION
MAIN2: 87T2MAIN2: 87T2
BCU((HV)BCU((HV)
MAIN2: 87T2MAIN2: 87T2
MAIN2: 87T2MAIN2: 87T2
33--PH HIGH IMPEDANCEPH HIGH IMPEDANCE
33--PH LOW IMPEDANCEPH LOW IMPEDANCE
ONE & HALF BREAKER ( 5 CT METHOD) WITH PROTECTION SCHEMEONE & HALF BREAKER ( 5 CT METHOD) WITH PROTECTION SCHEME
87BB1
CVT
VBB1
79
25
BF
VL1 / VL2
OR VBB2
VBB1
CVT VL1
87L 21M2VL1
BUSBARBUSBAR--1121M1 VL1
87 TD1 HZ
87 TD2 LZ
.
79
25
FEEDER1 / LINE1
FEEDER2 / LINE2
BF
VL1 / VBB1
VL2 / VBB2
87BB2
CVT
VBB279
25VBB2
BF
VL2 / VL1
OR VBB1
FEEDER2 / LINE2
CVT VL2
BUSBARBUSBAR--22
MAIN-1
MAIN-2
PROTECTION OF LINE2(OR TRANSFORMER, IF APPLICABLE)
87 TD1 HZ
87 TD2 LZ
.
FOR TRANSFORMER PROTECTION & METERING VOLTAGE SELECTION RELAYS FOR BUS-1, BUS-2& LINE ARE PROVIDED .
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM
3-89
BUS-1 BUS-2
1-89
(6CT METHOD)(6CT METHOD)
1-89A
11--52CB52CB
1-CT
3-89A
33--52CB52CB
3-CT
2B-CT
P2
P1
P2
P1
P1 P2P2 P12A-CT
LINE 1
22--52CB52CB2-89A 2-89B
1-89L 3-89T
T/F-1
P2
P1
P2
P11L-CT 3T-CT
11--CTCT 1L1L--CTCT 2A2A--CTCT 2B2B--CTCT 3T3T--CTCT 33--CTCT
CORECORE--1 1
(PS)(PS)
MAIN1 MAIN1
BUSBARBUSBAR--1 1
PROTECTION PROTECTION
LBB IN BUILTLBB IN BUILT
(87BB1M1)(87BB1M1)
TEED TEED
PROTPROT--11
(BAY 1&2)(BAY 1&2)
SPARESPARE SPARESPARE
TEED TEED
PROTPROT--11
(BAY 2&3)(BAY 2&3)
MAIN1 MAIN1
BUSBARBUSBAR--2 2
PROTECTION PROTECTION
LBB IN BUILTLBB IN BUILT
(87BB2M1)(87BB2M1)
CT CONNECTIONS IN 6CT METHODCT CONNECTIONS IN 6CT METHOD
(87BB1M1)(87BB1M1) (87BB2M1)(87BB2M1)
CORECORE--2 2
(PS)(PS)
MAIN2 MAIN2
BUSBARBUSBAR--1 1
PROTECTION PROTECTION
LBB INBUILT LBB INBUILT
(87BB1M2)(87BB1M2)
TEED TEED
PROTPROT--22
(BAY 1&2)(BAY 1&2)
TIE LBBTIE LBB SPARESPARE
TEED TEED
PROTPROT--22
(BAY 2&3)(BAY 2&3)
MAIN2 MAIN2
BUSBARBUSBAR--2 2
PROTECTION PROTECTION
LBB INBUILT LBB INBUILT
(87BB2M2)(87BB2M2)
CORECORE--3 3
(0.2)(0.2)BCU (L)BCU (L)
ENERGY ENERGY
METERMETER
BCUBCU
(HV)(HV)
BCU (L)BCU (L) ENERGY ENERGY
METERMETER
BCUBCU
(HV)(HV)
CORECORE--4 4
(PS)(PS)
TEED TEED
PROTPROT--22
(BAY 1&2)(BAY 1&2)
MAINMAIN--22
PROTECTION PROTECTION
(21L2/87L2)(21L2/87L2)
TEED TEED
PROTPROT--22
(BAY 2&3)(BAY 2&3)
TEED TEED
PROTPROT--22
(BAY 1&2)(BAY 1&2)
BACKUPBACKUP--ICTICT
PROTECTION PROTECTION
(67 HV)(67 HV)
TEED TEED
PROTPROT--22
(BAY 2&3) (BAY 2&3)
CORECORE--5 5
(PS)(PS)
TEED TEED
PROTPROT--11
(BAY 1&2)(BAY 1&2)
MAINMAIN--11
PROTECTION PROTECTION
(21L1/87L1)(21L1/87L1)
TEED TEED
PROTPROT--11
(BAY 2&3)(BAY 2&3)
TEED TEED
PROTPROT--11
(BAY 1&2)(BAY 1&2)
MAIN1 MAIN1 -- ICT ICT DIFFERENTIALDIFFERENTIAL
PROTECTIONPROTECTION
(87T1)(87T1)
TEED TEED
PROTPROT--11
(BAY 2&3)(BAY 2&3)
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM(6CT METHOD)(6CT METHOD)
87B
B1M
1B
U
87B
B1M
2B
U
87 T
EE
D
87 T
EE
D
87 T
EE
D
87 T
EE
D
87 T
EE
D
87 T
EE
D
87 T
EE
D
87 T
EE
D87B
B2M
1B
U
87B
B2M
2B
U
BU
S-1
BU
S-2
LBB
87B
B1M
1
87B
B1M
2
BC
U (L
)
87 T
EE
D-1
(1&
2)
87 T
EE
D-2
(1&
2)
87 T
EE
D-1
(2&
3)
87 T
EE
D-2
(2&
3)
87 T
EE
D-1
(1&
2)
87 T
EE
D-2
(1&
2)
87 T
EE
D-1
(2&
3)
87 T
EE
D-2
(2&
3)
BC
U (L
)
BC
U(H
V)
87B
B2M
1
87B
B2M
2
87 TEED-2 (1&2)
EM (L)
87 TEED-2 (3&2)
EM (HV)
MAIN1:87T1
B/U: 67HV
MA
IN1:8
7T
1
B/U
: 67LV
MAIN1:21L1 / 87L1
MAIN2: 21L2/87L2
BC
U (H
V)
ICT
MA
IN2:8
7T
2
87 TEED-1 (1&2)
87 TEED-2 (1&2)
87 TEED-1 (3&2)
87 TEED-2 (3&2)
MA
IN1:8
7T
1
B/U
: 67LV
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM(6CT METHOD) (6CT METHOD) –– LINE PROTECTIONLINE PROTECTION
BU
S-1
BCUBCU
87 TEED1 (BAY 1&2)87 TEED1 (BAY 1&2)
TIE LBB
ABB Network Partner AG REL 316*4
MAIN1: 87BB1MAIN1: 87BB1
MAIN2 :87BB1MAIN2 :87BB1 MAIN1: 21L1MAIN1: 21L1
MAIN2: 21L2MAIN2: 21L2
87 TEED2 (BAY 1&2)87 TEED2 (BAY 1&2)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
C
E
LINE C
E
50Z +87BBCENTRAL UNITLBB IS INBUILT
BUSBAR
ABB Network Partner AG
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ABB Network Partner AG REL 316*4
C
E
EMEM
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM(6CT METHOD) (6CT METHOD) –– ICT PROTECTIONICT PROTECTION
BU
S-2
87 TEED1 (BAY 2&3)87 TEED1 (BAY 2&3)
87 TEED2 (BAY 2&3)87 TEED2 (BAY 2&3)
BCU(HV)BCU(HV)
MAIN1: 87BB2MAIN1: 87BB2
MAIN2 :87BB2MAIN2 :87BB2
EM(HV)EM(HV)
B/U: 67HVB/U: 67HV
50Z +87BB
ABB Network Partner AG
1
2
9
10
ABB Network Partner AG REL 316*4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ABB Network Partner AG REL 316*4
C
E
ICT
MAIN1: 87T1MAIN1: 87T1
C
E
50Z +87BBCENTRAL UNITLBB IS INBUILT
BUSBAR
3
4
5
6
7
8
11
12
13
14
15
16
C
E
B/U: 67LVB/U: 67LV
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM(6CT METHOD) (6CT METHOD) –– ICT ICT –– BUSHING CT PROTECTIONBUSHING CT PROTECTION
MAIN2: 87T2MAIN2: 87T2
MAIN2: 87T2MAIN2: 87T2
MAIN2: 87T2MAIN2: 87T2
33--PH HIGH IMPEDANCEPH HIGH IMPEDANCE
33--PH LOW IMPEDANCEPH LOW IMPEDANCE
ONE & HALF BREAKER ( 6 CT METHOD) WITH PROTECTION SCHEMEONE & HALF BREAKER ( 6 CT METHOD) WITH PROTECTION SCHEME
87BB1
CVT
VBB1
79
25
BF
VL1 / VL2
OR VBB2
VBB1
CVT VL1
87L 21M2VL1
BUSBARBUSBAR--1121M1 VL1
87 TD1 HZ
87 TD2 LZ
.FEEDER1 / LINE1
FEEDER2 / LINE2
BF
79
25VL1 / VBB1
VL2 / VBB2
87BB2
CVT
VBB279
25VBB2
BF
VL2 / VL1
OR VBB1
FEEDER2 / LINE2
CVT VL2
BUSBARBUSBAR--22
MAIN-1
MAIN-2
PROTECTION OF LINE2(OR TRANSFORMER, IF APPLICABLE)
87 TD1 HZ
87 TD2 LZ
.
FOR TRANSFORMER PROTECTION & METERING VOLTAGE SELECTION RELAYS FOR BUS-1, BUS-2& LINE ARE PROVIDED .
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM
3-89
BUS-1 BUS-2
1-89
P1P11A-CT 3A-CT
(8CT METHOD)(8CT METHOD)
1-89A
11--52CB52CB
1B-CT
3-89A
33--52CB52CB
3B-CT
2B-CT
P2
P1
P2
P1
P2 P1P1 P2
P1
P2
P1
P21A-CT
2A-CT
3A-CT
LINE 1
22--52CB52CB2-89A 2-89B
1-89L 3-89T
T/F-1
P2
P11L-CT
P2
P1
3T-CT
CT CONNECTIONS IN 8CT METHODCT CONNECTIONS IN 8CT METHOD
1B1B--CTCT 1A1A--CTCT 1L1L--CTCT 2B2B--CTCT 2A2A--CTCT 3T3T--CTCT 3A3A--CTCT 3B3B--CTCT
CORECORE--1 1
(PS)(PS)
MAIN1 MAIN1
BUSBARBUSBAR--1 1
PROTECTION PROTECTION
LBB IN BUILT LBB IN BUILT
TEEDPROTTEEDPROT--11
(BAY 1&2)(BAY 1&2)
TEED PROTTEED PROT--11
(BAY 1&2)(BAY 1&2)
TEED PROTTEED PROT--11
(BAY 1&2)(BAY 1&2)
TEED PROTTEED PROT--11
(BAY 2&3)(BAY 2&3)
TEED PROTTEED PROT--11
(BAY 2&3)(BAY 2&3)
TEED PROTTEED PROT--11
(BAY 2&3)(BAY 2&3)
MAIN1 MAIN1
BUSBARBUSBAR--2 2
PROTECTION PROTECTION
LBB IN BUILT LBB IN BUILT (PS)(PS) LBB IN BUILT LBB IN BUILT
(87BB1M1(87BB1M1))
(BAY 1&2)(BAY 1&2) (BAY 1&2)(BAY 1&2) (BAY 1&2)(BAY 1&2) (BAY 2&3)(BAY 2&3) (BAY 2&3)(BAY 2&3) (BAY 2&3)(BAY 2&3) LBB IN BUILT LBB IN BUILT
(87BB2M1)(87BB2M1)
CORECORE--2 2
(PS)(PS)
MAIN2 MAIN2
BUSBARBUSBAR--1 1
PROTECTION PROTECTION
LBB INBUILT LBB INBUILT
(87BB1M2)(87BB1M2)
TEED PROTTEED PROT--22
(BAY 1&2)(BAY 1&2)
TEED PROTTEED PROT--22
(BAY 1&2)(BAY 1&2)
TEED PROTTEED PROT--22
(BAY 1&2)(BAY 1&2)
TEED PROTTEED PROT--22
(BAY 2&3)(BAY 2&3)
TEED PROTTEED PROT--22
(BAY 2&3)(BAY 2&3)
TEED PROTTEED PROT--22
(BAY 2&3)(BAY 2&3)
MAIN2 MAIN2
BUSBARBUSBAR--2 2
PROTECTION PROTECTION
LBB INBUILT LBB INBUILT
(87BB2M2)(87BB2M2)
CORECORE--3 3
(0.2)(0.2)BCU (L) SPARESPARE
ENERGY ENERGY
METER (L)METER (L)BCU (L) BCU (HV)
ENERGY ENERGY
METER (HV)METER (HV)SPARESPARE BCU (HV)
(0.2)(0.2)
CORECORE--4 4
(PS)(PS)
TEED-1 FOR
BAY-1 & 2 IS:
1L-CT, 1A-CT & 2A-CT
TEED-2 FOR
BAY-1 & 2 IS:
1L-CT, 1B-CT & 2B-CT
MAINMAIN--2 2
LINE LINE PROTECTIONPROTECTION
(21L2/87L2)(21L2/87L2)
MAIN1MAIN1--ICT ICT
DIFFFERENTIALDIFFFERENTIAL
PROTECTION PROTECTION
(87T1)(87T1)
TEED-1 FOR
BAY-2 & 3 IS:
3T-CT, 3A-CT & 2B-CT
TEED-2 FOR
BAY-2 & 3 IS:
3T-CT, 3B-CT & 2A-CT
CORECORE--5 5
(PS)(PS)
MAINMAIN--1 1
LINE LINE
PROTECTIONPROTECTION
(21L1/87L1)(21L1/87L1)
B/UB/U--ICT ICT PROTECTIONPROTECTION
(67 HV)(67 HV)
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM(8CT METHOD)(8CT METHOD)
87B
B1M
1B
U
87B
B1M
2B
U
87 T
EE
D
87 T
EE
D
87 T
EE
D
87 T
EE
D
87 T
EE
D
87 T
EE
D
87 T
EE
D
87 T
EE
D87B
B2M
1B
U
87B
B2M
2B
U
BU
S-1
BU
S-2
LBB
87B
B1M
1
87B
B1M
2
BC
U (L
)
87 T
EE
D-1
(1&
2)
87 T
EE
D-2
(1&
2)
87 T
EE
D-1
(2&
3)
87 T
EE
D-2
(2&
3)
87 T
EE
D-1
(1&
2)
87 T
EE
D-2
(1&
2)
87 T
EE
D-1
(2&
3)
87 T
EE
D-2
(2&
3)
BC
U (L
)
BC
U(H
V)
87B
B2M
1
87B
B2M
2
87 TEED-2 (1&2)
EM (L)
87 TEED-2 (3&2)
EM (HV)
MAIN1:87T1
B/U: 67HV
MA
IN1:8
7T
1
B/U
: 67LV
MAIN1:21L1 / 87L1
MAIN2: 21L2/87L2
BC
U (H
V)
ICT
MA
IN2:8
7T
2
87 TEED-1 (1&2)
87 TEED-2 (1&2)
87 TEED-1 (3&2)
87 TEED-2 (3&2)
MA
IN1:8
7T
1
B/U
: 67LV
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM(8CT METHOD) (8CT METHOD) –– LINE PROTECTIONLINE PROTECTION
BU
S-1
BCUBCU
87 TEED1 (BAY 1&2)87 TEED1 (BAY 1&2)
TIE LBB
ABB Network Partner AG REL 316*4
MAIN1: 87BB1MAIN1: 87BB1
MAIN2 :87BB1MAIN2 :87BB1 MAIN1: 21L1MAIN1: 21L1
MAIN2: 21L2MAIN2: 21L2
87 TEED2 (BAY 1&2)87 TEED2 (BAY 1&2)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
C
E
LINE C
E
50Z +87BBCENTRAL UNITLBB IS INBUILT
BUSBAR
ABB Network Partner AG
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ABB Network Partner AG REL 316*4
C
E
EMEM
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM(8CT METHOD) (8CT METHOD) –– ICT PROTECTIONICT PROTECTION
BU
S-2
87 TEED1 (BAY 2&3)87 TEED1 (BAY 2&3)
87 TEED2 (BAY 2&3)87 TEED2 (BAY 2&3)
BCU(HV)BCU(HV)
MAIN1: 87BB2MAIN1: 87BB2
MAIN2 :87BB2MAIN2 :87BB2
EM(HV)EM(HV)
B/U: 67HVB/U: 67HV
50Z +87BB
ABB Network Partner AG
1
2
9
10
ABB Network Partner AG REL 316*4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ABB Network Partner AG REL 316*4
C
E
ICT
MAIN1: 87T1MAIN1: 87T1
C
E
50Z +87BBCENTRAL UNITLBB IS INBUILT
BUSBAR
3
4
5
6
7
8
11
12
13
14
15
16
C
E
B/U: 67LVB/U: 67LV
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM(8CT METHOD) (8CT METHOD) –– ICT ICT –– BUSHING CT PROTECTIONBUSHING CT PROTECTION
MAIN2: 87T2MAIN2: 87T2
MAIN2: 87T2MAIN2: 87T2
MAIN2: 87T2MAIN2: 87T2
33--PH HIGH IMPEDANCEPH HIGH IMPEDANCE
33--PH LOW IMPEDANCEPH LOW IMPEDANCE
ONE & HALF BREAKER ( 8 CT METHOD) WITH PROTECTION SCHEMEONE & HALF BREAKER ( 8 CT METHOD) WITH PROTECTION SCHEME
87BB1
CVT
VBB1
79
25
BF
VL1 / VL2
OR VBB2
VBB1
CVT VL1
87L 21M2VL1
BUSBARBUSBAR--1121M1 VL1
87 TD1 HZ
87 TD2 LZ
.
.
FEEDER1 / LINE1
FEEDER2 / LINE2
BF
79
25VL1 / VBB1
VL2 / VBB2
87BB2
CVT
VBB279
25VBB2
BF
VL2 / VL1
OR VBB1
FEEDER2 / LINE2
CVT VL2
BUSBARBUSBAR--22
MAIN-1
MAIN-2
PROTECTION OF LINE2(OR TRANSFORMER, IF APPLICABLE)
87 TD1 HZ
87 TD2 LZ
.
FOR TRANSFORMER PROTECTION & METERING VOLTAGE SELECTION RELAYS FOR BUS-1, BUS-2& LINE ARE PROVIDED .
TYPICAL ONE & HALF BREAKER TYPICAL ONE & HALF BREAKER SYSTEM ADOPTED IN GISSYSTEM ADOPTED IN GIS
DS : DISCONNECTOR SWITCH, GS: GROUNDING SWITCH, CT: CURRENT TRANSFORMER, VD: VOLTAGE DIVIDER
1A1A--CTCT
1B1B--CTCT
2A2A--CTCT
2B2B--CTCT
3B3B--CTCT
3A3A--CTCT1L1L--CTCT 3T3T--CTCT
4A4A--CTCT
4B4B--CTCT
5A5A--
5B5B--
6B6B--CTCT
6A6A--CTCT4L4L--CTCT 6T6T--CTCT
CTCT
CTCT
--CTCT
--CTCT
CTCT
CTCT4L4L--CTCT 6T6T--CTCT
NUMERICAL BUSBAR SCHEME INCL LBB/BFR/CBFNUMERICAL BUSBAR SCHEME INCL LBB/BFR/CBF(DECENTRALISED & CENTRALISED ARCHITECTURE)(DECENTRALISED & CENTRALISED ARCHITECTURE)
BU/PU
(REB 500) ABB
DECENTRALISED CONCEPT CENTRALISED CONCEPT
FO
BU/PU
OR
OR
(7 SS 52) SIEMENS
ORFO
OR
(REB 670) ABB
(487B) SEL
BU/PU
OR
(MICOM P740) AREVA
LBB INBUILT FEATUREBU / PU TO BUSBAR
DIGITAL COMMUNICATION
FO
(MICOM P746) AREVA
LBB INBUILT FEATURE
ADOPTED CT METHODS IN ANDHRA PRADESHADOPTED CT METHODS IN ANDHRA PRADESH
CT METHODSCT METHODS SUBSTATIONSUBSTATION UTILITYUTILITY
3 CT METHOD3 CT METHOD WARANGALWARANGAL POWERGRIDPOWERGRID
4 CT METHOD4 CT METHOD MALKARAMMALKARAM APTRANSCOAPTRANSCO4 CT METHOD4 CT METHOD MALKARAMMALKARAM APTRANSCOAPTRANSCO
6 CT METHOD 6 CT METHOD NOT AVAILABLE IN INDIANOT AVAILABLE IN INDIA
5 CT METHOD5 CT METHOD NUNNANUNNA POWERGRIDPOWERGRID
6 CT METHOD6 CT METHOD SIMHADRISIMHADRI NTPCNTPC6 CT METHOD6 CT METHOD SIMHADRISIMHADRI NTPCNTPC
8 CT METHOD8 CT METHOD NOT AVAILABLE IN INDIANOT AVAILABLE IN INDIA
BUS SECTIONBUS SECTION NELLORENELLOREAPTRANSCO/APTRANSCO/
POWERPOWERGRIDGRID
COMPARISION BETWEEN DIFFERENT CT METHODSCOMPARISION BETWEEN DIFFERENT CT METHODSCT CT
PURPOSEPURPOSE3 CT 3 CT
METHODMETHOD4 CT 4 CT
METHODMETHOD6 CT 6 CT
METHODMETHOD5 CT5 CT
METHODMETHOD6 CT6 CT
METHODMETHOD8 CT8 CT
METHODMETHOD
MAIN1 & MAIN1 & MAIN2 MAIN2
BUSBAR BUSBAR
PROTECTIONPROTECTION
1 CT1 CT 1 CT1 CT 1B CT1B CT 1 CT1 CT 1 CT1 CT 1B CT1B CT
ABOVE FOR BUSABOVE FOR BUS--1 & BELOW FOR BUS1 & BELOW FOR BUS--22
3 CT3 CT 3 CT3 CT 3B CT3B CT 3 CT3 CT 3 CT3 CT 3B CT3B CT
MAINMAIN--1 1 1 1 -- CT & 2 CT & 2 -- CT CT 1 CT & 2 B 1 CT & 2 B -- CTCT 1 A 1 A –– CT & 2 B CT & 2 B –– CTCT 1 L 1 L -- CTCT 1 L 1 L -- CTCT 1 L 1 L -- CTCT
MAINMAIN--1 1 MAINMAIN--2 2
PROTECTION PROTECTION
BCU & EMBCU & EM
1 L 1 L -- CTCT 1 L 1 L -- CTCT 1 L 1 L -- CTCT
ABOVE CT SECONDARIES ARE CONNECTED PARALLEL FOR FEEDERABOVE CT SECONDARIES ARE CONNECTED PARALLEL FOR FEEDER--1 1
BELOW CT SECONDARIES ARE CONNECTED PARALLEL FOR FEEDERBELOW CT SECONDARIES ARE CONNECTED PARALLEL FOR FEEDER--22
ABOVE FOR FEEDERABOVE FOR FEEDER--1 1
BELOW FOR FEEDERBELOW FOR FEEDER--22
3 3 -- CT & 2 CT & 2 –– CTCT 3 3 -- CT & 2 A CT & 2 A -- CTCT 3 A 3 A -- CT & 2 A CT & 2 A -- CTCT 3 L 3 L -- CTCT 3 L 3 L -- CTCT 3 L 3 L –– CTCT
ADDITIONAL ADDITIONAL
PROTECTIONPROTECTION
AVAILABLEAVAILABLE
STUBSTUB--1 & STUB1 & STUB--2 PROTECTION 2 PROTECTION FOR LINE & AT/F FOR LINE & AT/F
TEEDTEED--1 & TEED1 & TEED--2 PROTECTION 2 PROTECTION FOR LINE & AT/F FOR LINE & AT/F
STUBSTUB--1 & STUB1 & STUB--2 PROTECTION IS INBUILT PROTECTION 2 PROTECTION IS INBUILT PROTECTION
FOR MAINFOR MAIN--1 & MAIN1 & MAIN--2 RELAYS. STUB PROTECTION 2 RELAYS. STUB PROTECTION
WORKS WHEN LINE ISOLATOR OPEN CONDITION ONLY.WORKS WHEN LINE ISOLATOR OPEN CONDITION ONLY.
TEEDTEED––1 IS HIGH IMPEDENCE DIFFERENTIAL RELAY & 1 IS HIGH IMPEDENCE DIFFERENTIAL RELAY &
TEEDTEED--2 IS LOW IMPEDENCE DIFFERENTIAL RELAY. 2 IS LOW IMPEDENCE DIFFERENTIAL RELAY.
BLIND BLIND ZONEZONE
A FAULT BETWEEN CIRCUIT BREAKERS AND CT (END FAULT) MAY THEN STILL BE FED FROM ONE SIDE EVEN WHEN THE BREAKER A FAULT BETWEEN CIRCUIT BREAKERS AND CT (END FAULT) MAY THEN STILL BE FED FROM ONE SIDE EVEN WHEN THE BREAKER HAS BEEN OPENED. CONSEQUENTLY, FINAL FAULT CLEARING BY CASCADED TRIPPING HAS TO BE ACCEPTED IN THIS CASE. THIS HAS BEEN OPENED. CONSEQUENTLY, FINAL FAULT CLEARING BY CASCADED TRIPPING HAS TO BE ACCEPTED IN THIS CASE. THIS SITUATION LBB/BFR OPERATES AND TIME TAKEN TO CLEAR FAULT IS ABOUT 300 SITUATION LBB/BFR OPERATES AND TIME TAKEN TO CLEAR FAULT IS ABOUT 300 mSECsmSECs. THIS IS BLIND ZONE AREA.. THIS IS BLIND ZONE AREA.
ADVANTAGESADVANTAGES
MINIMUM CT MINIMUM CT
METHODMETHOD
TIE CB BLIND ZONE TIE CB BLIND ZONE
AREA IS TAKEN AREA IS TAKEN
CARE. CARE.
MAIN CB & TIE CB MAIN CB & TIE CB
BLIND ZONE AREA IS BLIND ZONE AREA IS
TAKEN CARETAKEN CARE
BLIND ZONE FOR BLIND ZONE FOR
MAIN CB & TIE CBMAIN CB & TIE CB
TIE CB BLIND ZONE TIE CB BLIND ZONE
AREA IS TAKEN AREA IS TAKEN
CARECARE
GOOD PROTECTION GOOD PROTECTION
SYSTEMSYSTEM
WHEN THE FAULT IS TAKEN PLACE BETWEEN THE WHEN THE FAULT IS TAKEN PLACE BETWEEN THE MAIN CB, TIE CB & LINE ISOLATOR, DURING SERVICE MAIN CB, TIE CB & LINE ISOLATOR, DURING SERVICE ONLY, DISTANCE SCHEME SHOULD TAKE CAREONLY, DISTANCE SCHEME SHOULD TAKE CARE..
WHEN THE FAULT IS TAKEN PLACE BETWEEN THE WHEN THE FAULT IS TAKEN PLACE BETWEEN THE MAIN CB, TIE CB & LINE ISOLATOR, TEED PROTECTION MAIN CB, TIE CB & LINE ISOLATOR, TEED PROTECTION SHOULD TAKE CARE. SHOULD TAKE CARE.
ADVANTAGES & DISADVANTAGES OF ONE & HALF BREAKER SYSTEM ADVANTAGES & DISADVANTAGES OF ONE & HALF BREAKER SYSTEM AA.. ADVANTAGESADVANTAGES::1. THREE CIRCUIT BREAKERS IN A FULL DIA ARE ALWAYS IN CLOSED POSITION.
2. IF MAIN CB PROBLEM / FOR PERIODICAL MAINTANENCE, DURING THAT PERIOD THE FEEDER IS
FEEDING FROM TIE CB & OTHER BUS . NEED NOT REQUIRE TRANSFER THE FEEDER.
3. IF TIE CB PROBLEM / FOR PERIODICAL MAINTANENCE, DURING THAT PERIOD THE FEEDER IS
FEEDING FROM MAIN CB & CONNECTED BUS.
4. EVEN IF BOTH MAIN BREAKERS UNDER TROUBLE, DURING THAT PERIOD ONE FEEDER WORKS AS
INCOMING AND OTHER FEEDER WORKS AS OUTGOING VIA TIE CB. (WITHOUT INTERUPTION TOINCOMING AND OTHER FEEDER WORKS AS OUTGOING VIA TIE CB. (WITHOUT INTERUPTION TO
FEEDERS)
5. IF BUSBAR-1 OPERATED / FOR PERIODICAL MAINTANENCE, ONLY THE MAIN BREAKERS
CONNECTED TO BUSBAR-1 WILL TRIP. DURING THAT PERIOD THE FEEDERS CONNECTED TO BUS-1
ARE FEEDING VIA TIE CB FROM BUS-2.
6. IF BUSBAR-2 OPERATED / FOR PERIODICAL MAINTANENCE, ONLY THE MAIN BREAKERS
CONNECTED TO BUSBAR-2 WILL TRIP. DURING THAT PERIOD THE FEEDERS CONNECTED TO BUS-2
ARE FEEDING VIA TIE CB FROM BUS-1.
7. IN THIS BUSBAR PROTECTION IS SIMPLE AND NEED NOT REQUIRE SELECTION OF ISOLATOR.
8. IT IS MORE RELIABLE SYSTEM FOR OPERATION & MAINTANENCE POINT OF VIEW.8. IT IS MORE RELIABLE SYSTEM FOR OPERATION & MAINTANENCE POINT OF VIEW.
BB.. DISADVANTAGESDISADVANTAGES1. CT CONNECTIONS & PROTECTION TRIP LOGICS ARE SOME WHAT COMPLICATED. COMPLEX
CONTROL & PROTECTION PHILOSOPHY
2. COST TOWARDS CTs, CIRCUIT BREAKERS & PANELS ARE TO BE INCREASED DUE TO EXTRA BAY.
THE COST COMPARISION TABLE SHOWN IN NEXT PRESENTATION.
3. THE OPERATIONS FOR OPERATOR POINT OF VIEW IS LITTLE BIT COMPLICATED WHEN COMPARED
TO CONVENTIONAL SYSTEM.
4. SPACE OCUPATION FOR BAY IS MORE i.e COST OF LAND IS INCREASE.
COST COMPARISION BETWEEN CONVENTIONAL SYSTEM COST COMPARISION BETWEEN CONVENTIONAL SYSTEM & ONE AND HALF BREAKER SYSTEM FOR FEEDER & ONE AND HALF BREAKER SYSTEM FOR FEEDER
S.NoS.No EQUIPMENTEQUIPMENTCONVENTIONAL CONVENTIONAL
SYSTEMSYSTEM
ONE & HALF BREAKER SYSTEMONE & HALF BREAKER SYSTEM
FULL DIAFULL DIA
(FOR 2 FEEDERS)(FOR 2 FEEDERS)
% INCREASE% INCREASE
IN COSTIN COST
HALF DIAHALF DIA
(FOR 1 FEEDER)(FOR 1 FEEDER)
% INCREASE % INCREASE
IN COSTIN COST
1.1.CIRCUIT CIRCUIT
BREAKERSBREAKERS1 No 3 Nos 50% 2 Nos 100%
BREAKERSBREAKERS
2.2.
CURRENT CURRENT
TRANSFORMERSTRANSFORMERS
1 Set
INCLUDES THE COST OF CT MARSHELLING BOXES.
3 CT METHOD3 CT METHOD 3 Sets 50% 2 Sets 100%
4 CT METHOD4 CT METHOD 4 Sets 100% 2 Sets 100%
5 CT METHOD5 CT METHOD 5 Sets 125% 3 Sets 200%
6 CT METHOD6 CT METHOD 6 Sets 200% 3 Sets 200%
8 CT METHOD8 CT METHOD 8 Sets 300% 4 Sets 300%8 CT METHOD8 CT METHOD 8 Sets 300% 4 Sets 300%
3.3.CONTROL & CONTROL &
RELAY PANELSRELAY PANELS
I SET 3 SETS 30% 2 SETS 30%
NORMALLYNORMALLY EXTRAEXTRA PANELPANEL ISIS TIETIE BAYBAY PANELPANEL.. ITIT ISIS ARROUNDARROUND 3030%% COSTCOST OFOF MAINMAINPANELPANEL.. BECAUSEBECAUSE ITIT ISIS NOTNOT HAVINGHAVING PROTECTIONPROTECTION RELAYSRELAYS (( MM--11 && MM--22 ANDAND OTHEROTHERRELAYS)RELAYS) .. ONLYONLY TIETIE CBCB TRIPPINGTRIPPING RELAYSRELAYS && ASSOCIATEDASSOCIATED RELAYS(A/RRELAYS(A/R +LBB)+LBB)..
4. 4.
BAY BAY
MARSHALLING MARSHALLING
BOXES (BMB)BOXES (BMB)
1 No 3 Nos 50% 2 Nos 30%
5.5. CONTROL CABLESCONTROL CABLES 8 KM 30 KM 100% 20 KM 150%
MAINMAIN--1, MAIN1, MAIN--22PROTECTION &PROTECTION &
METERINGMETERINGMETERINGMETERINGFOR LINE FOR LINE
ADOPTED IN ADOPTED IN ONE AND HALFONE AND HALFONE AND HALFONE AND HALF
CIRCUIT BREAKER CIRCUIT BREAKER SCHEMESCHEME PREPARED BY
GOPALA KRISHNA PALEPUADE/MRT(PROTECTION)
NORMS OF PROTECTION FOLLOWED IN APTRANSCO NORMS OF PROTECTION FOLLOWED IN APTRANSCO FOR TRANSMISIION LINES & DISTRIBUTION LINES ( FEEDER / LINE PROTECTION )FOR TRANSMISIION LINES & DISTRIBUTION LINES ( FEEDER / LINE PROTECTION )
Sr.NoSr.No VOLTAGE VOLTAGE MAINMAIN-- 1 PROTECTION1 PROTECTION MAINMAIN--2 PROTECTION/ BACKUP PROTECTION2 PROTECTION/ BACKUP PROTECTION
1.1. 11 KV LINES11 KV LINES 2 O/L + E/F ( 51 + 51N )2 O/L + E/F ( 51 + 51N ) --
2.2. 33 KV LINES33 KV LINES 3 O/L + E/F ( 51 + 51N )3 O/L + E/F ( 51 + 51N ) --
3.3. 66 KV LINES66 KV LINES SWITCHED DISTANCE SCHEME SWITCHED DISTANCE SCHEME OROR
NUMERICAL DISTANCE SCHEME (21P+ 21N)NUMERICAL DISTANCE SCHEME (21P+ 21N)DIRECTIONAL O/L & E/F RELAYS WITH HIGH DIRECTIONAL O/L & E/F RELAYS WITH HIGH
SET ( 67 + 67N )SET ( 67 + 67N )4.4. 132 KV LINES132 KV LINES NUMERICAL DISTANCE SCHEME (21P+ 21N)NUMERICAL DISTANCE SCHEME (21P+ 21N) SET ( 67 + 67N )SET ( 67 + 67N )4.4. 132 KV LINES132 KV LINES
5.5. 220 KV LINES220 KV LINESNON SWITCHED DISTANCE SCHEME NON SWITCHED DISTANCE SCHEME OROR
NUMERICAL DISTANCE SCHEME (21P + 21N)NUMERICAL DISTANCE SCHEME (21P + 21N)
SWITCHED DISTANCE SCHEME SWITCHED DISTANCE SCHEME OROR
NUMERICAL DISTANCE SCHEME (21P+ 21N)NUMERICAL DISTANCE SCHEME (21P+ 21N)
6.6. 400 KV LINES400 KV LINESNUMERICAL DISTANCE SCHEME (21P + 21N) NUMERICAL DISTANCE SCHEME (21P + 21N)
+ in BUILT DEF RELAY(67N)+ in BUILT DEF RELAY(67N)NUMERICAL DISTANCE SCHEME (21) NUMERICAL DISTANCE SCHEME (21) OROR LINE LINE DIFFERENTIAL SCHEME (87L) WITH B/U 21DIFFERENTIAL SCHEME (87L) WITH B/U 21
7.7. 765 KV LINES765 KV LINESNUMERICAL DISTANCE SCHEME (21P + 21N) NUMERICAL DISTANCE SCHEME (21P + 21N)
+ in BUILT DEF RELAY(67N)+ in BUILT DEF RELAY(67N)NUMERICAL DISTANCE SCHEME (21) NUMERICAL DISTANCE SCHEME (21) OROR LINE LINE DIFFERENTIAL SCHEME (87L) WITH B/U 21DIFFERENTIAL SCHEME (87L) WITH B/U 21
IFIF MAINMAIN--11 && MAINMAIN--22 AREARE NUMERICALNUMERICAL RELAYS,RELAYS, BOTHBOTH SHOULDSHOULD BEBE SEPARATESEPARATE MEASURINGMEASURING PRINCIPLESPRINCIPLES (CHARECTERESTICS),(CHARECTERESTICS), MODELSMODELSIFIF MAINMAIN--11 && MAINMAIN--22 AREARE NUMERICALNUMERICAL RELAYS,RELAYS, BOTHBOTH SHOULDSHOULD BEBE SEPARATESEPARATE MEASURINGMEASURING PRINCIPLESPRINCIPLES (CHARECTERESTICS),(CHARECTERESTICS), MODELSMODELSANDAND ALGORITHAMSALGORITHAMS (SHOULD(SHOULD NOTNOT BEBE DUPLICATED)DUPLICATED) ANDAND ALLALL FEATURESFEATURES SHOULDSHOULD BEBE AVAILABLEAVAILABLE ININ BOTHBOTH SCHEMESSCHEMES ANDAND BOTHBOTH RELAYSRELAYSSHOULDSHOULD BEBE 100100%% REDENDENCYREDENDENCY ININ ALLALL ASPECTSASPECTS (( COMPLEMENTARYCOMPLEMENTARY TOTO EACHEACH OTHEROTHER )) .. DISSIMILARDISSIMILAR CARRIERCARRIER SCHEMESSCHEMES AREARE TOTO BEBESELECTEDSELECTED (( POTTPOTT && PUTTPUTT oror BLOCKBLOCK && UNBLOCK)UNBLOCK).. OTHEROTHER WISEWISE MAINMAIN--22 MAYMAY BEBE DIFFERENTDIFFERENT MAKEMAKE OROR PHASEPHASE COMPARISIONCOMPARISIONPROTECTION/LINEPROTECTION/LINE DIFFERENTIALDIFFERENTIAL PROTECTIONPROTECTION WITHWITH BACKUPBACKUP DISTANCEDISTANCE PROTECTIONPROTECTION ISIS TOTO BEBE ADOPTEDADOPTED.. BOTHBOTH MM11 && MM22 SHOULDSHOULDCONTAINCONTAIN DIRECTIONALDIRECTIONAL EARTHEARTH FAULTFAULT PROTECTIONPROTECTION ((6767N)N) WITHWITH DIRECTIONALDIRECTIONAL COMPARISIONCOMPARISION PICKUPPICKUP SCHEMESCHEME ASAS INBUILTINBUILT FUNCTIONFUNCTION........
ZONEZONE--1: 80% OF MAIN LINE1: 80% OF MAIN LINEZONEZONE--2: 100% OF MAIN LINE + 50% OF SHORTEST LINE AT OTHER END2: 100% OF MAIN LINE + 50% OF SHORTEST LINE AT OTHER ENDZONEZONE--3: 100% OF MAIN LINE + 100% OF SHORTEST LINE AT OTHER END3: 100% OF MAIN LINE + 100% OF SHORTEST LINE AT OTHER ENDZONEZONE--4: 100% OF MAIN LINE + (100% OF SHORTEST LINE + 20% OF LONGEST LINE)4: 100% OF MAIN LINE + (100% OF SHORTEST LINE + 20% OF LONGEST LINE) AT OTHER END.AT OTHER END.
MAINMAIN--1 PROTECTION FOR LINE (21L1)1 PROTECTION FOR LINE (21L1)(3/4/6 CT METHOD)(3/4/6 CT METHOD)
3 3 3
IR5 / A511
IY5 / A531
IB5 / A551
IN5 / A571
1-CT
CORE-5
CTR: 2000-1000-500/1A
CLASS: PS
5S4 5S4 5S4
5S25S2 5S2
P2P2P2 CT MB
VR11 / E111
VY11 / E131
VB11 / E151
VN11 / E171
1-CVT
CORE – 1
2-BCT
CT MB
CORE – 1
100VA
CLASS: 3P
3 C
T M
ET
HO
D :
1-C
T
& 2
-CT
4 C
T M
ET
HO
D :
1-C
T
& 2
-BC
T
6 C
T M
ET
HO
D :
1-A
CT
& 2
-BC
T
3 3 3
2-BCT
CORE-5
CTR: 2000-1000-500/1A
CLASS: PS
P2P2P2
5S4 5S4 5S4
5S25S2 5S2
MAINMAIN--1 PROTECTION FOR LINE (21L1)1 PROTECTION FOR LINE (21L1)(3/4/6 CT METHOD) (NEW DEVELOPMENT)(3/4/6 CT METHOD) (NEW DEVELOPMENT)
3 3 3
IR5 / A511
IY5 / A531
IB5 / A551
IN5 / A571
1-CT
CORE-5
CTR: 2000-1000-500/1A
CLASS: PS
5S4 5S4 5S4
5S25S2 5S2
P2P2P2 CT MB
VR11 / E111
VY11 / E131
VB11 / E151
VN11 / E171
1-CVT
CORE – 1
100VA
CLASS: 3P
IA =250.10 A
IB =250.10 A
IC =250.10 A
VAB =400.0 KV
VBC =400.0 KVCLASS: PS
CT MB
VBC =400.0 KV
VCA =400.0 KV
ESC ENT
ENABLED
TRIPTARGET RESET
3 C
T M
ET
HO
D :
1-C
T
& 2
-CT
4 C
T M
ET
HO
D :
1-C
T
& 2
-BC
T
6 C
T M
ET
HO
D :
1-A
CT
& 2
-BC
T
3 3 3
2-BCT
CORE-5
CTR: 2000-1000-500/1A
CLASS: PS
P2P2P2
5S4 5S4 5S4
5S25S2 5S2
INSTTIMECOMMSOTF
ZONE1ZONE2ZONE3ZONE4
PH-APH-BPH-CGND
5051
79 RESET
79 LOCKOUT
SEL- 421PROTECTION
AUTOMATION
CONTROL
SELIR5 / A511
IY5 / A531
IB5 / A551
IN5 / A571
MAINMAIN--1 PROTECTION FOR LINE (21L1)1 PROTECTION FOR LINE (21L1)(5/6/8 CT METHOD)(5/6/8 CT METHOD)
IR5 / A511
IY5 / A531
IB5 / A5511-LCT
P2P2P2 CT MB
VR11 / E111
VY11 / E131
VB11 / E151
3 3 3
IB5 / A551
IN5 / A571
CORE-5
CTR: 2000-1000-500/1A
CLASS: PS
5S4 5S4 5S4
5S25S2 5S2
VB11 / E151
VN11 / E171
1-CVT
CORE – 1
100VA
CLASS: 3P
MAINMAIN--2 PROTECTION FOR LINE 2 PROTECTION FOR LINE (21L2) (21L2) (3/4/6 CT METHOD)(3/4/6 CT METHOD)
3 3 3
IR4 / C411
IY4 / C431
IB4 / C451
IN4 / C471
1-CT
CORE-4
CTR: 2000-1000-500/1A
CLASS: PS
4S4 4S4 4S4
4S24S2 4S2
P2P2P2 CT MB
VR21 / E211
VY21 / E231
VB21 / E251
VN21 / E271
1-CVT
21 L2
CLASS: PS
CT MB
1-CVT
CORE – 2
100VA
CLASS: 3P
3 C
T M
ET
HO
D :
1-C
T
& 2
-CT
4 C
T M
ET
HO
D :
1-C
T
& 2
-BC
T
6 C
T M
ET
HO
D :
1-A
CT
& 2
-BC
T
3 3 3
2-BCT
CORE-4
CTR: 2000-1000-500/1A
CLASS: PS
P2P2P2
4S4 4S4 4S4
4S24S2 4S2
50ZT
LBB/BFR
MAINMAIN--2 PROTECTION FOR LINE (21L2)2 PROTECTION FOR LINE (21L2)(3/4/6 CT METHOD) ( NEW DEVELOPMENT)(3/4/6 CT METHOD) ( NEW DEVELOPMENT)
3 3 3
IR4 / C411
IY4 / C431
IB4 / C451
IN4 / C471
1-CT
CORE-4
CTR: 2000-1000-500/1A
CLASS: PS
4S4 4S4 4S4
4S24S2 4S2
P2P2P2 CT MB
VR21 / E211
VY21 / E231
VB21 / E251
VN21 / E271
1-CVT
CORE – 2
100VA
CLASS: 3P
CLASS: PS
CT MB
3 C
T M
ET
HO
D :
1-C
T
& 2
-CT
4 C
T M
ET
HO
D :
1-C
T
& 2
-BC
T
6 C
T M
ET
HO
D :
1-A
CT
& 2
-BC
T
3 3 3
2-BCT
CORE-4
CTR: 2000-1000-500/1A
CLASS: PS
P2P2P2
4S4 4S4 4S4
4S24S2 4S2
IR4 / C411
IY4 / C431
IB4 / C451
IN4 / C471
MULTI FUNCTION NUMERICAL RELAY FOR MULTI FUNCTION NUMERICAL RELAY FOR MULTI BREAKER, MULTI CT & CVT/PT APPLICATION MULTI BREAKER, MULTI CT & CVT/PT APPLICATION
(NEW APPLICATION) (ONE & HALF BREAKER SYSTEM or RING BUS SYSTEM)(NEW APPLICATION) (ONE & HALF BREAKER SYSTEM or RING BUS SYSTEM)
1-52 CB 2-52 CB 3-52 CB33 33 33 33
33 33 33 33
BUS-1 PT
1-52,2-52: MAIN & TIE CIRCUIT BREAKER21P: PHASE DISTANCE PROTECTION21N: GROUND DISTANCE PROTECTION
27: UNDER VOLTAGE RELAY
67P
50 BF-1 50 BF-2
21N
79-1
21P 50P 51P27
59
33 33
33 3333 33
33 33
BUS-1 PT BUS-2 PT
25-179-2 25-2
67N50N 51N
LINE
27: UNDER VOLTAGE RELAY67: DIRECTIONAL RELAY50: INST OVER CURRENT RELAY51: TIME OVER CURRENT RELAY59: OVER VOLTAGE RELAY
64: EARTH FAULT RELAY50BF-1: LBB/BFR OF MAIN CB50BF-2: LBB/BFR OF TIE CB79-1,2: AUTO RECLOSURE RELAY OF
MAIN & TIE CB
25-1,2: CHECK SYNCHRONISAM RELAYFOR MAIN & TIE CB
21N
3333
3333
LINE CVT
67N50N 51N
MAINMAIN--2 PROTECTION FOR LINE (21L2)2 PROTECTION FOR LINE (21L2)(5/6/8 CT METHOD)(5/6/8 CT METHOD)
IR4 / C411
IY4 / C431
IB4 / C4511-LCT
P2P2P2 CT MB
VR21 / E211
VY21 / E231
VB21 / E251
3 3 3
IB4 / C451
IN4 / C471
CORE-4
CTR: 2000-1000-500/1A
CLASS: PS
4S4 4S4 4S4
4S24S2 4S2
VB21 / E251
VN21 / E271
1-CVT
CORE – 2
100VA
CLASS: 3P
BAY CONTROL UNIT (BCU) & ENERGY METERBAY CONTROL UNIT (BCU) & ENERGY METER(3/4/6 CT METHOD)(3/4/6 CT METHOD)
3 3 3
IR3 / D311
IY3 / D331
IB3 / D351
IN3 / D371
1-CT
CORE-3
CTR: 2000-1000-500/1A
3S4 3S4 3S4
3S23S2 3S2
P2P2P2 CT MB
3 3 3
IN3 / D371CTR: 2000-1000-500/1A
CLASS: 0.2
3S23S2 3S2
CT MBVR31 / E311
VY31 / E3313 C
T M
ET
HO
D :
1-C
T
& 2
-CT
4 C
T M
ET
HO
D :
1-C
T
& 2
-BC
T
6 C
T M
ET
HO
D :
1-A
CT
& 2
-BC
T
3 3 3
2-BCT
CORE-3
CTR: 2000-1000-500/1A
CLASS: 0.2
3S4 3S4 3S4
3S23S2 3S2
VY31 / E331
VB31 / E351
VN31 / E371
1-CVT
CORE – 3
50VA
CLASS: 0.2P2P2P2
3 C
T M
ET
HO
D :
14 C
T M
ET
HO
D :
1
6 C
T M
ET
HO
D :
1
3 3 3
IR3 / D311
IY3 / D331
IB3 / D3511-LCT
CORE-3
CTR: 2000-1000-500/1A
3S4 3S4 3S4
3S23S2 3S2
P2P2P2 CT MB
BAY CONTROL UNIT (BCU) & ENERGY METERBAY CONTROL UNIT (BCU) & ENERGY METER(5/6/8 CT METHOD)(5/6/8 CT METHOD)
3 3 3
IN3 / D371
CTR: 2000-1000-500/1A
CLASS: 0.2
3S23S2 3S2
VR31 / E311
VY31 / E331VY31 / E331
VB31 / E351
VN31 / E371
1-CVT
CORE – 3
50VA
CLASS: 0.2
MAINMAIN--1 & MAIN1 & MAIN--22PROTECTION FORPROTECTION FOR
AUTO TRANSFORMER AUTO TRANSFORMER ADOPTED IN ADOPTED IN
ONE AND HALFONE AND HALFCIRCUIT BREAKER CIRCUIT BREAKER
SCHEMESCHEMEPREPARED BY
GOPALA KRISHNA PALEPUADE/MRT(PROTECTION)
BASICS OF TRANSFORMER PROTECTIONBASICS OF TRANSFORMER PROTECTION1. 1. PURPOSE OF POWER TRANSFORMER PROTECTIONPURPOSE OF POWER TRANSFORMER PROTECTION
POWER T/F PROTECTION IS USUALLY INSTALLED TO DISCONNECT THE T/F AT:
A.A. INTERNAL SHORT CIRCUITS AND EARTH FAULTS IN THE T/F AND ITS CONNECTED CIRCUITS.
B.B. EXTERNAL FAULTS ON OTHER CIRCUITS. (BACK-UP PROTECTION)
C.C. ABNORMAL SERVICE CONDITIONS SUCH AS OVERLOAD & OVER VOLTAGE.
2.2. PROTECTION DEVICES INBUILT OR MOUNTED ON POWER T/FPROTECTION DEVICES INBUILT OR MOUNTED ON POWER T/F
A.A. OIL IMMERSED POWER T/F USUALLY HAVE A GAS DETECTOR AND OIL SURGE. DETECTOR A.A. OIL IMMERSED POWER T/F USUALLY HAVE A GAS DETECTOR AND OIL SURGE. DETECTOR
(BUCHHOLZ ALARAM & TRIP DEVICES), WHICH ARE EXCELLENT FOR DETECTING INTERNAL
FAULTS.
B.B. LOAD TAPCHANGER COMPARTMENTS MAY HAVE A SIMILAR OVER PRESSURE DEVICE.
C.C. TEMPARATURE MONITORS FOR OIL & WINDING PROVIDE GOOD OVER LOAD PROTECTION.
D.D. PRESSURE RELIEF DEVICE IS PROVIDED TO SAFE GUARD THE T/F FROM HIGH PRESURES.
3.3. TRANSFORMER DIFFERENTIAL PROTECTIONTRANSFORMER DIFFERENTIAL PROTECTION
IT IS WIDELY USED AS INSTANTANEOUS PROTECTION FOR SHORT CIRCUIT FAULTS WITH IN
THE DIFFERENTIAL ZONE. THIS IS TREATED AS MAIN-1 PROT FOR T/F.
THE MOST COMMON TYPE OF PROTECTION IS THE CURRENT RESTRAINT TYPE.THE MOST COMMON TYPE OF PROTECTION IS THE CURRENT RESTRAINT TYPE.
SOME TYPE OF DIFFERENTIAL RELAYS REQUIRE INTERPOSING CTs FOR CT RATIO MATCHING
AND/OR PHASE SHIFT.
HIGH IMPEDENCE DIFFERENTIAL PROTECTION CAN BE USED ON AUTO T/F & REACTORS.
IT COVERS ONE GALVANICALLY INTERCONNECTED WINDING (WDG DIFF). BUT NOT A
SEPARATE TERTIARY WINDING.
IT REQUIRES A THREE PHASE SET OF CTs AT THE NEUTRAL SIDE OF WINDING.
87T1: MAIN1 TRANSFORMER DIFFERENTIAL PROTECTION USING CONVENTIONAL CTs
87T2: MAIN2 TRANSFORMER DIFFERENTIAL PROTECTION USING BUSHING CTs
4.4.RESTRICTED EARTH FAULT PROTECTIONRESTRICTED EARTH FAULT PROTECTIONAT/Fs are used to couple EHV Power Networks, If the Ratio of their Voltages is Moderate. An Alternative to
Differential Protection that can be applied to AT/Fs. A Circulating Current System is arranged betweenEqual Ratio Current Transformers in the Two Groups of Line Connections and the Neutral EndConnections. The Line Current Transformers can be connected in Parallel to A Single Element Relay, Thusproviding a Scheme Responsive to Earth Faults Only. If Current Transformers are fitted in Each Phase atthe Neutral End of the Windings and a Three-Element Relay is used, A Differential System can be provided,
giving Full Protection against Phase and Earth Faults. This Provides High-speed Sensitive Protection. It isUnaffected by Ratio Changes on the Transformer due to Tap-changing and is immune to the Effects ofMagnetizing In Rush Current. It does not respond to Interturn Faults. In Addition, This Scheme does notrespond to any Fault in a Tertiary Winding. Unloaded Delta-connected Tertiary Windings are often notProtected.Protected.
55. BACK UP PROTECTIONBACK UP PROTECTIONA VARIETY OF RELAYS ARE AVAILABLE.A.A. OVER CURRENT & EARTH FAULT PROTECTION. ( 50, 50N, 51, 51N, 67, 67N - ANY COMBINATION OF THESE)B.B. UNDER IMPEDENCE / DISTANCE ( Z<)(21T).
C.C. NEUTRAL DISPLACEMENT PROTECTION (Un>).
6.6.OTHER TYPES OF RELAYSOTHER TYPES OF RELAYSA.A. OVER VOLTAGE RELAY (U >).B.B. OVER FLUX/ EXCITATION (V/F >)( INVERSE TIME & DIFENITE TIME). FOR 400KV/220KV & 765/400KV TRANSFORMERS BOTH SIDES( i.e HV & LV) OVER FLUX RELAYS ARE
PROVIDED BECAUSE BOTH SIDES HAVING GRID.C.C. AT/F NEUTRAL CURRENT RELAY (51N).C.C. AT/F NEUTRAL CURRENT RELAY (51N).
NORMALLY ADOPTED POWER TRANSFORMERS CAPACITIES IN 400KV / 220KVNORMALLY ADOPTED POWER TRANSFORMERS CAPACITIES IN 400KV / 220KV
CAPACITY OF CAPACITY OF TRANSFORMERTRANSFORMER
HV HV VOLTAGEVOLTAGE
HV CURRENTHV CURRENT LV VOLTAGELV VOLTAGELV LV
CURRENTCURRENT
315 MVA315 MVA 400 KV400 KV 454.68 A454.68 A 220 KV220 KV 0826.68 A0826.68 A
500 MVA500 MVA 400 KV400 KV 721.71 A721.71 A 220 KV220 KV 1312.20 A1312.20 A
630 MVA630 MVA 400 KV400 KV 909.35 A909.35 A 220 KV220 KV 1653.37 A1653.37 A
NORMS OF PROTECTION FOLLOWED BY UTILITIES NORMS OF PROTECTION FOLLOWED BY UTILITIES FOR POWER TRANSFORMERS & AUTO TRANSFORMERSFOR POWER TRANSFORMERS & AUTO TRANSFORMERS
S.NoS.NoCAPACITYCAPACITY
IN IN
MVAMVA
VOLTAGE VOLTAGE RATIO IN RATIO IN
KVKV
T
YPE
MAINMAIN--11 MAINMAIN--22BACK UPBACK UP
PROTECTIONPROTECTION ADDITIONAL ADDITIONAL
PROTECTIONPROTECTION
SPECIALSPECIAL
PROTECTIONPROTECTIONPROTECTIONPROTECTION HVHVHVHVHVHVHVHV LVLVLVLVLVLVLVLV
11 7.5 & 167.5 & 16 66 / 1166 / 11
2 WIN
DING TRA
NSFORM
ER
87
T1
DIF
FE
RE
NT
IAL
RE
LA
Y
( LO
W IM
PE
DA
NC
E P
ER
CE
NTA
GE
BIA
SE
D P
HA
SE
SE
GR
EG
AT
ED
D
IFF
ER
EN
TIA
L R
EL
AY
PR
INC
IPL
E: M
ER
Z P
RIC
E)
NIL 3 OL +3 OL +
1 EL (51)1 EL (51)
3 OVER LOAD + 1 EA
RTH FAULT
3 OVER LOAD + 1 EA
RTH FAULT
BUCHHOLZ, BUCHHOLZ,
OLTC OSROLTC OSR
64
RE
F IS
1
87
T2 IS
3
(PR
INC
PL
E : C
IRC
UL
AT
ING
CU
RR
EN
T)
227.5 , 16 7.5 , 16 & 25& 25 66 / 3366 / 33
2 WIN
DING TRA
NSFORM
ER (STA
R/STAR)
87
T1
DIF
FE
RE
NT
IAL
RE
LA
Y
( LO
W IM
PE
DA
NC
E P
ER
CE
NTA
GE
BIA
SE
D P
HA
SE
SE
GR
EG
AT
ED
D
IFF
ER
EN
TIA
L R
EL
AY
PR
INC
IPL
E: M
ER
Z P
RIC
E)
1 EL (51)1 EL (51)
3 OVER LOAD + 1 EA
RTH FAULT
3 OVER LOAD + 1 EA
RTH FAULT
RELAY ( 51 )
RELAY ( 51 )
OLTC OSROLTC OSR
OIL TEMPOIL TEMP
WDNG TEMPWDNG TEMP
64
RE
F IS
1-P
H H
IGH
IMP
ED
AN
CE
D
IFF
ER
EN
TIA
L R
EL
AY
87
T2 IS
3-P
H H
IGH
IMP
ED
AN
CE
D
IFF
ER
EN
TIA
L R
EL
AY
(PR
INC
PL
E : C
IRC
UL
AT
ING
CU
RR
EN
T)
22 & 25& 25 66 / 3366 / 33
337.5 , 16 ,7.5 , 16 ,25 & 31.525 & 31.5 132 / 11132 / 11
HV REF (64)
3 OVER LOAD + 1 DIRECTION
AL
3 OVER LOAD + 1 DIRECTION
AL
EARTH FA
ULT RELAY ( 51P + 67N
)EA
RTH FAULT RELA
Y ( 51P + 67N
)
4416 , 31.5 16 , 31.5 50 & 8050 & 80 132 / 33 132 / 33
BUCHHOLZBUCHHOLZ
OVER FLUX OVER FLUX
55 31.5, 5031.5, 50 220 / 33220 / 33
6631.5, 50 & 31.5, 50 &
100100 220 / 66220 / 66HV & LV
(STAR/STA
R)
87
T1
DIF
FE
RE
NT
IAL
RE
LA
Y
( LO
W IM
PE
DA
NC
E P
ER
CE
NTA
GE
BIA
SE
D P
HA
SE
SE
GR
EG
AT
ED
D
IFF
ER
EN
TIA
L R
EL
AY
PR
INC
IPL
E: M
ER
Z P
RIC
E)
3 OVER LOAD + 1 EA
RTH FAULT
3 OVER LOAD + 1 EA
RTH FAULT
PH
HIG
H IM
PE
DA
NC
E
PH
HIG
H IM
PE
DA
NC
E
(PR
INC
PL
E : C
IRC
UL
AT
ING
CU
RR
EN
T)
3 OVER LOAD + 1 DIRECTION
AL
3 OVER LOAD + 1 DIRECTION
AL
EARTH FA
ULT RELAY ( 51P + 67N
)EA
RTH FAULT RELA
Y ( 51P + 67N
)
OVER FLUX OVER FLUX
OLTC OSROLTC OSR
PRV/PRDPRV/PRD
OIL TEMPOIL TEMP
WDNG TEMPWDNG TEMP
100100 HV & LV REF 64
77100, 200 100, 200 & 250& 250 400 / 132400 / 132
3 OL + 3 OL + 1 DIR EL 1 DIR EL (51P + (51P + 67N)67N)8 8 100 & 160100 & 160 220 / 132220 / 132
ICT / AUTO TFR
87 T2 / 64 REF
OVER LOAD OVER LOAD
ALARM ALARM
RELAY + RELAY +
NEUTRAL NEUTRAL
CURRENT E/F CURRENT E/F
RELAYRELAY
99 315, 500 315, 500 & 630 & 630 400 / 220400 / 220
3 DIR OL 3 DIR OL (HIGHSET) (HIGHSET)
+ + 1 DIR EL1 DIR EL
(HIGHSET)(HIGHSET)
3 DIR OL 3 DIR OL (HIGHSET) (HIGHSET)
+ + 1 DIR EL1 DIR EL
(HIGHSET)(HIGHSET)1010 1000 & 1000 &
15001500 765 / 400765 / 400
ICT BUSHING CT INFORMATIONICT BUSHING CT INFORMATIONS.No ITEM /MVA HV IV NEUTRAL LV
1 CORE 1 2 3 1 2 3 1 2 3
2 RATIO
100 600/1 300/1
- -
600/1 500/1
- -
600/1 600/1
- -160 800/1 500/1 800/1 800/1 800/1 800/1
315 1000/1 600/1 1000/1 1000/1 1000/1 1000/1
500 1600/1 1000/1 1600/1 1600/1 1600/1 1600/1500 1600/1 1000/1 1600/1 1600/1 1600/1 1600/1
NEUTRAL BUSHING CT : CORE-1 & 2 : BEFORE STAR FORMATION IN RYB PHASES,
3
VKNEE
FOR PS &
VA FOR MET
100 600 V 600 V
Param
eters of W
TI C
T fo
r each w
indin
g sh
all
be p
rovid
ed b
y th
e contracto
r.
600 V 600 VP
arameters o
f WT
I CT
for each
win
din
g sh
all be p
rovid
ed b
y th
e contracto
r600 V 600 V
Param
eters of W
TI C
T fo
r each w
indin
g sh
all be p
rovid
ed b
y th
e contracto
r
160 800 V 800 V 800 V 800 V 800 V 800 V
315 1000 V 1000 V 1000 V 1000 V 1000 V 1000 V
500 1600V 1600V 1600 V 1600 V 1600 V 1600 V
4 RCT IN OHMS
100 1.5 1.5 1.5 1.5 1.5 1.5
160 2.0 2.0 2.0 2.0 2.0 2.0
315 2.5 2.5 2.5 2.5 2.5 2.5
Param
eters of W
TI C
T fo
r each w
indin
g sh
all
be p
rovid
ed b
y th
e contracto
r.
Param
eters of W
TI C
T fo
r each w
indin
g sh
all be p
rovid
ed b
y th
e contracto
r
Param
eters of W
TI C
T fo
r each w
indin
g sh
all be p
rovid
ed b
y th
e contracto
r
500 4.0 4.0 4.0 4.0 4.0 4.0
5I MAG IN mA at VKNEE
100 100 100 100 100 100 100
160 80 80 80 80 80 80
315 60 60 60 60 60 60
500 25 25 25 25 25 25
6 CLASS OF ACURACY
PS PS PS PS PS PS
7 PURPOSE 87T2(L) 87T2(H) WTI 87T2(L) 87T2(H) WTI 87T2(L) 87T2(H) WTI
SELECTION OF AUX.CTs FOR DIFFERENTIAL PROTECTIONSELECTION OF AUX.CTs FOR DIFFERENTIAL PROTECTION
�� NORMALLY 400KV/220KV AUTO TRANSFORMERS ARE OF CAPACITY 315MVA.NORMALLY 400KV/220KV AUTO TRANSFORMERS ARE OF CAPACITY 315MVA.�� FOR MERZ PRICE PROTECTION IF TRANSFORMER IS CONNECTED IN STAR/STARFOR MERZ PRICE PROTECTION IF TRANSFORMER IS CONNECTED IN STAR/STAR
THEN CT SECONDARIES ARE TO BE CONNECTED IN DELTA/DELTA.THEN CT SECONDARIES ARE TO BE CONNECTED IN DELTA/DELTA.�� CORRECT RATIO CTs ARE NOT AVAILABLE, THEN AUX.CTs ARE TO BE PROVIDEDCORRECT RATIO CTs ARE NOT AVAILABLE, THEN AUX.CTs ARE TO BE PROVIDED
FOR ACHEVING SUITABLE CURRENTS.FOR ACHEVING SUITABLE CURRENTS.�� IF AUX CTs ARE USING THEN MAIN CT SECONDARIES ARE CONNECTED IN STAR.IF AUX CTs ARE USING THEN MAIN CT SECONDARIES ARE CONNECTED IN STAR.�� THIS IS BROUGHT TO AUX CTs. AUX CTs PRIMARY IS CONNECTED IN STAR & THIS IS BROUGHT TO AUX CTs. AUX CTs PRIMARY IS CONNECTED IN STAR &
SECONDARIES ARE CONNECTED IN DELTA.SECONDARIES ARE CONNECTED IN DELTA.�� NORMALLY THE RELAY RATED CURRRENT IS 1A.NORMALLY THE RELAY RATED CURRRENT IS 1A.�� AUX.CT s SECONDARIES ARE CONNECTED IN DELTA. FOR ACHIEVING 1A TOAUX.CT s SECONDARIES ARE CONNECTED IN DELTA. FOR ACHIEVING 1A TO
RELAY, AUX.CT SECONDARY CURRENT IS TO BE 0.577A.RELAY, AUX.CT SECONDARY CURRENT IS TO BE 0.577A.�� THE FULL LOAD PRIMARY CURRENT OF 315MVA AT/F IS 454.7A.THE FULL LOAD PRIMARY CURRENT OF 315MVA AT/F IS 454.7A.�� BUT THE 400KV CTs RATIOs ARE AVAILABLE : 2000BUT THE 400KV CTs RATIOs ARE AVAILABLE : 2000--10001000--500/1A500/1A�� NEAREST VALUE TO FULL LOAD CURRENT IS 500/1A. HENCE IT IS ADOPTED.NEAREST VALUE TO FULL LOAD CURRENT IS 500/1A. HENCE IT IS ADOPTED.�� HENCE AT FULL LOAD HV CURRENT i.e 454.7A, THEN SECONDARY OF CT HENCE AT FULL LOAD HV CURRENT i.e 454.7A, THEN SECONDARY OF CT
CURRENT WILL BE 0.91A.CURRENT WILL BE 0.91A.�� SO HV SIDE AUX.CT RATIO IS 0.91/0.577A.SO HV SIDE AUX.CT RATIO IS 0.91/0.577A.�� SO HV SIDE AUX.CT RATIO IS 0.91/0.577A.SO HV SIDE AUX.CT RATIO IS 0.91/0.577A.�� THE FULL LOAD SECONDARY CURRENT OF 315MVA AT/F IS 826.7A.THE FULL LOAD SECONDARY CURRENT OF 315MVA AT/F IS 826.7A.�� BUT THE 220KV CTs RATIOs ARE AVAILABLE: 1200BUT THE 220KV CTs RATIOs ARE AVAILABLE: 1200--800/1A.800/1A.�� NEAREST VALUE TO FULL LOAD CURRENT IS 1200/1A. HENCE IT IS ADOPTED.NEAREST VALUE TO FULL LOAD CURRENT IS 1200/1A. HENCE IT IS ADOPTED.�� HENCE AT FULL LOAD LV CURRENT i.e 826.7A,THEN SECONDARY OF CT CURRENT HENCE AT FULL LOAD LV CURRENT i.e 826.7A,THEN SECONDARY OF CT CURRENT
WILL BE 0.689A.WILL BE 0.689A.�� SO LV SIDE AUX CT RATIO IS 0.689/0.577A.SO LV SIDE AUX CT RATIO IS 0.689/0.577A.�� SPECIAL INFORMATION:SPECIAL INFORMATION: LATEST NUMERICAL RELAYS NEED NOT REQUIRE AUX LATEST NUMERICAL RELAYS NEED NOT REQUIRE AUX
CTs. IN THESE RELAYS, CT RATIOS MATCHING CAN BE PROGRAMMED.CTs. IN THESE RELAYS, CT RATIOS MATCHING CAN BE PROGRAMMED.
MAIN MAIN --1(87T1) 1(87T1) DIFFERENTIAL PROTECTION FOR ICTDIFFERENTIAL PROTECTION FOR ICT(3/4/6 CT METHOD)(3/4/6 CT METHOD)
3 3 3
3-CT
CORE-5
CTR: 2000-1000-500/1A
CLASS: PS
5S4 5S4 5S4
5S35S3 5S3
P2P2P2 CT MB
3 3 35S1 5S1 5S1
5S35S3 5S3
CT MB87 T187 T1
2-ACT
CT MB
LV-CT
CORE-5
CTR: 1200-800/1A
CLASS: PS
P2P2P2
IN CASE OF 1&1/2 CB SYSTEM, THE DIFFERENTIAL
3 C
T M
ET
HO
D :
3-C
T
&
2-C
T4 C
T M
ET
HO
D :
3-C
T
&
2-A
CT
6 C
T M
ET
HO
D :
3-A
CT
& 2
-AC
T
3 3 3
2-ACT
CORE-5
CTR: 2000-1000-500/1A
CLASS: PS
P2P2P2
5S4 5S4 5S4
5S35S3 5S3
PROTECTION CTs
ASSOCIATED WITH MAIN & TIE CBs SHOULD BE
CONNECTED TO SEPARATE BIAS WINDINGS AND THESE SHOULD NOT BE PARALLED
IN ORDER TO AVOID FALSE OPERATION DUE TO
DISSIMILAR CT TRANSIENT RESPONSE.
NUMERICAL RELAYS DOES NOT REQUIRE AUX CTs
MAINMAIN--1(87T1) 1(87T1) DIFFERENTIAL PROTECTION FOR ICTDIFFERENTIAL PROTECTION FOR ICT(5/6/8 CT METHOD)(5/6/8 CT METHOD)
3-TCT
P2P2P2 CT MB
3 3 35S1 5S1 5S1
5S35S3 5S3
CT MB87 T187 T1
3 3 3
3-TCT
CORE-5
CTR: 2000-1000-500/1A
CLASS: PS
5S4 5S4 5S4
5S35S3 5S3
LV-CT
CORE-5
CTR: 1200-800/1A
CLASS: PS
P2P2P2
NORMALLY LOW NORMALLY LOW IMPEDENCE BIASED
DIFFERENTIAL RELAY IS USED FOR
TRANSFORMER DIFFERENTIAL PROTECTION
NUMERICAL RELAYS DOES NOT REQUIRE AUX CTs
MAIN2 (87T2) : MAIN2 (87T2) : DIFFERENTIAL PROTECTION FOR ICTDIFFERENTIAL PROTECTION FOR ICT
3 3 3
400KV HV
BUSHING CT
CORE-1
CTR: 1000/1A
P2P2P2
S2S2S2
S1S1S1
87 T287 T2
CLASS: PS
3 3 3NEUTRAL
BUSHING CT
CORE-1
CTR: 1000/ 1A
CLASS: PS
P1P1P1
P1P1P1
P2P2P2
S1S1S1
S2S2S2
3 3 3
220KV LV
BUSHING CT
CORE-1
CTR: 1000/1A
CLASS: PS
P2P2P2
P2P2P2
P1P1P1
S2S2S2
S1S1S1
MAIN2 (87T2) : MAIN2 (87T2) : DIFFERENTIAL PROTECTION FOR ICTDIFFERENTIAL PROTECTION FOR ICT
3 3 3
400KV HV
BUSHING CT
CORE-1
CTR: 1000/1A
P2P2P2
S2S2S2
S1S1S1
CLASS: PS
3NEUTRAL
BUSHING CT
CORE-1
CTR: 1000/ 1A
CLASS: PS
P1P1P1
P1
P2
S1
S2
3 3 3
220KV LV
BUSHING CT
CORE-1
CTR: 1000/1A
CLASS: PS
P2P2P2
P1P1P1
S2S2S2
S1S1S1
3 3 3
400KV HV
BUSHING CT
CORE-2
CTR: 1000/1A
P2P2P2
S2S2S2
S1S1S1
MAIN2 (87T2) : MAIN2 (87T2) : DIFFERENTIAL PROTECTION FOR ICTDIFFERENTIAL PROTECTION FOR ICT
87 T287 T2
CLASS: PS
3 3 3NEUTRAL
BUSHING CT
CORE-2
CTR: 1000/ 1A
CLASS: PS
P1P1P1
P1P1P1
P2P2P2
S1S1S1
S2S2S2
ME
TR
OS
IL(N
ON
LIN
EA
RR
ES
IST
OR
)
3 3 3
220KV LV
BUSHING CT
CORE-2
CTR: 1000/1A
CLASS: PS
P2P2P2
P2P2P2
P1P1P1
S2S2S2
S1S1S1
MAINMAIN--2 (64 T) : 2 (64 T) : REF PROTECTION FOR ICTREF PROTECTION FOR ICT
3 3 3
400KV HV
BUSHING CT
CORE-1
CTR: 1000/1A
P2P2P2
S2S2S2
S1S1S1
CLASS: PS
3 3 3NEUTRAL
BUSHING CT
CORE-1
CTR: 1000/ 1A
CLASS: PS
P1P1P1
P1P1P1
P2P2P2
S2S2S2
S1S1S1
METROSIL(NON LINEARRESISTOR)
3 3 3
220KV LV
BUSHING CT
CORE-1
CTR: 1000/1A
CLASS: PS
P2P2P2
P2P2P2
P1P1P1
S2S2S2
S1S1S1
MAINMAIN--2 (64 T) 2 (64 T) : REF PROTECTION FOR ICT: REF PROTECTION FOR ICT
3 3 3
400KV HV
BUSHING CT
CORE-1
CTR: 1000/1A
P2P2P2
S2S2S2
S1S1S1
CLASS: PS
NEUTRAL
BUSHING CT
CORE-1
CTR: 1000/ 1A
CLASS: PS
P1P1P1
METROSIL(NON LINEARRESISTOR)
3P1
P2
S1
S2
3 3 3
220KV LV
BUSHING CT
CORE-1
CTR: 1000/1A
CLASS: PS
P2P2P2
P1P1P1
S2S2S2
S1S1S1
B/U 67 HV B/U 67 HV -- BACKUP PROTECTION FOR ICT HVBACKUP PROTECTION FOR ICT HV(3/4/5 CT METHOD)(3/4/5 CT METHOD)
3 3 3
3-CT
CORE-4
CTR: 2000-1000-500/1A
CLASS: PS
4S4 4S4 4S4
4S34S3 4S3
P2P2P2 CT MB
IR4 / C411
IY4 / C431
IB4 / C451
IN4 / C471
VR11 / E111
VY11 / E131
VB11 / E151
2-ACT
CT MB
CVT
SELECTION
BUS-1 CVT /
BUS-2 CVT /
LINE CVT
3 3 3
3 33
VN11 / E171
E172
E174
3 C
T M
ET
HO
D :
3-C
T
&
2-C
T4 C
T M
ET
HO
D :
3-C
T
&
2-A
CT
6 C
T M
ET
HO
D :
3-A
CT
& 2
-AC
T
3 3 3
2-ACT
CORE-4
CTR: 2000-1000-500/1A
CLASS: PS
P2P2P2
4S4 4S4 4S4
4S34S3 4S3
CORE-2
VA : 100
CLASS: 3P
IR4 / C411
IY4 / C431
IB4 / C451
B/U 67 HV B/U 67 HV -- BACKUP PROTECTION FOR ICT HVBACKUP PROTECTION FOR ICT HV(5/6/8 CT METHOD)(5/6/8 CT METHOD)
P2P2P2 CT MB
VR11 / E111
VY11 / E131
VB11 / E151
3 3 3
3-TCT
CORE-4
CTR: 2000-1000-500/1A
CLASS: PS
4S4 4S4 4S4
4S34S3 4S3
P2P2P2 CT MB
CVT
SELECTION
BUS-1 CVT /
BUS-2 CVT /
LINE CVT
IR4 / C411
IY4 / C431
IB4 / C451
IN4 / C471
3 3 3
3 33
VN11 / E171
E172
E174
CORE-2
VA : 100
CLASS: 3P
B/U 67 LV B/U 67 LV -- BACKUP PROTECTION FOR ICT LVBACKUP PROTECTION FOR ICT LV
3 3 3
LV-CT
CORE-4
CTR: 1200 – 800 /1A
CLASS: PS
4S2 4S2 4S2
4S14S1 4S1
P1P1P1 CT MB
IR4 / C411
IY4 / C431
IB4 / C451
IN4 / C471
VR11 / E111
VY11 / E131
VB11 / E151
P2P2P2
VOLTAGE
SELECTION
BUS-1 PT /
BUS-2 PT
3 3 3
3 33
VN11 / E171
E172
E174
CORE-2
VA : 100
CLASS: 3P
LBB & BUSBARLBB & BUSBARPROTECTIONPROTECTION
SCHEMES SCHEMES SCHEMES SCHEMES ADOPTED INADOPTED IN
ONE AND HALFONE AND HALFCIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER
SCHEMESCHEMEPREPARED BY
GOPALA KRISHNA PALEPUADE/MRT(PROTECTION)
LBB/BFR PROTECTIONLBB/BFR PROTECTION
2-52CB 3-52CBBUS-1 BUS-2
LINE1 AT/F-1
50Z 50Z50ZT
1-52CB
50Z 50Z
� LBB/BFR IS LOCAL BREAKER BACKUP PROTECTION/ BREAKER FAILURE RELAY.� 1No LBB RELAY IS PROVIDED FOR EACH BREAKER.� LBB IS CURRENT OPERATED RELAY.� LBB RELAY IS ENERGISED WHEN MASTER TRIP RELAY(86-A OR/AND 86-B OR/AND 96)
OPERATES OR SINGLE PHASE TRIP RELAYS OPERATES AND GIVEN SIGNAL TO BREAKER FOR TRIP.
� LBB RELAY TIME DELAY IS PROVIDED.
50ZT
� LBB RELAY TIME DELAY IS PROVIDED.� LBB RELAY OPERATES WHEN THE BREAKER IS UNDER TROUBLE/ FAILS TO OPERATE. � AFTER ENERGISED THE LBB RELAY AND TIME DELAY COMPLETES, EVEN CURRENT IS
THERE THIS THINKS BREAKER FAIL TO OPERATE AND GIVEN SIGNAL AS PER SCHEME DESCRIBED NEXT PRESENTATION.
� NEW CONCEPT: Normally the CT connections for LBB/BFR relay is in series withMain-2 Protection. In case of Numerical Distributed LBB/BFR and Centralized Bus-BarSystem, the CT connections for Bus-Bar are terminated at LBB/BFR and CentralizedBus-Bar is interconnected by Fiber-Optic cable.
11--52 CB LBB/BFR OPERATION52 CB LBB/BFR OPERATION
86
86
--AA
BB
LINELINE21L1/21L1/ICTICT
87T187T1
LINELINE21L2/21L2/
86
86
--AA
BB
86
86
--BB 21L2/21L2/ICTICT
87T287T2
86
86
--BB
BUSBAR-1 PROTECTION (96-BB )
OPTD
AND BUSBAR-1 ISOLATED
DIRECT TRIP 1&2VIA CARRIER TO
OTHER END
50Z
TO 96-ZT TRIP RELAYOF TIE CB(2-52CB)
BUS-1 BUS-2
1-52CB 3-52CB2-52CB
TC-1 TC-2
ISOLATED
TC-1TC-2
Breaker Failure Relay of the Main Circuit Breaker Trips the 1. Connected Bus Bar Protection, 2. Tie Circuit Breaker 96/50Z Relay & 3. Remote End Circuit Breaker through Carrier Tripping.
22--52 CB LBB/BFR OPERATION52 CB LBB/BFR OPERATIONLINELINE21L1/21L1/ICTICT
87T187T1
LINELINE
86
86
--AA
LINELINE21L1/21L1/ICTICT
87T187T1
LINELINELINELINE21L2/21L2/ICTICT
87T287T2
86
86
--BB
LINELINE21L2/21L2/ICTICT
87T287T2
TO 96-BB TRIP RELAYOF LINE CB(1-52CB)
DIRECT TRIP 1&2VIA CARRIER
TO OTHER END
TO 96-BB TRIP RELAYOF AT/F(ICT) CB (3-52CB)
INTER TRIP TOLVCB & TBCCB
50ZT
BUS-1 BUS-2
1-52CB 3-52CB2-52CB
TC-1 TC-2
OF LINE CB(1-52CB) OF AT/F(ICT) CB (3-52CB)
Breaker Failure Relay of the Tie Circuit Breaker Trips the 1. Both Sides Main Circuit Breakers and 2. Remote End Circuit Breakers through carrier Tripping
( In case of Transformer, LV Circuit Breaker)
33--52 CB LBB/BFR OPERATION52 CB LBB/BFR OPERATION
86
86
--AA
BB
LINELINE21L1/21L1/ICTICT
87T187T1
LINELINE21L2/21L2/
86
86
--AA
BB
86
86
--BB 21L2/21L2/ICTICT
87T287T2
86
86
--BB
BUSBAR-2 (96 BB)PROTECTION OPTD
AND BUSBAR-2
ISOLATED
INTER TRIP TO LV CB & TBC CB
50Z
TO 96-ZT TRIP RELAYOF TIE CB(2-52CB)
BUS-1 BUS-2
1-52CB 3-52CB2-52CB
TC-1 TC-2 TC-1TC-2
ISOLATED
Breaker Failure Relay of the Main Circuit Breaker Trips the 1. Connected Bus Bar Protection 2. Tie Circuit Breaker 96/50Z Relay & 3. Remote End Circuit Breaker ( In case of ICT, LV CB)
BASICS OF BUSBAR PROTECTIONBASICS OF BUSBAR PROTECTIONNEED FOR BUSBAR PROTECTIONNEED FOR BUSBAR PROTECTION� IN ITS ABSENCE FAULT CLEARING TAKES PLACE IN ZONE-2 OF DISTANCE RELAY BY
REMOTE END TRIPPING.
� THIS MEANS SLOW AND UNSELECTIVE TRIPPING AND WIDE SPREAD BLACKOUT.
EFFECT OF DELAYED CLEARENCEEFFECT OF DELAYED CLEARENCE� GREATER DAMAGE AT FAULT POINT.
� INDIRECT SHOCK TO CONNECTED EQUIPMENT LIKE SHAFTS OF GENERATOR AND
WINDINGS OF TRANSFORMER.WINDINGS OF TRANSFORMER.
BASIC THEORYBASIC THEORY� KIRCHOFF’s CURRENT LAW STATES THAT THE SUM OF THE CURRENTS ENTERING A
GIVEN NODE MUST BE EQUAL TO THE CURRENTS LEAVING AT THAT NODE.
BUS BAR PROTECTION SYSTEMSBUS BAR PROTECTION SYSTEMS1. HIGH IMPEDENCE DIFFERENTIAL PROTECTION
2. MODERATE-IMPEDENCE DIFFERENTIAL PROTECTION
3. LOW-IMPEDENCE DIFFERENTIAL PROTECTION
4. NUMERICAL BUS DIFFERENTIAL PROTECTION
HIGH IMPEDENCE DIFFERENCIAL PROTECTIONHIGH IMPEDENCE DIFFERENCIAL PROTECTIONTHE HIGH IMPEDENCE PROTECTION SCHEME, ON THE OTHER HAND, IS A GOOD SOLUTION FOR
SINGLE BUSBAR ARRANGEMENTS , ONE & HALF BREAKER SYSTEMS OR RING BUSBARS, PROVIDING
THAT APPROPRIATE DEDICATED CT CORES ARE AVAILABLE FOR THIS USE ALONE. IT IS SENSTIVE,
STABLE & FAST PROTECTION.
HOWEVER, SPECIAL CT REQUIREMENTS, ADDITIONAL HIGH VOLTAGE DEVICE PROTECTION,
DEMANDING MAINTANENCE etc PUT RESTRICTIONS IN ITS APPLICATIONS.
A MEASURING CIRCUIT COMPRISES A HIGH-IMPEDENCE STABILIZING RESISTOR CONNECTED
ACROSS THE CIRCULATING CURRENT ARRANGEMENT OF ALL THE CTs IN PARALLEL. THE VALUE OF
THE STABILIZING RESISTOR IS CHOOSEN SUCH THAT THE VOLTAGE DROP ACROSS THE RELAY
CIRCUIT IS INSUFFICIENT TO OPERATE THE FAULTS OUTSIDE THE PROTECTED ZONE.
LIMITATIONS OF CONVENTIONAL HIGH IMPEDENCE DIFFERENTIAL RELAYPUTS STRINGENT REQUIREMENTS ON CT’s. Class X for all CT Cores.NEED FOR DEDICATED CT CORES. Separate CT Cores for BUSBAR and CHECK ZONE Protection.IDENTICAL CT RATIO, MAGNETISING IMPEDENCE.AUX CT’s RATIO CORRECTIONS UNACCEPTABLE.IN ABILITY TO COPE WITH INCREASING FAULT CURRENT.SLOW RESPONSE.Advantage of Numerical Protection Technology (e.g. Fault recording, Communication etc) not available.BASIC OPERATING TIME EXCLUDING RELAY TIME IS 15 – 20ms.THIS RELAY REQUIRES CHECK ZONE FEATURE. THE TRIP COMMAND IS ONLY GIVEN WHEN BOTH A DISCRIMINATING & CHECK ZONE SYSTEM OPERATES.BOTH A DISCRIMINATING & CHECK ZONE SYSTEM OPERATES.
MEDIUM IMPEDENCE DIFFERENTIAL PROTECTIONMANY OF THE LIMITATIONS OF HIGH IMPEDENCE PROTECTION CAN BE OVERCOME
USING MODERATE MEDIUM IMPEDENCE PROTECTION (OR STABILIZED HIGH-IMP
SCHEME), WHICH IS A COMBINATION OF THE NORMAL HIGH-IMP AND STABILIZED
DIFFERENTIAL SCHEMES.
LOW IMPEDENCE DIFFERENTIAL PROTECTION LOW IMPEDENCE PROTECTION(PERCENTAGE BIASED BUS DIFFERENTIAL RELAY) IS
MOST SUITABLE PROTECTION SCHEME FOR DOUBLE AND MULTIPLE BUSBAR SYSTEMS
(WITH OR WITHOUT TRANSFER BUS) WITH FEEDERS BEING SWITCHED BETWEEN(WITH OR WITHOUT TRANSFER BUS) WITH FEEDERS BEING SWITCHED BETWEEN
SECTIONS OF BUSBAR, WHICH OPERATES WITH FULL SELECTIVITY FOR ALL POSSIBLE
BUSBAR CONFIGUARATIONS.
ADVANTAGES� FREE OF ANY NEED FOR MATCHED CT CHARACTERESTICS OR RATIOs, LOW
LEAKAGE REACTANCE OR RESISTANCE.
� OTHER PROTECTIVE RELAYS CAN BE INCLUDED IN THE SAME CIRCUIT.
� STABLE FOR INFINITE FAULT LEVELS. INSENSITIVE TO CT SATURATION.
� DETECTS FAULTS WITHIN 1 – 2ms & INITIATES TRIPPING WITHIN 5 – 7ms.
DIFFERENCE BETWEEN BUSBAR SCHEMESDIFFERENCE BETWEEN BUSBAR SCHEMES
DETAILSDETAILS HIGH IMPEDENCE BUSBAR PROTECTIONHIGH IMPEDENCE BUSBAR PROTECTIONPERCENTAGE BIASED LOW IMPEDENCE PERCENTAGE BIASED LOW IMPEDENCE
BUS BAR PROTECTIONBUS BAR PROTECTION
PRINCIPLEPRINCIPLE
THETHE CURRENTSCURRENTS ENTERINGENTERING ANDAND LEAVINGLEAVING THETHE BUSBARBUSBAR AREARE COMPAREDCOMPARED
CONTINUOSLYCONTINUOSLY.. ITIT INVOLVESINVOLVES CHOOSINGCHOOSING OFOF IMPEDENCEIMPEDENCE HIGHHIGH ENOUGHENOUGH
STABLISESTABLISE THETHE RELAYRELAY FORFOR HEAVYHEAVY EXTERNALEXTERNAL FAULTSFAULTS.. THISTHIS ISIS
CIRCULATINGCIRCULATING CURRENTCURRENT PRINCIPLEPRINCIPLE..
ITIT HASHAS DIFFERENTIALDIFFERENTIAL ANDAND BIASBIAS SETTINGSETTING.. THETHE RESULTANTRESULTANT BIASBIAS
ISIS PROPOTIONALPROPOTIONAL TOTO ARITHMATICARITHMATIC SUMSUM OFOF ALLALL CURRENTS,CURRENTS,
WHEREASWHEREAS THETHE OPERATINGOPERATING CURRENTCURRENT ISIS VECTORVECTOR SUMSUM OFOF ALLALL
CIRCUITCIRCUIT CURRENTSCURRENTS..
ITIT REQUIRESREQUIRES ALLALL IDENTICALIDENTICAL CTCT RATIO’sRATIO’s && TURNSTURNS RATIORATIO.. LOWLOW ITIT CANCAN WORKWORK WITHWITH CTsCTs OFOF UNEQUALUNEQUAL RATIOSRATIOS ALSOALSO.. FREEFREE OFOF
CTsCTs
ITIT REQUIRESREQUIRES ALLALL IDENTICALIDENTICAL CTCT RATIO’sRATIO’s && TURNSTURNS RATIORATIO.. LOWLOW
RESISTANCERESISTANCE OFOF SECONDARYSECONDARY WINDINGWINDING.. ClassClass XX forfor allall CTCT CoresCores..
MINIMUMMINIMUM KNEEKNEE POINTPOINT VOLTAGEVOLTAGE OFOF 300300--500500VV..
LOWLOW MAGNETISINGMAGNETISING CURRENT(FEWCURRENT(FEW MILLIAMPS)MILLIAMPS)..
ITIT CANCAN WORKWORK WITHWITH CTsCTs OFOF UNEQUALUNEQUAL RATIOSRATIOS ALSOALSO.. FREEFREE OFOF
ANYANY NEEDNEED OFOF MATCHEDMATCHED CTCT CHARACTERESTICCHARACTERESTIC OROR RATIOsRATIOs LOWLOW
LEAKAGELEAKAGE REACTANCEREACTANCE OROR RESISTANCERESISTANCE.. OTHEROTHER PROTECTIVEPROTECTIVE
RELAYSRELAYS CANCAN BEBE INCLUDEDINCLUDED ININ THETHE SAMESAME CIRCUITCIRCUIT..
BURDENBURDENIMPOSESIMPOSES COMPARATIVELYCOMPARATIVELY HIGHHIGH BURDENBURDEN ONON CTsCTs.. AUXILIARYAUXILIARY CTsCTs
REDUCEREDUCE THETHE PERFORMANCEPERFORMANCE OFOF THETHE SCHEMESCHEME
IMPOSESIMPOSES LESSLESS BURDENBURDEN ONON CTsCTs.. AUXILIARYAUXILIARY CTsCTs HAVEHAVE NONO
EFFECTEFFECT ONON PERFORMANCEPERFORMANCE OFOF SCHEMESCHEME..
CT SATURATIONCT SATURATIONOPERATIONOPERATION OFOF SCHEMESCHEME EVENEVEN WHENWHEN CTsCTs GETGET SATURATEDSATURATED DURINGDURING
INTERNALINTERNAL FAULTSFAULTS..
OPERATIONOPERATION OFOF SCHEMESCHEME EVENEVEN WHENWHEN CTsCTs GETGET SATURATEDSATURATED
DURINGDURING INTERNALINTERNAL FAULTSFAULTS.. INSENSITIVEINSENSITIVE TOTO CTCT SATURATIONSATURATION..
UTILISATIONUTILISATIONITIT ISIS GOODGOOD SOLUTIONSOLUTION FORFOR SINGLESINGLE BUSBARBUSBAR ARRANGEMENTS,ARRANGEMENTS, ONEONE &&
HALFHALF BREAKERBREAKER SYSTEMSSYSTEMS OROR RINGRING BUSBARBUSBAR SYSTEMSSYSTEMS..
MOSTMOST SUITABLESUITABLE FORFOR DOUBLEDOUBLE ANDAND MULTIPLEMULTIPLE BUSBARBUSBAR SYSTEMSSYSTEMS
(( WITHWITH OROR WITHOUTWITHOUT TRANSFERTRANSFER BUS)BUS)..
OPERATING TIMEOPERATING TIMEBASICBASIC OPERATINGOPERATING TIMETIME EXCLUDINGEXCLUDING RELAYRELAY TIMETIME ISIS 1515 –– 2020 mSmS.. DETECTSDETECTS FAULTSFAULTS WITHWITH ININ 11 ––22 mSmS ANDAND INITIATESINITIATES TRIPPINGTRIPPING
WITHWITH ININ 55--77 mSmS..
STABILITYSTABILITY INABILITYINABILITY TOTO COPECOPE WITHWITH INCREASINGINCREASING FAULTFAULT CURRENTCURRENT.. STABLESTABLE FORFOR INFINITEINFINITE FAULTFAULT LEVELLEVEL..
PERFORMANCEPERFORMANCEHIGHLYHIGHLY SENSITIVESENSITIVE FORFOR INTERNALINTERNAL FAULTSFAULTS ANDAND COMPLETELYCOMPLETELY STABLESTABLE
FORFOR EXTERNALEXTERNAL FAULTSFAULTS..
HIGHLYHIGHLY SENSITIVESENSITIVE FORFOR INTERNALINTERNAL FAULTSFAULTS ANDAND COMPLETELYCOMPLETELY
STABLESTABLE FORFOR EXTERNALEXTERNAL FAULTSFAULTS..
ADDITIONAL ADDITIONAL
PROTECTIONPROTECTION
THISTHIS RELAYRELAY REQUIRESREQUIRES CHECKCHECK ZONEZONE FEATUREFEATURE.. THETHE TRIPTRIP COMMANDCOMMAND ISIS
ONLYONLY GIVENGIVEN WHENWHEN BOTHBOTH AA DISCRIMINATINGDISCRIMINATING && CHECKCHECK ZONEZONE SYSTEMSYSTEM
OPERATESOPERATES..
THISTHIS RELAYRELAY HASHAS ININ BUILTBUILT CHECKCHECK ZONEZONE FEATUREFEATURE (NO(NO SEPARATESEPARATE
CHECKZONECHECKZONE FEATURE)FEATURE) ii..ee OVEROVER CURRENTCURRENT STARTINGSTARTING RELAYRELAY
PROVIDEDPROVIDED..
BUS BAR MAINBUS BAR MAIN--1 & MAIN1 & MAIN--2 PROTECTION2 PROTECTION(ANY CT METHOD)(ANY CT METHOD)
3 3 3
IY1 / B131
IB1 / B151
IN1 / B1711-CT
CORE-1
CTR: 2000-1000/1A
CLASS: PS
1S3 1S3 1S3
1S11S1 1S1
P2P2P2 CT MB
BUS BAR
PROTECTION
FOR
BUS-1
IR1 / B111
IY1 / B131CLASS: PS
3-CT
CT MB
IR1 / B111
IY1 / B131
MAINCB LBB IS
PART OF BUSBAR
PROTECTION
3 3 3
3-CT
CORE-1
CTR: 2000-1000/1A
CLASS: PS
P2P2P2
1S3 1S3 1S3
1S11S1 1S1
BUS BAR
PROTECTION
FOR
BUS-2
IB1 / B151
IN1 / B171
ONE AND HALF CB SYSTEM ONE AND HALF CB SYSTEM –– HIGH IMPEDANCEHIGH IMPEDANCE
BUS-1
52
52
52
-52
-52
-52
-52
87BB187BB1--MAIN1 BB1 PROTECTIONMAIN1 BB1 PROTECTION 87BB187BB1--MAIN2 BB1 PROTECTIONMAIN2 BB1 PROTECTION1
-52
2-5
2
4-5
25
-52
7-5
28
-52
10
-11
-52
13
-1
4-5
2
16
-1
7-5
2
19
-2
0-5
2
BUS-2
3-5
2
6-5
2
9-5
2
12
-52
15
-52
18
-52
21
-52
87BB287BB2--MAIN1 BB2 PROTECTIONMAIN1 BB2 PROTECTION 87BB287BB2--MAIN2 BB2 PROTECTIONMAIN2 BB2 PROTECTION
ONE AND HALF CB SYSTEM ONE AND HALF CB SYSTEM –– LOW IMPEDANCELOW IMPEDANCE
87 87 –– BB1 BUS BARBB1 BUS BAR--1 PROTECTION1 PROTECTION
BUS-1
52
-52
-52
-52
-52
52
52
1-C
T
7-5
28
-52
7-C
TC
T
10
-11
-52
10
-CT
CT
13
-1
4-5
2
13
-CT
CT
16
-1
7-5
2
16
-CT
CT
19
-2
0-5
2
19
-CT
CT
CT
2-5
21
-52
4-5
25
-52
4-C
TC
T
87 87 –– BB2 BUS BARBB2 BUS BAR--2 PROTECTION2 PROTECTION
BUS-2
9-5
2
9-C
T
12
-52
12
-CT
15
-52
15
- CT
18
-52
18
-CT
21
-52
21
-CT
3-C
T
3-5
2
6-5
2
6-C
T
NUMERICAL BUSBAR SCHEME INCL LBB/BFR/CBFNUMERICAL BUSBAR SCHEME INCL LBB/BFR/CBF(DECENTRALISED & CENTRALISED CONCEPTS)(DECENTRALISED & CENTRALISED CONCEPTS)
MAIN CB LBB
(REB 500) ABB
DECENTRALISED CONCEPT CENTRALISED CONCEPT
FO
MAIN CB LBB
TIE CB LBB
OR
OR
(7 SS 52) SIEMENS
ORFO
OR
(REB 670) ABB
(487B) SELOR
OR
MAIN CB LBB
OR
(MICOM P740) AREVA
LBB INBUILT FEATURELBB INBUILT FEATURELBB TO BUSBAR
DIGITAL COMMUNICATION
FO
LBB INBUILT FEATURELBB INBUILT FEATURE
(MICOM P746) AREVA
OR
NUMERICAL BUSBAR SCHEME INCL LBB/BFR/CBFNUMERICAL BUSBAR SCHEME INCL LBB/BFR/CBF(DECENTRALISED CONCEPT(DECENTRALISED CONCEPT-- DUPLICATE )DUPLICATE )
MAIN CB LBB
(REB 500) ABB
DECENTRALISED CONCEPT
FO(REB 500) ABB
DECENTRALISED CONCEPT
FO
TIE CB LBB
OR
OR
(7 SS 52) SIEMENSFO
OR
OR
(7 SS 52) SIEMENS
MAIN CB LBB
FO
MAIN CB LBB
OR
(MICOM P740) AREVA
LBB TO BUSBARDIGITAL COMMUNICATION
FO
OR
(MICOM P740) AREVA
LBB TO BUSBARDIGITAL COMMUNICATION
MAIN CB LBB
TIE CB LBB
FO
NUMERICAL BUSBAR SCHEME INCL LBB/BFR/CBFNUMERICAL BUSBAR SCHEME INCL LBB/BFR/CBF(CENTRALISED CONCEPT (CENTRALISED CONCEPT -- DUPLICATE)DUPLICATE)
CENTRALISED CONCEPT CENTRALISED CONCEPT
(REB 670) ABB
(487B) SEL
OR
OR
(REB 670) ABB
(487B) SEL
OR
LBB INBUILT FEATURE LBB INBUILT FEATURE
(MICOM P746) AREVA
OR
(MICOM P746) AREVA
OR
DISTRIBUTED LBB & NUMERICAL CENTRALISED BUS BAR PROTECTIONDISTRIBUTED LBB & NUMERICAL CENTRALISED BUS BAR PROTECTION
BUSBUS--11
1-5
2
4-5
2
7-5
2
10
-52
13
-52
OR OR
(REB 500) ABB (7 SS 52) SIEMENS (MICOM P740) AREVA
12
-52
45
-52
78
-52
10
11
-52
13
14
-52
BUSBUS--22
3-5
2
6-5
2
9-5
2
12
-52
15
-52
OR OR
LATEST DEVELOPMENT IN NUMERICAL DISTRIBUTED BUS BAR PROTECTIONLATEST DEVELOPMENT IN NUMERICAL DISTRIBUTED BUS BAR PROTECTION
ABBABB SIEMENSSIEMENS AREVAAREVA
BUSBAR
PROTECTION
CENTRAL UNIT
ABB Network Partner AG
c
E
ABB Network Partner AG REL 316*4
BAY UNIT
LINE
PROTECTION
TRANSFORMER
21 L1 21 L2 21 L1 21 L2 21 L1 21 L2
C
E
ABB Network Partner AG REL531
ABB Network Partner AG REL531
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
C
E
TRANSFORMER
PROTECTION
DESCRIPTION
1. IN THIS NO SEPARATE CORE IS REQUIRED FOR EITHER BUSBAR PROTECTION OR LBB / BFR.
2. CENTRALISED BUSBAR IS CONNECTED FROM BAY UNIT OR LBB OR BFR THROUGH FIBRE OPTIC.
3. BAY UNIT / BFR / LBB IS CONNECTED FROM MAIN-1 & MAIN-2 OF LINE PROTECTION OR MAIN &
BACKUP PROTECTION OF TRANSFORMER THROUGH FIBRE OPTIC FOR REDUNDANCY TO BAY UNIT.
4. THE CURRENT DATA IS TRANSFERED TO BAY UNIT TO BUSBAR CENTRAL UNIT FROM LINE /
TRANSFORMER PROTECTIONS FOR NUMIRICAL ALGORITHAM OF LBB & BUSBAR CENTRAL UNIT AND
IT WILL OPERATE FOR INTERNAL FAULTS AND DOES NOT OPERATE FOR THROUGH / EXTERNAL
FAULTS.
87 T1 87 T2 87 T1 87 T2 87 T1 87 T2
C
E
MISCELENEOUSMISCELENEOUSRELAYS & PROTECTIONSRELAYS & PROTECTIONS
ADOPTED FOR LINE INADOPTED FOR LINE INADOPTED FOR LINE INADOPTED FOR LINE INONE AND HALF ONE AND HALF
CIRCUIT BREAKERCIRCUIT BREAKERSCHEME SCHEME SCHEME SCHEME
(STUB, TEED AND AUTO RECLOSURE (STUB, TEED AND AUTO RECLOSURE FUNCTIONS)FUNCTIONS) PREPARED BY
GOPALA KRISHNA PALEPUADE/MRT(PROTECTION)
STUBSTUB--1/ STUB1/ STUB--2 PROTECTION2 PROTECTION1-52CB 2-52CB 3-52CBBUS-1 BUS-2
LINE-1 AT/F-1
STUB-1&2(BAY 1&2)
1-89L
REL 521REL 521
DISTANCE / ICT DISTANCE / ICT RELAYS RELAYS
CONVERTED CONVERTED TO STUB/BUS TO STUB/BUS
3-89T
RET 521RET 521
STUB-3&2(BAY 3&2)
WHEN A LINE IS SUPPLIED VIA TWO CIRCUIT BREAKERS IN A ONE & HALF CIRCUIT WHEN A LINE IS SUPPLIED VIA TWO CIRCUIT BREAKERS IN A ONE & HALF CIRCUIT BREAKER ARRANGEMENT, THE LINE PROTECTION INCLUDES THE AREA BETWEEN THE TWO BREAKER ARRANGEMENT, THE LINE PROTECTION INCLUDES THE AREA BETWEEN THE TWO CT’s. HOWEVER, WHEN THE LINE ISOLATOR IS OPEN THE LINE CVT‘s FOR THE DISTANCE CT’s. HOWEVER, WHEN THE LINE ISOLATOR IS OPEN THE LINE CVT‘s FOR THE DISTANCE PROTECTION ARE CONNECTED TO THE LINE AND CANNOT PROVIDE THE CORRECT PROTECTION ARE CONNECTED TO THE LINE AND CANNOT PROVIDE THE CORRECT VOLTAGE FOR THE STUB END.(VOLTAGE FOR THE STUB END.(i.ei.e THE AREA BETWEEN THE LINE ISOLATOR AND CT’s) (STUB THE AREA BETWEEN THE LINE ISOLATOR AND CT’s) (STUB = DEAD END)= DEAD END)
TO PROVIDE PROTECTION FOR A FAULT IN THIS AREA, REL 521/ REL 316 IS TO PROVIDE PROTECTION FOR A FAULT IN THIS AREA, REL 521/ REL 316 IS
REL 521REL 521
REL 316REL 316
TO STUB/BUS TO STUB/BUS OVER LOAD OVER LOAD
RELAYS WHEN RELAYS WHEN LINE ISOLATORLINE ISOLATOR
OPENSOPENS
RET 521RET 521
RET 316RET 316
TO PROVIDE PROTECTION FOR A FAULT IN THIS AREA, REL 521/ REL 316 IS TO PROVIDE PROTECTION FOR A FAULT IN THIS AREA, REL 521/ REL 316 IS PROVIDED WITH A STUB PROTECTION WHICH GIVES AN BUS OVER CURRENT TRIP IF THE PROVIDED WITH A STUB PROTECTION WHICH GIVES AN BUS OVER CURRENT TRIP IF THE LINE ISOLATOR IS OPEN AND THE CURRENT EXCEEDS THE SET VALUE IN ANY PHASE.LINE ISOLATOR IS OPEN AND THE CURRENT EXCEEDS THE SET VALUE IN ANY PHASE.
STUBSTUB--1 1 (BAY 1&2 OR BAY 3&2)(BAY 1&2 OR BAY 3&2)OPERATESOPERATES
IT OPERATES THE 3IT OPERATES THE 3--PH TRIP GRPH TRIP GR--A MAIN CB (1A MAIN CB (1--52CB OR 352CB OR 3--52CB) 52CB)
AND 3AND 3--PH TRIP GRPH TRIP GR--A TIE CB (2A TIE CB (2--52CB)52CB)
STUBSTUB--2 2 (BAY 1&2 OR BAY 3&2)(BAY 1&2 OR BAY 3&2)OPERATESOPERATES
IT OPERATES THE 3IT OPERATES THE 3--PH TRIP GRPH TRIP GR--B MAIN CB (1B MAIN CB (1--52CB OR 352CB OR 3--52CB) 52CB)
AND 3AND 3--PH TRIP GRPH TRIP GR--B TIE CB (2B TIE CB (2--52CB)52CB)
TEEDTEED--1/ TEED1/ TEED--2 PROTECTION2 PROTECTION1-52CB 2-52CB 3-52CBBUS-1 BUS-2
LINE-1 AT/F-1
TEED-1&2(BAY 1&2)
TEED-1&2(BAY 2&3)
TEED PROTECTION IS BASED ON KIRCHOFF’S CURRENT LAW. THREE SETS OF CTSTEED PROTECTION IS BASED ON KIRCHOFF’S CURRENT LAW. THREE SETS OF CTSARE CONNECTED IN STAR FASHION. SOME OF THE CURRENTS MUST BE ZERO. IF ANY ARE CONNECTED IN STAR FASHION. SOME OF THE CURRENTS MUST BE ZERO. IF ANY ARE CONNECTED IN STAR FASHION. SOME OF THE CURRENTS MUST BE ZERO. IF ANY ARE CONNECTED IN STAR FASHION. SOME OF THE CURRENTS MUST BE ZERO. IF ANY UNBALANCE CURRENTS ARE NOTICED THEN IMMEDIATELY TEED PROTECTION UNBALANCE CURRENTS ARE NOTICED THEN IMMEDIATELY TEED PROTECTION OPERATES. IF TEED PROTECTION BAY 1&2 OPERATED THEN IT TRIPS 1OPERATES. IF TEED PROTECTION BAY 1&2 OPERATED THEN IT TRIPS 1--52CB & 252CB & 2--52CB. 52CB. SIMILARLY IF TEED PROTECTION BAY 2&3 OPERATED THEN IT TRIPS 2SIMILARLY IF TEED PROTECTION BAY 2&3 OPERATED THEN IT TRIPS 2--52CB & 352CB & 3--52CB.52CB.
TEEDTEED--11
PROTECTIONPROTECTION
SUMMATION OF INDIVIDUAL PHASES OF TSUMMATION OF INDIVIDUAL PHASES OF T--SHAPED 3 SHAPED 3
CTs BEFORE REACHING TO RELAY. THIS IS CTs BEFORE REACHING TO RELAY. THIS IS
CIRCULATING CURRENT PRINCIPLE. THE CURRENT CIRCULATING CURRENT PRINCIPLE. THE CURRENT
FLOWING THROUGH IS ZERO DURING BALANCED FLOWING THROUGH IS ZERO DURING BALANCED
CONDITION. CONDITION.
HIGH IMPENDENCE THREE PHASE DIFFERENTIAL HIGH IMPENDENCE THREE PHASE DIFFERENTIAL HIGH IMPENDENCE THREE PHASE DIFFERENTIAL HIGH IMPENDENCE THREE PHASE DIFFERENTIAL
RELAY IS USED AS TEEDRELAY IS USED AS TEED--1 PROTECTION.1 PROTECTION.
TEEDTEED--22
PROTECTIONPROTECTION
TT-- SHAPED 3 CTs ARE CONNECTED TO RELAY. THE SHAPED 3 CTs ARE CONNECTED TO RELAY. THE
RELAY HAVING OPERATING COIL & RESTAIRING COIL. RELAY HAVING OPERATING COIL & RESTAIRING COIL.
BASED ON THE DIFFERENTIAL CURRENT FLOWING BASED ON THE DIFFERENTIAL CURRENT FLOWING
THROUGH THE OPERATING COIL THE RELAY THROUGH THE OPERATING COIL THE RELAY
OPERATES.OPERATES.
LOW IMPEDENCE PERCENTAGE BIASED THREE LOW IMPEDENCE PERCENTAGE BIASED THREE
TERMINAL THREE PHASE DIFFERENTIAL RELAY IS TERMINAL THREE PHASE DIFFERENTIAL RELAY IS
USED AS TEEDUSED AS TEED--2 PROTECTION.2 PROTECTION.
TEEDTEED--1 PROTECTION1 PROTECTION{BAY1&2} (5/6/8 CT METHOD){BAY1&2} (5/6/8 CT METHOD)
3 3 3
1-CT
CORE-5
CTR: 2000-1000-500/1A
CLASS: PS
P2P2P2
5S4 5S4 5S4
5S25S2 5S2
IT WORKS ON CIRCULATING
CURRENT PRINCIPLE AND
IR5IY5IB5
IN5
87 TEED-1
3 3 32-CT
CORE-5
CTR: 2000-1000-500/1A
CLASS: PS
P1P1P1
P2P2P2
P1P1P1
5S4 5S4 5S4
5S25S2 5S2
CURRENT PRINCIPLE AND
IT IS HIGH IMPEDENCE
DIFFERENTIAL RELAY.
TEED-1 PROTECTION FOR
BAY 2&3 IS ALSO SAME AS
ABOVE AND THE
FOLLOWING CTs & CORES
ARE USED
3-CT(CORE-5), 2-CT(CORE-1)
& 3-TCT(CORE-1) ARE
STARRED AND CONNECTED
IN5
IR5IY5IB5
IN5
3 3 3
1-LCT
CORE-1
CTR: 2000-1000/1A
CLASS: PS
P1P1P1
P1P1P1
P2P2P2
1S3 1S3 1S3
1S21S2 1S2
STARRED AND CONNECTED
TO TEED-1 PROTECTION
IR1IY1IB1
IN1
5 CT METHOD : 1-CT, 2-CT & 1L-CT6 CT METHOD : 1-CT, 2-BCT & 1L-CT8 CT METHOD : 1-ACT, 2-BCT & 1L-CT
TEEDTEED--2 PROTECTION2 PROTECTION{BAY1&2} (5/6/8 CT METHOD){BAY1&2} (5/6/8 CT METHOD)
3 3 3
1-CT
CORE-4
CTR: 2000-1000-500/1A
CLASS: PS
4S4 4S4 4S4
4S24S2 4S2
P2P2P2 CT MB
3 3 34S2 4S2 4S2
4S44S4 4S4
P2P2P2CT MB
87 TEED-2
1-LCT
CORE-2
CT MBP2P2P2
2-CT
CORE-4
CTR: 2000-1000-500/1A
CLASS: PS
TEED-2 PROTECTION FOR BAY 2&3 IS ALSO SAME AS ABOVE AND THE
3 3 3CORE-2
CTR: 2000-1000/1A
CLASS: PS2S2 2S2 2S2
2S32S3 2S3
ABOVE AND THE FOLLOWING CTs & CORES ARE USED. 3-CT(CORE-4), 2-CT(CORE-2) & 3-TCT (CORE-2) ARE CONNECTED TO TEED-2 PROTECTION.IT WORKS ON KIRCHOFF’S CURRENT PRINCIPLE & IT IS PERCENTAGE BIASED LOW IMPEDENCE DIFFERENTIAL RELAY
TEED / STUB PROTECTION TRIP SCHEMETEED / STUB PROTECTION TRIP SCHEME
8686--AAMTR/MTR/HSTRHSTR
8686--AAMTR/MTR/HSTRHSTR
8686--AAMTR/MTR/HSTRHSTR
STUBOR
TEED-1
C
E
12345678
910111213141516
ABB Network Partner AG REC 316*4
STUBOR
TEED-1
BUS-1 BUS-2
1-52CB 3-52CB2-52CB
HSTRHSTR
ABBABBREL521REL521
8686--BBMTR/MTR/
8686--BBMTR/MTR/
HSTRHSTR
8686--BBMTR/MTR/
HSTRHSTR
TRIP COIL-1 TRIP COIL-1 TRIP COIL-1
TRIP COIL-2 TRIP COIL-2 TRIP COIL-2(BAY 1&2)
(BAY 2&3)
(BAY 2&3)
(BAY 1&2)
TEED-2OR
TEED-2REL521REL521MAINMAIN--11MTR/MTR/HSTRHSTR
MTR/MTR/HSTRHSTR
MTR/MTR/HSTRHSTR
8686--A : GROUPA : GROUP--A MASTER TRIP RELAY / HIGH SPEED TRIP RELAY A MASTER TRIP RELAY / HIGH SPEED TRIP RELAY 8686--B : GROUPB : GROUP--B MASTER TRIP RELAY / HIGH SPEED TRIP RELAYB MASTER TRIP RELAY / HIGH SPEED TRIP RELAY
LINE/TRANSFORMER ISOLATOR OPENS THIS INTERLOCK WILL INITIATE LINE/TRANSFORMER ISOLATOR OPENS THIS INTERLOCK WILL INITIATE
21 L1 / 87 T1 & 21 L2 / 87 T221 L1 / 87 T1 & 21 L2 / 87 T2 CONVERTED STUBCONVERTED STUB--1 & 2 PROTECTION1 & 2 PROTECTION
OR
STUB
TEED-2OR
STUB
AUTO RECLOSURE BASICSAUTO RECLOSURE BASICS� FAULTS ARE THREE TYPES
1. TRANSIENT FAULT: These are cleared by the immediate tripping of Circuit Breakers and do not reoccur when the line is re-energized.
2. SEMI-PERMANENT FAULTS: These require a time interval to disappear before a line is charged again.3. PERMANENT FAULTS: These are to be located and repaired before the line is re-energized.
� About 80-90% of the faults occurring are transient in nature. Hence the Automatic Reclosure of breaker (after tripping on Fault) will result in the line being successfully re-energized.
� ADVANTAGES:A. Decreasing outage time.B. Improving Reliability.C. Improving system stability.
D. Reduce fault damage and Maintenance Time.D. Reduce fault damage and Maintenance Time.� DEAD TIME: The time between the Auto-reclosing Scheme being energized and
the operation of the contacts which energize the Circuit Breaker closing
circuit.� RECLAIM TIME: The Time Following a successful closing operation measured
from the instant the Auto-Reclosing relay closing contacts make which must elapse before the Auto-Reclosing relay initiates another reclosing
attempt. In other words, it may be said to be the time between 1st and 2nd
Auto-Reclosure.
� TYPES OF AUTO-RECLOSING SCHEMES:1. BASED ON PHASE
A. THREE PHASE AUTO-RECLOSING: This type of Auto-Reclosing causes an immediate drift part of the two systems and hence no interchange of synchronizing power can take place during the dead time. B. SINGLE PHASE AUTO-RECLOSING: In this, only the faulty phase(only SLG Faults) is reclosed without causing interruption in interchange synchronizing power between two systems through other two healthy phases.
2. BASED ON ATTEMPTS OF RECLOSUREA. SINGLE SHOT AUTO-RECLOSING: In this scheme, Breaker is reclosed only once on A. SINGLE SHOT AUTO-RECLOSING: In this scheme, Breaker is reclosed only once on a given fault before lockout of Circuit Breaker Occurs. High-Speed Auto-Reclosing for EHT System is invariably Single Shot.B. MULTI-SHOT AUTO-RECLOSING: In this scheme, more than one reclosing attempts made for a given fault before lockout of Circuit Breaker occurs.B.I. DISADVANTAGES: Repeated closure attempts has with high fault level would seriously affect the Circuit Breaker, Equipment and System Stability.B.ii. CIRCUIT BREAKER LIMITATIONS: Ability of Circuit Breaker to Perform several Trip Close operations in quick succession. B. iii. SYSTEM CONDITIONS: In the percentage of the semi-Permanent faults (which could be burnt out) is moderate, For example on the lines through the forest, multi could be burnt out) is moderate, For example on the lines through the forest, multi shot Auto-Reclosing is followed.
3. DEPENDING ON SPEED:A. HIGH-SPEED AUTO-RECLOSING: This aids in fast restoration of supply but should be done by taking into account the following factors.I. System disturbance time can be tolerated without loss of system stability.ii. Characteristics of Protection Schemes and Circuit Breaker. B. LOW SPEED OR DELAYED AUTO RECLOSING: This is suitable for highly inter-connected systems where the loss of a single line is unlikely to cause two sections of the system to drift apart and loose synchronism.
� METHOD OF ADOPTION IN ONE AND HALF BREAKER SYSTEM: The Auto-Reclosure Functions used for the Bus Breakers 1-52CB & 3-52CB are set as Masters and one for the Center Breaker 2-52CB(TIE) as Follower. Co-ordination is required between the Auto-Reclosure Functions. A Synchrocheck function is also loaded in each Relay to permit 3 pole Auto-Reclosing.Each Line Protection relays starts both MAIN & TIE Circuit Breakers to trip for the Concerned line. After a Successful reclosure of the Main Breaker, The Tie Breaker will be reclosed after a supplementary time delay. Should the Main CB Auto-Reclosure relay not be successful in its reclosing attempts, the Tie CB Auto-Reclosure relay not be successful in its reclosing attempts, the Tie CB Auto-Reclosure is blocked. If the Main CB is Open or its Auto-Reclosure Relay is not ready or Out of service, The TIE CB Auto-Reclosure will reclose The TIE Breaker after its own dead time without any supplementary time delay.
� CHOICES OF EHV SYSTEM:1. CHOICE OF DEAD TIME: A. Lower limit is decided by deionising of Circuit Breaker.B. Upper Limit is decided by Transient Stability and Synchronism.C. Longer Transmission Lines Require Longer dead Time.D. The dead time for High Speed Auto-Reclosing scheme with EHV System is 0.3 to 1.2 sec.1.2 sec.2. CHOICE OF RECLAIM TIME:This should not be set to such a low value that the operating cycle of Breaker is exceeded when two faults incident occurs close together. The reclaim time will be in the range of 10 to 30 sec., depending the breaker opening and closing mechanisms.3. CHOICE OF ZONE:This should normally kept in Zone-1. It is a Zone-1 fault and SLG fault only auto-reclosure is comes in to picture. In other zones the auto reclosure is blocked.
AUTOAUTO--RECLOSURE FOR RECLOSURE FOR ONE & HALF BREAKER SCHEMEONE & HALF BREAKER SCHEME
TRIP COMMANDSAUTO RECLOSURE
COMMANDS
1-52CB 2-52CB 3-52CB
79 (A/R)+79 (A/R)+25(SYNC) 25(SYNC) RAAAMRAAAM
RASCRASC
79 (A/R)+79 (A/R)+25(SYNC) 25(SYNC) RAAAMRAAAM
RASCRASC
79 (A/R)+79 (A/R)+25(SYNC) 25(SYNC) RAAAMRAAAM
RASCRASC
LINE-1 LINE-2C
E
ABB Network Partner AG REL531
21 MAIN-1REL 521
C
E
12345678
910111213141516
ABB Network Partner AG REC 316*4
21 MAIN-2REL 316
C
E
ABB Network Partner AG REL531
21 MAIN-1REL 521
C
E
12345678
910111213141516
ABB Network Partner AG REC 316*4
21 MAIN-2REL 316
AUTO RECLOSING TIMING CHARTAUTO RECLOSING TIMING CHARTINSTANT OF FAULT
PROTECTION
TR
AN
SIE
NT
F
AU
LT OPERATING
TIME
OPERATES
TRIP COIL
ENERGISED
CONTACTS
SEPARATE
ARC
EXTINGUISHED
CONTACTS
FULLY OPEN
RESETS
CLOSING COIL
ENERGISED
CONTACTS
MAKE
CONTACTS
FULLY CLOSED
CIRCUIT BREAKERT
RA
NS
IEN
T F
AU
LT
PE
RM
AN
EN
T F
AU
LT
PROTECTION
OPERATING
TIME
OPERATES
TRIP COIL
ENERGISED
CONTACTS
SEPARATE
ARC
EXTINGUISHED
CONTACTS
FULLY OPEN
RESETS
OPENING
TIMEARCING
TIME
OPERATING TIME
CLOSING
TIME
DEAD TIME
CLOSING COIL
ENERGISED
CONTACTS
MAKE
CONTACTS
FULLY CLOSED
RECLOSE
ON TO FAULT
OPERATES
CONTACTS
SEPARATE
ARC
EXTINGUISHED
CONTACTS
FULLY OPEN
RESETS
TIME
AUTO RECLOSERELAY
PE
RM
AN
EN
T F
AU
LT
CIRCUIT BREAKER
OPENING
TIMEARCING
TIME
OPERATING TIME
CLOSING
TIME
DEAD TIME
TRIP COIL
ENERGISED
SYSTEM DISTURBANCE TIME
RECLOSE INITIATED
BY PROTECTION
DEAD TIME CLOSING PULSE TIME
RECLAIM TIME
RELAY READY TO RESPOND
TO FURTHER FAULT INCIDENTS
(AFTER SUCEESFUL RECLOSRE)
CARRIER CARRIER INTERTRIPPING INTERTRIPPING
SCHEMESSCHEMESSCHEMESSCHEMESADOPTED IN ADOPTED IN
ONE AND HALFONE AND HALFCIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER
SCHEME SCHEME PREPARED BY
GOPALA KRISHNA PALEPUADE/MRT(PROTECTION)
TYPES OF CARRIER TRIPPING SCHEMESTYPES OF CARRIER TRIPPING SCHEMESPERMISSIVE TRIPPINGPERMISSIVE TRIPPING
Permissive trip commands are always monitored by a protectionrelay. The circuit breaker is tripped when receipt of the commandcoincides with operation of the protection relay at the receiving endresponding to a system fault. The receipt of an incorrect signalmust coincide with operation of the receiving end protection for aresponding to a system fault. The receipt of an incorrect signalmust coincide with operation of the receiving end protection for atrip operation to take place. Normally, the risk of a spurious trip islesser. The intention of these schemes is to speed up tripping forfaults occurring within the protected zone.
BLOCKING SCHEMEBLOCKING SCHEMEBlocking commands are initiated by a protection element thatdetects faults external to the protected zone. Detection of anexternal fault at the local end of a protected circuit results in adetects faults external to the protected zone. Detection of anexternal fault at the local end of a protected circuit results in ablocking signal being transmitted to the remote end. At the remoteend, receipt of the blocking signal prevents the remote endprotection operating if it had detected the external fault. Loss of thecommunications channel is less serious for this scheme than inothers as loss of the channel does not result in a failure to trip whenrequired. However, the risk of a spurious trip is higher.
TYPES OF CARRIER TRIPPING SCHEMESTYPES OF CARRIER TRIPPING SCHEMESConventional time-stepped distance protection has One of the main disadvantages is that theinstantaneous Zone 1 protection at each end of the protected line cannot be set to cover the wholeof the feeder length and is usually set to about 80%. This leaves two 'end zones', each being about20% of the protected feeder length. Faults in these zones are cleared in Zone 1 time by theprotection at one end of the feeder and in Zone 2 time (typically 0.25 to 0.5 seconds) by theprotection at the other end of the feeder. This situation cannot be tolerated in some applications,for two main reasons:
I). Faults remaining on the feeder for Zone 2 time may cause the system to become unstable.
II). Where high-speed auto-reclosing is used, the non-simultaneous opening of the circuit.
Breakers at both ends of the faulted section results in no 'dead time' during the auto- reclose cyclefor the fault to be extinguished and for ionized gases to clear. This results in the possibility that atransient fault will cause permanent lockout of the circuit breakers at each end of the line section.
Even where instability does not occur, the increased duration of the disturbance may give rise topower quality problems, and may result in increased plant damage.
Unit schemes of protection that compare the conditions at the two ends of the feedersimultaneously positively identify whether the fault is internal or external to the protected sectionand provide high-speed protection for the whole feeder length. This advantage is balanced by thefact that the unit scheme does not provide the back up protection for adjacent feeders given by adistance scheme.fact that the unit scheme does not provide the back up protection for adjacent feeders given by adistance scheme.
The most desirable scheme is obviously a combination of the best features of both arrangements,that is, instantaneous tripping over the whole feeder length plus back-up protection to adjacentfeeders. This can be achieved by interconnecting the distance protection relays at each end of theprotected feeder by a communications channel.
The purpose of the communications channel is to transmit information about the systemconditions from one end of the protected line to the other, including requests to initiate or preventtripping of the remote circuit breaker. The former arrangement is generally known as a 'transfertripping scheme' while the latter is generally known as a 'blocking scheme'. However, theterminology of the various schemes varies widely, according to local custom and practice.
1. ZONEZONE 11 EXTENSIONEXTENSION SCHEMESCHEME (Z(Z11XX SCHEME)SCHEME)
2. TRANSFERTRANSFER TRIPPINGTRIPPING SCHEMESSCHEMES
I. DIRECT UNDER REACH TRANSFER TRIP SCHEME (DUTT)
II. PERMISSIVE UNDER REACH TRANSFER TRIP SCHEME (PUTT)
III. PUTT – FWD SCHEME
TYPES OF CARRIER TRIPPING SCHEMESTYPES OF CARRIER TRIPPING SCHEMES
III. PUTT – FWD SCHEME
IV. PERMISSIVE UNDER REACH ACCELERATED SCHEME
V. PERMISSIVE OVER REACH TRANSFER TRIP SCHEME (POTT)
VI. WEEK IN FEED CONDITIONS.
3. BLOCKINGBLOCKING OVEROVER REACHINGREACHING SCHEMESSCHEMES
I. BLOCKING OVER-REACHING PROTECTION SCHEME USING ZONE 2.
OR DIRECTIONAL COMPARISION BLOCKING SCHEMEOR DIRECTIONAL COMPARISION BLOCKING SCHEME
II. BLOCKING OVER-REACHING PROTECTION SCHEME USING ZONE 1.
III. WEEK IN FEED CONDITIONS.
4. DIRECTIONAL COMPARISON UNBLOCKING SCHEMEDIRECTIONAL COMPARISON UNBLOCKING SCHEME
OPERATING
MODE
UNDER
REACHING
SENDING
OVER
REACHING
SENDING
PERMISSIVE
CRITERIA
RECEIVING
GENERAL
REQUIREMENTS
PERMISSIVE
UNDER
REACH ZONE-1 - - -
UNDER IMPEDENCE
UNDER VOLTAGE
OVER CURRENT
DISTANE &
SECURE & FAST
PROPERTIES OF COMMAND PROTECTION SYSTEMSPROPERTIES OF COMMAND PROTECTION SYSTEMS
REACH
(PUTT)DISTANE &
DIRECTION
FAST
PERMISSIVE
OVER
REACH
(POTT)
- - - ZONE-2SECURE &
FAST
DIRECT
TRIPZONE-1 - - -
DISTANCE &
DIRECTION
SECURE & DEPENDABLETRIP DIRECTION DEPENDABLE
ACCELERAT
ED UNDER
REACH
ZONE-1 - - - ZONE-2SECURE &
FAST
BLOCKING
OVER
REACH
- - -REVERSE LOCKING
DISTANCE &
DIRECTION
FAST & DEPENDABLE
PARAMETERSPARAMETERS PUTT POTT BLOCKING UNBLOCKING
SignalSignal
TransmissionTransmission
SystemSystem
Dependable and secure communication
channel
1. Power line carrier with frequency shiftmodulation. HF signal coupled to 2 phasesof the protected line, or even better, to aparallel circuit to avoid transmission of
Reliablecommunicationchannel (onlyrequired during
external faults)
1. Power line carrier
Dedicated channel
With continuoussignal Transfer
1. Power line carrierWith frequency shiftkeying. Continuous
PREFFERED APPLICATIONS OF TELE/ CARRIER TRIPPING SCHEMESPREFFERED APPLICATIONS OF TELE/ CARRIER TRIPPING SCHEMES
parallel circuit to avoid transmission ofthe HF signal through the fault location.
2. Microwave radio, especiallydigital(PCM)3. Fibre -optic cables
1. Power line carrierWith amplitudeModulation (ON/OFF).
The same frequency
may be used on all
terminals)
keying. Continuous
Signal transmission
must be permitted.
CharacteristicCharacteristic
Of lineOf line
Best suited for longer lines - where the Under-reach
1. Excellent coverage On short lines in the
All line types –
Preferred practice in the USA.
Same as POTT
Of lineOf line the Under-reach zone provides sufficient resistance coverage.
lines in the Presence of fault
resistance.
2. Suitable for the
Protection of multi-
terminal lines with
intermediate in-feed.
in the USA.
COMPARISION OF TELE/ CARRIER TRIPPING SCHEMESCOMPARISION OF TELE/ CARRIER TRIPPING SCHEMESOn normal two-terminal lines the main deciding factors in the choice of the typeof scheme, apart from the reliability of the signalling channel, operating speedand the method of operation of the system. Table compares the importantcharacteristics of the various types of scheme.
Criterion Transfer Tripping Scheme Blocking scheme
Speed of operation Fast Not as FastSpeed of operation Fast Not as Fast
Speed with in-service testing Slower As fast
Suitable for auto Re Close Yes Yes
Security against mal-operation due to:
Current reversal Special features required Special features required
Loss of communications Poor good
Weak In feed/Open CB Special features required Special features required
Modern digital or numerical distance relays are provided with a choice ofseveral schemes in the same relay. Thus scheme selection is now largelyindependent of relay selection, and the user is assured that a relay is availablewith all the required features to cope with changing system conditions.
PARAMETERS PUTT POTT BLOCKING UNBLOCKING
ADVANTAGESADVANTAGES1. Simple technique2. No coordination Of zones and times With the opposite End required.3.The combination Of different relay
1.1.1.1. Can be applied without Under reaching zone1 stage (e.g. overcompensated Series compensated lines).
2.2.2.2. Can be applied on Extremely short lines (impedance less than minimum relay setting)
3.3.3.3. Better for parallel lines as mutual
Same as POTT Same as POTT
but:
1. If no signal is
Received (no
block and no
unblock) then
ADVANTAGES & DRAWBACKS OF TELE/ CARRIER TRIPPING SCHEMESADVANTAGES & DRAWBACKS OF TELE/ CARRIER TRIPPING SCHEMES
Of different relay Types therefore presents no Problems.
3.3.3.3. Better for parallel lines as mutual coupling is not critical for the overreach zone
4.4.4.4. Weak in feed terminals are no problem. (Echo and Weak In feed logic is included)
unblock) then
tripping by the
overreach zone
is released
after 20 ms
DRAWBACKSDRAWBACKS1. 1. 1. 1. Overlapping of the zone 1 reaches must be ensured. On parallel lines, teed feeders and tapped lines, the influence of zero
1. Zone reach and signal timing coordination with the Remote end is necessary (current reversal).
Same as POTT1. Slow tripping – all Tele-protection trips must be delayed to wait for the eventual
Same as
POTT
influence of zero sequence coupling and intermediate In feeds must be carefully considered to make sure a minimum overlapping of the zone 1 reach is always present.
2.2.2.2. Not suitable for weak
In feed terminals
wait for the eventual blocking signal.2. Continuous channel Monitoring is not Possible.
PARAMETERS PUTT POTT BLOCKING UNBLOCKING
Short LineShort Line
Not Suitable as the Zone1 Operation is essential and Zone1 setting in X and R direction must be small on Short Lines.
Suitable as the Z1B setting may be substantially larger than the Line impedance so that signal Transmission is secure for all faults on the Line.
Suitable as Reverse Reach Setting is independent of Line Length.
Suitable Same as POTT.
ADVANTAGES & DRAWBACKS OF TELE/ CARRIER TRIPPING SCHEMESADVANTAGES & DRAWBACKS OF TELE/ CARRIER TRIPPING SCHEMES
the Line.
Weak InWeak In--feedfeed
Not Suitable as the Zone1 Operation is essential at Both Ends for 100% Coverage.
Suitable as the Strong end detects all the Line Faults with the Over-Reaching Z1B. The Weak In-feed end then echos the received Signal.
Partially Suitableas the Reverse Fault is also Detected at the Weak In-feed end but no trip at Weak In-feed end.
Suitable Same as POTT.
Amplitude Amplitude Modulated Modulated Power Line Power Line
Not Suitable as the Signal must be Trans-mitted through the Fault Location which
Not Suitable same as PUTT.
Suitable as the Signal is only sent when the Line is not Faulted.
Not Suitable Same as PUTT.
Power Line Power Line CarrierCarrier
Fault Location which Attenuates the Signal.
not Faulted.
Frequency or Frequency or Phase Phase
Modulated Modulated Power Line Power Line
CarrierCarrier
Suitable as the Signal can be Transmitted through the Fault Location.
Suitable same as PUTT.
Suitable as the Signal can be Transmitted under all Conditions.
Suitable Same as PUTT.
Communication Communication
independent independent of Power Lineof Power Line
Suitable. Suitable. Suitable. Suitable.
PROTECTION COUPLER PANELPROTECTION COUPLER PANEL
NSD 50/ NSD 50/
11--
2+2+
TXTXTRIP TRIP A(C)A(C)
CS
11--
2+2+
TXTXTRIP TRIP C(A)C(A)
CS
--11250V
DC
250V
DC55
DISPLAY
ACTIVE START TRIP
NSD 50/ NSD 50/ NSD 70NSD 70
2+2+
55--
6+6+
99--
A(C)A(C)
RXRXTRIPTRIPA(C)A(C)
TXTXTRIPTRIP
CS
CR
2+2+
55--
6+6+
99--
C(A)C(A)
RXRXTRIPTRIPC(A)C(A)
TXTXTRIPTRIP
CS
CR
AL
AR
MA
LA
RM
--250V
DC
250V
DC55
66
C
E
G4AC TB: V9LC
1010+
1313--
14+14+
TRIPTRIPB(D)B(D)
RXRXTRIPTRIPB(D)B(D)
S
CR
GA4D TB:V9LC
10+10+
1313--
14+14+
TRIPTRIPD(B)D(B)
RXRXTRIPTRIPD(B)D(B)
S
CR
G4AA TB: V9LB
AL
AR
MA
LA
RM
--22250V
DC
250V
DC77
88
PROTECTION COUPLERS FOR 400KV LINEPROTECTION COUPLERS FOR 400KV LINE
�� FOR EACH LINE 2Nos PROTECTION COUPLER PANELS PROVIDED.FOR EACH LINE 2Nos PROTECTION COUPLER PANELS PROVIDED.�� FOR EACH LINE 1NO CARRIER SPEECH PANEL PROVIDED.FOR EACH LINE 1NO CARRIER SPEECH PANEL PROVIDED.�� SO, ONE LINE REQUIRES TOTAL 3 PANELS.SO, ONE LINE REQUIRES TOTAL 3 PANELS.
�� CARRIER SPEECH PANEL PURELY FOR VOICE COMMUNICATION BETWEEN CARRIER SPEECH PANEL PURELY FOR VOICE COMMUNICATION BETWEEN TWO SUBSTATIONS, TWO SUBSTATIONS, i.ei.e THE LINE CONNECTED SUBSTATIONS.THE LINE CONNECTED SUBSTATIONS.
�� THE VOICE COMMUNICATION ARE TWO METHODS PROVIDED.THE VOICE COMMUNICATION ARE TWO METHODS PROVIDED.�� THE VOICE COMMUNICATION ARE TWO METHODS PROVIDED.THE VOICE COMMUNICATION ARE TWO METHODS PROVIDED.�� ONE IS HOTLINE COMMUNICATION/DEDICATED/ LIFT&TALK METHOD.ONE IS HOTLINE COMMUNICATION/DEDICATED/ LIFT&TALK METHOD.
�� ANOTHER IS DIAL METHOD.ANOTHER IS DIAL METHOD.�� IN PROTECTION COUPLER PANELIN PROTECTION COUPLER PANEL--1 TOTAL 3 CARDS ARE IMPORTANT FOR 1 TOTAL 3 CARDS ARE IMPORTANT FOR
SENDING & RECEIVING TRIP SIGNALS.SENDING & RECEIVING TRIP SIGNALS.
�� ONE CARD FOR ALARM ONE CARD FOR ALARM i.ei.e G4AA. ONE CARD FOR PERMISSIVE/PROTECTION G4AA. ONE CARD FOR PERMISSIVE/PROTECTION TRIP TRIP i.ei.e G4AC & ANOTHER CARD FOR DIRECT TRIPS G4AC & ANOTHER CARD FOR DIRECT TRIPS i.ei.e G4AD.G4AD.
�� IN PROTECTION COUPLERIN PROTECTION COUPLER--2 PANEL ALSO 3 CARDS ARE PROVIDED SIMILAR TO 2 PANEL ALSO 3 CARDS ARE PROVIDED SIMILAR TO PROTECTION COUPLERPROTECTION COUPLER--1 PANEL.1 PANEL.
�� THE PROTECTION COUPLER PANEL DRAWING IS SHOWN IN PREVIOUS MENU.THE PROTECTION COUPLER PANEL DRAWING IS SHOWN IN PREVIOUS MENU.�� THE PROTECTION COUPLER PANEL DRAWING IS SHOWN IN PREVIOUS MENU.THE PROTECTION COUPLER PANEL DRAWING IS SHOWN IN PREVIOUS MENU.�� 1SET TX & RX FOR PERMISSIVE/ PROTECTION TRIP(G4AC)1SET TX & RX FOR PERMISSIVE/ PROTECTION TRIP(G4AC)�� 1SET TX & RX FOR BACKUP FOR PERMISSIVE/ PROTECTION IN ANOTHER 1SET TX & RX FOR BACKUP FOR PERMISSIVE/ PROTECTION IN ANOTHER
PANEL(G4AC).PANEL(G4AC).�� 1SET TX & RX FOR DIRECT TRIP CHANNEL1SET TX & RX FOR DIRECT TRIP CHANNEL--1( G4AD).1( G4AD).�� 1SET TX & RX FOR SPARE UNDER EMERGENCY(G4AD).1SET TX & RX FOR SPARE UNDER EMERGENCY(G4AD).�� THE ABOVE ARRANGEMENT SIMILAR FOR PROTECTION COUPLER PANELTHE ABOVE ARRANGEMENT SIMILAR FOR PROTECTION COUPLER PANEL--2.2.
�� G4AA CARD FOR ALARM.G4AA CARD FOR ALARM.
MAINMAIN--1 PROTECTION CARRIER INTER TRIPPING1 PROTECTION CARRIER INTER TRIPPING
LINE 21L1LINE 21L1
CR
CS
-VECARRIER RECEIVE
IN
NS
D 5
0N
SD
50
OUT
G4AC V9LC 1
G4AC V9LC 2
G4AC V9LC 5
G4AC V9LC 6
CARRIER SEND
ALARMAB
BA
BB
PANEL-1
G4AC V9LC 2
G4AA V9LB 5
G4AA V9LB 6
NS
D 5
0N
SD
50 G4AC V9LC 10
G4AC V9LC 13
THIS IS BACKUP FOR PERMISSIVE/ PROTECTION TRIPTHIS IS BACKUP FOR PERMISSIVE/ PROTECTION TRIP
+VE -VE
PANEL-2
AB
BA
BB
NS
D 5
0N
SD
50
G4AC V9LC 14
G4AC V9LC 9
THIS IS BACKUP FOR PERMISSIVE/ PROTECTION TRIPTHIS IS BACKUP FOR PERMISSIVE/ PROTECTION TRIPAND CONNECTED IN ANOTHER PANELAND CONNECTED IN ANOTHER PANEL
MAINMAIN--2 PROTECTION CARRIER INTER TRIPPING2 PROTECTION CARRIER INTER TRIPPING
LINE 21L2LINE 21L2
CR
CS
-VECARRIER RECEIVE
IN
NS
D 5
0N
SD
50
OUT
G4AC V9LC 1
G4AC V9LC 2
G4AC V9LC 5
G4AC V9LC 6
CARRIER SEND
ALARMAB
BA
BB
PANEL-2
G4AC V9LC 2
G4AA V9LB 5
G4AA V9LB 6
NS
D 5
0N
SD
50 G4AC V9LC 10
G4AC V9LC 13
THIS IS BACKUP FOR PERMISSIVE/ PROTECTION TRIPTHIS IS BACKUP FOR PERMISSIVE/ PROTECTION TRIP
+VE -VE
PANEL-1
AB
BA
BB
NS
D 5
0N
SD
50
G4AC V9LC 14
G4AC V9LC 9
THIS IS BACKUP FOR PERMISSIVE/ PROTECTION TRIPTHIS IS BACKUP FOR PERMISSIVE/ PROTECTION TRIPAND CONNECTED IN ANOTHER PANELAND CONNECTED IN ANOTHER PANEL
DIRECT TRIP SEND CARRIER CHANNELDIRECT TRIP SEND CARRIER CHANNEL--11
T N C
CONTROL PANEL
87 BUSBAR TRIP (ZONE-1)
87 BUSBAR TRIP (ZONE-2)
96 BUSBAR PROT-1 PANEL
96 BUSBAR PROT-2 PANEL
ABBABBNSD 50NSD 50
DC +VE FROM PANEL
PANEL-1
T N C
MAIN CB(1-52CB)
T N C
TIE CB(2-52CB)
R Y B
R Y B
TIE CB (2-52 CB)
MAIN CB (1-52 CB)
50 LBB/BFR FOR MAIN CB / RAICA
G4AD V9LC 2
DC –VE FROM PANEL
G4AD V9LC 1
CONDITIONS FOR DIRECT TRIP59L1 / OVER VOLTAGE STAGE-1
59L2 / OVER VOLTAGE STAGE-2
50 LBB/BFR FOR TIE CB / RAICA
87 HZ / TEED-1 PROTECTION
87 LZ / TEED-2 PROTECTION
CONDITIONS FOR DIRECT TRIP
1. TIE CB OPEN CONDITION + MAIN CB REMOTE HAND TRIP GIVEN.
2. MAIN CB OPEN CONDITION + TIE CB REMOTE HAND TRIP GIVEN.
3. TIE CB OPEN CONDITION + 96 BUSBAR-1 OPERATED.
4. MAIN CB OPEN CONDITION + 96 BUSBAR-2 OPERATED (FOR HALF DIA ONLY).
5. MAIN CB 50 LBB/BFR OPERATED.
6. TIE CB 50 LBB/BFR OPERATED.
7. 59L1 OVER VOLTAGE STAGE-1 OPERATED.
8. 59L2 OVER VOLTAGE STAGE-2 OPERATED.
9. 87 HZ TEED-1 PROTECTION OPERATED
10. 87 LZ TEED-2 PROTECTION OPERATED.
DIRECT TRIP SEND CARRIER CHANNELDIRECT TRIP SEND CARRIER CHANNEL-- 22
T N C
CONTROL PANEL
87 BUSBAR TRIP (ZONE-1)
87 BUSBAR TRIP (ZONE-2)
96 BUSBAR PROT-1 PANEL
96 BUSBAR PROT-2 PANEL
ABBABBNSD 50NSD 50
DC +VE FROM PANEL
PANEL-2
T N C
MAIN CB(1-52CB)
T N C
TIE CB(2-52CB)
R Y B
R Y B
TIE CB (2-52 CB)
MAIN CB (1-52 CB)
50 LBB/BFR FOR MAIN CB / RAICA
G4AD V9LC 2
DC –VE FROM PANEL
G4AD V9LC 1
CONDITIONS FOR DIRECT TRIP59L1 / OVER VOLTAGE STAGE-1
59L2 / OVER VOLTAGE STAGE-2
50 LBB/BFR FOR TIE CB / RAICA
87 HZ / TEED-1 PROTECTION
87 LZ / TEED-2 PROTECTION
CONDITIONS FOR DIRECT TRIP
1. TIE CB OPEN CONDITION + MAIN CB REMOTE HAND TRIP GIVEN.
2. MAIN CB OPEN CONDITION + TIE CB REMOTE HAND TRIP GIVEN.
3. TIE CB OPEN CONDITION + 96 BUSBAR-1 OPERATED.
4. MAIN CB OPEN CONDITION + 96 BUSBAR-2 OPERATED (FOR HALF DIA ONLY).
5. MAIN CB 50 LBB/BFR OPERATED.
6. TIE CB 50 LBB/BFR OPERATED.
7. 59L1 OVER VOLTAGE STAGE-1 OPERATED.
8. 59L2 OVER VOLTAGE STAGE-2 OPERATED.
9. 87 HZ TEED-1 PROTECTION OPERATED
10. 87 LZ TEED-2 PROTECTION OPERATED.
DIRECT TRIP RECEIVE CHANNELDIRECT TRIP RECEIVE CHANNEL--1&21&2
ABBABB
NSD 50NSD 50
PANEL-1
DC +VE
TO 86TO 86--A MASTER TRIP RELAY A MASTER TRIP RELAY (HIGH SPEED TRIP RELAY) FOR (HIGH SPEED TRIP RELAY) FOR MAIN CB(152CB)MAIN CB(152CB)
TO 86TO 86--A MASTER TRIP RELAYA MASTER TRIP RELAY
G4AD V9LC 6
G4AD V9LC 5
ABBABB
NSD 50NSD 50
PANEL-2 +VE -VE
TO 86TO 86--A MASTER TRIP RELAYA MASTER TRIP RELAY(HIGH SPEED TRIP RELAY) FOR (HIGH SPEED TRIP RELAY) FOR TIE CB(252CB)TIE CB(252CB)
TO 86TO 86--B MASTER TRIP RELAYB MASTER TRIP RELAY(HIGH SPEED TRIP RELAY) FOR(HIGH SPEED TRIP RELAY) FOR
DIRECT TRIP-1CARRIER RECEIVE RELAY
NSD 50NSD 50
G4AD V9LC 6
G4AD V9LC 5
DC +VE
(HIGH SPEED TRIP RELAY) FOR(HIGH SPEED TRIP RELAY) FORMAIN CB(152CB)MAIN CB(152CB)
TO 86TO 86--B MASTER TRIP RELAY B MASTER TRIP RELAY (HIGH SPEED TRIP RELAY) FOR(HIGH SPEED TRIP RELAY) FORTIE CB(252CB)TIE CB(252CB)
DIRECT TRIP-2CARRIER RECEIVE RELAY
PLCC CARRIER PROTECTION SYSTEMPLCC CARRIER PROTECTION SYSTEM(TELEPROTECTION)(TELEPROTECTION)
C
E
ABB Network Partner AG REL531
REL 521MAIN-1
PROTECTIONC
E
ABB Network Partner AG REL531
PLCCPANEL
PLCCPANEL
NSD 50PANEL
NSD 50PANEL
NSD 50NSD 50
ELECTRICAL CONNECTION
ELECTRICAL POWER LINE
C
E
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ABB Network Partner AG REC 316*4
C
E
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ABB Network Partner AG REC 316*4
REL 316MAIN-2
PROTECTION
NSD 50PANEL
NSD 50PANEL
ELECTRICAL CONNECTION
FIBRE OPTIC PROTECTION SYSTEMFIBRE OPTIC PROTECTION SYSTEM(TELEPROTECTION)(TELEPROTECTION)
C
E
ABB Network Partner AG REL531
REL 521MAIN-1
PROTECTIONC
E
ABB Network Partner AG REL531
NSD 70PANEL
NSD 70PANEL
NSD 70NSD 70
ELECTRICAL CONNECTION
FOX-UFOX-515
TU
NO
S
GE
CO
D/
SIF
OX FOX-U
FOX-515
TU
NO
S
GE
CO
D/
SIF
OX
C
E
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ABB Network Partner AG REC 316*4
C
E
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ABB Network Partner AG REC 316*4
REL 316MAIN-2
PROTECTION
NSD 70PANEL
NSD 70PANEL
ELECTRICAL CONNECTION
FIBRE OPTIC CARRIER PROTECTION SYSTEMFIBRE OPTIC CARRIER PROTECTION SYSTEM(TELEPROTECTION)(TELEPROTECTION)
DIGITAL RELAY CONNECTION VIA FIBRE OPTICDIGITAL RELAY CONNECTION VIA FIBRE OPTICABB Network Partner AG REL531
REL 521MAIN-1
PROTECTION
ABB Network Partner AG REL531
FOX-UFOX-515
TU
NO
S
OT
ER
M
FOX-UFOX-515
TU
NO
S
OT
ER
M
C
E
PROTECTIONC
E
C
E
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ABB Network Partner AG REC 316*4
C
E
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ABB Network Partner AG REC 316*4
REL 316MAIN-2
PROTECTION
FIBRE OPTIC CARRIER PROTECTION SYSTEMFIBRE OPTIC CARRIER PROTECTION SYSTEM(TELEPROTECTION)(TELEPROTECTION)
DIGITAL RELAY CONNECTION VIA FIBRE OPTICDIGITAL RELAY CONNECTION VIA FIBRE OPTIC
MAIN-1 LINE
Tx
Rx
Rx
Tx
NMS
OP
TIM
UX
PR
OT
NC
OU
PL
ER
MAIN-1 LINEPROTECTION
21L1 /87L1
Tx
NMSOP
TIM
UX
PR
OT
NC
OU
PL
ER
CO
UP
LE
R
Tx
Rx
Rx
Tx
MAIN-2 LINEPROTECTION
21L2 /87L2
MISCELLENEOUSMISCELLENEOUSRELAYS & PROTECTIONSRELAYS & PROTECTIONS
ADOPTED FOR ADOPTED FOR ADOPTED FOR ADOPTED FOR AUTO TRANSFORMER INAUTO TRANSFORMER IN
ONE AND HALF ONE AND HALF CIRCUIT BREAKERCIRCUIT BREAKERCIRCUIT BREAKERCIRCUIT BREAKER
SCHEME SCHEME (OVER FLUX & REF FUNCTIONS)(OVER FLUX & REF FUNCTIONS)
PREPARED BYGOPALA KRISHNA PALEPU
ADE/MRT(PROTECTION)
OVER EXCITATION/FLUX RELAYOVER EXCITATION/FLUX RELAY{{FOR AUTO TRANSFORMER HV & LV}FOR AUTO TRANSFORMER HV & LV}
VOLTAGE
SELECTION
BUS-1 PT /
BUS-2 PT
99 T HV
CVT SELECTION
BUS-2 PT
CORE-1
VA : 100
CLASS: 3P
HV OVER FLUX RELAY IS IN BUILT FUNCTION OF MAIN1: 87T1: DIFF PROTN
LV OVER FLUX RELAY IS IN BUILT FUNCTION OF MAIN2: 87T2: DIFF PROTN
99 T LV
CVT SELECTION
BUS-1 CVT /
BUS-2 CVT /
LINE CVT
CORE-1
VA : 100
CLASS: 3P
315MVA, 400KV/220KV AT/F VOLAGE SELECTION315MVA, 400KV/220KV AT/F VOLAGE SELECTION
1-52CBBUS-1 BUS-2
LINE1AT/F-1
2-52CB 3-52CB
FEEDER HAVING LINE CVTs &BUSES ARE HAVING BUS CVTs BUT AT/Fs ARE FEEDER HAVING LINE CVTs &BUSES ARE HAVING BUS CVTs BUT AT/Fs ARE
NOT HAVING CVTs. FOR TRANSFORMER PANEL, PT SUPPLY IS SELECTED AS NOT HAVING CVTs. FOR TRANSFORMER PANEL, PT SUPPLY IS SELECTED AS
PER SELECTION DESCRIBED BELOW FOR METERING AND PROTECTION, PER SELECTION DESCRIBED BELOW FOR METERING AND PROTECTION,
WHICH IS FIRST SELECTED .WHICH IS FIRST SELECTED .
BUSBUS--11
CVTCVT
If AT/F is feeding from BusIf AT/F is feeding from Bus--1 and 11 and 1--52CB & 252CB & 2--52CB is closed. Then 52CB is closed. Then
BusBus--1 CVT is selected and this supply is extended to Control & 1 CVT is selected and this supply is extended to Control &
Relay Panels for Auto Transformer.Relay Panels for Auto Transformer.
BUSBUS--22
CVTCVT
If AT/F is feeding from BusIf AT/F is feeding from Bus--2 and 32 and 3--52 CB is closed & 252 CB is closed & 2--52CB is 52CB is
open. Then Busopen. Then Bus--2 CVT is selected and this supply is extended to 2 CVT is selected and this supply is extended to
Control & Relay Panels for Auto Transformer.Control & Relay Panels for Auto Transformer.
LINELINE
CVTCVT
If AT/F is feeding from Direct Line and 2If AT/F is feeding from Direct Line and 2--52CB is closed & 152CB is closed & 1--52 CB 52 CB
& 3& 3--52 CB is open and 389T ISO is Closed . Then line CVT is 52 CB is open and 389T ISO is Closed . Then line CVT is
selected and this supply is extended to Control & Relay Panels for selected and this supply is extended to Control & Relay Panels for
Auto Transformer.Auto Transformer.
11--PH UNITS OF 500 MVA TRANSFORMER ( EACH PH UNITS OF 500 MVA TRANSFORMER ( EACH 167 MVA ) WITH CHANGE OVER FACILITY167 MVA ) WITH CHANGE OVER FACILITY
RR YY BB RR YY BB
SP
AR
E
1 2 3 4 5 6 7
SP
AR
ES
PA
RE
SP
AR
E
RR YY BB RR YY BB
MAINMAIN--1 & MAIN1 & MAIN--22PROTECTION FORPROTECTION FORSHUNT REACTOR SHUNT REACTOR
ADOPTED IN ADOPTED IN ONE AND HALFONE AND HALF
CIRCUIT BREAKER CIRCUIT BREAKER SCHEMESCHEME
PREPARED BYGOPALA KRISHNA PALEPU
ADE/MRT(PROTECTION)
BASICS OF SHUNT REACTORBASICS OF SHUNT REACTOR1. 1. TYPES OF REACTORS :TYPES OF REACTORS :
A. BASED ON REACTOR CONNECTIONA. BASED ON REACTOR CONNECTIONi. SHUNT REACTOR. ii. SERIES REACTOR.B. BASED ON REACTOR LOCATIONB. BASED ON REACTOR LOCATIONi. BUS REACTOR ii. LINE REACTORC. BASED ON CONTROLC. BASED ON CONTROLi. 3-PH OIL IMMERSED REACTOR WITH GAPPED IRON CORE. i. 3-PH OIL IMMERSED REACTOR WITH GAPPED IRON CORE. ii. THYRISTOR CONTROLLED REACTOR (STATIC VAR COMPENSATOR)
(APTRANSCO UTILISING SHUNT REACTORS FOR BUS & LINE IN 400KV NETWORK)(APTRANSCO UTILISING SHUNT REACTORS FOR BUS & LINE IN 400KV NETWORK)
2. 2. NEED OF SHUNT REACTOR:NEED OF SHUNT REACTOR:
A. LINE REACTORA. LINE REACTORSHUNT REACTORS ARE USED IN ORDER TO COMPENSATE FOR THE CAPACITIVE SHUNT REACTANCEOF TRANSMISSION LINES. THE REACTOR IS CONNECTED PARALLEL TO THE LINE. THE LOCATION OFREACTOR IS OUT GOING SIDE OF LINE i.e AFTER CIRCUIT BREAKER. LENGTH OF LINE IS MORETHERE MAY BE VOLTAGE IS RAISING DUE TO FARANTI EFFECT(CAPACITANCE) DURING CHARGING.IN CASE OF ZONE-2 (OPEN JUMPER) FAULT, THE FAULT CLEARED BY REMOTE END IS FAST, BUTTHIS END IT WILL TAKE TIME DELAY DUE TO ZONE-2. DURING THIS TIME, VOLTAGE MAY RAISING. SO,THIS END IT WILL TAKE TIME DELAY DUE TO ZONE-2. DURING THIS TIME, VOLTAGE MAY RAISING. SO,LINE REACTOR IS USED FOR CONTROLLING THE SWITCHING OVER VOLTAGES AND SAFEGUARDTHE OPERATING EQUIPMENT. NORMALLY IT IS ALWAYS IN SERVICE. NORMALLY BOTH ENDS LINEREACTORS ARE PROVIDED. THE ELECTRICAL INTERLOCK IS PROVIDED THAT IF REACTORISOLATOR CLOSSED POSITION ONLY WILL GIVE PERMIT TO CLOSE THE LINE ISOLATOR. SIMILARLYFOR OPENING REACTOR ISOLATOR THE LINE ISOLATOR SHOULD BE IN OPEN POSITION. NEUTRALREACTOR CONNECTED BETWEEN THE STAR POINT OF EHV SHUNT REACTOR AND THE GROUND,LIMITS THE SECONDARY ARC CURRENT TO A LOW VALUE OF AROUND 10 AMPS TYPICALLY FOR400KV SYSTEM TO ENSURE COMPLETE DE-IONISATION OF ARC PATH WHEN EHV SYSTEM DEVELOPSA SINGLE LINE TO GROUND FAULT. ARC EXTINCTION DURING LINE SINGLE- PHASE AUTORECLOSEDEAD TIME IS ASSISTED BY THIS NEUTRAL REACTOR.
B. BUS REACTORB. BUS REACTORTHE REACTOR IS CONNECTED PARALLEL TO THE BUS i.e LIKE A FEEDER/LINE.DURING LIGHTLY LOADED CONDITIONS THERE MAY BE POSSIBULITY OF RAISINGBUS VOLTAGES. FOR SAFEGUARD THE OPERATING EQUIPMENT BUS REACTORSARE UTILISING. NORMALLY IT IS NOT IN SERVICE. WHENEVER THE VOLTAGERAISES TO 4%TO 5% MORE THAN THE RATED VOLTAGE THIS MAY BE KEPT INSERVICE AND 2% TO 3% LESS THAN THE RATED VOLTAGE THIS MAY BE KEPT OUTOF SERVICE.
3.3. SELECTION OF REACTORSELECTION OF REACTORA. LINE REACTORA. LINE REACTORA. LINE REACTORA. LINE REACTORNORMALLY LINE REACTORS ARE PROVIDED IF THE LINE IS MORE OR EQUAL TO250KM. IN APTRANSCO NETWORK MAXIMUM LENTH OF LINE IS 350KM. AS PERSYSTEM STUDIES RECOMANDATIONS IF LINE LENGTH IS 250KM TO 300KM 50MVARREACTOR IS TO BE USED. IF MORE THAN 300KM 63MVAR REACTOR IS TO BE USED.B. BUS REACTOR B. BUS REACTOR NORMALLY BUS REACTORS ARE PROVIDED IF THE SUBSTATION BUS VOLTAGE ISRAISING 5% MORE THAN THE RATED VOLTAGE DURING LIGHTLY LOADEDCONDITION. BASED ON THE SYSTEM STUDIES RECOMANDATIONS BUS REACTORSARE TO BE PROVIDED. CALCULATIONS ARE REQUIRED FOR PROVIDING BUSARE TO BE PROVIDED. CALCULATIONS ARE REQUIRED FOR PROVIDING BUSREACTOR. IN THIS THERE IS NO STANDARDISATION.
4.4. LOCATION OF REACTORS WITH CAPACITY IN APTRANSCOLOCATION OF REACTORS WITH CAPACITY IN APTRANSCOA. LINE REACTORA. LINE REACTOR1. 400KV KALAPAKA-KHAMMAM 1 AT BOTH ENDS – 63MVAR 2. 400KV KALAPAKA-KHAMMAM 2 AT BOTH ENDS – 63MVARB. BUS REACTORB. BUS REACTOR1. 400KV KALAPAKA SS – 2 X 50 MVAR2. 400KV NUNNA SS(PGCIL BAYS) – 1 x 63 MVAR
5. 5. PURPOSE OF SHUNT REACTOR PROTECTIONPURPOSE OF SHUNT REACTOR PROTECTIONTHE PURPOSE OF THE PROTECTION RELAYING IS TO DISCONNECT THE REACTOR AND LIMIT DAMAGE IN CASE OF INTERNAL SHORT CIRCUITS, EARTH FAULTS, INTERTURN FAULTS AND OVER VOLTAGE OR OVER LOAD.THE REACTOR FORMS CERTAIN IMPEDENCE FOR RATED FREQUENCY, AND AS IT IS SHUNT CONNECTED, AS OVER LOAD MAY BE CAUSED BY OVER VOLTAGE OR HARMONICS IN VOLTAGE AND CURRENT.
6. 6. PROTECTION DEVICES INBUILT OR MOUNTED ON REACTORPROTECTION DEVICES INBUILT OR MOUNTED ON REACTORA.A. OIL IMMERSED REACTOR USUALLY HAVE A GAS DETECTOR AND OIL SURGE. DETECTOR (BUCHHOLZ ALARAM & TRIP DEVICES), WHICH ARE EXCELLENT FOR DETECTING INTERNAL FAULTS.DETECTING INTERNAL FAULTS.B.B. TEMPARATURE MONITORS FOR OIL & WINDING PROVIDE GOOD OVER LOAD PROTECTION.C.C. PRESSURE RELIEF DEVICE IS PROVIDED TO SAFE GUARD THE REACTOR FROM HIGH PRESURES.
7.7. REACTOR DIFFERENTIAL PROTECTIONREACTOR DIFFERENTIAL PROTECTIONIT IS WIDELY USED AS INSTANTANEOUS PROTECTION FOR SHORT CIRCUIT FAULTS WITH IN THE DIFFERENTIAL ZONE. THIS IS TREATED AS MAIN-1 PROT FOR REACTOR.IT CAN BE OF HIGH IMPEDENCE TYPE OR OF A SENSITIVE CURRENT STABILISED TYPE. HIGH IMPEDENCE DIFFERENTIAL PROTECTION RELAYS REQUIRE AN EQUAL CT TURNS RATIO ON THE PHASE AND NEUTRAL SIDE. SENSITIVITY IS 5% OF NOMINAL REACTOR CT RATIO ON THE PHASE AND NEUTRAL SIDE. SENSITIVITY IS 5% OF NOMINAL REACTOR CT CURRENT.
8.8. BACKBACK--UP PROTECTIONUP PROTECTIONA VARIETY OF RELAYS ARE AVAILABLE.A.A. OVER CURRENT & EARTH FAULT PROTECTION. ( 50, 50N, 51, 51N, 67, 67N - ANY COMBINATION OF THESE)B.B. UNDER IMPEDENCE / DISTANCE ( Z<)(21R).C.C. NEUTRAL DISPLACEMENT PROTECTION (Un>).
9.9. RESTRICTED EARTH FAULT PROTECTIONRESTRICTED EARTH FAULT PROTECTIONIF, FOR SOME REASON, A SENSITIVE DIFFERENTIAL PROTECTION NOT CHOOSEN A RESTRICTED EARTH FAULT PROTECTION CAN BE UTILISED.
SHUNT REACTOR (BUS & LINE) SHUNT REACTOR (BUS & LINE) ((ONE AND HALF CIRCUIT BREAKER SYSTEM )ONE AND HALF CIRCUIT BREAKER SYSTEM )
1-89 3-89
BUS-1 BUS-2
IL
INTER LOCK FACILITY:WHEN 1-89R CLOSES ONLY
1-89A
11--52CB52CB
1-CT
3-89A
33--52CB52CB
3-CT
2-CT
P1
P1
P1
P2 P2
P21-89R .
WHEN 1-89R CLOSES ONLY PERMIT TO CLOSE 1-89L AND
1-89L OPENS ONLY PERMIT TO OPEN 1-89R.
LINE 1
22--52CB52CB2-89A 2-89B
1-89LUU UUUU UU
UU UU
LINESHUNT
REACTOR
UU UUUU UU
UU UU
BUSSHUNT
REACTOR
.3-89R
UU UUUU UUUU UUUU UU
IL
1-PH NEUTRAL GROUNDING REACTOR
REACTOR BUSHING CT INFORMATIONREACTOR BUSHING CT INFORMATION
CAPACITY OF 400KV REACTORS : 50, 63, 80, 125 MVAR
Sr Sr Sr Sr
NONONONOITEM
SHUNT REACTOR NGR
400KV / LINE SIDE STAR / NEUTRAL SIDE LINE SIDEEARTH SIDE
CORE-1 CORE -2 CORE-3 CORE-4 CORE-5 CORE-1 CORE-2 CORE -3 CORE-4 CORE-1 CORE-2
2000- 2000-
1111 RATIO 200/1 200/1 200/1
2000-
1000-
500/1
2000-
1000-
500/1
200/1 WTI 200/1 200/1 200/1 200/1
NEUTRAN BUSHING CT : BEFORE STAR FORMATION IN RYB PHASES
2222
VKNEE FOR PS & VA FOR
MET200V 200V 200V
1000-500-250V
1000-500-250V 1.0 CL
AND BURDEN
Parameters of W
TI CT for each winding shall be
provided by the contractor
200V 200V 200V 200V
10 – 5 – 10 – 5 BURDEN 10 VA
Parameters of W
TI CT for each winding shall be
provided by the contractor
3333 RCT IN OHMS 1 OHM 1 OHM 1 OHM10 – 5 –
2.5 OHM
10 – 5 – 2.5 OHM
1 OHM 1 OHM 1 OHM 1 OHM
4444CLASS OF ACURACY
PS PS PS PS PS PS PS PS PS
5555 PURPOSE87 R1DIFF1
87 R2 DIFF2
21 R IMP
FOR 21L2 /TEED-2
FOR 21L1 /TEED-1
MET87 R1DIFF1
87 R2DIFF2
64 RREF2
64 RREF1/2
SHUNT REACTOR PROTECTIONSHUNT REACTOR PROTECTION
CORES
ONE & HALF BREAKER
SYSTEM
DOUBLE BUS & TRANSFER
BUS SYSTEM
LINE BUS LINE BUS
400KV SIDE
87R1 – 3Ph, 2Wdg REACTOR DIFFERENTIAL RELAY OF LOW CORE-1
87R1 – 3Ph, 2Wdg REACTOR DIFFERENTIAL RELAY OF LOW IMPEDANCE TYPE.
CORE-287R2 - 3Ph, 3Wdg REACTOR DIFFERENTIAL RELAY OF HIGH
IMPEDANCE TYPE.
CORE-3
21R – 3Ph, REACTOR BACKUP IMPEDANCE RELAY OF SUITABLY SHAPED CHARECRESTICS EITHER SINGLE /
DOUBLE ZONE TYPE.
21L2 87 TEED-2 21L2CORE-4
21L2
(M_CT + T_CT – R_CT)
87 TEED-2
(M_CT, T_CT, R_CT)
21L2
(M_CT+T_CT – R_CT)87 BBC/BB-2
CORE-521L1
(M_CT + T_CT – R_CT)
87 TEED-1
(M_CT, T_CT, R_CT)
21L1
(M_CT + T_CT – R_CT)87 BBM/BB-1
M_CT: Main CT, T_CT: Tie CT, R_CT: Reactor CT
SHUNT REACTOR PROTECTIONSHUNT REACTOR PROTECTION
CORES
ONE & HALF BREAKER
SYSTEM
DOUBLE BUS & TRANSFER
BUS SYSTEM
LINE BUS LINE BUS
STAR / NEUTRAL SIDE
CORE-1 METERING OF REACTOR
CORE-2 WINDING TEMPARETURE OF REACTOR
CORE-387R2 - 3Ph, 3Wdg REACTOR DIFFERENTIAL RELAY OF HIGH
IMPEDANCE TYPE.
CORE-487R1 – 3Ph, 2Wdg REACTOR DIFFERENTIAL RELAY OF LOW
IMPEDANCE TYPE.
NEUTRAL GROUNDING REACTOR SIDENEUTRAL GROUNDING REACTOR SIDE
CORE-1 64 REF1 - - 64 REF2 - -
CORE-2 64 REF1 - - 64 REF 1 / 2 - -
REACTOR BUSHING CT INFORMATIONREACTOR BUSHING CT INFORMATION
LINESHUNT
REACTOR
1-PH NEUTRAL GROUNDING REACTOR
CO
RE
-1
CO
RE
-2
CO
RE
-3
CO
RE
-4
CO
RE
-5
CO
RE
-1
CO
RE
-2
CO
RE
-3
CO
RE
-4
CO
RE
-1
CO
RE
-2
UUUUUUUUUUUUUUUUUUUU
UUUUUUUUUUUUUUUUUUUU UUUUUUUUUUUU
.
UUUUUUUUUUUUUUUUUUUU
UUUUUUUUUUUUUUUUUUUU
UUUUUUUUUUUU
REACTOR BUSHING CT INFORMATIONREACTOR BUSHING CT INFORMATION
BUSSHUNT
REACTOR
CO
RE
-1
CO
RE
-2
CO
RE
-3
CO
RE
-4
CO
RE
-5
CO
RE
-1
CO
RE
-2
CO
RE
-3
CO
RE
-4
UUUUUUUU UUUUUUUUUUUU
UUUUUUUU UUUUUUUUUUUU
.
UUUUUUUU UUUUUUUUUUUU
UUUUUUUU UUUUUUUUUUUU
ONE & HALF BREAKER LINE & BUS SHUNT REACTOR PROTECTION SCHEMEONE & HALF BREAKER LINE & BUS SHUNT REACTOR PROTECTION SCHEME
87BB1
CVT
VBB1
79
25
BFVL1 / VL2
OR VBB2
VBB1
87L 21M2 CVT VL1VL1
BUSBARBUSBAR--11
21M1 VL1
79
25
FEEDER1 / LINE1
BF
VL1 / VBB1
VL2 / VBB2
UUUUUUUU UUUU UUUUUUUU UUUU
87R
64R
OR
21R
UUUUUUUU UUUU
87R
VL1/
VBB1
/VBB
2
87BB2
CVT
VBB279
25VBB2
BF
VL2 / VL1
OR VBB1
BUSBARBUSBAR--22
TEED-2
PROTECTION OF BUS REACTOR
FOR REACTOR PROTECTION & METERING VOLTAGE SELECTION RELAYS FOR BUS-1, BUS-2& LINE ARE PROVIDED .
UUUUUUUU UUUU
64R
VBB1
/VBB
2
21R
TEED-1
LINE/BUS REACTOR DIFFERENTIAL PROTECTION LINE/BUS REACTOR DIFFERENTIAL PROTECTION (LOW IMPEDANCE DIFFERENTIAL PROTECTION)(87R1)(LOW IMPEDANCE DIFFERENTIAL PROTECTION)(87R1)
R-CT
P2P2P2 CT MB
3 3 33S1 3S1 3S1
3S23S2 3S2
CT MB
RET 670RET 670
3 3 3
R-CT
HV BUSHING
CORE-1
CTR: 200/1A
CLASS: PS
1S2 1S2 1S2
1S11S1 1S1
R-CT
STAR BUSHING
CORE-4
CTR: 200/1A
CLASS: PS
P2P2P2
C
DISPLAY
ACTIVE START TRIP
NORMALLYC
E
NORMALLYLOW IMPEDENCE (87R1) DIFFERENTIAL RELAY IS
USED FOR BUS / LINE REACTOR
DIFFERENTIAL PROTECTION
IN CASE OF REACTOR BUSHING CT P2 IS AWAY FROM REACTOR & P1 IS TOWARDS REACTOR
ACTIVE START TRIP
RET 670RET 6703 3 3
R-CT HV
BUSHING CT
CORE-2
CTR: 200/1A
P2P2P2
1S21S21S2
1S11S11S1
LINE/BUS REACTOR DIFFERENTIAL PROTECTION LINE/BUS REACTOR DIFFERENTIAL PROTECTION (HIGH IMPEDANCE DIFFERENTIAL PROTECTION) (87R2)(HIGH IMPEDANCE DIFFERENTIAL PROTECTION) (87R2)
C
E
DISPLAYCLASS: PS
P1P1P1
NORMALLY
3 3 3
R-CT STAR
BUSHING CT
CORE-3
CTR: 200/1A
CLASS: PS
P2P2P2
P1P1P1
3S23S23S2
3S13S13S1
IN CASE OF REACTOR BUSHING CT P2 IS AWAY FROM REACTOR
& P1 IS TOWARDS REACTOR
NORMALLYHIGH IMPEDENCE (87R2) DIFFERENTIAL RELAY IS
USED FOR BUS / LINE REACTOR
DIFFERENTIAL PROTECTION
ACTIVE START TRIP
RET 670RET 6703 3 3
P2P2P2
2S22S22S2
2S12S12S1
LINE/BUS REACTOR REF PROTECTION LINE/BUS REACTOR REF PROTECTION (NGR IS NOT AVAIALBLE)(NGR IS NOT AVAIALBLE)
R-CT HV
BUSHING CT
CORE-2
CTR: 200/1A
NORMALLYHIGH IMPEDENCE
VOLTAGE/CURRENT OPERATED SINGLE
C
E
DISPLAYP1P1P1
CLASS: PS OPERATED SINGLE POLE RELAY IS USED
FOR BUS / LINE REACTOR RESTRICTED
EARTH FAULT PROTECTION.
PRESENTLY NUMERICAL DIFFERENTIAL RELAYS
HAVING IN BUILT FUNCTION OF 2 REF OR
3 3 3
P2P2P2
P1P1P1
4S24S24S2
4S14S14S1
R-CT STAR
BUSHING CT
CORE-3
CTR: 200/1A
CLASS: PS
IN CASE OF REACTOR BUSHING CT P2 IS AWAY FROM REACTOR
& P1 IS TOWARDS REACTOR
FUNCTION OF 2 REF OR 2 SEF PROTECTIONS.
3 3 3
P2P2P2
2S22S22S2
2S12S12S1
LINE REACTOR REF PROTECTION LINE REACTOR REF PROTECTION (NGR IS AVAIALBLE)(NGR IS AVAIALBLE)
R-CT HV
BUSHING CT
CORE-2
CTR: 200/1A
ACTIVE START TRIP
RET 670RET 670NORMALLY
HIGH IMPEDENCEVOLTAGE/CURRENT OPERATED SINGLE
P1P1P1
CLASS: PS
C
E
DISPLAYOPERATED SINGLE
POLE RELAY IS USED FOR BUS / LINE
REACTOR RESTRICTED EARTH FAULT PROTECTION.
PRESENTLY NUMERICAL DIFFERENTIAL RELAYS
HAVING IN BUILT FUNCTION OF 2 REF OR
NGR-CT EARTH
BUSHING CT
CORE-2
CTR: 200/1A
CLASS: PS
IN CASE OF REACTOR BUSHING CT P2 IS AWAY FROM REACTOR
& P1 IS TOWARDS REACTOR
FUNCTION OF 2 REF OR 2 SEF PROTECTIONS.
3
P1
S1
S2
P2
3 3 3
P2P2P2
2S22S22S2
2S12S12S1
LINE REACTOR 2 NOs REF PROTECTIONS LINE REACTOR 2 NOs REF PROTECTIONS (NGR IS AVAIALBLE)(NGR IS AVAIALBLE)
R-CT HV
BUSHING CT
CORE-2
CTR: 200/1A
ACTIVE START TRIP
RET 670RET 670
31S1
1S2
P2
P1P1P1
CLASS: PS
C
E
DISPLAY
NORMALLY
HIGH IMPEDENCE
NGR-CT BUSHING CT
CORE - 1 & 2CTR: 200/1A
CLASS: PS
P1
3 3 3
P2P2P2
P1P1P1
4S24S24S2
4S14S14S1
R-CT STAR
BUSHING CT
CORE-4
CTR: 200/1A
CLASS: PS
HIGH IMPEDENCE
VOLTAGE/CURRENT OPERATED
SINGLE POLE RELAY IS USED
FOR BUS / LINE REACTOR
RESTRICTED EARTH FAULT
PROTECTION.
PRESENTLY NUMERICAL
DIFFERENTIAL RELAYS HAVING
IN BUILT FUNCTION OF 2 REF OR
2 SEF PROTECTIONS.
3
P2
2S2
2S1
P1
REL 670REL 670
IR3 / A311
IY3 / A331
IB3 / A351
P2P2P2 CT MB
VR11 / E111
VY11 / E131
VB11 / E151
LINE/BUS REACTOR B/U IMPEDANCE PROTECTIONLINE/BUS REACTOR B/U IMPEDANCE PROTECTION
R-CT HV
BUSHING CT
C
E
DISPLAY
ACTIVE START TRIP
REL 670REL 6703 3 3
IB3 / A351
IN3 / A371
3S2 3S2 3S2
3S13S1 3S1
VB11 / E151
VN11 / E171BUSHING CT
CORE-3
CTR: 200/1A
CLASS: PS CVT
SELECTION
BUS-1 CVT /
BUS-2 CVT /
LINE CVT
CORE-2
VA : 100
CLASS: 3PE CLASS: 3P
LINE REACTOR PROTECTION FOR LINELINE REACTOR PROTECTION FOR LINE(MAIN(MAIN--1 PROTECTION)1 PROTECTION)
ACTIVE START TRIP
REL 521REL 5213 3 3
IR5 / A511
IY5 / A531
IB5 / A551
IN5 / A571
1-CT
CORE-5
CTR: 2000-1000-500/1A
CLASS: PS
5S4 5S4 5S4
5S25S2 5S2
P2P2P2 CT MB
VR11 / E111
VY11 / E131
VB11 / E151
VN11 / E171
1-CVT
CORE – 1
C
E
DISPLAY
3 3 32-CT
CORE-5
CTR: 2000-1000-500/1A
CLASS: PS
5S4 5S4 5S4
5S25S2 5S2
CORE – 1
100VA
CLASS: 3P
P2P2P2
3 3 3
LR-CT 400KV
CORE-5
CTR: 2000-1000-500/1A
CLASS: PS
P1P1P1
5S2 5S2 5S2
5S45S4 5S4
LINE REACTOR PROTECTION FOR LINELINE REACTOR PROTECTION FOR LINE(MAIN(MAIN--2 PROTECTION)2 PROTECTION)
ACTIVE START TRIP
REL 316REL 3163 3 3
IR4 / A411
IY4 / A431
IB4 / A451
IN4 / A471
1-CT
CORE-4
CTR: 2000-1000-500/1A
CLASS: PS
4S4 4S4 4S4
4S24S2 4S2
P2P2P2 CT MB
VR21 / E211
VY21 / E231
VB21 / E251
VN21 / E271
1-CVT
CORE – 2
C
E
DISPLAY
3 3 32-CT
CORE-4
CTR: 2000-1000-500/1A
CLASS: PS
4S4 4S4 4S4
4S24S2 4S2
CORE – 2
100VA
CLASS: 3P
P2P2P2
3 3 3
LR-CT 400KV
CORE-4
CTR: 2000-1000-500/1A
CLASS: PS
P1P1P1
4S2 4S2 4S2
4S44S4 4S4
BUS REACTOR TEEDBUS REACTOR TEED--1 PROTECTION1 PROTECTION{BAY3&2}{BAY3&2}
3 3 3
3-CT
CORE-5
CTR: 2000-1000-500/1A
CLASS: PS
P2P2P2
5S4 5S4 5S4
5S25S2 5S2
IR5IY5IB5
IN5
C
DISPLAY
ACTIVE START TRIP
RET 670RET 670
3 3 32-CT
CORE-1
CTR: 2000-1000-500/1A
CLASS: PS
P1P1P1
P2P2P2
P1P1P1
1S4 1S4 1S4
1S21S2 1S2
IN5
IR5IY5IB5
IN5
E
3 3 3
BR-RCT
CORE-5
CTR: 2000-1000-500/1A
CLASS: PS
P1P1P1
P1P1P1
P2P2P2
5S4 5S4 5S4
5S25S2 5S2 IT WORKS ON CIRCULATING CURRENT PRINCIPLE AND IT IS
HIGH IMPEDENCE DIFFERENTIAL RELAY. TEED-1 PROTECTION
FOR BAY 2&3 AND THE FOLLOWING CTs & CORES ARE USED 3-
CT(CORE-5), 2-CT(CORE-1) & BR-CT (CORE-5) ARE STARRED
AND CONNECTED TO TEED-1 PROTECTIONIR5IY5IB5
IN5
BUS REACTOR TEEDBUS REACTOR TEED--2 PROTECTION2 PROTECTION{BAY3&2}{BAY3&2}
3 3 3
3-CT
CORE-4
CTR: 2000-1000-500/1A
CLASS: PS
4S4 4S4 4S4
4S24S2 4S2
P2P2P2 CT MB
3 3 32S2 2S2 2S2
2S42S4 2S4
P2P2P2CT MB
RET 670RET 670CLASS: PS
BR-CT
CT MBP2P2P2
2-CT
CORE-2
CTR: 2000-1000-500/1A
CLASS: PS
C
DISPLAY
ACTIVE START TRIP
IT WORKS ON KIRCHOFF’S
3 3 3CORE-4
CTR: 2000-1000-500/1A
CLASS: PS4S2 4S2 4S2
4S44S4 4S4
C
E
IT WORKS ON KIRCHOFF’S CURRENT PRINCIPLE & IT IS PERCENTAGE BIASED LOW IMPEDENCE DIFFERENTIAL RELAY. TEED-2 PROTECTION FOR BAY 2&3 IS THE FOLLOWING CTs & CORES ARE USED. 3-CT(CORE-4), 2-CT(CORE-2) & BR-CT (CORE-4) ARE CONNECTED TO TEED-2 PROTECTION.
3 3 3
IR2 / D211
IY2 / D231
IB2 / D251R-CT STAR
BUSHING CT
CORE-2
2S2 2S2 2S2
2S12S1 2S1
P2P2P2 CT MB
REACTOR BAY CONTROL UNIT (BCU)REACTOR BAY CONTROL UNIT (BCU)
3 3 3
IN2 / D271
CORE-2
CTR: 200/1A
CLASS: 0.2
2S12S1 2S1
VR31 / E311
VY31 / E331VY31 / E331
VB31 / E351
VN31 / E371
BASED ON SELECTION
LINE CVT / BUS-1 CVT / BUS-2 CVT
CORE – 3
100VA
CLASS: 0.2
CARRIER INTERTRIPPING OF LINE SHUNT REACTORCARRIER INTERTRIPPING OF LINE SHUNT REACTORLINE SHUNT REACTOR PROTECTION TRIPPINGS WILL BE USED AS DIRECT TRIPPINGS OF LINE IN LINE SHUNT REACTOR PROTECTION TRIPPINGS WILL BE USED AS DIRECT TRIPPINGS OF LINE IN ADDITION TO OTHER TRIPPINGS. BUS SHUNT REACTOR NEED NOT REQUIRE CARRIER INTER ADDITION TO OTHER TRIPPINGS. BUS SHUNT REACTOR NEED NOT REQUIRE CARRIER INTER TRIPPING FACILITY.TRIPPING FACILITY.
87R1 REACTOR DIFFERENTIAL RELAY
21R REACTOR IMPEDENCE RELAY
ABBABB
NSD 50NSD 50DC +VE
FROM PANEL
LINE PROTECTION COUPLER PANEL-1RET 670
REL 670
87R2/64R RESTRICTED EARTH FAULT RELAY
FROM PANEL
G4AD V9LC 2
DC –VE FROM PANELG4AD V9LC 1
ABBABB
NSD 50NSD 50
LINE PROTECTION COUPLER PANEL-2
REL 670
RET 670
REACTORS INTERNAL FAULTS
87R1 REACTOR DIFFERENTIAL RELAY
GROUP-1/A TRIPPINGS
RET 670
NSD 50NSD 50
DC +VE FROM PANEL
G4AD V9LC 2
DC –VE FROM PANELG4AD V9LC 1
COUPLER PANEL-2
21R REACTOR IMPEDENCE RELAY
87R2/64R RESTRICTED EARTH FAULT RELAY
REACTORS INTERNAL FAULTS
GROUP-2/B TRIPPINGS
REL 670
RET 670
ADDITIONAL AND ADDITIONAL AND SPECIAL FUNCTIONS SPECIAL FUNCTIONS
ADOPTED INADOPTED INADOPTED INADOPTED INONE AND HALF ONE AND HALF
CIRCUIT BREAKERCIRCUIT BREAKERSCHEME SCHEME SCHEME SCHEME
(EVENT LOGGER & DISTURBANCE (EVENT LOGGER & DISTURBANCE RECORDER)RECORDER)
PREPARED BYGOPALA KRISHNA PALEPU
ADE/MRT(PROTECTION)
400KV SUBSTATION: MAMIDIPALLY 400KV SUBSTATION: MAMIDIPALLY EVENT LOGGER EVENTS INFORMATIONEVENT LOGGER EVENTS INFORMATION
19 MAR 2004 13:00:0019 MAR 2004 13:00:00A 13:09:37.090 # 195 400KV SRISAILAMA 13:09:37.090 # 195 400KV SRISAILAM--2 MAIN2 MAIN--2 RAZFE PROT TRIP 2 RAZFE PROT TRIP A 13:09:37.096 # 188 400KV SRISAILAMA 13:09:37.096 # 188 400KV SRISAILAM--2 MAIN2 MAIN--1 REL100 PROT START’Y’ 1 REL100 PROT START’Y’
A 13:09:37.097 # 187 400KV SRISAILAMA 13:09:37.097 # 187 400KV SRISAILAM--2 MAIN2 MAIN--1 REL100 PROT START’R’1 REL100 PROT START’R’A 13:09:37.100 # 181 400KV SRISAILAMA 13:09:37.100 # 181 400KV SRISAILAM--2 MAIN2 MAIN--1 REL100 PROT TRIP1 REL100 PROT TRIPA 13:09:37.104 # 162 400KV SRISAILAMA 13:09:37.104 # 162 400KV SRISAILAM--2 MAIN CB 752 Y2 MAIN CB 752 Y--PH OPENPH OPENA 13:09:37.110 # 196 400KV SRISAILAMA 13:09:37.110 # 196 400KV SRISAILAM--2 MAIN2 MAIN--2 RAZFE CARRIER SEND2 RAZFE CARRIER SEND
A 13:09:37.110 # 170 400KV SRISAILAMA 13:09:37.110 # 170 400KV SRISAILAM--2 AT/F2 AT/F--2 TIE CB 852 B2 TIE CB 852 B--PH OPENPH OPENA 13:09:37.111 # 161 400KV SRISAILAMA 13:09:37.111 # 161 400KV SRISAILAM--2 MAIN CB 752 R2 MAIN CB 752 R--PH OPENPH OPENA 13:09:37.111 # 161 400KV SRISAILAMA 13:09:37.111 # 161 400KV SRISAILAM--2 MAIN CB 752 R2 MAIN CB 752 R--PH OPENPH OPENA 13:09:37.111 # 163 400KV SRISAILAMA 13:09:37.111 # 163 400KV SRISAILAM--2 MAIN CB 752 B2 MAIN CB 752 B--PH OPENPH OPENA 13:09:37.111 # 169 400KV SRISAILAMA 13:09:37.111 # 169 400KV SRISAILAM--2 AT/F2 AT/F--2 TIE CB 852 Y2 TIE CB 852 Y--PH OPENPH OPENA 13:09:37.112 # 168 400KV SRISAILAMA 13:09:37.112 # 168 400KV SRISAILAM--2 AT/F2 AT/F--2 TIE CB 852 R2 TIE CB 852 R--PH OPENPH OPEN
A 13:09:37.113 # 182 400KV SRISAILAMA 13:09:37.113 # 182 400KV SRISAILAM--2 MAIN2 MAIN--1 REL100 CARRIER SEND1 REL100 CARRIER SENDA 13:09:37.126 # 199 400KV SRISAILAMA 13:09:37.126 # 199 400KV SRISAILAM--2 CARRIER PROT CH2 CARRIER PROT CH--2 RECEIVED2 RECEIVEDA 13:09:37.140 # 185 400KV SRISAILAMA 13:09:37.140 # 185 400KV SRISAILAM--2 CARRIER PROT CH2 CARRIER PROT CH--1 RECEIVED1 RECEIVEDN 13:09:37.147 # 195 400KV SRISAILAMN 13:09:37.147 # 195 400KV SRISAILAM--2 MAIN2 MAIN--2 RAZFE PROT TRIP RESET2 RAZFE PROT TRIP RESET
N 13:09:37.148 # 196 400KV SRISAILAMN 13:09:37.148 # 196 400KV SRISAILAM--2 MAIN2 MAIN--2 RAZFE CARRIER SEND RESET2 RAZFE CARRIER SEND RESETN 13:09:37.175 # 187 400KV SRISAILAMN 13:09:37.175 # 187 400KV SRISAILAM--2 MAIN2 MAIN--1 REL100 START ‘R’ RESET1 REL100 START ‘R’ RESETN 13:09:37.176 # 181 400KV SRISAILAMN 13:09:37.176 # 181 400KV SRISAILAM--2 MAIN2 MAIN--1 REL100 PROT TRIP RESET1 REL100 PROT TRIP RESETN 13:09:37.176 # 188 400KV SRISAILAMN 13:09:37.176 # 188 400KV SRISAILAM--2 MAIN2 MAIN--1 REL100 START ‘Y’ RESET1 REL100 START ‘Y’ RESETN 13:09:37.185 # 182 400KV SRISAILAMN 13:09:37.185 # 182 400KV SRISAILAM--2 MAIN2 MAIN--1 REL100 CARRIER SEND RESET1 REL100 CARRIER SEND RESETN 13:09:37.185 # 182 400KV SRISAILAMN 13:09:37.185 # 182 400KV SRISAILAM--2 MAIN2 MAIN--1 REL100 CARRIER SEND RESET1 REL100 CARRIER SEND RESET
N 13:09:37.257 # 199 400KV SRISAILAMN 13:09:37.257 # 199 400KV SRISAILAM--2 CARRIER PROT CH2 CARRIER PROT CH--2 RECEIVED RESET2 RECEIVED RESETN 13:09:37.279 # 185 400KV SRISAILAMN 13:09:37.279 # 185 400KV SRISAILAM--2 CARRIER PROT CH2 CARRIER PROT CH--1 RECEIVED RESET1 RECEIVED RESET19 MAR 2004 14:00:0019 MAR 2004 14:00:00N 14:09:48.702 # 163 400KV SRISAILAMN 14:09:48.702 # 163 400KV SRISAILAM--2 MAIN CB 752 B2 MAIN CB 752 B--PH CLOSEPH CLOSEN 14:09:48.704 # 161 400KV SRISAILAMN 14:09:48.704 # 161 400KV SRISAILAM--2 MAIN CB 752 R2 MAIN CB 752 R--PH CLOSEPH CLOSE
N 14:09:48.720 # 162 400KV SRISAILAMN 14:09:48.720 # 162 400KV SRISAILAM--2 MAIN CB 752 Y2 MAIN CB 752 Y--PH CLOSEPH CLOSEN 14:10:00.903 # 169 400KV SRISAILAMN 14:10:00.903 # 169 400KV SRISAILAM--2 AT/F2 AT/F--2 TIE CB 852 Y2 TIE CB 852 Y--PH CLOSEPH CLOSEN 14:10:00.907 # 168 400KV SRISAILAMN 14:10:00.907 # 168 400KV SRISAILAM--2 AT/F2 AT/F--2 TIE CB 852 R2 TIE CB 852 R--PH CLOSEPH CLOSEN 14:10:00.907 # 170 400KV SRISAILAMN 14:10:00.907 # 170 400KV SRISAILAM--2 AT/F2 AT/F--2 TIE CB 852 B2 TIE CB 852 B--PH CLOSEPH CLOSE
19 MAR 2004 15:00:0019 MAR 2004 15:00:00
R PH VOLTAGE
Y PH VOLTAGE
B PH VOLTAGE
OPEN DELTA VOLTAGE
DIS
TU
RB
AN
CE
RE
CO
RD
ER
DIS
TU
RB
AN
CE
RE
CO
RD
ER
R PH CURRENT
Y PH CURRENT
B PH CURRENT
STAR/NEUTRAL CURRENT
MAIN CB R PH OPENMAIN CB Y PH OPENMAIN CB B PH OPEN
TIE CB R PH OPEN
DIS
TU
RB
AN
CE
RE
CO
RD
ER
DIS
TU
RB
AN
CE
RE
CO
RD
ER
MAIN CB B PH OPENTIE CB R PH OPENTIE CB Y PH OPENTIE CB B PH OPEN
MAIN/TIE CB LBB OPTDDIRECT TRIP CH-1/2 OPTD
BUSBAR PROT OPTDMAIN-1 PROT OPTDMAIN-2 PROT OPTD
OVER VOLTAGE STAGE-1/2 OPTDSTUB PROT-1/2 OPTD
MAIN-1 PROT CARRIER RECEIVEMAIN-2 PROT CARRIER RECEIVE
DF/DT OPTD
EVENT NONAME OF FEEDER
DATE & TIME
DIS
TU
RB
AN
CE
RE
CO
RD
ER
DIS
TU
RB
AN
CE
RE
CO
RD
ER
PREFERRED DISTURBANCE RECORDER PREFERRED DISTURBANCE RECORDER 400 KV LINES400 KV LINES 400 KV TRANSFORMER400 KV TRANSFORMER
ANALOGANALOG CHANNELSCHANNELS1. R-PH VOLTAGE2. Y-PH VOLTAGE3. B-PH VOLTAGE4. OPEN DELTA VOLTAGE5. R-PH CURRENT6. Y-PH CURRENT7. B-PH CURRENT
ANALOGANALOG CHANNELSCHANNELS1. HV R-PH VOLTAGE2. HV Y-PH VOLTAGE3. HV B-PH VOLTAGE4. HV OPEN DELTA VOLTAGE5. LV R-PH VOLTAGE6. LV Y-PH VOLTAGE7. LV B-PH VOLTAGE
DIGITALDIGITAL CHANNELSCHANNELS1. HV MAIN CB R-PH OPEN2. HV MAIN CB Y-PH OPEN3. HV MAIN CB B-PH OPEN4. HV TIE CB R-PH OPEN5. HV TIE CB Y-PH OPEN6. HV TIE CB B-PH OPEN7. LV 220 CB R-PH OPEN
7. B-PH CURRENT8. NEUTRAL/STAR CURRENT
DIGITALDIGITAL CHANNELSCHANNELS1. HV MAIN CB R-PH OPEN2. HV MAIN CB Y-PH OPEN3. HV MAIN CB B-PH OPEN4. HV TIE CB R-PH OPEN5. HV TIE CB Y-PH OPEN6. HV TIE CB B-PH OPEN7. 21 MAIN1 REL 521 OPERATED8. 21 MAIN2 REL 316 OPERATED9. 87 BUSBAR RELAY OPERATED10. MAIN CB A/R OPERATED11. TIE CB A/R OPERATED
7. LV B-PH VOLTAGE8. LV OPEN DELTA VOLTAGE9. HV R-PH CURRENT10. HV Y-PH CURRENT11. HV B-PH CURRENT12. HV NEUTRAL/STAR CURRENT13. LV R-PH CURRENT14. LV Y-PH CURRENT15. LV B-PH CURRENT16. LV NEUTRAL/STAR CURRENT
7. LV 220 CB R-PH OPEN8. LV 220 CB Y-PH OPEN9. LV 220 CB B-PH OPEN10. 87 T1 DIFF RLY OPERATED11. 87 T2 DIFF RLY OPERATED12. HV 67 ABCN OPERATED13. LV 67 ABCN OPERATED14. 51 O/L RLY OPERATED15. NDR RLY OPERATED16. HV 99T OVER FLUX OPTD17. LV 99T OVER FLUX OPTD18. HV 400 BUSBAR OPERATED19. LV 220 BUSBAR OPERATED11. TIE CB A/R OPERATED
12. PSB OPERATED13. SOTF OPERATED14. 27 O/V STG-1/2 OPERATED15. 51 STUB-1/2 OPERATED16. 87HZ / LZ TEED-1/2 OPERATED17. MAIN CB LBB OPERATED18. TIE CB LBB OPERATED19. DIRECT TRIP CH-1/2 TRIP20. 21M1 / 21M2 CARRIER RECEIVE21. 86 GR-A/B RELAY OPERATED22. 67N DEF/TEF RLY OPERATED23. DF/DT RELAY OPERATED
19. LV 220 BUSBAR OPERATED20. HV MAIN CB LBB OPERATED21. HV TIE CB LBB OPERATED22. LV MAIN CB LBB OPERATED23. HV 86 GR-A/B RELAY OPTD24. LV 86 GR-A/B RELAY OPTD25. AT/F 21T UZ RELAY OPERATED
26. OIL TEMP HIGH TRIP27. WNDG TEMP HV/IV/LV TRIP28. BUCHHOLZ MAIN/OLTC TRIP29. PRD 1/ 2 TRIP30. AT/F NEUTRAL CURRENT TRIP
CONFIGUARATION CONFIGUARATION OF CONTROL & OF CONTROL &
RELAY PANELS IN RELAY PANELS IN ONE AND HALFONE AND HALF
CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER SCHEME SCHEME
PREPARED BYGOPALA KRISHNA PALEPU
ADE/MRT(PROTECTION)
CONFIGUARATION OF C & R PANELCONFIGUARATION OF C & R PANEL
BUSBAR PANEL CB RELAY PANELLINE PROTECTION
PANEL
1. BCU
2. BUS-1 V&F LED MFM WITH MODBUS
3. BUS-2 V&F LED MFM WITH MODBUS
4. BUSBAR CENTRAL UNIT
1. BAY CONTROL UNIT
2. BREAKER FAILURE RELAY
3. AUTO RECLOSURE RELAY
4. CHECK SYNCHRONISING RELAY
1. MAIN-1 NUM. DIST. PROT
2. MAIN-2 NUM. DIST. PROT.
3. O/V STAGE-1 (EXT/IN BUILT)
4. O/V STAGE-2 (EXT/IN BUILT)4. BUSBAR CENTRAL UNIT
5. BB OUT OF SERVICE SEL SWITCH
6. BUS-1 ES CMR
7. BUS-2 ES CMR
8. DC-1 HEALTHY INDICATION
9. DC-2 HEALTHY INDICATION
10. BUSBAR PROT AUX RELAYS
11. CLOSING AUX RELAYS
* IN CASE OF DUPLICATE
4. CHECK SYNCHRONISING RELAY
5. CB ALARM RELAYS
6. CB TRIP CKT SUPERVISION RELAYS
7. 3-PH TRIP UNITS 86-GA, 86-GB &
96/50Z
8. 1-PH TRIP RELAYS M1, M2 - 1 2 Nos
9. DIRECT TRIP RECEIVE RELAYS
10. DC SUPERVISION RELAYS
4. O/V STAGE-2 (EXT/IN BUILT)
5. DISTURBANCE RECORDER(EXT/INBUILT)
6. DISTANCE TO FAULT (EXT/ INBUILT)
7. DC SUPERVISION RELAYS
8. TEED-1 PROTECTION
9. TEED-2 PROTECTION
10. STUB-1/2 PROTECTION (EXT/ INBUILT)
11. MAIN-1 CARRIER SEL.SWITCH* IN CASE OF DUPLICATE PROTECTION 2 NOS BUSBAR CENTRAL UNITS ARE AVAILABLE
11. U/V RELAY E/S I/L
12. CB EMERGENCY TNC SWITCH
13. CLOSING AUX RELAYS
14. ENERGY METER WITH TTB
15. PANEL INDICATING LABEL
12. MAIN-2 CARRIER SEL.SWITCH
13. CARRIER RECEIVE RELAYS
14.PANEL INDICATING LABEL
CONFIGUARATION OF C & R PANELCONFIGUARATION OF C & R PANELTRANSFORMER
PROTECTION PANEL
BUS REACTOR
CB RELAY PANEL
LINE / BUS REACTOR
PROTECTION PANEL
1. T/F DIFFERENTIAL PROTECTION-1
2. T/F DIFFERENTIAL PROTECTION-2
3. DIRECTIONAL O/L E/F RELAYS-HV
4. DIRECTIONAL O/L E/F RELAYS-LV
1. BAY CONTROL UNIT
2. BREAKER FAILURE RELAY
3. CB ALARM RELAYS
4. CB TRIP CKT SUPERVISION RELAYS
1. REACTOR DIFFERENTIAL PROT
2. REF PROTECTION RELAY
3. REACTOR IMPEDENCE PROTECTION
4. CVT SELECTION RELAYS4. DIRECTIONAL O/L E/F RELAYS-LV
4. OVER FLUX PROTECTION-HV & LV
5. OVER LOAD PROTECTION
6. VOLTAGE SELECT RELAYS- HV & LV
7. FUSE FAILURE RELAY- HV & LV
8. AUX RELAYS FOR T/F TROBLES
9. CIRCUIT LABEL
4. CB TRIP CKT SUPERVISION RELAYS
5. 3-PH TRIP UNITS 86-GA, 86-GB & 96/50Z
6. DC SUPERVISION RELAYS
7. U/V RELAY E/S I/L
8. CB EMERGENCY TNC SWITCH
9. MFM WITH TTB
10. PANEL INDICATING LABEL
4. CVT SELECTION RELAYS
5. FLAG RELAYS
6. AUX RELAYS
7. TIMERS
8. CIRCUIT LABEL
IN ADDITION TO THE ABOVE THE FOLLOWING PANELS WILL BE AVAILABLE1. CONTROL & RELAY PANEL B/C, B/S, TBC (AS & WHEN REQ)2. COMMON CONTROL PANEL IS PART OF BUSBAR PANEL
I. NOMINCLATURE FOR PANELS ARE NORMALLYMAIN CB C&RPANEL – RLA, TIE CB C&R PANEL – RTB, HV CB C&RPANEL – RTRA, LV CB C&R PANEL – RTRC, LINE PROTECTION PANEL – RLB, ICT PROTECTION PANEL – RTRB, LINE REACTOR PROTECTION PANEL – RLRC, BUS REACTOR PROTECTION PANEL – RBRA, BUS
BAR PANEL – RBB,
400KV & 220KV BUSBAR & COMMON CONTROL PANEL400KV & 220KV BUSBAR & COMMON CONTROL PANEL
4RBB 2 RBB
MFM1 MFM2
� APTRANSCO IS FOLLOWING SINGLE BUS BAR PROTECTION.
� POWERGRID IS FOLLOWING DUPLICATE BUS BAR PROTECTION.
� ABB, AREVA, SIEMENS, TOSHIBA ARE HAVING DISTRIBUTED ARCHITECTURE.
� ABB, AREVA, GE, ERL PHASE, SEL ARE HAVING CENTRALISED ARCHITECTURE.
BCU
MFM1 MFM2
BUSBARCENTRAL UNIT
DC
-1
DC
-289
BB
1
AE
CM
R
89
BB
2
AE
CM
R BusBarAux
relays
BCU
BUSBARCENTRAL UNIT
DC
-1
DC
-2
89
BB
1
AE
CM
R
89
BB
2
AE
CM
R BusBarAux
relays
HAVING CENTRALISED ARCHITECTURE.� LBB IS THE PART OF BUSBAR IS LATEST
CONCEPT.� INCASE OF DISTRIBUTED ARCHITECTURE
BAY/PERIPHERAL UNIT IS DATA AQUSITION UNIT AND COMMUNICATE TO CENTRAL UNIT THROUGH FIBER OPTIC CABLE.
� DISTRIBUTED ARCHITECTURE - LBB IS INBUILT LOGIC.
� CENTRALISED ARCHITECTURE - LBB IS STAND ALONE.STAND ALONE.
FINALLY THE CONCEPT AS FOLLOWS IN FUTURE
� FOR FEEDER : REDUNDANT DISTANCE PROTECTION.
� FOR ICT : REDUNDANT DIFFERENTIAL PROTECTION.
� FOR BUSBAR : REDUNDANT BUSBAR PROTECTION.
400KV LINE + REACTOR CB RELAY & PROTN PANEL400KV LINE + REACTOR CB RELAY & PROTN PANEL
BAY1 BCU
4RLA 4RLB
21L1BAY2 BCU
4RTB24RLRC1/RBR3
87R
75A,B,L
A/R+SC79+25
LBB/ BU
50Z
CB
TROUBLES
& ALARMS
TRIP COIL1 & 2
HEALTHYLEDS
86 GR-A
186R1,Y1,B1
R2,Y2,B2
DC
-1
86 GR-B
286R1,Y1,B1
R2,Y2,B2
DC
-2
CB PB
9650Z
21L2
59-1&2
D/T-1Receive
D/T-2Receive
A/R+SC79+25
LBB/ BU
50Z
CB
TROUBLES
& ALARMS
TRIP COIL1 & 2
HEALTHYLEDS
86 GR-A
186R1,Y1,B1
R2,Y2,B2
DC
-1
86 GR-B
286R1,Y1,B1
R2,Y2,B2
DC
-2
CB PB
50 ZT
64R
Reactor Trouble
Alarms & Trips
21R
Receive
Relays
Receive
Relays
99R
400KV ICT CB RELAY & PROTN PANEL400KV ICT CB RELAY & PROTN PANEL
BAY3 BCU
4RTRA3 4RTRB3
87T1
475A,B,L
275A,B
LV BAY BCU
4RTRC3
BAY2 BCU
4RTB2
LBB/ BU
50Z
CB
TROUBLES
& ALARMS
TRIP COIL1 & 2
HEALTHYLEDS
86 GR-A
DC
-186
GR-B DC
-2
CB PB
InterTrip
Relays
96/50Z
87T2
Transformer Trouble
Alarms & Trips
67HV 67IV
99HV 99IV
LBB/ BU
50Z
CB
TROUBLES
& ALARMS
TRIP COIL1 & 2
HEALTHYLEDS
86 GR-A
DC
-1
86 GR-B D
C-2
CB PB
InterTrip
Relays
96/ 50Z
A/R+SC79+25
LBB/ BU
50Z
CB
TROUBLES
& ALARMS
TRIP COIL1 & 2
HEALTHYLEDS
86 GR-A
186R1,Y1,B1
R2,Y2,B2
DC
-1
86 GR-B
286R1,Y1,B1
R2,Y2,B2
DC
-2
CB PB
50 ZT
MFM
99HV
MFM
220KV FEEDER CB RELAY & PROTN PANEL220KV FEEDER CB RELAY & PROTN PANEL
BAY1 BCU
2RLA1 2RLB1
21L1
75A75B
A/R+SC79+25
LBB/ BU
50Z
CB
TROUBLES
& ALARMS
TRIP COIL1 & 2
HEALTHYLEDS
86 GR-A
186R1,Y1,B1
R2,Y2,B2
DC
-186
GR-B
286R1,Y1,B1
R2,Y2,B2D
C-2
CB PB
TTS96 /50Z
21L2
D/T-1Receive
D/T-2Receive
MFM
Receive
Relays
Receive
Relays
220KV BC, TBC & BS CB RELAY & PROTN PANELS220KV BC, TBC & BS CB RELAY & PROTN PANELS
BC BCU
2RBC
TBC BCU
2RTBC
BS BCU
2RBS
LBB/ BU
50Z
CB
TROUBLES
& ALARMS
TRIP COIL1 & 2
HEALTHYLEDS
86 GR-A
DC
-1
86 GR-B D
C-2
CB PB
LBB/ BU
50Z
96 50Z
LBB/ BU
50Z
CB
TROUBLES
& ALARMS
TRIP COIL1 & 2
HEALTHYLEDS
86 GR-A
186R1,Y1,B1
R2,Y2,B2
DC
-1
86 GR-B
286R1,Y1,B1
R2,Y2,B2
DC
-2
CB PB
96 50Z
A/R+SC79+25
LBB/ BU
50Z
CB
TROUBLES
& ALARMS
TRIP COIL1 & 2
HEALTHYLEDS
86 GR-A
DC
-1
86 GR-B D
C-2
CB PB
LBB/ BU
50Z
96 50Z
CB PB
50/51 A,B
C,N
CB PB
50/51 A,B
C,N
SUBSTATION AUXILIARIES & TERMINAL PANELSSUBSTATION AUXILIARIES & TERMINAL PANELS
BCU1 BCU2
SSAUX
For AC
415V
System-1
For AC
415V
System-2
For DC
220V
System-1
For DC
220V
System-2
AlarmUnit
Base System
ABB Network Partner AG
CE
COM581
AlarmUnit
Hot Standby
Main Server Redunt ServerABB Network Partner AG
CE
COM581
BCU3 BCU4
BCU5 BCU6
BCU7 BCU8
System-1 System-2
For DC
48V
System-1
For DC
48V
System-2
For Air
condition
System
For Fire
Fighting
System
For Diesel
Generator
For fire
& Smoke
Network PartnerSSLTA 88 SRS485M SREDU/MSRS485M
RS232 RS485 RS485
SERVICE
1MRSC60029 1MRSC60028 1MRSC60028 1MRSC60028 1MRSC60028 1MRSC60028 1MRSC60028
Ethernet Switch
CommunicationGateway
Network PartnerSSLTA 88 SRS485M SREDU/MSRS485M
RS232 RS485 RS485
SERVICE
1MRSC60029 1MRSC60028 1MRSC60028 1MRSC60028 1MRSC60028 1MRSC60028 1MRSC60028
Ethernet Switch
Line Printer forAlarm / Event Metering Values
DOT Matrix Printer
Router toALDC/SLDC
BCU9 BCU10
Generator
System
& Smoke
Detector
ABB Network Partner AG
CE
COM581
Surveillancesystem
SUBSTATION AUTOMATION
Base System
ServiceModem
AlarmAlarm
Alarm/EventLine Printer
Au
xil
iary
Ala
rm
An
nu
ncia
tio
nBase System
DM PrinterFor 15 Min
Metering & Trends
HardcopyPrinter +
MFD
GPSMeinberg
COMMUNICATION GATEWAY TO
RCC & ALDC
Engineering & DRwork Station
LAPTOP
2 Ports for RCC & 2 Ports for ALDC/SLDC
Network PartnerSSLTA 88SRS485M SREDU/MSRS485M
RS232 RS485 RS485SERVICE
1MRSC600291MRSC600281MRSC600281MRSC600281MRSC600281MRSC600281MRSC60028
Rugged Com/Equivalent Ethernet Switches forming ‘Redundant Managed switched Ethernet LAN on fiber optic medium Interbay bus
on IEC61850 Communication Gate way with hot standby for RCC and SLDC’ For Control and Protection Relays.
Network PartnerSSLTA 88SRS485M SREDU/MSRS485M
RS232 RS485 RS485SERVICE
1MRSC600291MRSC600281MRSC600281MRSC600281MRSC600281MRSC600281MRSC60028
AlarmUnit
AlarmUnit
Ethernet (TCP/IP)
Printer Server Au
xil
iary
Ala
rm
An
nu
ncia
tio
n
POWER
V1
OVP
LOCKACQR SATELLITE CONTROLLED CLOCK
GPS 166
NORMAL OPERATION
WED 11.12.1996MEZ 11.42.25
SV 24 > SYN
MENUCLRACK
NEXT INC
MEINBERG
Meinberg
ABB Network Partner AG
RCC LDC
RCC & ALDC
DIGITAL
PLCC/
DIGITAL
PLCC/
DIGITAL
PLCC/
?LOCAL
REMOTE
SET
OPERATION
M
M
M
?LOCAL
REMOTE
SET
OPERATION
M
M
M
?LOCAL
REMOTE
SET
OPERATION
M
M
M
?LOCAL
REMOTE
SET
OPERATION
M
M
M
?LOCAL
REMOTE
SET
OPERATION
M
M
M
?LOCAL
REMOTE
SET
OPERATION
M
M
M
12345678
910111213141516
CE
12345678
910111213141516
CE
12345678
910111213141516
CE
12345678
910111213141516
CE
12345678
910111213141516
CE
12345678
910111213141516
CE
CE
910111213141516
910
111213141516
910111213141516
CE
ABB Network Partner AGREL511
CE
ABB Network Partner AG REL531
CE
ABB Network Partner AG REL531
910111213141516
910111213141516
910111213141516
910111213141516
910111213141516
910111213141516
OTH
AVR
HYD
RANEM
EM
EM
EM
EM
EM
EM
EM
EM
PLCC/
OLTE
SYSTEM
CARR
PROT
SYSTEM
CARR
PROT
SYSTEM
CARR
PROT
SYSTEM
CARR
PROT
SYSTEM
CARR
PROT
SYSTEM
CARR
PROT
SYSTEM
PLCC/
OLTE
SYSTEM
PLCC/
OLTE
SYSTEM
OTH
AVR
HYD
RAN
OTH
AVR
HYD
RAN
TRIP LOGICS TRIP LOGICS OF OF OF OF
ONE AND HALF ONE AND HALF CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER
SCHEMESCHEMEPREPARED BY
GOPALA KRISHNA PALEPUADE/MRT(PROTECTION)
GROUPGROUP--A & GROUPA & GROUP--B TRIPPINGSB TRIPPINGSFOR 400KV STATIONS THERE SHALL BE TWO SEPARATE BATTERY SYSTEMS AVAILABLE FORPROTECTION, CONTROL & TRIPPING/CLOSING OPERATIONS. TO OBTAIN REDUNDENCY AND TO BEABLE TO TAKE PROTECTION OUT FOR MAINTANENCE, WHILE EQUIPMENT IS IN SERVICE, THERELAYS ARE ELECTRICALLY AND PHYSICALLY SEGREGATED IN TO TWO GROUPS. GROUPING ISDONE TO THE EXTENT POSSIBLE IN SUCH A WAY THAT EACH GROUP CAN INDEPENDENTLYCARRYOUT PROTECTIVE FUNCTIONS WITH NEAR EQUAL REDUNDENCY. INTER CONNECTION OFTHESE TWO GROUPS SHALL NOT BE GENERALLY BE ATTEMPTED.DISTRIBUTION OF DC SUPPLY SHALL BE DONE BAY WISE TO FEED THE FOLLOWING1. PROTECTION1. PROTECTION2. CB CONTROL3. ISOLATOR / EARTH SWITCH CONTROL4. ANNUNCIATION / INDICATION
LINE PROTECTIONLINE PROTECTION TRANSFORMER PROTECTIONTRANSFORMER PROTECTION REACTOR PROTECTIONREACTOR PROTECTION
GROUPGROUP--AAMAIN-1 : 21L1: LINE PROTECTION
M1 BUILT IN FUNCTIONSTEED-1 PROTECTION (87 TEED1)OVER VOLTAGE STAGE-1 PROT(59L1)
GROUPGROUP--AAMAIN1: 87T1 : ICT DIFF PROTN
B/U : 67HV: ICT HV BACKUP RELAYB/U : 21T: ICT B/U IMP RELAYT/F HV OVERFLUX RELAYOIL TEMP HIGH TRIP
GROUPGROUP--AAMAIN1: 87R1 : REACTOR DIFF PROT
B/U : 21R: REACTOR B/U IMP RELAYOIL TEMP HIGH TRIPPRESURE RELIEF TRIP
GROUPGROUP--BBDIRECT TRIP CHANNEL-1 RECEIVED
GROUPGROUP--BBMAIN-2 : 87L2 : LINE PROTECTIONM2 BUILT IN FUNCTIONSTEED-2 PROTECTION (87 TEED2)OVER VOLTAGE STAGE-2 PROT
(59L2)DIRECT TRIP CHANNEL-2 RECEIVED
GROUPGROUP--BBBBLBB/BFR RELAY
BUSBAR PROTECTION
PRESURE RELIEF TRIP
TERITIARY DELTA WNDG NDR PROT
GROUPGROUP--BBMAIN2 : 87T2: ICT DIFF PROTNB/U : 67LV: ICT LV BACKUP RELAYB/U : 51O/C: ICT NCT B/U RELAY
T/F LV OVERFLUX RELAYOVER LOAD PROT (ALARM ONLY)BUCHHOLZ TRIPOLTC BUCHHOLZ TRIPWINDING TEMP HIGH TRIP
LOW/ HIGH OIL LEVEL TRIP
GROUPGROUP--BBMAIN2: 87R2 : REACTOR DIFF PROT
BUCHHOLZ TRIPWINDING TEMP HIGH TRIPLOW/ HIGH OIL LEVEL TRIPFIRE PROTECTION TRIP
MAIN CB FOR LINE (1MAIN CB FOR LINE (1--52CB)TRIPPING LOGICS52CB)TRIPPING LOGICS
PROTECTION
RELAY
SY
MB
OL
GR
OU
P
OU
TP
UT
MAIN-1 PROTECTION 21 L1 A 1-PH X X X X X X X
INIT
IATE
M_C
B 1P
H TR
IP U
NIT
GR-
A
INIT
IATE
M_C
B 3P
H TR
IP U
NIT
GR-
A
INIT
IATE
M_C
B 1P
H TR
IP U
NIT
GR-
B
INIT
IATE
M_C
B 3P
H TR
IP U
NIT
GR-
B
INIT
IATE
T_C
B 1P
H TR
IP U
NIT
GR-
A
INIT
IATE
T_C
B 3P
H TR
IP U
NIT
GR-
A
INIT
IATE
T_C
B 1P
H TR
IP U
NIT
GR-
B
INIT
IATE
T_C
B 3P
H TR
IP U
NIT
GR-
B
START
M_C
B A/R
REL
AY
START
T_C
B A/R
REL
AY
BLOC
K M
_CB
A/R
REL
AY
BLOC
K T
_CB
A/R
REL
AY
MAIN
-1/M
AIN
-2 C
ARR
IER
SEND
INIT
IATE
ALA
RM
INIT
IATE
SCA
DA (D
R & S
OE)
DIRE
CT T
RIP
CARR
IER
SEND
INIT
IATE
400
KV B
/B P
ROT
MAIN-1 PROTECTION 21 L1 A 1-PH X X X X X X X
MAIN-2 PROTECTION 21 L2 B 1-PH X X X X X X X
SOTF, PSB IN BUILT FUNCTIONS OF DISTANCE SCHEME
OVER VOLTAGE
STAGE-1 & STAGE-2
(BUILT – IN 21 M1)
59 L1 & L2 A 3-PH X X X X X X X
OVER VOLTAGE
STAGE-1 & STAGE-2
(BUILT – IN 21 M2)
59 L1 & L2 B 3-PH X X X X X X X
STUB, TOC, BOC,
TEF, DEF,
(BUILT- IN 21M1)
A 3-PH X X X X X X X
(BUILT- IN 21M1)
STUB, TOC, BOC,
TEF, DEF,
(BUILT- IN 21M2)
B 3-PH X X X X X X X
TEED PROT-1 87T HZ A 3-PH X X X X X X X
TEED PROT-2 87T LZ B 3-PH X X X X X X X
DIRECT TRIP CH-1 RECD A 3-PH X X X X
DIRECT TRIP CH-2 RECD B 3-PH X X X X
M_CB BFR / LBB PROT B 3-PH X X X
T_CB BFR / LBB PROT B 3-PH X X
MAIN CB FOR LINE (1MAIN CB FOR LINE (1--52 CB) TRIPPING LOGICS52 CB) TRIPPING LOGICS
PROTECTION
RELAY
SY
MB
OL
GR
OU
P
OU
TP
UT
AUTO RECLOSURE RELAY 1-PH & 3-
INIT
IATE
T_C
B A/R
PRI
ORIT
Y
CLOS
E M
AIN
CB
TO S
CADA
(DR
& S
OE)
INIT
IATE
M_C
B T
RIP
COIL
-1
INIT
IATE
M_C
B T
RIP
COIL
-2
START
LBB
/BFR
M_C
B
89LE
C L
OSE
PERM
ISSI
ON
INIT
IATE
ALA
RM
AUTO RECLOSURE RELAY
(BUILT IN 21M1 & 21M2)79 A/R A&B
1-PH & 3-PH
X X X X
SYNC CHECK RELAY
(BUILT IN 21M1 & 21M2)25 SYNC A&B 3-PH X X X X
1-PH TRIP UNIT GR-A 186 A 1-PH X X X
3-PH TRIP UNIT GR-A 86 GR A A 3-PH X X X X X
1-PH TRIP UNIT GR-B 286 B 1-PH X X X
3-PH TRIP UNIT GR-B 86 GR B B 3-PH X X X X X
TRIP SIGNAL FROM 400KV
BUSBAR PROTECTION96 BB 3-PH X X X
LINE UNDER VOLTAGE RELAY 27 UV X
TIE CB TRIPPING LOGICSTIE CB TRIPPING LOGICS
PROTECTION
RELAY
SY
MB
OL
GR
OU
P
OU
TP
UT
INIT
IATE
M_C
B 1P
H TR
IP U
NIT
GR-
A
INIT
IATE
M_C
B 3P
H TR
IP U
NIT
GR-
A
INIT
IATE
M_C
B 1P
H TR
IP U
NIT
GR-
B
INIT
IATE
M_C
B 3P
H TR
IP U
NIT
GR-
B
INIT
IATE
T_C
B 1P
H TR
IP U
NIT
GR-
A
INIT
IATE
T_C
B 3P
H TR
IP U
NIT
GR-
A
INIT
IATE
T_C
B 1P
H TR
IP U
NIT
GR-
B
INIT
IATE
T_C
B 3P
H TR
IP U
NIT
GR-
B
INIT
IATE
ALA
RM
INIT
IATE
SCA
DA (D
R & S
OE)
DIRE
CT T
RIP
CARR
IER
SEND
INIT
IATE
M_C
B 1P
H TR
IP U
NIT
GR-
A
INIT
IATE
M_C
B 3P
H TR
IP U
NIT
GR-
A
INIT
IATE
M_C
B 1P
H TR
IP U
NIT
GR-
B
INIT
IATE
M_C
B 3P
H TR
IP U
NIT
GR-
B
INIT
IATE
T_C
B TR
IPCO
IL-1
& C
OIL-
2
START
LBB
/BFR
OF
T_CB
CLOS
E T_
CB
T_CB BFR / LBB PROT 50 ZT B 3-PH X X X X X
M_CB BFR / LBB PROT
(152 CB & 352 CB)50 Z B 3-PH X X X X
AUTO RECLOSURE RELAY79
A/R
A
&
B
1-PH &
3-PH
X X X
INIT
IATE
M_C
B 1P
H TR
IP U
NIT
GR
INIT
IATE
M_C
B 3P
H TR
IP U
NIT
GR
INIT
IATE
M_C
B 1P
H TR
IP U
NIT
GR
INIT
IATE
M_C
B 3P
H TR
IP U
NIT
GR
INIT
IATE
T_C
B 1P
H TR
IP U
NIT
GR
INIT
IATE
T_C
B 3P
H TR
IP U
NIT
GR
INIT
IATE
T_C
B 1P
H TR
IP U
NIT
GR
INIT
IATE
T_C
B 3P
H TR
IP U
NIT
GR
INIT
IATE
ALA
RM
INIT
IATE
SCA
DA (D
R & S
OE)
DIRE
CT T
RIP
CARR
IER
SEND
INIT
IATE
M_C
B 1P
H TR
IP U
NIT
GR
INIT
IATE
M_C
B 3P
H TR
IP U
NIT
GR
INIT
IATE
M_C
B 1P
H TR
IP U
NIT
GR
INIT
IATE
M_C
B 3P
H TR
IP U
NIT
GR
152
252
152
152
152
252
252
252
352
352
352
352
INIT
IATE
T_C
B TR
IPCO
IL
START
LBB
/BFR
OF
T_CB
252
252
CLOS
E T_
CB25
2
SYNC CHECK RELAY 25 3-PH X X X
1-PH TRIP UNIT GR-A 186 A 1-PH X X
3-PH TRIP UNIT GR-A 86A A 3-PH X X X X
1-PH TRIP UNIT GR-B 286 B 1-PH X X
3-PH TRIP UNIT GR-B 86B B 3-PH X X X X
DIRECT TRIP CH-1 RECD A 3-PH X
DIRECT TRIP CH-2 RECD B 3-PH X
MAIN CB FOR AT/F (3MAIN CB FOR AT/F (3--52CB)TRIPPING LOGICS52CB)TRIPPING LOGICS
PROTECTION
RELAY
SY
MB
OL
GR
OU
P
OU
TP
UT
DIFFERENTIAL RELAY 87T(LZ) A 3-PH X X X X X X
INIT
IATE
M_C
B 3P
H TR
IP U
NIT
GR-
A
INIT
IATE
M_C
B 3P
H TR
IP U
NIT
GR-
B
INIT
IATE
T_C
B 3P
H TR
IP U
NIT
GR-
A
INIT
IATE
T_C
B 3P
H TR
IP U
NIT
GR-
B
INIT
IATE
ALA
RM
INIT
IATE
SCA
DA (
SOE)
INTE
R TR
IP C
IRCU
IT H
V & L
V
INIT
IATE
400
KV B
/B P
ROT
INIT
IATE
LV_
CB 3
PH T
RIP
UNIT
GR-
A
INIT
IATE
LV_
CB 3
PH T
RIP
UNIT
GR-
B
INIT
IATE
M_C
B TR
IP C
OIL-
1
INIT
IATE
M_C
BTRI
P CO
IL-2
INIT
IATE
220
KV B
/B P
ROT
START
M_C
B LB
B/BF
R RE
LAY
START
LV_
CB L
BB/B
FR R
ELAY
INIT
IATE
LV_
CB T
RIP
COIL
-1
INIT
IATE
LV_
CBTR
IP C
OIL-
2
DIFFERENTIAL RELAY 87T(LZ) A 3-PH X X X X X X
HV BACKUP PROTECTION 67 ABCN A 3-PH X X X X X X
HV OVER FLUX PROT 99T HV A 3-PH X X X X X X
OVER LOAD RELAY 51 O/L A 3-PH X X X X X X
HV PROT TRIP UNIT GR-A & B 86 GR-A/B A/B 3-PH X X X X X X X
REF PROTECTION 64T(HZ) B 3-PH X X X X X X
TEED PROT-1 / 2 87T HZ/LZ A/B 3-PH X X X X X X X X X X X
STUB PROT 50 STUB A 3-PH X X X X X X
AT/F TROUBLE TRIP HV & LV 86 GR-A/B A/B 3-PH X X X X X X X X X
AT/F TROUBLE ALRM X X
M_CB BFR / LBB PROT 50Z B 3-PH X X X X X X
T_CB BFR / LBB PROT 50ZT B 3-PH X X X X X X
LV_CB BFR / LBB PROT 50Z B 3-PH X X X X X X X
400KV B/B PROT 87 BB 96 3-PH X X X X X
220KV B/B PROT 87 BB 96 3-PH X X X X X X
LV BACKUP PROTECTION 67 ABCN B 3-PH X X X X X X
LV OVER FLUX PROT 99T LV B 3-PH X X X X X X
TERI NEUTRAL DISP PROT 151N A 3-PH X X X X X X
LV PROT TRIP UNIT GR-A & B 86 GR-A/B A/B 3-PH X X X X X X X
PROTECTION TRIP SCHEMEPROTECTION TRIP SCHEME
8686--AAMTR/MTR/HSTRHSTR
8686--AAMTR/MTR/HSTRHSTR
8686--AAMTR/MTR/HSTRHSTR
ABB Network Partner AG REL531
21 MAIN 1
C
ABB Network Partner AG REL531
87 T LZ
BUS-1 BUS-2
1-52CB 3-52CB2-52CB
HSTRHSTR
ABBABBREL521REL521
8686--BBMTR/MTR/
8686--BBMTR/MTR/
HSTRHSTR
8686--BBMTR/MTR/
HSTRHSTR
TRIP COIL-1 TRIP COIL-1 TRIP COIL-1
TRIP COIL-2 TRIP COIL-2 TRIP COIL-2
C
E
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ABB Network Partner AG REC 316*4
21 MAIN 2
C
E
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ABB Network Partner AG REC 316*4
87 T HZ
REL521REL521MAINMAIN--11MTR/MTR/HSTRHSTR
MTR/MTR/HSTRHSTR
MTR/MTR/HSTRHSTR
8686--A : GROUPA : GROUP--A MASTER TRIP RELAY / HIGH SPEED TRIP RELAY A MASTER TRIP RELAY / HIGH SPEED TRIP RELAY 8686--B : GROUPB : GROUP--B MASTER TRIP RELAY / HIGH SPEED TRIP RELAYB MASTER TRIP RELAY / HIGH SPEED TRIP RELAY
C
E
C
E
MAINMAIN--1/ MAIN1/ MAIN--22ZONEZONE--1 & SINGLE PHASE FAULT1 & SINGLE PHASE FAULT
ACTIVE START TRIP
REL 521REL 521INITIATE MAIN CB GR-A 1-PH TRIP UNIT ( INTURN IT WILL TRIP 1-POLE )
INITIATE TIE CB GR-A 1-PH TRIP UNIT ( INTURN IT WILL TRIP 1-POLE )
START MAIN CB AUTO RECLOSURE
START TIE CB AUTO RECLOSURE
C
E
DISPLAY
REL 316REL 316
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER
CARRIER SEND
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
INITIATE MAIN CB GR-B 1-PH TRIP UNIT ( INTURN IT WILL TRIP 1-POLE )
TO LBB/BFR INITIATION
C
E
DISPLAY
ACTIVE START TRIP
REL 316REL 316 INITIATE TIE CB GR-B 1-PH TRIP UNIT ( INTURN IT WILL TRIP 1-POLE )
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER
START MAIN CB AUTO RECLOSURE
START TIE CB AUTO RECLOSURE
CARRIER SEND
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
TO LBB/BFR INITIATION
AUTO RECLOSUREAUTO RECLOSURE�� CONDITIONS REQUIRED FOR A/R OPERATIONCONDITIONS REQUIRED FOR A/R OPERATION1.1. CB CLOSE CONDITION.CB CLOSE CONDITION.2.2. TIME LAPSED MORE THAN RECLAIM TIME.TIME LAPSED MORE THAN RECLAIM TIME.
3.3. OPERATING PRESSURE OF CB SUITABLE FOR AUTORECLOSUREOPERATING PRESSURE OF CB SUITABLE FOR AUTORECLOSUREOPERATION.OPERATION.
4.4. DC SUPPLY TO AUTORECLOSURE SHOULD BE AVAILABLE. DC SUPPLY TO AUTORECLOSURE SHOULD BE AVAILABLE. 5.5. PREPARE 3PREPARE 3--PH TRIP RELAY SHOULD BE RELEASED CONDITION.PH TRIP RELAY SHOULD BE RELEASED CONDITION.5.5. PREPARE 3PREPARE 3--PH TRIP RELAY SHOULD BE RELEASED CONDITION.PH TRIP RELAY SHOULD BE RELEASED CONDITION.
6.6. NO BLOCKING SIGNAL TO AUTORECLOSURE RELAY.NO BLOCKING SIGNAL TO AUTORECLOSURE RELAY.7.7. POLE DISTURBANCE RELAY TIME SHOULD BE MORE THANPOLE DISTURBANCE RELAY TIME SHOULD BE MORE THAN
TWICE OF DEAD TIME OF AUTO RECLOSURE.TWICE OF DEAD TIME OF AUTO RECLOSURE.
7.7. CARRIER FAIL SIGNAL SHOULD NOT COME AT BOTH ENDS.CARRIER FAIL SIGNAL SHOULD NOT COME AT BOTH ENDS.8.8. CARRIER SWITCH SHOULD BE IN SERVICE CONDITION.CARRIER SWITCH SHOULD BE IN SERVICE CONDITION.9.9. SINGLE PHASE & ZONESINGLE PHASE & ZONE--1 FAULT ONLY.1 FAULT ONLY.
�� AUTO RECLOSURE OPERATIONAUTO RECLOSURE OPERATION1.1. TRIP MAIN CB SINGLE POLE.TRIP MAIN CB SINGLE POLE.1.1. TRIP MAIN CB SINGLE POLE.TRIP MAIN CB SINGLE POLE.2.2. TRIP TIE CB SINGLE POLE.TRIP TIE CB SINGLE POLE.
3.3. CLOSE MAIN CB AFTER DEAD TIME.CLOSE MAIN CB AFTER DEAD TIME.4.4. IF A/R SUCCESS FOR MAIN CB THEN AFTER SUPPLEMENTARY TIME IF A/R SUCCESS FOR MAIN CB THEN AFTER SUPPLEMENTARY TIME
DELAY CLOSE TIE CB.(NORMALLY SUPPLEMENTARY TIME DELAY IS DEAD DELAY CLOSE TIE CB.(NORMALLY SUPPLEMENTARY TIME DELAY IS DEAD TIME)TIME)
5.5. IF A/R UNSUCCESS THEN TRIP MAIN & TIE CBs.IF A/R UNSUCCESS THEN TRIP MAIN & TIE CBs.6.6. IF MAIN CB OPEN CONDITION, THEN NO SUPPLEMENTARY DELAY TIME IF MAIN CB OPEN CONDITION, THEN NO SUPPLEMENTARY DELAY TIME
FOR TIE A/R. IT WILL OPERATE ITs OWN DEAD TIME.FOR TIE A/R. IT WILL OPERATE ITs OWN DEAD TIME.
MAINMAIN--1/ MAIN1/ MAIN--22ZONEZONE--1 & TWO / THREE PHASE FAULT1 & TWO / THREE PHASE FAULT
ACTIVE START TRIP
REL 521REL 521INITIATE MAIN CB GR-A 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
INITIATE TIE CB GR-A 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB AUTO RECLOSURE
BLOCK TIE CB AUTO RECLOSURE
C
E
DISPLAY
REL 316REL 316
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER
CARRIER SEND
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
INITIATE MAIN CB GR-B 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
TO LBB/BFR INITIATION
C
E
DISPLAY
ACTIVE START TRIP
REL 316REL 316 INITIATE TIE CB GR-B 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER
BLOCK MAIN CB AUTO RECLOSURE
BLOCK TIE CB AUTO RECLOSURE
CARRIER SEND
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
TO LBB/BFR INITIATION
MAINMAIN--1/ MAIN1/ MAIN--22ZONEZONE--2 & 1 / 2 / 3 PHASE FAULT2 & 1 / 2 / 3 PHASE FAULT
ACTIVE START TRIP
REL 521REL 521INITIATE MAIN CB GR-A 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
INITIATE TIE CB GR-A 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB AUTO RECLOSURE
BLOCK TIE CB AUTO RECLOSURE
CARRIER SIGNAL RECEIVED
& ZONE-2 STARTER IS PICKUP CONDITION
C
E
DISPLAY
REL 316REL 316
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION CAME)
INITIATE MAIN CB GR-B 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
IS PICKUP CONDITION TO LBB/BFR INITIATION
C
E
DISPLAY
ACTIVE START TRIP
REL 316REL 316 INITIATE TIE CB GR-B 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER
BLOCK MAIN CB AUTO RECLOSURE
BLOCK TIE CB AUTO RECLOSURE
CARRIER SEND ( IF PUTT OR2 SCHEME SELECTED )
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
CARRIER SIGNAL RECEIVED
& ZONE-2 STARTER IS PICKUP CONDITION
TO LBB/BFR INITIATION
MAINMAIN--1/ MAIN1/ MAIN--22ZONEZONE-- 3/4/5 & 1 / 2 / 3 PHASE FAULT3/4/5 & 1 / 2 / 3 PHASE FAULT
ACTIVE START TRIP
REL 521REL 521INITIATE MAIN CB GR-A 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
INITIATE TIE CB GR-A 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB AUTO RECLOSURE
BLOCK TIE CB AUTO RECLOSURE
C
E
DISPLAY
REL 316REL 316
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION CAME)
INITIATE MAIN CB GR-B 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
TO LBB/BFR INITIATION
C
E
DISPLAY
ACTIVE START TRIP
REL 316REL 316 INITIATE TIE CB GR-B 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER
BLOCK MAIN CB AUTO RECLOSURE
BLOCK TIE CB AUTO RECLOSURE
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
TO LBB/BFR INITIATION
DISTANCE SCHEME TRIPPING OUTPUTSDISTANCE SCHEME TRIPPING OUTPUTS
ACTIVE START TRIP
REL 521REL 521
MAIN CBMAIN CB TIE CBTIE CBCO CO
186 R
186 Y
TO TRIP COIL-1
TO TRIP COIL-2
186 R
186 Y
TO TRIP COIL-1
TO TRIP COIL-2
C
E
DISPLAY
REL 316REL 316
186 Y
186 B
TO TRIP COIL-1
TO TRIP COIL-2
TO TRIP COIL-1
TO TRIP COIL-2
186 Y
186 B
TO TRIP COIL-1
TO TRIP COIL-2
TO TRIP COIL-1
TO TRIP COIL-2
CO286 R
CO286 R
TO TRIP COIL-1
C
E
DISPLAY
ACTIVE START TRIP
REL 316REL 316
286 Y
286 B
TO TRIP COIL-1
TO TRIP COIL-2
TO TRIP COIL-1
TO TRIP COIL-2
TO TRIP COIL-1
TO TRIP COIL-2
286 Y
286 B
TO TRIP COIL-1
TO TRIP COIL-2
TO TRIP COIL-1
TO TRIP COIL-2
TO TRIP COIL-1
TO TRIP COIL-2
TRANSFORMER PROTECTIONTRANSFORMER PROTECTION(DIFFERENCIAL & REF / 3(DIFFERENCIAL & REF / 3--PH HZ DIFF PROTECTION)PH HZ DIFF PROTECTION)
ACTIVE START TRIP
RET 521RET 521INITIATE 400KV MAIN CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 400KV TIE CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
87 T187 T1
INITIATE 220KV MAIN CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV TBC CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
C
E
DISPLAY
RET 316RET 316
TO EVENT RECORDER ( SOE/ SCADA )
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
87 T187 T1(LZ)(LZ)
INITIATE 400KV MAIN CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
C
E
DISPLAY
ACTIVE START TRIP
RET 316RET 316
TO EVENT RECORDER ( SOE/ SCADA )
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
87 T287 T2(LZ/HZ)(LZ/HZ)
INITIATE 400KV TIE CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV MAIN CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV TBC CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
TRANSFORMER PROTECTIONTRANSFORMER PROTECTION( BACKUP DIRECTIONAL O/L & E/F PROTECTION FOR HV & LV)( BACKUP DIRECTIONAL O/L & E/F PROTECTION FOR HV & LV)
ACTIVE START TRIP
REF 610REF 610INITIATE 400KV MAIN CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 400KV TIE CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
67 HV 67 HV INITIATE 220KV MAIN CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV TBC CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
C
E
DISPLAY
REX 521REX 521
TO EVENT RECORDER ( SOE/ SCADA )
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
67 HV 67 HV ABCNABCN
INITIATE 400KV MAIN CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
C
E
DISPLAY
ACTIVE START TRIP
REX 521REX 521
TO EVENT RECORDER ( SOE/ SCADA )
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
67 LV67 LVABCNABCN
INITIATE 400KV TIE CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV MAIN CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV TBC CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
MAIN LBBMAIN LBB
C
DISPLAY
ACTIVE START TRIP
REQ 650REQ 650
INITIATE BUSBAR PROTECTION ( INTURN IT WILL TRIP CONNECTED BUS CBs)
INITIATE TIE CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB & TIE CB AUTO RECLOSURE
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
CLOSE INTERLOCK OF MAIN CB & TIE CB
DIRECT TRANSFER TRIP-1 CARRIER SEND TO OTHER END
DIRECT TRANSFER TRIP-2 CARRIER SEND TO OTHER END
INITIATIONINITIATION
1-PH TRIP RELAYS OFMAIN-1 PROTECTION
1-PH TRIP RELAYS OFMAIN-2 PROTECTION
86-GR-AMASTER TRIP RELAY
C
E
ACTIVE START TRIP
REQ 650REQ 650
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER
INITIATE ALARM (ANNUNCIATION COME)
INITIATE MAIN CB 86-GR-B 3-PH TRIP UNIT (TRIP BAY1 CB 3-POLES )
INITIATE MAIN CB 86-GR-B 3-PH TRIP UNIT ( TRIP BAY3 CB 3-POLES )
BLOCK MAIN CB OF BAY1 & BAY3 AUTO RECLOSURE
BLOCK TIE CB AUTO RECLOSURE
86-GR-BMASTER TRIP RELAY
96 BB BUSBAR RELAY
TIE LBBTIE LBBINITIATIONINITIATION
1-PH TRIP RELAYS OFMAIN-1 PROTECTION
OF LINE-1(BAY1) & LINE-2 (BAY3)
1-PH TRIP RELAYS OF
C
E
DISPLAY
ACTIVE START TRIP
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER (BAY1 & BAY3)
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
CLOSE INTERLOCK OF TIE CB
BLOCK TIE CB AUTO RECLOSURE
CLOSE INTERLOCK OF MAIN CB OF BAY1 & BAY 31-PH TRIP RELAYS OFMAIN-2 PROTECTION
OF LINE-1 (BAY1) &LINE-2 (BAY 3)
86-GR-AMASTER TRIP RELAY
86-GR-BMASTER TRIP RELAY
DIRECT TRANSFER TRIP-1 CARRIER SEND TO BAY1 & BAY3 LINES
DIRECT TRANSFER TRIP-2 CARRIER SEND TO BAY1 & BAY3 LINES
MAIN LBBMAIN LBB
C
DISPLAY
ACTIVE START TRIP
RAICARAICA
INITIATE BUSBAR PROTECTION ( INTURN IT WILL TRIP CONNECTED BUS CBs)
INITIATE TIE CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
TO EVENT RECORDER ( SOE/ SCADA )
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
CLOSE INTERLOCK OF MAIN CB & TIE CB
INTER TRIP TO 220KV LV MAIN CB
INTER TRIP TO 220KV LV TBC CB
INITIATIONINITIATION
86-GR-AMASTER TRIP RELAY
86-GR-BMASTER TRIP RELAY
96 BB BUSBAR RELAY
C
E
ACTIVE START TRIP
RAICARAICA
TO EVENT RECORDER ( SOE/ SCADA )
INITIATE MAIN CB 86-GR-B 3-PH TRIP UNIT (TRIP BAY1 CB 3-POLES )
INITIATE MAIN CB 86-GR-B 3-PH TRIP UNIT ( TRIP BAY3 CB 3-POLES )
BLOCK MAIN CB OF BAY1 AUTO RECLOSURE
BLOCK TIE CB AUTO RECLOSURE
TIE LBBTIE LBBINITIATIONINITIATION
1-PH TRIP RELAYS OFMAIN-1 PROTECTION
OF LINE-1(BAY1)
1-PH TRIP RELAYS OF
C
E
DISPLAY
ACTIVE START TRIP
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER (BAY1)
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
CLOSE INTERLOCK OF TIE CB
BLOCK TIE CB AUTO RECLOSURE
CLOSE INTERLOCK OF MAIN CB OF BAY1 & BAY 31-PH TRIP RELAYS OFMAIN-2 PROTECTION
OF LINE-1 (BAY1)
86-GR-AMASTER TRIP RELAY
86-GR-BMASTER TRIP RELAY
DIRECT TRANSFER TRIP-1 CARRIER SEND TO BAY1 & BAY3 LINES
DIRECT TRANSFER TRIP-2 CARRIER SEND TO BAY1 & BAY3 LINES
LBB IS PART OF DISTRIBUTED ARCHITECTURELBB IS PART OF DISTRIBUTED ARCHITECTURE
186-R
186-Y
186-B
286-R
286-Y
286-B
MAIN CB (LINE SIDE) LBB & BUSBAR INPUT & OUTPUTSMAIN CB (LINE SIDE) LBB & BUSBAR INPUT & OUTPUTS
M_CB OPEN
M_CB CLOSE
BUS ISO OPEN
BUS ISO CLOSE
T_CB OPEN
T_CB CLOSE
TO DIRECT TRIP SEND CH1 (LBB OPTD)
TO DIRECT TRIP SEND CH2 (LBB OPTD)
TO DIRECT TRIP SEND CH1 (BB OPTD)
TO DIRECT TRIP SEND CH2 (BB OPTD)
TO TIE LBB TRIP RELAY (50ZTX/96TIE)
TO TC-1T_CB CLOSE
86-A
86-B
96-A
96-B
CB
CL
OS
EP
UL
SE
96 H
IGH
SP
EE
DM
AS
TE
R T
RIP
RE
LA
Y
TO TC-2
TO TC-1
TO TC-2TIE LBB OPTD
TO 21 L1 (DR)
TO 21 L2 (DR)
TO CLOSE I/L
TO BAY UNIT
TO BCU (SOE & A/R BLK)
LBB IS PART OF DISTRIBUTED ARCHITECTURELBB IS PART OF DISTRIBUTED ARCHITECTURE
186-R
186-Y
186-B
286-R
286-Y
286-B
TIE CB LBB INPUT & OUTPUTSTIE CB LBB INPUT & OUTPUTS
ABB Network Partner AG
TO M_T LBB TRIP RELAY (96 M_T CB)
T_CB OPEN
T_CB CLOSE
T_ ISO1 OPEN
T_ISO1 CLOSE
T_ISO2 OPEN
T_ISO2 CLOSE
TO DIRECT TRIP SEND CH1 (LINE RE SIDE)
TO DIRECT TRIP SEND CH2 (LINE RE SIDE)
TO INTER TRIP SEND CH1 (ICT LV SIDE)
TO M_L LBB TRIP RELAY (96 M_L CB)
TO TC-1
TO TC-2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ABB Network Partner AG REL 316*4
C
E
C
E
TO INTER TRIP SEND CH2(ICT LV SIDE)
86-A
86-B
50Z
TX
CB
CL
OS
EP
UL
SE
96 H
IGH
SP
EE
DM
AS
TE
R T
RIP
RE
LA
Y
TO TC-2
TO TC-1
TO TC-2M_L LBB OPTD
TO 21 L1 (DR M_L)
TO 21 L2 (DR M_T)
TO CLOSE I/L
TO BAY UNIT
TO BCU (SOE & A/R BLK)
M_T LBB OPTD
TO 87 T1 (DR M_L)
TO 87 T2 (DR M_T)
LBB IS PART OF DISTRIBUTED ARCHITECTURELBB IS PART OF DISTRIBUTED ARCHITECTUREMAIN CB (ICT SIDE) LBB & BUSBAR INPUT & OUTPUTSMAIN CB (ICT SIDE) LBB & BUSBAR INPUT & OUTPUTS
M_CB OPEN
M_CB CLOSE
BUS ISO OPEN
BUS ISO CLOSE
T_CB OPEN
T_CB CLOSE
TO INTERTRIP TRIP SEND CH1 (LBB OPTD)
TO INTERTRIP SEND CH2 (LBB OPTD)
TO INTERTRIP SEND CH1 (BB OPTD)
TO INTERTRIP SEND CH2 (BB OPTD)
TO TIE LBB TRIP RELAY (50ZTX/96TIE)
TO TC-1
86-A
86-B
96-A
96-B
CB
CL
OS
EP
UL
SE
96 H
IGH
SP
EE
DM
AS
TE
R T
RIP
RE
LA
Y
TO TC-2
TO TC-1
TO TC-2TIE LBB OPTD
TO 87 T1 (DR)
TO 87 T2 (DR)
TO CLOSE I/L
TO BAY UNIT
TO BCU (SOE)
LV M_LBB OPTD
LV T_LBB OPTD
LBB IS PART OF DISTRIBUTED ARCHITECTURELBB IS PART OF DISTRIBUTED ARCHITECTURE
186-R
186-Y
186-B
286-R
286-Y
286-B
MAIN CB (DBT SYSTEM) LBB & BUSBAR INPUT & OUTPUTSMAIN CB (DBT SYSTEM) LBB & BUSBAR INPUT & OUTPUTS
M_CB OPEN
M_CB CLOSE
BUS1 ISO OPEN
BUS1 ISO CLOSE
TO DIRECT TRIP SEND CH1 (LBB OPTD)
TO DIRECT TRIP SEND CH2 (LBB OPTD)
TO DIRECT TRIP SEND CH1 (BB OPTD)
TO DIRECT TRIP SEND CH2 (BB OPTD)
TO TBC LBB TRIP RELAY (96TBC)
TO TC-1
BUS2 ISO OPEN
BUS2 ISO CLOSE
BUS3 ISO OPEN
86-A
86-B
96-A
96-B
CB
CL
OS
EP
UL
SE
96 H
IGH
SP
EE
DM
AS
TE
R T
RIP
RE
LA
Y
TO TC-2
TO TC-1
TO TC-2TBC LBB OPTD
TO 21 L1 (DR)
TO 21 L2 (DR)
TO CLOSE I/L
TO BAY UNIT
TO BCU (SOE & A/R BLK)
BUS3 ISO CLOSE
BUS BAR PROTECTION BUS BAR PROTECTION
DISPLAY
ACTIVE START TRIP
REB 500REB 500
INITIATE ALL CBs TRIP UNITS CONNECTED TO THIS BUS AND OPERATE.
TO TRIP COIL-1 CONCERNED BAY CB
TO TRIP COIL-2 CONCERNED BAY CB
TO CLOSE CIRCUIT INTERLOCK OF CONCERN CB
DIRECT TRIP SEND CHANNEL-1 TO OTHER END
DIRECT TRIP SEND CHANNEL-2 TO OTHER END
C
E
DISPLAY
REB 670REB 670
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER OF MAIN-1
INITIATE ALARM (ANNUNCIATION COME)
TO LBB/BFR INITIATION
TO DISTURBANCE RECORDER OF MAIN-2
FROM LBB/BFR TO BUS BAR TRIPPING
INITIATE ALL CBs TRIP UNITS CONNECTED TO THIS BUS AND OPERATE.
TO TRIP COIL-1 CONCERNED BAY CB
TO TRIP COIL-2 CONCERNED BAY CB
C
E
DISPLAY
ACTIVE START TRIP
REB 670REB 670
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER OF MAIN-1
TO TRIP COIL-2 CONCERNED BAY CB
TO CLOSE CIRCUIT INTERLOCK OF CONCERN CB
DIRECT TRIP SEND CHANNEL-1 TO OTHER END
DIRECT TRIP SEND CHANNEL-2 TO OTHER END
INITIATE ALARM (ANNUNCIATION COME)
TO LBB/BFR INITIATION
TO DISTURBANCE RECORDER OF MAIN-2
FROM LBB/BFR TO BUS BAR TRIPPING
BUSBARBUSBAR--1 PROTECTION TRIPPING SCHEME1 PROTECTION TRIPPING SCHEMEHIGH SPEEDHIGH SPEEDTRIP RELAYTRIP RELAY
FOR FOR
11--52 CB52 CB
TO CLOSE CKT INTERLOCKTO BLOCK A/RTO TRIP COIL-1TO TRIP COIL-2DIRECT TRIP SEND CH-1DIRECT TRIP SEND CH-2TO DISTURBENCE RECORDER
11--52 CB PANEL52 CB PANEL
TO CLOSE CKT INTERLOCKTO BLOCK A/RTO TRIP COIL-1TO TRIP COIL-2DIRECT TRIP SEND CH-1
44--52 CB PANEL52 CB PANELHIGH SPEEDHIGH SPEEDTRIP RELAYTRIP RELAY
FOR FOR
44--52 CB52 CB
11--52 CB PANEL52 CB PANEL
TRIP FROM 50 LBB
TO START 50 LBB
44--52 CB PANEL52 CB PANEL
TRIP FROM 50 LBB
TO START 50 LBBDIRECT TRIP SEND CH-2TO DISTURBENCE RECORDER
TO CLOSE CKT INTERLOCKTO BLOCK A/RTO TRIP COIL-1TO TRIP COIL-2DIRECT TRIP SEND CH-1DIRECT TRIP SEND CH-2TO DISTURBENCE RECORDER
77--52 CB PANEL52 CB PANEL
TO CLOSE CKT INTERLOCKTO BLOCK A/RTO TRIP COIL-1TO TRIP COIL-2DIRECT TRIP SEND CH-1DIRECT TRIP SEND CH-2TO DISTURBENCE RECORDER
1010--52CB PANEL52CB PANEL
1313--52 CB PANEL52 CB PANEL
44--52 CB52 CB
HIGH SPEEDHIGH SPEEDTRIP RELAYTRIP RELAY
FOR FOR
77--52 CB52 CB
HIGH SPEEDHIGH SPEEDTRIP RELAYTRIP RELAY
FOR FOR
1010--52 CB52 CB
TO START 50 LBB
77--52 CB PANEL52 CB PANEL
TRIP FROM 50 LBB
TO START 50 LBB
1010--52 CB PANEL52 CB PANEL
TRIP FROM 50 LBB
TO START 50 LBB
TO CLOSE CKT INTERLOCKTO BLOCK A/RTO TRIP COIL-1TO TRIP COIL-2DIRECT TRIP SEND CH-1DIRECT TRIP SEND CH-2TO DISTURBENCE RECORDER
1313--52 CB PANEL52 CB PANEL
TO CLOSE CKT INTERLOCKTO BLOCK A/RTO TRIP COIL-1TO TRIP COIL-2DIRECT TRIP SEND CH-1DIRECT TRIP SEND CH-2TO DISTURBENCE RECORDER
1616--52 CB PANEL52 CB PANEL
HIGH SPEEDHIGH SPEEDTRIP RELAYTRIP RELAY
FOR FOR
1313--52 CB52 CB
HIGH SPEEDHIGH SPEEDTRIP RELAYTRIP RELAY
FOR FOR
1616--52 CB52 CB
TO START 50 LBB
1313--52 CB PANEL52 CB PANEL
TRIP FROM 50 LBB
TO START 50 LBB
1616--52 CB PANEL52 CB PANEL
TRIP FROM 50 LBB
TO START 50 LBB
+VE BUSBAR PANEL
BUSBARBUSBAR--2 PROTECTION TRIPPING SCHEME2 PROTECTION TRIPPING SCHEMEHIGH SPEEDHIGH SPEEDTRIP RELAYTRIP RELAY
FOR FOR
33--52 CB52 CB
TO CLOSE CKT INTERLOCKTO BLOCK A/RTO TRIP COIL-1TO TRIP COIL-2DIRECT TRIP SEND CH-1DIRECT TRIP SEND CH-2TO DISTURBENCE RECORDER
33--52 CB PANEL52 CB PANEL
TO CLOSE CKT INTERLOCKTO BLOCK A/RTO TRIP COIL-1TO TRIP COIL-2DIRECT TRIP SEND CH-1
66--52 CB PANEL52 CB PANELHIGH SPEEDHIGH SPEEDTRIP RELAYTRIP RELAY
FOR FOR
66--52 CB52 CB
33--52 CB PANEL52 CB PANEL
TRIP FROM 50 LBB
TO START 50 LBB
66--52 CB PANEL52 CB PANEL
TRIP FROM 50 LBB
TO START 50 LBBDIRECT TRIP SEND CH-2TO DISTURBENCE RECORDER
TO CLOSE CKT INTERLOCKTO BLOCK A/RTO TRIP COIL-1TO TRIP COIL-2DIRECT TRIP SEND CH-1DIRECT TRIP SEND CH-2TO DISTURBENCE RECORDER
99--52 CB PANEL52 CB PANEL
TO CLOSE CKT INTERLOCKTO BLOCK A/RTO TRIP COIL-1TO TRIP COIL-2DIRECT TRIP SEND CH-1DIRECT TRIP SEND CH-2TO DISTURBENCE RECORDER
1212--52CB PANEL52CB PANEL
1515--52 CB PANEL52 CB PANEL
66--52 CB52 CB
HIGH SPEEDHIGH SPEEDTRIP RELAYTRIP RELAY
FOR FOR
99--52 CB52 CB
HIGH SPEEDHIGH SPEEDTRIP RELAYTRIP RELAY
FOR FOR
1212--52 CB52 CB
TO START 50 LBB
99--52 CB PANEL52 CB PANEL
TRIP FROM 50 LBB
TO START 50 LBB
1212--52 CB PANEL52 CB PANEL
TRIP FROM 50 LBB
TO START 50 LBB
TO CLOSE CKT INTERLOCKTO BLOCK A/RTO TRIP COIL-1TO TRIP COIL-2DIRECT TRIP SEND CH-1DIRECT TRIP SEND CH-2TO DISTURBENCE RECORDER
1515--52 CB PANEL52 CB PANEL
TO CLOSE CKT INTERLOCKTO BLOCK A/RTO TRIP COIL-1TO TRIP COIL-2DIRECT TRIP SEND CH-1DIRECT TRIP SEND CH-2TO DISTURBENCE RECORDER
1818--52 CB PANEL52 CB PANEL
HIGH SPEEDHIGH SPEEDTRIP RELAYTRIP RELAY
FOR FOR
1515--52 CB52 CB
HIGH SPEEDHIGH SPEEDTRIP RELAYTRIP RELAY
FOR FOR
1818--52 CB52 CB
TO START 50 LBB
1515--52 CB PANEL52 CB PANEL
TRIP FROM 50 LBB
TO START 50 LBB
1818--52 CB PANEL52 CB PANEL
TRIP FROM 50 LBB
TO START 50 LBB
+VE BUSBAR PANEL
STUB PROTECTION STUB PROTECTION
ACTIVE START TRIP
REL 521REL 521INITIATE MAIN CB 86-GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE TIE CB 86-GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB AUTO RECLOSURELINE /AT/FISOLATOR
BLOCK TIE CB AUTO RECLOSURE
C
E
DISPLAY
REL 316REL 316
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
INITIATE MAIN CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
ISOLATOR
OPENS
CLOSE INTERLOCK OF TIE CB
CLOSE INTERLOCK OF MAIN CB
C
E
DISPLAY
ACTIVE START TRIP
REL 316REL 316 INITIATE TIE CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER
BLOCK MAIN CB AUTO RECLOSURE
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
CLOSE INTERLOCK OF TIE CB
BLOCK TIE CB AUTO RECLOSURE
CLOSE INTERLOCK OF MAIN CB
LINE /AT/FISOLATOR
OPENS
TEED PROTECTION TEED PROTECTION
ACTIVE START TRIP
RET 521RET 521INITIATE MAIN CB 86-GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE TIE CB 86-GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB AUTO RECLOSURE
BLOCK TIE CB AUTO RECLOSURE87 T187 T1
C
E
DISPLAY
RET 670RET 670
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
INITIATE MAIN CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
CLOSE INTERLOCK OF TIE CB
CLOSE INTERLOCK OF MAIN CB
87 T187 T1(HZ)(HZ)
C
E
DISPLAY
ACTIVE START TRIP
RET 670RET 670 INITIATE TIE CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER
BLOCK MAIN CB AUTO RECLOSURE
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
CLOSE INTERLOCK OF TIE CB
BLOCK TIE CB AUTO RECLOSURE
CLOSE INTERLOCK OF MAIN CB
87 T287 T2(LZ)(LZ)
MAINMAIN--1/ MAIN1/ MAIN--22OVER VOLTAGE STAGEOVER VOLTAGE STAGE--1 1
ACTIVE START TRIP
REL 521REL 521INITIATE MAIN CB 86-GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE TIE CB 86-GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB & TIE CB AUTO RECLOSURE
DIRECT TRANSFER TRIP-1 CARRIER SEND TO OTHER END
110% OF V4 SECS FOR
FEEDER-15 SECS FOR
C
E
DISPLAY
REL 316REL 316
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER
DIRECT TRANSFER TRIP-2 CARRIER SEND TO OTHER END
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
INITIATE MAIN CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
5 SECS FOR FEEDER-2
CLOSE INTERLOCK OF MAIN CB & TIE CB
C
E
DISPLAY
ACTIVE START TRIP
REL 316REL 316 INITIATE TIE CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER
BLOCK MAIN CB & TIE CB AUTO RECLOSURE
DIRECT TRANSFER TRIP-1 CARRIER SEND TO OTHER END
DIRECT TRANSFER TRIP-2 CARRIER SEND TO OTHER END
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
110% OF V4 SECS FOR
FEEDER-15 SECS FOR FEEDER-2
CLOSE INTERLOCK OF MAIN CB & TIE CB
OVER VOLTAGE STAGEOVER VOLTAGE STAGE--2 2
C
DISPLAY
ACTIVE START TRIP
REU 521REU 521INITIATE MAIN CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE TIE CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB & TIE CB AUTO RECLOSURE
DIRECT TRANSFER TRIP-1 CARRIER SEND TO OTHER END
DIRECT TRANSFER TRIP-2 CARRIER SEND TO OTHER END
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
120% OF V20m SECS
CLOSE INTERLOCK OF MAIN CB & TIE CB
C
E
REU 521REU 521
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER (MAIN-1 & MAIN-2)
INITIATE ALARM (ANNUNCIATION COME)
UNDER VOLTAGE RELAY UNDER VOLTAGE RELAY
C
E
DISPLAY
ACTIVE START TRIP
REU 521REU 521
LINE EARTH SWITCH CLOSE PERMISSION ONLY.1O% OF V
CARRIER TRIPPING SCHEMES(TELEPROTECTION)CARRIER TRIPPING SCHEMES(TELEPROTECTION)
DETAILSDETAILS PERMISSIVE TRIPPINGPERMISSIVE TRIPPING DIRECT TRIPPINGDIRECT TRIPPING
CHANNELCHANNEL--1 1
SENDSEND
MAINMAIN--11 PROTECTIONPROTECTION ::
IT SENDS SIGNAL PARALLEL VIA
PLCC PROTECTION COUPLER PANEL-1 AS A MAIN CHANNEL &
PLCC PROTECTION COUPLER PANEL-2 AS A ALTERNATE
CHANNEL..
HERE CHANNEL-1 & CHANNEL-2 SIGNALS ARE MAIN & ALTERNATE CHANNEL
1. TIE CB OPEN CONDITION + MAIN CB REMOTE HAND TRIP GIVEN.
2. MAIN CB OPEN CONDITION + TIE CB REMOTE HAND TRIP GIVEN.
3. TIE CB OPEN CONDITION + 87 BUSBAR-1 OPERATED.
4. MAIN CB OPEN CONDITION + 87 BUSBAR-2 OPERATEDCHANNEL..
MAINMAIN--22 PROTECTIONPROTECTION ::
IT SENDS SIGNAL PARALLEL VIA
PLCC PROTECTION COUPLER PANEL-2 AS A MAIN CHANNEL &
PLCC PROTECTION COUPLER PANEL-1 AS A ALTERNATE
CHANNEL.
4. MAIN CB OPEN CONDITION + 87 BUSBAR-2 OPERATED
(FOR HALF DIA ONLY).
5. MAIN CB 50 LBB/BFR OPERATED.
6. TIE CB 50 LBB/BFR OPERATED.
7. 59L1 OVER VOLTAGE STAGE-1 OPERATED.
8. 59L2 OVER VOLTAGE STAGE-2 OPERATED.
9. 87 TEED-1 PROTECTION OPERATED
10. 87 TEED-2 PROTECTION OPERATED
CHANNELCHANNEL--2 2
SENDSEND
CHANNELCHANNEL--1 1
RECEIVERECEIVE
MAINMAIN--11 PROTECTIONPROTECTION ::
IT RECEIVES SIGNAL PARALLEL VIA
1. TO 86-A MASTER TRIP RELAY (HIGH SPEED TRIP RELAY) FOR MAIN CB.
2. TO 86-A MASTER TRIP RELAY (HIGH SPEED TRIP RELAY) FOR TIE CB. RECEIVERECEIVE PLCC PROTECTION COUPLER PANEL-1 AS A MAIN CHANNEL &
PLCC PROTECTION COUPLER PANEL-2 AS A ALTERNATE
CHANNEL.
MAINMAIN--22 PROTECTIONPROTECTION ::
IT RECEIVES SIGNAL PARALLEL VIA
PLCC PROTECTION COUPLER PANEL-2 AS A MAIN CHANNEL &
PLCC PROTECTION COUPLER PANEL-1 AS A ALTERNATE
CHANNEL.
2. TO 86-A MASTER TRIP RELAY (HIGH SPEED TRIP RELAY) FOR TIE CB.
CHANNELCHANNEL--2 2
RECEIVERECEIVE1. TO 86-B MASTER TRIP RELAY (HIGH SPEED TRIP RELAY) FOR MAIN CB.
2. TO 86-B MASTER TRIP RELAY (HIGH SPEED TRIP RELAY) FOR TIE CB.
CARRIER TRIPPING SCHEMES(TELEPROTECTION)CARRIER TRIPPING SCHEMES(TELEPROTECTION)
C
E
ABB Network Partner AG REL531
C
E
ABB Network Partner AG REL531 CARRIERPROTECTION
PANEL-1
PT SEND
PT RECEIVE
PT SEND
PT RECEIVE
CARRIERPROTECTION
PANEL-1
PT SEND
PT RECEIVE
PT SEND
PT RECEIVEDIRECT TRIP DIRECT TRIP
21 M1 – REL 521 21 M1 – REL 521
1
2
3
9
10
11
ABB Network Partner AG REC 316*4
1
2
3
9
10
11
ABB Network Partner AG REC 316*4
PT RECEIVE
DT SEND
DT RECEIVE
CARRIERPROTECTION
PANEL-2
PT RECEIVE
DT SEND
DT RECEIVE
CARRIERPROTECTION
PANEL-2
DIRECT TRIP SEND CH-1
MAIN CB 86-A
TIE CB 86-A
DIRECT TRIP SEND CH-1
MAIN CB 86-A
TIE CB 86-A
ONE ENDONE END OTHER ENDOTHER END
21 M2REL 316
21 M2REL 316
C
E
3
4
5
6
7
8
11
12
13
14
15
16
C
E
3
4
5
6
7
8
11
12
13
14
15
16
PANEL-2
PT SEND
PT RECEIVE
PT SEND
PT RECEIVE
DT SEND
DT RECEIVE
PANEL-2
PT SEND
PT RECEIVE
PT SEND
PT RECEIVE
DT SEND
DT RECEIVE
DIRECT TRIP SEND CH-2
MAIN CB 86-B
TIE CB 86-B
DIRECT TRIP SEND CH-2
MAIN CB 86-B
TIE CB 86-B PT : PERMISSIVE PROTECTION TRANSFER TRIPDT : DIRECT TRANSFER TRIP
DIRECT TRANSFER TRIP DIRECT TRANSFER TRIP CHANNEL CHANNEL –– 1 / 2 RECEIVED 1 / 2 RECEIVED
ACTIVE START TRIP
85 LO X185 LO X1INITIATE MAIN CB 86-GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE TIE CB 86-GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB AUTO RECLOSUREDIRECT TRIP CHANNEL-1
BLOCK TIE CB AUTO RECLOSURE
C
E
DISPLAY
85 LO X285 LO X2
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
INITIATE MAIN CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
CHANNEL-1
RECEIVED
CLOSE INTERLOCK OF TIE CB
CLOSE INTERLOCK OF MAIN CB
C
E
DISPLAY
ACTIVE START TRIP
85 LO X285 LO X2 INITIATE TIE CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER
BLOCK MAIN CB AUTO RECLOSURE
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
DIRECT TRIPCHANNEL-2
RECEIVED.
CLOSE INTERLOCK OF TIE CB
BLOCK TIE CB AUTO RECLOSURE
CLOSE INTERLOCK OF MAIN CB
TRANSFORMER PROTECTION TRANSFORMER PROTECTION ( OVER FLUX PROTECTION FOR HV & LV)( OVER FLUX PROTECTION FOR HV & LV)
ACTIVE START TRIP
RALKRALKINITIATE 400KV MAIN CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 400KV TIE CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
99T HV99T HVINITIATE 220KV MAIN CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV TBC CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
C
E
DISPLAY
RATUBRATUB
TO EVENT RECORDER ( SOE/ SCADA )
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
99T HV99T HV
INITIATE 400KV MAIN CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
C
E
DISPLAY
ACTIVE START TRIP
RATUBRATUB
TO EVENT RECORDER ( SOE/ SCADA )
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
99T LV99T LV
INITIATE 400KV TIE CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV MAIN CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV TBC CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
TRANSFORMER PROTECTIONTRANSFORMER PROTECTION
ACTIVE START TRIP
RXIG 21RXIG 21INITIATE 400KV MAIN CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 400KV TIE CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
51 O/L51 O/LINITIATE 220KV MAIN CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV TBC CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
C
E
DISPLAY
RAEDK1RAEDK1
TO EVENT RECORDER ( SOE/ SCADA )
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
51 O/L51 O/L
INITIATE 400KV MAIN CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
C
E
DISPLAY
ACTIVE START TRIP
RAEDK1RAEDK1
TO EVENT RECORDER ( SOE/ SCADA )
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
NDRNDR
INITIATE 400KV TIE CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV MAIN CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV TBC CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
OVER VOLTAGE (LINE) AND OVER FLUX(ICT ) OVER VOLTAGE (LINE) AND OVER FLUX(ICT ) PROTECTION TRIP SCHEMEPROTECTION TRIP SCHEME
8686--AAMTR/MTR/HSTRHSTR
8686--AAMTR/MTR/HSTRHSTR
8686--AAMTR/MTR/HSTRHSTR
ABBABB
O/V O/V –– 11
O/V O/V –– 22
ABBABBRALKRALK
O/FO/F-- HVHV
(BAY 1&2) (BAY 2&3 / HV)
BUS-1 BUS-2
1-52CB 3-52CB2-52CB
ABBABBREL521REL521MAINMAIN--11
8686--BBMTR/MTR/HSTRHSTR
8686--BBMTR/MTR/HSTRHSTR
8686--BBMTR/MTR/HSTRHSTR
ABBABBO/V O/V –– 11
O/V O/V –– 22
TRIP COIL-1 TRIP COIL-1 TRIP COIL-1
TRIP COIL-2 TRIP COIL-2 TRIP COIL-2
(BAY 1&2)
ABBABBRATUBRATUBO/FO/F-- LVLV
(BAY LV)
LV - CB8686--BBMTR/MTR/HSTRHSTR
8686--AAMTR/MTR/HSTRHSTR
TRIP COIL-2 TRIP COIL-1
OVER VOLTAGE STAGE-1 & STAGE-2 ARE IN BUILT FUNCTIONS OF MAIN-1
& MAIN-2 LINE DISTANCE RELAYS.
HV OVER FLUX IS INBUILT FUNCTION OF MAIN-1 ICT DIFFERENTIAL RELAYLV OVER FLUX IS INBUILT FUNCTION OF MAIN-2 ICT DIFFERENTIAL RELAY
8686--GA & 86 GB MASTER TRIP / HIGH SPEED GA & 86 GB MASTER TRIP / HIGH SPEED TRIP LOCKOUT RELAY OPERATIONTRIP LOCKOUT RELAY OPERATION
8686--GAGAMASTERMASTER
TRIP /TRIP /HIGH HIGH
8686--GAGAMASTERMASTER
TRIP /TRIP /HIGH HIGH
2
M
AIN
CB
T
RIP
CO
IL
2
M
AIN
CB
T
RIP
CO
IL --
11T
RIP
CO
ILT
RIP
CO
IL
OVER VOLTAGE STAGE-1
(INBUILT MAIN-1)
DIRECT TRIP CHANNEL-1
RECEIVED
SOTF PROTECTION
8686--GBGBMASTERMASTER
HIGH HIGH SPEEDSPEEDTRIPTRIP
RELAYRELAY
8686--GBGBMASTERMASTER
HIGH HIGH SPEEDSPEEDTRIPTRIP
RELAYRELAY
2
M
AIN
CB
T
RIP
CO
IL
2
M
AIN
CB
T
RIP
CO
IL
TR
IP C
OIL
TR
IP C
OIL
--1 T
IE C
B T
RIP
CO
IL
1 T
IE C
B T
RIP
CO
IL
OVER VOLTAGE STAGE-1
( IN BUILT MAIN-2 )
DIRECT TRIP CHANNEL-2
RECEIVED
SOTF PROTECTION
(INBUILT MAIN-1)
SOTF PROTECTION
DEF,TOC, BOC, STUB
(INBUILT MAIN-1)
TEED-1 PROTECTION
MASTERMASTERTRIP /TRIP /HIGH HIGH
SPEEDSPEEDTRIPTRIP
RELAYRELAY
MASTERMASTERTRIP /TRIP /HIGH HIGH
SPEEDSPEEDTRIPTRIP
RELAYRELAY
TR
IP C
OIL
TR
IP C
OIL
--2
M
AIN
CB
T
RIP
CO
IL
2
M
AIN
CB
T
RIP
CO
IL
1 T
IE C
B T
RIP
CO
IL
1 T
IE C
B T
RIP
CO
IL --22
SOTF PROTECTION
( IN BUILT MAIN-2 )
OVER VOLTAGE STAGE-2
DEF, TOC, BOC, STUB
( IN BUILT MAIN-2 )
MAIN LBB OPERATED
TIE LBB OPERATED
TEED-2 PROTECTION
8686--GA & 86 GB MASTER TRIP / HIGH SPEED GA & 86 GB MASTER TRIP / HIGH SPEED TRIP LOCKOUT RELAY OPERATIONTRIP LOCKOUT RELAY OPERATION
8686--GAGAMASTERMASTER
TRIP /TRIP /HIGH HIGH
8686--GAGAMASTERMASTER
TRIP /TRIP /HIGH HIGH
2
M
AIN
CB
T
RIP
CO
IL
2
M
AIN
CB
T
RIP
CO
IL --
11T
RIP
CO
ILT
RIP
CO
IL
T/F DIFFERENTIAL RELAY
87 T
B/U O/C & E/F PROTN RLY
67 ABCN
INTER TRIP FROM LV SIDE
8686--GBGBMASTERMASTER
HIGH HIGH SPEEDSPEEDTRIPTRIP
RELAYRELAY
8686--GBGBMASTERMASTER
HIGH HIGH SPEEDSPEEDTRIPTRIP
RELAYRELAY
2
M
AIN
CB
T
RIP
CO
IL
2
M
AIN
CB
T
RIP
CO
IL
TR
IP C
OIL
TR
IP C
OIL
--1 T
IE C
B T
RIP
CO
IL
1 T
IE C
B T
RIP
CO
IL
RESTRICTED EARTH FAULT
RELAY 64 REF/T
INTER TRIP FROM LV SIDE
INTER TRIP FROM LV SIDE
ICT TROUBLES GR-B
ICT TROUBLES GR-A
PROTECTION TRIP
ICT HV OVER FLUX RELAY
MASTERMASTERTRIP /TRIP /HIGH HIGH
SPEEDSPEEDTRIPTRIP
RELAYRELAY
MASTERMASTERTRIP /TRIP /HIGH HIGH
SPEEDSPEEDTRIPTRIP
RELAYRELAY
TR
IP C
OIL
TR
IP C
OIL
--2
M
AIN
CB
T
RIP
CO
IL
2
M
AIN
CB
T
RIP
CO
IL
1 T
IE C
B T
RIP
CO
IL
1 T
IE C
B T
RIP
CO
IL --22
ICT TROUBLES GR-B
PROTECTION TRIP
STUB RELAY 50ST
MAIN LBB OPERATED
TIE LBB OPERATED
ICT LV OVER FLUX RELAY
INTER TRIP FROM TBC LBB
& MANUAL TRIP OF 220KV
MASTER TRIP RELAYS MASTER TRIP RELAYS HIGH SPEED TRIP RELAYSHIGH SPEED TRIP RELAYS
LOCKOUT RELAYSLOCKOUT RELAYS
8686--GAGAMASTERMASTER
PUSH BUTTON FOR RESETTING.TO CLOSING INTERLOCK OF CONCERNED BAY CB
TO INITIATE LBB/BFR OF CONCERNED BAY
BLOCK AUTO RECLOSURE OF CONCERNED BAY
8686--GBGB
MASTERMASTERTRIP /TRIP /HIGH HIGH
SPEEDSPEEDTRIPTRIP
RELAYRELAYTO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER (MAIN-1 & MAIN-2)
INITIATE FLAG RELAY (FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
BLOCK AUTO RECLOSURE OF CONCERNED BAY
TO TRIP COIL-1 CONCERNED BAY CB
TO TRIP COIL-2 CONCERNED BAY CB
PUSH BUTTON FOR RESETTING.
TO INITIATE LBB/BFR OF CONCERNED BAY
TO CLOSING INTERLOCK OF CONCERNED BAY CB
8686--GBGBMASTERMASTER
TRIP /TRIP /HIGH HIGH
SPEEDSPEEDTRIPTRIP
RELAYRELAY
TO INITIATE LBB/BFR OF CONCERNED BAY
TO EVENT RECORDER ( SOE/ SCADA )
TO DISTURBANCE RECORDER (MAIN-1 & MAIN-2)
INITIATE FLAG RELAY (FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
BLOCK AUTO RECLOSURE OF CONCERNED BAY
TO TRIP COIL-1 CONCERNED BAY CB
TO TRIP COIL-2 CONCERNED BAY CB
AUTO TRANSFORMER INTER TRIP CIRCUITSAUTO TRANSFORMER INTER TRIP CIRCUITSHV INTER TRIP CIRCUITS(TO LV)HV INTER TRIP CIRCUITS(TO LV) LV INTER TRIP CIRCUIT(TO HV)LV INTER TRIP CIRCUIT(TO HV)
FOR LV MASTER TRIP RELAY 86 GR-A
1. TIE CB OPEN CONDITION + MAIN CB REMOTE HAND TRIP
GIVEN.
2. MAIN CB OPEN CONDITION + TIE CB REMOTE HAND TRIP
GIVEN.
3. TIE CB OPEN CONDITION + 96 BUSBAR-1 OPERATED.
4. MAIN CB OPEN CONDITION + 96 BUSBAR-2 OPERATED
FOR HV M-CB MASTER TRIP RELAY 86 GR-A
1. LV CB REMOTE HAND TRIP GIVEN.
2. LV 87 BB(96) BUSBAR-1/2 (ISO SELECTION)
OPERATED.
3. LV CB 50 LBB/BFR OPERATED.
4. MAIN CB OPEN CONDITION + 96 BUSBAR-2 OPERATED
(FOR HALF DIA ONLY).
5. MAIN CB 50 LBB/BFR OPERATED.
6. TIE CB 50 LBB/BFR OPERATED.
7. 87 TEED-1 PROTECTION OPERATED
8. 87 TEED-2 PROTECTION OPERATED.
FOR LV MASTER TRIP RELAY 86 GR-B
1. TIE CB OPEN CONDITION + MAIN CB REMOTE HAND TRIP
GIVEN.
2. MAIN CB OPEN CONDITION + TIE CB REMOTE HAND TRIP
FOR HV M-CB MASTER TRIP RELAY 86 GR-B
1. LV CB REMOTE HAND TRIP GIVEN.
2. LV 87 BB(96) BUSBAR-1/2 (ISO SELECTION)
OPERATED.
3. LV CB 50 LBB/BFR OPERATED.
FOR HV T-CB MASTER TRIP RELAY 86 GR-A
1. LV CB REMOTE HAND TRIP GIVEN.
2. LV 87 BB(96) BUSBAR-1/2 (ISO SELECTION) 2. MAIN CB OPEN CONDITION + TIE CB REMOTE HAND TRIP
GIVEN.
3. TIE CB OPEN CONDITION + 96 BUSBAR-1 OPERATED.
4. MAIN CB OPEN CONDITION + 96 BUSBAR-2 OPERATED
(FOR HALF DIA ONLY).
5. MAIN CB 50 LBB/BFR OPERATED.
6. TIE CB 50 LBB/BFR OPERATED.
7. 87 TEED-1 PROTECTION OPERATED
8. 87 TEED-2 PROTECTION OPERATED.
2. LV 87 BB(96) BUSBAR-1/2 (ISO SELECTION)
OPERATED.
3. LV CB 50 LBB/BFR OPERATED.
FOR HV T-CB MASTER TRIP RELAY 86 GR-B
1. LV CB REMOTE HAND TRIP GIVEN.
2. LV 87 BB(96) BUSBAR-1/2 (ISO SELECTION)
OPERATED.
3. LV CB 50 LBB/BFR OPERATED.
TRANSFORMER TROUBLES TRIPPING TRANSFORMER TROUBLES TRIPPING GRGR--AA
OIL TEMP TRIP
86 AX
TO 3PH GR-A 400KV MAIN CB
BUCHHOLZ TRIP
PRD-1 TRIP
PRD-2 TRIP
DIFF RELAY 87T
OL RELAY 51OL
HV O/L+E/F PROT 6786 AY
TO 3PH GR-A 400KV TIE CB
TO 3PH GR-A 220KV MAIN CB
TO 3PH GR-A 220KV TBC CB
NDR RELAY 151N
HV O/F RELAY 99T
TRANSFORMER TROUBLES TRIPPING TRANSFORMER TROUBLES TRIPPING GRGR--BB
86 BX
TO 3PH GR-B 400KV MAIN CBOLTC BUCHHOLZ-R TRIP
REF RELAY 64REF
STUB RELAY 50ST
LV O/L+E/F PROT 6786 BY
TO 3PH GR-B 400KV TIE CB
TO 3PH GR-B 220KV MAIN CB
TO 3PH GR-B 220KV TBC CBOLTC BUCHHOLZ-Y TRIP
OLTC BUCHHOLZ –B TRIP
WNDG TEMP-HV TRIP
LV O/F RELAY 99TWNDG TEMP-LV TRIP
WNDG TEMP-IV TRIP
186R1
186R2
286R1
186Y1
186Y2
286Y1
186B1
186B2
286B1
186R1, 186R2, 186Y1, 186Y2, 186B1, 186B2 ARE CB 1-PH TRIP UNIT OF GR-A. THESE
ARE SELF RESETING.
TRIP COIL-1
TRIP COILTRIP COIL--1 CIRCUITS1 CIRCUITS
.
286R1
286R2
86GR-A
86GR-B
.
286Y1
286Y2
286B1
286B2
.
ARE SELF RESETING.286R1, 286R2, 286Y1, 286Y2, 286B1, 286B2 ARE CB 1-PH TRIP UNIT OF GR-B. THESE ARE SELF RESETING.THE BELOW ARE HAND RESETING.86GR-A, 86GR-B ARE 3-PH TRIP UNITS.
96 BB IS BUSBAR TRIPPING RELAY
.86GR-B
96BB
..
186R1
186R2
286R1
186Y1
186Y2
286Y1
186B1
186B2
286B1
186R1, 186R2, 186Y1, 186Y2, 186B1, 186B2 ARE CB 1-PH TRIP UNIT OF GR-A. THESE
ARE SELF RESETING.
TRIP COIL-2
TRIP COIL TRIP COIL –– 2 CIRCUITS2 CIRCUITS
.
286R1
286R2
86GR-A
86GR-B
.
286Y1
286Y2
286B1
286B2
.
ARE SELF RESETING.286R1, 286R2, 286Y1, 286Y2, 286B1, 286B2 ARE CB 1-PH TRIP UNIT OF GR-B. THESE ARE SELF RESETING.THE BELOW ARE HAND RESETING.86GR-A, 86GR-B ARE 3-PH TRIP UNITS.
96 BB IS BUSBAR TRIPPING RELAY
.86GR-B
96BB
..
ISOLATOR ISOLATOR
INTERLOCKSINTERLOCKSS.NOS.NO
ISOLATORISOLATOR
OPEN/CLOSEOPEN/CLOSE
EQUIPMENTEQUIPMENT--11 EQUIPMENTEQUIPMENT--22 EQUIPMENTEQUIPMENT--33 EQUIPMENTEQUIPMENT--44
INTERLOCKS REQUIRED FOR CONCERNED ISOLATOR / EARTH SWITCH OPEN OR CLOSEINTERLOCKS REQUIRED FOR CONCERNED ISOLATOR / EARTH SWITCH OPEN OR CLOSE
BAY BAY -- 11
11 1 1 -- 8989 ISOISO BB189 EBB189 E OO 189 AE189 AE OO 189 E189 E OO 152 CB152 CB OO
22 1 1 –– 89 E89 E ESES 189 A189 A OO 189189 OO ---- -- ---- --
33 1 1 –– 89 A89 A ISOISO 189 AE189 AE OO 189 E189 E OO 152 CB152 CB OO ---- --
44 1 1 –– 89 AE89 AE ESES 189 A189 A OO 189189 OO ---- -- ---- --
55 1 1 –– 89 L89 L ISOISO 189 LE189 LE OO 152 CB152 CB OO 252 CB252 CB OO ---- --
66 1 1 –– 89 LE89 LE ESES 189 L189 L OO UV RELAYUV RELAY AA ---- -- ---- --
BAY BAY -- 22
77 2 2 –– 89 A89 A ISOISO 289 BE289 BE OO 289 AE289 AE OO 252 CB252 CB OO ---- --
88 2 2 –– 89 AE89 AE ESES 289 B289 B OO 289 A289 A OO ---- -- ---- --
99 2 2 –– 89 B89 B ISOISO 289 BE289 BE OO 289 AE289 AE OO 252 CB252 CB OO ---- --
1010 2 2 –– 89 BE89 BE ESES 289 B289 B OO 289 A289 A OO ---- -- ---- --
NOTE:NOTE: All Earth Switches All Earth Switches
in the Bay are towards in the Bay are towards
Circuit Breaker side only. Circuit Breaker side only.
The Line and Transformer The Line and Transformer
Earth Switches are towards Earth Switches are towards
Line & Transformer.Line & Transformer.
BAY BAY -- 33
1111 3 3 –– 89 89 ISOISO BB289 EBB289 E OO 389 AE389 AE OO 389 E389 E OO 352 CB352 CB OO
1212 3 3 –– 89 E89 E ESES 389 A389 A OO 389389 OO ---- -- ---- --
1313 3 3 –– 89 A89 A ISOISO 389 AE389 AE OO 389 E389 E OO 352 CB352 CB OO ---- --
1414 3 3 –– 89 AE89 AE ESES 389 A389 A OO 389389 OO ---- -- ---- --
1515 3 3 –– 89 T89 T ISOISO LV89 E2LV89 E2 OO 389 TE389 TE OO 252 CB252 CB OO 352 CB352 CB OO
1616 3 3 –– 89 TE89 TE ESES 389 T389 T OO LV89 TLV89 T OO ---- -- ---- --
O: OPENO: OPEN
C: CLOSEC: CLOSE
A: ACTEDA: ACTED
BB189E : BUSBARBB189E : BUSBAR--1 EARTH SWITCH .1 EARTH SWITCH .
BB289E : BUSBARBB289E : BUSBAR--2EARTH SWITCH . 2EARTH SWITCH .
UV RELAY: UNDER VOLTAGE RELAY.UV RELAY: UNDER VOLTAGE RELAY.
ISOLATOR & CB INTERLOCKSISOLATOR & CB INTERLOCKS
1-52CB
&
OPEN
OPEN
OPEN
OPERATION1-89AE
1-89E
1-89A
&
BB189EOPEN
OPEN1-89AE
1-89EOPEN
OPEN
1-89OPERATION
1-52CB
&OPERATION
OPEN
OPEN
OPEN
OPEN
BB289E
3-89AE
3-89E
3-52CB
3-89
3-52CB
3-89AE&
OPEN
OPEN
OPEN3-89E
OPERATION3-89A
CLOSE &CLOSE
1-89E
1-89AE
LOCAL
CLOSE
1-52CB
CLOSE &CLOSE
2-89AE
2-89BE
LOCAL
CLOSE
2-52CB
&CLOSE
3-89ELOCAL
CLOSE
1-52CB
&
OPEN
OPEN
OPEN
OPERATION1-89LE
2-52CB
1-89L
&1-89
OPEN
OPEN1-89A
1-89EOPERATION
OPEN
&1-89
OPEN 1-89AEOPERATION
3-89E
2-52CB&
OPEN
OPEN
OPEN
3-52CB
3-89TEOPERATION3-89T
OPENLV89E2
OPEN
OPEN&3-89
3-89A
OPERATION3-89E
OPEN
OPEN&3-89
OPERATION
CLOSE &3-89E
3-89AE
CLOSE
3-52CB
RESET &
RESET86GR-A
86GR-B
REMOTE
CLOSE
1-52CBRESET96BB
RESET &RESET
86GR-A
86GR-B
REMOTE
CLOSE
2-52CB
RESET86GR-A
2-52CB
&
OPEN
OPEN
OPEN
OPERATION2-89AE
2-89BE2-89A
&OPEN1-89A
1-89AE
&1-89L
OPEN
ACTEDU/V RLY
1-89LEOPERATION
OPEN&3-89A
OPERATION3-89AE
OPEN
OPEN&OPERATION
3-89TE3-89T
LV89T
OPEN &OPEN
2-89A
2-89B
OPERATION
2-89AE
OPEN
OPEN &2-89A
2-89B
OPERATION
2-89BE
2-52CB
&
OPEN
OPEN
OPEN
OPERATION2-89AE
2-89BE2-89B
RESET &
RESET86GR-A
86GR-B
REMOTE
CLOSE
3-52CBRESET96BB
CLOSING INTERLOCK OF MAIN & TIE CBCLOSING INTERLOCK OF MAIN & TIE CB
86 GR86 GR--A A 96 BB 96 BB 86 GR86 GR--B B
T N CT N C
+ VE+ VE
CB REMOTE CLOSECB REMOTE CLOSE+ve+ve --veve
SYN SOCKETSYN SOCKET
CB REMOTE CLOSECB REMOTE CLOSE
MAIN CBMAIN CB21M1 AR21M1 AR
21M2 AR21M2 AR
86 GR86 GR--A A 86 GR86 GR--B B
CB AUTO RECLOSECB AUTO RECLOSE
+ve+ve --veve
T N CT N C
+ VE+ VE
TIE CBTIE CBTIE ARTIE AR
CB REMOTE CLOSECB REMOTE CLOSE
CB AUTO RECLOSECB AUTO RECLOSE
+ve+ve --veve
SYN SOCKETSYN SOCKET
OTHER OTHER INFORMATION INFORMATION REGARDING REGARDING REGARDING REGARDING RELAYS AND RELAYS AND
TESTING TESTING TESTING TESTING EQUIPMENTEQUIPMENT
PREPARED BYGOPALA KRISHNA PALEPU
ADE/MRT(PROTECTION)
ABB RELAYSABB RELAYS
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ABB Network Partner AG REL 316*4ABB Network Partner AG
ABB Network Partner AG REL 521
C
E
C
E
C
E
ABB Network Partner AG
REL 512ABB Relays
c
E
AREVA RELAYSAREVA RELAYS
P443 P445
P437 P442E-PAC
GE MULTILINGE MULTILINRELAYSRELAYS
B90 – 87BB
C60 – BCU
D60 – 21L
D90 – 21L
L60 – 87L
L90 – 87L
T60 – 87T
D25 – BCU
F90 – 67/51
G60 – GEN
M60 – MOTOR
N90 – NETWORKD90 – 21L D25 – BCU N90 – NETWORK
SIEMENS RELAYSSIEMENS RELAYS
IA =250.10 A
IB =250.10 A
ENABLED
TRIPTARGET RESET
INSTINSTINSTINST PH PH PH PH ---- AAAA
SPT
ENABLEDMC
ENABLED SEL- 421PROTECTION
SEL RELAYSSEL RELAYS
IB =250.10 A
IC =250.10 A
VAB =400.0 KV
VBC =400.0 KV
VCA =400.0 KV
ESC ENT
INSTINSTINSTINST
TIMETIMETIMETIME
COMMCOMMCOMMCOMM
SOTFSOTFSOTFSOTF
ZONE 1ZONE 1ZONE 1ZONE 1
ZONE 2ZONE 2ZONE 2ZONE 2
ZONE 3ZONE 3ZONE 3ZONE 3
ZONE 4ZONE 4ZONE 4ZONE 4
PH PH PH PH ---- AAAA
PH PH PH PH ---- BBBB
PH PH PH PH ---- CCCC
GNDGNDGNDGND
5051
79 RESET
79 LOCKOUT
COMM
ENABLED
RECLOSE
ENABLED
ALT
SETTINGS
CB
CLOSED
RELAY
TEST
CB
OPEN
AUTOMATION
CONTROL
SEL
ENABLEDTARGET
INST TIME COMM SOTF SEL- 321- 5 - 21 2 3 4
TRIPTARGET RESET PROTECTION
AUTOMATION
CONTROL
SEL
TRIP ZONE
EN A B C G Q 51 50
FAULT TYPE O/C
TARGET
RESET
TARGET FAULT SET METER STATUS OTHER GROUP
NO /
CANCEL
YES /
SELECTEXIT
VA TECH REYROLLE RELAYSVA TECH REYROLLE RELAYS
ERL PHASE RELAYSERL PHASE RELAYS
RELAY HARDWARERELAY HARDWARE
16 / 32 BIT
PCMODEM
NORMALLY 400KV RELAYS SUPPLIED WITH FOLLOWINGCONFIGUARATION/HARDWARE
1. MIN 4Nos MAX 8Nos COMMAND/TRIP OUTPUTS
2. MIN 24Nos SIGNAL OUTPUTS3. MIN 14 LED INDICATIONS4. MIN 24 BINARY INPUTS
IRIG-BRE/CC
RELAY SIGNAL DATA FLOWRELAY SIGNAL DATA FLOW
FUNCTIONS AVAILABLE NUMERICAL DISTANCE RELAYSFUNCTIONS AVAILABLE NUMERICAL DISTANCE RELAYS1.1. 4 TO 6 SETTING IMPEDENCE ZONES WITH 4 TO 6 SETTING GROUPS (21 + 21N).4 TO 6 SETTING IMPEDENCE ZONES WITH 4 TO 6 SETTING GROUPS (21 + 21N).2.2. DIR / INST / TIME OVERCURRENT & EARTH FAULT FUNCTION( 50 / 51 / 67 P+G).DIR / INST / TIME OVERCURRENT & EARTH FAULT FUNCTION( 50 / 51 / 67 P+G).3.3. EIGHT COMMUNICATION SCHEMES.EIGHT COMMUNICATION SCHEMES.4.4. SWITCH ON TO FAULT PROTECTION(21 SOTF).SWITCH ON TO FAULT PROTECTION(21 SOTF).5.5. PHASE SELECTION(R,Y,B).PHASE SELECTION(R,Y,B).6.6. POWER SWING BLOCKING(PSB)(68 + 68T).POWER SWING BLOCKING(PSB)(68 + 68T).7.7. FUSE FAILURE SUPERVISION(PT FFR).FUSE FAILURE SUPERVISION(PT FFR).
8.8. AUTO RECLOSER WITH CHECK SYNCHRNISATIONAUTO RECLOSER WITH CHECK SYNCHRNISATION & VOLTAGE CHECK(79 + 25 +86). & VOLTAGE CHECK(79 + 25 +86). 8.8. AUTO RECLOSER WITH CHECK SYNCHRNISATIONAUTO RECLOSER WITH CHECK SYNCHRNISATION & VOLTAGE CHECK(79 + 25 +86). & VOLTAGE CHECK(79 + 25 +86).
9.9. WEEK END INFEED LOGIC(27 WI).WEEK END INFEED LOGIC(27 WI).10.10. SYSTEM SUPERVISION.SYSTEM SUPERVISION.11.11. STUB PROTECTION(STUB).STUB PROTECTION(STUB).12.12. OVER VOLTAGE/ UNDER VOLTAGE FUNCTION(27+ 59).OVER VOLTAGE/ UNDER VOLTAGE FUNCTION(27+ 59).13.13. LBB/BFR FUNCTION(50 BF).LBB/BFR FUNCTION(50 BF).14.14. DISTANCE TO FAULT LOCATOR(21 FL).(SHOWS IN 1. %, 2. KM 3. MILES & 4. R+JX )DISTANCE TO FAULT LOCATOR(21 FL).(SHOWS IN 1. %, 2. KM 3. MILES & 4. R+JX )15.15. 16 PROGRAMABLE SIGNALLING RELAYS WITH LEDs.16 PROGRAMABLE SIGNALLING RELAYS WITH LEDs.16.16. RECORDABLE 10Nos LATEST DISTRUBANCES WITH BASIC EVALUATION RECORDABLE 10Nos LATEST DISTRUBANCES WITH BASIC EVALUATION
DISTURBANCE RECORDER.DISTURBANCE RECORDER.17.17. EVENT RECORDER RELATED TO RELAY EVENTS.EVENT RECORDER RELATED TO RELAY EVENTS.17.17. EVENT RECORDER RELATED TO RELAY EVENTS.EVENT RECORDER RELATED TO RELAY EVENTS.18.18. PREPRE--FAULT, FAULT & POSTFAULT, FAULT & POST--FAULT VALUES OF ANALOG POINTS WITH IMPEDENCE FAULT VALUES OF ANALOG POINTS WITH IMPEDENCE
DETAILS.DETAILS.19.19. USER CAN BE CONFIGUARED PROGRAMABLE LOGIC FUNCTIONS.USER CAN BE CONFIGUARED PROGRAMABLE LOGIC FUNCTIONS.20.20. TELE / CARRIER INTER TRIPPING SCHEMES(85 +21)(PUTT, POTT).TELE / CARRIER INTER TRIPPING SCHEMES(85 +21)(PUTT, POTT).21.21. TRIP CIRCUIT MONITORING(74 TC).TRIP CIRCUIT MONITORING(74 TC).22.22. METERING FUNCTION (INSTANTANEOUS VALUES DISPLAY FUNCTION).METERING FUNCTION (INSTANTANEOUS VALUES DISPLAY FUNCTION).23.23. 4 QUADRANT ENERGY METER FUNCTION (KWH,KVAH,KVARH)(KYZ PULSE OUTPUT).4 QUADRANT ENERGY METER FUNCTION (KWH,KVAH,KVARH)(KYZ PULSE OUTPUT).24.24. MINIMUM 8 COMMOND/ TRIP RELAYS, 24 SIGNAL RELAYSMINIMUM 8 COMMOND/ TRIP RELAYS, 24 SIGNAL RELAYS25.25. MINIMUM 20 BINARY INPUTS, 14 LEDsMINIMUM 20 BINARY INPUTS, 14 LEDs
DISTANCE RELAYS CHARACTERESTICSDISTANCE RELAYS CHARACTERESTICS( MHO CIRCULAR )( MHO CIRCULAR )
DISTANCE RELAYS CHARACTERESTICSDISTANCE RELAYS CHARACTERESTICS( QUADRILATERAL( QUADRILATERAL--1 )1 )
DISTANCE RELAYS CHARACTERESTICSDISTANCE RELAYS CHARACTERESTICS( QUADRILATERAL( QUADRILATERAL--2 )2 )
DISTANCE RELAYS CHARACTERESTICSDISTANCE RELAYS CHARACTERESTICS( BULLET )( BULLET )
DISTANCE RELAYS CHARACTERESTICSDISTANCE RELAYS CHARACTERESTICS( TRIANGLER )( TRIANGLER )
DISTANCE RELAYS CHARACTERESTICSDISTANCE RELAYS CHARACTERESTICS( LENS / OPTICAL )( LENS / OPTICAL )
DISTANCE RELAYS CHARACTERESTICSDISTANCE RELAYS CHARACTERESTICS( TOMATO )( TOMATO )
DISTANCE RELAYS CHARACTERESTICSDISTANCE RELAYS CHARACTERESTICS( PEANUT )( PEANUT )
RELAY MODELS OF LINE (DISTANCE) & TRANSFORMER( M & B ) OF DIFFERENT MANUFACTURERSRELAY MODELS OF LINE (DISTANCE) & TRANSFORMER( M & B ) OF DIFFERENT MANUFACTURERS
MANUFACTURERSMANUFACTURERSTRANSMISSION LINE PROTECTIONTRANSMISSION LINE PROTECTION T/F PROTECTIONT/F PROTECTION
MAINMAIN--1 (21)1 (21) CURVESCURVES MAINMAIN--2 (87)2 (87) CURVESCURVES DIFFERENTIALDIFFERENTIAL DIR O/L,E/FDIR O/L,E/F
ABBABB REL 670REL 670QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/
mhomhomhomhomhomhomhomho RED 670RED 670 QUADQUADQUADQUADQUADQUADQUADQUAD RET 670RET 670 REF 6XXREF 6XXABBABB REL 670REL 670 mhomhomhomhomhomhomhomho RED 670RED 670 QUADQUADQUADQUADQUADQUADQUADQUAD RET 670RET 670 REF 6XXREF 6XX
ALSTOMALSTOM
(AREVA)(AREVA)MICOM MICOM
P446/P443P446/P443
QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/
MHOMHOMHOMHOMHOMHOMHOMHO MICOM P545MICOM P545QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/
MHOMHOMHOMHOMHOMHOMHOMHO
MICOM P633 MICOM P633
MICOM P643MICOM P643MICOM P141MICOM P141
SIEMENS SIEMENS
( SIPROTEC )( SIPROTEC )
SIPROTECSIPROTEC
7SA5227SA522
QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/
MHOMHOMHOMHOMHOMHOMHOMHO
SIPROTECSIPROTEC
7SD5327SD532
QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/
MHOMHOMHOMHOMHOMHOMHOMHO
7UT 613/ 2 7UT 613/ 2
7UT 513/ 2 7UT 513/ 2
7SJ 62/3/4/5 7SJ 62/3/4/5
7SJ 52/3/4/57SJ 52/3/4/5
VA TECHVA TECH
REYROLLREYROLLOHMEGA 402OHMEGA 402
QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/
MHOMHOMHOMHOMHOMHOMHOMHO
OHMEGA OHMEGA
311/308311/308
QUAD/ QUAD/
MHOMHODUOBIAS MDUOBIAS M ARGUSARGUS
REYROLLREYROLL MHOMHOMHOMHOMHOMHOMHOMHO 311/308311/308 MHOMHO
GE GE
MULTILINMULTILINDD--60, 60,
DD--90 PLUS90 PLUS
QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/
MHOMHOMHOMHOMHOMHOMHOMHO LL--60/L60/L--9090QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/
MHOMHOMHOMHOMHOMHOMHOMHO TT--35 / T35 / T--60 60 FF--60 60
SELSEL SEL 421SEL 421 MHOMHOMHOMHOMHOMHOMHOMHO SEL 487LSEL 487L MHOMHOMHOMHOMHOMHOMHOMHO SEL 487TSEL 487T SEL 351SEL 351
ERL ERL
PHASEPHASELL--PROPRO
QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/ QUAD/
MHOMHOMHOMHOMHOMHOMHOMHO LL--PROPROLENS/ LENS/
TOMAT0TOMAT0TT--PROPRO FF--PROPRO
IEC 61850 RELAY MODELS OF DIFFERENT MANUFACTURERSIEC 61850 RELAY MODELS OF DIFFERENT MANUFACTURERS
MANUFACTURERSMANUFACTURERSBCUBCUBCUBCU
CB CONTROLCB CONTROLCB CONTROLCB CONTROL
FEEDERFEEDERFEEDERFEEDER
67676767
DISTANCEDISTANCEDISTANCEDISTANCE
21212121
LINE LINE LINE LINE
DIFFERENTIALDIFFERENTIALDIFFERENTIALDIFFERENTIAL
87 L87 L87 L87 L
DIFFERENTIALDIFFERENTIALDIFFERENTIALDIFFERENTIAL
87 T87 T87 T87 T
BUSBARBUSBARBUSBARBUSBAR
87 BB87 BB87 BB87 BB
ABBABB REC 670 REX 610 REL 670 RED 670 RET 670REB 670
REB 500ABBABB REC 670 REX 610 REL 670 RED 670 RET 670
REB 500
AREVAAREVAMICOM
C264
MICOM
P141MICOM
P44 2/3/4
MICOM
P543/547
MICOM
P633/P643
MICOM
P74 1/3/6
GE GE MULTILINMULTILIN
D 25
C 90 PLUSF 60 D 60, D 90 L 60, L 90 T 60 B 90, B 30
SIEMENS SIEMENS ( SIPROTEC )( SIPROTEC )
SIPROTEC6MD66/3
SIPROTEC7SJ 62/3/4
SIPROTEC7SA 522/6..
SIPROTEC7SD 532/61_
SIPROTEC7UT 633/13/2
SIPROTEC 7 SS 52( SIPROTEC )( SIPROTEC ) 6MD66/3 7SJ 62/3/4 7SA 522/6.. 7SD 532/61_ 7UT 633/13/2 7 SS 52
SELSELSEL
451-4
SEL
451
SEL
421/321
SEL
387L
SEL
487E
SEL
487B
TOSHIBATOSHIBAGBU
100/150GRD 140
GRZ
100/150
GRL
100 / 150
GRT
100/150
GRB
100/150
RELAY TESTING EQUIPMENTSRELAY TESTING EQUIPMENTS1. PROGRAMA_GE (MODEL: FREEJA1. PROGRAMA_GE (MODEL: FREEJA--300) 2. MANTA TEST SYSTEMS (MODEL: MTS 4000)300) 2. MANTA TEST SYSTEMS (MODEL: MTS 4000)3. OMICRON (MODEL: CMC 2563. OMICRON (MODEL: CMC 256--6)6) 4. DOBLE ( MODEL: F 6150)4. DOBLE ( MODEL: F 6150)
RELAY TESTING EQUIPMENTSRELAY TESTING EQUIPMENTS1. MEEGER_AVO (MODEL: MPRT 8430) 1. MEEGER_AVO (MODEL: MPRT 8430) 2. RES (MODEL: APTS 3)2. RES (MODEL: APTS 3)3. KOCOS (MODEL: ARTES 440 II) 3. KOCOS (MODEL: ARTES 440 II) 4. EURO SMC ( MODEL: TRES)4. EURO SMC ( MODEL: TRES)
400KV SUBSTATIONS IN APTRANSCO400KV SUBSTATIONS IN APTRANSCO
S.NoS.No 400KV SUBSTATION400KV SUBSTATION CAPACITYCAPACITY FEEDERSFEEDERS
1.1. MAMIDIPALLY (HYDERABAD)MAMIDIPALLY (HYDERABAD) 3 X 315 MVA3 X 315 MVA1. SRISAILAM 11. SRISAILAM 12. GHANAPUR (PGCIL)2. GHANAPUR (PGCIL)
3. KHAMMAM 1&2(PGCIL)3. KHAMMAM 1&2(PGCIL)4. YEDDUMAILARAM**4. YEDDUMAILARAM**
2.2. NURNOOR (KURNOOL)NURNOOR (KURNOOL) (2 + 1**) X (2 + 1**) X 315 MVA315 MVA
1. SRISAILAM1. SRISAILAM2. GHANAPUR (PGCIL)2. GHANAPUR (PGCIL)
3. GOOTY (PGCIL)3. GOOTY (PGCIL)4. KURNOOL**(PGCIL765)4. KURNOOL**(PGCIL765)
3.3. KALAPAKA (VISHAKHAPATNAM)KALAPAKA (VISHAKHAPATNAM) 2 X 315 MVA2 X 315 MVA1. SIMHADRI 1,2,3&4 (NTPC)1. SIMHADRI 1,2,3&4 (NTPC)2. GAJUWAKA 1&2 (PGCIL)2. GAJUWAKA 1&2 (PGCIL)
3. KHAMMAM 1&2 (PGCIL)3. KHAMMAM 1&2 (PGCIL)4. VEMAGIRI 1&24. VEMAGIRI 1&2
1. KALAPAKA 1&21. KALAPAKA 1&2 5. GVK EXTN 1&2 (IPP)5. GVK EXTN 1&2 (IPP)
4.4. VEMAGIRI (RAJHAMUNDRY)VEMAGIRI (RAJHAMUNDRY) 2 X 315 MVA2 X 315 MVA
1. KALAPAKA 1&21. KALAPAKA 1&22. GAJUWAKA 1&2 (PGCIL)2. GAJUWAKA 1&2 (PGCIL)3. NUNNA 1&2 (PGCIL)3. NUNNA 1&2 (PGCIL)4. NUNNA 3&4 (NRPT** 1&2)4. NUNNA 3&4 (NRPT** 1&2)
5. GVK EXTN 1&2 (IPP)5. GVK EXTN 1&2 (IPP)6. GOWTHAMI 1&2 (IPP)6. GOWTHAMI 1&2 (IPP)7. KONASEEMA 1&2 (IPP)7. KONASEEMA 1&2 (IPP)8. GMR VASAVI 1&2 (IPP)8. GMR VASAVI 1&2 (IPP)
5. 5. VELTUR (MB NAGAR)VELTUR (MB NAGAR) 3 X 315 MVA3 X 315 MVA1. TALLAPALLY1. TALLAPALLY 2. RAICHUR2. RAICHUR
6.6. CHITTOR(VEPANJIR)CHITTOR(VEPANJIR) 2 X 315 MVA2 X 315 MVA1. CHENNAI RED HILLS1. CHENNAI RED HILLS3. KRISHNAPATNAM**1&23. KRISHNAPATNAM**1&2
2. KADAPA2. KADAPA
7.7. NELLORE(MANUBOLU)NELLORE(MANUBOLU) (2 + 1**) X (2 + 1**) X 315 MVA315 MVA
1. KRISHNAPATNAM**1&21. KRISHNAPATNAM**1&2
8.8. DICHPALLY (NIZAMABAD)DICHPALLY (NIZAMABAD) 2 X 315 MVA2 X 315 MVA1. RAMAGUNDAM1. RAMAGUNDAM
1. RAMAGUNDAM1. RAMAGUNDAM 2. GHANAPUR2. GHANAPUR
9.9. GAJWEL (MEDAK)GAJWEL (MEDAK) 2 X 315 MVA2 X 315 MVA1. RAMAGUNDAM1. RAMAGUNDAM3. BTPS 1&2**3. BTPS 1&2**
2. GHANAPUR2. GHANAPUR4. YEDDUMAILARAM 1&2**4. YEDDUMAILARAM 1&2**
10.10. MALKARAM (SECUNDRABAD)MALKARAM (SECUNDRABAD) (2 + 1**)X (2 + 1**)X 315 MVA315 MVA
1. RAMAGUNDAM1. RAMAGUNDAM3. VTPS**1&23. VTPS**1&2
2. GHANAPUR2. GHANAPUR
11.11. SHANKARPALLY**SHANKARPALLY** 3 X 315 MVA3 X 315 MVA1. GAJWEL 1&2*1. GAJWEL 1&2* 2. MAMIDIPALLY *2. MAMIDIPALLY *
3. SRISAILAM*3. SRISAILAM*
12.12. NARASARAOPETA**(GUNTUR)NARASARAOPETA**(GUNTUR) 2 X 315 MVA2 X 315 MVA1. SRISAILAM 1&21. SRISAILAM 1&22. VTPS 1&22. VTPS 1&2
3. VEMAGIRI 1&23. VEMAGIRI 1&2
13.13. SURYAPETA** (NALGONDA)SURYAPETA** (NALGONDA) 2 X 315 MVA2 X 315 MVA1. VTPS 1&21. VTPS 1&2 2. MALKARAM 1&22. MALKARAM 1&2
400KV SUBSTATIONS OF PGCIL IN AP400KV SUBSTATIONS OF PGCIL IN APS.NoS.No 400KV SUBSTATION400KV SUBSTATION CAPACITYCAPACITY FEEDERSFEEDERS
1.1. RAMAGUNDAM(NTPC)RAMAGUNDAM(NTPC)2 X 200 MVA 2 X 200 MVA 2 X 250 MVA2 X 250 MVA1 X 315 MVA1 X 315 MVA
1. GHANAPUR 1&2 1. GHANAPUR 1&2 2. GAJWEL2. GAJWEL3. MALKARAM3. MALKARAM
4. TALLAPALLY 1&24. TALLAPALLY 1&25. DICHPALLY5. DICHPALLY6. WARANGAL6. WARANGAL7. CHANDRAPUR 1&27. CHANDRAPUR 1&2
2.2. GHANAPUR (HYDERABAD)GHANAPUR (HYDERABAD) 3 X 315 MVA3 X 315 MVA1. RAMAGUNDAM 1&2 1. RAMAGUNDAM 1&2 2. MAMIDIPALLY2. MAMIDIPALLY3. GAJWEL3. GAJWEL
4. NAGARJUNA SAGAR4. NAGARJUNA SAGAR5. KURNOOL5. KURNOOL6. MALKARAM6. MALKARAM
3.3. GAJUWAKA (VISHAKHAPATNAM)GAJUWAKA (VISHAKHAPATNAM) 2 X315 MVA2 X315 MVA1. NUNNA(*GMR)1. NUNNA(*GMR)2. KALAPAKA1&22. KALAPAKA1&25. BERAHUMPUR5. BERAHUMPUR--1&21&2
3. SIMHADRI (VMGR*) 1&2 3. SIMHADRI (VMGR*) 1&2 4. JAIPUR(HVDC)4. JAIPUR(HVDC)3.3. 2 X315 MVA2 X315 MVA
5. BERAHUMPUR5. BERAHUMPUR--1&21&2
4.4. NUNNA (VIJAYAWADA)NUNNA (VIJAYAWADA) 2 X315 MVA2 X315 MVA
1. GAJUWAKA(GMR*)1. GAJUWAKA(GMR*)2. VTPS 1&22. VTPS 1&23. VEMAGIRI 1&2 3. VEMAGIRI 1&2
4. VEMAGIRI 3&4 (#)4. VEMAGIRI 3&4 (#)5. KHAMMAM5. KHAMMAM6. NELLORE 1&26. NELLORE 1&27. LANCO1&27. LANCO1&2
5.5.TALLAPALLYTALLAPALLY(NAGARJUNA SAGAR)(NAGARJUNA SAGAR) 3 X 315 MVA3 X 315 MVA
1. RAMAGUNDAM 1&2 1. RAMAGUNDAM 1&2 2. GHANAPUR2. GHANAPUR3. MAHABOOBNAGAR3. MAHABOOBNAGAR
4. GOOTY(KNL765*)4. GOOTY(KNL765*)5. CHINAKAMPALLY 1&25. CHINAKAMPALLY 1&2
6. 6. BUDIDAMPADU (KHAMMAM)BUDIDAMPADU (KHAMMAM) 2 X 315 MVA2 X 315 MVA1. WARANGAL 1. WARANGAL 2. NUNNA2. NUNNA5. KTPS**1&25. KTPS**1&2
4. MAMIDIPALLY 1&24. MAMIDIPALLY 1&25. KALAPAKA 1&25. KALAPAKA 1&2
7.7. GOOTYGOOTY 2 X 315 MVA2 X 315 MVA1. TLPLY(KNL765*)1. TLPLY(KNL765*)2. SOMANAHALLY2. SOMANAHALLY3. KURNOOL3. KURNOOL
4. NEELAMANGALA4. NEELAMANGALA5. RAICHUR 1&25. RAICHUR 1&2
8.8. CHINAKAMPALLYCHINAKAMPALLY 2 X 315 MVA2 X 315 MVA1. TALLAPALLY 1&2 1. TALLAPALLY 1&2 2. SOMANAHALLY2. SOMANAHALLY
3. KOLAR3. KOLAR4. CHITTOR4. CHITTOR
9.9. NELLORE(MANUBOLU)NELLORE(MANUBOLU) 1. NUNNA 1&21. NUNNA 1&23. MEENAKSHI 1&23. MEENAKSHI 1&2
2. ALAMATHI 1&22. ALAMATHI 1&2
10.10. MULUGU* (WARANGAL)MULUGU* (WARANGAL) 2 X 315 MVA2 X 315 MVA1. RAMAGUNDAM1. RAMAGUNDAM2. KHAMMAM2. KHAMMAM
3. BTPS(KTPS)* 1&23. BTPS(KTPS)* 1&2
1. GAJUWAKA – VEMAGIRI 1&2 IS PROPOSED TO TAKE LILO AT SIMHADRI SS.2. GAJUWAKA – NUNNA CKT IS PROPOSED TO TAKE LILO AT GMR SS.3. 765KV KURNOOL IS ABOUT TO START, 765KV DC TO RAICHUR & 400KV KUMPP-DC, KNL 400-DC, LILO TLPLY-GOOTY.
4. 765KV NELLORE, EAST GODAVARI(VEMAGIRI), SRIKAKULAM IS UNDER FORMULATION STAGE.5. VEMAGIRI TO NUNNA (APTRANSCO) 1&2 LINES WILL BE DISCONNECTED AT NUNNA & EXTENDED UP TO NRPT
400KV NETWORK IN AP400KV NETWORK IN APSIMHADRI
KALAPAKA
GAJUWAKA
IPP3 IPP4
GA
JW
EL
TALLAPALLY
DICHPALLY
WA
RA
NG
AL
RAMAGUNDAM
MA
LK
AR
AM
BTPS
CHANDRAPUR(MAHARASTRA)
HVDCHVDC
JAIPUR
SIM
HA
DR
IBERHUMPUR
RELIANCE
VEMAGIRI
NUNNA
IPP2
IPP3 IPP4
IPP1
GHANAPUR
GA
JW
EL
MB
NG
R
KADAPA
MA
LK
AR
AM
YE
DD
UM
AIL
AR
AM
VTPS
KTPS
KPPTS
KPPTS
GMR
AS
UP
AK
A
LANCO
NE
LL
OR
E
MAMIDIPALLY
SRISAILAM
GUNTUR(NRPT)
KHAMMAM
RAICHURNLR**765ALAMETHI/ CHENNAI
GOOTY
BA
NG
AL
OR
E
KO
LA
R
CHITTOR
BA
NG
AL
OR
E
YE
DD
UM
AIL
AR
AM
MALKARAM
SU
RY
AP
ETA
AS
UP
AK
A
765 KV GRID MAP765 KV GRID MAP
765KV SS765KV SS
SHOLAPURSHOLAPUR
765KV SS765KV SS
WARDHAWARDHA
765KV765KV
GAJWELGAJWEL
765KV SS765KV SS
TEKKALITEKKALI
765KV SS765KV SS
ANGULANGUL
765KV SS765KV SS
KURNOOLKURNOOL
765KV SS765KV SS
RAICHURRAICHUR
SHOLAPURSHOLAPUR
765KV SS765KV SS
VEMAGIRIVEMAGIRI
765KV SS765KV SS
KHAMMAMKHAMMAM765KV SS765KV SS
HYDERABADHYDERABAD
765KV765KV
VODAREVUVODAREVU
GAJWELGAJWEL
POWER GRIDPOWER GRID
765KV SS765KV SS
NELLORENELLORE
765KV765KV
VODAREVUVODAREVUPOWER GRIDPOWER GRID
APTRANSCOAPTRANSCO
VEMAGIRI SUBSTATION DISPLAYVEMAGIRI SUBSTATION DISPLAY
NUNNA – I
(PGCIL)
NUNNA – II
(PGCIL)
GAJUWAKA – I
(PGCIL)
GAJUWAKA – II
(PGCIL)
KALAPAKA – I KALAPAKA – II GOWTHAMI – I GOWTHAMI – II FUTURE – I
PHES
FUTURE – II
PHES
GUNTUR – I GUNTUR – II VPGCL – I
GMR VASAVI
VPGCL – II
GMR VASAVI
KOPCL – I
KONASEEMA
KOPCL – II
KONASEEMA
GVK EXT – I GVK EXT – II 315MVA,
400/220KV
AUTO
TRANSFORMER-I
315MVA,
400/220KV
AUTO
TRANSFORMER-II
VEMAGIRI 765/400 GIS SUBSTATION DISPLAYVEMAGIRI 765/400 GIS SUBSTATION DISPLAY
� A large Pooling station at Vemagiri being planned with 28 nos 400
kV bays, 8 nos 765 kV line bays, 6 nos transformer bays
DISPLAYDISPLAY