48NPFC70 Lithium Battery Training
For Globe Philippines
An Expert of Lithium battery Solutions.
April.11.2016
Company profiles
Stored Energy Solutions for a Demanding World!
BackgroundWho are we
Narada Holdings
Electrochemical Power products
Financial service
Cable networks
Narada foundation
Infrastructures projects
Property & Hotel management
Narada Power Source Co., Ltd.
Stored Energy Solutions for a Demanding World!
Facts and figuresWho are we
• Established in 1994
• Listed in 2010
• $875.2mil. revenue in 2015
• $785.1 mil. total assets
• 5143 employees
• Top 1st brand in China
• 10% profit for invest in R&D
Stored Energy Solutions for a Demanding World!
MilestonesWho are we
Narada wuhan
established
2014
Narada power
established
1998
Licom power
established
2001
Listed
company
2010
Narada Asia
established
2005
Foundation
of Narada
1994
Stored Energy Solutions for a Demanding World!
Distinct cultureWho are we
To be a provider for a complete power solution in the world
Mission
To be a respected global player for the energy storage solutions
Vision
Create value for customers and win together with customers
Value
Stored Energy Solutions for a Demanding World!
Manufacturing locationsWhere are we
Lin'an Area: 113,333 ㎡ Linping Area: 166,667 ㎡ Sichuan Area: 110,667 ㎡
Wuhan Area: 413,333 ㎡ Anhui Area: 106,667 ㎡
Stored Energy Solutions for a Demanding World!
Product applicationWhat we do
To be whole solution provider in Telecom, motive power and energy storage
Motive power
Telecom & IDC Energy storage
Stored Energy Solutions for a Demanding World!
Strong R&D strength Why choose us
Mr. Herbert K. Giess
• 86 valid patents, 30 invention patents
• National R&D center & CNAS certified Labs
• Totally 215 highly educated engineers
• Participate in setting 20 industry standards
> Head of Narada tech center
> Group leader for IEC standard for VRLA batteries IEC 60896-21
> Chairman of IEC/EN TC21 cells
Stored Energy Solutions for a Demanding World!
Quality managementWhy choose us
By BUREAU VERITAS
SA8000
By DNV
ISO14001
By DNV
TL-9000
By DNV
OHSAS18001
By TUV
ISO9001> Head of Narada QM system
> 42 years QM experience in Toyota TPS system
> NPS, Narada production system
Mr. Hagimori Hajime
TS16949
Stored Energy Solutions for a Demanding World!
Clients of telecomHow is our performance
Stored Energy Solutions for a Demanding World!
Clients of motive powerHow is our performance
Stored Energy Solutions for a Demanding World!
Clients of energy storageHow is our performance
Stored Energy Solutions for a Demanding World!
Clients of IDC & UPSHow is our performance
Product introduction
Products:
LiFePO4 Lithium Battery
Type:
48NPFC series
Application:
Telecom, Energy storage system
What is our product
Model Specification H×W×D (mm)
48NPFC10 48V 10Ah 442*245*44 (1U)
48NPFC20 48V 20Ah 442*245*88 (2U)
48NPFC30 48V 30Ah 442*245*132.5 (3U)
48NPFC50 48V 50Ah 442*390*132.5 (3U)
48NPFC70 48V 70Ah 442*450*132.5 (3U)
48NPFC75 48V 75Ah 442*400*220 (5U)
48NPFC80 (coming soon) 48V 80Ah 442*400*220 (5U)
Serials SpecificationWhat is our product
Cell: 15 cells series connection
BMS: Integrated Monitor/ protection
Connection system: power line & signal line
The composition of batteryWhat is our product
The composition: CellWhat is our product
NLC36130208PFPrismatic cell
15 cells into one group
Cell
Barcode
Heat shrink tube
NLC36130208PF specificationWhat is our product
Stored Energy Solutions for a Demanding World!
Prismatic cell designWhat is our product
Positive/Negative terminalCell cover
Cell tabs
Aluminum case
Cell group: Positive:LiFePO4 platesNegative: Graphite plates Separators: Organic material
Safety valve
BMS Job: Make Battery Reliable And Safety !
1. Various protected function
2. Monitor voltage/current/temperature
3. high-efficiency cell balance function
4. LCD Display function
5. Dry contact function
6. Charge current limited function
7. Dormant function
8. Multiple communication interface
9. Narada customized/Modbus protocol
10. Maintenance management
11. Provide PC software to visualized operation
Built-in BMS functionWhat is our product
Stored Energy Solutions for a Demanding World!
Monitor
1. Single cell voltage
2. Module voltage/current
3. Module capacity
4. Module/ambient
temperature
5. Cumulative
Charge/discharge KWH
6. …
Protection
1. Cell over/under voltage
2. Module over/under voltage
3. Over/under temperature
4. Charge/discharge over-
current
5. Short-circuit
6. Communication fail
7. …
Communication port
1. RS232
2. RS485
Built-in BMS functionWhat is our product
BMS protection parameterWhat is our product
BMS function Description Active point
Single cell over-charge
Over-charge protection threshold voltage
3.80±0.02V
Over-charge protection delay time 1.0-2.5s
Single-cell over-discharge
Over-discharge protection threshold voltage
2.80±0.02V
Over-discharge protection delay time
1.0-2.5s
Discharge recover threshold voltage 3.1±0.02V
Module over charge
Over-charge protection threshold voltage
56.0±0.3V
Over-charge protection delay time 1.0-2.5s
Over-charge recover threshold voltage
54.5±0.3V
Module over discharge
Over-discharge protection threshold voltage
42±0.3V
Over-discharge protection delay time
1.0-2.5s
Discharge recover threshold voltage 48.00±0.02V
Over current protection
Over-current protection delay time 1 in discharge
5.0±2s
Over-current protection 2 in discharge 90±4A
Over-current protection delay time 2 in discharge
500±50ms
Over-Current protection in charge 50±3A
Short circuit
Short circuit protection 150±10A
Protection conditionLoad short
circuit
detection delay time About 500us
Recover conditionLoad cut-off /
charge module
Over Temperature
protection
High temperature protection in charge 70±3℃
Recover temperature in charge 60±3℃
High temperature protection in discharge 70±3℃
Recover temperature in discharge 60±3℃
Low temperature protection in charge 0±3℃
Recover temperature in charge 5±3℃
Low temperature protection in discharge -10±3℃
Recover temperature in discharge 0±3℃
No. Name Functions Remark
1 SOC Indicators for capacityThere are four green LED lights in front panel indicating SOC. SOC is short for state of charge. Each SOC LED light
represents 25% of rated capacity
CapacityLED Status
● ● ● ●
LED1 LED2 LED3 LED4
0-25% ON OFF OFF OFF
25%-50% ON ON OFF OFF
50%-75% ON ON ON OFF
75%-100% ON ON ON ON
Battery interfaceWhat is our product
No. Name Functions Remark
4 ADDAddress of
communication
ADD is applicable to modules connected in parallel. ADD consists of four binary bits, and maximum quantity of
batteries connected in parallel is 16pcs .
Battery interfaceWhat is our product
2 ALM Indicator for alarms There is one red LED light in front panel indicating alarms.
3 RUN Indicator for running status There is one green LED light in front panel indicating running status
Battery Status IndicatorRUN ALM SOC
Remark● ● ● ● ● ●
OFF or sleep mode / OFF OFF OFF OFF OFF OFF ——
Idle Normal0.25S ON3.75S OFF
OFF Battery SOC
Charge Normal0.5S ON0.5S OFF
OFF Battery SOC
Discharge Normal Continuous on OFF Battery SOC
Charge/discharge/Idle Protection According to battery
statusFlash ON OFF
Over-voltage under voltage ALM not flash
Charge/discharge/Idle BMS Fail OFF Continuous ON OFF Hardware fail
Battery interfaceWhat is our product
No. Name Functions Remark
5 RS232 Up-link communication portIt is adopting RS-232 series port to upload data, it only support single
battery communication. Also use for upgrading BMS firmware.
6 RS485Cascading communication
portIt is adopting RS485 series port communication pattern to upload data. It
can support multiple battery paralleling communication
RJ45 pins Definition
1 GND
2 RS485_A
3 RS485_B
4,5,6,7,8 Void
Battery interfaceWhat is our product
No. Name Functions Remark
7 RESET Reset buttonPress RESET button when abnormity occurs to assure stability of battery
performance.
8 Dry contact Dry contact indicators
Failure Alarm: indicate BMS or battery fail including but not limited to charge and discharge MOS fail, cell voltage under 0.5V, NTC disconnect.
Protection Alarm: Output short circuit, charge and discharge over current, charge and discharge over temperature/low temperature.
9 Power switch ON/OFF switchWhen turn-off, battery get into sleep mode, and cut-off output, the alarm
output also will be stopped.
Battery interfaceWhat is our product
No. Name Functions Remark
10 Battery Output Terminals for battery outputUsing terminals with four cores. Polarities are +, -, +, - from left to right.
The two ‘+’ and ‘-’ are equal relatively
11 LCD (optional) Display battery information Battery status, cell status, firmware version, protection/alarm
12 GND Ground screwConnect earth by flexible cable above 16AWG through earth connecting
hole on right side of cabinet back, assure well connection.
Battery interfaceWhat is our product
13Maintenance
InterfaceUsed for battery
maintenance
Using for measure cell/cells voltage and resistance.
Charge cell/cells directly with 2A current max.
Battery interfaceWhat is our product
Commissioning &Installation
• Battery maintenance should be carried out by the professional staff who are experienced and aware of the
preventive measures on the potential harm of the battery.
• Be care of the risk of electric shock for large current in case of battery short circuit, pay attention to the
following points during operation
• Remove watches, rings or other metal objects use tools with insulated handles
• Do not place tools or metal objects on the battery
• Do not direct access to the battery system to the mains grid power outlet
• Do not put the battery system into fire, do not use or storage the battery near to the high temperature source
• Do not use liquid or other objects placed into the battery system.
• Do not open or cut the battery, not to hit, throw or step on the battery
• Using special communication lithium battery charging rectifier power supply module to charge battery
• Do not to change default BMS parameters setting during usage
• The output interface of the system is still voltage when grid power cut, avoid electric shock or short circuit
when operation
• Please check if the box is damaged. If damaged, please immediately notify the supplier
• If you find leaking liquid or white powder residue on product, prohibit operation.
Do’s & Don’tWhat is our product
Stored Energy Solutions for a Demanding World!
Commissioning What is our product
Items Check point Judgment Result
1 Appearance
Module surface should be clean without rust, no scratch, no deformation and mechanical damage, no leakage phenomenon, interface contact no rust;
Barcode and trademark is clear.
□With clear surface
□ No leakage or erosion;
□ No physical damage
□ Barcode is clear
□ Trademark is clear
2 ConnectionBattery modules are fixed in cabinet properly;
Screws for connection are tighten properly.
□ Cable layout accordingly
□ Battery module fasten well
□ Screw tighten properly
3Performance
inspection
OCV: 48.9-51.0V
Normal charging test:
1) Set up charge voltage 54V, charge current 0.2C, Voltage range 48.0-54.0V Charge for 10s;
2) RUN indicator light Intermittent flash;
Normal discharge test:
1) Set up discharge current 0.2C, voltage range 46-50V, discharge time 5S;
2) RUN indicator always light-on.
□ OCV is in range
□ System can do charging
□ System can do discharging
4 BMS inspection
Battery module can communication with computer software successfully;
Data of battery voltage from upper computer software is consistent with manual tested OCV.
□ Can read data from computer software;
□ Data from upper computer software is correct.
No. Tool Items Remarks for Use
T1 Insulation gloves Insulation protection for body
T2 Insulation taps Insulation protection for tools
T3 Screw drivers Fix the cables of the batteries & power plant
T4 Multi meter (Fluke) Measure the module voltage in commission
T5 Current meter (Fluke) Measure the module current in commission
T6 USB to RS485 cable For communication between the batteries and laptop
T7 Laptop Operate the software
Pre-installationWhat is our product
Stored Energy Solutions for a Demanding World!
Pre-installationWhat is our product
Stored Energy Solutions for a Demanding World!
1. Whether the cabinet is stable to the ground
2. Whether passageway for maintenance is reserved
3. The distance between the battery and the heat source shall be more than 0.5 meters; the batteries
shall be installed in the bottom of the cabinet
4. Suggest the user to make modifications if the condition is not suitable. A memorandum should be
kept after modification.
Check of the installation conditionWhat is our product
Stored Energy Solutions for a Demanding World!
a) The battery shall not be crashed anyway;
b) The screws for the battery handle shall not be bumped with the rack;
c) The direction of the front case of the battery shall be right.
d) The batteries shall be fixed with the rack via the handles
During InstallationWhat is our product
Flexible InstallationWhat is our product
Four direction installation
48NPFC70 module can support 4 direction installation.
Stored Energy Solutions for a Demanding World!
1. Connect GND for the batteries
2. Connect and tight the power cables of batteries to cabinet terminal or switching power supply.
(The battery gaps shall be more than 10mm.)
3. Connect the communication cables of batteries to computer
4. Switch on the battery switch.
ConnectionWhat is our product
Not Recommend
paralleling batteriesWhat is our product
OK, but not good Good choice
Stored Energy Solutions for a Demanding World!
• Check the screws and other connection to ensure a reliable installation.
• Have a data read test for the batteries with software, and download the
information into the computer. If the displays passed, then we can know the
battery is well and the parameter settings are right.
• Please fill in related forms after installation and debugging, check and record
battery conditions. Ask the user to sign and confirm the records.
• Please turn off the switch of the batteries if main power is not connected.
• Please recharge the battery before put into use according to operation manual, or
it will do great harm to battery.
After-installationWhat is our product
Stored Energy Solutions for a Demanding World!
Power plant settingWhat is our product
No. Parameters Units Defaults
1 Float charge voltage V 54.0
2 Equalization charge voltage V NA or 54.1
3 Standard charge current A 0.2C
4 Charge current limitation A 0.5C ~ 1.0C
5 Equalization charge interval day NA
6 Equalization charge duration h NA
7 Condition to equalization charge A NA
8 Condition to float charge A 0.05C
9 LVLD (Low voltage load disconnection) V > 43.2
10 LVBD (Low voltage battery disconnection) V > 40.5
11 Restore voltage for LVBD V /
12 Temperature compensation for float charge -mV/℃ NA
13 Temperature compensation for equalization charge -mV/℃ NA
PC software setting
Stored Energy Solutions for a Demanding World!
• We provide 485_to_USB adapter data cable. This module converts
485 signal to USB signal for PC.
ToolsWhat is our product
Stored Energy Solutions for a Demanding World!
• Desktop → My Computer → Popup Right Menus → Properties → Device Manager
Check COM portWhat is our product
ATTENTION: WIN7/WIN8, this Software must be used by Administrator.
(click right mouse on software figure, then select ‘run by administrator’)
Stored Energy Solutions for a Demanding World!
PC interfaceWhat is our product
Stored Energy Solutions for a Demanding World!
PC interfaceWhat is our product
Stored Energy Solutions for a Demanding World!
PC interfaceWhat is our product
Stored Energy Solutions for a Demanding World!
PC interfaceWhat is our product
Stored Energy Solutions for a Demanding World!
PC interfaceWhat is our product
Maintenance
In order to assure service life, the batteries should be correctly inspected and maintained. Maintenance procedures are
recommended as follows:
1 Monthly Maintenance
— Keep the battery-room clean.
— Measure and record the ambient temperature of the battery-room.
— Check each battery’s cleanness; check damage and overheating trace of the terminal, container and lid.
— Measure and record the total voltage and current of the online battery system to make sure no abnormal system issue.
2 Quarterly Maintenance
— Repeat monthly inspection.
— Discharge battery and recharge battery to 80%SOC
— Measure and record voltage of individual cell during discharge
3 Yearly Maintenance
— Repeat quarterly maintenance and inspection.
— Check whether connectors are loose or not and tight them
— Make a discharge test to check with exact load, discharging 50% of rated capacity.
Maintenance in warehouseWhat is our product
54
1. Discharge test Periodicity
Optional every 3 months per once.
2. Rate of Discharge
Discharge current according to load power and discharge rate no more than 0.2C.
3. Depth of discharge
a) 50%DOD;
b) Discharge end voltage: 48V.
Maintenance for long floating batteryWhat is our product
1. Insufficient Charge
If charge voltage is not set correctly (lower than 3.8Vpc or 54.75V per 48V string), the battery system
will in an insufficient charge state, which may not impact battery service life, but may reduce battery
backup time as request.
2. Over Charge
If charge voltage is not set correctly (higher than 3.8Vpc individual or 54.75V per 48V string), the
battery system will be over charged, which may impact battery service life and even bring further safety
issue.
3. Too low or too high temperature
Too low temperature will affect the capacity of battery when discharge, and may destroy battery when
charge. While too high temperature will also cause problems, such as water loss, life decrease, thermal
runaway, deformation, etc.
Maintenance precautionsWhat is our product
Reasons:1. If communication failed and LED turn off which means BMS is not work, might be caused by B-/B+ cable or
sensor cable looseness;2. LED flashing but communication failed, might be used wrong PC software;3. LED flashing but communication failed, might be used wrong 485 to USB communication cable;4. LED flashing but communication failed, might be connection of 485 to USB communication cable is not well;5. LED flashing but communication failed, might be chosen wrong ADD channel;6. LED flashing but communication failed, might be 485 to USB communication cable broken.7. LED flashing but communication failed, might be BMS failed.
Solution:1. For reason a): Make sure B-/B+ cable and all sensor cables are connected well, if still looseness, please change
new cables;2. For reason b): Use right PC software;3. For reason c): Replace right 485 to USB communication cable;4. For reason d): Detect connection of 485 to USB communication cable, if still looseness, please change new
cables;5. For reason e): Choose right ADD channel;6. For reason f): Replace right 485 to USB communication cable;7. For reason g): Make sure U6 component is failed, if yes, return to the factory for repair.
Probable failures & solutions: communication
What is our product
Status Probable Reason How to check Solution
Battery module can'tdischarge
1)Low voltage protection is activated
Check if battery is over discharged.Read BMS if individual cell voltage has been lower than 2.5V
Charging the battery for at least 3hours
2)Over temperature protection
Check if battery temperature is higher than 70℃ or lower than 0℃
Regulate environment temperature to between 65℃to -5 ℃
3) Output is short circuit Visual checkRelieve short circuit and charging
4) Over load protection
Check if the load capacity (A) is higher then the limitation of battery module discharge current:1, Measure load capacity, or2, Check history data of
Remove unimportant load and recharge battery;Or, add more battery modules in parallel for proper backup
5) System failure
Check if BMS is fail1, check if is on working properlyIf yes, 2, check if indicator light of battery module is on; 3, battery information data can be monitor
Replace the BMS in battery module if it is failure
Battery module can'tcharge
6)In full charged, normal stopped by charging control
Check if battery is fully charged1, Read BMS if individual cell voltage is higher than 3.7V
Skip
7)Over temperature protection
Check if battery temperature is higher than 70℃ or lower than -10℃
Waiting for environment temperature be below 65 ℃ or above -5℃
8) System failure As issue 5) As issue 5)
Probable failures & solutions:What is our product