chinatcs · 6. can be equipped with type zn63a (vs1) and imported type vd4 vacuum circuit breaker....
TRANSCRIPT
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1)
A.C METALCLAD REMOVABLE SWITCHGEAR
FOR INDOOR USE
CHINATCS2001.09
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 1
KYN28A-12 (GZS1)
A.C Metalclad Removable Switchgear for Indoor Use
--------The Leader in Switchgear Up to 12kV
1. The cabinet is set up with the parts made of by aluminum-coated zinc plates.
2. Complete metalclad and isolated.
3. All operations can be carried out with the cubicle door closed.
4. The degree of protection of the enclosure is IP4X, which can prevent sundries and reptiles
from entering.
5. Simple and reliable interlocking system can avoid misoperations.
6. Can be equipped with type ZN63A (VS1) and imported type VD4 vacuum circuit breaker.
7. Few maintenance for the vacuum circuit breaker and its operation device in the H.V
compartment.
8. It is easy to replace circuit breaker, and the truck is provided with perfect
interchangeability.
9. The cabinet can be mounted against the wall and maintenance can be carried out in front
of the cubicles, thus less room required.
10. Easy connections for secondary circuit in the wiring channel with rich space.
11. Rich area for connection enough cables in cable compartment.
12. The cable compartment can be inspected easily through the front inspection window.
13. Quick earthing switch for earthling and short-circuit case.
14. Conforming to the standards of GB3906, DL404, and IEC298.
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 2
1 General
1.1 Summary
Type KYN28A-12 (GZS1) A.C Metalclad Removable Switchgear manufactured by Tianshui
Changcheng Switchgear Factory (called the switchgear or the switchgear in the following)
which is indoor power distributing equipment of 3-phase, A.C 50Hz system, is suitable to be
used to receive and distribute the electric power of 3.6 ~ 12 kV power system, as well as to
control, protect and monitor the circuit. The switchgear conforms to the standards of GB3906,
DL404, IEC298 and etc. The switchgear is provided with called 5-prevention function, that is:
Prevent the circuit-breaker from misoperation;
Prevent the truck from being pushed and pulled on-load;
Prevent the earthing switch from being closed while the switchgear is electrified;
Prevent the switchgear from being electrified with the earthing switch being closed;
Prevent entering electrified compartment.
The switchgear can be equipped with type ZN63A (VS1) as well as imported type VD4
vacuum circuit breaker.
1.2 Service Conditions
The switchgear can meet the requirement specified in the national standard GB11022 as well
as the requirement of condensation and dirty grade II.
2 Technical parameter
2.1 Technical Parameter of the Switchgear
The technical parameter of the switchgear is shown in table 1.
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 3
Table 1 The Technical Parameter of the Switchgear
Item Unit DataRated voltage kV 3.6 7.2 12
Power frequency withstand voltage(1 min) (r.m.s) kV 42Rated
insulationlevel Lightning impulse withstand voltage
(full wave) kV 75
Rated frequency Hz 50Rated current A 630,1250,1600,2000,2500,31504s withstand current (r.m.s.) kA 20,25,31.5,40,50Rated withstand current (peak) kA 50,63,80,100,130
Enclosure IP4XProtectiondegree With the door of circuit-breaker compartment open IP2X
2.2 The Technical Parameter of Type ZN63A Vacuum Circuit-breaker
The Technical parameter of the type ZN63A vacuum circuit breaker is shown in table 2.
Table 2 The Technical parameter of the type ZN63A vacuum circuit-breaker
Item Unit DataRated voltage kA 3.6, 7.2, 12
Power frequency withstand voltage(1 min) (r.m.s) 42
Lightning impulse withstand voltage(peak value before breaking) 75
Ratedinsulationlevel Lightning impulse withstand voltage
(peak value after breaking)
kV
75
Rated frequency Hz 50Rated current A 630,1250,1600,2000,2500.3150Single and back-to-bank capacitor bank breaking current A 630/400Rated short-circuit breaking current 20,25,31.5,40,50Rated short-circuit withstand current (4s r.m.s) 20,25,31.5,40,50Rated short-circuit marking current (peak) 50,63,100,130Rated peak withstand current
kA
50,63,100,130Rated operating sequence O-180s-CO-180s-COAuto-reclosing operating sequence O-0.3s-CO-180s-COClosing time 100Opening time 50Arcing time
ms15
Breaking times aganist rated short-circuit breaking current times 50 (30*)Mechanical endurance cycles 20000Accumulating thickness of permissive consumption forfixed and movable contacts mm 3
Note:* The breaker times against rated short circuit breaking current is 30 times when the rated shortcircuit breaking current is 40kA.
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 4
2.3 The Technical Parameter of Operating device
The technical parameter of operating device is shown in table 3.
Table 3 Technical Parameter of Operating Device
Item Unit Data
Closing coil DC220, 110AC220, 110Rated operating
voltage Opening coilV
Closing coilPower of coil
Opening coilW 245
Power of stored-energy motor W 70
Rated voltage of closing coil of stored-energy motor V DC220, 110
Energy storage time s 15
3 Overall Dimension and Weight
3.1 Cabinet
The overall dimension and weight of cabinet is shown in Figure 1 and table 4.
Table 4 The Overall Dimension and Weight of Cabinet
Height A (mm) 2365
Rated current of sub busbar up to 1250A, raged short timewithstand current being 31.5kA 800Width B
(mm) Rated current of sub busbar above 1250A 1000
Cable incoming and outgoing feeder 1500Depth C(mm) Overhead incoming and outgoing feeder 1800
Weight (kg) 800 ~ 1200
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 5
Fig 1 The overall dimension of the switchgear
3.2 Circuit Breaker
The overall dimension of type ZN63A vacuum circuit breaker is shown in Figure 2(a) andFigure 2(b).
Figure 2(a) The overall dimension of type ZN63A-12/1250-31.5 vacuum circuit breaker
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 6
Figure 2(b) The overall dimension of type ZN63A-12/3150-40 vacuum circuit breaker
4 Structure of Switchgear
The switchgear consists of 2 parts of fixed cabinet and removable parts (called truck). The
typical structure drawing of the switchgear is shown in Figure 3 and Figure 4. The enclosure
and all partitions of each functional units are all made by aluminum-coated zinc plate. The
degree of protection of the enclosure is IP4X, the degree of protection with the door of
circuit-breaker compartment open is IP2X.
The switchgear can be equipped with type ZN63A (VS1) vacuum circuit breaker, The
switchgear can be arranged in double rows, that is, arranged in back-to-back or face-to-
face way. Because the switchgear can be installed and adjusted from the front, it can be
installed against wall to save floor area as well as increase the safety of the switchgear and
the flexibility for installation.
4.1 Enclosure and Partitions
The enclosure and partitions of the switchgear is set up by aluminum-coated zinc plate
which is machined and bent by NC machine, so the finished switchgears are provided with
unity in size. The aluminum-coated zinc plate has excellent corrosion-proof and oxidation-
resistance function as well as high mechanical intensity, The switchgear is separated into
circuit-breaker compartment, busbar compartment, cable compartment, and instrument
compartment (LV compartment) by partitions. The enclosure for every unit is earthed
reliably.
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 7
4.2 Truck
The framework of truck is set up by thin steel plate through welding and riveting, the thin
steel plate is processed by laser cutting machine. The truck can be divided into circuit-
breaker truck, voltage transformer truck, measuring truck, and etc. the trucks with same
specification can be interchanged. The truck has test position and service position inside
the cabinet. The locking device is provided to every position in order to prevent the truck
from being moved away from its position. The truck can not be removed unless the
interlocking device being released. For example, the circuit-breaker truck can not be
removed before the circuit-breaker opens.
A ---- Busbar compartment B ---- Circuit breaker truck compartment
C ---- Cable compartment D ---- Instrument compartment1--Pressure releasing device; 2--Enclosure; 3--Branch busbar; 4--Busbar bushing; 5--Main busbar;
6--Fixed contacts device; 7--Fixed contacts box; 8--Current transformer; 9--Earthing switch;
10--Cable; 11--Surge arrester; 12--Main earthing busbar; 13--Partition; 14--Shutter;
15--Secondary plug; 16--Circuit-breaker truck; 17--Heater; 18--Removable partition;
19--Operating device for earthing switch; 20--Control busbar; 21--Cable cover
Figure 3 Typical structural drawing of the switchgear (being installed free from wall)
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 8
A ---- Busbar compartment B ---- Circuit breaker truck compartment
C ---- Cable compartment D ---- Instrument compartment1--Pressure releasing device; 2--Enclosure; 3--Branch busbar; 4--Busbar bushing; 5--Main busbar;
6--Fixed contacts device; 7--Fixed contacts box; 8--Current transformer; 9--Earthing switch;
10--Cable; 11--Surge arrester; 12--Main earthing busbar; 13--Partition; 14--Shutter;
15--Secondary plug; 16--Circuit-breaker truck; 17--Heater; 18--Removable partition;
19--Operating device for earthing switch; 20--Control busbar; 21--Cable cover
Figure 4 Typical structural drawing of the switchgear (being installed against wall)
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 9
4.3 Compartments
4.3.1 Circuit Breaker CompartmentSpecial rail are located inside the circuit-breaker compartment for the truck to move and work
in, the circuit-breaker can move between service position and test position in the rail. The
shutter (14) is mounted on the rear wall of circuit-breaker compartment. The shutter (14) can
open automatically during moving the truck from test position to service position, the shutter
can close completely after moving the truck from service position to test position, which
prevents the operators from touching the live parts. The truck can be operated with the
cabinet door closed. Through the inspection window, the position of truck, the ON/OFF
buttons (marking the circuit-breaker closing/opening) on the truck, ON/OFF mechanical
position indicator can be observed as well as energy-stored/energy-released indicator can be
observed clearly.
4.3.2 Busbar CompartmentThe busbar (5) is led from one switchgear to another, and fixed with branch busbar (3) and
fixed contacts terminal box. All busbar can be sealed with thermal shrinkage insulation
bushing in accordance with the requirement of users. Flat sub busbar is connected with fixed
contact terminal box and main busbar by bolts without any other wire clips and insulators. The
connecting bolts on the busbar can be enclosed with insulation bushing and cap. The busbar
is fixed with busbar bushing (4) when passing through the partitions, which can prevent the
default from extending to adjacent switchgear when internal arc appears, and increase the
intensity of busbar.
4.3.3 Cable CompartmentThe current transformer (8) and earthing switch (9) can be mounted at the top, rear wall and
front wall of the cable compartment, the surge arrester (11) can be mounted inside the cable
compartment. The operator can enter the cabinet from front to mount the cable after the truck
(16) and removable partition (18) being removed. Special cable connecting conductor is
located in the cable compartment, the removable metal cable cover (21) with slot is located
under the cable compartment, thereby, the cable connecting at site is made convenient.
4.3.4 LV CompartmentRelays, protective elements, instruments, voltage indicators and secondary devices for
special requirement can all be mounted in LV compartment. The control wires are placed in
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 10
the wire channel with enough area and closed with metal cover, the wire channel on the left
side is designed for control wires, the wire channel for the secondary wire of the switchgear
itself is located on the right side.
4.4 Interlocking Device
The switchgear has reliable interlocking device, which can guarantee the safety of operators
and the switchgear. It s function is as following:
a) The truck can be moved from the test position to the service position only when the
earthing switch is in open position.
b) The circuit breaker can not be operated before the truck being locked in the test or the
service position.
c) The secondary plug can not be removed with the truck in the service position.
d) The truck can not be moved from the test position to the service position with the
earthing switch closed.
e) The earthing switch can be operated only when the truck is in the test position.
4.5 Pressure Releasing Device
The pressure releasing devices are designed in truck compartment, busbar compartment as
well as cable compartment. When the air pressure inside the switchgear rises because of the
internal fault arc appearing on the circuit-breaker or busbar, the special seal ring on the door
can seal the front part of the cabinet, and the pressure releasing metal plate on the top can be
opened automatically, thereby, the gas is given out and the pressure inside goes down, so the
operators and the switchgear is in safety.
4.6 Interlocking between secondary plug and truck
The secondary wires of the switchgear and truck are connected by secondary plug, the
movable contacts of the secondary plug are connected with the truck by a nylon blowpipe,
The secondary fixed contact holder is located on the top right of the truck compartment. The
secondary plug can be pushed in and pulled out only when the truck is in the test position, on
the other hand, the secondary plug is licked and can not be removed when the truck is in the
service position.
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 11
4.7 Earthing Device
The earthing copper plate (10mm x 40mm) is designed in the cable compartment, it can pass
throng the neighboring switchgears and connected with the cabinet reliably. It is used for the
parts to be directly earthed, because the cabinet is assembled by aluminum-coated zinc plate,
the whole cabinet is earthed reliably, which makes the operators safe when they touch the
enclosure.
5 Installation and Adjustment
5.1 Type of Foundation
5.1.1 The construction of foundation for installing the switchgears should conform to the
Technical Specification for Electric Power Construction and Inspection.
5.1.2 The foundation for the switchgears should be cast for 2 times. For the first time, the
foundation for the structural components used to install the switchgears such as angle
steel, square steel or channel steel, should be cast; for the second time, the
supplementary layer of concrete surface should be cast, the thickness of which is
60mm. The supplementary layer of concrete surface should be lower than the
structural components used to install the switchgears for 1~3mm.
5.1.3 The foundation frame drawing is shown in Figure 5.
5.1.4 The foundation frame should be installed in order, the technical deviation for installing
the foundation frame is 1mm/mm2.
5.2 Installation of the Switchgear
5.2.1 The size of installing foundation and the installing size of the switchgear is shown in
Figure 6 and Figure 7.
5.2.2 The operating corridor in front of the switchgears should be 2.5m when the switchgears
are installed in single row; and the operating corridor between two rows of the
switchgears should be 3m when the switchgears are installed in double rows. The
installing drawing of switchgears installed face to face and against the wall is shown in
Figure 8.
5.2.3 Move the switchgear to the specified position according to the requirement and
drawings. If the switchgears in one roe is too many, the arrangement should begin an
the center.
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 12
5.2.4 Special transporting tools, such as cranes and forks, are necessary, it is not permitted
to use rollers and crowbars.
5.2.5 Pull the circuit breaker trucks out of the switchgears, and keep them appropriately.
5.2.6 Loosen the screws mounting the horizontal partition (18) under the circuit-breaker
compartment, and remove the horizontal partition (18).
5.2.7 Loosen and remove the cable cover (21).
5.2.8 Remove the cover of the control wire channel on the left side of the switchgear, and the
one on the right side.
5.2.9 Remove the hoisting plated and fastenings.
5.2.10 The rear cover of the switchgear and the cover of busbar compartment can be moved
away for installing when the switchgear is installed from wall.
5.2.11 Install the switchgear on the foundation in accordance with specified sequence. The
levelness in horizontal and vertical direction should not exceed 2mm.
5.2.12 After being combined (arranged) on the foundation, the switchgears should be
connected with the foundation frame by foundation bolts or by welding.
6 Installation of Busbar
The busbar in the switchgear are rectangular busbar and divided into sections, the busbar for
switchgear with different current are only different from quantity and specification. The
following should be complied with when installing the busbar.
6.1 Cleaning the busbar with soft cloth that is clean and dry, check whether there isdamage on the insulating bushing, apply conductive paste or neutral vaseline onthe connecting position of busbar.
6.2 Install the busbar in sequence, connect the sections of busbars andcorresponding sub busbar together, insert proper pads and then screw downwith bolts.
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 13
7 Earthing Device
7.1 Connect the earthing busbar (12) of all switchgear with prepared connectionboard.
7.2 Connect all earthing wires inside the switchgear.
7.3 Connect the foundation frame with the earthing plate.
7.4 Connect the earthing wire of earthing contact with the earthing busbar of thedistributing panel.
Width (A) Depth (B) M N L L11500 (cable incoming and outgoing) 1450 880800 1800 (overhead incoming and outgoing) 630 800 1750 10401500 (cable incoming and outgoing) 1450 8801000 1800 (overhead incoming and outgoing) 830 1000 1750 1040
Figure 5 The foundation frame drawing of the switchgear
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 14
Figure 6(a) The foundation drawing for the switchgears
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 15
Depth L1500 14501800 1750
Figure 6(b) The foundation drawing for the switchgears
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 16
A-AThe switchgears installed free from wall
A-AThe switchgears installed against wall
C-direction
Figure 6 (c) The foundation drawing for the switchgears
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 17
Width of theswitchgear
(A)Depth of the switchgear (b) L1 L2 L3
1500(cable incoming & outgoing) 880800
1500(overhead incoming & outgoing)530 630
990
1500(cable incoming & outgoing) 8801000
1500(overhead incoming & outgoing)730 830
990
Figure 7 Drawing for installing dimension of the switchgears
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 18
Figure 8 The installing drawing for the switchgears installed face-to-face against wall
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 19
8 Installation of Busbar Bridge
The installing dimension of the busbar bridge is shown in Figure 9.
Figure 9 The installing dimension of the busbar bridge
9 Installing dimension for overhead incoming scheme
The installing dimension for overhead incoming scheme is shown in Figure 10.
Figure 10 The installing dimension for overhead incoming scheme
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 20
10 Primary Circuit Scheme
The primary circuit scheme of the switchgears is shown in table 5.
11 Secondary Circuit Scheme
11.1 The electric wiring diagram of circuit-breaker truck is shown is Figure 11.
11.2 The typical control circuit (AC operation) of the switchgear with ZN63A vacuumcircuit-breaker (VCB) is shown in Figure 12.
11.3 The typical control circuit (DC operation) of the switchgear with ZN63A vacuumcircuit-breaker (VCB) is shown in Figure 12.
12 Ordering Information
Following information should be supplied when ordering:
12.1 Primary scheme serial No., primary scheme system drawings, arrangementdrawings and layout drawings.
12.2 Secondary functional drawings, arrangement drawings of terminals.
The terminals will be arranged in accordance with the standard mode by themanufacturer if the arrangement drawings of terminals are not supplied.
12.3 The type, specification and quantity of the electric components inside theswitchgears.
12.4 Summary schedule of electric equipments.
12.5 The span across two rows of switchgears and height when busbar bridge
(busbar bridge between tow rows of switchgears or the ones between the walland swtichgear) is needed.
12.6 If the switchgears is used in special condition, it should be specified whenordering.
12.7 The kinds and quantity of extra accessories and spare parts requited.
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 21
The secondary electric diagram of the switchgear with DC control.(The switchgear without anti-jumping function, the circuit-breaker with anti-jumping function.)
The secondary electric diagram of the switchgear with AC control.(The switchgear without anti-jumping function, the circuit-breaker with anti-jumping function.)
No. Symbol Name1 S1 Micro-switch for energy storage2 S2 Auxiliary switch interlocked with the principal axis3 K0 Intermediate relay4 V1~V3 Rectifying elements5 HQ Closing electromagnet6 TQ Opening electromagnet7 M Motor for energy storage8 Y1~Y3 Electromagnet for over-current release9 SW, YW Indicator for position of truck
Figure 11(a) The Electric diagram of circuit-breaker (with anti-jumping function)
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 22
The secondary electric diagram of the switchgear with DC control(The switchgear with anti-jumping function, the circuit-breaker without anti-jumping function)
The secondary electric diagram of the switchgear with AC control(The switchgear with anti-jumping function, the circuit-breaker without anti-jumping function)
No. Symbol Name1 S1 Micro-switch for energy storage2 S2 Auxiliary switch interlocked with the principal axis3 K0 Intermediate relay4 V1~V3 Rectifying elements5 HQ Closing electromagnet6 TQ Opening electromagnet7 M Motor for energy storage8 Y1~Y3 Electromagnet for over-current release9 SW, YW Indicator for position of truck
Figure 11(b) The electric diagram circuit-breaker (without anti-jumping function)
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 23
KK:LW2-Z-a.4.6a.40.20/F8; (HA,TA):LA18-22LD,HD,UD(1LD,1HD):AD1-25/21 220V(XD5) 1RD,2RD,3RD,4RD,HRD:RT19-16/6AHK:KN3-A 1Z1D; SW,YW:F1-41/Y.H(The indication ;amp of truck position)
The switchgear without anti-jumping function
KK:LW2-Z-a.4.6a.40.20/F8; (HA,TA):LA18-22LD,HD,UD(1LD,1HD):AS1-25/21 220V(XD5) 1RD,2RD,3RD,4RD,HRD:RT19-16/6ATBJ:DZ-52/220V;HK:KN3-A 1Z1D SW,YW:F1-41/Y.H(The indication ;amp of truck position)
The switchgear with anti-jumping function
Figure 12 The typical control circuit for the switchgear equippedwith type ZN63A vacuum circuit-breaker (AC operation)
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 24
KK:LW2-Z-a.4.6a.40.20/F8; (HA,TA):LA18-22;ZG11-50W/1KLD,HD,UD(1LD,1HD):AD1-25/21 220V(XD5) 1RD,2RD,3RD,4RD,HRD:RT19-16/6AHK:KN3-A 1Z1D; SW,YW:F1-41/Y.H(The indication ;amp of truck position)
The switchgear without anti-jumping function
KK:LW2-Z-a.4.6a.40.20/F8; (HA,TA):LA18-22;ZG11-50W/1KLD,HD,UD(1LD,1HD):AS1-25/21 220V(XD5) 1RD,2RD,3RD,4RD,HRD:RT19-16/6ATBJ:DZ-284/220V;HK:KN3-A 1Z1D SW,YW:F1-41/Y.H(The indication ;amp of truck position)
The switchgear with anti-jumping function
Figure 13 The typical control circuit for the switchgear equippedwith type ZN63A vacuum circuit-breaker (DC operation)
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 25
Appl
icat
ion
exam
ple
(1) o
f mai
n ci
rcui
t sch
eme
Appl
icat
ion
exam
ple
(1) o
f mai
n ci
rcui
t sch
eme
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 26
Table 5 Main Circuit Schemes
Scheme serial No. 001 002 003 004 005
Primary system diagrams
Rated current (A) 630 ~ 3150ZN63A (VS1)
VCBVD4
1 1 1 1 1
LZZBJ1-10GYLZZB1-10GYCTLZZB-10GY
2 2 2 3 3
RZL-10VT
REL-10HV Fuse RN2-10
Earthing Switch JN15 1 1 1
Main Prim
ary components
Surge arrester
Application Power receiving& Feeding
Power receiving& Feeding
Power receiving& Feeding
Power receiving& Feeding
Power receiving& Feeding
Remarks Width of the switchgears is 1000m when their rated current is above 1600A.
Scheme serial No. 006 007 008 009 010
Primary system diagrams
Rated current (A) 630 ~ 3150ZN63A (VS1)
VCBVD4
1 1 1 1 1
LZZBJ1-10GYLZZB1-10GYCTLZZB-10GY
3 2 2 2 2
RZL-10VT
REL-10HV Fuse RN2-10
Earthing Switch JN15 1 1 1
Main Prim
ary components
Surge arrester 3
Application Power receiving& Feeding
Coupler(right)
Coupler(right)
Coupler(left)
Coupler(left)
Remarks Width of the switchgears is 1000m when their rated current is above 1600A.
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 27
Table 5 Main Circuit Schemes (Continuous)
Scheme serial No. 011 012 013 014 015
Primary system diagrams
Rated current (A) 630 ~ 3150ZN63A (VS1)
VCBVD4
1 1 1 1 1
LZZBJ1-10GYLZZB1-10GYCTLZZB-10GY
2 2 2 3 3
RZL-10VT
REL-10HV Fuse RN2-10
Earthing Switch JN15 1 1
Main Prim
ary components
Surge arrester
Application Coupler(right)
Coupler(right)
Coupler(left)
Coupler(left)
Overheadincoming (left
coupler)
Remarks Width of the switchgears is 1000m when their rated current is above 1600A.
Scheme serial No. 016 017 018 019 020
Primary system diagrams
Rated current (A) 630 ~ 3150ZN63A (VS1)
VCBVD4
1 1 1 1 1
LZZBJ1-10GYLZZB1-10GYCTLZZB-10GY
3 3 3 3 2
RZL-10VT
REL-10HV Fuse RN2-10 3 3
Earthing Switch JN15 1 1 1
Main Prim
ary components
Surge arrester
ApplicationOverhead
incoming (leftcoupler)
Overheadincoming (right
coupler)
Overheadincoming (right
coupler)
Overheadincoming (left
coupler)
Overheadincoming (left
coupler)
Remarks Width of the switchgears is 1000m when their rated current is above 1600A.
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 28
Table 5 Main Circuit Schemes (Continuous)
Scheme serial No. 021 022 023 024 025
Primary system diagrams
Rated current (A) 630 ~ 3150ZN63A (VS1)
VCBVD4
1 1 1 1 1
LZZBJ1-10GYLZZB1-10GYCTLZZB-10GY
3 3 2 2 2
RZL-10VT
REL-10HV Fuse RN2-10
Earthing Switch JN15 1 1 1
Main Prim
ary components
Surge arrester 3
ApplicationOverhead
incoming (rightcoupler)
Overheadincoming (right
coupler)
Overheadincoming and
outgoing
Remarks 1. Width of the switchgears is 1000m when their rated current is above 1600A.2. The depth of No.23, No.24 and No.25 is 1800mm.
Scheme serial No. 026 027 028 029 030
Primary system diagrams
Rated current (A) 630 ~ 3150ZN63A (VS1)
VCBVD4
1 1 1 1 1
LZZBJ1-10GYLZZB1-10GYCTLZZB-10GY
3 3 3 2 2
RZL-10VT
REL-10RZL-10 2 RZL-10 2
HV Fuse RN2-10 3 3Earthing Switch JN15 1 1 1
Main Prim
ary components
Surge arrester 3
ApplicationOverhead
incoming andoutgoing
Overheadincoming and
outgoing
Cable incoming& PT
Cable incoming& PT
Remarks 1. Width of the switchgears is 1000m when their rated current is above 1600A.2. The depth of No.26, No.28 and No.29 is 1800mm.
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 29
Table 5 Main Circuit Schemes (Continuous)
Scheme serial No. 031 032 033 034 035
Primary system diagrams
Rated current (A) 630 ~ 3150ZN63A (VS1)
VCBVD4
1 1 1 1 1
LZZBJ1-10GYLZZB1-10GYCTLZZB-10GY
2 3 3 3 2
RZL-10VT
REL-10RZL-10 2 RZL-10 2 RZL-10 2 RZL-10 2 RZL-10 3
HV Fuse RN2-10 3 3 3 3 3Earthing Switch JN15 1
Main Prim
ary components
Surge arrester 3 3
Application Cable incoming& PT
Cable incoming& PT
Cable incoming& PT
Cable incoming& PT
Cable incoming& PT
Remarks Width of the switchgears is 1000m when their rated current is above 1600A.
Scheme serial No. 036 037 038 039 040
Primary system diagrams
Rated current (A) 630 ~ 3150ZN63A (VS1)
VCBVD4
1 1
LZZBJ1-10GYLZZB1-10GYCTLZZB-10GY
2 2
RZL-10VT
REL-10REL-10 3 REL-10 3 RZL-10 2 REL-10 3 RZL-10 2
HV Fuse RN2-10 3 3 3 3 3Earthing Switch JN15 1
Main Prim
ary components
Surge arrester 3
Application Cable incoming& PT
Cable incoming& PT
Voltagemeasuring
Voltagemeasuring
Voltagemeasuring &
arrester
Remarks Width of the switchgears is 1000m when their rated current is above 1600A.
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 30
Table 5 Main Circuit Schemes (Continuous)
Scheme serial No. 041 042 043 044 045
Primary system diagrams
Rated current (A) 630 ~ 3150ZN63A (VS1)
VCBVD4
LZZBJ1-10GYLZZB1-10GYCTLZZB-10GY
RZL-10VT
REL-10REL-10 3 RZL-10 2 REL-10 3 RZL-10 2 RZL-10 2
HV Fuse RN2-10 3 3 3 3 3Earthing Switch JN15
Main Prim
ary components
Surge arrester 3 3 3
ApplicationVoltage
measuring &arrester
Voltagemeasuring &
arrester
Voltagemeasuring &
arrester
Voltagemeasuring &
busbar coupler
Voltagemeasuring &
busbar coupler
Remarks Width of the switchgears is 1000m when their rated current is above 1600A.
Scheme serial No. 046 047 048 049 050
Primary system diagrams
Rated current (A) 630 ~ 3150ZN63A (VS1)
VCBVD4
LZZBJ1-10GYLZZB1-10GYCTLZZB-10GY
RZL-10VT
REL-10REL-10 3 REL-10 3 RZL-10 2 RZL-10 2 REL-10 3
HV Fuse RN2-10 3 3 3 3 3Earthing Switch JN15
Main Prim
ary components
Surge arrester 3 3 3
ApplicationVoltage
measuring &busbar coupler
Voltagemeasuring &
busbar coupler
Voltagemeasuring &
arrester &busbar coupler
Voltagemeasuring &
arrester &busbar coupler
Voltagemeasuring &
arrester &busbar coupler
Remarks 1. Width of the switchgears is 1000m when their rated current is above 1600A.2. The depth of No.69, No.70 is 1800mm.
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 31
Table 5 Main Circuit Schemes (Continuous)
Scheme serial No. 051 052 053 054 055
Primary system diagrams
Rated current (A) 630 ~ 3150ZN63A (VS1)
VCBVD4
LZZBJ1-10GYLZZB1-10GYCTLZZB-10GY
RZL-10VT
REL-10REL-10 3
HV Fuse RN2-10 3Earthing Switch JN15
Main Prim
ary components
Surge arrester 3
Application
Voltagemeasuring &
arrester &busbar coupler
Busbar coupler Busbar coupler Isolating Isolating &coupler (left)
Remarks Width of the switchgears is 1000m when their rated current is above 1600A.
Scheme serial No. 056 057 058 059 060
Primary system diagrams
Rated current (A) 630 ~ 3150ZN63A (VS1)
VCBVD4
LZZBJ1-10GYLZZB1-10GYCTLZZB-10GY
RZL-10VT
REL-10RZL-10 2 RZL-10 2
HV Fuse RN2-10 3 3Earthing Switch JN15 1
Main Prim
ary components
Surge arrester
Application Isolating &(right) coupler
Isolating & (left)coupler &voltage
measuring
Isolating &(right) coupler &
voltagemeasuring
Outgoingconverting
phase
Outgoingconverting
phase
Remarks Width of the switchgears is 1000m when their rated current is above 1600A.
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 32
Table 5 Main Circuit Schemes (Continuous)
Scheme serial No. 061 062 063 064 065
Primary system diagrams
Rated current (A) 630 ~ 3150ZN63A (VS1)
VCBVD4
LZZBJ1-10GYLZZB1-10GYCTLZZB-10GY
2 2 3 3 2
RZL-10VT
REL-10RZL-10 2 RZL-10 2 RZL-10 2 RZL-10 2 REL-10 3
HV Fuse RN2-10 3 3 3 3 3Earthing Switch JN15
Main Prim
ary components
Surge arrester
Application Measure & leftcoupler
Measure & rightcoupler
Measure & leftcoupler
Measure & rightcoupler
Measure & leftcoupler
Remarks Width of the switchgears is 1000m when their rated current is above 1600A.
Scheme serial No. 066 067 068 069 070
Primary system diagrams
Rated current (A) 630 ~ 3150ZN63A (VS1)
VCBVD4
1 1
LZZBJ1-10GYLZZB1-10GYCTLZZB-10GY
2 3 3 2 2
RZL-10VT
REL-10REL-10 3 REL-10 3 REL-10 3 RZL-10 2 RZL-10 2
HV Fuse RN2-10 3 3 3 3 3Earthing Switch JN15
Main Prim
ary components
Surge arrester
Application Measure & rightcoupler
Measure & leftcoupler
Measure & rightcoupler
Incoming &measure
Incoming &measure
Remarks 1. Width of the switchgears is 1000m when their rated current is above 1600A.2. The depth of No.69, No.70 is 1800mm.
Tianshui Changcheng Switchgear Factory
KYN28A-12 (GZS1) 33
Table 5 Main Circuit Schemes (Continuous)
Scheme serial No. 071 072 073 074 075
Primary system diagrams
Rated current (A) 630 ~ 3150ZN63A (VS1)
VCBVD4
1 1
LZZBJ1-10GYLZZB1-10GYCTLZZB-10GY
2 2 2 3 3
RZL-10VT
REL-10RZL-10 2 RZL-10 2 RZL-10 2 RZL-10 2 RZL-10 2
HV Fuse RN2-10 3 3 3 3 3Earthing Switch JN15
Main Prim
ary components
Surge arrester
Application Incoming &measure
Incoming &measure
Incoming &measure
Incoming &measure
Incoming &measure
Remarks 1. Width of the switchgears is 1000m when their rated current is above 1600A.2. The depth of No.71, No.75 is 1800mm.
Scheme serial No. 076 077 078
Primary system diagrams
Rated current (A) 630 ~ 3150ZN63A (VS1)
VCBVD4
LZZBJ1-10GYLZZB1-10GYCTLZZB-10GY
3 CapacitorBM12.7-16-1 3
RZL-10VT
REL-10TransformerSC4-63/10 1
HV Fuse RN2-10 3 RN3-10 orRN1-10 3 RN3-10 or
RN1-10 3
Earthing Switch JN15
Main Prim
ary components
Surge arrester 3 3
Application Incoming &measure
Stationtransformer
Capacitorprotecting
Remarks 1. Width of the switchgears is 1000m when their rated current is above 1600A.2. The depth of No.76 1800mm.
Note: When the power receiving & power feeding scheme is used as power receiving,the earthing switch should be taken out.