600-volt secondary bus enclosure bulletin three-phase 340...
TRANSCRIPT
600-Volt Secondary Bus EnclosureThree-Phase
Pad-Mounted – Outdoor
Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com
Bulletin
340-062Page 1 2015
Overlapping door andenclosure flanges - withother features - providetamper resistance tomeet national andregional standards
Superlife finish includes phosphatizing, rust-inhibiting epoxy primer and Pad-Mount Green (Munsell 7GY 3.29/1.5) polyurethane top coat -over 5 mils dryOptional Color: Grey(Munsell 5BG 7.0/0.4)
Coordinated padlock and hex-head or optional penta-head bolt (top and bottom) provides bolted door security with visual confirmation by supervisory personnel. Security bolt is made captive with a stainless steel washer compressed to an oval shape to severely discourage removal.
Open bottom and bus arrangement allows access to all cables for easy installation and maintenance
Stainless steel hinges are welded to the door and the enclosure – 0.375" pins are standard
Cross-kinked roof prevents standing moisture
Accepts NEMA Standard 2-hole and 4-hole lugs back-to-back
Nontracking self-scouring ELRIM cycloaliphatic epoxy insulators
Removable lift provisions with blind holes for tamper resistance
Door-holder rods are stainlesssteel and hold the door open100 degrees or 140 degrees
Corrosion proof nameplate is located to provide easy access for the operator
Nonferrous hardware for long life
Front and rear doors for easy access
Ground lugs on each wall of the enclosure accept #6 - #2/0 ground cable
Heavy duty 11-gauge steel enclosure is all-welded construction for long life
Aluminum bus standardCopper bus optional
ENCLOSURE OPTIONS:1) 0.125" #5052H32 Aluminum2) 12-gauge #304L Stainless Steel
600-Volt Secondary Bus EnclosureThree-Phase
Pad-Mounted – Outdoor
Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com
Bulletin
340-062Page 2 2015
0.5625" Dia. Holes Typical
0.5625" Dia. Holes Typical
0.5625" Dia. Holes Typical
0.5625" Dia. Holes Typical
2.25"
1.75"0.625"
1.75" 0.75"
1.75"0.625"
1.75"0.625"
1.75"0.625"
1.75" 0.75"
1.75" 0.75"
1.75" 0.75"
4.25"
6.25"
6.25"
Standard Bus:Four Single 0.25" x 8" Aluminum Bus1,500/1,750 Amp at 30/45 degree C rise over 40 degree C Ambient
Alternate Bus:Four Single 0.25" x 8" Copper Bus2,000/2,300 Amp at 30/45 degree C rise over 40 degree C Ambient
Standard Bus:Four Single 0.25" x 10" Aluminum Bus1,800/2,100 Amp at 30/45 degree C rise over 40 degree C Ambient
Alternate Bus:Four Single 0.25" x 10" Copper Bus2,400/2,800 Amp at 30/45 degree C rise over 40 degree C Ambient
Standard Bus:Four Sets: 1 - 0.25" x 12" and 1 - 0.25" x 8" Aluminum Bus2,700/3,400 Amp at 30/45 degree C rise over 40 degree C Ambient
Alternate Bus:Four Sets: 1 - 0.25" x 12" and 1 - 0.25" x 8" Copper Bus3,600/4,500 Amp at 30/45 degree C rise over 40 degree C Ambient
Standard Bus:Four Single 0.25" x 12" Aluminum Bus2,100/2,500 Amp at 30/45 degree C rise over 40 degree C Ambient
Alternate Bus:Four Single 0.25" x 12" Copper Bus2,800/3,400 Amp at 30/45 degree C rise over 40 degree C Ambient
Bus Selection Information
Supplied in 36"W x 36"D Enclosure
Supplied in 42"W x 42"D Enclosure
Supplied in 48"W x 48"D Enclosure
Supplied in 54"W x 54"D Enclosure
600-Volt Secondary Bus EnclosureThree-Phase
Pad-Mounted – Outdoor
Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com
Bulletin
340-062Page 3 2015
0.5625" Dia. Holes Typical
0.5625" Dia. Holes Typical
0.5625" Dia. Holes Typical
0.5625" Dia. Holes Typical
1.75"0.625"
1.75"0.625"
1.75" 0.75"
1.75" 0.75"
1.75"
1.75" 0.75"
0.625"
1.75"
1.75" 0.75"
0.625"
6.25"
6.25"
6.25"
8.25"
Standard Bus:Four Sets: 2 - 0.25" x 14" and 1 - 0.25" x 12" Aluminum Bus4,500/5,500 Amp at 30/45 degree C rise over 40 degree C Ambient
Alternate Bus:Four Sets: 2 - 0.25" x 14" and 1 - 0.25" x 12" Copper Bus6,000/7,400 Amp at 30/45 degree C rise over 40 degree C Ambient
Standard Bus:Four Sets: 2 - 0.25" x 12" and 1 - 0.25" x 10" Aluminum Bus3,750/4,650 Amp at 30/45 degree C rise over 40 degree C Ambient
Alternate Bus:Four Sets: 2 - 0.25" x 12" and 1 - 0.25" x 10" Copper Bus5,000/6,200 Amp at 30/45 degree C rise over 40 degree C Ambient
Bus Selection Information
Standard Bus:Four Sets: 1 - 0.25" x 12" and 2 - 0.25" x 8" Aluminum Bus3,000/3,800 Amp at 30/45 degree C rise over 40 degree C Ambient
Alternate Bus:Four Sets: 1 - 0.25" x 12" and 2 - 0.25" x 8" Copper Bus4,000/5,100 Amp at 30/45 degree C rise over 40 degree C Ambient
Standard Bus:Four Sets: 2 - 0.25" x 12" Aluminum Bus3,200/4,000 Amp at 30/45 degree C rise over 40 degree C Ambient
Alternate Bus:Four Sets: 2 - 0.25" x 12" Copper Bus4,250/5,300 Amp at 30/45 degree C rise over 40 degree C Ambient
Optional in 54"W x 54"D Enclosure
Supplied in 60"W x 60"D Enclosure
Supplied in 66"W x 66"D Enclosure
Optional in 66"W x 66"D Enclosure
600-Volt Secondary Bus EnclosureThree-Phase
Pad-Mounted – Outdoor
Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com
Bulletin
340-062Page 4 2015
Galv. Square
1.5"
BoltsAnchorØ.5"Enclosure Washer
2.25" X 2.25"
Bracket
1.5"
#6102-A81-7
Elliott Anchor
BoltsAnchorØ.5"Enclosure
Concrete Pad
Concrete Pad
Alternate #2
Alternate #1
36"
"C"
4" Min.
CL
CL
36"
36"
Bottom Open
Anchor Bolt Locations
3" Min.
3" Min.
17"
17"
17"17"
16.375"
11"
11"
16.375"
Ø 0.75" Typical
"C" 2
2"C"
Bracket#6102-A81-7
Elliott Anchor
BoltsAnchor0.5" Dia.
Enclosure
Concrete Pad
Galv. Square
BoltsAnchor0.5" Dia.
Concrete Pad
Enclosure Washer
2.25" X 2.25"
1.5"
1.5"
Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.
Catalog Number Dim. "C"
ESBE-0.6-331-36W36D-30H Measure in the Field
ESBE-0.6-331-36W36D-36H Measure in the Field
ESBE-0.6-331-36W36D-42H Measure in the Field
ESBE-0.6-331-36W36D-48H Measure in the Field
Cable Training and Anchor Bolt Locations
Section BBand Typical Pad Dimensions
Front & Rear ViewDoor Removed
600-Volt Secondary Bus EnclosureThree-Phase
Pad-Mounted – Outdoor
Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com
Bulletin
340-062Page 5 2015
CL
CL
A
A
BB
36"
"A"
"B"
36"
36"
3.5"3.5"
34"32"
34"32"
7" 7"GroundProvisionEach Side
Provision forPadlock andSecurity Bolt,Top andBottom
1.75" Centersdia. Holes ontwo 0.5625"16 Sets of
Bottom Open
Ø 0.75" Typical
36"
0.5625" Dia. Holes Typical
1.75"
2.25"
1.75" 0.75"
0.625"
Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.
Catalog Number Dim. "A" Dim. "B"
ESBE-0.6-331-36W36D-30H 30" 19.375"
ESBE-0.6-331-36W36D-36H 36" 25.375"
ESBE-0.6-331-36W36D-42H 42" 31.375"
ESBE-0.6-331-36W36D-48H 48" 37.375"
Standard Bus:Four Single 0.25" x 8" Aluminum Bus1,500/1,750 Amp at 30/45 degree C rise over 40 degree C Ambient
Alternate Bus:Four Single 0.25" x 8" Copper Bus2,000/2,300 Amp at 30/45 degree C rise over 40 degree C Ambient
Front & Rear ViewDoor Removed
Section BB
Section AA
600-Volt Secondary Bus EnclosureThree-Phase
Pad-Mounted – Outdoor
Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com
Bulletin
340-062Page 6 2015
Galv. Square
1.5"
BoltsAnchorØ.5"Enclosure Washer
2.25" X 2.25"
Bracket
1.5"
#6102-A81-7
Elliott Anchor
BoltsAnchorØ.5"Enclosure
Concrete Pad
Concrete Pad
Alternate #2
Alternate #1
Bottom Open
19.375" 19.375"3" Min.
3" Min.
20"20"
20"
20"
4" Min.
Anchor Bolt Locations
"C" 2
2"C"
Ø 0.75" Typical
14"
14"
"C"
42"
42"
42"
CL
CL
Bracket#6102-A81-7
Elliott Anchor
BoltsAnchor0.5" Dia.Enclosure
Concrete Pad
Galv. Square
BoltsAnchor0.5" Dia.
Concrete Pad
Enclosure Washer
2.25" X 2.25"
1.5"
1.5"
Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.
Catalog Number Dim. "C"
ESBE-0.6-331-42W42D-36H Measure in the Field
ESBE-0.6-331-42W42D-42H Measure in the Field
ESBE-0.6-331-42W42D-48H Measure in the Field
ESBE-0.6-331-42W42D-54H Measure in the Field
Cable Training and Anchor Bolt Locations
Section BBand Typical Pad Dimensions
Front & Rear ViewDoor Removed
600-Volt Secondary Bus EnclosureThree-Phase
Pad-Mounted – Outdoor
Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com
Bulletin
340-062Page 7 2015
GroundProvisionEach Side
40"38"
40"38"
Provision forPadlock andSecurity Bolt,
Bottom Open
4.5"4.5"
Top andBottom
1.75" Centersdia. Holes ontwo 0.5625"20 Sets of
9" 9"
Ø 0.75" Typical
A
A
BB
42"
42" 42"
42"
"A""B"
CL
CL
0.5625" Dia. Holes Typical
4.25"
1.75"
1.75" 0.75"
0.625"
Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.
Catalog Number Dim. "A" Dim. "B"
ESBE-0.6-331-42W42D-36H 36" 23.375"
ESBE-0.6-331-42W42D-42H 42" 29.375"
ESBE-0.6-331-42W42D-48H 48" 35.375"
ESBE-0.6-331-42W42D-54H 54" 41.375"
Standard Bus:Four Single 0.25" x 10" Aluminum Bus1,800/2,100 Amp at 30/45 degree C rise over 40 degree C Ambient
Alternate Bus:Four Single 0.25" x 10" Copper Bus2,400/2,800 Amp at 30/45 degree C rise over 40 degree C Ambient
Front & Rear ViewDoor Removed
Section BB
Section AA
600-Volt Secondary Bus EnclosureThree-Phase
Pad-Mounted – Outdoor
Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com
Bulletin
340-062Page 8 2015
Galv. Square
1.5"
BoltsAnchorØ.5"Enclosure Washer
2.25" X 2.25"
Bracket
1.5"
#6102-A81-7
Elliott Anchor
BoltsAnchorØ.5"Enclosure
Concrete Pad
Concrete Pad
Alternate #2
Alternate #1
Anchor Bolt Locations
3" Min.
3" Min.
23"
23"
23"23"
22.375"22.375"
17"
17"
Bottom Open
4" Min.
Ø 0.75" Typical
"C" 2
2"C"
"C"
48"
48"
48"
CL
CL
Bracket
1.5"
#6102-A81-7
Elliott Anchor
BoltsAnchor0.5" Dia.
Enclosure
Concrete Pad
Galv. Square
1.5"
BoltsAnchor0.5" Dia.
Concrete Pad
Enclosure Washer
2.25" X 2.25"
Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.
Catalog Number Dim. "C"
ESBE-0.6-331-48W48D-36H Measure in the Field
ESBE-0.6-331-48W48D-42H Measure in the Field
ESBE-0.6-331-48W48D-48H Measure in the Field
ESBE-0.6-331-48W48D-54H Measure in the Field
Cable Training and Anchor Bolt Locations
Section BBand Typical Pad Dimensions
Front & Rear ViewDoor Removed
600-Volt Secondary Bus EnclosureThree-Phase
Pad-Mounted – Outdoor
Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com
Bulletin
340-062Page 9 2015
GroundProvisionEach Side
46"44"
46"44"
Provision forPadlock andSecurity Bolt,
Bottom Open
10" 10"
5"5"
Top andBottom
1.75" Centersdia. Holes ontwo 0.5625"22 Sets of
Ø 0.75" Typical
CL
CL
A
A
BB
48" 48"
48"
48"
"A""B"
6.25"
1.75"
0.75"1.75"
0.625"
0.5625" Dia. Holes Typical
Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.
Catalog Number Dim. "A" Dim. "B"
ESBE-0.6-331-48W48D-36H 36" 21.375"
ESBE-0.6-331-48W48D-42H 42" 27.375"
ESBE-0.6-331-48W48D-48H 48" 33.375"
ESBE-0.6-331-48W48D-54H 54" 39.375"
Standard Bus:Four Single 0.25" x 12" Aluminum Bus2,100/2,500 Amp at 30/45 degree C rise over 40 degree C Ambient
Alternate Bus:Four Single 0.25" x 12" Copper Bus2,800/3,400 Amp at 30/45 degree C rise over 40 degree C Ambient
Front & Rear ViewDoor Removed
Section BB
Section AA
600-Volt Secondary Bus EnclosureThree-Phase
Pad-Mounted – Outdoor
Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com
Bulletin
340-062Page 10 2015
Galv. Square
1.5"
BoltsAnchorØ.5"Enclosure Washer
2.25" X 2.25"
Bracket
1.5"
#6102-A81-7
Elliott Anchor
BoltsAnchorØ.5"Enclosure
Concrete Pad
Concrete Pad
Alternate #2
Alternate #1
Anchor Bolt Locations
3" Min.
3" Min.
26"
26"
26"26"
25.375"25.375"
20"
20"
Bottom Open
4" Min.
Ø 0.75" Typical
"C" 2
"C" 2
54"
54"
54"
"C"
CL
CL
Bracket
1.5"
#6102-A81-7
Elliott Anchor
BoltsAnchor0.5" Dia.Enclosure
Concrete Pad
Galv. Square
1.5"
BoltsAnchor0.5" Dia.
Concrete Pad
Enclosure Washer
2.25" X 2.25"
Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.
Catalog Number Dim. "C"
ESBE-0.6-331-54W54D-36H Measure in the Field
ESBE-0.6-331-54W54D-42H Measure in the Field
ESBE-0.6-331-54W54D-48H Measure in the Field
ESBE-0.6-331-54W54D-54H Measure in the Field
Cable Training and Anchor Bolt Locations
Section BBand Typical Pad Dimensions
Front & Rear ViewDoors Removed
600-Volt Secondary Bus EnclosureThree-Phase
Pad-Mounted – Outdoor
Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com
Bulletin
340-062Page 11 2015
54"
A
A
BB
54" 54"
54"
"A""B"
GroundProvisionEach Side
52"50"
52"50"
Provision for Padlock andSecurity Bolt, Top and Bottom
Bottom Open
10" 10"
5"5"1.75" Centersdia. Holes ontwo 0.5625"24 Sets of
Ø 0.75" Typical
CL
CL
0.5625" Dia. Holes Typical
1.75"
6.25"
1.75" 0.75"
0.625"
Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.
Catalog Number Dim. "A" Dim. "B"
ESBE-0.6-331-54W54D-36H 36" 21.375"
ESBE-0.6-331-54W54D-42H 42" 27.375"
ESBE-0.6-331-54W54D-48H 48" 33.375"
ESBE-0.6-331-54W54D-54H 54" 39.375"
Standard Bus:Four Sets: 1 - 0.25" x 12" and 1 - 0.25" x 8" Aluminum Bus2,700/3,400 Amp at 30/45 degree C rise over 40 degree C Ambient
Alternate Bus:Four Sets: 1 - 0.25" x 12" and 1 - 0.25" x 8" Copper Bus3,600/4,500 Amp at 30/45 degree C rise over 40 degree C Ambient
Front & Rear ViewDoors Removed
Section BB
Section AA
600-Volt Secondary Bus EnclosureThree-Phase
Pad-Mounted – Outdoor
Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com
Bulletin
340-062Page 12 2015
Galv. Square
1.5"
BoltsAnchorØ.5"Enclosure Washer
2.25" X 2.25"
Bracket
1.5"
#6102-A81-7
Elliott Anchor
BoltsAnchorØ.5"Enclosure
Concrete Pad
Concrete Pad
Alternate #2
Alternate #1
Anchor Bolt Locations
3" Min.
3" Min.
29"
29"
29"29"
28.375"28.375"
Bottom Open
4" Min.
23"
23"
Ø 0.75" Typical
60"
60"
"C"
60"
CL
CL
"C" 2
2"C"
Bracket
1.5"
#6102-A81-7
Elliott Anchor
BoltsAnchor0.5" Dia.Enclosure
Concrete Pad
Galv. Square
1.5"
BoltsAnchor0.5" Dia.
Concrete Pad
Enclosure Washer
2.25" X 2.25"
Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.
Catalog Number Dim. "C"
ESBE-0.6-331-60W60D-36H Measure in the Field
ESBE-0.6-331-60W60D-42H Measure in the Field
ESBE-0.6-331-60W60D-48H Measure in the Field
ESBE-0.6-331-60W60D-54H Measure in the Field
Cable Training and Anchor Bolt Locations
Section BBand Typical Pad Dimensions
Front & Rear ViewDoors Removed
600-Volt Secondary Bus EnclosureThree-Phase
Pad-Mounted – Outdoor
Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com
Bulletin
340-062Page 13 2015
GroundProvisionEach Side
58"56"
58"56"
Provision for Padlock and
Bottom Open
12" 12"6"
Security Bolt, Top and Bottom
1.75" Centersdia. Holes ontwo 0.5625"26 Sets of6"
Ø 0.75" Typical
CL
CL 60"
A
A
BB
60" 60"
60"
"A""B"
0.5625" Dia. Holes Typical
6.25"
0.75"
1.75"
1.75"
0.625"
Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.
Catalog Number Dim. "A" Dim. "B"
ESBE-0.6-331-60W60D-36H 36" 21.375"
ESBE-0.6-331-60W60D-42H 42" 27.375"
ESBE-0.6-331-60W60D-48H 48" 33.375"
ESBE-0.6-331-60W60D-54H 54" 39.375"
Standard Bus:Four Sets: 2 - 0.25" x 12" Aluminum Bus3,200/4,000 Amp at 30/45 degree C rise over 40 degree C Ambient
Alternate: Bus:Four Sets: 2 - 0.25" x 12" Copper Bus4,250/5,300 Amp at 30/45 degree C rise over 40 degree C Ambient
Front & Rear ViewDoors Removed
Section BB
Section AA
600-Volt Secondary Bus EnclosureThree-Phase
Pad-Mounted – Outdoor
Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com
Bulletin
340-062Page 14 2015
Galv. Square
1.5"
BoltsAnchorØ.5"Enclosure Washer
2.25" X 2.25"
Bracket
1.5"
#6102-A81-7
Elliott Anchor
BoltsAnchorØ.5"Enclosure
Concrete Pad
Concrete Pad
Alternate #2
Alternate #1
Anchor Bolt Locations
3" Min.
3" Min.
32"
32"
32"32"
31.375"31.375"
26"
26"
Bottom Open
4" Min.
"C" 2
"C" 2
Ø 0.75" Typical
66"
66"
"C"
66"
CL
CL
Bracket
1.5"
#6102-A81-7
Elliott Anchor
BoltsAnchor0.5" Dia.
Enclosure
Concrete Pad
Galv. Square
1.5"
BoltsAnchor0.5" Dia.
Concrete Pad
Enclosure Washer
2.25" X 2.25"
Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.
Catalog Number Dim. "C"
ESBE-0.6-331-66W66D-36H Measure in the Field
ESBE-0.6-331-66W66D-42H Measure in the Field
ESBE-0.6-331-66W66D-48H Measure in the Field
ESBE-0.6-331-66W66D-54H Measure in the Field
Cable Training and Anchor Bolt Locations
Section BBand Typical Pad Dimensions
Front & Rear ViewDoors Removed
600-Volt Secondary Bus EnclosureThree-Phase
Pad-Mounted – Outdoor
Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com
Bulletin
340-062Page 15 2015
GroundProvisionEach Side
64"62"
64"62"
Provision for Padlock and
Bottom Open
12" 12"6"
Security Bolt, Top and Bottom
1.75" Centersdia. Holes ontwo 0.5625"28 Sets of6"
Ø 0.75" Typical
66"
A
A
BB
66" 66"
66"
"A""B"
CL
CL
6.25"
0.75"
1.75"
1.75"
0.625"
0.5625" Dia. Holes Typical
Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.
Catalog Number Dim. "A" Dim. "B"
ESBE-0.6-331-66W66D-36H 36" 21.375"
ESBE-0.6-331-66W66D-42H 42" 27.375"
ESBE-0.6-331-66W66D-48H 48" 33.375"
ESBE-0.6-331-66W66D-54H 54" 39.375"
Standard Bus:Four Sets: 2 - 0.25" x 12" and 1 - 0.25" x 10" Aluminum Bus3,750/4,650 Amp at 30/45 degree C rise over 40 degree C Ambient
Alternate Bus:Four Sets: 2 - 0.25" x 12" and 1 - 0.25" x 10" Copper Bus5,000/6,200 Amp at 30/45 degree C rise over 40 degree C Ambient
Front & Rear ViewDoors Removed
Section BB
Section AA
600-Volt Secondary Bus EnclosureThree-Phase
Pad-Mounted – Outdoor
Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com
Bulletin
340-062Page 16 2015
Typical Specification
GeneralThe secondary bus enclosure shall be 600 volt class,
suitable for use on systems that do not exceed 600 volts to ground (nor 1000 volts phase to phase). The bus shall be constructed for connection to the electrical system with two-hole and/or four-hole NEMA Standard bolt-on cable-terminal lugs (terminal lugs shall be supplied by the user). Tamper resistance shall meet the Enclosure Security requirements of IEEE Standard C57.12.28 (Pad-Mounted Equipment—Enclosure Integrity) to resist unauthorized entry, protect authorized and unauthorized persons, and provide positive safety features when installed in areas accessible to the general public. The enclosure shall be constructed for outdoor installation in areas subject to heavy precipitation and in areas of windblown contamination. The equipment shall be completely assembled prior to shipment.
Enclosure ConstructionThe enclosure shall be tamper-resistant, all-welded
construction utilizing 11-gauge minimum sheet steel. Corner plates and braces shall be used as necessary to assure rigidity. The enclosure top shall be cross-kinked to provide watershed and rigidity. The enclosure shall be open bottom with a 1-inch flange inside, all around. The door(s) shall be furnished with a stainless steel door holder that will latch the door open 100 degrees and 140 degrees and resist accidental closing. Door(s) shall be provided with provisions for padlocking and a recessed hex-head (or penta-head) security bolt to prevent unauthorized entry (coordinated to prevent installation of the padlock until the security bolt is tightened when closing the door(s) and to prevent a wrench from operating the security bolt until the padlock is removed when opening the door(s)). The security bolt shall be made captive with a stainless steel washer compressed to an oval shape to severely discourage removal. Hinges shall be stainless steel (with stainless steel pins not less than 0.3125-inch diameter) and shall be welded to both the enclosure and the door(s) to maintain door alignment for the life of the equipment. The enclosure shall be nonventilated to minimize the entrance of airborne contamination, insects, rodents or reptiles. The protective finish shall include necessary grinding, cleaning and phosphatizing, two-component rust-inhibiting epoxy primer and a Pad-Mount Green two-component polyurethane top coat finish (Munsell color 7GY 3.29/1.5). The primer and top coat shall be electronically monitored during application to insure proper ratio and mixing of each component. Total average thickness of paint (after curing) shall be not less than 5 mils. The protective coating shall meet the Enclosure Coating System requirements of IEEE Standard C57.12.28 (Pad-Mounted Equipment—Enclosure Integrity). Removable lift provisions, adequate to withstand handling with normal utility equipment, shall be provided on the outside of the enclosure. Threaded openings for lift provision bolts shall be blind holes to prevent the entrance of wire or other foreign objects into the enclosure when lift provisions are removed.
Bus and Bus MountingsThe bus shall be aluminum (Alternate #1—bare copper,
Alternate #2—tin-plated copper) with all burrs and sharp corners
removed prior to installation. It shall be punched with multiple sets (Alternate #1—as shown on the drawings, Alternate #2—specify number) of two 0.5625-inch diameter holes on 1.75-inch centers to accommodate both two-hole and four-hole NEMA standard cable-terminal lugs. When the bus for each phase is constructed with more than one conductor, two 0.25-inch x 0.5625-inch ID x 1-inch OD spacers shall be supplied for each set of two 0.5625-inch diameter holes. The spacers shall be the same metal alloy as the bus conductor. A minimum of two insulators shall be provided for each bus. The insulators shall be cycloaliphatic epoxy and shall be mounted in a manner that will allow field replacement with standard tools without removal of cables that may be bolted to the bus. Insulators and bus bars shall be installed with stainless steel mounting hardware to provide long life and reduced maintenance. All components shall be arranged to allow visual inspection without de-energizing or removing the equipment from service.
Grounding ProvisionsFour high-conductivity bronze eyebolt-type ground lugs,
which accept #6 through #2/0 copper conductor, shall be installed on the inside walls of the enclosure (located on each side of each door opening in an accessible position as shown on the drawings).
Accessory EquipmentA corrosion proof nameplate with permanent thermal
transfer printing shall be installed inside one door on the cable compartment. It shall be located at the top corner farthest from the cables when the door is open. The nameplate will provide Type of Equipment, Model Number, Amps Continuous, kV Maximum, BIL, Serial Number, Job Number, Date Manufactured and Weight of Equipment.
When specified, one “Warning - Keep Out! - Hazardous Voltage” sign, Elliott #7201-W2003-316, shall be provided on the outside of each door.
When specified, four anchor-bolt brackets, Elliott #6102-A81-7 or approved equal, shall be supplied with each secondary bus enclosure to provide a means of clamping the equipment to the concrete pad.
PackagingEach secondary bus enclosure shall be bolted to a
solid-top wood pallet (to prevent the forks of a forklift truck from entering the open bottom of the equipment) to prevent hidden damage. The equipment shall be wrapped with 0.125-inch thick polyethylene foam or other suitable material to minimize damage to the finish during shipment.
DrawingsWhen specified, drawings shall be furnished for each
secondary bus enclosure that include:1) enclosure dimensions and location of components.2) proposed cable-training layout and dimensions.3) proposed pad dimensions and location of anchor bolts.