624255r00 arc view handheld operator s guide

Upload: oflorez72

Post on 09-Jan-2016

24 views

Category:

Documents


0 download

DESCRIPTION

hamilton

TRANSCRIPT

  • HAMILTON ARC SystemARC View HandheldOperator's Guide

  • All rights reserved. No part of this document may be reproduced, stored in a retrieval system, or transmitted in any form without written permission from HAMILTON Bonaduz AG.

    The contents of this manual are subject to change without notice. Technical changes reserved.

    All efforts have been made to ensure the accuracy of the contents of this manual. However, should any errors be detected, HAMILTON Bonaduz AG would greatly appreciate being informed of them.

    The above notwithstanding, HAMILTON Bonaduz AG can assume no responsibility for any errors in this manual or their consequences.

    Copyright 2009 HAMITLON Bonaduz AG, Switzerland.

  • List of Contents

    ARC View Handheld Operators Guide List of Contents-1

    List of Contents

    List of Contents

    ForewordAbout this manualHow to use this manual

    The ARC system

    Safety notices

    Equipment warnings

    Typographic standards in this manual

    Section 1, The HAMILTON ARC View Handheld and System

    1.1 Getting started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11.2 Setting up the ARC View Handheld . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-21.3 ARC View Handheld keys and interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-31.4 ARC View Handheld power management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-81.5 ARC system components and principles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9

    1.5.1 ARC sensors: communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-91.5.1.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-91.5.1.2 ARC sensor communication with a PLC system . . . . . . . . . . . . . . . . . . . . . . 1-101.5.1.3 ARC sensor communication with a Handheld . . . . . . . . . . . . . . . . . . . . . . . . 1-101.5.1.4 ARC sensor communication with a computer . . . . . . . . . . . . . . . . . . . . . . . . . 1-11

    1.5.2 ARC sensors: operator levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-111.5.3 ARC sensors: operational status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-12

    1.5.3.1 ARC View Handheld status colors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-121.5.3.2 ARC Wi Sensor Adapter status colors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-13

    1.5.4 ARC sensors: calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-141.5.4.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-141.5.4.2 Calibration procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-14

    1.5.5 ARC sensors: digital interface configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-151.5.5.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-151.5.5.2 Modbus device addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-161.5.5.3 Baud rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-16

    1.5.6 ARC sensors: analog interface configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-171.5.6.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-171.5.6.2 Mapping parameters to the analog interfaces . . . . . . . . . . . . . . . . . . . . . . . . 1-171.5.6.3 Configuring the mode of the analog interfaces . . . . . . . . . . . . . . . . . . . . . . . . 1-181.5.6.4 Configuring the output current of the analog inte rfaces . . . . . . . . . . . . . . . . . 1-181.5.6.5 Configuring Errors and Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-20

    1.5.7 ARC sensors: Cleanings and Sterilizations In Place . . . . . . . . . . . . . . . . . . . . . . . 1-211.5.8 ARC sensor measurements: moving average . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-22

  • List of Contents

    List of Contents-2 11 December 2009

    1.5.9 ARC sensor measurements: resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-231.5.10 ARC sensor measurements: temperature compensation factor . . . . . . . . . . . . . . 1-231.5.11 ARC sensor measurements: Quality Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-24

    Section 2, ARC View Handheld tasks tutorial

    2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12.2 User tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1

    Task 1 Checking the status of all sensors in the ARC system . . . . . . . . . . . . . . . . . 2-1Task 2 Reading basic parameter values from a sensor . . . . . . . . . . . . . . . . . . . . . . 2-2

    2.1 Reading basic parameter values in numeric form . . . . . . . . . . . . . . . . . . . . 2-22.2 Reading basic parameter values in graphic form . . . . . . . . . . . . . . . . . . . . . 2-2

    Task 3 Reading detailed data from a sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-33.1 Reading sensor status data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-33.2 Reading sensor information data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-43.3 Reading interface configuration data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4

    2.3 Administrator tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4Task 1 Setting the Administrator operator level . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5Task 2 Calibrating a sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5

    2.4 Specialist tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7Task 1 Setting the Specialist operator level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7Task 2 Adding or exchanging a sensor in an ARC sys tem . . . . . . . . . . . . . . . . . . . 2-7

    2.1 Entering the Sensor ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-82.2 Configuring the Modbus device address . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-82.3 Configuring the Baud rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-82.4 Configuring the analog interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-92.5 Configuring a calibration procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9

    Section 3, Reference to HAMILTON ARC View Handheld screens

    3.1 ARC View Handheld screens: full listing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13.2 ARC View Handheld screens: full details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2

    Section 4, Warning Messages, Error Messages and Troubleshooting

    4.1 Troubleshooting a faulty wireless connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14.2 Troubleshooting Handheld sensor status colors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-24.3 Troubleshooting ARC Wi Sensor Adapter status colors . . . . . . . . . . . . . . . . . . . . . . . 4-24.4 Warning Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3

    4.4.1 Troubleshooting Measurement Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-34.4.2 Troubleshooting Calibration Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-44.4.3 Troubleshooting Calibration Status Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-44.4.4 Troubleshooting Interface Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-54.4.5 Troubleshooting Hardware Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5

    4.5 Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-64.5.1 Troubleshooting Measurement Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-64.5.2 Troubleshooting Calibration Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-74.5.3 Troubleshooting Hardware Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7

  • List of Contents

    ARC View Handheld Operators Guide List of Contents-3

    Section 5, Firmware Upload

    5.1 FW Upload ARC View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-25.2 FW Upload ARC View Handheld RF Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-35.3 FW Upload ARC View Handheld Dock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-45.4 FW Upload ARC sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-55.5 FW Upload ARC Wi Sensor Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6

    Appendix A, HAMILTON ARC System components

    A.1 HAMILTON ARC System core components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1A.1.1 Core components illustrations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1A.1.2 ARC View Handheld specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2

    A.2 HAMILTON ARC System additional components . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3A.3 HAMILTON ARC System spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-4A.4 HAMILTON ARC System documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5

  • Foreword

    About this manual

    This manua l is for a ll operato rs of the HAMILTON ARC process anal ytics system. Th e manual serves two func tions :

    It gives an overview of the integrat ion of the com plete ARC system: sensors, cables, and ARC Wi Sensor adapters.

    It exp lains in detail the use o f the ARC View Handheld.

    How to use this manual

    First , make sure you are famil iar with the Handhelds basic func tions and that you understa nd what Users , Admin istrat ors and Special ists are. You can learn abo ut these in Sectio n 1, The HAMILTON ARC View Handheld and System.

    Then, try perfo rming some of the tasks th at your job requires of yo u. There i s help about th is in Section 2, ARC View Handheld tasks tutorial .

    If you have difficu lty understanding a screen or a field, use Section 3, Reference to HAMILTON ARC View Handheld screens. If you have diffi culty finding the screen you wan t, use the index in the back of the manual.

    The ARC system

    The ARC View Handheld is an advanced too l for sensor communi cation, configu ration and management . Combining the cost saving and rel iabil ity o f the ARC sensors wi th the power and convenience of the ARC View Handheld, the user pro fits f rom measurement , lab precalibration , configurat ion, and management of mult iple HAMILTON ARC sensors within one integrated sys tem.

    Safety notices

    The ARC View Handheld is environmentally protected acco rding to the IP 67 standard. However, the Dock is not. For this reason, on ly use the Dock in dr y locat ions.

    Do no t open the power adapter.

    Do no t use the ARC system or any ARC sys tem component in an explos ive environment (ATEX zones).

    Use only w ired digital or analog connect ions for th e process control. The ARC wireless i nterface i s des igned for sensor mon itoring, maintenance , and servi ce purposes.

    Do no t open the ARC V iew Handhe ld. Only t rained service specialists are permi tted to exchange the inte rnal b attery.

  • Equipment warnings

    ARC View Handheld Operators Guide Equipment warnings-2

    Do not use the internal te mpera ture sensor of any ARC sensor t o con trol the temperature of a process.

    Equipment warnings

    Do not use sol vents , strong acids, bases, or ammon ia (NH 3) in gas eous or any oth er form to clean the ARC View Handheld or th e Dock.

    Be sure not t o damage the screen of the Handheld when cleaning. Sma ll par ticles of dirt on a cloth can cause scra tching. A new paper tissue is recommended.

    Typographic standards in this manual

    Example Explanation

    Graph Courier font indicates text on the Handheld screen.

    View Courier font, underlined, indicates a soft-key on the Handheld screen.

    [Sensor] Courier font, italic with square brackets indicates a variable on the Handheld screen.

    [Sensor] indicates any ARC sensor shown on the Handheld screen.

  • Section 1 The HAMILTON ARC View Handheld and System

    ARC View Handheld Operators Guide Page 1-1

    Section 1 The HAMILTON ARC View Handheld and System

    This section gives a detailed description of the HAMILTON ARC View Handheld, and of the principles that lie behind its use with other components in the ARC System.

    Section 1.1 Getting started

    Your ARC Handhe ld package inclu des the fo llowing components:

    ARC V iew Handhe ld and Dock. You can fin d specifica tions for t hese items in Table A.1, ARC View Handheld specifications., on Page A-2.

    Power supp ly fo r Handheld and Dock. This u nit requires a power source of 100 to 240 V, and has adapter s for standard power sockets in Europe, Great Britain, Australi a and the USA.

    ARC Cable VP 8.This is a data and power cable between a sensor and the Dock.

  • Section 1 The HAMILTON ARC View Handheld and System

    Page 1-2 December 11, 2009

    Section 1.2 Setting up the ARC View HandheldThe HAMILTON ARC Handheld is easy to set up and convenient to use as a conf igura tion and calib ration too l for HAMILTON ARC sensors.

    The follow ing s teps descr ibe th e setup procedure fo r both wired and wireless connection opti ons:

    1. Connect the provided ARC Cable VP8 to the Doc k.

    2. Connect one of the ARC sens ors (no t included in thi s package) to the VP8 plug of the sensor cab le.

    3. Place the ARC V iew Handhe ld on the Dock.

    4. Connect the Power Adapter Cable to the Dock, and p lug th e Power Adapter into an suitable power outle t (100 to 240 V ac).

    5. Turn the Handhe ld on by pressing the Lef t and Right keys toge ther for 3 seconds. After star tup, the Handhe ld recognizes and di splays the connected sensor automatica lly.

    NOTE: In this setup, the Handheld functions as a desktop system for a laboratory environment, not an industrial environment.

    For w ireless connect ion:

    1. Plug the ARC Wi Sensor Adapter (not included in thi s package) between th e ARC sensor and the senso r cab le.

    2. Take the Handhe ld ou t of the Dock. The w ireless connect ion is established automatical ly.

    NOTE: In this setup the Handheld can be used as a mobile tool for both laboratory and industrial applications .

    Figure 1.1 Plugs on the ARC View Handheld Dock.

    ARC Cable VP8

    Power Supply Cable

  • Section 1 The HAMILTON ARC View Handheld and System

    ARC View Handheld Operators Guide Page 1-3

    Section 1.3 ARC View Handheld keys and interface

    Switching on and off

    To switc h on Handheld, press the Lef t and Righ t Keys together for three seconds . To switch off the Handh eld, press the Down Key for three seconds. For more information, see Section 1.4, ARC View Handheld power management, on Page 1-8.

    Figure 1.2 The ARC View Handheld showing top level of interface, pH sensor attached).

    C. Sensor number. D. Wireless connection status.

    E. Battery status.A. Clock.

    B. Operator level.

    F. Panel for DeviceSetup. (There isonly ever one.)

    O. Primary sensormeasurement value andparameter name.

    P. Status symbol for

    N. Status symbol forempty panel. Here, itis red as the panel doeshave a connection

    L. Left Key. (Functionshown on screen

    M. Up and Down Keys.

    G. Sensor ID.

    H. Panel for sensormeasurements.(pH sensor shown.)

    K. Right Key. (Functionshown on screen

    I. Secondary sensorparameter. (Here,temperature.)

    J. Panel for sensor(No sensor connected.)

    (Here, pH.)

    sensor. Here it is green.

    to a sensor.

    above.) above.)

  • Section 1 The HAMILTON ARC View Handheld and System

    Page 1-4 December 11, 2009

    Symbol or field Function Additional information

    A. Clock Real time clock. Shows time of day. You adjust the clock by selecting Device Setupon the opening screen and clicking Tools.

    B. Operator level Displays the current operator level of the selected sensor.

    For detailed information, see Section 1.5.2, ARC sensors: operator levels, on Page 1-11.

    There is no panel selected on the Handheld.

    This is the case when the Handheld is first switched on.

    The Device setup panel or sensor panel selected in the Handheld has its operator level set to User.

    A User can:

    Read most sensor data.

    The Device setup panel or sensor panel selected in the Handheld has its operator level set to Administrator.

    An Administrator can: Read most sensor data.

    Calibrate the sensor.

    The Device setup panel or sensor panel selected in the Handheld has its operator level set to Specialist.

    A Specialist can: Read all sensor data.

    Calibrate the sensor.

    Configure the sensor.

    In addition, the letter D (for which a special password is required) can indicate a level used by HAMILTON service personne l.

    C. Sensor number The first field displays the number of the sensor selected on the Handheld as it appears within the list of sensors currently being monitored by the Handheld. The second field displays the total number of sensors monitored by the Handheld.

    For example, '4/7' means that Sensor 4 is selected within a list of seven sensors displayed on the Handheld.

    Do not confuse the sensor number with the sensor's Modbus device address or Sensor ID.

    For more information, see Section 1.5.5.2, Modbus device addresses , on Page 1-16.

    Table 1.1 ARC View Handheld keys and interface.

  • Section 1 The HAMILTON ARC View Handheld and System

    ARC View Handheld Operators Guide Page 1-5

    D. Wireless connection status

    The selected sensor or the wireless connection is not functioning.

    For information about dealing with failed wireless connection, see Section 4, Warning Messages, Error Messages and Troubleshooting .

    Wireless connection between the Handheld and the selected sensor is poor or non-existent.

    Wireless connection between the Handheld and the selected sensor is moderate.

    Wireless connection between the Handheld and the selected sensor is excellent.

    E. Battery status Battery 1/3 full. If your Handhelds battery life between charges is shorter than about 5 hours, have the battery replaced.Battery 2/3 full.

    Battery full.

    Battery charging in Dock (levels flash continuously).

    F. Panel for device The top-most level of the Handhelds user interface is divided into four visible panels and 27 invisible panels. If a sensor is displayed on a panel, whether visible or currently invisible, you can scroll to it with the Up and Down keys.

    The device panel is positioned above the sensor panels, and by default is out of sight when the Handheld is first switched on.The device panel gives access to screens enabling configuration of the Handheld.

    G. Sensor ID Displays a text string uniquely identifying the selected sensor.

    By factory default, the Sensor ID is the sensor's part number followed by its serial number.

    The Sensor ID can be changed in the Handheld by the Specialist on Screen 36 on Page 3-35: [Sensor] Tools Sensor info.

    Symbol or field Function Additional information

    Table 1.1 ARC View Handheld keys and interface.

  • Section 1 The HAMILTON ARC View Handheld and System

    Page 1-6 December 11, 2009

    H. Panel for sensor The top-most level of the Handhelds user interface is divided into four visible panels and 27 invisible panels. If a sensor is displayed on a panel, whether visible or currently invisible, you can scroll to it with the Up and Down keys.The Panel for sensor displays a measurements data overview from the sensor you select using the Up and Down Keys. You can then press the Right Key to Viewmore detailed data, or the Left Key to access Tools for calibration and configuration of the corresponding sensor.

    I. Secondary sensor measurement parameter

    The sensors secondary parameter (temperature), the measurement unit, and the current value are displayed here.

    J. Panel for sensor (no sensor connected)

    The top-most level of the Handhelds user interface is divided into four visible panels and 27 invisible panels. If a sensor is displayed on a panel, whether visible or currently invisible, you can scroll to it with the Up and Down keys.This panel is blank in Figure 1.2 because there is no sensor associated with it. As soon as a new ARC sensor is added to the ARC System, a new wireless connection will be automatically created, and information will be shown here.

    Symbol or field Function Additional information

    Table 1.1 ARC View Handheld keys and interface.

  • Section 1 The HAMILTON ARC View Handheld and System

    ARC View Handheld Operators Guide Page 1-7

    K. Right Key Click View to see additional information for the selected panel.

    The functions of these keys are context-dependent. Functions are indicated by the software field immediately above each key.

    Press the Left Key and Right Key together for three seconds to switch on the Handheld.

    Click OK to see more screens for the field you have selected.

    L. Left Key Click Tools to access the tools menu options for the selected panel. The menu for Device panel enables to configure the Handheld. The menu for Sensor panel enables to see detailed sensor and measurements information, and to access screens enabling calibration and configuration of the sensor. You have to enter a password to use the Tools menu. (Task 1, on Page 2-5, and Task 1, on Page 2-7.)

    Click OK to see more screens for the field you have selected.

    Click Back to move backwards through the menu system.

    M. Up Key Scrolls up. Press the Down Key for three seconds to switch off the Handheld.

    M. Down Key Scrolls down.

    N. Status symbol for empty panel

    Displays status: empty panels that are not associated with a sensor always display a red status symbol.

    O. Primary sensor measurement value and parameter name

    The parameter shown in this field depends on the sensor displayed: Cond = Conductivity pH= pH DO= Dissolved oxygen

    ARC sensors measure a secondary parameter (always temperature) in addition to the primary one. The secondary parameter is shown to the right of the primary one.

    Symbol or field Function Additional information

    Table 1.1 ARC View Handheld keys and interface.

  • Section 1 The HAMILTON ARC View Handheld and System

    Page 1-8 December 11, 2009

    Section 1.4 ARC View Handheld power management

    P. Status symbol for sensor

    GREEN

    Continuous: Sensor and connection functioning correctly.

    Flashing: Updating data.

    Status colors on the Handheld (shown here) and on the ARC Wi Sensor Adapter do not have the same meaning.For more information, see:

    Section 1.5.3, ARC sensors: operational status, on Page 1-12.

    Section 4.2, Troubleshooting Handheld sensor status colors, on Page 4-2.

    YELLOW

    Continuous: Sensor indicates error or warning message.

    Flashing: Updating data.

    RED

    Continuous: Sensor or connection not functioning.

    Function Action

    Switch on Handheld Press Left and Right Keys together for 3 seconds.

    Switch off Handheld Press Down Key for 3 seconds.

    Handheld switches off automatically If Handheld is unused for 30 minutes.

    Reset Handheld Push Down Key for 30 seconds.

    Backlight switches off automatically If Handheld is unused for 5 minutes.

    Wake up Handheld when backlight switched o ff Press any key.

    Table 1.2 Power management functions

    Symbol or field Function Additional information

    Table 1.1 ARC View Handheld keys and interface.

  • Section 1 The HAMILTON ARC View Handheld and System

    ARC View Handheld Operators Guide Page 1-9

    Section 1.5 ARC system components and principlesYou shou ld be famili ar with the foll owing componen ts and princ iples before operating the Handheld in a real working environment.

    Section 1.5.1 ARC sensors: communications

    Section 1.5.1.1 Overview

    Every HAMILTON ARC System sensor has two kinds of inter face. These comprise :

    Two ana log 4-20 mA interfaces (wit h the exception of the VISIFERM DO ARC, wh ich has one).

    One d igita l RS485 Modbus RTU interface.

    Analog inter faces

    The sensor s two ana log in terfac es are mapped by the factor y in t he fo llowing manner:

    mA inter face #1: Parameter 1 (conducti vity, pH, or di ssolved oxygen) . mA inter face #2: Parameter 2 (temperat ure, excep t for the VISIFERM DO ARC).

    However, Specia lists can change this mapp ing, i f required .

    Final ly, the rela tionship between the values measured by the sensor, and the outpu t sign als fr om the i nterface can also be conf igured.

    You can fi nd ou t more about al l thes e aspects of the ana log interf ace in Sect ion 1 .5.6, ARC sensors: analog interface configuration, on Page 1-17.

    Analog interface connections between a sensor and a con trol device such as a PLC are always wired .

    Figure 1.3 HAMILTON ARC sensor with analog and dig ital interfaces.

  • Section 1 The HAMILTON ARC View Handheld and System

    Page 1-10 December 11, 2009

    Digital RS485 Modbus RTU inter face

    The sensor s RS485 Modbus digi tal in terface is used fo r wired connections to ot her ha rdware. An ARC Wi Sensor Adapte r mounted on each ARC sensor i s requ ired for w ireless connect ion, and provides the radio functionali ty. (However, th e sensor a lso requires a separate, wired , powe r supply.)

    Section 1.5.1.2 ARC sensor communication with a PLC system

    Connection to a PLC system can be by means of the senso rs analog or d igita l interface s, depending on whether the process control system accepts analog or digi tal inputs. If necessary, both digital and ana log i nterfaces can function at the same time.

    For reasons of safety, connect ion to a p rocess con trol system is always wired.

    Section 1.5.1.3 ARC sensor communication with a Handheld

    Senso r communica tion w ith a Handheld is always digi tal. I t can be wired or wi reless. Wired mod e can be use ful for testing , con figur ing, and calibrating sensors outside a p rocess env ironment. Wireless mode (using an ARC Wi Sensor A dapter mounted o n the senso r) is suitable fo r proc ess environments.

    Wireless communication be tween the Handheld and the sensors starts automatically when you take the Ha ndheld from its Dock (Figure 1.5).

    Simil arly, wireless communica tion sw itches off automati cally when you replace the Handheld in its Dock. Sensors connec ted by wire to the Do ck always commu nicate by wire to the Dock, even if they have an ARC Wi Senso r Adapter.

    Figure 1.4 HAMILTON pH ARC sensor, showing ARC Wi Sensor Adapter and cable.

    Cable for signal and power supply

    ARC Wi Sensor Adapterfor wireless functionality

    ARC sensor

    VP8 Connector

  • Section 1 The HAMILTON ARC View Handheld and System

    ARC View Handheld Operators Guide Page 1-11

    Up to 3 0 sensors can be connected to t he Handheld at the same t ime, but only the four (o r fewer) that are curren tly v isible on t he sc reen are active ly mon itored.

    Section 1.5.1.4 ARC sensor communication with a computer

    A computer runn ing the ARC Sensor Configurator freeware i s an altern ative to the Handheld in many respects: it has slightly grea ter f unctionali ty, bu t cannot operate wireless ly.

    Senso r commun ication with a computer always takes place by means of the RS485 Modbu s digita l inter face usi ng a wired connection. If you wish to connect a sensor to a compute r, you require bot h a cable to connec t to one of the compute rs USB ports and also an RS485/USB adapter . (For more information, see Appendix A, HAMILTON ARC System components .)

    Section 1.5.2 ARC sensors: operator levels

    Every ARC sensor always has it s cur rent opera tor level value stored in i ts memory. The ARC System supports three operator leve ls (Table 1.3).

    Figure 1.5 The ARC Handheld starts wireless communication when removed from its Dock.

    Operator level Password Actions possible Tasks possible

    User Not required Read most sensor data. All tasks in Section 2.2, User tasks.

    Administrator 18111978 Read most sensor data. Calibrate sensors.

    All tasks in Section 2.2, User tasks. All tasks in Section 2.3,

    Administrator tasks

    Specialist 16021966 Read all sensor data. Calibrate sensors. Configure sensors.

    All tasks in Section 2.2, User tasks. All tasks in Section 2.3,

    Administrator tasks All tasks in Section 2.4, Specialist

    tasks.

    Table 1.3 Actions and tasks possible at different operator levels. Passwords are factory default.

  • Section 1 The HAMILTON ARC View Handheld and System

    Page 1-12 December 11, 2009

    On power-up, eac h sensor falls b ack to the User operator level . This also happens when an opera tor working with the Handheld leaves the password-protec ted area of the Handheld.

    When a sensor is set to the User operato r level, it permits only Use r rights to any devic e access ing the data s tored in it s memory, and only User r ights to perform some act ions (Table 1.3).

    However, by entering the Admin istra tor o r Speciali st password in t he Handheld, an operator can obtain Administr ator or Speciali st ri ghts (Table 1.3).

    Task 1, Setting the Administrator operator level, on Page 2-5 and Task 1, Setting the Specialist operator level, on Page 2-7 exp lain how you en ter a pas sword to obtai n Admin istra tor or Specia list rights.

    Section 1.5.3 ARC sensors: operational status

    Status colo rs on the Handheld and on the ARC Wi Sensor Adapte r refe r to t he status of:

    The se nsor. The sensor /Handheld connection .

    NOTE: The status colors do not refer to the status of the Handheld. Sta tus co lor s d o n ot hav e t he sam e m ean ing on the A RC Wi Sen sor Ad apt er

    tha t t hey do on th e A RC Vie w H and hel d.

    Section 1.5.3.1 ARC View Handheld status colors

    Figure 1.6 Status colors for sensors as shown on the ARC View Handheld.

    Color Meaning

    If a sensor panel has a green dot, the sensor it represents is correctly sending data to the Handheld. The communication medium (wireless or wired), and the sensor are both functioning correctly.

    Table 1.4 The meaning of status colors on the Handheld.

    Status symbol for sensor.Here it is yellow.

  • Section 1 The HAMILTON ARC View Handheld and System

    ARC View Handheld Operators Guide Page 1-13

    For help in correcting an unsatisfactory status, see Section 4.2, Troubleshooting Handheld sensor status colors, on Page 4-2 .

    Section 1.5.3.2 ARC Wi Sensor Adapter status colors

    NOTE: Sensor Adapter status colors do not have the same meaning as Handheld status colors. For more information, see Section 1.5.3.1, ARC View Handheld status colors .

    If a sensor panel has a yellow dot, the sensor it represents has a Warning or Error status. The associated sensor and communications link are functioning, but the sensor reading is possibly compromised. In the picture above, the DO sensor is giving a parameter measurement, but is also sending a Warning status signal. This could be, for example, because the last calibration failed, and the sensor therefore knows its reading is not accurate.You can find more information about an active Warning by going to Screen 34 on Page 3-34: [Sensor] Tools Sensor status, where you can read the warning message.You can find an explanation of all Warning and Error messages in Section 4.4, Warning Messages, on Page 4-3 and Section 4.5, Error Messages, on Page 4-6.

    If a sensor panel has a red dot, the sensor it represents has an undefined status. The sensor, the communications link (wireless or wired), or both sensor and link are not functioning at all.

    Figure 1.7 The ARC Wi Sensor Adapter.

    Sensor Adapter Meaning

    Does not illuminate This is the normal sensor status.

    The sensor is correctly connected and funct ioning normally, and the panel corresponding to the sensor is not currently selected in the Handheld.

    Table 1.5 The meaning of status colors on the ARC Wi Sensor Adapter.

    Color Meaning

    Table 1.4 The meaning of status colors on the Handheld.

    illuminate red or greenARC Wi Sensor Adapter can

  • Section 1 The HAMILTON ARC View Handheld and System

    Page 1-14 December 11, 2009

    For he lp in co rrect ing a re d status, see Sect ion 4.3, Troubleshooting ARC Wi Sensor Adapter status colors, on Page 4-2.

    Section 1.5.4 ARC sensors: calibration

    Section 1.5.4.1 Introduction

    The primary parameter of a sensor can be calibra ted to ensu re the grea test possible measurement accuracy. (The primary pa rameter of a sensor is dissolved oxygen for a DO se nsor, conductivi ty for a Cond sensor, an d so on. Temper ature is the secondary parameter in every ARC sensor, and canno t be calib rated .)

    Calib ration offsets the e ffects of t ime and wear on the sensor.

    NOTE: Operators can see calibration values for, and Specialists can configure, the primary parameter of a sensor using screens accessed from Screen 29 on Page 3-28: [Sensor] Tools Calibration.

    NOTE: Do not confuse calibration with configuration. See Section 1.5.6, ARC sensors: analog interface configuration , on Page 1-17.

    Section 1.5.4.2 Calibration procedure

    Calib ration of disso lved oxygen and pH ARC sensors takes place at two calib ration points. Calib ration of conductivi ty ARC sensors takes place at just one point. During cal ibrat ion a t each point , sensors are exposed to a def ined and s trict ly-control led environment , and their read ings compensated aga inst the known condi tions of that environment. For example, the VISI FERM DO ARC sensor is ca librat ed:

    In an envi ronment of 0% oxygen at it s fir st ca libra tion point . In an envi ronment of atmospher ic oxygen at it s second calibration poin t.

    This is shown i n Figure 1.8. Here, the two calibration poin ts are used to const ruct a vir tual curve to plot the luminescence phase shif t (the real parameter underlying the sensor's primary parameter) against t he stated primary pa rameter, namely , dissolved oxygen.

    Illuminates green Data is passing between sensor and Handheld.

    The sensor is correctly connected and funct ioning normally, and the panel corresponding to the sensor is current ly selected in the Handheld.

    Illuminates red There are three conditions in which this can happen:

    The ARC View Handheld was switched on a short time ago, and the ARC Wi Sensor Adapter is searching for connected sensors.

    The sensor is not functioning. No sensor is connected to the ARC Wi Sensor Adapter.

    Sensor Adapter Meaning

    Table 1.5 The meaning of status colors on the ARC Wi Sensor Adapter.

  • Section 1 The HAMILTON ARC View Handheld and System

    ARC View Handheld Operators Guide Page 1-15

    This curve is th en used to inter pret luminescence phase shift values during sensor o perat ion, t o give accurate d issolved oxygen measurements.

    Other ARC sensors require ca libra tion in different env ironments, and do not always use a curve to interpret the real underl ying parameter (the pH sensor uses a straight -line virtu al graph). Never theless, the principles for the calibra tion o f the primary parameter are the same for all ARC senso rs.

    NOTE: If calibration fails at one of the calibration points and a corresponding warning message is generated, this does not necessarily mean that the sensor cannot be used. In event of failure at a calibration point, the sensor uses its most recent successful calibration data for that point. Operators can see the Quality Indicator in Screen 14 on Page 3-8: [Sensor] View Sensor status.

    Section 1.5.5 ARC sensors: digital interface configuration

    Section 1.5.5.1 Introduction

    Confi gurat ion o f an ARC sensor digi tal in terface is quite simp le. There are only two parameters:

    Modbus dev ice address Baud rate

    NOTE: Specialists configure the digital interface on screens accessed from Screen 37 on Page 3-36: [Sensor] Tools Interface configuration Digital RS485.

    Figure 1.8 Calibration of the primary parameter at two points on a VISIFERM DO ARC sensor

    Oxygen (%-vol)

    Lum

    ines

    cenc

    eph

    ase

    shift

    ()

  • Section 1 The HAMILTON ARC View Handheld and System

    Page 1-16 December 11, 2009

    Section 1.5.5.2 Modbus device addresses

    Background

    Modbus is a dig ital serial communica tions protocol publi shed by Modicon for use w ith it s programmab le logic contro llers (PLCs). I t has become a stand ard commun ications p rotocol, an d is now the most commonly available means of connec ting industrial elec tronic dev ices.

    Modbus all ows f or com munication between many d evices connected to the same n etwork, for examp le, a syste m tha t measures temperatu re and hum idity and commun icates the resu lts t o a compu ter.

    HAMILTON u se a Modbus pro tocol in wh ich there is one mas ter device (the PLC or ARC View Handheld) and numerous passive slave devices ( the sensors). The master device transmit s a Modbus dev ice address to estab lish a communica tions link with a sensor. All sensors that do not have this address ign ore the transmission .

    The HAMILTON Modbus protocol i s described in detai l in the VISIFERMTM DO Modbus RTU Programmers Manual, PN 624179.

    Modbus device addresses and sensors

    An ARC sensors Modb us device address un iquely identifi es an ARC senso r with respect to it s digit al commu nicat ions wit h the PLC. The address is represented by a number in the range 1 to 30.

    NOTE: Do not confuse the Modbus device address of a sensor with its Sensor ID or Sensor Number. For more information about Sensor IDs or Sensor Numbers, see: Fig ure 1.2 , The ARC View Handheld showing top level of interface, pH sensor

    attached).. Tab le 1.1 , ARC View Handheld keys and interface. .

    By def ault, every ARC sensor has a Modbus devi ce address of 1. This is set at the factory du ring the sensor s product ion. Because of this , a new Modbus device address (in ot her words, not 1) must be configured for every ARC sensor t hat i s added to an ARC System with a dig ital P LC, thereby making sure t hat every sensor in the Sys tem has a unique address. (If two sensors have the same address, then when the PLC transmits an address , only the quicker of the two sensors responds).

    Section 1.5.5.3 Baud rates

    The Baud rate a ffects the wired connection mad e by an ARC sensors RS48 5 Modbus d igita l inter face. It has no influ ence on the ana log connect ion between a sensor and an analog PLC system. It is th erefo re on ly cr itica l for wired connections between ARC sensors an d dig ital PLC systems.

    Naturally, higher Bau d rates equate to qu icker communica tions between sensors and othe r hardware. However, h igher Baud rates can lead to unreli able connections in some instances. A typical example of this is a long cab le connection between a sensor and a digita l PLC system. It is not possib le to be specif ic about cable lengths or to o ffer recommenda tions , because variables such as cable qualit y and loca l inte rferen ce are as important as cabl e length.

    If you have an d igita l PLC system, you mus t exper iment to find the bes t combination of speed and reliabilit y.

  • Section 1 The HAMILTON ARC View Handheld and System

    ARC View Handheld Operators Guide Page 1-17

    Section 1.5.6 ARC sensors: analog interface configuration

    NOTE: Specialists configure the analog interface using screens accessed from Screen 35 on Page 3-34: [Sensor] Tools Interface configuration.

    Section 1.5.6.1 Introduction

    All ARC sensors have two analog interf aces (w ith the exception of the VISIFERM DO ARC, which has one). N ormal ly, yo u use one analog inter face for on e measurement par amete r. For exam ple, by de fault , the Easy ferm Plus s ensor uses mA inter face #1 for its primary pa rameter (pH ) and mA inter face #2 for its secondary parameter (temperatu re).

    However, you do not have to keep the defaul t sett ings. You might even want to map the senso rs primary paramete r to b oth an alog inter faces . You could then conf igure each inte rface diffe rentl y, for example, op timiz ing mA inter face #1 for pH readings be tween pH 3 and pH 4, and opti mizing mA inter face #2 for read ings between pH 6 and pH 7.

    You can configu re each of a sensors ana log interf aces indep enden tly.

    NOTE: Analog interface configuration is for both of a sensors parameters. Sensor calibration (for measurement accuracy) is for only a sensors primary parameter. (See Section 1.5.4, ARC sensors: calibration , on Page 14).

    There are four a spects to configu ring an ana log in terface:

    Selec ting the inter face/parameter combina tion. (Sectio n 1.5.6 .2, Mapping parameters to the analog interfaces).

    Selec ting the in terface mode fo r the inte rface and p arameter selected. (Sectio n 1.5.6 .3, Configuring the mode of the analog interfaces ).

    Configuring the output current for the interfa ce mode. (Section 1.5.6.4, Configuring the output current of the analog interfaces).

    Configuring Errors and Warnings for the interf ace mode. (Sect ion 1.5. 6.5, Configuring Errors and Warnings).

    Section 1.5.6.2 Mapping parameters to the analog interfaces

    Specialist s firs t defi ne the inter face/parameter combination to they will configure. Remem ber th at pH and conducti vity sensors have two analog inter faces , dissol ved oxyg en senso rs, only one. This means that for pH and conducti vity senso rs, there are two in terface/parameter combinat ions to configure.

    NOTE: Specialists map parameters to interfaces by: Select ing th e a nal og int erf ace .

    The y d o t his in Sc ree n 35 on Page 3-3 4: [Sensor] Tools Interface configuration.

    Select ing th e p ara met er the y w ish to ma p t o t he ana log in ter fac e a lready sel ect ed.The y d o t his wi th the Measurement parameter fie ld on Scr een 41 on Pag e 3-39: [Sensor] Tools Interface configuration mA interface #1 [or #2] Output current configuration.

  • Section 1 The HAMILTON ARC View Handheld and System

    Page 1-18 December 11, 2009

    Section 1.5.6.3 Configuring the mode of the analog interfaces

    Introduct ion

    Each analog interface can be switched on and off. An ac tive inter face can operate in t wo ways:

    Measuremen ts: The ou tput of the 4-20 mA in terface is a func tion of the measurement parameter.

    Test: The outpu t of the 4-20 mA inter face is a constan t signal . This cou ld be used , for example fo r tes ting of the 4-20 mA current loop.

    NOTE: Specialists choose the operation mode on Screen 40 on Page 3-38: [Sensor] Tools Interface configuration mA interface #1 [or #2] Interface mode.

    Configuration

    In reality, choice of senso r ana log interface mode requires that a number of f urther cho ices m ust be made by the Specialist . These are discussed in Sectio n 1.5 .6.4.

    Section 1.5.6.4 Configuring the output current of the analog interfaces

    Introduct ion

    Specialist s can configure t he way in which each analog inter face of the senso r sends info rmation to the PLC system. Spec ialis ts do thi s by defining the relationship between the value measured by the sensor (for instance, the pH 7) , and the e lectri c cur rent transmitted to the PLC system (for instance, 10 mA).

    NOTE: Specialists configure the analog interface ou tput current starting on Screen 40 on Page 3-38: [Sensor] Tools Interface configuration mA interface #1 [or #2] Interface mode.

    Configuration

    The Specia list has al ready decided on the opera tion mode o f the inte rface:

    Measuremen t. Test.

    (This is d iscussed in Sec tion 1.5.6. 3, Configuring the mode of the analog interfaces).

    If the Specialist is using the inte rface for measurements, he can decide whe ther the relati onship between the measured value and the outpu t current is to be determined by two po ints as a str aight -line grap h, or by three poin ts as a two-stra ight- line graph. These options are called 420 mA linear , and 420 mA in terface bili near, and are explain ed in Table 1.6, Explanation of interface modes configured on Screen 40 on Page 3-38.

    Alternatively, the Special ist can choose the test mode. This is ca lled 420 mA fixed, and is also shown in Table 1.6, Explanation of interface modes configured on Screen 40 on Page 3-38.

    If the Speciali st is not using a test mode, he now conf igures values for the relationship (linear or bilinear) he has selected . If he is using a test mode, h e can defi ne va lue for the tes t mode.

  • Section 1 The HAMILTON ARC View Handheld and System

    ARC View Handheld Operators Guide Page 1-19

    NOTE: The Specialist configures values on Screen 41 on Page 3-39: [Sensor] Tools Interface configuration mA interface #1 [or #2] Output current configuration.

    The task o f the Spec ialis t is t o con figure the senso r signal sent to the analog PLC in a way that emphasizes the measurement range th at is of most in terest . For instance, if the pH in the process is always in the range pH 4 to pH 6 , then the Spec ialist conf igures the signal fo r this range, and allows measurement values outs ide pH 4 to pH 6 to fall out of 4-20 mA range o f the analog inter face.

    Mode Explanation

    OFF The analog interface is switched off. No signals are sent.

    420 mA fixed The interface sends a continuous fixed signal fo r test purposes.

    NOTE: Specialists can configure this fixed test signal on Screen 41 on Page 3-39: [Sensor] Tools Interface configuration mA interface #1 [or #2] Output current configuration.

    420 mA linear Configuration of the interface takes place using two points. In this kind of configuration, the two points become the ends of a straight-line graph that determines the relationship between:

    The value measured by the sensor immersed in the process, for instance, the DO value.

    The output of the 4-20 mA interface to the process control system.

    The figure above shows two virtual straight-line g raphs expressing the relationship between measurements on the VISIFERM DO ARC sensor, and interfaces output current. The graphs are for dissolved oxygen and for temperature. (Both parameters cannot be mapped to the single analog interface at the same time.)

    NOTE: Specialists can enter a value for each end of the graph on Screen 41 on Page 3-39: [Sensor] Tools Interface configuration mA interface #1 [or #2] Output current configuration.

    Table 1.6 Explanation of interface modes configured on Screen 40 on Page 3-38.

    Current (mA)

    DO

    (vol

    %)

    Tem

    pera

    ture

    (C

    )

  • Section 1 The HAMILTON ARC View Handheld and System

    Page 1-20 December 11, 2009

    Section 1.5.6.5 Configuring Errors and Warnings

    Introduct ion

    Specialist s can configure the way in which the analog in terfaces o f the senso r electron icall y represent a Warning or Er ror s tatus to the PLC sys tem. I n add ition , Speciali sts can de fine the parameters for a Warn ing or Error status.

    NOTE: Specialists configure Errors and Warnings on Screen 42 on Page 3-41: [Sensor] Tools Interface configuration mA interface #1 Error/Warning configuration.

    Configuration

    The range of pa rameters available for con figuration depend on the senso r connected and the choices made in Sect ion 1 .5.6.3, Configuring the mode of the analog interfaces.

    The comple te lis t of fields is s hown on Screen 42, on Page 3-41.

    420 mA bilinear Configuration of the interface takes place using three points. In this kind of configuration, the three points define the two stra ight lines of a graph that determines the relationship between:

    The value measured by the sensor immersed in the process, for instance, the DO value.

    The output of the 4-20 mA interface to the process control system.

    The figure above shows two graphs expressing the relationship between measurements on the VISIFERM DO ARC sensor, and the output current.

    NOTE: Specialists can enter a value for each end, and the center point of the graph on Screen 41 on Page 3-39: [Sensor] Tools Interface configuration mA interface #1 [or #2] Output current configuration.

    Mode Explanation

    Table 1.6 Explanation of interface modes configured on Screen 40 on Page 3-38.

    Current (mA)

    DO

    (vol

    %)

    Tem

    pera

    ture

    (C

    )

  • Section 1 The HAMILTON ARC View Handheld and System

    ARC View Handheld Operators Guide Page 1-21

    Section 1.5.7 ARC sensors: Cleanings and Sterilizations In Place

    Clean ings In Place (CIPs) and Steri lizat ions In Place (SIPs) are both s uppor ted by the ARC System.

    NOTE: All operators can see, and Specialists can configure, the definitions and total number of CIPs and SIPs for a sensor. They do this Screen 26 on Page 3-26: [Sensor] Tools Measurement CIP/SIP definition.

    As the name suggests , a CIP and SIP are the events in wh ich a sensor is cleaned and sterilized without removing it from the process equipment. A typica l defin ition for a CIP and a SIP are shown below:

    Every ARC sensor automati cally coun ts the number o f CIPs and SIPs it ha s undergone, and records the totals internally. Depending on whether an at tempted CIP or S IP meets i ts ta rget parameters , the senso r determines the attempted CIP or S IP to have taken place or not. Figure 1.9, on Page 1-21 shows sensor recordings for the CIPs and SIPs defined in Tab le 1.7.

    Point 1: The sensor does not record a S IP because the time durat ion was too short to meet the definit ion o f a S IP shown in Tab le 1.7.

    Point 2: The sensor reco rds a CIP b ecause the time and tempe rature were in range.

    Point 3: The sensor does not record a C IP because the tempe rature cont inues to ri se above the upper maximum for a CIP. Instead, the SIP at Point 4 is reco rded.

    Temp Min Temp Max Time

    CIP 80C 100C 30 min

    SIP 120C 130C 30 min

    Table 1.7 Typical CIP and SIP definitions.

    Figure 1.9 Technique for counting CIPs and SIPs in ARC sensors.

    Time

    Tem

    pera

    ture

    (C

    )

  • Section 1 The HAMILTON ARC View Handheld and System

    Page 1-22 December 11, 2009

    Point 4: The sensor reco rds a SIP because the time and temperatu re were in range.

    Both CIPs and SIPs are wearing the sensors , and are the main cause for the l imited sensor life of senso rs from al l manufacturers . Typ ically, sensors can withs tand 5 0 to 100 CIPs and SIPs, depending on the temperature and tim e duration of the events, and a lso depend ing on whether clean ing and sterili zation agents a re used.

    With experience, opera tors can combine t he informat ion found on Scree n 26 about the number o f CIPs and SIPs that a sensor has undergone, together with the ir know ledge of the kind of CIPs and SIPs used, to estimate the remaining life-span of their sensors.

    Section 1.5.8 ARC sensor measurements: moving average

    A moving avera ge is a win dow dur ing whi ch a sensor looks back wards in time, averag ing its latest reading wi thin the w indow. The use of averaged readings can be preferable when real readings fluctuate greatly . This is because an ave raged reading is a bet ter ind icatio n of an underly ing trend than are many, variable readings.

    NOTE: A Speciali st se ts the mov ing average for a sensor on Sc reen 24 on Page 3-23: [Sensor] Tools Measurement.

    Do not co nfu se a r ead ing (o f whic h t her e c an be man y i n a mo vin g a ver age ) wit h the resol uti on valu e (V ISI FER M DO ARC only). Resolu tio n is exp lai ned in Sec tio n 1 .5.9, ARC sensor measurements: resolution.

    Mov ing av era ges are e xplain ed in gre at det ail in the VISIFERMTM DO Modbus RTU Programmers Manual, P N 624 179 .

    A moving average improves signal stabili ty over the shor t term. Howeve r, the response time of the senso r inc reases (degrades ) with the increased moving average. For examp le, V ISIFERM DO ARC calcu lates a new oxygen reading every three seconds. You can smooth this reading by means of a movi ng average (Fi gure 1.10, on Page 1-22) . Howev er, a mov ing ave rage applied to 20 thre e-second readings resul ts in a resp onse time of at leas t 60 seconds. The Special ist ca n set the number of readings i n the moving average array between 1 and 16 (pH and conductiv ity sensors) , or 1 and 30 (DO senso r), or can enter a va lue of zero (0 ) to ac tivate the automatic mod e, in wh ich the sensor vari es th is se tting depending on the measuri ng signal trend .

    Figure 1.10 Comparison of the response of VISIFERM DO ARC to a change from air to nitrogen, using n=1 (no moving average) or a moving average of n=20.

    Effects of Moving Average (n=1 and n=20)

    Oxy

    gen%

    -vol

    Time

  • Section 1 The HAMILTON ARC View Handheld and System

    ARC View Handheld Operators Guide Page 1-23

    Section 1.5.9 ARC sensor measurements: resolution

    With respec t to ARC sensor measurements, t he expression resolution refers to the number of sub-measu remen ts underlying a recorded measurement made by the VISIFERM DO ARC sensor. The expression is not used w ith any other kind of sensor, and the Resolution field is onl y avai lable on the Handheld for d issolved oxygen sensors.

    NOTE: The Speciali st sets the resolution for a VISIFERM DO ARC sensor on Screen 24 on Page 3-23: [Sensor] Tools Measurement.

    The measurement made by VISIFERM DO ARC in each 3-second inte rval is, in reality, the average of up to 16 sub-measurements (F igure 1.11, on Page 1-23) . The Spec ialis ts can set the number of

    sub-measurements between 1 and 16, or can enter a value of zero (0) to acti vate the au tomat ic mode, in which the sensor varies th is se tting depending on the measuring signal trend.

    The advantage of using a lower reso lution is the shor ter pe riod o f exposure o f the l uminophore to the exci tation light. Thi s reduces the photo bleaching of the luminophore and enhances its lifet ime, and therefore the lif etime of the sensor. The advantage o f usin g a hi gher resolution is enhanced signa l qua lity.

    Section 1.5.10 ARC sensor measurements: temperature compensation factor

    With res pect to ARC sensor measurements, the exp ressio n temperature compensation factor refers to an adjustment tha t an Specialist can make to compare the conductivi ty measurements at diffe rent temperatures. It provide s an estima te of the samp les conducti vity at a common refe rence tempe rature (25C ). The Temp. comp. factor field is available on the Handheld for conductivi ty sensors only .

    Figure 1.11 Comparison of signal stability of VISIFERM DO ARC when using a resolution of 1 and 16.

    Effects of Resolution (1 and 16) on Stability

    Oxy

    gen%

    -vol

    Time

    (Moving Average = 1 in both cases)

    Resolution = 1Resolution = 16

  • Section 1 The HAMILTON ARC View Handheld and System

    Page 1-24 December 11, 2009

    NOTE: The Specia list sets the temperature compensat ion fa ctor for a Conducell 4USF senso r on Screen 24 on Page 3-23: [Sensor] Tools Measurement.

    The temperature compensat ion factor i s the rate at whi ch a solutions conduc tivit y incr eases with an increase of temperature and is expressed as the percentage inc rease of conduct ivity for a tempe rature rise of 1 C. The compensation factor chosen by the Specialist must be depe ndent on the l iquid being mon itored by the sensor .

    Section 1.5.11 ARC sensor measurements: Quality Indicator

    With respec t to AR C sensor measurements, the ex press ion Quality Indicator refers to an esti mate made by the sensor o f the accuracy and reliab ility of i ts pri mary reading: conduc tivit y, pH , or disso lved oxygen (not temp eratu re, whi ch is the secondary reading) . The Quality Indicatorfield is available for al l ARC sensors an d rep resen ts the senso r condition in s ix gradations: Excellent, High, Acceptable, Poor, Very Poor, Defective.

    NOTE: All operators can see the Quality Indicator for a measurement on Screen 14 on Page 3-8: [Sensor] View Sensor status.

    The calcula tion o f the Quali ty Ind icato r for a sensor takes i nto consideration a n umber of factors, some senso r-specific, and some genera l. Sensor-speci fic co nside rations include:

    Disso lved oxygen sensors: luminophore status is continuously moni tored .

    pH sensors : 0 ( zero) poin t pos ition and s lope of the pH graph is ch ecked foll owing calib ration.

    Conductivi ty sensors : Cel l constant of the sensor is checked follo wing calib ration.

    General consider ations for the calcu lation of the Qualit y Ind icato r inc lude:

    The qualit y of the most recent calibration. If a calib ration fails at one of the ca libra tion po ints and a calibration warning message is generated, this does not necessarily mean that the sensor cannot be used. In event of fail ure at a calibration point, the sensor use s its most recent successful cal ibrat ion data, but the Quality Indicator can degrade.

    Because the accuracy and r eliab ility of a ll sensors can decli ne wi th use: The number of C leanings In Place (C IPs) the sensor has underg one. The number of S teril izations In Place (S IPs) the sensor has underg one. The number of operat ing hours at dif feren t temperatures. (You ca n see th ese statist ics on Screen 15 on Page 3-11: [Sensor] View Sensor status Operating hours/counters).

  • Section 2 ARC View Handheld tasks tutorial

    ARC View Handheld Operators Guide Page 2-1

    Section 2 ARC View Handheld tasks tutorial

    This section offers an introduction to the main tasks that operatorsUsers, Administrators, and Specialistsperform on a regular basis for a HAMILTON ARC System, using the HAMILTON ARC View Handheld.

    Section 2.1 IntroductionThis section guides you throu gh some of the tasks that operato rs perform with the ARC Sys tem on a dai ly basis. Before star ting this section, you must understand the d ifferent le vels of access that Users , Administrators, and Special ists have to the ARC System. For more information, see Section 1.5.2 , ARC sensors: operator levels , on Page 1-11.

    Admin istra tors and S pecial ists m ust enter a pas sword to perform Administ rator -leve l and Specialist -leve l tasks.

    Section 2.2 User tasks

    The HAMIL TON ARC System supports three kinds of operator: User, Administ rator, and Special ist. To read more about this, s ee Section 1.5.2, ARC sensors: operator levels, on Page 1-11.

    The User has the lowest level of access to the ARC System of all operat or types: he or she can only check the status of the System, and read measurements made by sensors in the Syste m.

    Task 1 Checking the status of all sensors in the ARC system

    Introduction

    The Handheld can display data from only the four (or fewer) sens ors that it activel y monito rs at any time. Data from each of these sensors is shown in a data-overv iew panel conta ining infor matio n about sensor type, pa rameters and va lues measured, and s ensor status. I f eve rything is funct ioning corr ectly , the status symbol is green (Figure 2.1).

    Actions

    1. If necessary, switch on the Handheld by pressing the Left Key and Right Key together for th ree se conds.

    2. If the Handheld is already swi tched on, press the Left Key unti l you reach the top level of the interf ace, where you see the data-ove rview panels . (Figu re 1.2, The ARC View Handheld showing top level of interface, pH sensor attached)., on Page 1-3).

    Figure 2.1 Status symbol of a sensor (top level of Handheld interface).

    Status symbol in the sensors data-overview panel.Here it is green, showing that the sensoris functioning correctly.

  • Section 2 ARC View Handheld tasks tutorial

    Page 2-2 December 11, 2009

    3. Check the s tatus of the senso rs displayed on the top level of the inter face. All status indicators must be g reen or ye llownot red. (Figure 2.1.)

    4. Use the Up Key and Down Key to scro ll and check the sta tus o f any othe r sens ors connected.

    5. If a senso r does not have a green s tatus indicator , you must read the assoc iated Warning or Error message to find out why, and then corre ct the situa tion. You can find this information in Sub-Task 3 .1, Reading sensor status data , on Page 2-3.

    Comments

    You can check the status of a senso r when the Handheld is in the Dock o r out of th e Dock.

    When you scroll to see a sensor not currently disp layed on the screen, you must wait for a new connection (cab le or wire less) to establ ish i tself between th e sensor and the Handheld . This can take some time . (The connect ion between the sensor and Process Con trol System is not affected. )

    Task 2 Reading basic parameter values from a sensor

    Sub-Task 2.1 Reading basic parameter values in numeric form

    You can read a senso rs pa ramete r valu es in numeric form f rom the top level of the Handhe lds inter face, as mentioned i n Task 1, Checking the status of all sensors in the ARC system.

    Sub-Task 2.2 Reading basic parameter values in graphic form

    Introduction

    With the ARC View Handhe ld you can observe data t rends over t ime pe riods , as we ll as real-ti me numer ic va lues. To do this , you must open a graph.

    Actions

    1. Selec t the requ ired senso r on the top level o f the inter face.

    2. Click View Graph OK.A graph similar to F igure 2.2 appears.

    Comments

    The graph begins to form as soon as you c lick OK. As ti me passes, the scale on the bottom of the graph changes from 1 minu te, to 5 minutes, to 10 minu tes. This is fully documented on Scree n 13 on Page 3-7.

    The graph function inclu des a short-t erm da ta-logging funct ion. A ll data disp layed on the graph is recorded. When the buffer is f ull, n ew da ta overwri tes th e oldest data.

    Never theless, to observe d ata concerning past event s tha t was not recorded on using the graph funct ion, u se your Process Cont rol Sy stem.

  • Section 2 ARC View Handheld tasks tutorial

    ARC View Handheld Operators Guide Page 2-3

    Task 3 Reading detailed data from a sensor

    Introduction

    As well as being able to read mea surements from a sensor, it is also possibl e to read a lot of oth er data, in addition. Categories available are:

    Sensor sta tus.This has to do with sensor wear and the sensors curren t per formance.

    Sensor informati on.This has to do with sensor identifi cation: pa rt number, softw are ve rsion , and so on.

    Inter face configurat ion.This has to do with the way in which the Spec ialis t has set up the digi tal and analog inter faces of the sensor selected.

    Sub-Task 3.1 Reading sensor status data

    Introduction

    There are five k inds of sensor s tatus data:

    The total n umber of operat ing hours during the sensors entire lifet ime. These are broken down into sub-categories : Above 110C. Above 130C.(Natu rally , the sub-category for hours above 110C also includes all hours above 130C.)

    The number of C leanings I n Place and Ste rilizations In P lace that the sensor has undergone in it s ent ire l ife.

    Figure 2.2 Graph for dissolved oxygen sensor as displayed before 1 minute has elapsed.

  • Section 2 ARC View Handheld tasks tutorial

    Page 2-4 December 11, 2009

    Warning messages associated wi th a senso r Warning status.

    Error messages assoc iated with a sensor Error status.

    Quali ty Indicator.

    Actions

    1. Selec t the requ ired senso r on the top level o f the inter face.

    2. Click View Sensor status

    You can fi nd fu ll in format ion on Screen 14 on Page 3-8: [Sensor] View Sensor status.

    Sub-Task 3.2 Reading sensor information data

    Introduction

    The data you fin d is very much as you might expect: sensor name, part number , ser ial number , and so on. The data is of use in precise ly identif ying a par ticular sensor.

    Actions

    1. Selec t the requ ired senso r on the top level o f the inter face.

    2. Click View Sensor info

    You can find full in forma tion about this scr een on Screen 16 on Page 3-12: [Sensor] View Sensor info.

    Sub-Task 3.3 Reading interface configuration data

    All HAMILTON ARC sensors have two analog inter faces with the exception of the VIS IFERM DO ARC dissolved oxyg en sensor, whi ch has only one analog interf ace (and the standard ARC digital inter face) .

    It is the task of a Specialist to configure these inter faces appropriately for the process control system. As a User, you cannot make any ch anges .

    Actions

    1. Selec t the requ ired senso r on the top level o f the inter face.

    2. Click View Interface configuration.

    You can fi nd fu ll in formation on:

    Screen 17 on Page 3-14. Screen 18 on Page 3-15. Screen 18 on Page 3-15.

    Section 2.3 Administrator tasksThe HAMIL TON ARC System supports three kinds of operator: User, Administ rator, and Special ist. To read more about this, s ee Section 1.5.2, ARC sensors: operator levels, on Page 1-11.

    In addition to his own tasks, the Admini strator can per form all User tasks.

  • Section 2 ARC View Handheld tasks tutorial

    ARC View Handheld Operators Guide Page 2-5

    NOTE: Be sure you are familiar with User tasks before continuing in this section. (See Section 2.2, User tasks, on Page 2-1.)

    Task 1 Setting the Administrator operator level

    Int roduct ion

    To be able to perform Adminis trato r tasks, an operato r must firs t enter the Adminis trato r password. This is explained immedia tely below .

    Act ions

    1. If necessary, switch on the Handheld by pressing the Left Key and Right Key together for th ree se conds.

    2. If the Handheld is already swi tched on, press the Left Key unti l you reach the top level of the interf ace, where you see the data-ove rview panels . (Figu re 1.2, The ARC View Handheld showing top level of interface, pH sensor attached)., on Page 1-3.)

    3. Selec t the sensor wi th wh ich you want to work .

    4. Click Tools.

    5. Selec t A for Admini strato r.

    6. Click OK, and enter the following password:18111978

    NOTE: The pa ssw ord sh own ab ove is the f act ory de fau lt for th e A dmi nis tra tor . T his passwo rd can be ch ang ed usi ng the ARC Sensor Configurator fre ewa re .

    Eve ry tim e t he Han dhe ld swi tch es off , e ith er man ual ly or aut oma ticall y, and eve ry tim e a n A dmi nis tra tor mo ves to a par t o f t he Han dhe ld int erf ace that is not pr ote cte d b y t he Adm ini str ato r p ass wor d, the op era tor le vel in th e ass oci ate d s ens or def aul ts to Use r.

    Task 2 Calibrating a sensor

    Int roduct ion

    When you calibrate a senso r, you cal ibrate the senso rs pr imary measurement pa rameter (dissolved oxygen, conduc tivit y, pH and s o on) . You cannot ca librat e the senso rs secondary measu remen t parameter, tempera ture.

    The ARC System applies an automatic calibration (AC) procedure and enables you, the Admin istrat or, to ea sily ca librat e senso rs. AC ut ilizes a micro processor wi thin the senso r to adju st the measurements to the va lues of the corresponding standa rds. The AC options availab le depend on sensor type (pH, conductivit y, or DO).

    Cal ibration

    Calib ration is a t wo-sta ge procedure for p H and d issolved oxygen (DO) sensors , and a one-s tage procedure for conduc tivit y sensors:

    pH and DO: calibration at data -poin t 1, f ollowed by calib ration at data-point 2. Conductivi ty: calibration at data-point 1 only .

  • Section 2 ARC View Handheld tasks tutorial

    Page 2-6 December 11, 2009

    You must apply the required conditions a t each cal ibrat ion point. This means app lying two appropriate pH so lutions for a pH sensor, t he two requir ed oxygen levels for a DO sensor, and an appropriate cal ibrat ion solution fo r the cond uctiv ity sensor .

    HAMILTOM ARC pH and conductivi ty sensors have an auto-ca librat e function , by which they automatica lly recogn ize the recomme nded HAMILTON calibra tion standard in which they are immersed. This means tha t you can choose from one of a range of HAMILTON stand ards fo r both data-point 1 and data -poin t 2 cal ibrat ion, and the sensor automatica lly calibrates appropriately.

    NOTE: You can find more sensor-specific information in the documentation that accompanies your ARC sensors.

    Act ions

    1. Selec t the requ ired sensor on the top level o f the Handhelds interface.

    2. If necessary, enter the Administrator password as descr ibed in Task 1, Setting the Administrator operator level , on Page 2-5.

    3. Go to Calibration Calibrate.You see a screen showing the two opti ons for ca libra tion (for conductivi ty sensors , only one), and the corresponding va lues for calibration standards from the last successful calib ration event. For example , for the pH sensor, you see:

    This informs you tha t for optim al accuracy you must perform the fir st stage o f the calib ration with the senso r in an env ironment of pH 4.01, and the second stage of the calibration with the sensor in an env ironment o f pH 7.00.

    4. Apply the correc t condit ions (oxygen level or standard) to the senso r for calib ration at data-point 1.

    5. Click Calibration data point 1.The f irst stage of the ca libra tion t akes place .

    6. Apply the correc t condit ions (oxygen level or standard) to the senso r for calib ration at data-point 2.

    7. Click Calibration data point 2.The second stage of the calibration takes place.

    NOTE: If calibration fails at one of the calibration points, this does not mean that the sensor cannot be used. In event of failure at a calibration point, the sensor uses its most recent successful calibration data for that point. Operators can see the Quality Indicator in Screen 14 on Page 3-8: [Sensor] View Sensor status.

    You can fi nd more in formation a bout calib ration on Screen 33 on Page 3-32: [Sensor] Tools Calibration Calibrate.

    Calibration point 1 4.01pH

    Calibration point 2 7.00pH

  • Section 2 ARC View Handheld tasks tutorial

    ARC View Handheld Operators Guide Page 2-7

    Section 2.4 Specialist tasksAs you know , the HAMILTON ARC System suppor ts thr ee kinds of opera tor: User, Admin istra tor, and Special ist. O f these, t he Speciali st has the highest level of access. (If this is no t clear, read Secti on 1.5.2, ARC sensors: operator levels, on Page 1-11. )

    In addition to his own tasks, the Specia list can perform:

    All User tasks. He can do this with or w ithou t entering the Admin istra tor password

    All Admini strator tasks. He does th is by ente ring the Administrator or Spec ialis t password.

    NOTE: Be sure you are familiar with User and Admin istrator tasks before continuing in this section. (See , Administrators and Specialists must enter a password to perform Administrator-level and Specialist-level tasks ., on Page 2-1, and Sect ion 2 .3, Administrator tasks, on Page 2-4.)

    Task 1 Setting the Specialist operator level

    Int roduct ion

    To be able to perform Speciali st tas ks, an ope rator must first ente r the Spec ialis t password . This is explained immedia tely below.

    Act ions

    1. If necessary, switch on the Handheld by pressing the Left Key and Right Key together for th ree se conds.

    2. If the Handheld is already swi tched on, press the Left Key unti l you reach the top level of the interf ace, where you see the data-ove rview panels . (Figu re 1.2, The ARC View Handheld showing top level of interface, pH sensor attached)., on Page 1-3.)

    3. Selec t the sensor wi th wh ich you want to work .

    4. Click Tools.

    5. Selec t S for Specia list.

    6. Click OK, and enter the following password:16021966

    NOTE: The pa ssw ord sh own ab ove is the f act ory de fau lt for th e S pec ial ist . T his passwo rd can be ch ang ed usi ng the ARC Sensor Configurator fre ewa re .

    Eve ry tim e t he Han dhe ld swi tch es off , e ith er man ual ly or aut oma ticall y, and eve ry tim e a Sp eci ali st mov es to a p art of the H and hel d i nte rfa ce tha t i s n ot pro tec ted by the Spe cia lis t passw ord , the operat or pa ssw ord in the ass oci ate d sensor de fau lts to Us er.

    Task 2 Adding or exchanging a sensor in an ARC system

    As a Specialist , your job includes setting up and configuring elements of the ARC Syste m. The most common task is adding or exchanging a sensor. This breaks down into the following sub-tasks .

  • Section 2 ARC View Handheld tasks tutorial

    Page 2-8 December 11, 2009

    Sub-Task 2.1 Entering the Sensor ID

    NOTE: Thi s s ub- tas k i s r ecomme nde d w hen yo u a dd an ARC se nso r t o a n A RC Sys tem .

    Thi s s ub- tas k c onc erns o nly the s ens or s d igi tal in ter fac e.

    Every sensor in an ARC System has a numb er of iden tifie rs. These include:

    The p roduc t name, fo r inst ance VISIFERM DO ARC. The f irmware ve rsion of the code included in t he sensor. The sensor s pa rt number. The sensor s serial number. The sensor s Modbus device add ress.

    All oper ators can see these fields on Screen 16 on Page 3-12: [Sensor] View Sensor info.

    Most of these id entifi ers ar e set in the fac tory, and cannot be changed. However, Spec ialis ts can change the Sensor ID . By defau lt, this s tring contains the sensor s part number followed by the senso rs serial number. It is o ften helpful to enter a st ring in thi s fie ld tha t iden tifies the senso r in the con text of your ARC System environment . For example, the stri ng Process C3might enable other operators to quickly identify the sensor within your p roces s envi ronment.

    NOTE: The Sensor ID is held in memory in the sensor. Every time you exchange a sensor for a new one, always check the ID Sensor string in the new sensor.

    You can fi nd in forma tion about changing the Sensor ID in Screen 36 on Page 3-35: [Sensor] Tools Sensor info.

    Sub-Task 2.2 Configuring the Modbus device address

    NOTE: Thi s s ub- tas k i s m and ato ry whe n y ou add an AR C s ens or to a d igi tal PL C sys tem .

    Thi s s ub- tas k c onc erns o nly the s ens or s d igi tal in ter fac e.

    An ARC sensors Modbus dev ice addr ess uniq uely identifi es an ARC sensor with in a group of ARC senso rs wi th respect to it s dig ital c ommun ications w ith a digi tal PLC system. (However, it has no effec t on communicat ions with the ARC View Handheld, or with the connection to the 4-20 mA analog interface.)

    It is recommend ed, that every senso r in an ARC Sys tem must have a unique Modbus device address. You can read more about Modbus device addresses in Secti on 1.5.5.2 , Modbus device addresses, on Page 1-16.

    You can fi nd in forma tion about sett ing th e Modbus device address for a senso r in Screen 37 on Page 3-36: [Sensor] Tools Interface configuration Digital RS485.

    Sub-Task 2.3 Configuring the Baud rate

    NOTE: Thi s sub- tas k i s reco mme nde d when you add an ARC senso r to a d igi tal PLC sys tem .

    Thi s s ub- tas k c onc erns o nly the s ens or s d igi tal in ter fac e.

  • Section 2 ARC View Handheld tasks tutorial

    ARC View Handheld Operators Guide Page 2-9

    The Baud rate a ffects the wired connection mad e by an ARC sensors RS 485 M odbus digi tal inter face. It has no influ ence on ei ther wireless o r ana log connec tion of a sensor.

    You can read mo re about Baud rates in Section 1.5.5.3, Baud rates, on Page 1-16.

    You can fi nd in forma tion about sett ing th e Baud rate for a sensor in Sc reen 37 on Page 3-36: [Sensor] Tools Interface configuration Digital RS485.

    Sub-Task 2.4 Configuring the analog interface

    NOTE: Thi s s ub- tas k i s necessary when the sensor is connec ted to an analog PLC system.

    Thi s s ub- tas k c onc erns o nly the s ens or s a nal og int erf ace .

    By configuring the ARC sensor s ana log interf ace, you make i t able to map a measured value to the 4-20 mA standard in terface. Con figura tion op tions for the ana log interface are quite extens ive, and a re explained in deta il in Sect ion 1 .5.6.3, Configuring the mode of the analog interfaces.

    If you are not using the analog connection it is recommended to switch the analog interface off .

    You can fi nd in formation about conf iguring the ana log i nterface o f a sensor in Screen 38 on Page 3-36: [Sensor] Tools Interface configuration mA interface #1.

    Sub-Task 2.5 Configuring a calibration procedure

    The ARC View Handheld util izes an au tomat ic ca libra tion procedure with prede fined set of calib ration standards where you canno t defi ne the detai ls or p erform a manual ca librat ion a t user speci fic s tandard. For exa mple, for a dissolved oxygen sensor , you could not deter mine that the first stage o f the cal ibrat ion (Calibration data point 1) should be at 10% oxyge n, and the second stage (Calibration data point 2) should be at 90% oxygen.

    However, you can conf igure calibra tion and perform the manual procedures using the ARC Sensor Configurator freeware.

  • Section 3 Reference to HAMILTON ARC View Handheld screens

    Page 3-1 November 22, 2009

    Section 3 Reference to HAMILTON ARC View Handheld screens

    This section offers full details of all screens on the HAMILTON ARC View Handheld.

    Section 3.1 ARC View Handheld screens: full listing

    Scrn Path Page

    1 Device Setup View 3-3

    2 Device Setup View Device info 3-3

    3 Device Setup View Connectivity 3-3

    4 Device Setup Tools 3-4

    6 Device Setup Tools Data management 3-4

    7 Device Setup Tools Connectivity 3-5

    12 [Sensor] View 3-6

    13 [Sensor] View Graph 3-7

    14 [Sensor] View Sensor status 3-8

    15 [Sensor] View Sensor status Operating hours/counters

    3-11

    16 [Sensor] View Sensor info 3-12

    17 [Sensor] View Interface configuration 3-14

    18 [Sensor] View Interface configuration Digital RS485

    3-15

    19 [Sensor] View Interface configuration mA interface #1

    3-16

    20 [Sensor] View Interface configuration mA interface #2

    3-17

    21 [Sensor] View Interface configuration mA interface #1 [or 2] Output current configuration

    3-17

    22 [Sensor] View Interface configuration mAinterface #1 or[or 2] Error/Warning configuration

    3-19

    23 [Sensor] Tools 3-21

    24 [Sensor] Tools Measurement 3-23

    Table 3.1 Reference list of ARC View Handheld screens

  • Section 3 Reference to HAMILTON ARC View Handheld screens

    ARC View Handheld Operators Guide Page 3-2

    25 [Sensor] Tools Measurement Measurement data 3-26

    26 [Sensor] Tools Measurement CIP/SIP definition 3-26

    27 [Sensor] Tools Measurement Graph 3-27

    28 [Sensor] Tools Measurement Measurement data Measurement data screen 1

    3-28

    29 [Sensor] Tools Calibration 3-28

    30 [Sensor] Tools Calibration Calibration data 3-29

    31 [Sensor] Tools Calibration Calibration data Calibration data point 1

    3-30

    32 [Sensor] Tools Calibration Calibration data Calibration data point 2

    3-32

    33 [Sensor] Tools Calibration Calibrate 3-32

    34 [Sensor] Tools Sensor status 3-34

    35 [Sensor] Tools Interface configuration 3-34

    36 [Sensor] Tools Sensor info 3-35

    37 [Sensor] Tools Interface configuration Digital RS485

    3-36

    38 [Sensor] Tools Interface configuration mA interface #1

    3-36

    39 [Sensor] Tools Interface configuration mA interface #2

    3-37

    40 [Sensor] Tools Interface configuration mA interface #1 [or #2] Interface mode

    3-38

    41 [Sensor] Tools Interface configuration mA interface #1 [or #2] Output current configuration

    3-39

    42 [Sensor] Tools Interface configurationmA interface #1 Error/Warning configuration

    3-41

    Scrn Path Page

    Table 3.1 Reference list of ARC View Handheld screens

  • Section 3 Reference to HAMILTON ARC View Handheld screens

    Page 3-3 November 22, 2009

    Section 3.2 ARC View Handheld screens: full details

    Screen 0: Highest level of Handheld screen interface

    Screen name: None.

    Purpose: Enables se lection of the Handhe ld it self or of a connected sensor, for monitoring or configuration.

    Comments: This scree n is fully explained in F igure 1.2, The ARC View Handheld showing top level of interface, pH sensor attached). , on Page 1-3.

    Screen 1: Device Setup View

    Screen name: ARC V iew / Device In foPurpose: Enables acc ess to information about both the Handheld it self, and a lso about

    connected sensors. This screen is not pas sword protected . All operators can access it.

    Screen 2: Device Setup View Device info

    Screen name: ARC V iew / Device in foPurpose: Displays devi ce-specifi c information such as Device ID, part number, firmwar e

    version, and so on, for t he Handheld and Dock (when the Handheld is in the Dock) . This screen is not password protected. All opera tors can access it.

    Screen 3: Device Setup View Connectivity

    Screen name: ARC V iew / Conne ctivit y

    Purpose: Displays info rmation about the number of sensors connected to the Handhe ld. This screen is not password protected. A ll operato rs can access i t.

    Comments: The total number of H andhe ld/sensor connections possible at any time is 30. Connections can be wired or wireless, depending on whether the Handheld is in its

    Dock (wired) or not in its Dock (when connections automatically become radio connections).

    All Handhe ld/sensor connections take place th rough the digital in terface.

    Sensors connected 1 Displays the number of sensors (1 to 30) currently connected to the Handheld.

  • Section 3 Reference to HAMILTON ARC View Handheld screens

    ARC View Handheld Operators Guide Page 3-4

    Screen 4: Device Setup Tools

    Screen name: ARC V iew / Device...Purpose: Enables changing of settings and fi rmware updates for t he Handheld, Dock,

    and ARC Wi Sensor Adapter . This screen is password protected . Only Admin istrat ors and Special ists can access it.

    Comments: This screen is similar to Screen 1 on Page 3-3: Device Setup View, but enables Adminis trato rs and Specialists access to screens offering more funct ions.

    Addit ional opti on Data management enables access to screens for firmware update.

    Screen 5: Device Setup Tools Device info

    Screen name: ARC V iew / Device in fo

    Purpose: Displays devi ce-specifi c information such as Device ID, part number, firmwar e version, and so on, for t he Handheld and Dock (when the Handheld is in the Dock) . This screen is not password protected. All opera tors can access it

    Comments: This screen is simila r to Screen 2 on Page 3-3: Device Setup View Device info, but enables Specia lists to change sensor Device IDs and some other data .

    Screen 6: Device Setup Tools Data management

    Screen name: ARC V iew/ Data m anagement. ..Purpose: Enables Specia lists to perform a firmware update for Handheld, Dock and ARC

    Wi Sensor Adapter. ARC Fi rmware update f iles are delivered on a US B memory sti ck.

    Baud rate 19200 Displays the Baud rate of the digital interface between the Handheld and all connected sensors.

    (Specialists can change the Baud rate in Screen 7 on Page 3-5: Device Setup Tools Connectivity.)

    NOTE: For more information about Baud rates, see Section 1.5.5.3, Baud rates.

  • Section 3 Reference to HAMILTON ARC View Handheld screens

    Page 3-5 November 22, 2009

    Comments: This scree n is password p rotec ted. Only Specialist s can acces s it. The Handhe ld must be in the docking posi tion, and the Dock must be

    connected to the power supply. To update the ARC Wi Sensor Adapter , connect it wit h its cable to the Dock. Connect the USB memory stick containing update to the USB port of the Dock. Choose the corresponding update opt ion on the screen and cli ck OK.

    Screen 7: Device Setup Tools Connectivity

    Screen name: ARV V iew / Connectivi ty...

    Purpose: This screen is the same as Sc reen 3 on Page 3-3: Device Setup View Connectivity, but enab les Specia lists to change the Baud rate of Handheld..

    Screen 8: Device Setup Tools Set date

    Screen name: ARC V iew/ Set date.. .Purpose: Enables Special ist to set current da te.

    Firmware update ARC View Update for Handheld or Dock.

    Firmware update RF module Update for Handhelds wireless module.

    Firmware update ARC Dock Update for the ARC Dock.

    Firmware update ARC Wi Update for ARC Wi Sensor Adapter.

    Sensors connected 1 Displays the number of sensors (1 to 30) currently connected to the Handheld.

    Baud rate 19200 Displays the Baud rate of the digital interface of the Handheld.

    Click OK to access a screen enabling you to change the Baud rate for Handheld. Affects the wired connection between Handheld and sensor.

    NOTE: For more information about Baud rates, see Section 1.5.5.3, Baud rates.

    Set date 01.12.2009 day.month.year

  • Section 3 Reference to HAMILTON ARC View Handheld screens

    ARC View Handheld Operators Guide Page 3-6

    S