7EM Temperature Controllers
Con
trol
lers
1250-DB-100-0-0176 Barber-Colman Company, Loves Park, IL
p
ADVANTAGE EZSeries 7EM
1/8 DIN Temperature Controller
• Dual 3 Digit LED Display• Input (T/C, RTD)• Autotuning• NEMA 4X• 100 to 240 Vac Switching Power Supply• Algorithms for Heat or Heat/Cool Control• Up to 3 Outputs• Up to 2 Independent Alarms Configurable
with Automatic or Manual Reset• Control Output Disable Function
The Advantage EZ 7EM 1/8 DIN Controllers are configurable autotuningcontrollers for applications where input ranges do not exceed 999.
Optional Features
• 24 Vac/Vdc Supply• Heater Breakdown Input• Two Temperature Alarms• Heater Breakdown Alarm and Load Current Display in Engineering Units
Introduction
The Barber-Colman Series 7 establishes a new class of microprocessor basedtemperature controllers. As part of the Series 7 family, the 7EM offers outstand-ing performance features in a cost effective package. Designed specifically forequipment manufacturers who demand tight process control, the 7EM has a va-riety of standard features commonly found as options on our competitors control-lers. NEMA 4X faceplates allow these units to be used in severe conditions. The3 digit display offers complete coverage for extrusion and environmental cham-ber applications without excess cost for unused digits.
The 7EM is easy to configure and use. Even operators without skills in tempera-ture process control or knowledge of PID control parameters can obtain perfectcontrol. For best results in control stability, simply:
• wire the instrument• configure the setpoint and alarm thresholds• initiate the autotune function
7EM Temperature Controllers
1250-DB-100-0-01 77Barber-Colman Company, Loves Park, IL
Con
trol
lers
p
Ordering Information
1/8 DIN Three Digit DisplayTemperature Controller
MODEL: 0 7 E M - 4 3 1 1 - 0 0 - 0 - 0 0Field No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Fields 1 through 4. BASE07EM - Controller
Field 5. INPUT4 - TC types J, K, L and N; Pt 100, 3 wire RTD
Note: All inputs are factory calibrated and selectableby keyboard. Factory set at Type J.
Field 6. CONTROL ACTION3 - PID and Smart AT
Field 7. OUTPUT 1 (Heating)1 - Relay (SPDT) or SSR Driver (jumper selectable)
Field 8. OUTPUT 2 (Cooling/Alarm 1)1 - Relay (SPST–NC or NO jumper selectable)
or SSR Driver (jumper selectable)
Field 9. OUTPUT 30 - None1 - Alarm 2 (when output 2 configured for alarm 1)2 - Alarm 2, plus Hbd Input (heater breakdown).
Order transformer separately.Field 10. POWER SUPPLY
3 - 100 to 240 Vac5 - 24 Vac/Vdc
Fields 11 through 15. RESERVED
07EM-43110-300-0-00 PID with autotune, two programmable outputs, 100 to 240 Vac07EM-43110-500-0-00 PID with autotune, two programmable outputs, 24 Vac/Vdc07EM-43111-300-0-00 PID with autotune, two programmable outputs, alarm, 100 to 240 Vac07EM-43111-500-0-00 PID with autotune, two programmable outputs, alarm, 24 Vac/Vdc07EM-43112-300-0-00 PID with autotune, two programmable outputs, alarm, Hbd Input , 100 to 240 Vac
Shading denotes commonly stocked item. Standard lead time applies.
Available Models
7EM Temperature Controllers
Con
trol
lers
1250-DB-100-0-0178 Barber-Colman Company, Loves Park, IL
Specifications
Case: ABS black. Self-extinguishing degree V-0 according to UL, VDE and CSA.Front Protection: Designed and tested for IP54 according to IEC 529 and CEI 70-1.Installation: Panel mounting by means of brackets.Rear Terminal Block: Up to 21 screw terminals, with safety rear cover.Dimensions: 48 x 96 mm (1.890 x 3.780 in.) according to DIN 43700; 89 mm (3.504 in.) deep.Weight: 400 grams maximum (1 pound).Power Supply(Switch Mode): - 100 to 240 Vac. 50/60 Hz (10% to -15% of the nominal value).
- 24 Vac/Vdc. (±10% of the nominal value).Power Consumption: 11 VA.Insulation Resistance: Greater than 2 GΩ for 500 Vdc according to IEC 348.Isolation Voltage: 1500 Vrms according to IEC 348.D/A Conversion: Dual slope integration.Noise Immunity: a)Electrical fast transient/burst requirements:
Severity Level 3 (according to IEC 801-4).b)Electric discharge requirements:
Severity Level 8 (according to IEC 801-2).Sampling Time: 500 ms.Accuracy: ±0.2% full scale span or ±1°C, @ 25 °C and nominal power supply voltage.Common ModeRejection Ratio: 120 dB @ 50/60 Hz.Normal ModeRejection Ratio: 60 dB @ 50/60 Hz.Operating Temperature: From 0 to 50 °C.Storage Temperature: From -20 to 70 °C.Humidity: From 20% to 85% RH non-condensing.Protection: Internal jumper for configuration and calibration parameters.
Control Action
On/Off, PID or Smart AT AutotuningSpecial Function: Standby alarm sequence.
Inputs (All inputs are factory calibrated and selectable from the keyboard.)
Types: Thermocouples (J, K, L, N, T) or RTD Pt 100, keyboard configurable.Engineering Units: °C and °F keyboard configurable.Reference Junction: Automatic compensation for an ambient temperature between 0 and 50 °C.Line Impedance: 100 Ω maximum for TC input.
20 Ω/wire maximum for RTD input.Reference Junction Drift: 0.1 °C/°C.Input Impedance: Greater than 1 MΩ.Sensor Break: Downscale or upscale programmable. On RTD inputs, an OVERRANGE is indi-
cated when input resistance is less than 15 Ω (short circuit sensor detection.)Calibration: According to IEC 584-1 and DIN 43710-1977.
p
7EM Temperature Controllers
1250-DB-100-0-01 79Barber-Colman Company, Loves Park, IL
Con
trol
lers
p
Specifications (continued)
Standard Ranges
Current Transformer Input for OUT 1 Heater Breakdown Detection (Optional)
This feature allows measurement of the load current by means of a current transformer and signals an alarmcondition when the current is below a pre-programmed threshold value.
Input Range: 50 mAac.Scaling: Configurable from 10 Amps to 100 Amps (with a 1 Amp step).Resolution: - for full scale up to 20 Amps: 0.1 Amp.
- for full scale from 21 Amps to 100 Amps: 1 Amp.Active Period: - for relay output: NO or NC configurable.
- for SSR output: logic level 1 or 0 configurable.Minimum On Time to performthe measurement: 50 ms.
Outputs
Main Output: (Heating)Relay or SSR (jumper selectable)- Relay SPDT, contact rating 3 Amps @ 250 Vac on resistive load.- Logic output for SSR, 700 Ω maximum load, short circuit protected.
Logic Level 1:14 Vdc ±20% @ 20 mA max.24 Vdc ±20% @ 1 mA max.
Logic Level 0:Less than 0.5 Vdc
Output 2 (Cooling or Alarm 1)Relay or SSR (jumper selectable)- Relay SPST, contact rating 2 Amp @ 250 Vac on resistive load.- Logic output for SSR, 700 Ω maximum load, short circuit protected.
Logic Level 1:14 Vdc ±20% @ 20 mA max.24 Vdc ±20% @ 1 mA max.
Logic Level 0:Less than 0.5 Vdc
Output 3 (Alarm 2 or Heater breakdown)- Relay SPST, contact rating 2 Amp @ 250 Vac on resistive load.
(normally open contact only)
tupnI segnaR
L C˚008ot0 F˚999ot0 7791-01734NID
J C˚008ot0 F˚999ot0 1-485CEI
K C˚999ot0 F˚999ot0 1-485CEI
N C˚999ot0 F˚999ot0 1-485CEI
001tPDTR C˚9.99ot9.91- 06734NID
001tPDTR C˚005ot991- F˚999ot991- 06734NID
7EM Temperature Controllers
Con
trol
lers
1250-DB-100-0-0180 Barber-Colman Company, Loves Park, IL
p
Specifications (continued)
AlarmsAlarm Functions: Process Alarm
Deviation AlarmBand Alarm
Type of Alarm: - High/Low (Outside/Inside for band alarm)- Direct/Reverse- Standby Sequence/No Standby Sequence
Alarm Hysteresis: 0.1 to 10.0% of input span or 1 least significant digit.Alarm Output: Relay SPST 2 Amp @ 250 Vac resistive load.
Display Characteristics
Upper Display: 3 digit 7 segment green LED display; 10 mm high.Lower Display: 3 digit 7 segment orange LED display; 7.6 mm high.Indicators: 1 red LED when main (heating) output is ON.
1 red LED when cooling (or alarm 1) output is ON.1 red LED when alarm 2 (or hbd alarm) output is ON.1 red LED when Smart AT is enabled.
Operator Interface
Upper DisplayShows the actual measured value or
(during configuration) the value of theselected parameter.
Lower DisplayShows the operating setpoint; the heater
current (in Amps); and the abbreviatedname of the selected parameter.
Keyboard DescriptionDecreases the selected parameter.
Increases the selected parameter.
Displays in sequence all parametersand saves new settings or displaysthe output level and heater current.
Starts the default param-eter loading procedure.
Enables/disables the out-put power OFF function.
FUNC
+ FUNC
+
MAIN AL1COOL
AL2HB
AT
PV
SV
AT
FUNC
IndicatorsMAIN Lit during the ON period of the heating
cycle.
AL1COOL Lit when Alarm 1 is ON or during the ON
period of the cooling cycle.
AL2HB Lit when Alarm 2 is in ON or when the heater
breakdown alarm is ON.
AT Flashes during startup autotuning. Litsteadily during adaptive autotuning.
7EM Temperature Controllers
1250-DB-100-0-01 81Barber-Colman Company, Loves Park, IL
Con
trol
lers
p
Wiring
Rear Terminal Block
PWR LINE100/240Vac24 Vac/Vdc
12
13
15
14SSR
AL1/C
IN-CT
16
17
18
19
21
22 11
10
9
8
7
6
5
4
3
TC
1
20
RT
D
AL2/HB
NO
C
AL1/C
C
NO
SSRMAIN
+
-
MAIN
NO
NC
C
+
-
Controller Wiring
Power Line WiringNOTE: Connect neutral to terminal 12.
Before connecting power to the instrument,make certain the line voltage corresponds tothe model number.
To avoid electric shock, connect the powerline at the end of the wiring procedure.
24 Vdc supplies are not polarity sensitive.
12
13
Power Supply
100 to 240 Vac RMSor
24 Vac/Vdc
6
7
Heater
Currenttransformer
7EM Temperature Controllers
Con
trol
lers
1250-DB-100-0-0182 Barber-Colman Company, Loves Park, IL
p
Wiring (continued)
4 3 1 4 3 1
RTD RTD
RTD Input Wiring
Thermocouple Input Wiring
3
1
_
Shield
_ 3
1
Shield
NOTE: Any external components (like zener diodesetc.) connected between sensor and input ter-minals may cause errors in measurement dueto excessive or unbalanced line resistance, orpossible leakage currents.
Voltage Output for SSR Drive
Logic voltage for SSR drive.Logic status 1: 24V +20% @ 1 mA
14 V +20% @ 20 mALogic status 0: Less than 0.5 V
NOTE: This output is not isolated. Isolation betweeninstrument output and power supply must beassured by the external solid state relay.
Solid State Relay
18
19
_
_OUT 1(Main)
Solid State Relay
14
15
_
_
OUT 2(Al 1/Cool)
Input Wiring
NOTE: Do not run input wires together with powercables. For TC wiring use proper compensat-ing cable, preferably shielded. If shieldedcable is used, it should be grounded at onepoint only.
Do not run RTD wires together with powercables. If shielded cable is used, it should begrounded at one point only. Use copper wiresof the appropriate size (see "Specifications").The resistance of the 3 wires must be thesame.
7EM Temperature Controllers
1250-DB-100-0-01 83Barber-Colman Company, Loves Park, IL
Con
trol
lers
p
Wiring (continued)
16
17C
NO
OUT 2(Al 1/Cool)
OUT 3(Al 2/Hbd)
20
21
22
C - OUT 1
NC - OUT 1
NO - OUT 1OUT 1(Main)
11
10C
NO
C
R
LOAD
RC
PowerLine
External Switch in Series with the Internal Contact
Inductive Loads
High voltage transients may occur when switching in-ductive loads. These transients may introduce distur-bances which can affect the performance of the in-strument. The internal varistor assures protection upto 0.5 Amp of inductive component of the load. Thesame problem may occur when a switch is used inseries with the internal contacts. In this case, it is rec-ommended to install an additional RC network acrossthe external contact as shown.
Relay output wiring must be as far away as possible from input or communication cables.
The value of capacitor (C) and resistor (R) are shown in the following table.
LoadCurrent
Less than 150 mALess than 0.5 AmpLess than 1 Amp
C(uF)0.1
0.330.47
ResistorPower (W)
222
Resistor andCapacitor Voltage
260260260
R(W)224747
Relay Output Wiring
The relay outputs are protected by a varistor. Refer tothe specifications for contact ratings of individual re-lays.
See “Controller Mounting Dimensions” at the end of this section.
7SL Limitrols
Con
trol
lers
1250-DB-100-0-01200 Barber-Colman Company, Loves Park, IL
ADVANTAGE EZSeries 7SL
1/16 DIN Limitrol
The Advantage EZ 7SL 1/16 DIN Limitrols are configurable high/low limit devicesdesigned to be used where small panel space requirements exist.
Also available withDIN rail mount
Optional Features
Introduction
The Barber-Colman Series 7 establishes a new class of microprocessor basedtemperature controllers. As part of the Series 7 family, the 7SL offers safety limitfunctionality in a 1/16 DIN package. Designed specifically for equipment manu-facturers who require high limit safety, the 7SL has a variety of standard featurescommonly found as options on our competitors controllers. NEMA 4X faceplatesallow these units to be used in applications where severe conditions exist. The 2display faceplate allows the operator to configure the instrument with simple,easy to use codes.
The 7SL can be set to either a high or low limit. In addition, the 7SL can be set asa high/low limit which provides two independent setpoints. In this mode, theprocess must be within the two setpoints or the unit resets. A logic input, whichcan be used for remote reset, is optionally available
The 7SL was specifically designed with one optional alarm. This alarm can beconfigured as a process high, process low, band or deviation alarm. As such, thisalarm can act as a process event to begin data acquisition or recording as yourprocess nears unsafe conditions.
The 7SL is easy to configure and use. Operators with no skills in temperatureprocess control or knowledge of high limit control parameters can achieve idealresults. Simply wire the instrument and configure the setpoint and alarm thresholds.
• 4 Digit LED Display• Universal Input (T/C, RTD, mV, V, mA)• NEMA 4X• 100 to 240 Vac Switching Power Supply• 3 Level Passcode Security• High Limit, Low Limit or High/Low Limit• Time in Reset Display• Peak Temperature Display
• 24 Vac/Vdc Supply• Logic Input (Remote Reset)• RS-485 Digital Communications
• Additional Alarm• Wall or Rail Mount
7SL Limitrols
1250-DB-100-0-01 201Barber-Colman Company, Loves Park, IL
Con
trol
lers
Shading denotes commonly stocked item. Standard lead time applies.
Field No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Available Models
Panel Mount
7SL-91003-000-0-00 Form C Relay Output, 100 to 240 Vac7SL-91103-000-0-00 Form C Relay Output, Alarm, 100 to 240 Vac7SL-91113-000-0-00 Form C Relay Output, Alarm, RS-485 & Logic Input, 100 to 240 Vac7SL-91005-000-0-00 Form C Relay Output, 24 Vac/Vdc7SL-91105-000-0-00 Form C Relay Output, Alarm, 24 Vac/Vdc7SL-91115-000-0-00 Form C Relay Output, Alarm, RS-485 & Logic Input, 24 Vac/Vdc
DIN or Rail Mount
7SL-91003-0R0-0-00 Form C Relay Output, 100 to 240 Vac7SL-91103-0R0-0-00 Form C Relay Output, Alarm, 100 to 240 Vac7SL-91113-0R0-0-00 Form C Relay Output, Alarm, RS-485 & Logic Input, 100 to 240 Vac7SL-91005-0R0-0-00 Form C Relay Output, 24 Vac/Vdc7SL-91105-0R0-0-00 Form C Relay Output, Alarm, 24 Vac/Vdc7SL-91115-0R0-0-00 Form C Relay Output, Alarm, RS-485 & Logic Input, 24 Vac/Vdc
Fields 1 through 4. BASE07SL - Limitrol (shipped as high limit).
Field 5. INPUT9 - TC types J, K, T, E, N, S, R, B, L, U, G, D, C and
Platinel II; RTD Pt 100;0 to 20 mAdc and 4 to 20 mAdc;0 to 60 mVdc and 12 to 60 mVdc;0 to 5 Vdc or 1 to 5 Vdc;0 to 10 Vdc or 2 to 10 VdcNote: All inputs are factory calibrated andselectable by jumper. Factory set at Type J.
Field 6. OUTPUT (High/Low Limit)1 - Relay (Form C)
Fields 7, 8. OPTIONS00 - None10 - RS-485* and one logic input11 - RS-485*, one logic input,
and one Form A alarm relay*Controllers with RS-485 require a longer case. See“Controller Mounting Dimensions” section.
Field 9. POWER SUPPLY3 - 100 to 240 Vac5 - 24 Vac/Vdc
Fields 10. RESERVED
Field 11. MOUNTING0 - Panel MountR - Wall or Rail Mount
Field 12 through 15. RESERVED
Ordering Information
MODEL 0 7 S L - 9 1 - 0 0 - 0 - 0 0
7SL Limitrols
Con
trol
lers
1250-DB-100-0-01202 Barber-Colman Company, Loves Park, IL
Specifications
Case: ABS Grey. Self-extinguishing degree V0 according to UL 94.Front panel: Designed and tested for IP65 and NEMA 4X for indoor location with panel gasket installed.
(Tests performed in accordance with IEC 529, CEI 70-1 and NEMA 250-1991 STD.)Installation: Panel mounting; wall or DIN rail mountingRear terminal block(panel mt): 15 screw terminals with safety rear cover.Dimensions: DIN 43700 48 x 48 mm (1.890 x 1.890 in) 122 mm (4.803 in) depth (non RS-485 units-105mm).Cut-out: 45 x 45 mm (1.772 x 1.772 in).Weight: 250 grams (8.75 oz).Upper display: 4 digits, 7 segment red LEDs with decimal point, 7.62 mm (5/16 in) high.Lower display: 2 digits, 7 segment red LEDs with decimal point, 7.62 mm (5/16 in) high.Indicators: 2 red LED annunciators for
RESET Indicates control output status as follows:a) With the Ack mode (parameter c2) = 0, an acknowledge is ignored if
performed while setpoint is exceeded and:The Reset LED will be ON when the Output is OFF.The Reset LED will be OFF when the Output is ON.
b) With the Ack mode (parameter c2) = 1, an acknowledge is recognizedif performed while the setpoint is exceeded (the output will be restoredonce the process is within setpoint) and:The Reset LED will flash when the Output is OFF.The Reset LED will be ON when the Output is OFF & acknowledged.The Reset LED will be OFF when the Output is ON.
ALM Flashes when the alarm is ON.ON when alarm has been acknowledged.OFF when alarm is off.
RMT The decimal point at the righthand of the LSD on the upper display is used(flashing) to indicate that the device is controlled by serial link.
Keyboard: Four keys (polyester membrane) labeled “RESET,” “,” “” and “FUNC.”Power supply: From 100 to 240 Vac 50/60 Hz switching or 24 Vac/Vdc. Device power interruptions must
be less than 100 ms.Power supply variation: From -15% to 10% (for 100 to 240 Vac).
From -10% to 10% (for 24 Vac/Vdc).Power consumption: 8 VA maximum.Insulation resistance: Greater than 100M Ω.Insulation strength: 1500 Vrms for 1 minute.Noise immunity: Conforms with EEC 89/336 directive regarding electromagnetic compatibility.
Emission Complies with:Generic emission standard EN50081-2Basic emission standard EN55011.
Immunity Complies with the generic immunity standard EN50082-2:a) Radio frequency electromagnetic field (amplitude modulation):
severity level 3 (according to ENV50140).b) Electrostatic discharge requirements severity level 3
(according to IEC 1000-4-2).c) Electrical fast transient/burst requirements: severity level 3
(according to IEC 1000-4-4).d) Radio frequency common mode: severity level 3
(according to ENV50141).e) Power frequency magnetic field: severity level 4
(according to EN61000-4-8).f) Radio frequency electromagnetic field (pulse modulation)
(according to ENV50140 and ENV50204).Sampling time: 250 ms for linear input.
500 ms for TC/RTD input.Display update time: 500 ms.
The display value can be filtered.
7SL Limitrols
1250-DB-100-0-01 203Barber-Colman Company, Loves Park, IL
Con
trol
lers
Specifications (continued)
Reference Accuracy: ±0.2% full scale value ±1 digit @ 25˚C and nominal power supply voltage.Temperature drift: Less than 200 ppm/˚C of full span for mV and TC ranges 1, 2, 4, 5, 9 and 14 (CJ excluded).
Less than 300 ppm/ˆC of full span for mA/V and TC ranges 11, 12 and 13 (CJ excluded).Less than 400 ppm/ˆC of full span for RTD range 15 and TC range 10 (CJ excluded).Less than 500 ppm/˚C full span for TC ranges 3, 6 and 7 (CJ excluded).Less than 600 ppm/˚C of full span for TC range 8.Note: Precision and drift guaranteed (for T > 300˚C/570˚F).
Reference junction drift: 0.1 ˚C/˚C.Common mode rejection ratio: 120 db @ 50/60 Hz.Normal mode rejection ratio: 60 db @ 50/60 Hz.Ambient temperature: From 0 to 50 ˚C.Storage Temperature: From -20 to 70 ˚C.Humidity: Max 85% RH non condensing.Input: Selectable by keyboard or jumperRange:
tupnIrebmuN
tupnI segnaR
1 JCT C˚0001ot001- F˚0381ot051- 1-485CEI
2 KCT C˚0731ot001- F0052ot051- 1-485CEI
3 TCT C˚004ot002- F˚057ot033- 1-485CEI
4 ECT C˚008ot001- F˚0741ot051- 1-485CEI
5 NCT C˚0041ot001- F˚0552ot051- 1-485CEI
6 SCT C˚0671ot05- F˚0023ot06- 1-485CEI
7 RCT C˚0671ot05- F˚0023ot06- 1-485CEI
8 BCT C˚0281ot0 F˚0033ot23 1-485CEI
9 LCT C˚009ot002- F˚0561ot033- 7791-01734NID
01 UCT C˚006ot001- F˚0111ot051- 7791-01734NID
11 GCT C˚0032ot0 F˚0714ot0
21 DCT C˚0032ot0 F˚0714ot0
31 CCT C˚0032ot0 F˚0714ot0
41 IIlenitalPCT C˚0041ot001- F˚0552ot051-
51 001TPDTR C˚058ot002- F˚0651ot033- 06734NID
- raeniL cdAm02ot0
- raeniL cdVm06ot0
- raeniL cdV5ot0
- raeniL cdV01ot0
7SL Limitrols
Con
trol
lers
1250-DB-100-0-01204 Barber-Colman Company, Loves Park, IL
Specifications (continued)
Source impedence: 100Ω maximum for TC/mV input.Less than 20Ω per wires for RTD input.
Input impedence: Greater than 1M Ω for TC/mV input.Greater than 400K Ω for 5 V to 10V input range.Less than 5Ω for mA input.
Cold junction: Automatic compensation from 0 to 50 ˚C.Digital input: Input from dry contact (voltage free) to restart process (optional).Control OUT 1: Relay (form C) 3 Amps @ 250 Vac, resistive load (with varistor on contacts).
(Relay operates in failsafe mode.)Limit type: High limit (for heating process).
Low limit (for cooling process).High/Low limit (for special process).
Acknowledgement mode: In order to restart process two conditions must occur:a) The process returns within setpoint.b) The operator has acknowledged the process (from keyboard or digital input or serial
link).The “a” and “b” sequence may or may not be important depending on how parameter C2,acknowledge mode, is configured.
Limit Function when C1 = Hi and C2 = 0
A, B, C = Acknowledgment by “RESET” key, digital inputor serial link.
Note that acknowledgment B has no effect.
(Hysteresis)
FlashUpper display
Steady
ON"Reset" LED
OFF
ONRelay OUT 1
OFF
A B C
(Setpoint)(Hysteresis)
FlashUpper display
Steady
ON"Reset" LED
OFF
ONRelay OUT 1
OFF
A B
(Setpoint)
FLASH FLASH
Limit Function when C1 = Hi and C2 = 1
A, B = Acknowledgment by “RESET” key, digital inputor serial link.
Powerup mode: Automatic or Manual restart.(When in automatic restart the control output is guaranteed OFF for 1 second.)
Setpoint threshold: Span limits.Threshold hysteresis: From 0.1 to 10.0% of span or ±1 digit.OUT 2: Relay (form A) 2 Amps @ 250 Vac resistive load.
OUT 2 is used as alarm output (optional).Alarm function: Process alarm.
Deviation alarm.Band alarm.
Type of alarm: High/Low (Outside/Inside if band alarm).Direct/Reverse.Automatic/Manual reset.Standby sequence/No standby sequence.
Alarm threshold: Span limits for process alarm.From 0 to 500 digits for band alarm.From -500 to 500 digits for deviation alarm.
Alarm hysteresis: From 0.1 to 10.0% of span or ±1 digit.Serial interface: RS-485, opto-isolated (optional).Protocol type: Modbus/Jbus (RTU mode).
7SL Limitrols
1250-DB-100-0-01 205Barber-Colman Company, Loves Park, IL
Con
trol
lers
+ Initiates the default parameter loading pro-cedure.
+ Increases or decreases the values at ahigher rate when modifying parameters.
+
+ Jumps to the maximum or minimum param-eter value when modifying parameters.
+
Note: All the actions explained above which require twoor more keys must follow (exactly) the key sequenceshown.
Operator Interface
FUNC
RESET
FUNC
RESET
Keyboard Description
Used to manually “reset” control action whenpressed for more than 1 second. When monitor-ing/modifying parameters and during calibration/configuration it scrolls back the parameters.
During normal operation, key is used to changedisplayed information. In calibration, configurationor routine parameter modes, key decreases theselected parameter.
During normal operation, key is used to changedisplayed information. In calibration, configurationor routine parameter modes, key increases the se-lected parameter.
During operating mode, pressing the “FUNC” keystarts parameter modification.Pressing and holding the “FUNC” key for more than10 seconds initates a lamp test.Pressing the “FUNC” key again ends the lamp test.During configuration and calibration modes the“FUNC” key stores the modified parameter and dis-plays the next parameter.
FUNC
RESET
Specifications (continued)
Device address: From 1 to 255Note: The interface can support only 31 devices.
Baud rate: 600 to 19200 baud.Format: 1 start bit.
8 bits with/without parity.1 stop bit.
Parity: Even/Odd.Watchdog: Hardware and Software Watchdog circuits provided for automatic restart.Protection: Internal dip switch for calibration and configuration parameters protection.
RESET
ALM
°F
RMT
LIMITROL 7SL
RESET FUNC
Barber-Colman
Upper DisplayShows the actual measured value or(during configuration) the value of theselected parameter.
Lower DisplayShows the abbreviated name of theselected parameter.
IndicatorsRESET
Alarm
7SL Limitrols
Con
trol
lers
1250-DB-100-0-01206 Barber-Colman Company, Loves Park, IL
Wiring
Rear Terminal Block
w/o RS-485 w/ RS-485
1
3
4
5
6
7
8
9
10
2
NC
CLI
NE
AR
PW
R L
INE
100/
240V
ac
NOC
NO
OUT 2
OUT 1
TC
RT
D
+
_
1
3
4
5
6
7
8
9
10
2
11
13
14
15
12RS 485
NC
C
LIN
EA
R
PW
R L
INE
100/
240V
ac
A/A'
B/B'
NO
DIG 1
C
C
NO
OUT 2
OUT 1
TC
RT
D
+
_
4
5
Power Supply
100 to 240 Vac rmsor
24 Vac/Vdc(Optional)
Thermocouple Input Wiring
9
10
_
Shield
+
_ 9
10
Shield
+
Power Line Wiring NOTE:Connect neutral to terminal 4.
Before connecting power to the instrument,make certain the line voltage corresponds tothe model number.
To avoid electric shock, connect the powerline at the end of the wiring procedure.
24 Vdc supplies are not polarity sensitive.
Input Wiring
NOTE: Do not run input wires together with powercables. For TC wiring use propercompensating cable, preferably shielded. Ifshielded cable is used, it should be groundedat one end only.
Do not run RTD wires together with powercables. If shielded cable is used, it should begrounded at one end only. Use copper wiresof the appropriate size (see "Specifications").The resistance of the 3 wires must be thesame.
7SL Limitrols
1250-DB-100-0-01 207Barber-Colman Company, Loves Park, IL
Con
trol
lers
6C
OUT 2(Al 1)
2
1
3
C - OUT 1
NC - OUT 1
NO - OUT 1OUT 1(Main)
7NO
External Switch in Series with the Internal Contact
C
R
LOAD
RC
PowerLine
Relay output wiring must be as far away as possible from input or communication cables.
The value of capacitor (C) and resistor (R) are shown in the following table.
LoadCurrent
< 150 mA< 0.5 Amp< 1 Amp
C(uF)0.1
0.330.47
ResistorPower (W)
222
Resistor andCapacitor Voltage
260260260
R(Ω)224747
8 9 10 8 9 10
RTD RTD
RTD Input Wiring
NOTE: Any external components (like zener diodesetc.) connected between sensor and inputterminals may cause errors in measurementdue to excessive or unbalanced line resistance,or possible leakage currents.
Inductive Loads
High voltage transients may occur when switching inductiveloads. These transients may introduce disturbances whichcan affect the performance of the instrument. The internalvaristor assures protection up to 0.5 Amp of inductive com-ponent of the load. The same problem may occur when aswitch is used in series with the internal contacts. In thiscase, it is recommended to install an additional RC networkacross the external contact as shown.
Relay Output Wiring
The relay outputs are protected by a varistor. Refer to thespecifications for contact ratings of individual relays.
Wiring (continued)
See “Controller Mounting Dimensions” at the end of this section.
Logic Input WiringSafety note:- Use an external contact with a contact rating
greater than 0.5 mA, 5 Vdc.- The instrument needs 100 ms to recognize a
change in contact status.
14
15
Locic Input
7SD/7SH/7SM Temperature Controllers
Con
trol
lers
1250-DB-100-0-0144 Barber-Colman Company, Loves Park, IL
ADVANTAGE EZSeries 7SD, 7SH, 7SM
1/16 DIN Temperature Controllers
• 3-Digit LED Display• Thermocouple and RTD Input• Autotuning• NEMA 4X• Field Configurable• 100 to 240 Vac
Switching Power Supply• Programmable Soft Start• Setpoint Ramp• Password Security• Alarm Standby
The Advantage EZ 1/16 DIN Controllers are configurable general purposecontrollers for applications where input ranges do not exceed 999.
Optional Features
• Heat/Cool Control (7SH) • Relay or SSR DRIVER Output• 24 Vac/Vdc Supply • Alarm Relay
Introduction
The Barber-Colman Series 7 establishes a new class of microprocessor based tempera-ture controllers. As part of the Series 7 family, the 7SD, 7SM and 7SH offer outstandingperformance features in a cost effective package. Designed specifically for equipmentmanufacturers who demand tight process control, the 7SD, 7SM and 7SH offer a variety ofstandard features commonly found as options on our competitors controllers. NEMA 4Xfaceplates allow these units to be used in applications where washdowns and dust condi-tions exist. The three digit display offers complete coverage for plastics, packaging andenvironmental chamber applications without excess cost for unused digits.
These controllers are light and compact (1/16 DIN size). They perform reliably in the mostdemanding applications.
Even operators without skills in temperature process control or knowledge of PID controlparameters can obtain perfect control. For the best results in control stability, simply:
• wire the instrument• configure the setpoint and alarm thresholds• initiate the autotune function
p
7SD/7SH/7SM Temperature Controllers
1250-DB-100-0-01 45Barber-Colman Company, Loves Park, IL
Con
trol
lers
Ordering Information
1/16 DIN, Three Digit DisplayTemperature Controller
MODEL: 0 7 S - 4 9 - 0 0 - 0 - 0 0Field No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Fields 1 through 4. BASE07SD - Deviation Display See Table Below07SH - Heat/Cool Controller See Table Below07SM - Dual Display Controller See Table Below
Field 5. INPUT4 - TC Types J, K, L, N; Pt 100 RTDNote: All inputs are factory calibrated and selectable
by keyboard. Factory set at Type J.
Field 6. CONTROL ACTION9 - PID and Smart AT
Field 7. OUTPUT 11 - Relay6 - SSR Driver
Field 8. OUTPUT 2Models 07SD and 07SM Only0 - None1 - One AlarmModel 07SH Only1 - Relay (Cooling/Alarm)
Fields 9, 10. POWER SUPPLYModels 07SD and 07SM Only30 - 100 to 240 Vac50 - 24 Vac/VdcModel 07SH Only03 - 100 to 240 Vac05 - 24 Vac/Vdc
Fields 11 through 15. RESERVED
Available Models/Options
Base Model Controller
07SD-49103-000-0-00 PID with autotune, relay output, 100 to 240 Vac07SD-49113-000-0-00 PID with autotune, relay output, alarm, 100 to 240 Vac07SD-49603-000-0-00 PID with autotune, SSR output, 100 to 240 Vac07SD-49613-000-0-00 PID with autotune, SSR output, alarm, 100 to 240 Vac07SD-49115-000-0-00 PID with autotune, relay output, alarm, 24 Vac/Vdc07SD-49615-000-0-00 PID with autotune, SSR output, alarm, 24 Vac/Vdc
Dual Display Controller
07SM-49103-000-0-00 Dual display, PID with autotune, relay output, 100 to 240 Vac07SM-49113-000-0-00 Dual display, PID with autotune, relay output, alarm, 100 to 240 Vac07SM-49603-000-0-00 Dual display, PID with autotune, SSR output, 100 to 240 Vac07SM-49613-000-0-00 Dual display, PID with autotune, SSR output, alarm, 100 to 240 Vac07SM-49115-000-0-00 Dual display, PID with autotune, relay output, alarm, 24 Vac/Vdc07SM-49615-000-0-00 Dual display, PID with autotune, SSR output, alarm, 24 Vac/Vdc
Heat/Cool Controller
07SH-49110-300-0-00 Dual display, PID with autotune, relay/relay output, 100 to 240 Vac07SH-49610-300-0-00 Dual display, PID with autotune, SSR/relay output, 100 to 240 Vac07SH-49110-500-0-00 Dual display, PID with autotune, relay/relay output, 24 Vac/Vdc07SH-49610-500-0-00 Dual display, PID with autotune, SSR/relay output, 24 Vac/Vdc
p
Shaded areas denote commonly stocked items (Standard lead times apply).
7SD/7SH/7SM Temperature Controllers
Con
trol
lers
1250-DB-100-0-0146 Barber-Colman Company, Loves Park, IL
Specifications
General
Case: Polycarbonate in dark grey. Self-extinguishing degree V-0 according to UL-94.Front Protection: Designed and tested for IP65 and NEMA 4X for indoor locations (when panel
gasket is installed).Installation: Panel mounting.Rear Terminal Block: Ten screw terminals with safety rear cover.Dimensions: 48 x 48 mm (1.890 x 1.890 in.) according to DIN 43700; 100 mm (3.937 in.) depth.Cutout: 45 x 45 mm -0 mm, +0.6 mm. (1.772 x 1.772 in. -0 in, +0.024)Weight: 160 grams (6.6 ounces).Power Supply: From 100 to 240 Vac, 50/60 Hz, or 24 Vac/Vdc.Power Supply Variation: -15% to +10% of nominal value.Power Consumption: 5 VA.Insulation Resistance: Less than 100 MΩ (Class III apparatus) according to IEC 348.Isolation Voltage: 1500 Vrms.D/A Conversion: Dual slope integration.Noise Immunity: a) Electrical fast transient/burst requirements:
Severity Level 3 (according to IEC 801-4).b) Electrical discharge requirements: Severity Level 8 (according to IEC 801-2).
Sampling Time: 500 ms typical.Accuracy: ±0.3% full scale value ±1 digit @ 25 °C and nominal power supply value.Temperature Drift: Less than 200 ppm/°C of full scale value selected (RJ excluded).
Less than 400 ppm/°C of full scale value for RTD range -19.9 to 99.99.Reference Junction Drift: 0.1 °C/°C.Common ModeRejection Ratio: 120 dB @ 50/60 Hz.Normal ModeRejection Ratio: 60 dB @ 50/60 Hz.Operating Temperature: 0 to 50 °C.Storage Temperature: -30 to 70 °C.Humidity: From 20% to 85% RH non-condensing.
Control Actions
On/Off, PID or Smart AT AutotuningSpecial Function: Standby alarm sequence.Protection: Internal jumper for calibration and configuration parameter protection.
Inputs (All inputs are factory calibrated and selectable by front keyboard.)
Input: Thermocouples (J, L, K, N) or RTD Pt 100. Input types are keyboard programmable.Engineering Units: °C or °F configurable.Reference Junction: Automatic compensation from 0 to 50 °C.Line Impedance: 100 Ω max for TC input.
Less than 4 Ω per wire for RTD input.Sensor Break: Downscale or upscale programmable. On RTD input, a special test is provided
to signal OVERRANGE when input resistance is less than 15 Ω. (Short circuitsensor detection.)
Calibration: According to IEC 584-1 and DIN 43710-1977.
p
7SD/7SH/7SM Temperature Controllers
1250-DB-100-0-01 47Barber-Colman Company, Loves Park, IL
Con
trol
lers
Outputs
Main Output: a) Relay SPDT, contact rating 3 Amps @ 250 Vac on resistive load.b) Logic output for SSR, 700 Ω maximum load, short circuit protected.Logic Level 1: 14 Vdc ±20% @ 20 mA max 24 Vdc max ±20% @ 1 mALogic Level 0: Less than 0.5 Vdc
Cooling Output (7SH only) a) Relay SPST and contact normally open, contact rating 1 Amp @ 250 Vac on resistive load.b) Logic output for SSR, 700 Ω maximum load, short circuit protected.Logic Level 1: 14 Vdc ±20% @ 20 mA max 24 Vdc max ±20% @ 1 mALogic Level 0: Less than 0.5 Vdc
Alarm
Alarm Functions: Process AlarmDeviation AlarmBand AlarmInstrument Malfunctioning Annunciator
Type of Alarm: - High/Low (Outside/Inside for band alarm)- Direct/Reverse- Standby Sequence/No Standby Sequence
Alarm Hysteresis: 0.1 to 10.0% of input span or 1 least significant digit.Alarm Output: Relay SPST 1 Amp @ 250 Vac resistive load.
7SD Characteristics
Display: 3 digit 7 segment LED display; 10 mm high.Bargraph: 1 green LED + 2 red LEDs for 5 level deviation indication.Indicators: 1 red LED when heating output is ON.
1 red LED when Alarm 1 is ON.1 green LED when Smart AT is enabled.
Specifications (continued)
tupnI segnaR
LCT 008ot0 °C 009ot0 °F 7791-01734NID
JCT 008ot0 °C 999ot0 °F 1-485CEI
KCT 999ot0 °C 999ot0 °F 1-485CEI
NCT 999ot0 °C 999ot0 °F 1-485CEI
001tPDTR 9.99ot9.91- °C 06734NID
001tPDTR 005ot991- °C 999ot991- °F 06734NID
p
7SD/7SH/7SM Temperature Controllers
Con
trol
lers
1250-DB-100-0-0148 Barber-Colman Company, Loves Park, IL
Specifications (continued)
7SM and 7SH Characteristics
Upper Display: 3 digit 7 segment LED display; 10 mm high.Lower Display: 3 digit 7 segment LED display; 7.6 mm high.Indicators: 1 red LED when heating output is ON.
1 red LED when cooling output is ON or alarm is ON.1 green LED when Smart AT is enabled.
Cooling Output (7SH only): a) Relay SPST and contact normal open, contact rating 1 Amp @ 250 Vac on resistive load.b) Logic output for SSR 700 Ω maximum load, short circuit protected.Logic Level 1: 14 Vdc ±20% @ 20 mA max 24 Vdc max ±20% @ 1 mALogic Level 0: Less than 0.5 Vdc
Operator Interface
7SD Front Panel Description
7SM and 7SH Front Panel Description
p
ALMCOOL
OUT
°F
AT
7SH
AT FUNC
Barber-Colman
Lower DisplayShows the setpoint. During configurationprocedure, it shows the parameter code.
Increases the parameter or togglesbetween measured value and setpointindication.
Decreases the selected parameter.
Keyboard DescriptionEnables the self-tuning function (SmartAT) or, during configuration/calibra-tion procedure, scrolls back throughparameters without saving them.
Upper DisplayShows the measured value. During configurationprocedure, it shows the configured setting of theselected parameter.
IndicatorsALM Lit during the ON period of the cooling
cycle (7SH only). Lit when alarm conditionis present.
OUT Lit during the ON period of the heatingcycle.
AT Lit when Smart AT is active.
FUNCStores the parameter into memory andscrolls to the next parameter display.
AT
SVALM
OUT LOW HIGH AT
°F
7SD
AT FUNC
Barber-ColmanKeyboard Description
BargraphShows the deviation between process andsetpoint. Five levels of deviation can be shown.
IndicatorsALM Lit when alarm condition is present.OUT Lit during the ON period of the heating
cycle.AT Lit when Smart AT function is active.SV Flashing when the display shows the
setpoint.
DisplayShows the measured value. During configuration,the display toggles between the selectedparameter and configured value.
Decreases the selected parameter.
Increases the parameter or togglesbetween measured value and setpointindication.
Stores the parameter into memory andscrolls to the next parameter display.
Enables the self-tuning function (SmartAT) or, during configuration/calibra-tion procedure, scrolls back throughparameters without saving them.
FUNC
AT
7SD/7SH/7SM Temperature Controllers
1250-DB-100-0-01 49Barber-Colman Company, Loves Park, IL
Con
trol
lers
Threshold
Soft Start
SV
SV
AlarmDisabled
Alarm
AlarmThreshold
Dead Band
100%
50%
0%
Proportional Band
Output
CoolingOutput(Gain = 0.5)
CoolingOutput(Gain = 1.0)
HeatingOutput
Operator Interface (continued)
Soft StartA configurable threshold can be used to limit output powerduring initial startup. Used when the impedance of heatingloads change with process temperature increases.
Cooling Gain (7SH only)Relative cooling gain can be set from 1.0to 0.2 (1x to 5x the heating proportionalband). Configurable overlap/deadbandallows customization of the 7SH to yourunique process requirements.
Alarm StandbyAlarm Standby is configurable ON/OFF to allowmasking of alarm conditions when process lowalarms are employed and the process value hasnot yet reached the alarm threshold.
p
7SD/7SH/7SM Temperature Controllers
Con
trol
lers
1250-DB-100-0-0150 Barber-Colman Company, Loves Park, IL
Power Line Wiring
NOTE: To avoid electric shock, connect powerline at the end of the wiring procedure.
Rear Terminal Block
1
2
3
-
Shield
+
-
1
2
3
Shield
+
Thermocouple Input Wiring
1 2 3 1 2 3
RTD RTD
9
10
Power Supply
100 to 240 Vac RMS24 Vac/dc
1345
678910
2
MAIN SSRPWR LINE100/240 Vac
or 24 Vac/Vdc
OUT2
NO NCC
TC
RTD
+
+
-
-
MAIN RELAY
NOC
p
Wiring
Input Wiring
NOTE: Do not run input wires together with power cables.For TC wiring use proper compensating cable,preferably shielded. If shielded cable is used, itshould be grounded at one point only.
NOTE: Do not run RTD wires together with power cables. Ifshielded cable is used, it should be grounded at onepoint only. Use copper wires of appropriate size (see"Product Specifications"). The resistance of the 3wires must be the same.
Any external components (like zener diodes, etc.) connectedbetween sensor and input terminals may cause errors inmeasurement due to excessive or unbalanced line resistance,or possible leakage currents.
7SD/7SH/7SM Temperature Controllers
1250-DB-100-0-01 51Barber-Colman Company, Loves Park, IL
Con
trol
lers
Logic voltage for SSR drive (time proportioning).
Logic status 1: 24V +20% @ 1 mA14 V +20% @ 20 mA
Logic status 0: Less than 0.5 V
NOTE: This output is not isolated. Isolation betweeninstrument output and power supply must be assuredby the external solid state relay.
Voltage Outputs for SSR Drive
Solid State Relay
7
8
MainOutput
_
+
_
+
Relay output wiring must be as far away as possible from input or communication cables.
The value of capacitor (C) and resistor (R) are shown in the following table.
SSR Drive Output Wiring
LoadCurrent
< 150 mA< 0.5 Amp< 1 Amp
C(uF)0.1
0.330.47
R(Ω)224747
ResistancePower(W)
222
Resist. andCapac. Voltage
260260260
p
See “Controller Mounting Dimensions” at the end of this section.
Wiring (continued)
C
RLOAD
RC
PowerLine
External Switch in Series with the Internal Contact
Relay Output Wiring
6
7
8
CMainOutput
(heating)
4
5
NO
C
OUT 2(AL1/cooling)
NC
NO
Relay Outputs
The MAIN OUTPUT and OUT 2 relays are internally protectedwith a varistor. The contact rating for the main output is 3Amps/250 Vac on a resistive load. The contact rating for OUT2 is 1 Amp/250 Vac on a resistive load.
Inductive Loads
High voltage transients may occur when switching inductiveloads. These transients may introduce disturbances whichcan affect the performance of the instrument. The internalvaristor assures protection up to 0.5 Amp of inductivecomponent of the load. The same problem may occur whena switch is used in series with the internal contacts. In thiscase, it is recommended to install an additional RC networkacross the external contacts as shown.
Output Wiring