7.short circuit calculations

Upload: kvramanan1

Post on 03-Apr-2018

238 views

Category:

Documents


3 download

TRANSCRIPT

  • 7/28/2019 7.Short Circuit Calculations

    1/14

    7Short-Circuit Calculations

    7.1.0 Introduction7.1.1 Point-to-Point Method, Three-Phase Short-Circuit Calculations, Basic

    Calculation Procedure and Formulas7.1.2 System A and System B Circuit Diagrams for Sample Calculations Using

    Point-to-Point Method7.1.3 Point-to-Point Calculations for System A to FaultsX1

    andX2

    7.1.4 Point-to-Point Calculations for System B to FaultsX1

    andX2

    7.1.5 CValues for Conductors and Busway7.1.6 Shortcut Method 1: AddingZs

    7.1.7 Average Characteristics of 600-V Conductors (Ohms per 100 ft): Two orThree Single Conductors

    7.1.8 Average Characteristics of 600-V Conductors (Ohms per 100 ft): ThreeConductor Cables (and Interlocked Armored Cable)

    7.1.9 LV Busway,R, X, andZ (Ohms per 100 ft)

    7.1.10 Shortcut Method 2: Chart Approximate Method7.1.11 Conductor Conversion (Based on Using Copper Conductor)

    7.1.12 Charts 1 through 13 for Calculating Short-Circuit Currents Using ChartApproximate Method

    7.1.13 Assumptions for Motor Contributions to Fault Currents

    7.1.14 Secondary Short-Circuit Capacity of Typical Power Transformers

    7.1.0 Introduction

    Of the four basic methods used to calculate short-circuit currents, the point-to-pointmethod offers a simple, effective, and quick way to determine available short-circuit

    levels in simple to medium-complexity three-phase and single-phase electrical

    distribution systems with a reasonable degree of accuracy. This method is bestillustrated by the figures and table that follow. Figure 7.1.1 shows the steps and

    equations needed in the point-to-point method. Figure 7.1.2 shows one-line diagramsof two systems (A and B) to be used as illustrative examples. Figures 7.1.3 and 7.1.4

    show the calculations for these two examples. And Table 7.1.5 provides the circuitconstants needed in the equations for the point-to-point method.

    The point-to-point method is followed by two shortcut methods for determining

    short-circuit currents at ends of conductors, specifically, addingZs and the chart

    approximate method. These two methods make use of simplifications that are rea-sonable under most circumstances and almost certainly will yield answers that

    are on the safe side.

    Section

    7.1

  • 7/28/2019 7.Short Circuit Calculations

    2/14

    7.1.1 Point-to-Point Method, Three-PhaseShort-Circuit Calculations, Basic CalculationProcedure and Formulas

    7.2 Section Seven

    7.1.1

  • 7/28/2019 7.Short Circuit Calculations

    3/14

    Short-Circuit Calculations 7.3

    7.1.2 System A and System B Circuit Diagrams forSample Calculations Using Point-to-Point Method

    7.1.2

  • 7/28/2019 7.Short Circuit Calculations

    4/14

    7.1.3 Point-to-Point Calculations forSystem A to Faults X

    1and X

    2

    7.4 Section Seven

    7.1.3

  • 7/28/2019 7.Short Circuit Calculations

    5/14

    7.1.4 Point-to-Point Calculations forSystem B to Faults X

    1and X

    2

    Short-Circuit Calculations 7.5

    7.1.4

  • 7/28/2019 7.Short Circuit Calculations

    6/14

    7.1.5 CValues for Conductors and Busway

    7.6 Section Seven

    TABLE 7.1.5

  • 7/28/2019 7.Short Circuit Calculations

    7/14

    7.1.6 Shortcut Method 1: Adding Zs

    This method uses the approximation of addingZs instead of the accurate methodofRs andXs (in complex form).

    Example

    1. For a 480/277-V system with 30,000 A symmetrical available at the line side of a conductorrun of 100 ft of two 500-kcmil per phase and neutral, the approximate fault current at theload side end of the conductors can be calculated as follows:

    2. 277 V/30,000 A 0.00923 (source impedance).

    3. Conductor ohms for 500-kcmil conductor from Table 7.1.7 in magnetic conduit is 0.00546 per 100 ft. For 100 ft and two conductors per phase, we have

    4. 0.00546/2 0.00273 (conductor impedance).

    5. Add source and conductor impedance, or 0.00923 0.00273 0.01196 total.

    6. Next, 277 V/0.001196 23,160 A rms at load side of conductors.

    For impedance values, refer to Tables 7.1.7, 7.1.8, and 7.1.9.

    7.1.7 Average Characteristics of 600-VConductors (Ohms per 100 ft): Two orThree Single Conductors

    Short-Circuit Calculations 7.7

    TABLE 7.1.7

  • 7/28/2019 7.Short Circuit Calculations

    8/14

    7.1.8 Average Characteristics of 600-V Conductors(Ohms per 100 ft): Three Conductor Cables (andInterlocked Armored Cable)

    7.8 Section Seven

    TABLE 7.1.8

    TABLE 7.1.9

    7.1.9 LV Busway, R, X, and Z(Ohms per 100 ft)

  • 7/28/2019 7.Short Circuit Calculations

    9/14

    7.1.10 Shortcut Method 2: ChartApproximate Method

    The chart method is based on the following:

    Motor Contribution Assumptions

    120/208-V systems 50 percent motor load4 times motor FLA contribution

    240/480-V systems 100 percent motor load

    4 times motor FLA contribution

    Feeder Conductors. The conductor sizes most commonly used for feeders from mold-

    ed-case circuit breakers are shown. For conductor sizes not shown, Table 7.1.11 has

    been included for conversion to equivalent arrangements. In some cases, it may be

    necessary to interpolate for unusual feeder ratings. Table 7.1.11 is based on using cop-

    per conductor.

    Short-Circuit Current Readout. The readout obtained from the charts is the rms sym-

    metrical amperes available at the given distance from the transformer. The circuit

    breaker should have an interrupting capacity at least as large as this value.

    How to Use the Short-Circuit Charts

    Step 1. Obtain the following data:

    I System voltage

    I Transformer kVA rating

    I Transformer impedance

    I Primary source fault energy available in kVA

    Step 2. Select the applicable chart from Figure 7.1.12 (Charts 113). The charts are grouped by

    secondary system voltage, which is listed with each transformer. Within each group, the chart for the

    lowest-kVA transformer is shown first, followed in ascending order to the highest-rated transformer.

    Step 3. Select the family of curves that is closest to the available source kVA. The upper-

    value-line family of curves is for a source of 500,000 kVA. The lower-value-line family of curves is

    for a source of 50,000 kVA. You may interpolate between curves if necessary, but for values above

    100,000 kVA, it is appropriate to use the 500,000-kVA curves.

    Step 4. Select the specific curve for the conductor size being used. If your conductor size is some-

    thing other than the sizes shown on the chart, refer to the conductor conversion table (Table 7.1.11).

    Step 5. Enter the chart along the bottom horizontal scale with the distance (in feet) from the

    transformer to the fault point. Draw a vertical line up the chart to the point where it intersects

    the selected curve. Then draw a horizontal line to the left from this point to the scale along the

    left side of the chart.

    Step 6. The value obtained from the left-hand vertical scale is the fault current (in thousands

    of amperes) available at the fault point.

    Short-Circuit Calculations 7.9

  • 7/28/2019 7.Short Circuit Calculations

    10/14

    7.1.11 Conductor Conversion (Basedon Using Copper Conductor)

    7.10 Section Seven

    TABLE 7.1.11

    7.1.12 Charts 1 through 13 for Calculating

    Short-Circuit Currents Using Chart ApproximateMethod

    7.1.12

    (continued)

  • 7/28/2019 7.Short Circuit Calculations

    11/14

    Short-Circuit Calculations 7.11

    7.1.12

    (continued)

  • 7/28/2019 7.Short Circuit Calculations

    12/14

    7.12 Section Seven

    7.1.12

  • 7/28/2019 7.Short Circuit Calculations

    13/14

    7.1.13 Assumptions for MotorContributions to Fault Currents

    To determine the motor contribution to the first half-cycle fault current when the

    system motor load is known, the following assumptions generally are made:

    Induction motors: Use 4.0 times motor full-load current (impedance value of 25

    percent).Synchronous motors: Use 5.0 times motor full-load current (impedance valueof 20 percent).

    When the motor load is not known, the following assumptions generally are made:

    208Y/120-V systems

    I Assume 50 percent lighting and 50 percent motor load.I Assume motor feedback contribution of 2.0 times full-load current of trans-

    former.

    240-480-600-V three-phase, three-wire systems

    I Assume 100 percent motor load.I Assume motors 25 percent synchronous and 75 percent induction.I Assume motor feedback contribution of 4.0 times full- load current of

    transformer.

    480Y/277-V systems in commercial buildings

    I Assume 50 percent induction motor load.I Assume motor feedback contribution of 2.0 times full- load current of

    transformer or source.I For industrial plants, make same assumptions as for three-phase, three-wire

    systems (above).

    Medium-voltage motors

    I If known, use actual values. Otherwise, use the values indicated in thepreceding for the same type of motor.

    Note on asymmetrical currents. The calculation of asymmetrical currents is a labo-

    rious procedure because the degree of asymmetry is not the same on all three phases.

    It is common practice to calculate the rms symmetrical fault current, with the

    assumption being made that the dc component has decayed to zero, and then apply a

    multiplying factor to obtain the first half-cycle rms asymmetrical current, which is

    called the momentary current. For medium-voltage systems (defined by the IEEE as

    greater than 1000 V up to 69,000 V), the multiplying factor is established by NEMAand ANSI standards depending on the operating speed of the breaker; for low-voltage

    systems, 600 V and below, the multiplying factor is usually 1.17 (based on generally

    accepted use of anX/R ratio of 6.6 representing a source short-circuit power factor of

    15 percent). These values take into account that medium-voltage breakers are rated

    on maximum asymmetry and low-voltage breakers are rated on average asymmetry.

    Short-Circuit Calculations 7.13

  • 7/28/2019 7.Short Circuit Calculations

    14/14

    7.1.14 Secondary Short-Circuit Capacityof Typical Power Transformers

    7.14 Section Seven

    TABLE 7.1.14