8698462 short circuit calculations
TRANSCRIPT
-
8/3/2019 8698462 Short Circuit Calculations
1/72
Copyright Siemens AG 2008. All rights reserved.
Short Circuit Calculation
Sector Energy
D SE PTI NC
Steffen Schmidt
-
8/3/2019 8698462 Short Circuit Calculations
2/72
Page 2 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Standards and Terms
-
8/3/2019 8698462 Short Circuit Calculations
3/72
Page 3 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Purpose of Short-Circuit Calculations
Dimensioning of switching devices
Dynamic dimensioning of switchgear
Thermal rating of electrical devices (e.g. cables)
Protection coordination
Fault diagnostic
Input data for
Earthing studies
Interference calculations EMC planning
..
-
8/3/2019 8698462 Short Circuit Calculations
4/72
Page 4 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Short-Circuit Calculation
Standards
IEC 60909:Short-Circuit Current Calculation in Three-Phase A.C. Systems
European Standard EN 60909 German National Standard DIN VDE 0102 further National Standards
Engineering Recommendation G74 (UK)Procedure to Meet the Requirements of IEC 60909 for theCalculation of Short-Circuit Currents in Three-Phase AC Power
Systems
ANSI IIEEE Std. C37.5 (US)IEEE Guide for Calculation of Fault Currents for Application of a.c.High Voltage Circuit Breakers Rated on a Total Current Basis.
-
8/3/2019 8698462 Short Circuit Calculations
5/72
Page 5 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Short-Circuit Calculations
Standard IEC 60909
IEC 60909 : Short-circuit currents in three-phase a.c. systems
Part 0: Calculation of currentsPart 1: Factors for the calculation of
short-circuit currentsPart 2: Electrical equipment; data for
short-circuit current calculationsPart 3: Currents during two separate
simultaneous line-to-earth shortcircuits and partial short-circuitcurrents flowing through earth
Part 4: Examples for the calculation ofshort-circuit currents
-
8/3/2019 8698462 Short Circuit Calculations
6/72
Page 6 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Short-Circuit Calculations
Scope of IEC 60909
three-phase a.c. systems low voltage and high voltage systems up to 500 kV nominal frequency of 50 Hz and 60 Hz balanced and unbalanced short circuits
three phase short circuits two phase short circuits (with and without earth connection) single phase line-to-earth short circuits in systems with solidly
earthed or impedance earthed neutral two separate simultaneous single-phase line-to-earth short circuits
in a systems with isolated neutral or a resonance earthed neutral(IEC 60909-3) maximum short circuit currents minimum short circuit currents
-
8/3/2019 8698462 Short Circuit Calculations
7/72Page 7 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen SchmidtCopyright Siemens AG 2007. All rights reserved.
Short-Circuit Calculations
Types of Short Circuits
3-phase
2-phase
1-phase
-
8/3/2019 8698462 Short Circuit Calculations
8/72Page 8 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Variation of short circuit current shapes
fault at voltage peak fault at voltagezero crossing
fault located inthe network
fault locatednear generator
-
8/3/2019 8698462 Short Circuit Calculations
9/72Page 9 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Short-Circuit Calculations
Far-from-generator short circuit
Ik Initial symmetrical short-circuit currentip Peak short-circuit currentIk Steady-state short-circuit current
A Initial value of the d.c component
-
8/3/2019 8698462 Short Circuit Calculations
10/72Page 10 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Short-Circuit Calculations
Definitions according IEC 60909 (I)
initial symmetrical short-circuit current Ikr.m.s. value of the a.c. symmetrical component of a prospective(available) short-circuit current, applicable at the instant of short circuit ifthe impedance remains at zero-time value
initial symmetrical short-circuit powerSkfictitious value determined as a product of the initial symmetrical short-circuit current Ik, the nominal system voltage Un and the factor 3:
NOTE: Sk is often used to calculate the internal impedance of a network feeder at the
connection point. In this case the definition given should be used in the following form:
"
kn
"
k IU3S =
"
k
2
n
S
UcZ
=
-
8/3/2019 8698462 Short Circuit Calculations
11/72Page 11 28.06.2008
Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Short-Circuit Calculations
Definitions according IEC 60909 (II)
decaying (aperiodic) component id.c. of short-circuit current
mean value between the top and bottom envelope of a short-circuitcurrent decaying from an initial value to zero
peak short-circuit current ipmaximum possible instantaneous value of the prospective (available)short-circuit current
NOTE: The magnitude of the peak short-circuit current varies in accordance with the
moment at which the short circuit occurs.
-
8/3/2019 8698462 Short Circuit Calculations
12/72Page 12 28.06.2008
Copyright Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Short-Circuit Calculations
Near-to-generator short circuit
Ik Initial symmetrical short-circuit currentip Peak short-circuit currentIk Steady-state short-circuit currentA Initial value of the d.c componentIB Symmetrical short-circuit breaking current
tB
BI22
-
8/3/2019 8698462 Short Circuit Calculations
13/72Page 13 28.06.2008
Copyright Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Short-Circuit Calculations
Definitions according IEC 60909 (III)
steady-state short-circuit current Ikr.m.s. value of the short-circuit current which remains after the decay ofthe transient phenomena
symmetrical short-circuit breaking current Ibr.m.s. value of an integral cycle of the symmetrical a.c. component of theprospective short-circuit current at the instant of contact separation ofthe first pole to open of a switching device
-
8/3/2019 8698462 Short Circuit Calculations
14/72Page 14 28.06.2008
Copyright Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Short-Circuit Calculations
Purpose of Short-Circuit Values
Minimum symmetrical short-circuit current IkSelective detection of partialshort-circuit currents
Protection setting
Maximum initial symmetricalshort-circuit current Ik
Potential rise;
Magnetic fields
Earthing, Interference, EMC
Initial symmetrical short-circuit current Ik
Fault duration
Temperature rise of electrical
devices (e.g. cables)
Thermal stress to equipment
Peak short-circuit currentipForces to electrical devices
(e.g. bus bars, cables)Mechanical stress toequipment
Symmetrical short-circuitbreaking current Ib
Thermal stress to arcing
chamber; arc extinction
Breaking capacity of circuit
breakers
Relevant short-circuit currentPhysical EffectDesign Criterion
-
8/3/2019 8698462 Short Circuit Calculations
15/72Page 15 28.06.2008
Copyright Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Standard IEC 60909
Simplifications and Assumption
Assumptions quasi-static state instead of dynamic calculation
no change in the type of short circuit during fault duration
no change in the network during fault duration
arc resistances are not taken into account impedance of transformers is referred to tap changer in main position
neglecting of all shunt impedances except for C0
-> safe assumptions
-
8/3/2019 8698462 Short Circuit Calculations
16/72Page 16 28.06.2008
Copyright Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Equivalent Voltage Source
-
8/3/2019 8698462 Short Circuit Calculations
17/72
Page 17 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Short-circuit
Equivalent voltage source at the short-circuit location
AQ
Q A ZLZTZN
F
~
I"K3
.n
Uc
real network
equivalent circuit
Operational data and the passive load of consumers are neglectedTap-changer position of transformers is dispensableExcitation of generators is dispensableLoad flow (local and time) is dispensable
-
8/3/2019 8698462 Short Circuit Calculations
18/72
Page 18 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Short circuit in meshed grid
Equivalent voltage source at the short-circuit location
real network equivalent circuit
-
8/3/2019 8698462 Short Circuit Calculations
19/72
Page 19 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Voltage Factor c
c is a safety factorto consider the following effects: voltage variations depending on time and place, changing of transformer taps, neglecting loads and capacitances by calculations, the subtransient behaviour of generators and motors.
1.001.10Medium voltage >1 kV 35 kV
0.950.95
1.051.10
Low voltage 100 V 1000 V
-systems with a tolerance of 6%-systems with a tolerance of 10%
1.001.10High voltage >35 kV
minimum short circuit currentsmaximum short circuit currentsNominal voltage
Voltage factor c for calculation of
-
8/3/2019 8698462 Short Circuit Calculations
20/72
Page 20 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Maximum and minimum Short-Circuit Currents
shall be neglectedshall be consideredMotors
Maximum impedanceMinimum impedanceNetwork feeders
minimum
short circuit currents
maximum
short circuit currents
Minimum contributionMaximum contributionPower plants
CminCmaxVoltage factor
at maximum temperatureat 20CResistance of lines and cables
-
8/3/2019 8698462 Short Circuit Calculations
21/72
Page 21 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Short Circuit Impedances and Correction Factors
-
8/3/2019 8698462 Short Circuit Calculations
22/72
Page 22 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Short Circuit Impedances
For network feeders, transformer, overhead lines, cable etc.
impedance of positive sequence system = impedance of negativesequence system
impedance of zero sequence system usually different
topology can be different for zero sequence system
Correction factors for
generators,
generator blocks, network transformer
factors are valid in zero, positive, negative sequence system
-
8/3/2019 8698462 Short Circuit Calculations
23/72
Page 23 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Network feeders
At a feeder connection point usually one of the following values is given: the initial symmetrical short circuit current Ik the initial short-circuit power Sk
If R/X of the network feeder is unknown, one of the following values canbe used: R/X = 0.1 R/X = 0.0 for high voltage systems >35 kV fed by overhead lines
"k
2n
"k
n
Q S
Uc
I3
Uc
Z
=
=
2
QQ
)X/R(1
ZX
+=
-
8/3/2019 8698462 Short Circuit Calculations
24/72
Page 24 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Network transformer
Correction of Impedance
ZTK = ZT KT
general
at known conditions of operation
no correction for impedances between star point and ground
T
maxTx6,01
c95,0K +=
b
TrT
b
TT
maxbnT sin)II(x1
c
U
UK +=
-
8/3/2019 8698462 Short Circuit Calculations
25/72
Page 25 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Network transformer
Impact of Correction Factor
The Correction factor is KT7.5 %.
Reduction of transformer impedanceIncrease of short-circuit currents
0.80
0.85
0.90
0.95
1.00
1.05
0 5 10 15 20
xT [%]
KT
cmax = 1.10
cmax = 1.05
-
8/3/2019 8698462 Short Circuit Calculations
26/72
Page 26 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Generator with direct Connection to Network
Correction of Impedance
ZGK = ZG KG
general
for continuous operation above rated voltage:
UrG (1+pG) instead of UrG
turbine generator: X(2) = X(1)
salient pole generator: X(2) = 1/2 (Xd"+ Xq")
rGd
max
rG
nG
sinx1c
UUK
+=
-
8/3/2019 8698462 Short Circuit Calculations
27/72
Page 27 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Generator Block (Power Station)
Correction of Impedance
ZS(O) = (tr2 ZG +ZTHV) KS(O)
power station with on-load tap changer:
power station without on-load tap changers:
rGTd
max
2
rTHV
2rTLV
2
rG
2nQS
sinxx1c
UU
UUK
+=
G
Q
( )rGd
maxt
rTHV
rTLV
GrG
nQSO
sinx1
cp1
U
U
)p1(U
UK
+
+=
-
8/3/2019 8698462 Short Circuit Calculations
28/72
Page 28 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Asynchronous Motors
Motors contribute to the short circuit currents and have to be consideredfor calculation of maximum short circuit currents
If R/X is unknown, the following values can be used: R/X = 0.1 medium voltage motors power per pole pair > 1 MW R/X = 0.15 medium voltage motors power per pole pair 1 MW R/X = 0.42 low voltage motors (including connection cables)
rM
2
rM
rMLRM S
U
I/I
1
Z=
2
MM
MM
)X/R(1
ZX
+=
-
8/3/2019 8698462 Short Circuit Calculations
29/72
Page 29 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Special Regulations for low Voltage Motors
low voltage motors can be neglected if IrM Ik groups of motors can be combined to a equivalent motor ILR/IrM = 5 can be used
-
8/3/2019 8698462 Short Circuit Calculations
30/72
Page 30 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Calculation of initial short circuit current
-
8/3/2019 8698462 Short Circuit Calculations
31/72
Page 31 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Calculation of initial short circuit current
Procedure
Set up equivalent circuit in symmetrical components
Consider fault conditions in 3-phase system transformation into symmetrical components
Calculation of fault currents in symmetrical components transformation into 3-phase system
-
8/3/2019 8698462 Short Circuit Calculations
32/72
Page 32 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen SchmidtCopyright Siemens AG 2007. All rights reserved.
Calculation of initial short circuit current
Equivalent circuit in symmetrical components
positive sequence system
negative sequence system
zero sequence system
(1) (1) (1)
(1) (1) (1) (1)
(1)
(2)
(2)
(2)
(2)
(2)
(2) (2)
(2)
(0)(0)
(0)
(0)
(0)
(0)
(0)
(0)
-
8/3/2019 8698462 Short Circuit Calculations
33/72
Page 33 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Calculation of initial short circuit current
3-phase short circuit
L1L2L3
~ -Uf
012-system
UL1 = Uf
UL2 = a2 ( Uf)
UL3 = a ( Uf)
U(1) = Uf
U(2) = 0
U(0) = 0
(1)
rsc3
3 Z
UcI
=
L1-L2-L3-system~ ~Z
(1)l
Z(1)r
~ ~Z(2)l Z(2)r
~ ~Z(0)l Z(0)r
(1)
(2)
(0)
network left offault location
network right offault locationfault location
~ c Un3
~~
-
8/3/2019 8698462 Short Circuit Calculations
34/72
-
8/3/2019 8698462 Short Circuit Calculations
35/72
Page 35 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Calculation of 2-phase initial short circuit current
with ground connection
L1-L2-L3-system 012-system
0L1 =I
3
n2
L2
UcaU =
3
nL3
UcaU =
I(0) = I(1) = I(2)
)0()1(n
)2()1(3
UUU
cUU ==
~ ~
Z(1)l Z(1)r
~ ~
Z(2)l Z(2)r
~ ~
Z(0)l Z(0)r
(1)
(2)
(0)
network left offault location
network right offault location
fault location
c Un
3~
( ) ( )01
r
scE2E 2
3
ZZ
UcI
+
=
L1
L2
L3
~ -Uf
-
8/3/2019 8698462 Short Circuit Calculations
36/72
Page 36 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Calculation of 1-phase initial short circuit current
L1
L2
L3
L1-L2-L3-System 012-System
IL2 = 0
IL3 = 0
3
nL1
UcU =
3
n)2()1()0(
UcUUU =++
I(0) = I(1) = I(2)
~ ~
Z(1)l Z(1)r
~ ~
Z(2)l Z(2)r
~ ~
Z(0)l Z(0)r
(1)
(2)
(0)
network left offault location
network right offault location
fault location
~
c Un
3~ -Uf )0()2()1(
r"
sc1
3
ZZZ
UcI
++
=
-
8/3/2019 8698462 Short Circuit Calculations
37/72
Page 37 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Largest initial short circuit current
Because of Z1 Z2 thelargest short circuit current canbe observed
forZ1 / Z0 < 1
3-phase short circuitforZ1 / Z0 > 1 2-phase short circuit with
earth connection(current in earth connection)
-
8/3/2019 8698462 Short Circuit Calculations
38/72
Page 38 28.06.2008Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Feeding of short circuits
single fed short circuit
multiple fed short circuit
= "sc_part"
sc_part
"
sc III
SkQ
UnQ
"r:1
k3
"
scI
G3~
M3~
IscG IscN IscM
Fault
-
8/3/2019 8698462 Short Circuit Calculations
39/72
Page 39 28.06.2008Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Calculation of short circuit currents by programs (1/3)
Basic equationi = Yu Y: matrix of admittances (for short circuit)
=
n
r
2
1
nnn1
ini1
2n21
1n11
''
sci
.
.
.3
.
.
.
....
..
..
..
....
..
..
..
....
....
0
.
.
.
.
.
.
0
0
U
Uc
U
U
YY
YY
YY
YY
I
-
8/3/2019 8698462 Short Circuit Calculations
40/72
Page 40 28.06.2008Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Calculation of short circuit currents by programs (2/3)
Inversion of matrix of admittancesu = Y-1i
=
0
.
.
.
.
.
.
0
0
....
..
..
..
...
..
..
..
....
....
.
.
.3
.
.
.
''
sci
nnn1
iniii1
2n21
1n11
n
r
2
1
I
ZZ
ZZZ
ZZ
ZZ
U
Uc
U
U
-
8/3/2019 8698462 Short Circuit Calculations
41/72
Page 41 28.06.2008Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Calculation of short circuit currents by programs (3/3)
from line i:
from the remaining lines:
calculation of all node voltages
from there -> calculation of all short circuit currents
3
"
sciiir
IZUc
=
3 ii
r"
sciZ
UcI
=
"
sciscisc IZU =
-
8/3/2019 8698462 Short Circuit Calculations
42/72
Page 42 28.06.2008Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Short Circuit Calculation Results
Faults at all Buses
-
8/3/2019 8698462 Short Circuit Calculations
43/72
Page 43 28.06.2008Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Short Circuit Calculation Results
Contribution for one Fault Location
-
8/3/2019 8698462 Short Circuit Calculations
44/72
Page 44 28.06.2008Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Example
-
8/3/2019 8698462 Short Circuit Calculations
45/72
Page 45 28.06.2008Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Data of sample calculation
Network feeder:
110 kV3 GVAR/X = 0.1
Transformer:
110 / 20 kV40 MVAuk = 15 %
PkrT = 100 kVA
Overhead line:
20 kV10 kmR1 = 0.3 / km
X1 = 0.4 / km
-
8/3/2019 8698462 Short Circuit Calculations
46/72
Page 46 28.06.2008Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Impedance of Network feeder
"
k
2
nI
S
UcZ
=
( )GVA3
kV201.1Z
2
I
=
= 1467.0ZI = 0146.0RI = 1460.0XI
-
8/3/2019 8698462 Short Circuit Calculations
47/72
Page 47 28.06.2008Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Impedance of Transformer
n
2
nkT
S
UuZ =
= 5000.1ZT = 0250.0RT = 4998.1XT
( )
MVA40
kV2015.0Z
2
T =
2n
2n
krTT S
UPR =
( )
( )2
2
TMVA40
kV20kVA100R =
-
8/3/2019 8698462 Short Circuit Calculations
48/72
Page 48 28.06.2008Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Impedance of Transformer
Correction Factor
T
max
Tx6.01
c
95.0K +=
14998.06.01
1.195.0KT
+=
95873.0KT =
= 4381.1ZTK = 0240.0RTK = 4379.1XTK
-
8/3/2019 8698462 Short Circuit Calculations
49/72
Page 49 28.06.2008Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Impedance of Overhead Line
= 'RRL
= 0000.3RL = 0000.4XI
km10km/3.0RL =
= 'XXL
km10km/4.0XL =
-
8/3/2019 8698462 Short Circuit Calculations
50/72
Page 50 28.06.2008Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Initial Short-Circuit Current Fault location 1
TKI RRR += TKI XXX +=
+= 0240.00146.0R += 4379.11460.0X
= 0386.0R = 5839.1X
( )11
n"
kXjR3
UcI
+
=
( ) ( )22"
k
5839.10386.03
kV201.1I+
=
kA0.8I"k =
-
8/3/2019 8698462 Short Circuit Calculations
51/72
Page 51 28.06.2008Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Initial Short-Circuit Current Fault location 2
LTKI RRRR ++= LTKI XXXX ++=
++= 0000.30240.00146.0R ++= 0000.44379.11460.0X
= 0386.3R = 5839.5X
( )11
n"
kXjR3
UcI
+
=
( ) ( )22"
k
5839.50386.33
kV201.1I+
=
kA0.2I"k =
-
8/3/2019 8698462 Short Circuit Calculations
52/72
Page 52 28.06.2008Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Calculation of Peak Current
-
8/3/2019 8698462 Short Circuit Calculations
53/72
Page 53 28.06.2008Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Peak Short-Circuit Current
Calculation acc. IEC 60909
maximum possible instantaneous value of expected short circuit current
equation for calculation: "kp I2i =
X/R3e98.002.1 +=
-
8/3/2019 8698462 Short Circuit Calculations
54/72
Page 54 28.06.2008Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Peak Short-Circuit Current
Calculation in non-meshed Networks
The peak short-circuit current ip at a short-circuit location, fed fromsources which are not meshed with one another is the sum of the partialshort-circuit currents:
M
G
M
ip1 ip2 ip3 ip4
ip = ip1 + ip2 + ip3 + ip4
-
8/3/2019 8698462 Short Circuit Calculations
55/72
Page 55 28.06.2008Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Peak Short-Circuit Current
Calculation in meshed Networks
Method A: uniform ratio R/X smallest value of all network branches quite inexact
Method B: ratio R/Xat the fault location
factorb from relation R/Xat the fault location (equation or diagram) =1,15 b
Method C: procedure with substitute frequency factor from relation R
c/X
cwith substitute frequency fc = 20 Hz
best results for meshed networks
ff
XR
XR c
c
c =
-
8/3/2019 8698462 Short Circuit Calculations
56/72
Page 56 28.06.2008Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Peak Short-Circuit Current
Fictitious Resistance of Generator
RGf = 0,05 Xd" for generators with UrG > 1 kV and SrG 100 MVA
RGf = 0,07 Xd" for generators with UrG > 1 kV and SrG < 100 MVA
RGf = 0,15 Xd" for generators with UrG 1000 V
NOTE: Only for calculation ofpeak short circuit current
-
8/3/2019 8698462 Short Circuit Calculations
57/72
Page 57 28.06.2008Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Peak Short-Circuit Current Fault location 1
= 0386.0R = 5839.1X
kA0.8I"k =
0244.0X/R =
"kp I2i =
X/R3e98.002.1 +=
93.1=
kA8.21ip =
-
8/3/2019 8698462 Short Circuit Calculations
58/72
Page 58 28.06.2008 Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Peak Short-Circuit Current Fault location 2
= 0386.3R = 5839.5X
kA0.2I"k =
5442.0X/R =
"kp I2i =
X/R3e98.002.1 +=
21.1=
kA4.3ip =
-
8/3/2019 8698462 Short Circuit Calculations
59/72
-
8/3/2019 8698462 Short Circuit Calculations
60/72
Page 60 28.06.2008 Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Breaking Current
Differentiation
Differentiation between short circuits near or far from generator
Definition short circuit near to generator
for at least one synchronous machine is: Ik > 2 Ir,Generatoror Ikwith motor > 1.05 Ikwithout motor
Breaking current Ib for short circuit far from generator
Ib = Ik
-
8/3/2019 8698462 Short Circuit Calculations
61/72
Page 61 28.06.2008 Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Breaking Current
Calculation in non-meshed Networks
The breaking current IB at a short-circuit location, fed from sources whichare not meshed is the sum of the partial short-circuit currents:
M
G
M
IB1 = Ik
IB = IB1 + IB2 + IB3 + IB4
IB2 = Ik IB3 = qIk IB4 = qIk
-
8/3/2019 8698462 Short Circuit Calculations
62/72
Page 62 28.06.2008 Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Breaking current
Decay of Current fed from Generators
IB
= Ik
Factor to consider the decay of short circuit current fed fromgenerators.
-
8/3/2019 8698462 Short Circuit Calculations
63/72
Page 63 28.06.2008 Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Breaking current
Decay of Current fed from Asynchronous Motors
IB
= q Ik
Factor q to consider the decay of short circuit current fed fromasynchronous motors.
C
-
8/3/2019 8698462 Short Circuit Calculations
64/72
Page 64 28.06.2008 Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Breaking Current
Calculation in meshed Networks
Simplified calculation:
Ib = Ik
For increased accuracy can be used:
XdiK subtransient reactance of the synchronous machine (i)XMj reactance of the asynchronous motors (j)IkGi , IkMj contribution to initial symmetrical short-circuit current from the synchronous machines (i)
and the asynchronous motors (j) as measured at the machine terminals
"
kMjjjj n
Mj"
kGiii n
Gi"
kb I)q1(3/Uc
"UI)1(
3/Uc
"UII
=
"
kGi"
diK
"
Gi IjXU ="
kMj"
Mj
"
Mj IjXU =
C ti h t i it t
-
8/3/2019 8698462 Short Circuit Calculations
65/72
Page 65 28.06.2008 Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Continuous short circuit current
Continuous short circuit current Ik
r.m.s. value of short circuit current after decay of all transienteffects
depending on type and excitation of generators statement in standard only for single fed short circuit calculation by factors (similar to breaking current)
Continuous short circuit current is normally not calculated bynetwork calculation programs.
For short circuits far from generator and as worst case estimation
Ik = Ik
-
8/3/2019 8698462 Short Circuit Calculations
66/72
Page 66 28.06.2008 Copyright
Siemens AG 2008. All rights reserved.E D SE PTI NCSteffen Schmidt
Short-circuit with preload
Sh t i it ith l d
-
8/3/2019 8698462 Short Circuit Calculations
67/72
Page 67 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Short-circuit with preload
Principle
A Load flow calculation that considers all network parameters,such as loads, tap positions, etc.
B Place voltage source with the voltage that was determined by
the load flow calculation at the fault location.
C Superposition of A and B
Sh t i it ith l d
-
8/3/2019 8698462 Short Circuit Calculations
68/72
Page 68 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Short-circuit with preload
Example
A Load flow calculation
B Short circuit calculation
Sh t i it ith l d
-
8/3/2019 8698462 Short Circuit Calculations
69/72
Page 69 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Short-circuit with preload
Results
720V336V592.11V
1000V
192.0A168A197.37A203.95A
Short-circuit with preload
~ ~
365.37A
720V
-0V
720V700V
-364V
336V
900. V
-307.89V
592.11V
1000V
-0V
1000V
10A
182A
192A
40A
208A
168A
40. A
157.37A
197.37A
50. A
153.95A
203.95A
Superposition: Load flow + feed back
~ ~
365.37A
24A6.58A
720V1000V
40A40A50A
Load flow
~ ~
50A10A
2 3 2 10A 2
14780V900V
90700V
0V0V208.0A
365.3A153.95A
Short-circuit: feed back
26A3.42A
182A
780V307.89V 364V
157.37A
-
8/3/2019 8698462 Short Circuit Calculations
70/72
Page 70 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Break time!
Copyright Siemens AG 2008. All rights reserved.
-
8/3/2019 8698462 Short Circuit Calculations
71/72
Page 71 28.06.2008Copyright Siemens AG 2008. All rights reserved.
E D SE PTI NCSteffen Schmidt
Contact
Steffen SchmidtSenior ConsultantSiemens AG, Energy SectorE D SE PTI NC
Freyeslebenstr. 191058 Erlangen
Phone: +49 9131 - 7 32764Fax: +49 9131 - 7 32525
E-mail: [email protected]
mailto:[email protected]:[email protected] -
8/3/2019 8698462 Short Circuit Calculations
72/72
Thank you for your attention!