    SIPROTEC

    Multi-Functional ProtectivRelays7SJ61...7SJ64

    Overcurrent Protection7SJ80

    Motor Protection7SK80

    IEC 61850

    PIXIT

    Preface, Table of Contents

    Applications 1

    Basics 2

    Mapping 3

    Literature, Index

  • 7/31/2019 7SJ61 64 Ingles

    2/178

    Siemens Aktiengesellschaft Order No.: C53000-G1140-C211-4

    Disclaimer of LiabilityWe have checked the text of this manual against the hardware andsoftware described. However, deviations from the description can-not be completely ruled out, so that no liability can be accepted forany errors or omissions contained in the information given.The information given in this document is reviewed regularly andany necessary corrections will be included in subsequent editions.We appreciate any suggestions for improvement.We reserve the right to make technical improvements without no-tice.

    Document Release V04.20.00Edition 03.2010

    CopyrightCopyright Siemens AG 2010Dissemination or reproduction of this document, or evaluation andcommunication of its contents, is not authorized except where ex-pressly permitted. Violations are liable for damages. All rights re-served, particularly for the purposes of patent application ortrademark registration.Registered TrademarksSIPROTEC, SINAUT, SICAM and DIGSI are registered trademarksof Siemens AG. Other designations in this manual might be trade-marks whose use by third parties for their own purposes would in-fringe the rights of the owner.

  • 7/31/2019 7SJ61 64 Ingles

    3/178

    3SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    Preface

    Purpose of this manual

    In this Manual, you will find the

    Specification of the applications of the IEC 61850 interface

    General information about the effects of configuration of your device to the different LogicalNodes and DOIs

    Mapping of device relevant information to Logical Nodes as part of protocol IEC61850

    Target audience

    This manual is intended mainly for all persons who configure, parameterize and operate aSIPROTEC Devices 7SJ61, 7SJ62, 7SJ63, 7SJ64, 7SJ80, 7SK80.

    Scope of validity of this Manual

    SIPROTEC 7SJ61, 7SJ62 and 7SJ64, Versions 4.7, 4.8

    SIPROTEC 7SJ63, Version 4.66

    SIPROTEC 7SJ80, Version 4.6

    SIPROTEC 7SK80, Version 4.6

    Standards

    This document has been created according to the ISO 9001 quality standards.

    Further Support

    If you have questions about SIPROTEC IEC 61850 interface, please contact your Siemens salesrepresentative.

  • 7/31/2019 7SJ61 64 Ingles

    4/178

    4 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

  • 7/31/2019 7SJ61 64 Ingles

    5/178

    5SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    Table of contents

    1 Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    1.2 Association model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    1.3 Server model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    1.4 Data set model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    1.5 Substitution model. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    1.6 Setting group control model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    1.7 Reporting model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    1.7.1 Unbuffered Report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    1.7.2 Buffered Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    1.8 Logging model. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    1.9 Generic substation model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    1.10 Transmission of sample values model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    1.11 Control model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    1.12 Time and time synchronisation model. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

    1.13 File transfer model. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

    1.14 General items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

    1.15 TISSUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

    2 Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

    2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

    2.2 Effects of Configuration on the Logical Nodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

    2.2.1 Function parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

    2.2.2 Function parameters SIPROTEC 7SJ61 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

    2.2.3 Function parameters SIPROTEC 7SJ62/63/64 . . . . . . . . . . . . . . . . . . . . . . . . . 382.2.4 Function parameters SIPROTEC 7SJ80 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

    2.2.5 Function parameters SIPROTEC 7SK80. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

    2.3 Allocation of Logical Nodes to Logical Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

    2.4 Logical Node LLN0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

    2.4.1 Logical Device PROT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

    2.4.2 Logical Devices MEAS, DR and EXT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

    2.4.3 Logical Device CTRL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

    2.5 DOI Behavior. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

    2.5.1 Logical Device PROT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

    2.5.2 Logical Devices MEAS, CTRL, DR and EXT. . . . . . . . . . . . . . . . . . . . . . . . . . . 59

  • 7/31/2019 7SJ61 64 Ingles

    6/178

    Table of contents

    6 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    3 Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

    3.1 Device (LPHD1, CALH1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

    3.1.1 Error with a summary alarm and Alarm summary event. . . . . . . . . . . . . . . . . . . 63

    3.2 Oscillographic Fault Records (RDRE1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

    3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2) . . . . . . . . . . . . . . . . . . 68

    3.3.1 Overcurrent Protection 50, 51 PH (PTOC6, PTOC7, PTOC1, PTOC18) . . . . . . 68

    3.3.2 Overcurrent Protection 50N, 51N (PTOC8, PTOC9, PTOC2) . . . . . . . . . . . . . . 74

    3.3.3 Overcurrent Protection 50N, 51N (PTRC2). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

    3.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3). . . . . . . . . . . . . . . . . 81

    3.4.1 Directional Overcurrent Protection 67 (PTOC10, PTOC11, PTOC3) . . . . . . . . . 81

    3.4.2 Directional Overcurrent Protection 67N (PTOC12, PTOC13, PTOC4). . . . . . . . 85

    3.4.3 Directional Overcurrent Protection 67N (PTRC3) . . . . . . . . . . . . . . . . . . . . . . . . 89

    3.5 Single-Phase Overcurrent Protection (PTOC16, PTOC17) . . . . . . . . . . . . . . . . . . . 93

    3.6 Voltage Protection 27, 59 (PTUVx, PTOVx). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96

    3.6.1 Undervoltage Protection 27 (PTUV1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96

    3.6.2 Undervoltage Protection 27 (PTUV2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98

    3.6.3 Overvoltage Protection 59 (PTOV1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100

    3.6.4 Overvoltage Protection 59 (PTOV2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102

    3.7 Negative Sequence Protection 46 (PTOC14, PTOC15, PTOC5). . . . . . . . . . . . . . . 104

    3.8 Motor Protection (PMSS1, PMRI1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108

    3.8.1 Motor Starting Protection 48 (PMSS1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108

    3.8.2 Motor Restart Inhibit 66 (PMRI1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110

    3.9 Load Jam Protection (PMLJ1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111

    3.10 Frequency protection 81 O/U (PTUFx, PTOFx). . . . . . . . . . . . . . . . . . . . . . . . . . . . 113

    3.10.1 Frequency protection 81-1 U (PTUF1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1133.10.2 Frequency protection 81-2 U (PTUF2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115

    3.10.3 Frequency protection 81-3 U (PTUF3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117

    3.10.4 Frequency protection 81-4 U (PTUF4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119

    3.10.5 Frequency protection 81-1 O (PTOF1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121

    3.10.6 Frequency protection 81-2 O (PTOF2). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123

    3.10.7 Frequency protection 81-3 O (PTOF3). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125

    3.10.8 Frequency protection 81-4 O (PTOF4). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127

    3.11 Thermal overload protection (PTTR1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129

    3.12 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx) . . . . . . . . . . . . . . . . . 131

    3.12.1 Ground Fault Protection 64 (PHIZ1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131

    3.12.2 Ground Fault Protection 50N(s) (PSDE1, PSDE2) . . . . . . . . . . . . . . . . . . . . . . . 1353.12.3 51 N(s) (PSDE3). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138

    3.13 Automatic Reclosing System 79 (RREC1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140

    3.14 Fault Locator (RFLO1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142

    3.15 Circuit breaker failure protection 50BF(RBRF1). . . . . . . . . . . . . . . . . . . . . . . . . . . . 144

    3.16 Synchronism and Voltage Check 25 (RSYNx) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146

    3.17 Three-pole tripping 52 Breaker (XCBR1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158

    3.18 Tripping Logic of the Entire Device (PTRC1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162

  • 7/31/2019 7SJ61 64 Ingles

    7/178

    Table of contents

    7SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    3.19 Measurement (MMXU1, MSQI1, MMTR1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164

    3.19.1 Measures (MMXU1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164

    3.19.2 Measured values, symmetrical components (MSQI1) . . . . . . . . . . . . . . . . . . . . 169

    3.19.3 Power Metering (MMTR1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171

    Literature

    Index

  • 7/31/2019 7SJ61 64 Ingles

    8/178

    Table of contents

    8 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

  • 7/31/2019 7SJ61 64 Ingles

    9/178

    9SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    Applications 1

    Contents

    This chapter specifies the protocol implementation extra information for testing (PIXIT) of theIEC 61850 interface in SIPROTEC 7SJ6, 7SJ80, 7SK80.

    1.1 General 10

    1.2 Association model 11

    1.3 Server model 12

    1.4 Data set model 13

    1.5 Substitution model 14

    1.6 Setting group control model 15

    1.7 Reporting model 16

    1.8 Logging model 19

    1.9 Generic substation model 20

    1.10 Transmission of sample values model 22

    1.11 Control model 23

    1.12 Time and time synchronisation model 25

    1.13 File transfer model 26

    1.14 General items 27

    1.15 TISSUES 28

  • 7/31/2019 7SJ61 64 Ingles

    10/178

    Applications

    1.1 General

    10 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    1.1 General

    This chapter specifies the protocol implementation extra information for testing (PIXIT) of the

    IEC 61850 interface in SIPROTEC 7SJ6, 7SJ80, 7SK80.

    It is based on the service subset definition given in the protocol implementation conformancestatement (PICS), which is specified within the user manual SIPROTEC 4 Ethernet ModuleEN 100 IEC 61850 Electrical Interface 100 MBit, Manual /1/.

    The following applicable ACSI service models are specified:

    Association model

    Server model

    Data set model

    Substitution model

    Setting group control model

    Reporting model

    Logging model

    Generic substitution model

    Transmission of sample values model

    Control model

    Time and time synchronisation model

    File transfer model

    General items

    Together with the PICS and the MICS the PIXIT forms the basis for a conformance testaccording to IEC 61850-10.

    The mapping between the IEC 61850 server data model and the SIPROTEC specific data isspecified in Chapter 3.

  • 7/31/2019 7SJ61 64 Ingles

    11/178

    Applications

    1.2 Association model

    11SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    1.2 Association model

    Description Value / Clarification

    Maximum number of clients that can set-upan association simultaneously

    5 with IEC 61850 Protocol Update

    Version EN100 V04.02 and lower

    6 with IEC 61850 Protocol UpdateVersion EN100 V04.03 and higher

    Lost connection detection time range(default range of TCP_KEEPALIVE is 1 20 seconds)

    10 seconds

    Is authentication supported N

    What called association parameters arenecessary for successful association ?

    Transport selector YSession selector YPresentation selector Y

    AP Title ANYAE Qualifier ANY

    WhereY means: as defined within the ICD-File

    ANY means: any value accepted

    What is the maximum and minimum MMSPDU size ?

    Max MMS PDU size 32768Min MMS PDU size

    What is the typical startup time after a

    power supply interrupt ?

    15 SECONDS

  • 7/31/2019 7SJ61 64 Ingles

    12/178

    Applications

    1.3 Server model

    12 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    1.3 Server model

    Description Value / Clarification

    Which analogue value (MX) quality bits aresupported (can be set by server) ?

    Validity:Y Good,Y Invalid,N Reserved,Y QuestionableY OverflowY OutofRangeN BadReferenceN OscillatoryY FailureY OldDataN InconsistentY Inaccurate

    Source:Y ProcessN SubstitutedY TestY OperatorBlocked

    Which status value (ST) quality bits aresupported (can be set by server) ?

    Validity:Y Good,Y Invalid,N Reserved,Y Questionable

    N BadReferenceY OscillatoryY FailureY OldDataN InconsistentN Inaccurate

    Source:Y ProcessY SubstitutedY TestY OperatorBlocked

    What is the maximum number of data

    values in one GetDataValues request ?

    Not restricted; depends on the max. MMS PDU size given

    above.

    What is the maximum number of datavalues in one SetDataValues request ?

    Not restricted; depends on the max. MMS PDU size givenabove. No Data Attribute within our object directory iswritable with the service SetDataValues.

  • 7/31/2019 7SJ61 64 Ingles

    13/178

    Applications

    1.4 Data set model

    13SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    1.4 Data set model

    Description Value / Clarification

    Maximum number of data elements in onedata set

    Not limited by an internal configuration parameter. Itdepends on the available memory.

    How many persistent data sets can becreated by one or more clients ?

    64 data sets for each LD. It depends on the availablememory.

    How many non-persistent data sets can becreated by one or more clients ?

    10 data sets. It depends on the available memory.

    additional items:

    Maximum number of data sets Could not be defined, it depends on the available memoryspace. In principle, this information it not necessary fromtype conformance testing standpoint.

  • 7/31/2019 7SJ61 64 Ingles

    14/178

    Applications

    1.5 Substitution model

    14 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    1.5 Substitution model

    This service will not be supported (see also SIPROTEC 4 Ethernet Module EN 100 IEC 61850Electrical Interface 100 MBit, Manual /1/).

  • 7/31/2019 7SJ61 64 Ingles

    15/178

    Applications

    1.6 Setting group control model

    15SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    1.6 Setting group control model

    Description Value / Clarification

    What is the number of supported settinggroups for each logical device ?

    Setting groups available for LLN0 only in LD PROT. Thenumber of supported setting groups is 1 or 4, it dependson the given configuration. Specified in the ICD-File.

    What is the effect of when and how thenon-volatile storage is updated ?(compare IEC 61850-8-1 $16.2.4)

    Just SelectActiveSG service will supported according toPICS.

  • 7/31/2019 7SJ61 64 Ingles

    16/178

    Applications

    1.7 Reporting model

    16 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    1.7 Reporting model

    1.7.1 Unbuffered Report

    Description Value / Clarification

    The supported trigger conditions are Y IntegrityY Data changeY Quality changeY Data updateY General Interrogation

    The supported optional fields are Y Sequence-number Y Report-time-stampY Reason-for-inclusion

    Y Data-set-nameY Data-referenceN Buffer-overflowN EntryIDY Conf-revY Segmentation

    Can the server send segmented reports ? Y

    Mechanism on second internal datachange notification of the same analoguedata value within buffer period(Compare IEC 61850-7-2 $14.2.2.9)

    Send report immediately

    Multi client URCB approach(Compare IEC 61850-7-2 $14.2.1) All clients can access all URCBs

    additional items:

    Interrupt of general interrogation Running GI could not be interrupted. If a new GI requestoccurs during a running GI, the current GI will be finishedfirst before the second GI request will be processed.

    Integrity period Configurable >=1 second;

    Dynamic URCB reservation after an abortof the client/server association

    Reservation of the URCB is lost. After a re-establishmentof the association the URCB reservation has to be doneby the client before. This behavior is implemented toavoid unnecessary memory residuals if temporarily client

    associations (e.g. for maintenance) are established.

    Configured URCB reservation after anabort of the client/server association

    Reservation of the URCB is not lost.

  • 7/31/2019 7SJ61 64 Ingles

    17/178

    Applications

    1.7 Reporting model

    17SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    1.7.2 Buffered Report

    Description Value / Clarification

    The supported trigger conditions are Y IntegrityY Data changeY Quality changeY Data updateY General Interrogation

    The supported optional fields are Y Sequence-number Y Report-time-stampY Reason-for-inclusionY Data-set-nameY Data-referenceY Buffer-overflowY EntryID

    Y Conf-revY Segmentation

    Can the server send segmented reports ? Y

    Mechanism on second internal datachange notification of the same analoguedata value within buffer period(Compare IEC 61850-7-2 $14.2.2.9)

    Buffer the EntrySend report if the report is enabled

    Multi client BRCB approach(Compare IEC 61850-7-2 $14.2.1)

    All clients can access all BRCBs

    What is the format of EntryID ? First 2 Byte : Integer Last 6 Bytes: BTime6 time stamp

    What is the buffer size for each BRCB orhow many reports can be buffered ?

    About 1 MB are available for the buffering.Each BRCB has an extension attribute Memory thatdisplay the percentage of those 1 MB that have beenreserved/forseen for its own entries.Default amount 1 MB/(2*Number of logical devices)

    additional items:

    Interrupt of general interrogation Running GI could not be interrupted. If a new GI requestoccurs during a running GI, the current GI will be finishedfirst before the second GI request will be processed.

    Integrity period Configurable >=1 second;

    Dynamic BRCB reservation after an abortof the client/server association

    Reservation of the BRCB has been fixed with TISSUE453.The value of the attribute ResvTms delivers the timeinterval during which the reservation is still active after theconnection has been lost. In case a BRCB is stillreserved, and a client connects with the same IP addressas the one used during the reservation, then the BRCBattribute can be written by this client without prior settingthe ResvTms attribute as long as the reservation timerhas not expired.

  • 7/31/2019 7SJ61 64 Ingles

    18/178

    Applications

    1.7 Reporting model

    18 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    Configured BRCB reservation after anabort of the client/server association

    Reservation of the BRCB is not lost for BRCBs that havebeen pre-associated to a specific client (pre-associationdefined with means of the CLientLN element with theBRCB instantiation in the SCD file).Reservation of a BRCB is lost for BRCBs, that have notbeen pre-associated to a specific client, after theexpiration of the reservation timer set with the ResvTmsattribute. In case ResvTms is not set (backwardcompatibility), ResvTms will get a default value for allpreconfigured BRCBs that are not pre-associated to aspecific client.

    Optional use of a flow control fortransmitting history of a BRCB

    As specified in the IEC61850-7-2, transmission of entriesmay required some times, depending of the amount ofentries that have to be transmitted.Therefore, the SIPROTEC has an optional flow controlfeature to accelerate the transmission of the entries: eachBRCB has an extended attribute MaxOutReports that can

    be set from the associated-client to change thetransmmision strategy of the entries. The number orderedwill then be transmitted as long as they exist in the buffer;the server then reset the attribute to 0 and wait for theclient to set it again in order to continue the historytransmission with MaxOutReports entries. The attributeonly influences the flow control of entries while dealingwith the history, and not after the history transmission hascompleted.

  • 7/31/2019 7SJ61 64 Ingles

    19/178

    Applications

    1.8 Logging model

    19SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    1.8 Logging model

    This service will not be supported (see also SIPROTEC 4 Ethernet Module EN 100 IEC 61850

    Electrical Interface 100 MBit, Manual /1/).

  • 7/31/2019 7SJ61 64 Ingles

    20/178

    Applications

    1.9 Generic substation model

    20 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    1.9 Generic substation model

    Description Value / Clarification

    What is the behavior when one subscribedGOOSE message isnt received orsyntactically incorrect ?

    The telegram will be discarded (i.e not forwarded to theapplication) since it is corrupt or syntactically incorrectand therefore not readable. The data objects will bedeclared as invalid after a timeout detection since notelegram have been received by the application.

    What is the behavior when a subscribedGOOSE message is out-of-order ?

    Error message will be stored into the error buffer (couldbe accessed by EN100 web-server).

    All expected data objects will be declared as invalid.

    What is the behavior when a subscribedGOOSE message is duplicated ?

    The sequence number given in the GOOSE-message isout-of-order. Error message will be stored into the error

    buffer (could be accessed by EN100 web-server).All expected data objects will be declared as invalid.

    additional items:

    Maximum number of GOOSE messageswhich could be sent

  • 7/31/2019 7SJ61 64 Ingles

    21/178

    Applications

    1.9 Generic substation model

    21SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    What is the behavior when there is an out-of-order entry in the allData?

    The confRev attribute in the header guarantees that theallData entries are in the correct order. Therefore, itsnecessary to check the confRev attribute. There is nochance to detect such an out-of-order.

    What is the behavior when no telegram isreceived within a TAL timeout?

    To avoid an incorrect timeout detection, the subscriberdetects a timeout after a period of 2TAL.The information is then declared as questionable,oldData.

    What is the behavior when a GOOSEheader parameter goCBRef is mismatchingwith the expected one?

    Since the goCBRef shall be unique stationwide, thereceived telegram with the mismatched goCBRef will bediscarted: it has not been published. In that case only thetimeout detection will set the data to invalid.

    What is the behavior when a GOOSEheader parameter APPID is mismatchingwith the expected one?

    The APPID is a link layer parameter. It is used as a filteron link layer. If the APPID is mismatching, the tellegramwill therefore be discarded on link layer without notifyingthe application. Only the timeout detection will set the

    data to invalid.

    What is the behavior when a GOOSEheader parameter t is not increasing?

    The t parameter is not checked. Therefore it doesn't leadto any error detection.

    What is the behavior whennumDatSetEntries and number of allDataare inconsistent?

    The telegram is discarded since it is corrupt (not wellformed). After the timeout detection (no telegramforwarded to the application) the data objects aredeclared invalid.

  • 7/31/2019 7SJ61 64 Ingles

    22/178

    Applications

    1.10 Transmission of sample values model

    22 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    1.10 Transmission of sample values model

    Compare the Implementation Guidelines for Electrical Current and Voltage Transducers

    according to IEC 60044-7/8 with Digital Output according to IEC 61850-9-2; Version 1.0; asspecified by ABB, Areva, Landis+Gyr, OMICRON and SIEMENS

    This service will not be supported (see also SIPROTEC 4 Ethernet Module EN 100 IEC 61850Electrical Interface 100 MBit, Manual /1/).

  • 7/31/2019 7SJ61 64 Ingles

    23/178

    Applications

    1.11 Control model

    23SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    1.11 Control model

    Description Value / Clarification

    What control models are supported ? Y Status-onlyY Direct-with-normal-securityN Sbo-with-normal-securityY Direct-with-enhanced-securityY Sbo-with-enhanced-security

    Is Time activated operate (operTm)supported

    N

    What is the behavior when the test attributeis set in the SelectWithValue and/orOperate request ?

    Will be acknowledged with negative response. TheAddCause attribute will be set to not supported

    What are the conditions for the time (T)attribute in the SelectWithValue and/orOperate request ?

    Time attribute is not relevant.

    Is operate-many supported ? N

    Is pulse configuration supported ? N

    What check conditions are supported ? Y SynchrocheckY Interlock-check

    What service error types are supported ? Y Instance-not-availableY Instance-in-useY Access-violation

    Y Access-not-allowed-in-current-stateY Parameter-value-inappropriate

    Y Parameter-value-inconsistentY Class-not-supportedY Instance-locked-by-other-client

    Y Control-must-be-selectedY Type-conflictY Failed-due-to-communicationsY Constraint failed-due-to-server-constraint

  • 7/31/2019 7SJ61 64 Ingles

    24/178

    Applications

    1.11 Control model

    24 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    What additional cause diagnosis aresupported ?

    N Blocked-by-switching-hierarchy

    Y Select-failedY Invalid-positionY Position-reached

    Y Parameter-change-in-executionY Step-limit

    Y Blocked-by-ModeY Blocked-by-processY Blocked-by-interlocking

    Y Blocked-by-synchrocheckY Command-already-in-executionN Blocked-by-health

    Y 1-of-n-controlY Abortion-by-cancelY Time-limit-over

    N Abortion-by-tripY Object-not-selected

    additional items:

    What additional cause diagnosisextensions are supported ?

    Y Plausibility_error

    Y Parameter_setting_invalidY Hardware_errorY System_overload

    Y Internal_faultY Command_sequence_error

    Changing the control services byconfiguration

    N

    Inconsistency between Select and (Oper orcancel)

    Oper or cancel will be acknowledged with negativeresponse if inconsistencies to the select request aredetected.The following attributes will not be checked in this case:T (Time)

    Cancel request could be sent after anoperate request.

    Y

    Format of the control time stamp attribute ? TimeStamp instead of EntryTimeacc. to the 7-2 Errata List.

    Negative response for select request couldbe performed only

    If test mode is activated orIf the selection is always done.

  • 7/31/2019 7SJ61 64 Ingles

    25/178

    Applications

    1.12 Time and time synchronisation model

    25SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    1.12 Time and time synchronisation model

    Description Value / Clarification

    What kind of quality bits are supported ? N LeapSecondsKnownY ClockFailureY ClockNotSynchronized

    What kind of quality accuracy bits aresupported ?

    Y InvalidN Unspecified

    What is the behavior when the timesynchronization signal/messages are lost ?

    The quality attribute ClockFailure will be set to TRUEafter a configured time period.

    What is the behaviour when the timesynchronisation messages indicate that the

    stratum is greater than 3?

    A stratum with a value greater than 3 with the SNTP timesynchronization messages indicates that the time server

    has a questionable synchronisation.It might also indicate that no GPS connection areavailable.Therefore the time quality attributeClockNotSynchronized will be set to TRUE as long asthe stratum content is greater than 3.

    additional items:

    What is the behavior at start up time whena time synchronization via SNTP isconfigured ?

    The ClockNotSynchronized attribute is set to TRUE aslong as no time synchronization is established.

  • 7/31/2019 7SJ61 64 Ingles

    26/178

    Applications

    1.13 File transfer model

    26 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    1.13 File transfer model

    Description Value / Clarification

    What is structure of files and directories? Directory name / COMTRADE / *;Directory name / LD / *;Files according to the comtrade standard.

    What is the resulting behavior if no filespecification is present in the file directoryrequest?

    If no file specification is present in the directory request,all files are returned - not only the files in the rootdirectory.

    Is the IETF FTP protocol also implemented ? N

    Directory names are separated from the filename by

    /

    The maximum file name size including path(default 64 chars)

    64

    Are directory/file name case sensitive Case sensitive

    Maximum file size Not limited by implementation or configuration. Dependson available memory.

    additional items:

    Maximum number of clients that can use theFTP service simultaneously

    1

    Maximum number of files that can be

    accessed simultaneously

    1

  • 7/31/2019 7SJ61 64 Ingles

    27/178

    Applications

    1.14 General items

    27SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    1.14 General items

    Description Value / Clarification

    IED behavior when the Logical Deviceis blocked : LLN0.Mod.stVal = blocked

    Unlike the definition of the Data Objects Mod/Beh in IEC61850-7-4, outputs to the process will be generated.Details to this behavior are specified in SIPROTEC 4Ethernet Module EN 100 IEC 61850 Electrical Interface

    100 MBit, Manual /1/

    additional items:

    GOOSE Proxy object To be able to subscribe Data over GOOSE, ProxyObjects are added into the object directory.Typically, they are Data of GGIO logical nodes:SPCSOxx, DPCSOxx, ISCSOxx.

    The Data Attributes of those Data are ctlVal, q and t.The control model associated to those Data is status-only.They are not controllable from an IEC61850 client, andtheir function is only to enable the GOOSE subscribing.

    What is the type of the attribute actVal inthe BCR (Binary Counter Reading) CDC?

    The type is integer 32 (INT32).

  • 7/31/2019 7SJ61 64 Ingles

    28/178

    Applications

    1.15 TISSUES

    28 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    1.15 TISSUES

    Topic TISSUE

    -No.

    Link Description Impact of

    Interoper.

    Object Model 120 http://www.tissue.iec61850.com/tissue.mspx?issueid=120

    Type - Mod.stVal andMod.ctlVal

    -

    146 http://www.tissue.iec61850.com/tissue.mspx?issueid=146

    CtxInt -

    173 http://www.tissue.iec61850.com/tissue.mspx?issueid=173

    Ctl modellingharmonization

    -

    234 http://www.tissue.iec61850.com/tissue.mspx?issueid=234

    New type CtxInt x

    Services 377 http://www.tissue.iec61850.com/tissue.mspx?issueid=377

    DeleteDataSet response- -

    276 http://www.tissue.iec61850.com/tissue.mspx?issueid=276

    File Services NegativeResponses

    -

    183 http://www.tissue.iec61850.com/tissue.mspx?issueid=183

    GetNameList errorhandling

    x

    165 http://www.tissue.iec61850.com/tissue.mspx?issueid=165

    Improper Error Responsefor GetDataSetValues

    x

    116 http://www.tissue.iec61850.com/tissue.mspx?issueid=116

    GetNameList with emptyresponse?

    x

    Reporting 474 http://www.tissue.iec61850.com/tissue.mspx?issueid=474

    GI for URCB -

    453 http://www.tissue.iec61850.com/tissue.mspx?issueid=453

    Reporting & Loggingmodel revision

    x

    438 http://www.tissue.iec61850.com/tissue.mspx?issueid=438

    EntryTime base shouldbe GMT

    -

    349 http://www.tissue.iec61850.com/tissue.mspx?issueid=349

    BRCB TimeOfEntry hastwo definitions

    x

    348 http://www.tissue.iec61850.com/tissue.mspx?issueid=348

    URCB class and report x

  • 7/31/2019 7SJ61 64 Ingles

    29/178

    Applications

    1.15 TISSUES

    29SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    Reporting 344 http://www.tissue.iec61850.com/tissue.mspx?issueid=344

    TimeOfEntry misspelled -

    335 http://www.tissue.iec61850.com/tissue.mspx?issueid=335

    Clearing of Bufovfl x

    332 http://www.tissue.iec61850.com/tissue.mspx?issueid=332

    Ambiguity in use oftrigger options

    x

    329 http://www.tissue.iec61850.com/tissue.mspx?issueid=329

    Reporting and BufOvl x

    322 http://www.tissue.iec61850.com/tissue.mspx?issueid=322

    Write Configurationattribute of BRCBs

    301 http://www.tissue.iec61850.com/tissue.mspx?issueid=301

    SqNum in BufferedReports

    -

    300 http://www.tissue.iec61850.com/tissue.mspx?issueid=300

    Attribute Resv in BRCB x

    298 http://www.tissue.iec61850.com/tissue.mspx?issueid=298

    Type of SqNum x

    297 http://www.tissue.iec61850.com/tissue.mspx?issueid=297

    Sequence number x

    278 http://www.tissue.iec61850.com/tissue.mspx?issueid=278

    EntryId not valid for aserver

    x

    275 http://www.tissue.iec61850.com/tissue.mspx?issueid=275

    Confusing statement onGI usage

    x

    191 http://www.tissue.iec61850.com/tissue.mspx?issueid=191

    BRCB: Integrity andbuffering reports

    x

    190 http://www.tissue.iec61850.com/tissue.mspx?issueid=190

    BRCB: EntryId andTimeOfEntry

    x

    177 http://www.tissue.iec61850.com/tissue.mspx?issueid=177

    Ignoring OptFlds bits forURCB

    -

    52 http://www.tissue.iec61850.com/tissue.mspx?issueid=52

    Ambiguity GOOSESqNum

    x

    49 http://www.tissue.iec61850.com/tissue.mspx?issueid=49

    BRCB TimeOfEntry? x

    Control Model 46 http://www.tissue.iec61850.com/

    tissue.mspx?issueid=46

    Synchro check cancel x

    44 http://www.tissue.iec61850.com/tissue.mspx?issueid=44

    AddCause - Object notsel

    x

    30 http://www.tissue.iec61850.com/tissue.mspx?issueid=30

    control parameter T x

  • 7/31/2019 7SJ61 64 Ingles

    30/178

    Applications

    1.15 TISSUES

    30 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

  • 7/31/2019 7SJ61 64 Ingles

    31/178

    31SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    Basics 2

    Contents

    This chapter contains general information about the effects of device configuration on LogicalNodes and DOIs.

    2.1 General 32

    2.2 Effects of Configuration on the Logical Nodes 34

    2.3 Allocation of Logical Nodes to Logical Devices 49

    2.4 Logical Node LLN0 53

    2.5 DOI Behavior 58

  • 7/31/2019 7SJ61 64 Ingles

    32/178

    Basics

    2.1 General

    32 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    2.1 General

    The protocol IEC 61850 was developed to define a standard that can be internationally

    employed for the transmission of power automation system data.

    This cross national standard enables an interoperability between automation systems anddevices made by different manufacturers.

    The devices and high voltage bay control units of the SIPROTEC 4 series can be equipped withan Ethernet module EN100 via which the protocol IEC 61850 is interpreted.

    The configuration of the protocol and the integration of the device with redundant IEC 61850interfaces in your network are performed via the configuration system DIGSI.

    For details please refer to the manuals:

    SIPROTEC 4 Ethernet Module EN 100 IEC 61850 Electrical Interface 100 MBit, Manual /1/and

    SIPROTEC 4 System Description /2/.

    Logical Devices

    LD Logical Devices represent a functional structuring of the LN Logical Nodes of a SIPROTECdevice.

    The following Logical Devices are present:

    Logical Device Protection PROT

    Logical Device Measurement MEAS

    Logical Device Disturbance Recorder DR

    Logical Device Control CTRL

    Logical Device Extended EXT

    Each LD contains LN LLN0 and LN LPHD1.

    The allocation of the Logical Nodes to the Logical Devices is listed in Chapter 2.3.

    Note

    The following definitions are taken mainly from standard IEC 61850, Technical SpecificationIEC TS 61850-2.

  • 7/31/2019 7SJ61 64 Ingles

    33/178

    Basics

    2.1 General

    33SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    Logical Node LN

    Smallest part of a function that exchanges data. A logical node is an object defined by its dataand methods.

    Data object instance DOIA Data object is part of a logical node object representing specific information for example statusof measurement. From an object-oriented point of view, a data object is an instance of a dataclass. Specific data classes carry the semantic within a logical node.

    Data attribute instance DAI

    A Data attribute defines the name (semantic), format, range of possible values, andrepresentation of values while being communicated.

    Annunciation types via GOOSE

    Generic Object Oriented Substation Event

    A GOOSE report enables high speed trip signals to be issued with a high probability of delivery.The following types of information can be configured via GOOSE.

    External single point indication O/O

    External single point indication I/O

    External double point indication

    External double point indication, fast

    External operational measured values

    External metered values

  • 7/31/2019 7SJ61 64 Ingles

    34/178

    Basics

    2.2 Effects of Configuration on the Logical Nodes

    34 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    2.2 Effects of Configuration on the Logical Nodes

    2.2.1 Function parameters

    Depending on the configuration of the function parameters the functions of the SIPROTEC areenabled or disabled. If a function is disabled, the corresponding Logical Node is not available.

    The following Logical Nodes are always available:

    Logical Device Protection: LLN0, LPHD1, XCBR1,PTRC1

    Logical Device Measurement: LLN0, LPHD1, MMXU1,MMTR1, MSQI1

    Logical Device Control: LLN0, LPHD1, CALH1

  • 7/31/2019 7SJ61 64 Ingles

    35/178

    Basics

    2.2 Effects of Configuration on the Logical Nodes

    35SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    2.2.2 Function parameters SIPROTEC 7SJ61

    The following table shows which Logical Nodes are available when setting the correspondingfunction parameter.

    The setting (-) implies that no corresponding LN is available.

    Table 2-1 SIPROTEC 7SJ61 - Effects of Function parameters to the Logical Nodes

    No. Function Setting Logical Nodes

    103 Setting Group Change Option No effect

    104 Oscillographic Fault Records Disabled -

    Enabled RDRE1

    112 50/51 (Charac. Phase)Overcurrent Protection

    Disabled -

    Definite Time PTOC6, PTOC7,PTOC18, PTRC2

    TOC IEC PTOC6, PTOC7, PTOC1PTOC18, PTRC2

    TOC ANSI PTOC6, PTOC7,PTOC1, PTOC18,PTRC2

    User Defined PU PTOC6, PTOC7, PTOC1PTOC18, PTRC2

    Userdef. Reset PTOC6, PTOC7, PTOC1,PTOC18, PTRC2

    113 50N/51N (Charac. Ground)Overcurrent Protection

    Disabled -

    Definite Time PTOC8, PTOC9, PTRC2

    TOC IEC PTOC8, PTOC9, PTOC2,PTRC2

    TOC ANSI PTOC8, PTOC9, PTOC2,PTRC2

    User Defined PU PTOC8, PTOC9, PTOC2,PTRC2

    Userdef. Reset PTOC8, PTOC9, PTOC2,PTRC2

    117 Cold Load Pickup No effect

  • 7/31/2019 7SJ61 64 Ingles

    36/178

    Basics

    2.2 Effects of Configuration on the Logical Nodes

    36 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    122 2nd Harmonic Inrush Restraint No effect

    127 50 1PhSingle Phase Overcurrent Protection

    Disabled -

    Enabled PTOC16, PTOC17

    131 (sens.) Ground fault Disabled -

    Enabled PHIZ1, PSDE1, PSDE2

    133 Intermittent earth fault protection No effect

    140 46 Negative Sequence Protection Disabled -

    TOC ANSI / TOC IEC PTOC14, PTOC15,PTOC5

    Definite Time PTOC14, PTOC15

    141 48 Startup Supervision of Motors Disabled -

    Enabled PMSS1

    142 49 Thermal Overload Protection Disabled -

    No ambient temp PTTR1

    With amb. temp. PTTR1

    143 66 Startup Counter for Motors Disabled -

    Enabled PMRI1

    144 Load Jam Protection Disabled -

    Enabled PMLJ1

    170 50BF Breaker Failure Protection Disabled -

    Enabled RBRF1

    enabled w/ 3I0> RBRF1

    171 79 Auto-Reclose Function Disabled -

    Enabled RREC1

    172 52 Breaker Wear Monitoring No effect

    Table 2-1 SIPROTEC 7SJ61 - Effects of Function parameters to the Logical Nodes (Forts.)

    No. Function Setting Logical Nodes

  • 7/31/2019 7SJ61 64 Ingles

    37/178

    Basics

    2.2 Effects of Configuration on the Logical Nodes

    37SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    182 74TC Trip Circuit Supervision Disabled -

    2 Binary Inputs DOI CirSpv, LN XCBRLD PROT

    1 Binary Input DOI CirSpv, LN XCBRLD PROT

    190 External Temperature Input No effect

    191 Ext. Temperature Input Connection Type No effect

    Table 2-1 SIPROTEC 7SJ61 - Effects of Function parameters to the Logical Nodes (Forts.)

    No. Function Setting Logical Nodes

  • 7/31/2019 7SJ61 64 Ingles

    38/178

    Basics

    2.2 Effects of Configuration on the Logical Nodes

    38 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    2.2.3 Function parameters SIPROTEC 7SJ62/63/64

    The following table shows which Logical Nodes are available when setting the correspondingfunction parameter.

    The setting (-) implies that no corresponding LN is available.

    Table 2-2 SIPROTEC 7SJ62/63/64 - Effects of Function parameters to the Logical Nodes

    No. Function Setting Logical Nodes

    103 Setting Group Change Option No effect

    104 Oscillographic Fault Records Disabled -

    Enabled RDRE1

    112 50/51 (Charac. Phase)Overcurrent Protection

    Disabled -

    Definite Time PTOC6, PTOC7,PTOC18, PTRC2

    TOC IEC PTOC6, PTOC7, PTOC1PTOC18, PTRC2

    TOC ANSI PTOC6, PTOC7,PTOC1, PTOC18,PTRC2

    User Defined PU PTOC6, PTOC7, PTOC1PTOC18, PTRC2

    Userdef. Reset PTOC6, PTOC7, PTOC1,PTOC18, PTRC2

    113 50N/51N (Charac. Ground)Overcurrent Protection

    Disabled -

    Definite Time PTOC8, PTOC9, PTRC2

    TOC IEC PTOC8, PTOC9, PTOC2,PTRC2

    TOC ANSI PTOC8, PTOC9, PTOC2,PTRC2

    User Defined PU PTOC8, PTOC9, PTOC2,PTRC2

    Userdef. Reset PTOC8, PTOC9, PTOC2,PTRC2

  • 7/31/2019 7SJ61 64 Ingles

    39/178

    Basics

    2.2 Effects of Configuration on the Logical Nodes

    39SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    115 67, 67-TOC

    Directional Overcurrent Protection

    Disabled -

    Definite Time PTOC10, PTOC11,PTRC3

    TOC IEC PTOC10, PTOC11,PTOC3, PTRC3

    TOC ANSI PTOC10, PTOC11,PTOC3, PTRC3

    User Defined PU PTOC10, PTOC11,PTOC3, PTRC3

    Userdef. Reset PTOC10, PTOC11,PTOC3, PTRC3

    116 67N, 67N-TOCDirectional Overcurrent Protection

    Disabled -

    Definite Time PTOC12, PTOC13,PTRC3

    TOC IEC PTOC12, PTOC13,PTOC4, PTRC3

    TOC ANSI PTOC12, PTOC13,

    PTOC4, PTRC3

    User Defined PU PTOC12, PTOC13,PTOC4, PTRC3

    Userdef. Reset PTOC12, PTOC13,PTOC4, PTRC3

    117 Cold Load Pickup No effect

    122 2nd Harmonic Inrush Restraint No effect

    127 50 1Ph

    Single Phase Overcurrent Protection

    Disabled -

    Enabled PTOC16, PTOC17

    130 (sens.) Ground fault dir. characteristic cos / sin see Parameter 131

    V0/I0 mea. see Parameter 131

    Table 2-2 SIPROTEC 7SJ62/63/64 - Effects of Function parameters to the Logical Nodes (Forts.)

    No. Function Setting Logical Nodes

  • 7/31/2019 7SJ61 64 Ingles

    40/178

    Basics

    2.2 Effects of Configuration on the Logical Nodes

    40 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    131 (sensitive) Ground fault

    and(sens.) Ground fault dir. characteristic =cos / sin

    Disabled -

    Definite Time PHIZ1, PSDE1, PSDE2

    TOC IEC PHIZ1, PSDE2, PSDE3

    TOC IANSI PHIZ1, PSDE2, PSDE3

    User Defined PU PHIZ1, PSDE2, PSDE3

    Log. inverse 1 PHIZ1, PSDE2, PSDE3

    Log. inverse 2 PHIZ1, PSDE2, PSDE3

    131 (sensitive) Ground faultand(sens.) Ground fault dir. characteristic =V0/I0 mea.

    Disabled -

    Definite Time PHIZ1, PSDE1, PSDE2

    User Defined PU PHIZ1, PSDE1, PSDE2

    133 Intermittent earth fault protection No effect

    140 46 Negative Sequence Protection Disabled -

    TOC ANSI PTOC14, PTOC15,PTOC5

    TOC IEC PTOC14, PTOC15,PTOC5

    Definite Time PTOC14, PTOC15

    141 48 Startup Supervision of Motors Disabled -

    Enabled PMSS1

    142 49 Thermal Overload Protection Disabled -

    No ambient temp PTTR1

    With amb. temp. PTTR1

    143 66 Startup Counter for Motors Disabled -

    Enabled PMRI1

    144 Load Jam Protection Disabled -

    Enabled PMLJ1

    Table 2-2 SIPROTEC 7SJ62/63/64 - Effects of Function parameters to the Logical Nodes (Forts.)

    No. Function Setting Logical Nodes

  • 7/31/2019 7SJ61 64 Ingles

    41/178

    Basics

    2.2 Effects of Configuration on the Logical Nodes

    41SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    150 27, 59 Under/Overvoltage Protection Disabled -

    Enabled PTUV1, PTUV2,PTOV1, PTOV2

    154 81 Over/Underfrequency Protection Disabled -

    Enabled PTOF1 PTOF4,PTUF1 PTUF4

    161 25 Function group 1Synchronism and Voltage Check

    Disabled -

    ASYN/SYNCHRON RSYN1

    SYNCHROCHECK RSYN1

    162 25 Function group 2Synchronism and Voltage Check

    Disabled -

    ASYN/SYNCHRON RSYN2

    SYNCHROCHECK RSYN2

    163 25 Function group 3Synchronism and Voltage Check

    Disabled -

    ASYN/SYNCHRON RSYN3

    SYNCHROCHECK RSYN3

    164 25 Function group 4Synchronism and Voltage Check

    Disabled -

    ASYN/SYNCHRON RSYN4

    SYNCHROCHECK RSYN4

    170 50BF Breaker Failure Protection Disabled -

    Enabled RBRF1

    enabled w/ 3I0> RBRF1

    171 79 Auto-Reclose Function Disabled -

    Enabled RREC1

    172 52 Breaker Wear Monitoring No effect

    180 Fault Locator Disabled -

    Enabled RFLO1

    Table 2-2 SIPROTEC 7SJ62/63/64 - Effects of Function parameters to the Logical Nodes (Forts.)

    No. Function Setting Logical Nodes

  • 7/31/2019 7SJ61 64 Ingles

    42/178

    Basics

    2.2 Effects of Configuration on the Logical Nodes

    42 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    181 Line sections for fault locator No effect

    182 74TC Trip Circuit Supervision Disabled -

    2 Binary Inputs DOI CirSpv, LN XCBRLD PROT

    1 Binary Input DOI CirSpv, LN XCBRLD PROT

    190 External Temperature Input No effect

    191 Ext. Temperature Input Connection Type No effect

    Table 2-2 SIPROTEC 7SJ62/63/64 - Effects of Function parameters to the Logical Nodes (Forts.)

    No. Function Setting Logical Nodes

  • 7/31/2019 7SJ61 64 Ingles

    43/178

    Basics

    2.2 Effects of Configuration on the Logical Nodes

    43SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    2.2.4 Function parameters SIPROTEC 7SJ80

    The following table shows which Logical Nodes are available when setting the correspondingfunction parameter.

    The setting (-) implies that no corresponding LN is available.

    Table 2-3 SIPROTEC 7SJ80 - Effects of Function parameters to the Logical Nodes

    No. Function Setting Logical Nodes

    103 Setting Group Change Option No effect

    104 Oscillographic Fault Records Disabled -

    Enabled RDRE1

    112 50/51 (Charac. Phase)Overcurrent Protection

    Disabled -

    Definite Time PTOC6, PTOC7,PTOC18, PTRC2

    TOC IEC PTOC6, PTOC7, PTOC1PTOC18, PTRC2

    TOC ANSI PTOC6, PTOC7,PTOC1, PTOC18,PTRC2

    113 50N/51N (Charac. Ground)Overcurrent Protection

    Disabled -

    Definite Time PTOC8, PTOC9, PTRC2

    TOC IEC PTOC8, PTOC9, PTOC2,PTRC2

    TOC ANSI PTOC8, PTOC9, PTOC2,PTRC2

    115 67, 67-TOCDirectional Overcurrent Protection

    Disabled -

    Definite Time PTOC10, PTOC11,

    PTRC3

    TOC IEC PTOC10, PTOC11,PTOC3, PTRC3

    TOC ANSI PTOC10, PTOC11,PTOC3, PTRC3

  • 7/31/2019 7SJ61 64 Ingles

    44/178

    Basics

    2.2 Effects of Configuration on the Logical Nodes

    44 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    116 67N, 67N-TOC

    Directional Overcurrent Protection

    Disabled -

    Definite Time PTOC12, PTOC13,PTRC3

    TOC IEC PTOC12, PTOC13,PTOC4, PTRC3

    TOC ANSI PTOC12, PTOC13,PTOC4, PTRC3

    117 Cold Load Pickup No effect

    122 2nd Harmonic Inrush Restraint No effect

    127 50 1PhSingle Phase Overcurrent Protection

    Disabled -

    Enabled PTOC16, PTOC17

    130 (sens.) Ground fault dir. characteristic cos / sin see Parameter 131

    V0/I0 mea. see Parameter 131

    131 (sensitive) Ground faultand(sens.) Ground fault dir. characteristic =

    cos / sin

    Disabled -

    Definite Time PHIZ1, PSDE1, PSDE2

    User Defined PU PHIZ1, PSDE2, PSDE3

    131 (sensitive) Ground faultand(sens.) Ground fault dir. characteristic =V0/I0 mea.

    Disabled -

    Definite Time PHIZ1, PSDE1, PSDE2

    User Defined PU PHIZ1, PSDE1, PSDE2

    140 46 Negative Sequence Protection Disabled -

    TOC ANSI PTOC14, PTOC15,

    PTOC5

    TOC IEC PTOC14, PTOC15,PTOC5

    Definite Time PTOC14, PTOC15

    142 49 Thermal Overload Protection Disabled -

    No ambient temp PTTR1

    Table 2-3 SIPROTEC 7SJ80 - Effects of Function parameters to the Logical Nodes (Forts.)

    No. Function Setting Logical Nodes

  • 7/31/2019 7SJ61 64 Ingles

    45/178

    Basics

    2.2 Effects of Configuration on the Logical Nodes

    45SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    150 27, 59 Under/Overvoltage Protection Disabled -

    Enabled PTUV1, PTUV2,PTOV1, PTOV2

    154 81 Over/Underfrequency Protection Disabled -

    Enabled PTOF1 PTOF4,PTUF1 PTUF4

    161 25 Function group 1Synchronism and Voltage Check

    Disabled -

    SYNCHROCHECK RSYN1

    170 50BF Breaker Failure Protection Disabled -

    Enabled RBRF1

    enabled w/ 3I0> RBRF1

    171 79 Auto-Reclose Function Disabled -

    Enabled RREC1

    172 52 Breaker Wear Monitoring No effect

    180 Fault Locator Disabled -

    Enabled RFLO1

    181 Line sections for fault locator 1 Section

    2 Sections

    3 Sections

    No effect

    182 74TC Trip Circuit Supervision Disabled -

    2 Binary Inputs DOI CirSpv, LN XCBRLD PROT

    1 Binary Input DOI CirSpv, LN XCBRLD PROT

    192 Capacitive voltage measurement No effect

    617 Port B usage No effect

    Table 2-3 SIPROTEC 7SJ80 - Effects of Function parameters to the Logical Nodes (Forts.)

    No. Function Setting Logical Nodes

  • 7/31/2019 7SJ61 64 Ingles

    46/178

    Basics

    2.2 Effects of Configuration on the Logical Nodes

    46 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    2.2.5 Function parameters SIPROTEC 7SK80

    The following table shows which Logical Nodes are available when setting the correspondingfunction parameter.

    The setting (-) implies that no corresponding LN is available.

    Table 2-4 SIPROTEC 7SK80 - Effects of Function parameters to the Logical Nodes

    No. Function Setting Logical Nodes

    103 Setting Group Change Option No effect

    104 Oscillographic Fault Records Disabled -

    Enabled RDRE1

    112 50/51 (Charac. Phase)Overcurrent Protection

    Disabled -

    Definite Time PTOC6, PTOC7,PTOC18, PTRC2

    TOC IEC PTOC6, PTOC7, PTOC1PTOC18, PTRC2

    TOC ANSI PTOC6, PTOC7,PTOC1, PTOC18,PTRC2

    113 50N/51N (Charac. Ground)Overcurrent Protection

    Disabled -

    Definite Time PTOC8, PTOC9, PTRC2

    TOC IEC PTOC8, PTOC9, PTOC2,PTRC2

    TOC ANSI PTOC8, PTOC9, PTOC2,PTRC2

    116 67N, 67N-TOCDirectional Overcurrent Protection

    Disabled -

    Definite Time PTOC12, PTOC13,PTRC3

    TOC IEC PTOC12, PTOC13,PTOC4, PTRC3

    TOC ANSI PTOC12, PTOC13,PTOC4, PTRC3

    117 Cold Load Pickup No effect

  • 7/31/2019 7SJ61 64 Ingles

    47/178

    Basics

    2.2 Effects of Configuration on the Logical Nodes

    47SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    122 2nd Harmonic Inrush Restraint No effect

    130 (sens.) Ground fault dir. characteristic cos / sin see Parameter 131

    V0/I0 mea. see Parameter 131

    131 (sensitive) Ground faultand(sens.) Ground fault dir. characteristic =cos / sin

    Disabled -

    Definite Time PHIZ1, PSDE1, PSDE2

    User Defined PU PHIZ1, PSDE2, PSDE3

    131 (sensitive) Ground fault

    and(sens.) Ground fault dir. characteristic =V0/I0 mea.

    Disabled -

    Definite Time PHIZ1, PSDE1, PSDE2

    User Defined PU PHIZ1, PSDE1, PSDE2

    140 46 Negative Sequence Protection Disabled -

    TOC ANSI PTOC14, PTOC15,PTOC5

    TOC IEC PTOC14, PTOC15,PTOC5

    Definite Time PTOC14, PTOC15

    141 48 Startup Supervision of Motors Disabled -

    Enabled PMSS1

    142 49 Thermal Overload Protection Disabled -

    No ambient temp PTTR1

    With amb. temp. PTTR1

    143 66 Startup Counter for Motors Disabled -

    Enabled PMRI1

    144 Load Jam Protection Disabled -

    Enabled PMLJ1

    Table 2-4 SIPROTEC 7SK80 - Effects of Function parameters to the Logical Nodes (Forts.)

    No. Function Setting Logical Nodes

  • 7/31/2019 7SJ61 64 Ingles

    48/178

    Basics

    2.2 Effects of Configuration on the Logical Nodes

    48 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    150 27, 59 Under/Overvoltage Protection Disabled -

    Enabled PTUV1, PTUV2,PTOV1, PTOV2

    154 81 Over/Underfrequency Protection Disabled -

    Enabled PTOF1 PTOF4,PTUF1 PTUF4

    170 50BF Breaker Failure Protection Disabled -

    Enabled RBRF1

    enabled w/ 3I0> RBRF1

    172 52 Breaker Wear Monitoring No effect

    182 74TC Trip Circuit Supervision Disabled -

    2 Binary Inputs DOI CirSpv, LN XCBRLD PROT

    1 Binary Input DOI CirSpv, LN XCBRLD PROT

    190 External Temperature Input No effect

    191 Ext. Temperature Input Connection Type No effect

    192 Capacitive voltage measurement No effect

    617 Port B usage No effect

    Table 2-4 SIPROTEC 7SK80 - Effects of Function parameters to the Logical Nodes (Forts.)

    No. Function Setting Logical Nodes

  • 7/31/2019 7SJ61 64 Ingles

    49/178

    Basics

    2.3 Allocation of Logical Nodes to Logical Devices

    49SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    2.3 Allocation of Logical Nodes to Logical Devices

    All Logical Nodes (LN) are allocated to Logical Devices (LD). The following tables show this

    allocation and the DOIs available for each LN.

    LD PROT

    The Logical Device PROT (Protection) contains the following LNs:

    Table 2-5 LD PROT - Logical Nodes

    LN Function DOI

    LLN0 General Mod, Beh, Health, NamPlt, OpTmh

    PTRC1 General device pickup

    General OFF

    Mod, Beh, Health, NamPlt, Str,Tr,FinTr

    XCBR1 52 Breaker Three-pole tripping

    Mod, Beh, Health, NamPlt, Loc, OpCnt, PosBlkOpn, BlkCls, CBOpCapSumSwARs1, SumSwARs2, SumSwARs3

    PTOC6PTOC7PTOC1PTOC18PTRC2

    50/51 (Charac. Phase) Mod, Beh, Health, NamPlt, Str, Op, ChgSet

    PTOC8

    PTOC9PTOC2PRTC2

    50N/51N (Charac. Ground) Mod, Beh, Health, NamPlt, Str, Op, ChgSet

    PTOC10PTOC11PTOC3PTRC3

    67, 67-TOC Mod, Beh, Health, NamPlt, Str, Op, ChgSet

    PTOC12PTOC13PTOC4PRTC2

    67N, 67N-TOC Mod, Beh, Health, NamPlt, Str, Op, ChgSet

    PTOC16PTOC17

    50 1Ph Mod, Beh, Health, NamPlt, Str, Op

    PTUV1PTUV2

    27 Undervoltage Protection Mod, Beh, Health, NamPlt, Str, Op

    PTOV1PTOV2

    59 Overvoltage Protection Mod, Beh, Health, NamPlt, Str, Op

  • 7/31/2019 7SJ61 64 Ingles

    50/178

    Basics

    2.3 Allocation of Logical Nodes to Logical Devices

    50 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    PTOC14

    PTOC15PTOC5

    46 Negative Sequence Protection Mod, Beh, Health, NamPlt, Str, Op

    PMSS1 48 Startup Supervision of Motors Mod, Beh, Health, NamPlt, Str, Op

    PMRI1 66 Startup Counter for Motors Mod, Beh, Health, NamPlt, Op, StrInhTmm

    PMLJ1 Load Jam Protection Mod, Beh, Health, NamPlt, Str, Op, LDJamAlm,ChgSet

    PTUF1PTUF2PTUF3PTUF4

    81 Underfrequency Protection Mod, Beh, Health, NamPlt, Str, Op, BlkV

    PTOF1PTOF2PTOF3PTOF4

    81 Overfrequency Protection Mod, Beh, Health, NamPlt, Str, Op, BlkV

    PTTR1 49 Thermal Overload Protection Mod, Beh, Health, NamPlt, Str, Op, AlmThm

    PSDE1PSDE2PSDE3

    (sensitive) Ground fault Mod, Beh, Health, NamPlt, Str, Op

    PHIZ1 (sensitive) Ground fault Mod, Beh, Health, NamPlt, Str, Op

    RREC1 79 Auto-Reclose Function Mod, Beh, Health, NamPlt, Op, AutoRecSt

    RFLO1 Fault Locator Mod, Beh, Health, NamPlt, FltZ, FltDiskm, FltDisPrc

    RBRF1 50BF Breaker Failure Protection Mod, Beh, Health, NamPlt, Str, OpEx, OpIn

    LPHD1 Device PhyNam, PhyHealth, Proxy

    Table 2-5 LD PROT - Logical Nodes (Forts.)

    LN Function DOI

  • 7/31/2019 7SJ61 64 Ingles

    51/178

    Basics

    2.3 Allocation of Logical Nodes to Logical Devices

    51SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    LD MEAS

    The Logical Device MEAS (Measurement) contains the following LNs:

    LD DR

    The Logical Device DR (Disturbance Recorder) contains the following LNs:

    Table 2-6 LD MEAS - Logical Nodes

    LN Function DOIs

    LLN0 General Mod, Beh, Health, NamPlt

    MMXU1 Operational measured values Mod, Beh, Health, NamPlt,TotW, TotVAr, TotVA, TotPF, Hz, PPV, PhV, A

    MMTR1 Power Metering Mod, Beh, Health, NamPlt,SupWh, SupVArh, DmdWh, DmdVArh

    MSQI1 Measured values, symmetricalcomponents

    Mod, Beh, Health, NamPlt, SeqA, SeqV

    LPHD1 Device PhyNam, PhyHealth, Proxy

    Table 2-7 LD DR - Logical Nodes

    LN Function DOIs

    LLN0 General Mod, Beh, Health, NamPlt

    RDRE1 Oscillographic Fault Records Mod, Beh, Health, NamPlt, RcdMade, RcdStrFltNum, GriFltNum

    LPHD1 Device PhyNam, PhyHealth, Proxy

  • 7/31/2019 7SJ61 64 Ingles

    52/178

    Basics

    2.3 Allocation of Logical Nodes to Logical Devices

    52 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    LD CTRL

    The Logical Device CTRL (Control) contains the following LNs:

    LD EXT

    The Logical Device EXT (Extended) contains the following LNs:

    The Logical Nodes of the switching (and userdefined) objects will be created by DIGSI duringthe parameterization of your SIPROTEC device.

    MICS,Model Implementation Conformance Statement, shows the assignment of the DOIs;you can use DIGSI to print the MICS.

    Table 2-8 LD CTRL - Logical Nodes

    LN Function DOIs

    LLN0 General Mod, Beh, Health, NamPlt, LEDRs, Loc

    RSYN1RSYN2RSYN3RSYN4

    25 Function group 125 Function group 225 Function group 325 Function group 4

    Mod, Beh, Health, NamPlt,Rel, VInd, AngInd, HzInd, SynPrg,DifVClc, DifHzClc, DifAngClc

    CALH1 Error with a summary alarm andAlarm summary event

    Mod, Beh, Health, NamPlt, GrAlm, GrWrn,ErrBoard1, ErrBoard2, ErrBoard3, ErrBoard4,ErrBoard5, ErrBoard6, ErrBoard7

    LPHD1 Device PhyNam, PhyHealth, Proxy, CtlNum, DevStr

    Table 2-9 LD EXT - Logical Nodes

    LN Function DOIs

    LLN0 General Mod, Beh, Health, NamPlt, LEDRs, Loc

    LPHD1 Device PhyNam, PhyHealth, Proxy, CtlNum

  • 7/31/2019 7SJ61 64 Ingles

    53/178

    Basics

    2.4 Logical Node LLN0

    53SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    2.4 Logical Node LLN0

    2.4.1 Logical Device PROT

    LLN0.Mod

    LLN0.Beh

    LLN0.Health

    No. Information

    52 At Least 1 Protection Funct. is Active (ProtActive) 0 1 1 1 1

    Test mode (Test mode) x 0 0 1 1

    Stop data transmission (DataStop) x 0 1 0 1

    LLN0.Mod.stVal 5 1 2 3 4

    device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON

    0 - OFF / FALSE 2 - BLOCKED

    x - irrelevant 3 - TEST

    4 - TEST/BLOCKED

    5 - OFF

    No. Information

    52 At Least 1 Protection Funct. is Active (ProtActive) 0 1 1 1 1

    Test mode (Test mode) x 0 0 1 1

    Stop data transmission (DataStop) x 0 1 0 1

    LLN0.Beh.stVal 5 1 2 3 4

    device annunciation / setting: 1 - ON / TRUE IEC Status Beh.stVal: 1 - ON

    0 - OFF / FALSE 2 - BLOCKED

    x - irrelevant 3 - TEST

    4 - TEST/BLOCKED

    5 - OFF

    No. Information

    51 Device is Operational and Protecting (Device OK) 0 1

    LLN0.Health.stVal 3 1

    device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK

    0 - OFF 2 - WARNING

    3 - ALARM

  • 7/31/2019 7SJ61 64 Ingles

    54/178

    Basics

    2.4 Logical Node LLN0

    54 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    LLN0.OpTmh

    No. Information Value

    1020 Counter of operating hours (Op.Hours=) LLN0.OpTmh.stVal Operating hours (Absolute value)

  • 7/31/2019 7SJ61 64 Ingles

    55/178

    Basics

    2.4 Logical Node LLN0

    55SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    2.4.2 Logical Devices MEAS, DR and EXT

    LLN0.Mod

    LLN0.Beh

    LLN0.Health

    No. Information

    51 Device is Operational and Protecting (Device OK) x x x x

    Test mode (Test mode) 1 1 0 0

    Stop data transmission (DataStop) 1 0 1 0

    LLN0.Mod.stVal 4 3 2 1

    device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON

    0 - OFF / FALSE 2 - BLOCKED

    x - irrelevant 3 - TEST

    4 - TEST/BLOCKED

    5 - OFF

    No. Information

    51 Device is Operational and Protecting (Device OK) 0 1 1 1 1

    Test mode (Test mode) x 0 0 1 1

    Stop data transmission (DataStop) x 0 1 0 1

    LLN0.Beh.stVal 5 1 2 3 4

    device annunciation / setting: 1 - ON / TRUE IEC Status Beh.stVal: 1 - ON

    0 - OFF / FALSE 2 - BLOCKED

    x - irrelevant 3 - TEST

    4 - TEST/BLOCKED

    5 - OFF

    No. Information

    51 Device is Operational and Protecting (Device OK) 0 1

    LLN0.Health.stVal 3 1

    device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK

    0 - OFF 2 - WARNING

    3 - ALARM

  • 7/31/2019 7SJ61 64 Ingles

    56/178

    Basics

    2.4 Logical Node LLN0

    56 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    LLN0.OpTmh

    2.4.3 Logical Device CTRL

    LLN0.Mod

    LLN0.Beh

    No. Information Value

    1020 Counter of operating hours (Op.Hours=) LLN0.OpTmh.stVal Operating hours (Absolute value)

    No. Information

    55 Reset Device (Reset Device) 1 1 1 1 1

    51 Device is Operational and Protecting (Device OK) 1 1 1 1 0

    Test mode (Test mode) 1 1 0 0 0

    Stop data transmission (DataStop) 1 0 1 0 0

    LLN0.Mod.stVal 4 3 2 1 5

    device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON

    0 - OFF / FALSE 2 - BLOCKED

    x - irrelevant 3 - TEST

    4 - TEST/BLOCKED

    5 - OFF

    No. Information

    55 Reset Device (Reset Device) 1 1 1 1 1

    51 Device is Operational and Protecting (Device OK) 1 1 1 1 0

    Test mode (Test mode) 1 1 0 0 0

    Stop data transmission (DataStop) 1 0 1 0 0

    LLN0.Beh.stVal 4 3 2 1 5

    device annunciation / setting: 1 - ON / TRUE IEC Status Beh.stVal: 1 - ON

    0 - OFF / FALSE 2 - BLOCKED

    x - irrelevant 3 - TEST

    4 - TEST/BLOCKED

    5 - OFF

  • 7/31/2019 7SJ61 64 Ingles

    57/178

    Basics

    2.4 Logical Node LLN0

    57SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    LLN0.Health

    LLN0.OpTmh

    No. Information

    51 Device is Operational and Protecting (Device OK) 0 1

    LLN0.Health.stVal 3 1

    device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK

    0 - OFF 2 - WARNING

    3 - ALARM

    No. Information Value

    1020 Counter of operating hours (Op.Hours=) LLN0.OpTmh.stVal Operating hours (Absolute value)

  • 7/31/2019 7SJ61 64 Ingles

    58/178

    Basics

    2.5 DOI Behavior

    58 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    2.5 DOI Behavior

    2.5.1 Logical Device PROT

    For the Logical Nodes of the PROT Logical Device, LNx.Beh.stVal is formed fromLNx.Mod.stVal of the Logical Node and the status of the following device messages:

    Test mode (Test mode),

    Stop data transmission and

    At Least 1 Protection Funct. is Active.

    No. Information

    Test mode (Test mode) x 0 1 0 1 0 1 x

    Stop data transmission (DataStop) x 0 0 1 1 x x x

    52 At Least 1 Protection Funct. is Active (ProtActive) x 1 1 1 1 1 1 0

    LNx .Mod.stVal 5 1 1 1 1 2 2 x

    LNx.Beh.stVal 5 1 3 2 4 2 4 5

    device annunciation / setting: 1 - ON / TRUE IEC Status stVal: 1 - ON

    0 - OFF / FALSE 2 - BLOCKED

    x - irrelevant 3 - TEST

    4 - TEST/BLOCKED

    5 - OFF

  • 7/31/2019 7SJ61 64 Ingles

    59/178

    Basics

    2.5 DOI Behavior

    59SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    2.5.2 Logical Devices MEAS, CTRL, DR and EXT

    For the Logical Nodes of the MEAS, CTRL, DR and EXT Logical Devices, LNx.Beh.stVal isformed from LNx.Mod.stVal of the Logical Node and the status of the following device

    messages: Test mode (Test mode),

    Stop data transmission.

    No. Information

    Test mode (Test mode) x 0 1 0 1 0 1

    Stop data transmission (DataStop) x 0 0 1 1 x x

    LNx .Mod.stVal 5 1 1 1 1 2 2

    LNx.Beh.stVal 5 1 3 2 4 2 4

    device annunciation / setting: 1 - ON / TRUE IEC Status stVal: 1 - ON

    0 - OFF / FALSE 2 - BLOCKED

    x - irrelevant 3 - TEST

    4 - TEST/BLOCKED

    5 - OFF

  • 7/31/2019 7SJ61 64 Ingles

    60/178

    Basics

    2.5 DOI Behavior

    60 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

  • 7/31/2019 7SJ61 64 Ingles

    61/178

    61SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    Mapping 3

    Contents

    This chapter shows the mapping of the information relevant to the device on the Logical Node ofprotocol IEC61850. It is structured according to function. In Chapter 2 you can find whatconsequences non-configured functions have on the Logical Nodes as well as generalinformation about IEC 61850 mapping of information.

    3.1 Device (LPHD1, CALH1) 62

    3.2 Oscillographic Fault Records (RDRE1) 66

    3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2) 68

    3.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3) 81

    3.5 Single-Phase Overcurrent Protection (PTOC16, PTOC17) 93

    3.6 Voltage Protection 27, 59 (PTUVx, PTOVx) 96

    3.7 Negative Sequence Protection 46 (PTOC14, PTOC15, PTOC5) 104

    3.8 Motor Protection (PMSS1, PMRI1) 108

    3.9 Load Jam Protection (PMLJ1) 111

    3.10 Frequency protection 81 O/U (PTUFx, PTOFx) 113

    3.11 Thermal overload protection (PTTR1) 129

    3.12 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx) 131

    3.13 Automatic Reclosing System 79 (RREC1) 140

    3.14 Fault Locator (RFLO1) 142

    3.15 Circuit breaker failure protection 50BF(RBRF1) 144

    3.16 Synchronism and Voltage Check 25 (RSYNx) 146

    3.17 Three-pole tripping 52 Breaker (XCBR1) 158

    3.18 Tripping Logic of the Entire Device (PTRC1) 162

    3.19 Measurement (MMXU1, MSQI1, MMTR1) 164

  • 7/31/2019 7SJ61 64 Ingles

    62/178

    Mapping

    3.1 Device (LPHD1, CALH1)

    62 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    3.1 Device (LPHD1, CALH1)

    LPHD1.DevStr

    LPHD1.Proxy

    LPHD1.PhyHealth

    No. Information

    56 Initial Start of Device (Initial Start) 0 0 1 1

    67 Resume (Resume) 0 1 0 1

    LPHD1.DevStr.stVal T 2 1 T

    device annunciation: 1 - ON IEC Status DevStr.stVal: 1 - Initial Start

    0 - OFF 2 - Resume

    T - toggel between 1 and 2

    No. Information

    55 Reset Device (Reset Device) 0 1

    LPHD1.Proxy.stVal 1 0

    device annunciation: 1 - ON IEC Status Proxy.stVal: 0 - DEVICE is not a PROXY

    0 - OFF 1 - DEVICE is a PROXY

    No. Information

    51 Device is Operational and Protecting (Device OK) 0 1

    LPHD1.PhyHealth.stVal 3 1

    device annunciation: 1 - ON IEC Status PhyHealth.stVal: 1 - OK

    0 - OFF 2 - WARNING

    3 - ALARM

  • 7/31/2019 7SJ61 64 Ingles

    63/178

    Mapping

    3.1 Device (LPHD1, CALH1)

    63SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    3.1.1 Error with a summary alarm and Alarm summary event

    CALH1.Mod

    CALH1.Health

    CALH1.GrAlm

    CALH1.GrWrn

    No. Information

    51 Device is Operational and Protecting (Device OK) 1 0

    CALH1.Mod.stVal 1 5

    device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON

    0 - OFF 2 - BLOCKED

    3 - TEST

    4 - TEST/BLOCKED

    5 - OFF

    No. Information

    51 Device is Operational and Protecting (Device OK) 0 1

    CALH1.Health.stVal 3 1

    device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK

    0 - OFF 2 - WARNING

    3 - ALARM

    No. Information

    140 Error with a summary alarm (Error Sum Alarm) 1 0

    CALH1.GrAlm.stVal 1 0

    device annunciation: 1 - ON IEC Status GrAlm.stVal: 0 - FALSE

    0 - OFF 1 - TRUE

    No. Information

    160 Alarm Summary Event (Alarm Sum Event) 1 0

    CALH1.GrWrn.stVal 1 0

    device annunciation: 1 - ON IEC Status GrWrn.stVal: 0 - FALSE

    0 - OFF 1 - TRUE

  • 7/31/2019 7SJ61 64 Ingles

    64/178

    Mapping

    3.1 Device (LPHD1, CALH1)

    64 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    The LN CALH1.ErrBoard1 to CALH1.ErrBoard7 are available with Firmware7SJ61 V4.71 and higher, 7SJ62 V4.71 and higher, 7SJ64 V4.71 and higher,7SJ80 V4.61 and higher, 7SK80 V4.61 and higher

    CALH1.ErrBoard1

    CALH1.ErrBoard2

    CALH1.ErrBoard3

    CALH1.ErrBoard4

    No. Information

    183 Error Board 1 (Error Board 1) 1 0

    CALH1.ErrBoard1.stVal 1 0

    device annunciation: 1 - ON IEC Status ErrBoard1.stVal: 0 - FALSE

    0 - OFF 1 - TRUE

    No. Information

    184 Error Board 2 (Error Board 2) 1 0

    CALH1.ErrBoard2.stVal 1 0

    device annunciation: 1 - ON IEC Status ErrBoard2.stVal: 0 - FALSE

    0 - OFF 1 - TRUE

    No. Information

    185 Error Board 3 (Error Board 3) 1 0

    CALH1.ErrBoard3.stVal 1 0

    device annunciation: 1 - ON IEC Status ErrBoard3.stVal: 0 - FALSE

    0 - OFF 1 - TRUE

    No. Information

    186 Error Board 4 (Error Board 4) 1 0

    CALH1.ErrBoard4.stVal 1 0

    device annunciation: 1 - ON IEC Status ErrBoard4.stVal: 0 - FALSE

    0 - OFF 1 - TRUE

  • 7/31/2019 7SJ61 64 Ingles

    65/178

    Mapping

    3.1 Device (LPHD1, CALH1)

    65SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    CALH1.ErrBoard5

    CALH1.ErrBoard6

    CALH1.ErrBoard7

    No. Information

    187 Error Board 5 (Error Board 5) 1 0

    CALH1.ErrBoard5.stVal 1 0

    device annunciation: 1 - ON IEC Status ErrBoard5.stVal: 0 - FALSE

    0 - OFF 1 - TRUE

    No. Information

    188 Error Board 6 (Error Board 6) 1 0

    CALH1.ErrBoard6.stVal 1 0

    device annunciation: 1 - ON IEC Status ErrBoard6.stVal: 0 - FALSE

    0 - OFF 1 - TRUE

    No. Information

    189 Error Board 7 (Error Board 7) 1 0

    CALH1.ErrBoard7.stVal 1 0

    device annunciation: 1 - ON IEC Status ErrBoard7.stVal: 0 - FALSE

    0 - OFF 1 - TRUE

  • 7/31/2019 7SJ61 64 Ingles

    66/178

    Mapping

    3.2 Oscillographic Fault Records (RDRE1)

    66 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    3.2 Oscillographic Fault Records (RDRE1)

    RDRE1.Mod

    RDRE1.Health

    RDRE1.RcdMade

    No. Information

    55 Reset Device (Reset Device) x

    RDRE1.Mod.stVal 1

    device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON

    0 - OFF 2 - BLOCKED

    x - irrelevant 3 - TEST

    4 - TEST/BLOCKED

    5 - OFF

    No. Information

    51 Device is Operational and Protecting (Device OK) 0 1

    RDRE1.Health.stVal 3 1

    device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK

    0 - OFF 2 - WARNING

    3 - ALARM

    No. Information

    30053 Fault recording is running (Fault rec. run.) 0 1

    RDRE1.RcdMade.stVal 1 0

    device annunciation: 1 - ON IEC Status RcdMade.stVal: 0 - FALSE

    0 - OFF 1 - TRUE(Recording complete)

  • 7/31/2019 7SJ61 64 Ingles

    67/178

    Mapping

    3.2 Oscillographic Fault Records (RDRE1)

    67SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    RDRE1.FltNum

    RDRE1.GriFltNum

    RDRE1.RcdStr

    No. Information Value

    302 Fault Event (Fault Event) RDRE1.FltNum.stVal Present fault number

    No. Information Value

    301 Power System fault (Pow.Sys.Flt.) RDRE1.GriFltNum.stVal Network fault number

    No. Information

    30053 Fault recording is running (Fault rec. run.) 0 1

    RDRE1.RcdStr.stVal 0 1

    device annunciation: 1 - ON IEC Status RcdStr.stVal: 0 - FALSE

    0 - OFF 1 - TRUE

  • 7/31/2019 7SJ61 64 Ingles

    68/178

    Mapping

    3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

    68 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

    3.3.1 Overcurrent Protection 50, 51 PH (PTOC6, PTOC7, PTOC1, PTOC18)

    PTOC6.Mod

    PTOC6.Health

    PTOC6.Str

    No. Information

    1753 50/51 O/C is ACTIVE (50/51 PH ACT) x x x x x

    1752 50/51 O/C is BLOCKED (50/51 PH BLK) x x x 1 0

    1751 50/51 O/C switched OFF (50/51 PH OFF) 1 x 0 0 0

    50-1 PICKUP (P1204) = x 1 0 0 0

    Frequency range is exceeded x x 1 x 0

    PTOC6.Mod.stVal 5 5 2 2 1

    device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON

    0 - OFF / FALSE 2 - BLOCKED

    x - irrelevant 3 - TEST

    4 - TEST/BLOCKED

    5 - OFF

    No. Information

    51 Device is Operational and Protecting (Device OK) 0 1

    PTOC6.Health.stVal 3 1

    device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK

    0 - OFF 2 - WARNING

    3 - ALARM

    No. Information

    1810 50-1 picked up (50-1 picked up) 0 1

    PTOC6.Str.general 0 1

    device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE

    0 - OFF 1 - TRUE

  • 7/31/2019 7SJ61 64 Ingles

    69/178

    Mapping

    3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

    69SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    PTOC6.Op

    PTOC6.ChgSet

    PTOC7.Mod

    PTOC7.Health

    No. Information

    1815 50-1 TRIP (50-1 TRIP) 0 1

    PTOC6.Op.general 0 1

    device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE

    0 - OFF 1 - TRUE

    No. Information

    1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1

    PTOC6.ChgSet.stVal 0 1

    device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE

    0 - OFF 1 - TRUE

    No. Information

    1753 50/51 O/C is ACTIVE (50/51 PH ACT) x x x x x

    1752 50/51 O/C is BLOCKED (50/51 PH BLK) x x x 1 0

    1751 50/51 O/C switched OFF (50/51 PH OFF) 1 x 0 0 0

    50-2 PICKUP (P1202) = x 1 0 0 0

    Frequency range is exceeded x x 1 x 0

    PTOC7.Mod.stVal 5 5 2 2 1

    device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON

    0 - OFF / FALSE 2 - BLOCKED

    x - irrelevant 3 - TEST

    4 - TEST/BLOCKED

    5 - OFF

    No. Information

    51 Device is Operational and Protecting (Device OK) 0 1

    PTOC7.Health.stVal 3 1

    device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK

    0 - OFF 2 - WARNING

    3 - ALARM

  • 7/31/2019 7SJ61 64 Ingles

    70/178

    Mapping

    3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

    70 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    PTOC7.Str

    PTOC7.Op

    PTOC7.ChgSet

    PTOC1.Mod

    No. Information

    1800 50-2 picked up (50-2 picked up) 0 1

    PTOC7.Str.general 0 1

    device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE

    0 - OFF 1 - TRUE

    No. Information

    1805 50-2 TRIP (50-2 TRIP) 0 1

    PTOC7.Op.general 0 1

    device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE

    0 - OFF 1 - TRUE

    No. Information

    1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1

    PTOC7.ChgSet.stVal 0 1

    device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE0 - OFF 1 - TRUE

    No. Information

    1753 50/51 O/C is ACTIVE (50/51 PH ACT) x x x x x

    1752 50/51 O/C is BLOCKED (50/51 PH BLK) x x x 1 0

    1751 50/51 O/C switched OFF (50/51 PH OFF) 1 x 0 0 0

    51 PICKUP (P1207) = x 1 0 0 0

    Frequency range is exceeded x x 1 x 0

    PTOC1.Mod.stVal 5 5 2 2 1

    device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON

    0 - OFF / FALSE 2 - BLOCKED

    x - irrelevant 3 - TEST

    4 - TEST/BLOCKED

    5 - OFF

  • 7/31/2019 7SJ61 64 Ingles

    71/178

    Mapping

    3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

    71SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    PTOC1.Health

    PTOC1.Str

    PTOC1.Op

    PTOC1.ChgSet

    No. Information

    51 Device is Operational and Protecting (Device OK) 0 1

    PTOC1.Health.stVal 3 1

    device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK

    0 - OFF 2 - WARNING

    3 - ALARM

    No. Information

    1820 51 picked up (51 picked up) 0 1

    PTOC1.Str.general 0 1

    device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE

    0 - OFF 1 - TRUE

    No. Information

    1825 51 TRIP (51 TRIP) 0 1

    PTOC1.Op.general 0 1

    device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE

    0 - OFF 1 - TRUE

    No. Information

    1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1

    PTOC1.ChgSet.stVal 0 1

    device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE

    0 - OFF 1 - TRUE

  • 7/31/2019 7SJ61 64 Ingles

    72/178

    Mapping

    3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

    72 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    PTOC18.Mod

    PTOC18.Health

    PTOC18.Str

    No. Information

    1753 50/51 O/C is ACTIVE (50/51 PH ACT) x x x x x

    1752 50/51 O/C is BLOCKED (50/51 PH BLK) x x x 1 0

    1751 50/51 O/C switched OFF (50/51 PH OFF) 1 x 0 0 0

    50-3 PICKUP(P1217) = x 1 0 0 0

    Frequency range is exceeded x x 1 x 0

    PTOC18.Mod.stVal 5 5 2 2 1

    device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON

    0 - OFF / FALSE 2 - BLOCKED

    x - irrelevant 3 - TEST

    4 - TEST/BLOCKED5 - OFF

    No. Information

    51 Device is Operational and Protecting (Device OK) 0 1

    PTOC18.Health.stVal 3 1

    device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK

    0 - OFF 2 - WARNING

    3 - ALARM

    No. Information

    1767 50-3 picked up (50-3 picked up) 0 1

    PTOC18.Str.general 0 1

    device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE

    0 - OFF 1 - TRUE

  • 7/31/2019 7SJ61 64 Ingles

    73/178

    Mapping

    3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

    73SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    PTOC18.Op

    PTOC18.ChgSet

    No. Information

    1769 50-3 TRIP (50-3 TRIP) 0 1

    PTOC18.Op.general 0 1

    device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE

    0 - OFF 1 - TRUE

    No. Information

    1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1

    PTOC18.ChgSet.stVal 0 1

    device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE

    0 - OFF 1 - TRUE

  • 7/31/2019 7SJ61 64 Ingles

    74/178

    Mapping

    3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

    74 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXITC53000-G1140-C211-4, Edition 03.2010

    3.3.2 Overcurrent Protection 50N, 51N (PTOC8, PTOC9, PTOC2)

    PTOC8.Mod

    PTOC8.Health

    PTOC8.Str

    No. Information

    7158 50N/51N is ACTIVE (50N/51N ACT) x x x x x

    7157 50N/51N is BLOCKED (50N/51N BLK) x x x 1 0

    7156 50N/51N is OFF (50N/51N OFF) 1 x 0 0 0

    50N-1 PICKUP (P1304) = x 1 0 0 0

    Frequency range is exceeded x x 1 x 0

    PTOC8.Mod.stVal 5 5 2 2 1

    device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON

    0 - OFF