aal 31m catalogue

Upload: rajesh-malhotra

Post on 05-Jul-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/15/2019 AAL 31M Catalogue

    1/2

    Green Power

    These systems behave like a linear load oninput supply and restrict input harmonics tominimum, therefore, do not pollute theelectrical environment unlike conventionalUPS systems.

    Almost unity input power factor and sinusoidal

    input current enables UPS operation withalmost same capacity generator. This is notpossible with the conventional UPS systems,where the generator has to be over sized toalmost twice the capacity of the UPS.

    Features

    Wider Input Voltage Range

    High Frequency PWM Inverter Using IGBT

    Computer Interface

    Auto Retransfer External Battery Rack for Longer Backup

    Software for monitoring, Control and autoshutdown

    SNMP for remote monitoring

    Inbuilt Isolation Transformer 

     AAL 31/M SERIES3 Phase Input - 1Phase Output

    True On-Line UPS System

    BUILT TO PERFECTION

    ®

  • 8/15/2019 AAL 31M Catalogue

    2/2

    Capacity

    Input

    Output

    Efficiency

    Battery

    Transfer Time

    Indicator 

    Audible Alarm

    Dimension

    Weight

    Environment

    Interface

    VA/W 10000VA / 7000W 15000VA / 10500W 20000VA / 14000W

    Voltage Range 340 - 460 VAC

    Frequency Range 46~54Hz / 56~64Hz

    Phase Three phase with ground

    Current THDI 15%

    Power Factor 0.98

    Generator Input Compatible

    Voltage 208 / 220 / 230 / 240VAC

    Voltage Regulation ±1%

    Frequency 46 ~ 54Hz / 56-64Hz(Synchronized Range)

    Frequency 50 / 60 Hz ± 0.1Hz(Battery Mode)

    Current Crest Ratio 3:1

    Harmonic Distortion 2% THD (Linear Load)

    6% THD (Non-Linear Load)

    Output Waveform Pure Sine Wave

    Outlet Terminal Block

    Overload Capacity 125% for 10 Sec., & 130% for 60 Sec., in main mode

    Inverter Mode >93%

    No. of Batteries per set 16

    Rated Battery Voltage 192Vdc

     AC to DC Zero

    Inverter to bypass 5ms (Typical)

    LED Version Load Level / Battery Level / Battery Mode / AC Mode / Bypass Mode / Fault

    LCD Version Load / Battery / Input / Output / Operating Mode Information

    Battery Mode Sounding every 4 Secs.

    Low Battery Sounding every Sec.

    Overload Sounding twice every Sec.

    Fault Continuously Sounding

    Tower Case 740×300×700 740×300×700 800×400×1180(D×W×H)mm

    Tower Case (kgs) 135 135 170

    Operating Environment 0-40C

    Relative Humidity 20-95% (Non Condensing)

    Noise Level