  • ABB| Slide 1

    Power Product Utility SeminarHigh Voltage Gas Insulated Switchgear.

    Mukesh Sharma, Projects / Engineering Manager, July 2013.

    July 15, 2013

  • ABB| Slide 2

    What is Gas Insulated Switchgear (GIS)?

    Benefits of Gas Insulated Switchgear.

    Additional advantage with ABB GIS.

    ABB High Voltage Gas Insulated Switchgear portfolio.

    Integrated Gas Insulated Switchgear solution.

    Local capability and references.

    Topics

    July 15, 2013

  • ABB| Slide 3

    What is Gas Insulated Switchgear (GIS) ?

    July 15, 2013

    GIS is a type of switchgear having usual components of a substation (e.g. busbars, disconnectors, circuit-breakers, earthing switches, instrument transformers, surge arrester) arranged in metal enclosure and insulated with Gas (SF6) at high pressure.

    Equipment are segregated into sufficient independent gas zones to allow the required degree of operational flexibility.

    Usual substation components GIS

  • ABB| Slide 4

    Benefits of Gas Insulated Switchgear

    July 15, 2013

    Low Life Cycle Costs

    High safety level

    Low space requirement

    Low environmental impact

  • ABB| Slide 5

    Life Cycle Costs

    GIS AIS

    Operation & Maintenance(AIS = 1.5 GIS)Installation & Commissioning(AIS = 2 GIS)Engineering & Project Management(AIS = 1.5 GIS)Auxiliary Cables(AIS > GIS)Building, Civil work(GIS = AIS)Space Saving(GIS = 10 to 20 % AIS)Earth levelling, Site preparation,Fence and Road (AIS = 2 to 3 GIS)Earthing, Lighting(AIS = 2 to 3 GIS)Equipment Price(GIS= 1.3 to 1.7 AIS)

    ~35 %

    Investment cost and O&M cost.

    July 15, 2013

  • ABB| Slide 6

    Earthed enclosure (touch proof)

    Viewports for each switch (disconnector and earthing switch)

    Provisions to padlock disconnector and earthing switch.

    Bursting disks.

    Safety

    July 15, 2013

  • ABB| Slide 7

    Additional advantages of ABB GIS

    July 15, 2013

    0.1% per annum SF6 leakage type tested.

    Compact design means lower infrastructure costs and

    lower environmental impact.

    Highest ratings covers future customer increase in

    network demands.

  • ABB| Slide 8

    ELK-36300A

    ELK-144000A

    ELK-044000A

    ABB GIS product portfolioOverview and technical data

    July 15, 2013

    kA

    kV72.5 145 170 245 300 362 1100765550420

    40

    50

    63

    80

    ENK2500A

    ELK-14 compact3150A

    ELK-3 compact5000A

    ELK-45000A

    ELK-55000A

    252

    ELK-04compact3150A

  • ABB| Slide 9

    ELK 04 72.5 170kVDouble Busbar Bay

    July 15, 2013

    1 Busbar side Disconnecting and Earthing switch

    2 Circuit Breaker3 Current Transformer4 Line side Disconnecting and

    Earthing switch5 Voltage Transformer6 Fast Acting Earthing Switch7 Cable Exit

    Control

    Cubicle

    1Barrier Insulator

    2

    4 5

    6

    73

  • ABB| Slide 10

    Switching components

    Circuit Breaker : Mechanical endurance class M2 (10,000 CO)

    Capacitive switching class C2

    Used for 170 kV and up to 63 kA

    Combine Disconnector Earthing Switch :

    Mechanical endurance class M2 (10,000 CO)

    Common moving contact for disconnector and earthing switch, the safest way for interlocking between earthing and disconnecting function (automatic mechanical interlock)

    Fast Acting Earthing Switch :

    With max two full load fault making capacity.

    Access to main current path is possible without opening gas compartment.

    ELK 04, 72.5 170 kV

    July 15, 2013

  • ABB| Slide 11

    ELK-14 compact, 245 kV, 3150 A and 50 kA Double busbar cable bay

    July 15, 2013ELK-14, compact

    ELK-14, standard

    Dimensions reduced by 40% (building

    cost reduction, reduced steel structures)

    Weight reduce by 25% (reduced

    transport & handling cost, reduce

    foundation load)

    SF6-gas reduced by 20% (ready for

    environmental regulations)

    Crane size reduce to 1.5 tonne

  • ABB| Slide 12

    ELK-14 compact, 245 kVLayout =D01 cable exit

    July 15, 2013

  • ABB| Slide 13

    ELK-3 Compact, 420 kV, 5000 A and 63 kA Double Busbar Bay

    July 15, 2013

    Dimensions reduced by 45% (building

    cost reduction, reduced steel

    structures & land acquisition costs)

    Weight reduce by 25% (reduced

    transport & handling cost, reduce

    foundation load)

    SF6-gas reduced by 40% (ready for

    environmental regulations)

    Crane size reduce to 3 tonne

  • ABB| Slide 14

    ELK-3 compact, 420 kV & ELK 14 compact, 245kV.

    Front access to drives : Emergency hand crank operation

    and padlocking at front panel. Single type drive for disconnector and

    earthing switches for simple spare part handling.

    Circuit-breaker emergency operation and supervision unit at front panel.

    Easy access to gas density monitoring and indications.

    Service platform with openings for accessibility to viewports and filling point

    3/75mm contact view ports for visual checks

    Excellent accessibility

    July 15, 2013

    Service platforms

  • ABB| Slide 15

    Based on a typical substation of 7 bays / PO = project order* Shipping time is not shown in above time line.

    Reduction of installation and commissioning time by 60% Significant reduction of cabling works on-site Reduced overall lead time by 25 - 30%

    Order execution and installation, compact GIS.Shipped as a complete factory tested bay

    PO BaseDesign1 month

    Design freeze1.5 months

    Manufacturing6 months

    Installation4.5 months

    ELK-3, 420 kV

    ELK-3 compact, 420 kV

    PO BaseDesign1 month

    Designfreeze1.5 months

    Manufacturing3 months

    Installation2 months

  • ABB| Slide 16

    Switching components

    Circuit Breaker : Mechanical endurance class M2 (10,000 CO)

    Capacitive switching class C2

    Double-motion technology introduced in 1990th

    Disconnector / Earthing Switch :

    Mechanical endurance class M2 (10,000 CO)

    Contains a three-pole operated disconnector to isolate the feeder from the Busbar.

    Fast Acting Earthing Switch :

    Exceeds the requirement : Mechanical endurance class M1 (3000 CO)

    Access to main current path is possible using insulated earthing contacts (10 kV), without opening gas compartment.

    ELK 3, compact

    July 15, 2013

    AnimationDouble-motion

    principle

  • ABB| Slide 17

    Circuit Breaker Operating MechanismExperience with Hydro-Mechanical Spring Drive

    July 15, 2013

    More than 100,000 operating mechanisms successfully in operation

  • ABB| Slide 18

    Circuit Breaker Operating Mechanism

    Energy storage:

    Disk spring: Single spring package stores the energy for multiple close/open operations

    Energy transmission:

    Hydraulic: Smooth damping of the breaker, integrated in the hydraulic system

    In the unlikely event of rupture of one disc within the stack of springs only approx. 8% of the stored energy will be lost.

    Even with three broken springs (Material failure), safe open -Operation is possible.

    Benefits of Hydro-Mechanical Spring Drive (HMB)

    July 15, 2013

  • ABB| Slide 19

    Circuit Breaker Operating MechanismMTBF (Mechanisms Manufactured 2000-2010)

    July 15, 2013

  • ABB| Slide 20

    SF6 Gas Monitoring System

    Data visualization and alarm signalization Remotely via IEC 61850-8-1

    Remotely via embedded web server

    Via local HMI

    Leakage rate estimation analysis

    early leak detection.

    Maintenance planning by calculation of leakage rate. Reduces inspection work

    Reduces maintenance costs

    MSM

    July 15, 2013

  • ABB| Slide 21

    Integrated GIS ApplicationsCustomer success story City of Anchorage, Alaska

    The customer had growing demand for power and required substation to be modest, as the project was in close proximity to a shopping center.

    ABB responded by providing an ELK-04 / 145 kV fully integrated GIS substation that was installed and energized in a few weeks.

    The substation consists of a 4-breaker ring integrated into two 40-foot containers.

    The local control cubicles are also fully integrated inside the containers.

    July 15, 2013

  • ABB| Slide 22

    ABB is locally available!

    GIS Service World wide engagement for your satisfaction

    International and local 24/7/365 emergency hotline

    Locally available factory Certified GIS Engineers and Technicians

    Local service centers fully equipped with tools required for installation and maintenance.

    Local center for marketing and sales support.

    Training for customer personnel available.

  • ABB| Slide 23

    ABB Gas Insulated Switchgear AU GIS Projects since 2006

    Customer Substation Rating GIS Type Design Delivered Installed

    Integral Energy Bella Vista ZS 145kV / 2000A / 40kA 7 Bay Ring Bus 2006

    Integral Energy Springhill TS 145kV / 2500A / 40kA 22 Bay DBB 2008

    Integral Energy Lawson ZS 72kV / 2000A / 40kA 7 Bay SBB 2010

    Integral Energy Mungerie Park ZS

    145kV / 2000A / 40kA 8 Bay SBB 2009

    Integral Energy Camellia TS 145kV / 2500A / 40kA 13 Bay DBB 2012

    Integral Energy Cheriton ZS 145kV / 2000A / 40kA 8 Bay SBB 2011

    Ergon Energy Berserker ZS 72.5kV / 2000A / 40kA 5 Bay SBB 2009

    CitiPower Southbank 72.5kV / 2500A / 40kA 7 Bay Ring Bus 2010

    AGL Bogong 300kV / 630A / 40kA 1 Bay Y Circuit 2009

    Rio Tinto Cape Lambert Substation

    220kV / 2500A / 16kA 5 Bays DBB 2012

    Transgrid Beaconsfield South Substation

    145kV / 3150A / 50kA 22 Bay DBB 2012

  • ABB| Slide 24

    ABB Gas Insulated Switchgear AU GIS Projects since 2006

    Customer Substation Rating GIS Type Design Delivered Installed

    Transgrid Beaconsfield North Substation

    145kV / 3150A / 50kA 22 Bay DBB 2012

    Transgrid Beaconsfield South Substation

    145kV / 3150A / 50kA 4 off Circuits

    SF6 GIL

    2012

    Transgrid Beaconsfield South Substation

    362kV / 1600A / 50kA 2 off Circuits

    SF6/Air GIL

    2012

    Actew AGL Eastlake 145kV / 2500 A/ 40 kA 10 Bay SBB Delivery Aug 2103

    Commence 2013

    Rio Tinto Cape Lambert Substation Extn.

    220kV / 2500A / 16kA 5 Bays DBB Delivery Oct 2103

    Commence 2013

  • ABB| Slide 25

    GIS Technology & ApplicationsOptimal & efficient use of resources

    GIS is a mature technology and offers immense flexibility and benefits to the users.

    All products in the market are not same.

    Service continuity needs careful evaluation.

    New generation of switchgear are compact , environmentally friendly and provide lower infrastructure costs across the whole value chain.

    Ideal for pre-fabricated , pre-tested substation in factory

    Is fully realiasable with the compact generation of switchgear & further enhances the benefits of GIS

    July 15, 2013

  • ABB| Slide 26

    Mukesh S Sharma

    Mukesh S SharmaProjects / Engineering Manager