acb easypact mvs...> conforms to iec 60947- 2 & 3 easypact mvs08 to mvs40 easypact mvs...

92
Catalogue 2018 Low Voltage EasyPact MVS LV power circuit breakers and switch-disconnectors 800 to 4000A

Upload: others

Post on 02-Aug-2020

22 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

Catalogue2018

Low Voltage

EasyPact MVSLV power circuit breakers and switch-disconnectors800 to 4000A

Page 2: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

Performancewithout compromise

Exceptionalreliability,flexibilityand convenience

Quality and safetyyou can trust

Outstanding value for an optimized feature set

Buildings Industry Panelbuilders

Page 3: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

3

EasyPact MVS rangeThe easy choice for reliable performance

> Performance without compromise

> Assured quality and safety you can trust

> Deliver exceptional reliability and flexibility in its class

> Outstanding value for an optimized feature set

> Precision engineered to meet your needs

> Unbeatable value throughout its lifecycle

> Simple to choose and easy to install

Page 4: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

Choose the leader> 800 to 4000A ratings

> Breaking capacity: 50 & 65kA

> Suitable for 690V applications

> Complete selectivity with Ics=Icu=Icw (1 s)

> Intelligent ET range of trip system with display

> Fully protected neutral on 4 pole breakers

> Common accessories for complete range

> Conforms to IEC 60947- 2 & 3

Page 5: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

EasyPact MVS08 to MVS40

EasyPact MVSBenefits for every customer

5

Panel builders/contractors

End Users Designers

> Single frame size from 800 to 4000A with identical door cut-outs

> Suitable for copper & Aluminium termination with a single pole pitch of 115 mm

> Terminal orientation can be converted from horizontal to vertical and vice-versa at workshop

> Direct mounting Door frames (escutcheon) without drilling any holes

>release, shunt release & closing coil for complete range

> Conversion of manual operated breaker in to electrical operated, with

EasyPact MVS with single frame size,common accessories

swith boards.

> Conforms to IEC60947-2 for breakers & IEC60947-3 for disconnectors

> Designed and manufactured using advanced manufacturing methods to

the needs of each project.

> Continuous rated coils helps in simple interlocking schemes

>documentation to reduce design time.

> EasyPact MVS respects the environment throughout their life cycle

EasyPact MVS is designed to meet the

design phase

> Moulded case design ensures high endurance without maintenance

> Intelligent ET range of trip system with thermal memory and display for measurements.

> Overload run alarm & individual LED

> lcu=lcs=lcw(1sec)=50kA & 65kA ensures complete selectivity

> Inbuilt safety shutter & interlocks

> Designed to provide utmost user safety during installation, during use, and while under maintenance.

> All 4 pole breakers are with fully rated neutral and protected with adjustable settings at OFF – 50%-100%

EasyPact MVS answers even to the most stringent application with most reliable distribution systems assuring continuity of service

Page 6: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

The Key values

90%

100%

30%

of applications are

covered

Commitment to

quality

Reduce stock by up to

The performance you need

With the quality you demand

At a cost-effective investment

EasyPact MVS provides the ideal level of capability for your installation from 800 to 4000 A.

Designed and manufactured by Schenider Electric using advanced manufacturing methods and premium mate-rials.

Pay for what you need: Get outstanding durability with the features you need, with the benefit of easy to order and stock.

6

Page 7: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

Gain peace ofmind and optimised cost for every installation

Page 8: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

Green Premium, stamping the most eco-friendly products of the industry

With Green Premium, Schneider Electric commits to be transparent disclosing extensive and reliable information on environmental impacts of its products:

Green Premium is the only label allowing you to develop effectively an environmental policy and to promote it, while preserving your business efficiency.

It guarantees compliance with the most up-to-date environmental regulations, but it is more than this.

With Green Premium eco-mark, Schneider Electric helps you:

the solutions you offer

substances and chemical components

to certify eco-design of your solutions

while ensuring optimized recycling.

Discover what we mean by green …. and

CHECK a PRODUCT!

RoHSSchneider Electric applies RoHS requirements to all its products and worldwide, even for

are available for all products involved.

REAChSchneider Electric applies REACh regulation worldwide, and releases all information about presence of Substances of Very High-Concern (SVHC) in its products.

PEP: Product Environmental ProfileFor all its products, Schneider Electric publishes the most complete set of environmental data, including carbon footprint and energy consumption for each of the life cycle phases, in compliance with ISO 14025 PEPecopassport program.

EoLI: End of Life InstructionsAvailable at a click, these documents provide:

recycling operations

Over 75% of Schneider Electric manufactured products awarded Green Premium eco-mark

Page 9: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

EasyPact MVS General contents

Functionsand characteristics A-1

Installationrecommendations B-1

Dimensionsand connection C-1

Electrical diagrams D-1

Additionalcharacteristics E-1

Catalogue numbers and order form F-1

Page 10: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

Functions and characteristics

Page 11: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-1

Functions and characteristics

General overview A-2Detailed contents A-2

Circuit breakers and switch-disconnectors A-4MVS08 to MVS40 A-4

Identifying ET range of trip system A-6

Overview of functions A-8 ET trip system A-8ETA trip system A-10ETV trip system A-12

ET range of trip system A-14 Accessories and test equipment A-14

Connections A-15 Overview of solutions and accessories A-15

Locking A-19 On the device A-19On the chassis A-20

Indication contacts A-21

Remote operation A-22 Remote ON / OFF A-22Remote tripping A-24

Source-changeover systems A-25Mechanical interlocking A-25

Accessories A-26

Installation recommendations B-1Dimensions and connection C-1Electrical diagrams D-1Additional characteristics E-1Catalogue numbers and order form F-1

EasyPact MVS

Page 12: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-2

Functionsand characteristics

General overviewDetailed contents

This overview describes all the functions offered byEasyPact MVS devices.

Circuit breakers and switch-disconnectors page A-4 b Ratings: v EasyPact MVS 800 to 4000 A b Circuit breakers type N, H b Switch-disconnectors type NA, HA b 3 or 4 poles b

ET trip system page A-8 b 2I basic protection b 5S selective protection b 6G selective + earth-fault protection b Standard long-time rating plug: v

ETA trip system with current measurement page A-10 b 2I basic protection b 5S selective protection b 6G selective + earth-fault protection b Standard long-time rating plug: v b

ETV trip system with voltage measurement page A-12 b 2I basic protection b 5S selective protection b 6G selective + earth-fault protection b Standard long-time rating plug: v b

Connections page A-15 b Rear connection: v Horizontal v Vertical b Optional accessories: v Interphase barriers v Safety shutters and shutter locking blocks

Locking page A-18 b Pushbutton locking by padlockable transparent cover

b OFF-position locking by keylock b Chassis locking in disconnected position by keylock

b Chassis locking in connected, disconnected and test positions

b Door interlock (inhibits door opening with breaker in ‘connected’ or ‘test’ position

CP

B10

0000

CD

B50

0000

CD

B50

0001

CD

B50

0002

short time

long timealarm

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

ET6G Trip System

alarm

Ir

(s)

long time

instantaneous

ET2I Trip System

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

.3instantaneous

I i

ET6G Trip System

alarm

Ir

on off off

(s)

(s)

long time

short time instantaneous

ET5S Trip System

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

ground fault

setting

4

test

.4.5.6

.7 .8 .9.95.981

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

BC

D E FGH

I

Ig

Aon I

2t

.2

.3.4 .4

.1

.2.3

.10off

tg(s)

.3instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

on off

on off off

(s)

(s)

(s)

long time

short time instantaneous

ET6G Trip System

DB

1011

09

DB

1011

10

E46

459

DB

1011

49

Page 13: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-3

Indication contacts page A-20 b Standard: v ON/OFF indication (OF) v “Fault” trip indication (SDE) b Optional: v Additional ON/OFF indication (OF) v Ready-to-close contact (PF) v Carriage switches for connected (CE) disconnected (CD) and test (CT) positions

Remote operation page A-21 b Remote ON/OFF: v Gear motor v XF closing or MX opening voltage releases

b Remote tripping function: v MN voltage release - Standard - Adjustable or non-adjustable

delay

Accessories page A-25 b b Operation counter b Escutcheon (Door sealing frame) b Transparent cover for escutcheon b Escutcheon blanking plate

Source-changeover systems page A-24 b Mechanical interlocking using cables: v Interlocking between two devices v Interlocking between three devices

PB

1043

54A

40C

PB

1000

03C

PB

1000

15C

PB

1000

16

DB

1011

13

DB

1011

14

E46

438

DB

1011

12

CD

B50

0053

E46

669

E46

668

DB

1011

15

Page 14: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-4

Functionsand characteristics

Circuit breakersand switch-disconnectorsMVS08 to MVS40

Common characteristicsNumber of poles 3/4Rated insulation voltage (V) Ui 1000Impulse withstand voltage (kV) Uimp 12Rated operational voltage (V AC 50/60 Hz) Ue 690Suitability for isolation IEC 60947-2 YesDegree of pollution IEC 60664-1 4

Basic circuit-breakerCircuit-breaker as per IEC 60947-2Rated current (A) In at 40°C(1)

Rating of 4th pole (A)Sensor ratings (A)Type of circuit breakerUltimate breaking capacity (kA rms) Icu 220...440VV AC 50/60 Hz 690 VRated service breaking capacity (kA rms) Ics % IcuUtilisation categoryRated short-time withstand current (kA rms) Icw 1s 220...440 VV AC 50/60 Hz 690V

3s 440/690VRated making capacity (kA peak) Icm 220...440 VV AC 50/60 Hz 690 V

Closing time (ms)

Switch-disconnector as per IEC60947-3 and Annex AType of switch-disconnectorOperational current AC23ARated making capacity (kA peak) IcmRated short-time withstand current (kA rms) Icw 1s

3s

Maintenance/Connection/InstallationService life Mechanical with maintenance

without maintenanceElectrical without maintenance 440 V

690 VConnection Horizontal

VerticalDimensions (mm) Draw-out 3P

4P3P4P

Draw-out 3P/4P3P/4P

CP

B10

0000

CP

B10

0014

(1)

Page 15: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-5

MVS08 MVS10 MVS12 MVS16 MVS20 MVS25 MVS32 MVS40

800 1000 1250 1600 2000 2500 3200 4000800 1000 1250 1600 2000 2500 3200 4000800 1000 1250 1600 2000 2500 3200 4000N H N H N H N H N H N H N H N H50 65 50 65 50 65 50 65 50 65 50 65 50 65 55 6542 50 42 50 42 50 42 50 42 50 42 50 42 50 42 50100% 100% 100% 100% 100% 100% 100% 100%B B B B B B B B50 65 50 65 50 65 50 65 50 65 50 65 50 65 55 6542 50 42 50 42 50 42 50 42 50 42 50 42 50 42 5025 36 25 36 25 36 25 36 25 36 25 36 25 36 30 36105 143 105 143 105 143 105 143 105 143 105 143 105 143 121 14388 105 88 105 88 105 88 105 88 105 88 105 88 105 88 10525 25 25 25 25 25 25 25<70 <70 <70 <70 <70 <70 <70 <70

MVS08 MVS10 MVS12 MVS16 MVS20 MVS25 MVS32 MVS40NA HA NA HA NA HA NA HA NA HA NA HA NA HA NA HA800 1000 1250 1600 2000 2500 3200 4000105 143 105 143 105 143 105 143 105 143 105 143 105 143 121 14350 65 50 65 50 65 50 65 50 65 50 65 50 65 55 6525 36 25 36 25 36 25 36 25 36 25 36 25 36 30 36

20 20 20 20 20 20 20 2010 10 10 10 10 10 10 106000 6000 6000 6000 6000 5000 5000 50004000 4000 4000 4000 4000 2500 2500 2500YesYes

70/85 90/12040/50 60/80

Page 16: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-6

Functionsand characteristics

Identifying ET range of trip system

EasyPact MVS circuit breakers equipped with ET range of trip system are designed to protect power circuit and connected loads.Measurement of current and voltage helps users to maintain continuity of service and optimize installation.

DependabilityIntegration of protection functions in an ASIC electronic component used in all trip units guarantees a high degree of reliability and immunity to conducted or radiated disturbances.On ET range, measurement functions are managed by an independent microprocessor. Protection functions are independent of measurement functions, ensure system protection even at very low load currents.

AccessoriesCertain functions require the addition of trip unit accessories, described on page A-14.

DB

1011

16

CP

B10

0011

DB

1011

17D

B10

1117

Trip unit name codesType of protection

b 2I for basic protection b 5S for selective protection b 6G for selective + earth-fault protection

Type of measurement b ET for basic b ETA for “Current” b ETV for “Current” and “Voltage”

ET2I: basic protection

Protection:

ET5S: selective protection

Protection:

ET6G: selective + earth-fault protection

DB

1011

18

Protection:

Page 17: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-7

Protection and measurement functionsET ETA ETV

b Fault indications b Settings in amperes and in seconds

b I1, I2, I3, IN, Iearth-fault,

these measurements: v Fault indications v Settings in amperes and in seconds

b Incorporates all the rms measurements of ETA trip unit, plus voltage readings:

v Calculates the current demand value v “Quickview” function for the automatic cyclical display of the most useful values

2I

CD

B50

0000

short time

long timealarm

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

ET6G Trip System

alarm

Ir

(s)

long time

instantaneous

ET2I Trip System 2IC

DB

5000

28

long timealarm

ground fault

4

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x In

3

6 8 101215

off2

instantaneousI i

alarm

off

(s)

long time

instantaneous

ETA2I

Ir

2I

long timealarm

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x In

3

6 8 101215

off2

instantaneousI i

alarm

Ir

test

off

(s)

long time

instantaneous

2I

CD

B50

0035

5S

CD

B50

0001

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

.3instantaneous

I i

ET6G Trip System

alarm

Ir

on off off

(s)

(s)

long time

short time instantaneous

ET5S Trip System 5S

CD

B50

0029

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

ground fault

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

.3instantaneous

I i

alarm

Ir

on off off

(s)

(s)

long time

short time instantaneous

ETA5S 5S

CD

B50

0030

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

.3instantaneous

I i

alarm

Ir

on off off

(s)

(s)

long time

short time instantaneous

ETV5S

6G

CD

B50

0002

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

ground fault

setting

4

test

.4.5.6

.7 .8 .9.95.981

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

BC

D E FGH

I

Ig

Aon I

2t

.2

.3.4 .4

.1

.2.3

.10off

tg(s)

.3instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

on off

on off off

(s)

(s)

(s)

long time

short time instantaneous

ET6G Trip System 6G

CD

B50

0003

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

ground fault

setting

4

test

.4.5.6

.7 .8 .9.95.981

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

BC

D E FGH

I

Ig

Aon I

2t

.2

.3.4 .4

.1

.2.3

.10off

tg(s)

.3instantaneous

I i

alarm

Ir

ground fault

test

on off

on off off

(s)

(s)

(s)

long time

short time instantaneous

6G

CD

B50

0004

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

ground fault

setting

4

test

.4.5.6

.7 .8 .9.95.981

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

BC

D E FGH

I

Ig

Aon I

2t

.2

.3.4 .4

.1

.2.3

.10off

tg(s)

.3instantaneous

I i

alarm

Ir

ground fault

test

on off

on off off

(s)

(s)

(s)

long time

short time instantaneous

Page 18: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-8

Functionsand characteristics

Overview of functionsET trip system

ProtectionProtection thresholds and delays are set using the adjustment dials.Overload protectionTrue rms long-time protection.Protects cables (phase and neutral) against overloadsThermal memory(1): thermal image before and after tripping.Short-time protection

b The short-time protection function protects the distribution system against impedant short-circuits

b The short-time tripping delay can be used to ensure discrimination with downstream circuit breaker

b The I2t ON and I2t OFF options enhance discrimination with a downstream protection devices

b Use of I2t curves with short-time protection: v I2t OFF selected: the protection function implements a constant time curve v I2t ON selected: the protection function implements an I2t inverse-time curve up to 10 lr. Above 10 lr, the time curve is constant

Earth-fault protection on ET6G trip systemResidual earth fault protection.Selection of I2t type (ON or OFF) for delay.A ground fault in the protection conductors can provoke local temperature rise at the site of the fault or in the conductors. The purpose of the ground-fault protection function is to eliminate this type of fault.Type DescriptionResidual b The function determines the zero-phase sequence current, i.e. the

vectorial sum of the phase and neutral currents b It detects faults downstream of the circuit breaker

Instantaneous protectionThe Instantaneous-protection function protects the distribution system against solid short-circuits. Contrary to the short-time protection function, the tripping delay for instantaneous protection is not adjustable. The tripping order is sent to the circuit

20 milliseconds.Neutral protectionOn three-pole circuit breakers, neutral protection is not possible.On four-pole circuit breakers, neutral protection may be set using a three-positionswitch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutralprotection at Ir (4P 4d).Zone selective interlocking (ZSI)A ZSI(2) terminal block may be used to interconnect a number of control units to provide total discrimination for short-time and earth-fault protection, without a delay before tripping.

Overload alarm

Fault indicationsLEDs indicate the type of fault:

b Overload (long-time protection Ir) b Short-circuit (short-time Isd or instantaneous li protection) b Earth fault (Ig) b Internal fault (Ap)

Battery powerThe fault indicating LEDs are powered by an in-built battery. The fault indication LEDs remain on until the test/reset button is pressed.

TestA hand-held test kit may be connected to the test connector on the front to check circuit-breaker operation. For ET6G trip unit, the operation of earth-fault protection can be checked by pressing the test button located above the test connector.

Note:

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

ground fault

setting

4

test

.4.5.6

.7 .8 .9.95.981

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

BC

D E FGH

I

Ig

Aon I

2t

.2

.3.4 .4

.1

.2.3

.10off

tg(s)

.3instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

on off

on off off

(s)

(s)

(s)

long time

short time instantaneous

ET6G Trip System

CD

B50

0002

12345678910

7

(1)

(2)

ET trip unit protect power circuits, under overload & short-circuit conditions. They are equipped with individual fault trip indication LEDs. ET6G provides earth-fault protection.

Page 19: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-9

Protection ET2ILong time ET2I

DB

1011

26

Current setting (A) Ir 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1

Time setting tr (s) 0.5 1 2 4 8 12 16 20 24Time delay (s) Accuracy: 0 to -30 % 12.5 25 50 100 200 300 400 500 600

Accuracy: 0 to -20 % 0.7(1) 1 2 4 8 12 16 20 24Accuracy: 0 to -20 % 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6

Thermal memory 20 minutes before and after tripping(1) (2)InstantaneousPick-up (A) Isd 1.5 2 2.5 3 4 5 6 8 10Accuracy: ±10 %Time delay

Protection ET5S/ET6GLong time ET5S/ET6G

DB

1011

27

Current setting (A) Ir 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1

Time setting tr (s) 0.5 1 2 4 8 12 16 20 24Time delay (s) Accuracy: 0 to -30 % 12.5 25 50 100 200 300 400 500 600

Accuracy: 0 to -20 % 0.7(1) 1 2 4 8 12 16 20 24Accuracy: 0 to -20 % 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6

Thermal memory 20 minutes before and after tripping(1) (2)Short timePick-up (A) Isd 1.5 2 2.5 3 4 5 6 8 10Accuracy: ±10 %Time setting tsd (s) Settings I2t Off 0 0.1 0.2 0.3 0.4

I2t On - 0.1 0.2 0.3 0.4tsd 20 80 140 230 350

(I2t Off or I2t On) tsd 80 140 200 320 500InstantaneousPick-up (A) Ii 2 3 4 6 8 10 12 15 offAccuracy: ±10 %Time delay

Earth fault ET6G

DB

1011

28

Pick-up (A) Ig A B C D E F G H JAccuracy: ±10 % In y 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

400 A < In y 1000 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1In u 1250 A 500 640 720 800 880 960 1040 1120 1200

Time setting tg (s) Settings I2t Off 0 0.1 0.2 0.3 0.4I2t On - 0.1 0.2 0.3 0.4

Time delay (ms) tg 20 80 140 230 350at In or 1200 A (I2t Off or I2t On) tg 80 140 200 320 500Note:

Page 20: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-10

Functionsand characteristics

Overview of functionsETA trip system

“Ammeter” measurementsETA trip units measure the true (rms) value of currents.They provide continuous current measurements from 0.2 to 1.2 In and are accurateto within 1.5 % (including the sensors).

displays the I1, I2, I3, IN, Ig

successively pressing the navigation button.

changes linearly from 4 % to 1.5 %.

ProtectionProtection thresholds and delays are set using the adjustment dials.Overload protectionTrue rms long-time protection.Protects cables (phase and neutral) against overloadsThermal memory(1): thermal image before and after tripping.Short-time protection

b The short-time protection function protects the distribution system against impedant short-circuits

b The short-time tripping delay can be used to ensure discrimination with downstream circuit breaker

b The I2t ON and I2t OFF options enhance discrimination with a downstream protection devices

b Use of I2t curves with short-time protection: v I2t OFF selected: the protection function implements a constant time curve v I2t ON selected: the protection function implements an I2t inverse-time curve up to 10 lr. Above 10 lr, the time curve is constant

Earth-fault protection on ETA6G trip systemResidual earth fault protection.Selection of I2t type (ON or OFF) for delay.A ground fault in the protection conductors can provoke local temperature rise at the site of the fault or in the conductors. The purpose of the ground-fault protection function is to eliminate this type of fault.Type DescriptionResidual b The function determines the zero-phase sequence current, i.e. the

vectorial sum of the phase and neutral currents b It detects faults downstream of the circuit breaker

Instantaneous protectionThe Instantaneous-protection function protects the distribution system against solid short-circuits. Contrary to the short-time protection function, the tripping delay for instantaneous protection is not adjustable. The tripping order is sent to the circuit

20 milliseconds.Neutral protectionOn three-pole circuit breakers, neutral protection is not possible.On four-pole circuit breakers, neutral protection may be set using a three-positionswitch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutralprotection at Ir (4P 4d).Zone selective interlocking (ZSI)A ZSI(2) terminal block may be used to interconnect a number of control units to provide total discrimination for short-time and earth-fault protection, without a delay before tripping.

Overload alarm

Fault indicationsLEDs indicate the type of fault:

b Overload (long-time protection Ir) b Short-circuit (short-time Isd or instantaneous li protection) b Earth fault (Ig) b Internal fault (Ap)

Battery powerThe fault indicating LEDs are powered by an in-built battery. The fault indication LEDs remain on until the test/reset button is pressed.

TestA hand-held test kit may be connected to the test connector on the front to check circuit-breaker operation. For ETA6G trip unit, the operation of earth-fault protection can be checked by pressing the test button located above the test connector.

CD

B50

0003

ETA trip units include all functions offered by ET trip unit. In addition, they also offer measurements, display

1234567891011121314

Note:

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

ground fault

setting

4

test

.4.5.6

.7 .8 .9.95.981

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

BC

D E FGH

I

Ig

Aon I

2t

.2

.3.4 .4

.1

.2.3

.10off

tg(s)

.3instantaneous

I i

alarm

Ir

ground fault

test

on off

on off off

(s)

(s)

(s)

long time

short time instantaneous

7

1314

(1)

(2)

Page 21: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-11

Protection ETA2ILong time ETA2I

DB

1011

26

Current setting (A) Ir 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1

Time setting tr (s) 0.5 1 2 4 8 12 16 20 24Time delay (s) Accuracy: 0 to -30 % 12.5 25 50 100 200 300 400 500 600

Accuracy: 0 to -20 % 0.7(1) 1 2 4 8 12 16 20 24Accuracy: 0 to -20 % 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6

Thermal memory 20 minutes before and after tripping(1) (2)InstantaneousPick-up (A) Isd 1.5 2 2.5 3 4 5 6 8 10Accuracy: ±10 %Time delay

Protection ETA5S/ETA6GLong time ETA5S/ETA6G

DB

1011

27

Current setting (A) Ir 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1

Time setting tr (s) 0.5 1 2 4 8 12 16 20 24Time delay (s) Accuracy: 0 to -30 % 12.5 25 50 100 200 300 400 500 600

Accuracy: 0 to -20 % 0.7(1) 1 2 4 8 12 16 20 24Accuracy: 0 to -20 % 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6

Thermal memory 20 minutes before and after tripping(1) (2)Short timePick-up (A) Isd 1.5 2 2.5 3 4 5 6 8 10Accuracy: ±10 %Time setting tsd (s) Settings I2t Off 0 0.1 0.2 0.3 0.4

I2t On - 0.1 0.2 0.3 0.4tsd 20 80 140 230 350

(I2t Off or I2t On) tsd 80 140 200 320 500InstantaneousPick-up (A) Ii 2 3 4 6 8 10 12 15 offAccuracy: ±10 %Time delay

Earth fault ETA6G

DB

1011

28

Pick-up (A) Ig A B C D E F G H JAccuracy: ±10 % In y 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

400 A < In y 1000 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1In u 1250 A 500 640 720 800 880 960 1040 1120 1200

Time setting tg (s) Settings I2t Off 0 0.1 0.2 0.3 0.4I2t On - 0.1 0.2 0.3 0.4

Time delay (ms) tg 20 80 140 230 350at In or 1200 A (I2t Off or I2t On) tg 80 140 200 320 500

Ammeter ETA2I/ETA5S/ETA6GType of measurements Range AccuracyInstantaneous currents I1, I2, I3, In ± 1.5 %

Ig (ETA6G) ± 10 %I1, I2, I3, In ± 1.5 %

Note:

Page 22: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-12

Functionsand characteristics

Overview of functionsETV trip system

“Voltage meter” measurementsIn addition to the ammeter measurements of ETAETV trip units measure and display:

b Current demand b Voltages: phase to phase, phase to neutral, average and unbalanced

The range of measurement is the same as current with ETA, depending of an

ProtectionProtection thresholds and delays are set using the adjustment dials.Overload protectionTrue rms long-time protection.Protects cables (phase and neutral) against overloadsThermal memory(1): thermal image before and after tripping.Short-time protection

b The short-time protection function protects the distribution system against impedant short-circuits

b The short-time tripping delay can be used to ensure discrimination with downstream circuit breaker

b The I2t ON and I2t OFF options enhance discrimination with a downstream protection devices

b Use of I2t curves with short-time protection: v I2t OFF selected: the protection function implements a constant time curve v I2t ON selected: the protection function implements an I2t inverse-time curve up to 10 lr. Above 10 lr, the time curve is constant

Earth-fault protection on ETV6G trip systemResidual or source ground return earth fault protection.Selection of I2t type (ON or OFF) for delay.A ground fault in the protection conductors can provoke local temperature rise at the site of the fault or in the conductors. The purpose of the ground-fault protection function is to eliminate this type of fault.Type DescriptionResidual b The function determines the zero-phase sequence current, i.e. the

vectorial sum of the phase and neutral currents b It detects faults downstream of the circuit breaker

Instantaneous protectionThe Instantaneous-protection function protects the distribution system against solid short-circuits. Contrary to the short-time protection function, the tripping delay for instantaneous protection is not adjustable. The tripping order is sent to the circuit

20 milliseconds.Neutral protectionOn three-pole circuit breakers, neutral protection is not possible.On four-pole circuit breakers, neutral protection may be set using a three-positionswitch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutralprotection at Ir (4P 4d).Zone selective interlocking (ZSI)A ZSI(2) terminal block may be used to interconnect a number of control units to provide total discrimination for short-time and earth-fault protection, without a delay before tripping.

Overload alarm

Fault indicationsLEDs indicate the type of fault:

b Overload (long-time protection Ir) b Short-circuit (short-time Isd or instantaneous li protection) b Earth fault (Ig) b Internal fault (Ap)

Trip historyThe trip history displays the list of the last 10 trips. For each trip, the following indications are recorded and displayed:

b the tripping cause: Ir, Isd, Ii, Ig or Auto-protection (Ap) tripsBattery powerThe fault indicating LEDs are powered by an in-built battery. The fault indication LEDs remain on until the test/reset button is pressed.

TestA hand-held test kit may be connected to the test connector on the front to check circuit-breaker operation. For ETV6G trip unit, the operation of earth-fault protection can be checked by pressing the test button located above the test connector.

ETV trip units include all the functions offered by ETA.In addition, they measure voltage values.They also offer trip history & display tripping cause.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Note:

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

ground fault

setting

4

test

.4.5.6

.7 .8 .9.95.981

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

BC

D E FGH

I

Ig

Aon I

2t

.2

.3.4 .4

.1

.2.3

.10off

tg(s)

.3instantaneous

I i

alarm

Ir

ground fault

test

on off

on off off

(s)

(s)

(s)

long time

short time instantaneous

CD

B50

0004

7

13

1415

(1)

(2)

Page 23: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-13

Protection ETV2ILong time ETV2I

DB

1011

26

Current setting (A) Ir 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1

Time setting tr (s) 0.5 1 2 4 8 12 16 20 24Time delay (s) Accuracy: 0 to -30 % 12.5 25 50 100 200 300 400 500 600

Accuracy: 0 to -20 % 0.7(1) 1 2 4 8 12 16 20 24Accuracy: 0 to -20 % 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6

Thermal memory 20 minutes before and after tripping(1) (2)InstantaneousPick-up (A) Isd 1.5 2 2.5 3 4 5 6 8 10Accuracy: ±10 %Time delay

Protection ETV5S/ETV6GLong time ETV5S/ETV6G

DB

1011

27

Current setting (A) Ir 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1

Time setting tr (s) 0.5 1 2 4 8 12 16 20 24Time delay (s) Accuracy: 0 to -30 % 12.5 25 50 100 200 300 400 500 600

Accuracy: 0 to -20 % 0.7(1) 1 2 4 8 12 16 20 24Accuracy: 0 to -20 % 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6

Thermal memory 20 minutes before and after tripping(1) (2)Short timePick-up (A) Isd 1.5 2 2.5 3 4 5 6 8 10Accuracy: ±10 %Time setting tsd (s) Settings I2t Off 0 0.1 0.2 0.3 0.4

I2t On - 0.1 0.2 0.3 0.4tsd 20 80 140 230 350

(I2t Off or I2t On) tsd 80 140 200 320 500InstantaneousPick-up (A) Ii 2 3 4 6 8 10 12 15 offAccuracy: ±10 %Time delay

Earth fault ETV6G

DB

1011

28

Pick-up (A) Ig A B C D E F G H JAccuracy: ±10 % In y 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

400 A < In y 1000 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1In u 1250 A 500 640 720 800 880 960 1040 1120 1200

Time setting tg (s) Settings I2t Off 0 0.1 0.2 0.3 0.4I2t On - 0.1 0.2 0.3 0.4

Time delay (ms) tg 20 80 140 230 350at In or 1200 A (I2t Off or I2t On) tg 80 140 200 320 500

Energy ETV2I/5S/6GType of measurements Range AccuracyInstantaneous currents I1, I2, I3, In ± 1.5 %

Ig (ETV6G) ± 10 %I1, I2, I3, In ± 1.5 %

Demand currents of I1, I2, I3, Ig ± 1.5 %Voltages V12, V23, V31, V1N, V2N, V3N 100 to 690 V ± 0.5 %Note:

Page 24: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-14

Functionsand characteristics

ET range of trip systemAccessories and test equipment

External sensorsExternal sensor for earth-fault protectionThe sensors, used with the 3P circuit breakers, are installed on the neutral conductor for:

b Residual type earth-fault protection (with 6G trip units)The rating of the sensor (CT) must be compatible with the rating of the circuit breaker:

b MVS08 to MVS20: TC 400/2000 b MVS25 to MVS40: TC 1000/4000

Voltage measurement inputs(1)

As standard, the control unit is supplied by internal voltage measurement inputs placed downstream of the pole for voltages between 220 and 690 V AC.

External 24 V DC power-supply module

conditions of use, see the “electrical diagrams” part of this catalogue).Characteristics

b Power supply: v 110/130, 200/240, 380/415 V AC (+10 % -15 %) v 24/30, 48/60, 100/125 V DC (+20 % -20 %) b Output voltage: 24 V DC ±5 %, 1 A b Ripple < 1 % b Dielectric withstand : 3.5 kV rms between input/output, for 1 minute b Overvoltage category: as per IEC 60947-1 cat. 4

Spare partsLead-seal coversA lead-seal cover controls access to the adjustment dials.

b It is impossible to modify settings using the keypad unless the settings lockout pin on the cover is removed

b The test connector remains accessible b The test button for the earth-fault protection function remains accessible

Characteristics b Transparent cover for all trip units

Spare batteryA battery supplies power to the LEDs identifying the tripping causes.The healthiness of the battery to be checked periodically. A test button on the front of the control unit is used to check the battery condition. The battery may be replaced on site when discharged.

Test equipmentHand-held test kitThe hand-held mini test kit may be used to:

b Check operation of the control unit and the tripping and pole-opening system by sending a signal simulating a short-circuit

b Power source: standard LR6-AA battery

DB

1015

24P

B10

0775

-32

CD

B50

0038

PB

1010

26-3

2A

(1)

Page 25: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-15

ConnectionsOverview of solutions and accessories

Available connection: b

The solutions presented are similar in principle for all

Rear connectionHorizontal Vertical

Simply turn a horizontal rear connector 90° to make it a vertical connector.

PB

1043

55A

40

PB

1043

59A

40P

B10

4354

A40

Page 26: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-16

Functionsand characteristics

ConnectionsOverview of solutions and accessories

Interphase barriers EIP

connection points in installations with busbars, whether insulated or not.For EasyPact MVS devices, they are installed vertically between rear connection terminals. They are not compatible with spreaders.

Safety shutters VOMounted on the chassis, the safety shutters automatically block access to thedisconnecting contact cluster when the device is in the disconnected or test positions

parts are accessible.The shutter-locking system is made up of a moving block (optional device) that can be padlocked (padlock not supplied). The block:

b Prevents connection of the device b Locks the shutters in the closed position

For EasyPact MVS08 to MVS40A support at the bottom of the chassis is used to store the blocks when they are not used:

b 2 blocks for MVS08 to MVS40

CP

B10

0010

PB

1043

64A

50

Page 27: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-17

Accessories and auxiliaries

Type of accessory EasyPact MVS08 to MVS40Draw-out breaker

Rear connection Rear connection Interphasebarriers

DB

1011

49

Optional

DB

1011

49

OptionalSafety shutters

DB

1011

53

StandardSafety shutters locking blocks

E46

460

OptionalDoor interlock

E46

452

OptionalPushbutton locking device E

4666

6

Optional

E46

666

OptionalOFF position locking

CD

B50

0039

Optional

CD

B50

0039

Optional“Disconnected” position locking

DB

1174

58

OptionalON/OFF indication contacts(OF) E

4668

9

Standard

E46

689

StandardAdditional ON/OFF indication contacts(OF) E

4668

9

Optional

E46

689

Optional“Fault trip” indication contact(SDE)

CD

B50

0040

Standard

CD

B50

0040

Standard

Page 28: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-18

Type of accessory EasyPact MVS08 to MVS40Draw-out breaker

Rear connection Rear connection “Connected, disconnected, test position”indication contact(CE,CD,CT)

E46

661

Optional“Ready to close” contact(PF) E

4643

8

Optional

E46

438

OptionalEscutcheon(CDP)

CD

B50

0061

Standard

CD

B50

0061

StandardMechanical operation counter(CDM)

DB

1256

17

Optional

DB

1256

17

OptionalEscutcheon blanking plate

E46

670

Optional

E46

670

Optional

terminal shield(CB) E46

458

OptionalTransparent cover (IP54) E

4666

9

Optional

Functionsand characteristics

Accessories and auxiliaries

Page 29: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-19

LockingOn the device

Pushbutton locking VBPThe transparent cover blocks access to the pushbuttons used to open and close the device.It is possible to independently lock the opening button and the closing button.The locking device is often combined with a remote operating mechanism.The pushbuttons may be locked using either:

b Three padlocks (not supplied) b Lead seal b Two screws

Device locking in the OFF position by keylocks VSPOThe circuit breaker is locked in the OFF position by physically maintaining theopening pushbutton pressed down:

b Using keylocks (one or two keylocks, supplied)

b One keylock b One keylock mounted on the device + one identical keylock supplied separately for interlocking with another device

A locking kit (without locks) is available for installation of one or two keylocks (Ronis,

PB

1008

11-3

2P

B10

0810

-32

CP

B10

0007 CD

B50

0036

Door interlock catch VPECMounted on the right or left-hand side of the chassis, this device inhibits opening ofthe cubicle door when the circuit breaker is in “connected” or “test” position. It thebreaker is put in the “connected” position with the door open, the door may be closedwithout having to disconnect the circuit breaker.

Automatic spring discharge before breaker removal DAEThis option discharges the springs before the breaker is removed from the chassis.

CD

B50

0006

1 2 3 4 5 6 7 8 9

MVS08 N

IEC 60947-2 50/60H

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long time

alarm

ground fault

setting

4

test

.4.5.6

.7.8 .9

.95

.981

Ir

x In

.512

48 12

1620

tr(s)

at 6 Ir24

x Ir

22.5

34 5

68

10

Isd

1.5

tsd(s)

x In3

68 10

1215

off2

BC

DE F

GH

I

Ig

Aon I

2t.2.3

.4.4

.1

.2.3

.10off

tg(s)

.3

instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

onoff

onoff

off

(s)

(s)

(s)

long time

short time

instantaneous

ET6G Trip System

CP

B10

0008

Page 30: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-20

LockingOn the chassis

CD

B50

0007

1 2 3 4 5 6 7 8

“Connected”, “disconnected” and “test” position racking interlockThe “connected”, “disconnected” and “test” positions are shown by an indicator and

blocks. A release button is used to free it.

“Disconnected” position locking by padlocks or keylocks VSPDMounted on the chassis and accessible with the door closed, these devices lock thecircuit breaker in the “disconnected” position in two manners:

b Using padlocks (standard), up to three padlocks (not supplied) b Using keylocks (optional), one or two different keylocks are available

b One keylock b Two identical key locks - one keylock mounted on the device + one identical keylock supplied separately for interlocking with another device

A locking kit (without locks) is available for installation of one or two keylocks

Padlock

CP

B10

0006

CP

B10

0017

Circuit breaker in “disconnected” position.

5 to 8 mm) of the padlock(s).

Pull out the tab.

The crank connot be inserted.

KeylockCircuit breaker in “disconnected” position.

Remove the key(s)

Turn the key(s).

The crank cannot be inserted.

1

8

3

7 56

4

2

Functionsand characteristics

Page 31: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-21

Indication contacts

PB

1008

18-1

6P

B10

0807

-20

Indication contacts are available: b in the standard version for relay applications

ON/OFF indication contacts OFIndication contacts indicate the ON or OFF position of the circuit breaker:

b Rotary type changeover contacts directly driven by the mechanism for EasyPact MVS. These contacts trip when the minimum isolation distance between the main circuit-breaker contacts is reached

OF MVSSupplied as standard 1 (4 C/O)Optional contact 1 (4 C/O)Breaking capacity (A) Standard Minimum load: 100 mA/24 Vp.f.: 0.3 V AC 240/380 10/6 (1)

AC12/DC12 480 10/6 (1)

690 6V DC 24/48 10/6 (1)

125 10/6 (1)

250 3

“Fault-trip” indication contacts SDECircuit-breaker tripping due to a fault is signalled by:

b A red mechanical fault indicator (reset) b One changeover contact SDE

Following tripping, the mechanical indicator must be reset before the circuit breakermay be closed. One SDE is supplied as standard.SDE MVSSupplied as standard 1Breaking capacity (A) Standard Minimum load: 100 mA/24 Vp.f.: 0.3 V AC 240/380 5AC12/DC12 480 5

690 3V DC 24/48 3

125 0.3250 0.15

“Connected”, “disconnected” and “test” position carriage switches CE, CD & CT

b Changeover contacts to indicate the “connected” position CE b Changeover contacts to indicate the “disconnected” position CD. This position

circuits is reached b Changeover contacts to indicate the “test” position CT. In this position, the power

MVSContacts CE/CD/CT

Standard 3 3 3Breaking capacity (A) Standard Minimum load: 100 mA/24 Vp.f.: 0.3 V AC 240 8AC12/DC12 380 8

480 8690 6

V DC 24/48 2.5125 0.8250 0.3

PB

1008

17-3

2

Page 32: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-22

Remote operationRemote ON / OFF

PB

1043

49A

68

DB

1117

83

The remote ON / OFF function is used to remotely open and close the circuit breaker.It is made up of:

b An electric motor MCH equipped with a “springs charged” limit switch contact CH b Two voltage releases: v A closing release XF v An opening release MX

Optionally, other function may be added: b A “ready to close” contact PF

A remote-operation function is generally combined with: b Device ON / OFF indication OF b “Fault-trip” indication SDE

Wiring diagram of a point-to-point remote ON / OFF function

A point-to-point solution for remote operation of EasyPact MVS

Note:

Functionsand characteristics

Page 33: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-23

Electric motor MCHThe electric motor automatically charges and recharges the spring mechanism whenthe circuit breaker is closed. Instantaneous reclosing of the breaker is thus possiblefollowing opening. The spring-mechanism charging handle is used only as a backup

The electric motor MCH is equipped as standard with a limit switch contact CH thatsignals the “charged” position of the mechanism (springs charged).CharacteristicsPower supply V AC 50/60 Hz 100/130 - 200/240 - 380/415

V DC 24/30 - 48/60 - 100/125 - 200/250Operating threshold 0.85 to 1.1 Un

180Motor overcurrent 2 to 3 In for 0.1 sCharging timeOperating frequencyCH contact 10 A at 240 V

Voltage releases XF and MXTheir supply can be maintained or automatically disconnected.Closing release XFThe XF release remotely closes the circuit breaker if the spring mechanism is charged.Opening release MXThe MX release instantaneously opens the circuit breaker when energised. It locks the circuit breaker in OFF position if the order is maintained.Characteristics XF MXPower supply V AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 380/480

V DC 12 - 24/30 - 48/60 - 100/130 - 200/250Operating threshold 0.85 to 1.1 Un 0.7 to 1.1 Un

Hold: 4.5 Hold: 4.5Pick-up: 200 (200 ms) Pick-up: 200 (200 ms)

Circuit-breaker response time at Un 70 ms ±10 50 ms ±10

“Ready to close” contact PFThe “ready to close” position of the circuit breaker is indicated by a mechanical indicator and a PF changeover contact. This signal indicates that all the following are valid:

b The circuit breaker is in the OFF position b The spring mechanism is charged b A maintained opening order is not present: v MX energised v Fault trip v Remote tripping MN v Device not completely racked in v Device locked in OFF position v Device interlocked with a second device

Characteristics1

Breaking capacity (A) Standard Minimum load: 100 mA/24 Vp.f.: 0.3 V AC 240/380 5AC12/DC12 480 5

690 3V DC 24/48 3

125 0.3250 0.15

PB

1008

09-1

6P

B10

0818

-16

DB

1170

37P

B10

0808

-32

Remote operationRemote ON / OFF

Page 34: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-24

Remote operationRemote tripping

DB

1008

09-1

605

6422

N

Instantaneous voltage releases MNThe MN release instantaneously opens the circuit breaker when its supply voltagedrops to a value between 35 % and 70 % of its rated voltage. If there is no supply onthe release, it is impossible to close the circuit breaker, either manually or electrically.Any attempt to close the circuit breaker has no effect on the main contacts. Circuit breaker closing is enabled again when the supply voltage of the release returns to 85% of its rated value.CharacteristicsPower supply V AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 380/480

V DC 24/30 - 48/60 - 100/130 - 200/250Operating threshold Opening 0.35 to 0.7 Un

Closing 0.85 UnPick-up: 200 (200 ms) Hold: 4.5

MN consumption Pick-up: 200 (200 ms) Hold: 4.5

Circuit-breaker response time at Un 90 ms ±5

MN delay unitsTo eliminate circuit-breaker nuisance tripping during short voltage dips, operation of

delay unit in the MN voltage-release circuit. Two versions are available, adjustableand non-adjustable.CharacteristicsPower supply Non-adjustable 100/130 - 200/250V AC 50-60 Hz /DC Adjustable 48/60 - 100/130 - 200/250 - 380/480Operating threshold Opening 0.35 to 0.7 Un

Closing 0.85 UnDelay unit consumption Pick-up: 200 (200 ms) Hold: 4.5Circuit-breaker response time at Un Non-adjustable 0.25 s

Adjustable 0.5 s - 0.9 s - 1.5 s - 3 s

Functionsand characteristics

Page 35: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-25

Source-changeover systemsMechanical interlocking

Interlocking of two EasyPact MVS or up to three EasyPact MVS devices using cablesFor cable interlocking, the circuit breakers may be mounted one above the other or

pole, and have different ratings.Interlocking between two devicesThis function requires:

b b A set of cables with no-slip adjustments b The use of a mechanical operation counter CDM is compulsory

Interlocking between three devicesThis function requires:

bof each device

b Two or three sets of cables with no-slip adjustments b The use of a mechanical operation counter CDM is compulsory

Installation

are supplied separately, ready for assembly by the customer.

Installation conditions for cable interlocking systems: b Cable length: 2.5 m b Radius of curvature: 100 mm b

Possible combinations of “Normal” and “Replacement” source circuit breakers“Normal N” “Replacement” RMVS08 to MVS40 MVS08 to MVS40Ratings 800...4000A b

Possible combinations of three deviceMVS08 to MVS40 MVS08 to MVS40Ratings 800...4000A b

All combinations of two or three EasyPact MVS devices are possible, whatever the rating of the devices.

CP

B10

0009

Page 36: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-26

AccessoriesP

B10

4740

PB

1043

82A

32D

B10

1173

PB

1007

76-4

2

Auxiliary terminal shield CBOptional equipment mounted on the chassis, the shield prevents access to the

Operation counter CDMThe operation counter sums the number of operating cycles and is visible on the front panel. It is compatible with manual and electrical control functions.This option is compulsory for all the source-changeover systems.

Escutcheon CDPStandard equipment mounted on the door of the cubicle, the escutcheon increasesthe degree of protection to IP 40 (circuit breaker installed free standing: IP30) .

Blanking plate for escutcheon OPUsed with the escutcheon, this option closes off the door cut-out of a cubicle not yet

draw-out devices.

Transparent cover for escutcheon CPOptional equipment mounted on the escutcheon, the cover is hinged and secured bya screw. It increases the degree of protection to IP54, IK10. It adapts to draw-outdevices.

Functionsand characteristics

Page 37: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

A-27

Page 38: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

Installationrecommendations

Page 39: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

B-1

Installation recommendations

Functions and characteristics A-1

Operating conditions B-2

Installation in switchboard B-3

Door interlock catch B-5

Control wiring B-6

Power connection B-7

Recommended busbars drilling B-9

Busbar sizing B-10

Temperature deratingPower dissipation B-12

Dimensions and connection C-1Electrical diagrams D-1Additional characteristics E-1Catalogue numbers and order form F-1

EasyPact MVS

Page 40: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

B-2

Installationrecommendations

Operating conditions

EasyPact MVS circuit breakers have been tested for operation in industrial atmospheres. It is recommended that the equipment be cooled or heated to the proper

vibration and dust.

CD

B50

0008 Ambient temperature

EasyPact MVS devices can operate under the following temperature conditions: b The electrical and mechanical characteristics are stipulated for an ambient temperature of -5°C to +60°C

b Circuit-breaker closing is guaranteed down to -35°CStorage conditions are as follows:

b -40 to +85°C for a Easypact MVS device without its control unit b -25°C to +85°C for the control unit

CD

B50

0011

CD

B50

0012

Altitude

resistance, cooling capacity) lower the following characteristics as follows:

Altitude (m) 2000 3000Impulse withstand voltage uimp (kV) 12 11Rated insulation voltage (Ui) 1000 900

voltage 50/60 Hz Ue (V)690 5901000 890

Rated current 40°C

Intermediate values may be obtained by interpolation.

Electromagnetic disturbancesEasyPact MVS devices are protected against:

b Overvoltages caused by devices that generate electromagnetic disturbances b Overvoltages caused by atmospheric disturbances or by a distribution-system outage (e.g. failure of a lighting system)

b Devices emitting radio waves (radios, walkie-talkies, radar, etc.) b Electrostatic discharges produced by users

EasyPact MVS devices have successfully passed the electromagnetic-compatibility

bThe above tests guarantee that:

b No nuisance tripping occurs b Tripping times are respected

MVS08 N

IEC 60947-2 50/60H

delay

short time

onI2t

.2

.3.4 .4

.1

.2

.10

long time

alarm

ground fault

setting

4

test

.4.5.6

.7.8 .9

.95

.981

Ir

x In

.512

48 12

1620

tr(s)

at 6 Ir24

x Ir

22.5

34 5

68

10

Isd

1.5

tsd(s)

x In3

68 10

1215

off2

BC

DE F

GH

I

Ig

Aon

I2t

.2

.3.4.4

.1

.2.3

.10off

tg(s)

.3

instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

onoff

onoff

off

(s)

(s)

(s)

long time

short time

instantaneous

ET6G Trip System

2000(m)

MVS08 N

IEC 60947-2 50/60H

delay

short time

onI2t

.2

.3.4 .4

.1

.2

.10

long time

alarm

ground fault

setting

4

test

.4.5.6

.7.8 .9

.95

.981

Ir

x In

.512

48 12

1620

tr(s)

at 6 Ir24

x Ir

22.5

34 5

68

10

Isd

1.5

tsd(s)

x In3

68 10

1215

off2

BC

DE F

GH

I

Ig

Aon

I2t

.2

.3.4.4

.1

.2.3

.10off

tg(s)

.3

instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

onoff

onoff

off

(s)

(s)

(s)

long time

short time

instantaneous

ET6G Trip System

MVS08 N

IEC 60947-2 50/60H

delay

short time

onI2t

.2

.3.4 .4

.1

.2

.10

long time

alarm

ground fault

setting

4

test

.4.5.6

.7.8 .9

.95

.981

Ir

x In

.512

48 12

1620

tr(s)

at 6 Ir24

x Ir

22.5

34 5

68

10

Isd

1.5

tsd(s)

x In3

68 10

1215

off2

BC

DE F

GH

I

Ig

Aon

I2t

.2

.3.4.4

.1

.2.3

.10off

tg(s)

.3

instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

onoff

onoff

off

(s)

(s)

(s)

long time

short time

instantaneous

ET6G Trip System

Page 41: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

B-3

Installation in switchboard

CD

B50

0013

CD

B50

0016

CD

B50

0017

CD

B50

0018

CD

B50

0014

CD

B50

0015

Possible positions

Power supplyEasyPact MVS devices can be supplied either from the top or from the bottom without reduction in performance, in order to facilitate connection when installed in a switchboard.

Mounting the circuit-breakerIt is important to distribute the weight of the device uniformily over a rigid mountingsurface such as rails or a base plate.

This eliminates any risk of deformation which could interfere with correct operationof the circuit breaker.EasyPact devices can also be mounted on a vertical plane using the special brackets.

MVS08 N

IEC 60947-2 50/60H

delay

short time

onI2t

.2

.3.4 .4

.1

.2

.10

long time

alarm

ground fault

setting

4

test

.4.5.6

.7.8 .9

.95

.981

Ir

x In

.512

48 12

1620

tr(s)

at 6 Ir24

x Ir

22.5

34 5

68

10

Isd

1.5

tsd(s)

x In3

68 10

1215

off2

BC

DE F

GH

I

Ig

Aon

I2t

.2

.3.4.4

.1

.2.3

.10off

tg(s)

.3

instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

onoff

onoff

off

(s)

(s)

(s)

long time

short time

instantaneous

ET6G Trip System

MVS08 N

IEC 60947-2 50/60H

delay

short time

onI2t

.2

.3.4 .4

.1

.2

.10

long time

alarm

ground fault

setting

4

test

.4.5.6

.7.8 .9

.95

.981

Ir

x In

.512

48 12

1620

tr(s)

at 6 Ir24

x Ir

22.5

34 5

68

10

Isd

1.5

tsd(s)

x In3

68 10

1215

off2

BC

DE F

GH

I

Ig

Aon

I2t

.2

.3.4.4

.1

.2.3

.10off

tg(s)

.3

instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

onoff

onoff

off

(s)

(s)

(s)

long time

short time

instantaneous

ET6G Trip System

MVS08 N

IEC 60947-2 50/60H

delay

short time

onI2t

.2

.3.4 .4

.1

.2

.10

long time

alarm

ground fault

setting

4

test

.4.5.6

.7.8 .9

.95

.981

Ir

x In

.512

48 12

1620

tr(s)

at 6 Ir24

x Ir

22.5

34 5

68

10

Isd

1.5

tsd(s)

x In3

68 10

1215

off2

BC

DE F

GH

I

Ig

Aon

I2t

.2

.3.4.4

.1

.2.3

.10off

tg(s)

.3

instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

onoff

onoff

off

(s)

(s)

(s)

long time

short time

instantaneous

ET6G Trip System

MVS08 N

IEC 60947-2 50/60H

delay

short time

onI2t

.2

.3.4 .4

.1

.2

.10

long time

alarm

ground fault

setting

4

test

.4.5.6

.7.8 .9

.95

.981

Ir

x In

.512

48 12

1620

tr(s)

at 6 Ir24

x Ir

22.5

34 5

68

10

Isd

1.5

tsd(s)

x In3

68 10

1215

off2

BC

DE F

GH

I

Ig

Aon

I2t

.2

.3.4.4

.1

.2.3

.10off

tg(s)

.3

instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

onoff

onoff

off

(s)

(s)

(s)

long time

short time

instantaneous

ET6G Trip System

Page 42: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

B-4

DB

1014

34D

B10

1435

A :

Partitions

ensure good air circulation around the circuit breaker;Any partition between upstream and downstreamconnections of the device must be made of nonmagnetic material.For high currents, of 2500 A and upwards, the metalsupports or barriers in the immediate vicinity of aconductor must be made of non-magnetic material A.Metal barriers through which a conductor passes mustnot form a magnetic loop.

DB

1170

45

DB

1014

36Busbars

possibility of formation of a magnetic loop around a conductor.

CD

B50

0041

DB

1014

39

453

Interphase barrierIf the insulation distance between phases is not

y 14 mm), it is advised to install phasebarriers (taking into account the safety clearances).

Installationrecommendations

Installation in switchboard

Page 43: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

B-5

Door interlock catch

DB

1170

44D

B10

3819

83103

DB

1021

94

Breaker in “connected” or “test” positionDoor cannot be opened

Breaker in “disconnected” positionDoor can be opened

Door interlock VPECMounted on the right or left-hand side of the chassis,this device inhibits opening of the cubicle door whenthe circuit breaker is in “connected” or “test” position.It the breaker is put in the “connected” position with thedoor open, the door may be closed without having todisconnect the circuit breaker.

Dimensions (mm)Type (1) (2)MVS08-40 (3P) 215 215MVS08-40 (4P) 330 215

Note:

Note:

CD

B50

0034

Page 44: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

B-6

Control wiring

Wiring of voltage releases

cross-sectional area of cables.Recommended maximum cable lengths (meter).

12 V 24 V 48 V2,5 mm2 1,5 mm2 2,5 mm2 1,5 mm2 2,5 mm2 1,5 mm2

MN U source 100 % – – 58 35 280 165U source 85 % – – 16 10 75 45

MX-XF U source 100 % 21 12 115 70 550 330U source 85 % 10 6 75 44 350 210

Note:

24 V DC power-supply moduleExternal 24 V DC power-supply module (F1-, F2+)

b Do not connect the positive terminal (F2+) to earth b The negative terminal (F1-) can be connected to earth b A number of trip units can be connected to the same 24 V DC power supply (the

b Do not connect any devices other than a trip unit badvised to twist the supply wires together

b The 24 V DC supply wires must cross the power cables perpendicularly. If this is

bindicated on page A-14.

Note:

Installationrecommendations

Page 45: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

B-7

Power connection

Cables connectionsIf cables are used for the power connections, make

forces to the circuit breaker terminals.For this, make the connections as follows:

bbars designed and installed according to the recommendations for bar-type power connections:

v For a single cable, use solution B opposite v For multiple cables, use solution C opposite b In all cases, follow the general rules for connections to busbars:

v Position the cable lugs before inserting the bolts v E

DB

1014

48

DB

1014

49

DB

1014

50D

B10

1453

DB

1014

51

DB

1014

52Busbars connectionsThe busbars should be suitably adjusted to ensure thatthe connection points are positioned on the terminalsbefore the bolts are inserted BThe connections are held by the support which is

that the circuit breaker terminals do not have to support its weight C. (This support should be placed close to the terminals).

Electrodynamic stresses

the connection point of the breaker (see table below). This distance must berespected so that the connection can withstand the electrodynamic stressesbetween phases in the event of a short circuit.

support or spacer with respect to the value of the prospective short-circuit current.Isc (kA) 30 50 65Distance A (mm) 350 300 250

Page 46: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

B-8

DB

1014

54 ClampingCorrect clamping of busbars depends amongst other things, on the tighteningtorques used for the nuts and bolts. Over-tightening may have the sameconsequences as under-tightening.For connecting busbars (Cu ETP-NFA51-100) to the circuit breaker, the tighteningtorques to be used are shown in the table below.These values are for use with copper busbars and steel nuts and bolts, class 8.8. The same torques can be used with AGS-T52 quality aluminium bars (French standardNFA 02-104 or American National Standard H-35-1).Examples

1 2 3 4 5 6

DB

1014

55

DB

1014

56

DB

1014

57

Tightening torquesØ (mm)Nominal

Ø (mm)Drilling

Tightening torques (Nm) Tightening torques (Nm)with contact or corrugatecwashers

10 11 37.5 50

Busbar drillingExamples

DB

1014

58

DB

1014

59

DB

1014

60

DB

1014

61D

B10

1462

Isolation distance

Dimensions (mm)Ui X min600 V 8 mm1000 V 14 mm

Busbar bending

cause cracks).

Dimensions (mm)e Radius of curvature r

Min Recommended5 5 7.510 15 18 to 20

Installationrecommendations

Power connection

Page 47: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

B-9

Recommended busbars drillingEasyPact MVS08 to MVS40

Horizontal rear connection MVS08 to MVS32

Vertical rear connection MVS08 to MVS32

MVS40

MVS40

DB

1014

63

DB

1014

64

DB

1014

65

CD

B50

0042

CD

B50

0054

CD

B50

0055

CD

B50

0056

CD

B50

0043

DB

1014

74D

B10

1476

DB

1014

77

Page 48: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

B-10

Installationrecommendations

Busbar sizing

Basis of tables: b b Ti: temperature around the ciruit breaker and its connection

b Busbar material is unpainted Copper / Aluminium

ExampleConditions:

b Drawout version b Horizontal busbars b Ti

b Service current: 1600ASolution:For Ti

Aluminium.

Rear horizontal connection

Note:

(Rear horizontal connection)

Page 49: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

B-11

Busbar sizing

Basis of tables: b b Ti: temperature around the ciruit breaker and its connection

b Busbar material is unpainted Copper / Aluminium

ExampleConditions:

b Drawout version b Hertical connections b Ti: 40 °C b Service current: 1100 A.

Solution:For Ti = 40 °C use an MVS12 which can be connected

Rear vertical connection

Note:

Page 50: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

B-12

Temperature deratingPower dissipation

Temperature derating

for each connection type, as a function of Ti around thecircuit breaker and the busbars.For Ti greater than 60°C, consult us.Ti: temperature around the circuit breaker and its connection.

Version Draw-out FixedConnection Rear horizontal Rear vertical Rear horizontal Rear verticalTemp. Ti 40 °C 45 °C 50 °C 55 °C 60 °C 40 °C 45 °C 50 °C 55 °C 60 °C 40 °C 45 °C 50 °C 55 °C 60 °C 40 °C 45 °C 50 °C 55 °C 60 °CMVS (50kA)MVS08N 800 800 800 800MVS10N 1000 1000 1000 1000MVS12N 1250 1250 1250 1250MVS16N 1600 1600 1600 1600MVS20N 2000 1900 1800 2000 1900 2000 1920 2000MVS25N 2500 2450 2500 2500 2500MVS32N 3200 3100 3000 2900 3200 3200 3200MVS40N 4000 3900 3750 3650 4000 3900 4000 3900 3800 4000MVS (65kA)MVS08H 800 800 800 800MVS10H 1000 1000 1000 1000MVS12H 1250 1250 1250 1250MVS16H 1600 1600 1600 1600MVS20H 2000 1900 1800 2000 1900 2000 1920 2000MVS25H 2500 2450 2400 2300 2200 2500 2450 2400 2300 2500 2500MVS32H 3200 3100 3000 2900 3200 3200 3200MVS40H 4000 3900 3750 3650 4000 3900 4000 3900 3800 4000

Power dissipationTotal power dissipation is the value measured at IN, 50/60 Hz, for a 3 pole or 4 pole breaker (values above the power P = 3RI2). The resistance between input / output is the value measured per pole (cold state).

Type Draw-out Fixed50kA Power loss

(W)Input/output resistance (μohm)

Power loss (W)

Input/output resistance (μohm)

MVS08N 120 36 60 19MVS10N 180 36 100 19MVS12N 280 36 140 19MVS16N 460 36 200 19MVS20N 470 30 250 13MVS25N 600 19 260 13MVS32N 670 13 420 8MVS40N 900 11 650 865kAMVS08H 100 30 42 13MVS10H 150 30 70 13MVS12H 230 30 100 13MVS16H 390 30 170 13MVS20H 470 30 250 13MVS25H 600 19 260 8MVS32H 670 13 420 8MVS40H 900 11 650 8

Page 51: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

B-13

Page 52: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

Dimensions and connection

Page 53: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

C-1

Dimensions and connection

Functions and characteristics A-1Installation recommendations B-1

MVS08 to MVS32 circuit breakers C-2

Draw-out 3/4-poles device C-4

MVS40 circuit breakers C-6

Draw-out 3/4-poles device C-8

Accessories C-10

External modules C-11

Electrical diagrams D-1Additional characteristics E-1Catalogue numbers and order form F-1

EasyPact MVS

Page 54: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

C-2

Dimensionsand connection

MVS08 to MVS32 circuit breakersFixed 3/4-poles device

Dimensions

DB

1012

67

CD

B50

0019

DB

1012

69D

B10

1271

CD

B50

0020

DB

1012

73D

B10

1270

Mounting on base plate or rails Mounting detail

Safety clearances

(1)(2)Note: X and YA(*)

Insulated Metal Energisedparts parts parts

A 0 0 100B 0 0 60

Page 55: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

C-3

Connections

DB

1012

74D

B10

1279

DB

1012

76

DB

1012

77D

B10

1287

DB

1012

82D

B10

1278

Horizontal rear connection

Vertical rear connection

Detail

Detail

Note: M1050 Nm

DB

1012

80

Page 56: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

C-4

Dimensionsand connection

MVS08 to MVS32 circuit breakersDraw-out 3/4-poles device

Dimensions

DB

1012

89

CD

B50

0021

DB

1012

91D

B10

1293

CD

B50

0022

DB

1012

95D

B10

1292

Mounting on base plate or rails Mounting detail

Safety clearances Door cutout

Insulated Metal Energisedparts parts parts

A 0 0 60B 0 0 60

(1)(2)Note: X and Y

DB

1012

94

Page 57: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

C-5

Connections

CD

B50

0044

CD

B50

0045

DB

1012

97D

B10

1301

DB

1012

98D

B10

1307

Horizontal rear connection

Vertical rear connection

Detail

Detail

DB

1012

82

Note: M1050 Nm

DB

1012

78

Page 58: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

C-6

Dimensionsand connection

MVS40 circuit breakersFixed 3/4-poles device

CD

B50

0019

Dimensions

DB

1012

67

Mounting on base plate or rails Mounting detail

DB

1012

69D

B10

1271

DB

1012

73D

B10

1270

Safety clearances

(1)(2)Note: X and YA(*)

Insulated Metal Energisedparts parts parts

A 0 0 100B 0 0 60

Door cutout

CD

B50

0020

Page 59: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

C-7

Connections

DB

1013

09D

B10

1312

Horizontal rear connection

Vertical rear connection

Detail

Detail

DB

1013

11D

B10

1314

DB

1013

15

DB

1012

76C

DB

5000

49D

B10

1287

DB

1013

13

Note: M1050 Nm

400(3P)15

Page 60: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

C-8

Dimensionsand connection

MVS40 circuit breakersDraw-out 3/4-poles device

CD

B50

0021

Dimensions

DB

1012

89D

B10

1291

DB

1012

93

DB

1012

95D

B10

1292

Safety clearances Door cutout

Insulated Metal Energisedparts parts parts

A 0 0 60B 0 0 60 (1)

(2)Note: X and Y

Mounting on base plate or rails Mounting detail

CD

B50

0022

DB

1012

94

Page 61: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

C-9

Connections

CD

B50

0046

CD

B50

0047

DB

1012

97

DB

1013

07

Horizontal rear connection

Vertical rear connection

Note: M1050 Nm

Detail

Detail

DB

1013

11D

B10

1315

DB

1013

14

CD

B50

0050

DB

1013

19

400(3P)15

Page 62: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

C-10

Dimensionsand connection

AccessoriesD

B10

1350

DB

1013

51

Page 63: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

C-11

External modules

Connection of auxilary wiring to terminal block

External power supply module (AD)

Delay unit for MN release

DB

1013

67

DB

1020

77D

B10

1375

DB

1170

25D

B10

2076

DB

1013

68

Page 64: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

C-12

External sensor for external neutral

DB

1170

24D

B10

1386

DB

1013

87D

B11

7023

Dimensions400/2000 A (MVS08 to MVS20) 1000/4000 A (MVS25 to MVS40)

Installation400/2000 A (MVS08 to MVS20) 1000/4000 A (MVS25 to MVS40)

Dimensionsand connection

External modules

Page 65: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

C-13

Page 66: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

Electrical diagrams

Page 67: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

D-1

Electrical diagrams

Functions and characteristics A-1Installation recommendations B-1Dimensions and connection C-1

EasyPact MVS08 to 40 D-2

EasyPact MVS D-4Earth-fault protection/Neutral protection D-4Zone selective interlocking D-5

Additional characteristics E-1Catalogue numbers and order form F-1

EasyPact MVS

Page 68: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

D-2

Electrical diagrams Masterpact MVS08 to MVS40Fixed and draw-out devices

The diagram is shown with circuitsde-energised, all devices open, connectedand charged and relays in normal position.

Power ET/ETA/ETV trip system Remote operation

ET trip system

NCT

ETA/ETV trip systemV

N

UV1

V2

V3

E89

955

StopFaul

t

E89

956

E60

065A

Ope

nE

4613

6A

Clo

seE

4613

7A

Rea

dy-

to-c

lose

E60

066A

Cha

rged

E60

067A

ET trip systemUC1 UC2

Z5

Z3 Z4 T3 T4

Z1 Z2 T1 T2

ETA/ETV trip systemUC1 UC2 UC3

Z5 F2+

Z3 Z4 T3 T4 VN

Z1 Z2 T1 T2 F1-

Remote operationSDE MN MX XF PF MCH

84 D2 C2 A2 254 B2

82 252 B3

81 D1 C1 A1 251 B1

ET/ETA/ETV trip system Remote operationUC1 :Z1-Z5 zone selective interlockingZ1=ZSI OUT SOURCEZ2=ZSI OUT ; Z3 = ZSI IN SOURCEZ4 =ZSI IN ST (short time)Z5 =ZSI IN GF (earth fault)

UC2 :

UC3 :

connected to the neutral CT with a 3P circuit breaker equipped with ETV trip system)

SDE: Fault-trip indication contact (supplied as standard)MN: Undervoltage releaseMX: Shunt release (standard for Electrical breaker)XF: Closing release (standard for Electrical breaker)PF: “Ready to close”contactMCH: Gear motor (standard for Electrical breaker)

E47

477

External sensors ( Neutral CT)

The sensors, used with the 3P circuit breakers, are installed on the neutral conductor for:1. Residual type earth-fault protection(ET/ETA/ETV 6G trip system)

The rating of the sensor (CT) must be compatible with the rating of the circuit breaker:1. MVS08 to MVS20: CT 400/2000;2. MVS25 to MVS40: CT 1000/4000;

Note:

Page 69: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

D-3

Indication contacts

Indication contacts

Chassis contacts

Chassis contacts

DB

1014

09

Indication contactsOF4 OF3 OF2 OF1 OF14 OF13 OF12 OF11

44 34 24 14 144 134 124 114

42 32 22 12 142 132 122 112

41 31 21 11 141 131 121 111

Chassis contactsCD3 CD2 CD1 CE3 CE2 CE1 CT3 CT2 CT1

834 824 814 334 324 314 934 924 914

832 822 812 332 322 312 932 922 912

831 821 811 331 321 311 931 921 911

Standard Optional Optional

OF 4 StandardOF 3 ON/OFFOF 2 Indication contactsOF 1

OF 14 OptionalON/OFFIndication contacts

OF 13OF 12OF 11

CD3 Disconnected CE3 Connected CT3 TestCD2 Position CE2 Position CT2 PositionCD1 Contacts CE1 Contacts CT1 Contacts

XXX as standard

Page 70: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

D-4

Electrical diagrams EasyPact MVSEarth-fault protectionNeutral Protection

External sensor (CT) for residual earth-fault protection

Neutral protection

DB

1256

01Connection of current-transformer secondary circuit for external neutralEasyPact MVS equipped with a ET/ETA/ETV 6G:

b Shielded cable with 2 twisted pairs b T1 twisted with T2 b b Cable cross-sectional area 0.4 to 1.5 mm2

b Recommended cable: Belden 9552 or equivalentFor proper wiring of neutral CT, refer to instructionBulletin 48041-082-03 shipped with it.Do not remove factory-installed jumper between T1and T2 unless neutral CT is connected.If supply is via the top, follow the shematics.If supply is via the bottom, control wiring is identical; forthe power wiring, H1 is connected to the source side,H2 to the load side.For four-pole versions, for residual earth-fault

neutral is not necessary.

b Three pole circuit breaker: v Neutral protection is impossible b Four pole circuit breaker: vnecessary

ET/ETA/ETV 6G

VN

Shield DrainVNExternal

Neutral CT

Page 71: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

D-5

Zone Selective Interlocking

Zone selective interlocking

DB

1014

20Zone-selective interlocking is used to reduce the

the time required to clear faults, while maintaining timediscrimination between the various devices.A pilot wire interconnects a number of circuit breakers equipped with ET range of trip system, as illustrated in the diagram above.The control unit detecting a fault sends a signal upstream andchecks for a signal arriving from downstream. If there is a signalfrom downstream, the circuit breaker remains closed for the fullduration of its tripping delay. If there is no signal fromdownstream, the circuit breaker opens immediately, regardlessof the tripping-delay setting.

Fault 1.Only circuit breaker A detects the fault. Because it receives nosignal from downstream, it opens immediately, regardless of itstripping delay set to 0.3.

Fault 2.Circuit breakers A and B detect the fault. Circuit breaker Areceives a signal from B and remains closed for the full durationof its tripping delay set to 0.3. Circuit breaker B does notreceive a signal from downstream and opens immediately, inspite of its tripping delay set to 0.2.

b / 300 m b Capacity of connectors: 0.4 to 2.5 mm2

b b b Limits to device interconnection: v The common ZSI - OUT (Z1) and the output ZSI - OUT (Z2)

vto the common ZSI - IN (Z3) and to an input ZSI - IN CR ( Z4) or GF (Z5)

Page 72: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

D-6

Electrical diagrams EasyPact MVS24 V DC external power supply AD module

bis not required for basic protections LSIG

b(AD module) to the Micrologic control unit (F1- F2+) in order to keep available the display and the energy metering, even if Current < 20 % In

Note:

Connection

Do not ground F2+, F1-, or power supply output: b The positive terminal (F2+) on the trip unit must not be connected to earth ground b The negative terminal (F1-) on the trip unit must not be connected to earth ground b The output terminals (- and +) of the 24 V DC power supply must not be grounded

Reduce electromagnetic interference: b The input and output wires of the 24 V DC power supply must be physically separated as much as possible

b If the 24 V DC power supply wires cross power cables, they must cross perpendicularly. If this is not physically possible, the power supply conductors must be twisted together

b

ETA/ETV trip system

DB

1283

83

Page 73: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

D-7

Page 74: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

Additional characteristics

Page 75: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

E-1

Additional characteristics

Functions and characteristics A-1Installation recommendations B-1Dimensions and connection C-1Electrical diagrams D-1

Tripping curves E-2

Catalogue numbers and order form F-1

EasyPact MVS

Page 76: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

E-2

Additionalcharacteristics

Tripping curves

ET range of trip system - 2I

ET range of trip system - 5S, 6G

DB

1051

12D

B10

5113

Page 77: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

E-3

Earth fault protection (ET range of trip system - 6G)

DB

1015

05

Ig = In x... A B C D E F G H IIn y 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1400 A < In y 1000 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1In u 1250A 500 640 720 800 880 960 1040 1120 1200

Page 78: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

Catalogue numbersand order form

Page 79: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

F-1

Catalogue numbersand order form

Functions and characteristics A-1Installation recommendations B-1Dimensions and connection C-1Electrical diagrams D-1Tripping curves E-2

Nomenclature F-2

EasyPact MVS F-3Connection F-3ET Trip System & accessories F-4Remote operation F-5Chassis locking and accessories F-7Clusters F-8Circuit breaker locking and accessories F-9Mechanical interlocking for source changeover F-10Indication contacts F-11Instructions F-12

Order form F-13

EasyPact MVS

Page 80: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

F-2

Catalogue numbersand order form

Nomenclature

Range Current rating Type Pole Operating mechanism Installation Protection No. TypeEasyPact MVS (from 800 to 4000A) Icu=Ics=Icw (1 sec)=50kA & 65kAMVS 08 N 3 M F 2 L

10 H 4 N 5 A12 O 6 V16 P 0 D20 Q25 R32 S40 T

11 digits3 2 1 1 1 1 1 1 Type

L Basic protectionA Protection+current meteringV Protection+voltage meteringD Switch disconnector

Protections No.2 LI protection5 LSI protection6 LSIG protection0 No protection for switch disconnector

Type of installation F

Draw-out

Operating mechanismM Manually operated ACB/SDN Electrical 200/240 VAC MCH + XF + MX O Electrical 110/130 VAC MCH + XF + MX P Electrical 380/415 VAC MCH + XF + MX Q Electrical 200/250 VDC MCH + XF + MX R Electrical 100/125 VDC MCH + XF + MX S Electrical 48/60V DC MCH + XF + MX T Electrical 24/30V DC MCH + XF + MX

Number of poles3P 3 Poles4P 4 Poles

Type based on breaking capacityN Circuit breaker/ switch disconnector Icu=Ics=Icw(1sec)=50kAH Circuit breaker/ switch disconnector Icu=Ics=Icw(1sec)=65kA

Current rating08 800A10 1000A12 1250A16 1600A20 2000A25 2500A32 3200A40 4000A

Example 1 MVS32N4EW6LMVS 32 N 4 E 6 L

EasyPact MVS

3200A 50kA 4 Pole Electrical operated Draw-out type LSIG protection Basic trip unit with LED indications

Example 2 MVS16H3MF0DMVS 16 H 3 M F 0 D

EasyPact MVS

1600A 65kA 3 Pole Manual operated No protection Switch disconnector

Page 81: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

F-3

EasyPact MVSConnection

Catalogue numbersand order form

Connection3P 4P

Fixed circuit breakersRear connection (vertical or horizontal mounting) / Replacement kit (3 or 4 parts)

800-2000 A Vertical 47964 47965Horizontal 47964 47965

2500/3200 A Vertical 47966 47967Horizontal 47966 47967

4000 A Vertical 47968 47969Horizontal 47970 47971

Installation manual MVS21735Draw-out circuit breakersRear connection (vertical or horizontal mounting) / Replacement kit (3 or 4 parts)

800-2000 A Vertical 47964 47965Horizontal 47964 47965

2500/3200 A Vertical 47966 47967Horizontal 47966 47967

4000 A Vertical 47968 47969Horizontal 47970 47971

Installation manual MVS21735

Connection accessoriesInterphase barriers / Replacement kit (3 parts)

48599 48599For draw-out rear-connected circuit breaker 48600 48600Installation manual MVS21735

E46

446

E46

445

E46

446

E46

445

E46

428

Page 82: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

F-4

ET Trip System & accessoriesE

9554

0E

4667

1D

B10

5360

CD

B50

0038

ET trip units & accessoriesBattery + cover

Battery (1 part) 33593Cover (1 part) 33592

External sensorsExternal sensor for earth-fault protection (TCE) / 1 part

Sensor rating 400/2000 A 340351000/4000 A 34036

External power supply module (AD) / 1 part24-30 V DC 5444048-60 V DC 54441100-125 V DC 54442110-130 V AC 54443200-240 V AC 54444380-415 V AC 54445

Test equipments / 1 PartHand held test kit (HHTK) 33594

menu

Page 83: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

F-5

EasyPact MVSRemote operation

Catalogue numbersand order form

Remote operationGear motor

MCH (1 part)AC 50/60 Hz 100/130 V 47893

200/240 V 47894380/415 V 47896

DC 24/30 V 4788848/60 V 47889100/125 V 47890200/250 V 47891

Terminal block (1 part) 47074For draw-out circuit breaker 47849

Installation manual MVS21736Closing release (XF)

Standard coil (1 part)AC 50/60 HzDC

24/30 V DC, 24 V AC 3365948/60 V DC, 48 V AC 33660100/130 V AC/DC MVS15511200/250 V AC/DC MVS15512380/480 V AC MVS15513

Terminal block (1 part) 47074For draw-out circuit breaker 47849

Installation manual MVS21736Opening release (MX)

Standard coil (1 part)AC 50/60 HzDC

24/30 V DC, 24 V AC 3365948/60 V DC, 48 V AC 33660100/130 V AC/DC 33661200/250 V AC/DC 33662380/480 V AC 33664

Terminal block (1 part) 47074For draw-out circuit breaker 47849

Installation manual MVS21736

E95

172

E95

170

E95

170

E95

169

E95

171

E95

169

E95

171

E95

169

E95

171

Page 84: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

F-6

Remote operationUndervoltage release MN

Undervoltage release (1 part)AC 50/60 HzDC

24/30 V DC, 24 V AC 3366848/60 V DC, 48 V AC 33669100/130 V AC/DC 33670200/250 V AC/DC 33671380/480 V AC 33673

Terminal block (1 part) 47074For draw-out circuit breaker 47849

Installation manual MVS21736MN delay unit

MN delay unit (1 part)R (non-adjustable) Rr (adjustable)

AC 50/60 HzDC

48/60 V AC/DC 33680100/130 V AC/DC 33684 33681200/250 V AC/DC 33685 33682380/480 V AC/DC 33683

Installation manual MVS21736

E95

170

E46

694

E95

169

E95

171

Page 85: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

F-7

EasyPact MVSChassis locking and accessories

Catalogue numbersand order form

Chassis locking“Disconnected” position locking / 1 part

By padlocksVCPO Standard

By Profalux keylocks1 lock with 1 key + adaptation kit 649342 locks 1 key + adaptation kit 64935

4288842878

Adaptation kit (without key locks) 48564By Ronis keylocksRonis 1 lock with 1 key + adaptation kit 64937

2 locks 1 key + adaptation kit 64938Ronis 1 lock+ 1 key (without adaptation kit) 41940Ronis 2 locks + 1 key (without adaptation kit) 41950Adaptation kit (without key locks) 48564

Installation manual MVS21737Door interlock / 1 part

Right and left-hand side of chassis (VPECD or VPECG) 47914

Installation manual MVS21737

Chassis accessoriesAuxiliary terminal shield (CB) / 1 part

800/4000 A 3P 649424P 48596

Installation manual MVS21737Safety shutters + locking block / 1 part

800/4000 A 3P 487214P 48723

Installation manual MVS21737Shutter locking block (for replacement) / 1 part

2 parts for 800/4000 A 48591

Installation manual MVS21737

Earthing kit for chassis3P 4P

Types for N/H/NA/HA48433 48434

DB

1174

58E

4645

2E

4645

8E

4645

9E

4646

0

Page 86: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

F-8

Clusters

Clusters1 disconnecting contact cluster for chassis (see table below) (part 1) 33166

Table : number of clusters required for the different chassis modelsChassis rating (A) EasyPact MVS(3P) EasyPact MVS(4P)

N H NA HA N H NA HA800 12 12 12 12 16 16 16 161000 12 12 12 12 16 16 16 161250 12 12 12 12 16 16 16 161600 12 12 12 12 16 16 16 162000 12 12 12 12 16 16 16 162500 24 12 24 12 32 16 32 163200 36 36 36 36 48 48 48 484000 42 42 42 42 56 56 56 56

Racking handleRacking handle 47944

E95

538

E95

561

Page 87: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

F-9

Circuit breaker lockingPushbutton locking device / 1 part

By padlocks 48536

Installation manual MVS21736OFF position locking / 1 part

By Profalux keylocks1 lock with 1 key + adaptation kit 649282 locks 1 keys + adaptation kit 64929

4288842878

Adaptation kit (without key locks) 64925By Ronis keylocksRonis 1 lock with 1 key + adaptation kit 64931

2 locks 1 keys + adaptation kit 64932Ronis 1 lock+ 1 key (without adaptation kit) 41940Ronis 2 locks + 1 key (without adaptation kit) 41950Adaptation kit (without key locks) 64925

Installation manual MVS21736Mechanical operation counter / 1 part

Operation counter CDM 48535

Installation manual MVS21736Escutcheon and accessories / 1 part

E46

669

E46

670

Escutcheon Cover Blanking plate

Draw-outEscutcheon 48601 48603Transparent cover (IP 54) - 48604Escutcheon blanking plate 48605 48605

Installation manual MVS21736Front cover (3P / 4P) / 1 part

MVS Front cover MVS21808

Installation manual MVS21736Spring charging handle / 1 part

Spring charging handle 47940

Installation manual MVS21736Arc chute for EasyPact MVS / 1 part

3P 4PType N/NA MVS21807Type H/HA MVS21807Installation manual MVS21736

E46

666

E46

735

DB

1256

17C

DB

5000

61C

DB

5000

58E

9553

6C

DB

5000

59

EasyPact MVSCircuit breaker locking and accessories

Catalogue numbersand order form

Page 88: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

F-10

Mechanical interlocking for source changeover

Mechanical interlocking for source changeoverInterlocking of 2 devices using cables (1)

Choose 2 adaptation sets (1 for each device + 1 set of cables)4792647926

1 set of 2 cables 33209(1)

Installation manual MVS21738Interlocking of 3 devices using cables

486104860948608

Installation manual MVS21738

CD

B50

0053

CD

B50

0060

Page 89: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

F-11

Indication contactsON/OFF indication contacts (OF) / 12 parts

1 additional block of 4 contacts 4788747074

For draw-out circuit breaker 47849

Installation manual MVS21736“Ready to close” contact (1 max.) / 1 part

1 changeover contact (5 A - 240 V) 4708047074

For draw-out circuit breaker 47849

Installation manual MVS21736“Connected, disconnected, test position” indication contact (carriage switches) / 1 part

Changeover contacts 6 A - 240 V 33170

Installation manual MVS21736Auxiliary terminals for chassis alone

3 wire terminal (1 part) 478496 wire terminal (1 part) 47850Jumpers (10 parts) 47900

E46

689

E46

438

E46

661

EasyPact MVSIndication contacts

Catalogue numbersand order form

Page 90: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

F-12

Instructions

InstructionsEasyPact MVS User Manual (English) MVS21734

MVS21735Circuit breaker accessories MVS21736Chassis accessories MVS21737Interlocking of EasyPact MVS devices MVS21738

Page 91: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

F-13

And enter the appropriate information in the rectangles

Circuit breaker or switch-disconnector Quantity

Rating A

Circuit breaker N/ H

Switch Disconnector NA/HA

Number of poles 3 or 4

Type of equipment

Draw out with chassis

Draw out without chassis

(moving part only)

Chassis alone

Operating Mechanism Manual Operated

Electrical Operated

MCH - Gear motor V

XF - Closing coil V

MX - Shunt/Opening voltage release V

ET Trip System0- Without display 2I 5S 6G

A - Current Metering 2I 5S 6G

V - Voltage Metering 2I 5S 6G

LR - Long-time rating plug Standard 0.4 to 1 Ir

ConnectionHorizontal Top Bottom

Vertical Top Bottom

EasyPact MVS

EasyPact MVSCircuit breaker and Switch-disconnectorsCustomer Order form

Indication contactsOF - ON/OFF indication contacts

Standard 1 block of 4 OF 10 A-240/380V AC

Additional 1 block of 4 OF 6 A-240/380V AC

SDE - “fault-trip” indication contact

Standard 1 SDE 5A -240/380V AC

OptionalCarriage switches 8 A-240/380V AC

CE - “Connected” position qty

CT - “Test” position qty

CD - “Disconnected” position qty

Remote tripping MN - Under voltage release V

R - 0.25s

Rr - Adjustable delay unit

AD - V

TCE - 400/2000A

TCE - 1000/4000A

PF - “Ready to close” contact 5A-240/380V AC

LocksVBP - ON/OFF pushbutton locking (by transparent cover using padlock)

VSPO - Device locking in OFF position by key lock (Only one key lock per ACB possible)

Key lock kit (w/o key lock) Ronis

1 key lock Ronis

2 identical key locks, 1 key Ronis

Chassis locking in “Disconnected” position:

VSPD - by key locks Key lock kit (w/o key lock) Ronis

1 key lock Ronis

2 identical key locks, 1 key Ronis

Door Interlock - VPEC On left-hand side of chassis (LH)

On right-hand side of chassis (RH)

Mechanical Interlocking of ACBs with Cable1 Normal source & 1 replacement source (2 devices)

2 sources with coupler on busbars (3 devices)

AccessoriesVO - Safety shutters on chassis Standard

CDP - Escutcheon Standard

Safety Shutter locking blocks

CP - Transparent cover for escutcheon

OP - Blanking plate for escutcheon

CDM - Mechanical operation counter for MVS

CB -

EIP - Interphase barriers

HHTK - Hand held test kit

Notes:

Order ref no:

Date:

Product ref no:OA No.

Catalogue numbersand order form

Page 92: ACB EasyPact MVS...> Conforms to IEC 60947- 2 & 3 EasyPact MVS08 to MVS40 EasyPact MVS Benefits for every customer 5 Panel builders/ contractors End Users Designers > Single frame

© 2

014

- Sch

neid

er E

lect

ric -

All

right

s re

serv

ed.

08-2018LVED211021EN

Schneider Electric Industries SAS35, rue Joseph MonierCS 30323

RCS Nanterre 954 503 439Capital social 896 313 776 €www.schneider-electric.com