User manual for circuit breakers and switch-disconnectors Easypact SPS
1HRB75971 - 03/2013HRB75971 - 03/2013
Contents
Identifying Easypact SPS 2Rating plate 2Discovering Easypact SPS 3Components 3Using Easypact SPS 7Understanding the controls and indications 7Charging the circuit breaker 8Closing the circuit breaker 9Opening the circuit breaker 10Resetting after a fault trip 11Locking the controls 12Using the Easypact SPS drawout chassis 14Identifying the circuit breaker positions 14Racking 15Locking the switchboard door 18Locking the circuit breaker in position 19Locking the safety shutters 21
Identifying the electrical auxiliaries 22Identification of the connection terminals 22Operation 23Electrical diagrams 24Discovering Easypact SPS Trip system accessories 26ET Trip system 26Indication contacts 27Auxiliaries for remote operation 29Device mechanical accessories 32Chassis accessories 34Inspecting and testing before use 36Initial tests 36What to do when the circuit breaker trips 37Maintaining Easypact SPS performance 38Recommended maintenance program 38Maintenance operations 39Ordering replacement parts 40Troubleshooting and solutions 41Checking Easypact SPS operating conditions 43Environmental conditions 43
51201116AA-P01a09.indd 1 2013/3/23 0:54:33
2 HRB75971- 03/2013
Easy Pact
UiUimp
Ue(V)220/410~
Ics=100%Icucat.B
12kV
Icu(kA) Icw(kA/1s)50 42
50/60HzIEC / EN 60947-2
SPS 12F
1000V
Rated current (x 100 A)
Suitability f or isolation
P erf or mance le ve l
Rated insulation le ve l
Rated short-time withstand current
Rated operational voltage
Icu - ultimate breaking capacity
Impulse withstand vo ltage
Ics - rated service breaking capacity
T ype of de vice: circuit break er or sw itch-disconnector
F requency
Standards
DB
1193
13
DB
1193
14
Rating plateIdentifying EasyPact
51201116AA-P01a09.indd 2 2013/3/23 0:05:02
3HRB75971 - 03/2013
Discovering EasyPact
EasyPact circuit breakers are available in drawout and fixed versions.The drawout version is mounted on a chassis and the fixed version is installed using fixing brackets.
Drawout version
Fixed version
E51
321A
E51
322A
Components
51201116AA-P01a09.indd 3 2013/3/23 0:05:04
4 HRB75971- 03/2013
Chassis
DB
1193
15
Carr ying gr ip
Dr aw out gr ip
Carr iage sw itch ter minal s
Te rm inals f or control-unit and f ault-tr ip indication contacts
Door inter lo ck
Arc-chute co ve r
Disconnecting-contact cluster
A uxilia ry ter minal shiel d
Control auxilia ry ter minal s
ON/OFF indication contact ter minal s Carr iage sw itch ter minal s
Saf ety shutters
Shutter lo ck ing bl oc ks
"Connected", "test" or "disconnected" position indicator
Loc king by key lo ck s
Crank storage
Crank so cke t
P osition release b utton
Loc king by padloc ks
Crank
Discovering EasyPact Components
51201116AA-P01a09.indd 4 2013/3/23 0:05:05
5HRB75971 - 03/2013
Drawout circuit breaker / switch-disconnector
DB
1193
16
MCH gear motor fo r electr ical charging of the operating mechanism
Operating-mechanism charging handl e
PF "ready to close" contact Te rm inals f or control unit, f aul t indication contacts , control auxilia ri es and auxilia ry contacts
MN under vo ltage release
XF closing release
MX opening release
Closing pushb utton
Carr ying gr ip
SDE "fault-tr ip" indication contact
Arc chute
Trip unit*
OF "ON/OFF" indication contacts
Opening pushb utton
Ke yloc k f or lo ck ing in open position
Side plate fo r dr aw out de vice
Discovering EasyPact Components
* Switch disconnector is without trip unit
51201116AA-P01a09.indd 5 2013/3/23 0:05:06
6 HRB75971- 03/2013
DB
1193
17
MCH gear motor forelectrical charging of theoperating mechanism
Operating-mechanismcharging handle
PF "ready to close" contactTerminals for control unit and faultindication contacts
MN undervoltage release
XF closing release
MX opening release
Closing pushbutton
Carrying grip
SDE "fault-trip" indication contact
Trip unit*
OF "ON/OFF" indication contacts
Opening pushbutton
Side plate for fixeddevice
Auxiliary contact terminals
Control auxiliary terminals
Arc chute
Keylock for lockingin open position
Fixed circuit breaker / switch-disconnector
DB
1193
18
Indicator f or position of the main contacts
"Spr ings charged" and "Ready to close" indicato r
Loc king by padloc k, lead-seal co ve r or scre ws f or pushb uttons
Rating plate
Tr ip indication b utton used to reset bef ore closing
Front
Discovering EasyPact Components
* Switch disconnector is without trip unit
51201116AA-P01a09.indd 6 2013/3/23 0:05:06
7HRB75971 - 03/2013
Understanding the controls and indications
Circuit breaker open and discharged
Circuit breaker closed and discharged
Circuit breaker open, charged and not "ready to close"
Circuit breaker closed and charged
Circuit breaker open, charged and "ready to close"
DB
1193
19
Push OFFOI
Push ON
Push OFFOI
Push ON
Push OFFOI
Push ON
Push OFFOI
Push ON
E51
488A
E51
489A
E51
490A
E51
491A
E51
492A
Push OFFOI
Push ON
Using EasyPact
51201116AA-P01a09.indd 7 2013/3/23 0:05:15
8 HRB75971- 03/2013
The charge status is indicated as follows. The springs in the circuit breaker operating mechanism must be charged to store the energy required to close the main contacts. The springs may be charged manually using the charging handle or automatically by the optional MCH gear motor.
Manual charging.Pull the handle down six times until you hear a "clack".
Automatic charging.If the MCH gear motor is installed, the spring is automatically recharged after each closing.
DB
1193
20
DB
1193
37
E46
790A
Charging the circuit breaker
Push OFFOI
Push ON
or
Using EasyPact
51201116AA-P01a09.indd 8 2013/3/23 0:05:16
9HRB75971 - 03/2013
Using EasyPact Closing the circuit breaker
Closing conditionsClosing (i.e. turning the circuit ON) is possible only if the circuit breaker is "ready to close". The prerequisites are the following:
b device open (OFF) b springs charged b no opening order present.
The circuit breaker will not close unless it is "ready to close" when the order is given.
Closing the circuit breakerLocally (mechanical)Press the mechanical ON pushbutton.
Remotely
Anti-pumping functionThe purpose of the mechanical anti-pumping function is to ensure that a circuit breaker receiving simultaneous opening and closing orders does not open and close indefinitely. If there is a continuous closing order, after opening the circuit breaker remains open until the closing order is discontinued. A new closing order is required to close the circuit breaker. A new order is not required if the closing release is wired in series with the PF "ready to close" contact.
When connected to a remote control panel, the XF closing release can be used to close the circuit breaker remotely.
XF
Push OFFOI
E51
291A
E51
292A
E60
047A
E51
493A
DB
1193
21
E51
294A
Device not "ready to close"
Device "ready to close"
EasyPact
51201116AA-P01a09.indd 9 2013/3/23 0:05:19
10 HRB75971 - 03/2013
Opening the circuit breaker
LocallyPress the OFF pushbutton.
RemotelyUse one of the following solutions:
b one MX opening releases (MX1) b one MN undervoltage release b one MN undervoltage release with a delay unit.
When connected to a remote control panel, these releases can be used to open the circuit breaker remotely.
E60
047A
DB
1193
21
E51
294A
E51
296A
E51
499A
3 6
MNUVR
1012
100/130 V
AC/DC
S
0.5 1
3 1.5
Retardateur de MN
Time delay for UVR
4 5 6
1 2 3
1 2 3
MX / MN Delay unit
Using Easypact
51201116AA-P10a18.indd 10 2013/3/23 0:05:32
11HRB75971 - 03/2013HRB75971 - 03/2013
Using Easypact
The circuit breaker signals a fault trip by: b a mechanical indicator on the front b one SDE "fault-trip" indication contacts.
LocallyIf the circuit breaker is not equipped with the automatic reset option, reset it manually.
Resetting after a fault tripE
6004
7A
DB
1193
22
RESET
51201116AA-P10a18.indd 11 2013/3/23 0:05:32
12 HRB75971 - 03/2013
Locking the controlsDisabling circuit-breaker local closing and opening
Pushbutton locking using a padlock (shackle diameter 5 to 8 mm), a lead seal or screws.
DB
1193
23
UnlockingRemove the padlock, lead seal or screws.
DB
1193
24
DB
1193
25
DB
1193
27
DB
1193
238
Padlock. Lead seal.
LockingClose the covers. Insert the padlock
shackle, lead seal or screws.
DB
1193
28
DB
1193
29
DB
1193
30
Lift the covers and swing them down.
The pushbuttons are no longer locked.
Push OFF
OPush ON
I
Push OFF
OPush ON
I
DB
1193
26
Screws.
Using Easypact
51201116AA-P10a18.indd 12 2013/3/23 0:05:34
13HRB75971 - 03/2013HRB75971 - 03/2013
CheckThe closing control is inoperative.
E51
446A
UnlockingInsert the key.
Two types of keylocks are available
E60
008A
E60
009A
E60
010A
DB
1184
79
Turn the key. The key cannot be removed.
RONIS PROFALUX
Locking the controls with a keylockLockingOpen the circuit breaker.
E51
499A
E51
448A
E51
449A
Turn the key. Remove the key.
E51
270A
Using Easypact Locking the controlsDisabling local and remote closing
51201116AA-P10a18.indd 13 2013/3/23 0:05:38
14 HRB75971 - 03/2013
Using the Easypact drawout chassis
Identifying the circuit breaker positions
b "connected" position
DB
1193
41
The indicator on the front signals the position of the circuit breaker in the chassis.
E51
453A
b "test" position
E51
454A
DB
1193
42
b "disconnected" position
E51
455A
DB
1193
43
Test
Test
10.9 mm
Test
32.2 mm
DB
1193
44
51201116AA-P10a18.indd 14 2013/3/23 0:05:44
15HRB75971 - 03/2013HRB75971 - 03/2013
Racking
PrerequisitesTo connect and disconnect Easypact, the crank must be used. The locking systems, padlocks and the racking interlock all inhibit use of the crank.
Withdrawing the circuit breaker from the "connected" to "test" position, then to "disconnected" position
The circuit breaker is in "connected" position.
The circuit breaker is in "test" position.
DB
1197
17
The circuit breaker is in "test" position. Remove the crank or continue to "disconnected" position.
The circuit breaker is in "disconnected" position.
These operations require that all chassis-locking functions be disabled (see page 19).
Using the Easypact drawout chassis
51201116AA-P10a18.indd 15 2013/3/23 0:05:44
16 HRB75971 - 03/2013
Using the Easypact drawout chassis
Racking
Position the circuit breaker on the rails.Check that it rests on all four supports.
DB
1193
48
Open the circuit breaker (in any case, it opens automatically during connection).
E51
499A
Push the circuit breaker into the chassis, taking care not to push on the control unit.
For complete information on Easypact handling and mounting, see the installation manual(s).
Before mounting the circuit breaker, make sure it matches the chassis.
Inserting Easypact
DB
1193
49
DB
1193
50
Removing the railsPress the release tabs and pull the rails out.
Press the release tabs to push the rails in.
DB
1193
47
DB
1193
46
1
2 3
DB
1193
51
51201116AA-P10a18.indd 16 2013/3/23 0:05:48
17HRB75971 - 03/2013HRB75971 - 03/2013
Racking the circuit breaker from the "disconnected" to "test" position, then to "connected" position
The device is in "disconnected" position.
The device is in "test" position.
The device is in "test" position. Remove the crank or continue to "connected" position.
The device is in "connected" position.
Using the Easypact drawout chassis
Racking
DB
1197
18
51201116AA-P10a18.indd 17 2013/3/23 0:05:48
18 HRB75971 - 03/2013
Locking the switchboard door
Disabling door openingClose the door.
DB
1193
57
Enabling door openingPut the Easypact in "disconnected" position.
E51
469A
The door is unlocked.
The locking device is installed on the left or right-hand side of the chassis. b When the circuit breaker is in "connected" or "test" position, the latch is lowered
and the door is locked b When the circuit breaker is in "disconnected" position, the latch is raised and the
door is unlocked.
DB
1193
54E
5146
5A
DB
1193
55
DB
1193
56
Put the Easypact in "test" or "connected" position.
The door is locked.
Using the Easypact drawout chassis
51201116AA-P10a18.indd 18 2013/3/23 0:05:51
19HRB75971 - 00 - 03/2013
Using the Easypact drawout chassis
Locking the circuit breaker in position
Circuit breaker in "disconnected" position.
DB
1193
58Pull out the tab.
DB
1193
60
DB
1193
59
Insert the shackle (max. diameter 5 to 8 mm) of the padlock(s).
DB
1193
64
DB
1193
61
Padlocks and keylocks may be used together.
UnlockingRelease the tab.
The crank can be inserted.
The crank cannot be inserted.
DB
1193
62
DB
1193
63
Test
1 2
3
1 2
3 4
Combination of locking systemsTo disable connection of the circuit breaker in "disconnected" position in thechassis, use as needed:
b one to three padlocks b one or two keylocks b a combination of the two locking systems.
Disabling connection when the circuit breaker is in "disconnected" position, using one to three padlocks (maximum shackle diameter 5 to 8 mm)Locking
Remove the padlock(s).
If specified when ordering the chassis, this locking function may be adapted to operate in all positions ("connected", "test" and "disconnected"), instead of in "disconnected" position alone.
51201116AA-P19a26.indd 19 2013/3/23 0:09:42
20 HRB75971 - 00 - 03/2013
1 3
Unlocking
Two types of keylocks are available
DB
1193
69
The crank can be inserted.
Insert the key(s).
DB
1193
70
DB
1193
71
Turn the key(s).
E51
270A
RONIS
DB
1187
49
PROFALUX
2
Padlocks and keylocks may be used together.
Remove the key(s). The crank cannot be inserted.
DB
1193
67
DB
1193
6833 44
Disabling connection when the circuit breaker is in "disconnected" position, using one or two keylocks.Locking
DB
1193
65
Circuit breaker in "disconnected" position.
DB
1193
66
Turn the key(s).
T est
1 22
Using the Easypact drawout chassis
Locking the circuit breaker in position
51201116AA-P19a26.indd 20 2013/3/23 0:09:45
21HRB75971 - 00 - 03/2013
Locking the safety shuttersPadlocking inside the chassis
Four locking possibilities: using one or two padlocks (maximum shackle diameter 5 to 8 mm) for each shutter
DB
1193
75D
B11
9376
Top and bottom shutters not locked.
Top shutter not locked.Bottom shutter locked.
Top shutter locked.Bottom shutter not locked.
Top and bottom shutters locked.
Using the Easypactdrawout chassis
51201116AA-P19a26.indd 21 2013/3/23 0:09:45
22 HRB75971 - 00 - 03/2013
CD1814812811
CE1 CT1314 914312 912311 911
OF4444241
OF3343231
OF2 OF124 1422 1221 11
MXC2C3C1
MND2
D1
XFA2A3A1
PF254252251
UC1 UC2 SDEZ5Z3Z1
Z4Z2
T3T1
T4T2
848281
MCHB2B3B1
MXC2C3C1
XFA2A3A1
PF254252251
UC1 UC2 SDEZ5Z3Z1
Z4Z2
T3T1
T4T2
848281
MCHB2B3B1
OF4444241
OF3343231
OF2 OF124 1422 1221 11
MND2
D1
SDE
DB
1193
77
Identifying the electrical auxiliaries
Identification of the connection terminalsLayout of terminal blocks
Key: Only for ET6G
SDE, OF1, OF2 supplied as standard and OF3,OF4 optional
51201116AA-P19a26.indd 22 2013/3/23 0:09:46
23HRB75971 - 00 - 03/2013
DB
1193
78
Operation
Circuit breaker
closed
completely closed completely open
main contacts
OF: ON/OFF (closed/open)indication changeover contacts
open
closed open
open closed
test position
separation of the auxiliary circuits
separation of the main circuits
completely connected
open
closed
closed
open
closed
open
CE: connected-positioncarriage switch
CT: test-position carriageswitch
CD: disconnected-positioncarriage switch
closed
open open
closed
completely disconnected
DB
1193
79
The ON/OFF indication contacts signal the status of the device main contacts.
ChassisFor information on the separation distance of the main circuits in the "test" and "disconnected" positions, see page 16.
The carriage switches indicate the "connected", "test" and "disconnected" positions.
Identifying the electrical auxiliaries
51201116AA-P19a26.indd 23 2013/3/23 0:09:46
24 HRB75971 - 00 - 03/2013
2.0 6G
Identifying the electrical auxiliaries
Electrical diagramsFixed and drawout devices
b
b
E60
062A
The diagram is shown with circuits de-energised, all devices open, connected and charged and relays in normal position.
E60
063A
E60
064A
E60
067A
Power
UC1: Z1-Z5 zone selective interlocking; Z1 = ZSI OUT SOURCE Z2 = ZSI OUT; Z3 = ZSI IN SOURCE Z4 = ZSI IN ST (short time) Z5 = ZSI IN GF (earth fault)
UC2: T1, T2, T3, T4 = external neutral;
Control unit
Control unit Remote operation
SDE1 : Fault-trip indication contact (supplied as standard)
MN: Undervoltage release
MX1: Shunt release XF: Closing release
PF: "Ready to close" contact
MCH : Gear motor
2.0: Basic Protection6G: 2.0 + Isd + Ig
MX
C2
C1
BPO
A2
A1
BPF
XFPF
252
254
251
read
y to
clos
e
B1
MCH
B3
B2
char
ged
CH
E60
065A
E46
136A
E46
137A
E60
066A
T4T3T2T1Z4
ET Trip System
Z4Z3Z2Z1Z5 Z1 Z2N L3L2L1
Q
Powerupstream cb downstream
cb
Z5
Z3Z2Z1 Z3 Z4 Z5
I
SG
1
SG
2
X1
X2
Remote operation
Remote operation SDE1 MN MX1 XF PF MCH
84 D2 C2 A2 254 B2 82 252 B3 81 D1 C1 A1 251 B1
Control unit UC1 UC2
Z5 Z3 Z4 T3 T4 Z1 Z2 T1 T2
81
82 84
SDE
faul
t
D2
D1
AT
MN
Note: Z1...Z5 & T1..T4 are available only in ET6G trip system
51201116AA-P19a26.indd 24 2013/3/23 0:09:48
25HRB75971 - 00 - 03/2013
E60
068A
E60
069A
E60
070A
E60
076A
Indication contacts
(*) 440/480 V AC gear motor for charging(380 V motor + additional resistor)
CD1: Disconnected-position
CT1: Test-positioncontacts
CE1: Connected-position
12 1411
22 2432 3431 21
OF4
42 4441
OF3 OF2 OF1
open closed
Key: Drawout device only
SDE,OF1, OF2, supplied as standard Interconnected connections (only one wire per connection point)
914
912
911
CT1
test
Chassis contacts
Chassis contacts
B1
CN2 - 440/480 V
9 11
MCH380V
CH
B3 B2
R440/480 V"charged LED"
CN1 - 440/480 V
XXX
E60
075A
Indication contacts
CD1 CE1 CT1 814 314 914
812 312 912
811 311 911
Indication contactsOF4 OF3 OF2 OF1 44 34 24 14
42 32 22 12
41 31 21 11
Contacts châssis
Identifying the electrical auxiliaries
Electrical diagramsFixed and drawout devices
812
814
811
CD1
disconnected
311
312
314
CE1
connected
51201116AA-P19a26.indd 25 2013/3/23 0:09:48
26 HRB75971 - 00 - 03/2013
Discovering Easypact’s accessories
ET Trip System
E51
329A
E46
108A
.4.5.6
.7.8 .9
.95
.981
.512
48 12
1620
24
long time
alarm
Irtr(s)
x In@ 6 Ir
ET6G Trip System
ET trip system
Long-time rating plugs
b Standard equipment, one per device
b Part numbers (long-time rating plug and connectors not included, see below):ET 2.0
b Part numbers for connectors for ET6G
v for fixed device v for drawout device.
b Depending on the model, control units offer in addition:
v fault indications v trip system v ET6G trip system
b Standard equipment, one per control unit
b Part numbers for setting options:
v standard 0.4 to 1 x Ir setting
b The plugs determine the setting range for the long-time protection.
51201116AA-P19a26.indd 26 2013/3/23 0:09:50
27HRB75971 - 03/2013HRB75971 - 03/2013
Indication contacts
ON/OFF indication contacts (OF) b 4 changeover contacts b Breaking capacity at
cos ϕ = 0.3 (AC12 / DC12 as per 947-5-1)
v standard, minimum current 10 mA / 24 VV AC 240/380 6 A (rms)
480 6 A (rms)
V DC 24/48 2.5125 0.5250 0.3
"Fault-trip" indication contact (SDE) b Standard equipment on
circuit breakers, one SDE contact per device
b Not available for switch-disconnector versions.
b Changeover contact b Breaking capacity at
cos ϕ = 0.3 (AC12 / DC12 as per 947-5-1)
v standard, minimum current 10 mA / 24 VV AC 240/380 5 A (rms)
480 5 A (rms)
V DC 24/48 3 A125 0.3 A250 0.15 A
b Standard equipment, 2 OF per device
b Part numbers: v standard b Part numbers for
connectors: v for fixed device v for drawout device.
b The contact provides a remote indication of device opening due to an electrical fault.
b OF contacts indicate the position of the main contacts
b They trip when the minimum isolation distance between the main contacts is reached.
Discovering Easypact’s accessories
51201116AA-P28a37.indd 27 2013/3/23 0:16:44
28 HRB75971 - 03/2013
Indication contactsE
5133
2A "Ready to close" contact (PF) b Optional equipment,
one PF contact per device
b Part numbers (connectors not included, see below):
v standard b Part numbers for
connectors: v for fixed device v for drawout device.
b The contact indicates that the device may be closed because all the following are valid:
v circuit breaker is open v spring mechanism is
charged v a maintained closing
order is not present v a maintained opening
order is not present.
b Changeover contact b Breaking capacity at
cos ϕ = 0.3 (AC12 / DC12 as per 947-5-1)
v standard, minimum current 10 mA / 24 VV AC 240/380 5 A (rms)
480 5 A (rms)
V DC 24/48 3 A125 0.3 A250 0.15 A
Discovering Easypact’s accessories
51201116AA-P28a37.indd 28 2013/3/23 0:16:46
29HRB75971 - 03/2013HRB75971 - 03/2013
Discovering Easypact’s accessories
Auxiliaries for remote operation
Gear motor (MCH) b The gear motor
automatically charges the spring mechanism.
b Power supply: v V AC 50/60 Hz: 48/60
100/130 - 200/240 -277 440/480
v V DC: 24/30 - 48/60 100/125 - 200/250
b Operating threshold:0.85 to 1.1 Un
b Consumption:180 VA or W
b Inrush current:2 to 3 In for 0.1 second
b Charging time: 3 seconds max.
b Operating rate: maximum 3 cycles per minute
b CH contact: see page 32.
E51
294A Opening releases MX closing release XF
b Optional equipment, 1 MX releases per device, 1 XF per device
b The function (MX or XF) is determined by where the coil is installed
b Part numbers (connectors not included, see below)V AC 50/60 Hz, V DC:
v standard version:24/30 AC/DC48/60 AC/DC100/130 AC/DC200/250 AC/DC380/480 AC
b Part numbers for connectors:
v for fixed device v for drawout device.
b The MX release instantaneously opens the circuit breaker when energised
b The XF release instantaneously closes the circuit breaker when energised, if the device is "ready to close".
b Optional equipment, one MCH gear motor per device
b Part numbers (connectors not included, see below):
v AC 50 / 60 Hz:48/60100/130200/240277/415440/480
v DC24/3048/60100/125200/250
b Part numbers for connectors:
v for fixed device v for drawout device.
b Power supply: v V AC 50 / 60 Hz:
24 48 - 100/130 - 200/250 -240/277 - 380/480
v V DC: 12 - 24/30 48/60 - 100/130 200/250
b Operating threshold: v XF: 0.85 to 1.1 Un v MX: 0.7 to 1.1 Un b Consumption: v pick-up: 200 VA or W
(80 ms) v hold: 4.5 VA or W b Circuit-breaker
response time at Un: v XF: 55 ms ± 10 v MX: 50 ms ± 10.
E46
790A
51201116AA-P28a37.indd 29 2013/3/23 0:16:48
30 HRB75971 - 03/2013
Discovering Easypact’s accessories
Instantaneous undervoltage releases (MN) b Optional equipment,
1 MN per device b Not compatible with the
MX/2 opening release b Part numbers
(connectors not included, see below)V AC 50/60 Hz, V DC:24/30 AC/DC48/60 AC/DC100/130 AC/DC200/250 AC/DC380/480 AC
b Part numbers for connectors:
v for fixed device v for drawout device.
b The MN release instantaneously opens the circuit breaker when its supply voltage drops.
b Power supply: v V AC 50/60 Hz: 24/48
100/130 - 200/250 240/277 - 380/480
v V DC: 24/30 - 48/60 100/130 - 200/250
b Operating threshold: v opening: 0.35 to 0.7 Un v closing: 0.85 Un b Consumption: v pick-up: 200 VA or W
(80 ms) v hold: 4.5 VA or W b Circuit-breaker
response time at Un: 40 ms ± 10.
Auxiliaries for remote operationE
5129
4AE
5129
6A
b Optional equipment, 1 MN with delay unit per device
b Delay-unit part numbers V AC 50/60 Hz, V DC:
v non adjustable:100/130 AC/DC200/250 AC/DC
v adjustable:48/60 AC/DC100/130 AC/DC200/250 AC/DC380/480 AC/DC.
Delay unit for MN releases b The unit delays
operation of the MN release to eliminate circuit-breaker nuisance tripping during short voltage dips
b The unit is wired in series with the MN and must be installed outside the circuit breaker.
b Power supply V AC 50/60 Hz, V DC:
v non adjustable:100/130 - 200/250
v adjustable:48/60 - 100/130200/250 - 380/480
b Operating threshold: v opening: 0.35 to 0.7 Un v closing: 0.85 Un b Consumption: v pick-up: 200 VA or W
(80 ms) v hold: 4.5 VA or W b Circuit-breaker
response time at Un: v non adjustable:
0.25 second v adjustable: 0.5 - 0.9 -
1.5 - 3 seconds.
3 6
MNUVR
1012
100/130 V
AC/DC
S
0.5 1
3 1.5
Retardateur de MN
Time delay for UVR
4 5 6
1 2 3
1 2 3
51201116AA-P28a37.indd 30 2013/3/23 0:16:49
31HRB75971 - 03/2013HRB75971 - 03/2013
Wiring of control auxiliariesUnder pick-up conditions, the level of consumption is approximately 150 to 200 VA.Consequently, for low supply voltages (12, 24, 48 V), cables must not exceed a maximum length determined by the supply voltage and the cross-section of the cables.Indicative values for maximum cable lengths (in meters)
12 V 24 V 48 V2.5 mm2 1.5 mm2 2.5 mm2 1.5 mm2 2.5 mm2 1.5 mm2
MN 100 % source voltage — — 58 36 280 16585 % source voltage — — 16 10 75 45
MX-XF 100 % source voltage 21 12 115 70 550 33085 % source voltage 10 6 75 44 350 210
Note: The indicated length is that for each of the two supply wires.
Discovering Easypact’s accessories
Auxiliaries for remote operation
51201116AA-P28a37.indd 31 2013/3/23 0:16:49
32 HRB75971 - 03/2013
Discovering Easypact’s accessories
Device mechanical accessoriesE
6049
9A Escutcheon (CDP) b Optional equipment,
one CDP per device b Part numbers: v for fixed device: 33718 v for drawout device:
33857.
b The CDP increases the degree of protection to IP 40 and IK 07 (fixed and drawout devices).
E60
498A
E60
498A
Transparent cover (CCP)
Blanking plate (OP)
b Optional equipment, one CCP per device equipped with a CDP
b Part number: 38859 (for drawout devices).
b Optional equipment, one OP per device
b Part number: 38858.
b Mounted with a CDP, the CCP increase the degree of protection to IP 54 and IK 10 (fixed and drawout devices).
b Used with the escutcheon, this option closes off the door cut-out of a cubicle not yet equipped with a device. It may be used with the escutcheon for both fixed and drawout devices.
51201116AA-P28a37.indd 32 2013/3/23 0:16:49
33HRB75971 - 03/2013HRB75971 - 03/2013
E60
347A Transparent cover for pushbutton locking using a
padlock, lead seal or screws b Optional equipment, one
locking cover per device b Part number.
b The transparent cover blocks access (together or separately) to the pushbuttons used to open and close the device
b Locking requires a padlock, a lead seal or two screws.
Device OFF position locking kit for keylocks b Optional equipment:
one locking kit (without keylock) per device
b Part numbers: v for Profalux keylocks v for Ronis keylocks v for Castell keylocks v for Kirk keylocks. b Optional equipment,
one locking system per device.
b The kit inhibits local or remote closing of the device
b Mounted on the chassis and accessible with the door closed, this system locks the circuit breaker in "disconnected" position using one or two keylocks.
E60
348A
Ronis
Profalux
Keylocks required for the device OFF position b One or two keylocks
per locking kit b Part numbers: v Ronis:
1 keylock v Profalux:
1 keylock.
E51
286A
DB
1191
80
Discovering Easypact’s accessories
Device mechanical accessories
51201116AA-P28a37.indd 33 2013/3/23 0:16:51
34 HRB75971 - 03/2013
Discovering Easypact’s accessories
Chassis accessories
Safety shutters b Optional equipment b Part numbers (set of
shutters for top and bottom) drawout, front/rear connection:
v 3 poles v 4 poles.
b Mounted on the chassis, the safety shutters automatically block access to the disconnecting contact cluster when the device is in the "disconnected" or "test" positions.
b IP 20 for chassis connections
b IP 40 for the disconnecting contact cluster.
E60
030A
Ronis
Profalux
Keylocks required with the "disconnected" position locking system
b One keylock per locking system
b Part numbers: v Ronis:
1 keylock1 keylock + one identical keylock
v Profalux:1 keylock1 keylock + one identical keylock
E51
286A
E51
273A
DB
1191
80
DB
1191
91
Top shutter closed Bottom shutter closed
E60
031A
Circuit breaker locking in "disconnected" position b Optional equipment,
one locking system per device
b Part numbers (keylocks not included):
v for Profalux keylocks v for Ronis keylocks v for Castell keylocks v for Kirk keylocks.
b Mounted on the chassis and accessible with the door closed, this system locks the circuit breaker in "disconnected" position using one or two keylocks.
If specified when ordering the chassis, this locking function may be adapted to operate in all positions ("connected", "test" and "disconnected"), instead of in "disconnected" position alone.
51201116AA-P28a37.indd 34 2013/3/23 0:16:52
35HRB75971 - 03/2013HRB75971 - 03/2013
Door interlock b Optional equipment,
one door interlock per chassis
b Part number.
b This device inhibits opening of the cubicle door when the circuit breaker is in "connected" or "test" position.
b It may be mounted on the left or right-hand side of the chassis.
E60
011A
Opush OFF
O OFF
Auxiliary terminal shield (CB) b Optional equipment,
one CB shield per chassis b Part numbers:
3 poles 4 poles.
b The shield prevents access to the terminal block of the electrical auxiliaries.
E60
345A
"Connected", "disconnected" and "test" position carriage switches (CE, CD, CT)
b Optional equipment, one to three carriage switches
b Standard configuration, 0 to 1 CE, 0 to 1 CD, 0 to 1 CT
b Part numbers: v standard v low level.
b The carriage switches indicate the three positions:CE: connected positionCD: disconnected position (when the minimum isolation distance between the main contacts and the auxiliary contacts is reached) CT: test position.
b Changeover contact b Breaking capacity at
cos ϕ = 0.3 (AC12 / DC12 as per 947-5-1)
v standard, minimum current 10 mA / 24 VV AC 240 8 A (rms)
380 8 A (rms)
V DC 24/48 2.5 A125 0.8 A250 0.3 A
E46
095A
Discovering Easypact’s accessories
Chassis accessories
51201116AA-P28a37.indd 35 2013/3/23 0:16:53
36 HRB75971 - 03/2013
Inspecting and testing before use
Initial testsProcedure
A general check of the circuit breaker takes only a few minutes and avoids any risk of mistakes due to errors or negligence.A general check must be carried out:
b prior to initial use b following an extended period during which the circuit breaker is not used.
A check must be carried out with the entire switchboard de-energised. In switchboards with compartments, only those compartments that may be accessed by the operators must be de-energised.
Electrical testsInsulation and dielectric-withstand tests must be carried out immediately after delivery of the switchboard. These tests are precisely defined by international standards and must be directed and carried out by a qualified expert.
Prior to running the tests, it is absolutely necessary to: b disconnect all the electrical auxiliaries of the circuit breaker (MCH, MX, XF, MN) b remove the long-time rating plug on the 2.0, 6G control units. Removal of the
rating plug disconnects the voltage measurement input.
Switchboard inspectionCheck that the circuit breakers are installed in a clean environment, free of any installation scrap or items (tools, electrical wires, broken parts or shreds, metal objects, etc.).
Conformity with the installation diagramCheck that the devices conform with the installation diagram:
b breaking capacities indicated on the rating plates b identification of the control unit (type, rating) b presence of any optional functions (remote ON/OFF with motor mechanism,
auxiliaries, measurement and indication modules, etc.) b protection settings (long time, short time, instantaneous, earth fault) b identification of the protected circuit marked on the front of each circuit breaker.
Condition of connections and auxiliariesCheck device mounting in the switchboard and the tightness of power connections.Check that all auxiliaries and accessories are correctly installed:
b electrical auxiliaries b terminal blocks b connections of auxiliary circuits.
OperationCheck the mechanical operation of the circuit breakers:
b opening of contacts b closing of contacts.
Check on the control unitCheck the control unit of each circuit breaker using the respective user manuals.
These operations must be carried out in particular before using a Easypact device for the first time.
51201116AA-P28a37.indd 36 2013/3/23 0:16:53
3751201116AA - 03/2013HRB75971 - 03/2013
Note the faultFaults are signalled locally and remotely by the indicators and auxiliary contacts installed on circuit breakers (depending on each configuration). See page 12 in this manual and the user manual of the control unit for information on the fault indications available with your circuit breaker.
Identify the cause of trippingA circuit must never be reclosed (locally or remotely) before the cause of the fault has been identified and cleared.A fault may have a number of causes:
b depending on the type of control unit, fault diagnostics are available. See the user manual for the control unit.
b depending on the type of fault and the criticality of the loads, a number of precautionary measures must be taken, in particular the insulation and dielectric tests on a part of or the entire installation. These checks and test must be directed and carried out by qualified personnel.
Inspect the circuit breaker following a short-circuit b Check the arc chutes (see page 40) b Check the contacts (see page 40) b Check the tightness of connections (see the device installation manual) b Check the disconnecting-contact clusters (see page 40).
Reset the circuit breakerThe circuit breaker can be reset locally or remotely. See page 12 in this manual for information on how the circuit breaker can be reset.
What to do when the circuit breaker trips
Inspecting and testing before use
51201116AA-P37a48.indd 37 2013/3/23 0:20:47
38 HRB75971 - 03/2013
Interval Operation ProcedureEach year b Open and close the device locally
and remotely, successively using the various auxiliaries
b Test the operating sequences b Test the control unit using the mini
test kit
v see pages 9 and 10
v see pages 9 and 10 v see the user manual of the
control unitEvery two years b Check the arc chutes
b Check the main contacts b Check the tightness of
connections
v see page 40 v see page 40 v see the device installation
manual
Maintaining Easypact performance
Recommended maintenance program
Periodic inspections required
Type of circuitbreaker
Maximumservice life
Service life of various parts
Arc chutes,main contacts
Connecting-rod springs, MCH,interlockingsystems
MX / XF / MNreleases
SPS08 to 16type F
25000 440 V: 6000 12500 12500
Recommended program for devices used under normal operating conditions:Ambient temperature: -5 °C / +70 °CNormal atmosphere
Part Intervening entity Description or procedure
Arc chutes b User v see page 40Main contacts b Inspection: user
b Replacement: Schneider After Sales Support
v see page 40
MCH gear motor b User v see page 8Mechanical interlocks b UserConnecting-rod springs
b Schneider After Sales Support
MX/MN/XF b User v see pages 9 and 10
Parts requiring replacement, depending on the number of operating cyclesThe following parts must be replaced periodically to lengthen the service life of the device (maximum number of operating cycles).
Part replacement must be programmed on the basis of the data below, listing the service life of the various parts in numbers of O/C cycles at the rated current.
Number of O/C cycles at the rated current
51201116AA-P37a48.indd 38 2013/3/23 0:20:47
3951201116AA - 03/2013HRB75971 - 03/2013
Arc chutes b Remove the fixing screws
Maintenance operations
Before undertaking any maintenance work, de-energise the installation and fit locks or warnings in compliance with all applicable safety standards.
22
E60
045A
If the control unit has a maintenance indicator, there is no need to systematically check the contacts.
If the contacts are worn, have the concerned poles replaced by the Schneider service centre.
1
E60
000A
33
E60
001A
E60
002A
Wear of main contacts b Remove the arc chutes b Visually check the contacts.
If necessary, contact Schneider After-sales support.
b Check the arc chutes: v chamber intact v separators not corroded.
If necessary, replace the arc chutes.
b Refit the arc chutes and secure with a tightening torque of 1.5 Nm.
Disconnecting-contact clusters b Grease the contacts using the grease listed on page 41, supplied by Schneider
Electric b Check the contacts as follows: v open the circuit breaker v de-energise the busbars v disconnect the circuit breaker v remove the circuit breaker v check the contact fingers (no sign of copper should be visible).
Replace any worn clusters.
Maintaining Easypact performance
51201116AA-P37a48.indd 39 2013/3/23 0:20:47
40 HRB75971 - 03/2013
Maintaining Easypact performance
Ordering replacement parts
Electrical accessoriesThe electrical accessories that may require replacement are the following:
b MCH gear motor b MX opening release(s) b XF closing release b MN undervoltage release.
See pages 33 and 34 in the "Auxiliaries for remote operation" section for their characteristics and part numbers.
E60
002A
E60
349A
Arc chutes b Part numbers
(1 arc chute): v type F
b One chute per pole.
Front b Part number. b 1 per 3- or 4-pole device.
Crank b Part number (1 crank). b 1 per device.E
5133
6A
b 1 per device.Charging handle
E60
496A
b Part number (1 handle).
Support for MX / XF / MN releases b Part number. b 1 per device.
Disconnecting-contact clusters b Part number (1 cluster).
Grease for disconnecting-contact clusters b Part number (1 can).
E46
237A
51201116AA-P37a48.indd 40 2013/3/23 0:20:48
4151201116AA - 03/2013HRB75971 - 03/2013
Maintaining Easypact performance
Troubleshooting and solutions
Problem Probable causes SolutionsCircuit breaker cannot be closed locally or remotely b Circuit breaker padlocked or keylocked in the
"open" position
b Circuit breaker interlocked mechanically in a source changeover system
b Circuit breaker not completely connected
b The reset button signalling a fault trip has not been reset
b Stored energy mechanism not charged
b MX opening shunt release permanently supplied with power
b MN undervoltage release not supplied with power
b XF closing release continuously supplied with power, but circuit breaker not "ready to close" (XF not wired in series with PF contact)
v disable the locking fonction
v check the position of the other circuit breaker in the changeover system
v modify the situation to release the interlock v terminate racking in (connection) of the
circuit breaker
v clear the fault v push the reset button on the front of the
circuit breaker v charge the mechanism manually v if it is equipped with a an MCH gear motor,
check the supply of power to the motor. If the problem persists, replace the gear motor (MCH)
v there is an opening order. Determine the origin of the order. The order must be cancelled before the circuit breaker can be closed
v there is an opening order. Determine the origin of the order.
v check the voltage and the supply circuit (U > 0.85 Un). If the problem persists, replace the release
v cut the supply of power to the XF closing release, then send the closing order again via the XF, but only if the circuit breaker is "ready to close"
Circuit breaker cannot be closed remotely but can be opened locally using the closing pushbutton
b Closing order not executed by the XF closing release
v check the voltage and the supply circuit (0.85 - 1.1 Un). If the problem persists, replace the XF release
Unexpected tripping without activation of the reset button signalling a fault trip
b MN undervoltage release supply voltage too low b Load-shedding order sent to the MX opening
release by another device
b Unnecessary opening order from the MX opening release
v check the voltage and the supply circuit (U > 0.85 Un)
v check the overall load on the distribution system
v if necessary, modify the settings of devices in the installation
v determine the origin of the order
Unexpected tripping with activation of the reset button signalling a fault trip
A fault is present : b overload b earth fault b short-circuit detected by the control unit
v determine and clear the causes of the fault
v check the condition of the circuit breaker before putting it back into service
Instantaneous opening after each attempt to close the circuit breaker with activation of the reset button signalling a fault trip
b Thermal memory
b Transient overcurrent when closing
b Closing on a short-circuit
v see the user manual of the control unit v press the reset button v modify the distribution system or the control-
unit settings v check the condition of the circuit breaker
before putting it back into service v press the reset button v clear the fault v check the condition of the circuit breaker
before putting it back into service v press the reset button
51201116AA-P37a48.indd 41 2013/3/23 0:20:48
42 HRB75971 - 03/2013
Maintaining Easypact performance
Troubleshooting and solutions
Problem Probable causes SolutionsCircuit breaker cannot be opened remotely, but can be opened locally
b Opening order not executed by the MX opening release
b Opening order not executed by the MN undervoltage release
v check the voltage and the supply circuit (0.7 - 1.1 Un). If the problem persists, replace the MX release
v drop in voltage insufficient or residual voltage (> 0.35 Un) across the terminals of the undervoltage release. If the problem persists, replace the MN release
Circuit breaker cannot be opened locally b Operating mechanism malfunction or welded contacts
v contact a Schneider service centre
Circuit breaker cannot be reset locally but not remotely b Insufficient supply voltage for the MCH gear motor
v check the voltage and the supply circuit (0.7 - 1.1 Un). If the problem persists, replace the MCH release
Nuisance tripping of the circuit breaker with activation of the reset button signalling a fault trip
b Reset button not pushed-in completely v push the reset button in completely
Impossible to insert the crank in connected, test or disconnected position
b A padlock or keylock is present on the chassis or a door interlock is present
v disable the locking function
Impossible to turn the crank b The reset button has not been pressed v press the reset button Circuit breaker cannot be removed from chassis b Circuit breaker not in disconnected position
b The rails are not completely out
v turn the crank until the circuit breaker is in disconnected position and the reset button out
v pull the rails all the way outCircuit breaker cannot be connected (racked in) b Cradle/circuit breaker mismatch protection
b The safety shutters are locked b The disconnecting-contact clusters are
incorrectly positioned b Cradle locked in disconnected position b The reset button has not been pressed,
preventing rotation of the crank b The circuit breaker has not been sufficiently
inserted in the cradle
v check that the cradle corresponds with the circuit breaker
v remove the lock(s) v reposition the clusters
v disable the cradle locking function v press the reset button
v insert the circuit breaker completely so that it is engaged in the racking mechanism
Circuit breaker cannot be locked in disconnected position b The circuit breaker is not in the right position
b The cranck is still in the cradle
v check the circuit breaker position by making sure the reset button is out
v remove the crank and store itCircuit breaker cannot be locked in connected, test or disconnected position
b Check that locking in any position is enabled b The circuit breaker is not in the right position
b The cranck is still in the cradle
v contact a Schneider Electric service centre
v check the circuit breaker position by making sure the reset button is out
v remove the crank and store it
51201116AA-P37a48.indd 42 2013/3/23 0:20:48
4351201116AA - 03/2013HRB75971 - 03/2013
Checking Easypactoperating conditions
E60
004A
E60
005A
E60
003A Ambient temperature
Easypace SPS devices can operate under the following temperature conditions: b the electrical and mechanical characteristics are stipulated for an ambient
temperature of -5 °C to +70 °C b circuit-breaker closing is guaranteed down to -35 °C b the control unit can be stored in an ambient temperature of -25 °C to +85 °C
Extreme atmospheric conditionsEasypace SPS devices have successfully passed the tests defined by the following standards for extreme atmospheric conditions:
b IEC 68-2-1: dry cold at -55 °C b IEC 68-2-2: dry heat at +85 °C b IEC 68-2-30: damp heat (temperature +55 °C, relative humidity 95 %) b IEC 68-2-52 level 2: salt mist.
Easypace SPS devices can operate in the industrial environments defined by standard IEC 947 (pollution degree up to 4).
It is nonetheless advised to check that the devices are installed in suitably cooled switchboards without excessive dust.
VibrationsEasypace SPS devices resist electromagnetic or mechanical vibrations.Tests are carried out in compliance with standard IEC 68-2-6 for the levels required by merchant-marine inspection organisations (Veritas, Lloyd’s, etc.):
b 2 to 13.2 Hz: amplitude ±1 mm b 13.2 to 100 Hz: constant acceleration 0.7 g.
Excessive vibration may cause tripping, breaks in connections or damage to mechanical parts.
Environmental conditions
51201116AA-P37a48.indd 43 2013/3/23 0:20:49
44 HRB75971 - 03/2013
E60
006A
2000
m
Altitude Easypace SPS devices are designed for operation at altitudes under 2000 metres.At altitudes higher than 2000 metres, the modifications in the ambient air (electrical resistance, cooling capacity) lower the following characteristics.
Altitude (m) 2000 3000 4000 5000Dielectric withstand 3500 3150 2500 2100 voltage (V)Rated insulation level (V) 1000 900 700 600Rated operational 440 440 440 440 voltage (V)Rated current (A) at 40 °C 1 x In 0.99 x In 0.96 x In 0.94 x In
E60
007A Electromagnetic disturbances
Easypace SPS devices are protected against: b overvoltages caused by devices that generate electromagnetic disturbances b overvoltages caused by an atmospheric disturbance or by a distribution-system
outage (e.g. failure of a lighting system) b devices emitting radio waves (radios, walkie-talkies, radar, etc.) b electrostatic discharges produced by users.
Easypace SPS devices have successfully passed the electromagnetic-compatibility tests (EMC) defined by the following international standards:
b IEC 947-2, appendix F b IEC 947-2, appendix B (trip units with earth-leakage function).
The above tests guarantee that: b no nuisance tripping occurs b tripping times are respected.
Checking Easypactoperating conditions
Environmental conditions
Cleaning b Non-metallic parts:
never use solvent, soap or any other cleaning product. Clean with a dry cloth only b Metal parts:
clean with a dry cloth whenever possible. If solvent, soap or any other cleaning product must be used, make sure that it does not come into contact with non-metallic parts.
51201116AA-P37a48.indd 44 2013/3/23 0:20:50
4551201116AA - 03/2013HRB75971 - 03/2013
Notes
51201116AA-P37a48.indd 45 2013/3/23 0:20:50
46 HRB75971 - 03/2013
51201116AA-P37a48.indd 46 2013/3/23 0:20:50
4751201116AA - 03/2013HRB75971 - 03/2013
Notes
51201116AA-P37a48.indd 47 2013/3/23 0:20:50
48 HRB75971 - 03/2013
51201116AA-P37a48.indd 48 2013/3/23 0:20:50
LVED313102EN
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.
This document has been printed on ecological paper
Design: Schneider ElectricPhotos: Schneider ElectricPrinted:
Schneider Electric Industries SAS35, rue Joseph MonierCS 30323F - 92506 Rueil Malmaison Cedex
RCS Nanterre 954 503 439Capital social 896 313 776 €www.schneider-electric.com
© 2
013
- Sch
neid
er E
lect
ric -
Tous
dro
its ré
serv
és
03-2013
51201116AA-couv_EN.indd 2 2013/3/23 0:03:35