acimaterialsjournaljanfeb03ir.pdf

Upload: oscar-wong-chong

Post on 08-Jul-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/19/2019 ACIMaterialsJournalJanFeb03IR.pdf

    1/10

    ACI Materials Journal/January-February 2003 63

     ACI Materials Journal , V. 100, No. 1, January-February 2003.MS No. 02-061 received February 7, 2002, and reviewed under Institute publica-

    tion policies. Copyright © 2003, American Concrete Institute. All rights reserved,including the making of copies unless permission is obtained from the copyright pro-prietors. Pertinent discussion will be published in the November-December 2003  ACI 

     Materials Journal if received by August 1, 2003.

    ACI MATERIALS JOURNAL TECHNICAL PAPER

     Bonded carbon fiber-reinforced polymer (CFRP) composites are

    rapidly gaining acceptance as a feasible solution for repair and strengthening of concrete structures. A reliable method of non-destructive evaluation (NDE) is needed to monitor the installation

    quality and the long-term efficacy of the repair. This paper presentsresearch into the use of infrared (IR) thermography to evaluatebonded CFRP composites used to strengthen concrete beams.

     Reinforced concrete beams were constructed and then strengthened with several configurations of wet layup or precured laminateCFRP composites. Two beam configurations were used to force

    either a shear failure mode or a flexural failure mode. IR inspectionswere conducted on the CFRP composite systems before loading to

    determine the extent of bond. The beams were then tested staticallyto failure. Periodically during load testing, IR inspections wereconducted to determine the amount and characteristics of bond damage. Results indicated that IR inspections were able to

    consistently determine loss of bond as loading progressed.

    Keywords: bond; concrete; fiber-reinforced polymer; strength.

    INTRODUCTIONStrengthening of concrete members with carbon fiber-

    reinforced polymer (CFRP) composites has become increasinglypopular in recent years. These systems are generally surfaceapplied, which prevents the visual inspection of the encapsulated

    concrete member. Post-installation detection of unbonded,

    debonded, and delaminated areas is critical in evaluating theactual capacity and durability of the CFRP composite, as

    well as the underlying concrete and reinforcing. Qualitative

    infrared thermography (IR) can be used to detect unbonded,debonded, and delaminated areas under the surface and within

    the CFRP strengthening system.

    Thermography is commonly used for a variety of industrial

    applications including problems associated with bearinglubrication, pipes, valves, seals, motor windings, motor

    overloads, electrical circuits and components, and chemical

    processes. Thermography has been used in buildings forenergy audits, moisture problems with roofs, and inspectionof reinforced masonry. IR thermography has also been

    used for qualitative nondestructive evaluation (NDE) of 

    bridge piers wrapped with CFRP strengthening systems(Jackson et al. 1999).

    RESEARCH SIGNIFICANCE

    The Federal Highway Administration estimates that230,000 of the nation’s 575,000 bridges are structurallydeficient or functionally obsolete (Witcher 1996). Many of 

    these bridges can be repaired or strengthened with CFRP

    composites. Much work has been conducted on the structuralaspects of bonded repair systems. The long-term performance

    characteristics of the system, however, are still largely

    unknown. With the promise of increased use of CFRP systems

    in structural applications, it is imperative that a simple andeffective method for NDE be developed. IR thermography can

    potentially be used to detect flaws in bonded repair systems,including installation defects and long-term degradation.

    The work presented in this paper provides fundamentalqualitative and quantitative data indicating IR inspection

    to be a viable method for the NDE of bonded CFRP systems.

    CFRP STRENGTHENING AND BOND

    Bonded CFRP systems can add flexural strength, shear

    strength, and/or confinement to an existing reinforced or

    prestressed concrete element. Flexural and shear strengtheningare commonly applied to beam elements while confinementis used to improve the ductility of concrete columns underearthquake loads. When adding flexural strength, CFRP

    sheets or laminates are placed so that the fibers are oriented

    along the length of the beam in the region of high flexuraltensile stresses. Shear strength is added by orienting the fibers

    perpendicular to the beam’s axis, thus providing a stirrupconfiguration. Confinement is typically provided by wrapping

    the element, usually a column, with CFRP. In some cases,the column may be wrapped multiple times to ensure sufficient

    confinement will be obtained.

    Loss of bond in flexural or shear configurations can be

    catastrophic. Bond is of lesser importance when consideringconfinement, but it could be an indicator of other more

    serious problems.

    To avoid confusion, it is necessary to define the four types

    of bond loss that will be discussed in this paper. The firsttype is an unbonded area that is not a structural failure butrather an initial lack of bond that occurred during application.

    The second type is a debond, which describes the separation

    that occurs between the CFRP composite and the underlyingconcrete surface. This type of failure is structural and is

    characterized by the fact that there is very little concrete

    attached to the composite after pulling away from the concrete.The third type is a delamination, which is the separation of two layers of CFRP composite. This type of bond loss can

    occur as a result of faulty installation or as a result of loading.The final type is a substrate failure. The substrate failure is

    structural and is characterized by a tensile rupture of the concretebelow the surface of the bond line. This is the preferred mode of 

    failure because the adhesive has performed adequately and

    allows for the maximum transfer of stress between the CFRP

    and concrete for that particular concrete strength.

    Title no. 100-M8

    Nondestructive Evaluation of Carbon Fiber-Reinforced

    Polymer-Concrete Bond Using Infrared Thermography

    by John M. Levar and H. R. (Trey) Hamilton III

  • 8/19/2019 ACIMaterialsJournalJanFeb03IR.pdf

    2/10

    ACI Materials Journal/January-February 200364

    Current applicable limits for unbonded, debonded, and

    delaminated areas are given by the ACI Committee 440 report“Guide for the Design and Construction of Externally Bonded

    FRP Systems for Strengthening Concrete Structures (ACI440.2R-02).” These guidelines (hereinafter referred to as ACI440.2R-02) recommend the following for general acceptance of wet layup systems:

    1. Inspection methods should be capable of detecting

    delaminations of 2 in.2

    (1300 mm2) or greater;

    2. Small delaminations less than 2 in.2 (1300 mm

    2) each

    are permissible, as long as the delaminated area is less than5% of the total laminate area and there are no more than 10

    such delaminations per 10 ft2 (1 m2);

    3. Large delaminations, greater than 25 in.2 (16,000 mm

    2), can

    affect the performance of the installed FRP and should be

    repaired by selectively cutting away the affected sheet and

    applying an overlapping sheet patch of equivalent plies; and

    4. Delaminations less than 25 in.2  (16,000 mm2) may be

    repaired by resin injection or ply replacement, depending onthe size and number of delaminations and their locations.

    There were four objectives determined at the outset of this

    research. The first objective was to determine the overalleffectiveness of qualitative IR thermography for use in

    inspecting CFRP strengthening systems for concrete. For IR

    thermography to be effective, it must be capable of providingquality control information for both initial application

    and long-term performance. The second objective was to

    determine the behavior of the CFRP systems as loadingprogressed. Observations of debonded area progression

    through failure can be useful in future research and field

    detection of strengthening systems that have been overloadedor otherwise damaged. The third objective was to determine

    the installation quality that can be expected from the

    strengthening systems. These data can be used to developguidelines for initial tolerances of unbonded areas in thestrengthening systems. The flexural and shear capacity of 

    strengthened beams are calculated based on the assumptionthat a perfect bond exists between the composite and the

    concrete. While this assumption is rarely attained in practice,

    it is not clear what minimum area of bond is required to ensurethat there is a reasonably low risk of bond failure. The final

    objective was to determine the ability of IR thermography

    to detect the extent and characteristics of the debondingsurrounding flexural or shear cracks under the CFRP composite.

    EXPERIMENTAL PROGRAMSpecimen construction

    The specimens used for testing were 4.9 m (16 ft) long

    concrete beams, 102 x 305 mm (4 x 12 in.) in cross section.Two 12.7 mm (No. 4) bars with a yield strength of 414 MPa

    (60 ksi) were placed in the bottom of the beam with an effective

    depth of 250 mm (10 in.). A total of eight specimens were

    John M. Levar  is President and Co-founder of Advanced Structural Technologies, Inc.,

     Minneapolis , Minn. He received his MSCE from the Universit y of Wy oming. He is a

    member of ACI Committee 440, Fiber Reinforced Polymer Reinforcement. His researchinterests include the durability and inspection of fiber-reinforced polymer composites and 

    the effect of reinforcing steel corrosion on composite strengthening systems.

    H. R. (Trey) Hamilton III  is an associate professor of civil engineering at theUniversity of Florida. He is a member of ACI Committees 222, Corrosion of Metals in

    Concrete, and 440, Fiber Reinforced Polymer Reinforcement; and Joint ACI-ASCE 

    Committee 423, Prestressed Concrete. His research interests include evaluation and strengthening of existing structures.

    Table 1—CFRP composite properties

    CFRPtype

    Fabricweight

    System tensilestrength,MPa (ksi)

    System modulus,GPA (ksi)

    Materialthickness,mm (in.)

    Fabric 19.23 oz./yd2 1034 (150) 69 (10,000) 1.0 (0.041)

    Laminate na* 2482 (360) 200 (29,000) 1.4 (0.055)

    * na = not available.

    Fig. 1—Detail of flexural load testing setup.

    Fig. 2—Detail of shear load testing setup.

    Table 2—Flexural test matrix

    Specimen CFRP typeCFRP width,

    mm (in.) CFRP layout

    F1F5

    Fabric 102 (4) Single strip

    F2F3F4

    Fabric 406 (16) 50% U wrap

    F6 Laminate 51 (2) Single strip

    CF1CF2

    None na na

    *na = not available.

  • 8/19/2019 ACIMaterialsJournalJanFeb03IR.pdf

    3/10

    ACI Materials Journal/January-February 2003 65

    constructed. The concrete strength at the time of testing was

    35 MPa (5.0 ksi).

    Two different bonded CFRP systems were applied to theconcrete specimens using a wet layup, unidirectional fabric and

    unidirectional laminate, each from a different supplier. Each

    system was applied using the manufacturer’s instructions. Shearand flexural capacities under the test load configuration were

    calculated using the guidelines presented in ACI 440.2R-02.

    CFRP system and material properties were taken from themanufacturer’s literature and are shown in Table 1.

    Beams to receive the wet layup system (hereinafter referredto as fabric) were prepared by rounding the edges in the

    applic ation area to a 12.7 mm (0.5 in) minimum radius with

    a handheld grinder. Beams receiving laminate and/or fabricwere lightly sandblasted using 20 grit silica sand in the contactarea. After sandblasting, the beams were cleaned with

    compressed air to remove residual sand and laitance.

    There were eight flexural specimens with varying con-figurations of CFRP composites as shown in Table 2.

    Specimens F1 through F5 used a single layer of fabric foreach specimen. Fabrics used to form the composite wereunidirectional with the strong direction oriented parallel with the

    length of the beam. Specimen F6 used a precured laminate

    placed on the tension face of the beam. Shear specimens were cut

    from the flexural specimens after the completion of the flexural

    tests. A total of 10 shear specimens were tested with varying

    CFRP composite types and configurations as shown in Table 3.

    Test setup and instrumentation

    The flexural specimens were loaded in four-point bending

    (Fig. 1). The shear test involved a much shorter span with asingle point load to ensure diagonal cracking and a shear failure

    mode (Fig. 2). Both test setups were designed so that the

    flexural tension face was oriented upward allowing convenient

    access for IR inspection (Fig. 3).

    The instrumentation included equipment for load-deflection

    data collection and IR imaging prior to and during loading.Instrumentation included two 44.5 kN (10 k) load cells, dial

    gages, and a multimeter. The load cells were connected to

    the multimeter to measure the output and confirm the

    support reactions. The dial gages were placed at midspan

    to monitor deflection.

    The infrared thermometer, infrared camera, an 8 mm VHS

    camcorder, and a television formed the IR inspectionequipment. The infrared thermometer was used to take

    surface temperature readings for use in scaling the IR images,

    and the camera was used to collect IR images during the test.

    The IR images were recorded with the VHS camera to provide

    the best selection of photos possible. The IR camera had

    a 25 mm lens. This particular camera/lens combinationallowed for visualization of defects 320 mm 2  (0.5 in.2)and larger. The display was monochromatic. Detailed

    specifications for the IR camera include: detector type/ 

    format; uncooled ferroelectric (320 x 240), spectral response; 7

    to 14 microns, thermal stabilization; thermoelectric cooler,

    video update rate; 30 Hz-real time, time to operation (typical);

    < 25 s at 25 °C. The thermometer specifications included: 8:1target size, back-lit LCD display, temperature range of –32 to

    400 °C (–25 to 750 °F), preset emissivity of 0.95, and accuracy

    within 0.10 °C.

    EXPERIMENTAL PROCEDURES

    The experimental program consisted of flexure and shear

    tests on the strengthened concrete beams. Control tests were

    also conducted on beams that were not strengthened. The

    beams were tested statically to failure. IR inspection was

    conducted during the testing. The following sections describe

    the testing details.

    Table 3—Shear test matrix

    Specimen CFRP type

    CFRPwidth,

    mm (in.) CFRP layout

    S1S2S3S4

    Fabric 406 (16)50% with fiber

    longitudinal

    S6S7

    Fabric 406 (16)

    50% with fiberlongitudinal and

    50% withtransverse

    S5S8

    Fabric na

    Strip with fiberlongitudinal and50% with fiber

    transverse

    S9S10

    Laminate 51 (2)Strip longitudinal

    and stirrup8@ 152 mm o.c.

    CS1CS2

    None na na

    *na = not available.

    Fig. 3—Fully integrated test setup.

  • 8/19/2019 ACIMaterialsJournalJanFeb03IR.pdf

    4/10

    ACI Materials Journal/January-February 200366

    IR inspectionCreating Temperature Differential—The IR inspections

    were conducted using a lagging process to develop the

    temperature differential as illustrated in Fig. 4. The specimenstarts with the concrete and CFRP composite at the same

    temperature (Fig. 4(a)). When heat is applied to the CFRP

    composite surface, its temperature rises (Fig. 4(b)). The un-derlying concrete is now cooler than the composite, creating a

    thermal gradient and heat flow from the composite to the

    concrete. The rate at which the heat flows is a function of theintimacy of contact between the composite and the concrete.

    In areas where the composite is not in contact, the heat transferfrom composite to concrete will be slower than in areaswhere there is intimate contact. In the time following heat

    application, this results in a higher temperature and resulting

    emittance (or hot spot) at the debonded areas detectable withthe IR camera.

    The heat sources that were tested included a heat gun, hair

    dryer, kerosene heater, propane torch, and quartz lamp. Hair

    dryers and heat guns were unable to heat the surface quicklyenough to create a gradient. The kerosene heater worked

    well over large areas. This was especially useful in heatingthe laminate stirrups, as it allowed for the inspection of morethan one stirrup at a time. The propane torch also worked

    well on the laminate, but without modification it didn’t provide

    enough even coverage for use on the fabric. The most effective

    and convenient heat source for the indoor inspection of theCFRP fabric was the quartz lamp. In under 20 s, an area of approximately 0.28 m2  (3 ft2) was heated evenly to 35 to

    43.3 °C (95 to 110 °F). They also provided a significant

    advantage when working indoors where combustion vaporswere a concern.

    The specimen temperature was monitored during testing

    using an infrared digital thermometer. Spot temperatures

    were taken to aid in control of surface heating. Delayscaused by time-consuming reheating or waiting for the sur-

    face to cool after overheating were avoided using this tech-

    nique. Monitoring the temperature during heating alsoensured that the CFRP composite temperature was kept wellbelow the glass transition temperature.

    The temperature of the specimen relative to the ambienttemperature affected the heat flow from the CFRP composite.

    IR inspection was conducted repeatedly on a single specimen

    during load testing. Consequently, the average temperatureincreased steadily as the test progressed, resulting in a less

    effective IR inspection. The best results were obtained with

    the following conditions:

    • Ambient temperature below approximately 23.9 °C(75 °F);

    • Use a 500 W lamp at a distance of 152 mm (6 in.) from

    the surface; and

    • Heat surface to 35 to 43.3 °C (95 to 110 °F).

    Fig. 4—Lagging method of creating temperature gradient for IR inspection: (a) specimen

    at ambient conditions; (b) heat application; and (c) hot spot development after heating.

  • 8/19/2019 ACIMaterialsJournalJanFeb03IR.pdf

    5/10

    ACI Materials Journal/January-February 2003 67

    Temperatures above this level heated the composite more

    than was necessary for a satisfactory inspection. Caution

    must be exercised when heating so the glass transitiontemperature of the epoxy, usually 60 to 82.3 °C (140 to180 °F), is not exceeded. Exceeding this temperature limit is

    easy to do with available heating methods and can have anadverse effect on the strengthening system.

    Qualitative evaluation—IR inspection can be either

    quantitative or qualitative. Quantitative IR inspection usesdirect temperature measurement to detect actual temperatures

    of an object and requires equipment with temperaturemeasurement capabilities. The results of quantitative inspectionsare influenced by the object’s surface emissivity and texture,

    the reflected background, ambient air temperature, cameraresolution, camera accuracy, and operator experience.Qualitative IR does not focus on obtaining the actual surface

    temperature but rather the magnitude and configuration of 

    the temperature gradient. Qualitative IR inspection was usedin this research.

     Defect identification and labeling—The need for identifyingand labeling defects is dependent on the intent of the IRinspection. As briefly discussed in the objectives, the purpose of 

    using IR thermography for NDE is twofold. The first use for

    this type of evaluation is quality control of the application

    process. The second is continued monitoring of existingrepairs over time to evaluate long-term performance. In the

    case of quality control, locating the defects is not necessaryunless continued inspection is required. When continued

    inspection is required, debonding, delaminations, and unbonded

    areas need to be located for future inspection.

    Metallic paint pens were used to mark the boundaries

    of the hot spots (Fig. 5). Chalk was used in initial testing

    and was found to be ineffective. Chalk was convenient inthat it could be easily removed from a surface, but when

    it was needed for longer durations, it was insufficient.

    The metallic pens worked well for showing the boundariesand were detectable in the IR camera and visible with the

    naked eye. Nonmetallic pens were used for filling in the

    areas of progression throughout the load steps. At the endof the test, the areas outlined at each load step were measured

    using a transparent 650 mm 2 (1 in2) square grid, resulting in

    areas of initial defects as well as damage that occurredduring testing.

    Flexural testsIt was impractical to monitor the entire beam with IR

    inspection during loading. Consequently, the area of maximum

    moment was selected on which to focus the IR inspection(shown as the influence area in Fig. 1). During loading, heat

    was applied for 15 to 20 s to an approximately 0.1 m2 (1 ft2)

    area on one face of the beam with a 500 W quartz lamp.Immediately after heating, temperature readings were taken

    with the infrared thermometer. The heat was removed and

    the IR camera operator sketched the outline of the unbondedor debonded area directly on the CFRP composite. IR inspectionwas also conducted prior to loading to identify existing

    unbonded areas and then after loading to 60, 80, and100% of the calculated capacity. At each of the selected

    load steps, the beam was unloaded and each face was inspected

    with the IR camera.

    Shear testsThe influence area for the shear specimens consisted of a

    762 mm (30 in.) length encompassing the beam within the

    load points on the three sides reinforced with CFRP (Fig. 2).

    The general IR procedures of inspection with the IR camera

    were similar to those used for flexure. The shear specimenswere inspected initially with the IR camera to identify

    unbonded areas. The test then progressed with load steps of 

    25, 50, and 75% of the ultimate capacity, and then ultimate

    capacity after initial failure occurred. The ultimate capacitywas chosen over the calculated capacity in the shear tests due

    to the variability in CFRP composite bond strength. The

    beam was unloaded at each load step followed by IR inspection.

    The 500 W quartz lamp was used for the fabric and a 79 MJ(75,000 BTU) kerosene heater was used for the laminate. IR

    images were recorded during loading to determine if significant

    changes in damage could be detected. The boundaries of 

    unbonded and damaged areas were marked and measured asin the flexure tests.

    DEFECT VERIFICATION

    The verification of the debonded, delaminated, and unbondedareas of CFRP was done using several different approaches.Prior to initiating the load tests and IR inspections, several

    mockups were constructed with known unbonded areas. IR

    inspection was conducted on these known defects to help in

    distinguishing areas that have defects or damage. Surfacetemperature variations can occur due to variations in the

    thickness of the epoxy. The temperature differential for these

    areas was much more subtle than for the areas that have

    defects or damage.

    A common form of FRP composite inspection is acoustic

    sounding (coin tap). The surface is impacted or tapped whilethe inspector listens for hollow sounds. Coin tap was conducted

    occasionally during testing to verify results of the IR inspection.

    It was found that an estimated 20 to 30% of the defects or

    damage found with IR inspection were undetectable with thecoin tap. Unfortunately, it was not possible to verify these

    areas following testing due to the destructive nature of the

    testing. It was noted, however, that the areas detectable with

    IR inspection but not with coin tap increased in size duringthe course of the load test, indicating that the areas were

    indeed defects and not variations of epoxy thickness or other

    false sources.

    The difficulty arises when trying to distinguish at what

    depth the anomalies occur. All forms of damage can be

    detrimental to the CFRP composite system, but the specific

    failure mode is required to determine the capacity of anexisting structural member. Unbonded and debonded areas

    appeared differently in the IR image than a delamination due

    to the variation in depth between the three types of bond loss.

    This difference is not obvious and is difficult to determine

    Fig. 5—Outlines created by metallic paint pens representing

    hot spots.

  • 8/19/2019 ACIMaterialsJournalJanFeb03IR.pdf

    6/10

    68 ACI Materials Journal/January-February 2003

    correctly due to the variability of layer thickness, system

    composition, and heating methods. By studying the behaviorof single-layer systems of unidirectional fabric, it was possible

    to verify the signatures when layers were combined in different

    orientations. In this way, the characteristics of delaminationsin exterior layers were separated from debonding at theconcrete CFRP interface. The more CFRP layers a system

    has, the more difficult it is to distinguish between the differenttypes of defects.

    The final approach for verification came from physicalremoval of the CFRP from the specimen in an attempt toobserve the debonded/unbonded areas. The CFRP laminate

    provided evidence of unbonded areas by a lack of epoxyresidue on the interior surface of the laminate. The fabric did

    not provide an obvious indication of subsurface voids when

    removed from the concrete. Upon removal from the concretesurface, the CFRP was covered uniformly with concrete

    fragments. The concrete fragment also splintered off the

    fabric as it was peeled from the concrete substrate. The

    remaining concrete substrate looked very similar to the

    CFRP and did not provide verification of specific unbonded

    or debonded areas.

    RESULTS AND DISCUSSIONUnbonded areas

    The results of the initial IR inspections prior to load testingare shown in Table 4 and 5 for the flexure and shear specimens,

    respectively. Note that the table gives areas as a percentageof the area covered by composite. In addition, the table

    gives loss of bond during load test, which will be discussedsubsequently. For the flexural specimens that had a singlelayer of fabric on the tension face (F1 and F5), the bonded

    area was found to be 90% while the wrap around configuration

    (F2-F4) was less at 82.5%, indicating additional installationdifficulty when wrapping corners. This is true even with the

    fiber direction parallel with the beam axis. Note that both of 

    these measurements exceed the 5% allowed by ACI 440.2R-02.The laminate (F6) has a somewhat better bond coverage

    (92%) than the fabrics. The shear specimens using the fabric

    with the longitudinal orientation had similar bond coverageas that of the flexural specimens. Somewhat surprising is the80.5 and 85% bond coverage for the shear specimens with

    transverse fiber orientation (S5-S8). It is expected thatthere would be a reduction in a bond area caused by having towrap the fabric around the corners of the beam, but none

    was apparent.Unbonded areas in fabrics were oriented along the principal

    fiber direction regardless of the orientation of the fabrics

    with respect to the beam. Figure 6 shows Specimen S1 with

    the defects oriented parallel to the beam axis. Figure 5 showsSpecimen S6 in which the fiber direction of the top layer is

    oriented perpendicular to the beam axis. This pattern of 

    unbonded areas is believed to be due to the tension requiredto stretch the fabric to provide a smooth application. This

    tension does not allow the fabric to conform to uneven areas

    on the surface of the concrete. The fibers tend to pull awayfrom the uneven areas on the concrete surface after application

    but before the epoxy cures. IR inspection was performed on

    several specimens immediately after CFRP application butbefore full cure was reached. It was found that the detectable

    unbonded areas increased as the epoxy cured.Unbonded areas under the laminate were also somewhat

    elongated following the axis of the strip (Fig. 7). The laminateis applied by placing a ridge of fresh epoxy along the centerline

    of the laminate. As the laminate is pushed into the concrete,

    the ridge is flattened and the epoxy is supposed to squeezeout to the edge of the laminate to cover the entire width. If 

    insufficient epoxy is used, the epoxy is overly viscous, or

    inadequate pressure is used, then the entire width may not be

    Fig. 6—Orientation of unbonded area aligned with fiber direction.

    Table 4—Bonded area of CFRP for flexuraltest specimen

    Specimen

    Bonded area (% of total composite area)

    Initial Average100% of capacity Average Decrease

    F1 nana

    *na

    na 10F5 90 80

    F2 na

    82.5

    na

    69.5 10F3 83 78

    F4 82 67F6 92 na 86 na 6

    *na = not available.

    Table 5—Bonded area of CFRP for sheartest specimen

    Specimen

    Bonded area (% of total composite area)

    Initial Average75% of capacity Average Decrease

    S1 80

    80.5

    66

    66.8 13.7S2 81 64

    S3 77 63

    S4 84 74

    S5 8380.5

    5049 31.5

    S8 78 48

    S6 8685

    7573 12

    S7 84 71

    S9 9291

    8685.5 5.5

    S10 90 85

  • 8/19/2019 ACIMaterialsJournalJanFeb03IR.pdf

    7/10

    ACI Materials Journal/January-February 2003 69

    covered, leaving unbonded areas at the edge of the laminate

    as shown in the figure.

    Load tests

    Flexural specimens were tested with three different CFRP

    composite configurations. There were several failure modes

    exhibited as indicated in Table 6. The failure load of each

    flexural specimen is also given in Table 6. The failure load

    given in the table is the total load applied to the beam (thesum of the two-point loads). There was only one test in

    which the failure mode was debonding (F3). The remainder

    of the tests failed by CFRP rupture, concrete crushing, or

    shear. When comparing the capacity of the flexural specimen

    with the unbonded area of CFRP, the influence of the unbonded

    area is not evident. There is a decrease in the experimental

    capacity associated with higher debonding during loading.

    This may be attributed in part to the unbonded area. The

    crushing failure mode exhibited by the strengthened flexural

    specimen, however, discredits this relationship. The over-

    reinforced sections failed in compression prior to CFRP

    rupture and prevented a comparison with the calculated

    capacity. For an adequate comparison to be made, thespecimen must be designed such that the failure mode is

    CFRP rupture with little chance of compression or shear

    failures. The focus of this experimental work was to test

    the IR inspection rather than the improvement in capacity

    provided by the CFRP.

    Although the load test results appear to indicate that larger

    unbonded areas did not adversely affect the flexural capacity

    of the strengthened beams, there is some doubt cast by the

    failure modes. Other work (Jackson et al. 1999) has indicated

    high unbonded areas in field applications in which field tests

    using infrared inspection on CFRP fabric wrapped bridge

    columns showed a total unbonded area after application of 

    8190 mm2

     (12.7 in2

    ) out of 31,940 mm2

     (49.5 in2

    ) or 26% of the total CFRP area evaluated.

    The load test results for the shear specimens are shown in

    Table 7. In general, the shear specimens exhibited far more

    debonding and delamination than their flexural counterparts.

    This is likely due to the lack of shear reinforcement in the

    beams, allowing excessive cracking to take place. The

    improvement provided by the CFRP composite does not appear

    to have been affected by the large unbonded areas. It should

    be noted that the shear test configuration provided a rather

    short shear span, likely resulting in a shear failure dominated

    by compression rather than diagonal tension.

    Debonding and delamination

    The IR inspections revealed that delamination and debonding

    occurred during loading on both the flexural and shear

    specimens. In general, debonding and delamination aremanifested as unbonded area growth rather than the appearance

    of new areas. This characteristic was common among all of 

    the fabric and laminate specimens.

    One of the objectives of this research was to determine if 

    flexural cracks under the CFRP composite could be located

    and tracked with IR inspection during load testing. It was

    thought that the flexural crack would cause local delamination

    immediately adjacent to the crack of sufficient size that the

    IR inspection could detect. This capability would be a useful

    tool in evaluating the CFRP system, particularly to determine if 

    the system had been overloaded. Unfortunately, cracking

    Table 6—Flexural test results

    Designation

    Failure loadPexp , kN (kips)

    Calculatedcapacity Pn ,

    kN (kips) Pexp / Pn Failure mode

    F1 36.0 (8.1)51.9 (11.7)

    0.69 CFRP rupture

    F5 48.0 (10.8) 0.92 Shear failure

    F2 57.8 (13.0)

    51.9 (11.7)

    1 .11 Concre te c rushing

    F3 48.5 (10.9) 0.93 CFRP debond

    F4 45.8 (10.3) 0.85 Concrete crushing

    F6 52.9 (11.9) 53.4 (12.0) 0.99 Shear failure

    CF1 28.0 (6.3)26.2 (5.9)

    1.07 Steel yield

    CF2 29.4 (6.6) 1.12 Steel yield

    Table 7—Shear test results

    Designation

    Failure loadPexp ,

    kN (kips)

    Calculatedcapacity Pn ,

    kN (kips) PVexp / PVn Failure mode

    S1 257.6 (57.9)

    151.8 (34.1)

    1.70 CFRP debond

    S2 242.9 (54.6) 1.60 CFRP debond

    S3 251.8 (56.6) 1.66 CFRP debond

    S4 165.9 (37.3) 1.09 CFRP debond

    S5 234.4 (52.7) 101.5 (22.8) 2.31 CFRP debondS8 201.0 (45.2) 1.98 CFRP debond

    S6 162.8 (36.6)na na

    CFRP debond

    S7 173.5 (39.0) CFRP debond

    S9 188.2 (42.3)157.0 (35.3)

    1.20 CFRP debond

    S10 162.4 (36.5) 1.03 CFRP debond

    CS1 155.2 (34.9)71.2 (16.0)

    2.18 Shear failure

    CS2 146.8 (33.0) 2.06 Shear failure

    *na = not available.

    Fig. 7—Typical unbonded area alignment on laminate specimens.

  • 8/19/2019 ACIMaterialsJournalJanFeb03IR.pdf

    8/10

    ACI Materials Journal/January-February 200370

    generally shows up as the enlargement and eventual connecting

    of adjacent unbonded areas as the load is increased.

    There was one occasion when a flexural crack caused

    debonding of the adjacent CFRP without the aid of unbondedareas. Figure 8 shows the tension face of Specimen F3. Note

    that this specimen failed by CFRP rupture at the location

    indicated by the IR inspection. The IR signature was notedduring testing as unusual because it was perpendicular to the

    direction of the fabric.

    Specimens F1 and F5 had composite applied to the tension

    face only, leaving the sides exposed. Visible flexural crackson the sides were traced to confirm the location of the cracking

    under the CFRP. The IR signatures for these flexural cracks,

    however, were not as distinct as on Specimen F3.

    Specimen F6 was reinforced with a single strip of laminatealong the tension face. By having the faces of the beam

    exposed, cracking could be tracked to the laminate and

    signature locations could be readily anticipated and identified.However, there was no associated IR signature detected

    prior to failure.

    Specimens S1 through S4 displayed behavior similar to F2through F4 in that debonding resulted in the enlargement of unbonded areas as the load was increased. When 65 to 75%

    of the capacity was reached, the debonded areas increased

    significantly at the diagonal cracks.

    Shear Specimens S6 and S7 were reinforced with two

    layers of CFRP fabric. The inner layer was oriented with theprincipal fiber direction parallel to the beam axis. This allowed

    for IR inspection of the multilayer systems during load

    progression. During load application, most of the damage wasdebonding with little delamination noted. This was verified by

    the lack of growth in the vertically oriented signatures inthe external layer of fabric. On further inspection, it wasdiscovered that there were cloudy signatures in some areas

    that were not associated with the exterior layer. This cloudy

    area was thought to be debonding of the internal layer of CFRP. This was not evident until failure occurred. Once

    failure occurred, the area surrounding the failure displayed

    the same cloudy signature that was seen during the loadprogression. The status of the cloudy area was unverified as

    removal of the fabric layers destroyed the appearance of the

    concrete/CFRP interface.

    Shear Specimens S5 and S8 were reinforced with a singlestrip of fabric on the tension face and then a perpendicular

    wrap encompassing half of each side. Debonding initiated at

    the boundaries of unbonded areas. The debonded areas

    continued to grow in the principal fiber direction until

    failure occurred.

    Shear Specimens S9 and S10 used the carbon fiber laminate

    in a stirrup configuration. Because of its stiffness, the

    laminate did not conform to inconsistencies in the concretesubstrate as well. The increased thickness and density of the

    laminate and epoxy substrate also changed the IR signaturefrom that of the fabric. Initial debonding started at unbondedsignatures near the edge of the laminate. The debonded

    area usually extended immediately to the top of the stirrup.

    Intermediate load levels showed moderate progression of debonding through the stirrup, but most debonding occurred

    at the edges. This reinforcing configuration provided capacity

    beyond the expected value. The epoxy did not perform well,however, and with better materials and surface preparation

    the system may have provided a higher shear capacity. The

    stirrup configuration engaged the 45 degree crack as expected.It is evident that the interfacial bond is critical in areas directly

    affected by shear.

    Area analysisUnbonded, debonded, and delaminated areas were measured

    and recorded during the construction and load testing of the

    flexure and shear specimens. The IR inspection procedurewas somewhat subjective in that the thermographer identified

    and sized the defect while viewing the specimen with the IR

    camera. Furthermore, the measured areas were totaledmanually. Even with this low-tech procedure, it was possible

    to perform the inspections with remarkable repeatability.

    This section presents the results of the area analysis.

    Figure 9 shows the loss of CFRP bond as a function of the

    applied load for flexural Specimen F3 to F6. The figureshows the loss of bond as a function of the applied load. The

    loss of bond is the sum of unbonded, debonded, and delaminated

    areas. Hence, at zero load, the loss of bond is equal to theunbonded area determined before the test was initiated. All

    of the flexural specimens displayed a gradual increase in the

    amount of damage. Specimens F3 and F4 (side wrap specimens)are clustered above F5 and F6 (fabric and laminate strips,

    respectively). The close match among the plots is an indication

    of good repeatability and may also indicate that bondcharacteristics can be categorized with the configuration of the CFRP composite. No flexural specimen had more than

    35% loss of bond at failure.

    Table 4 compares the total area bonded at initial inspection

    and at 100% of the calculated capacity for the flexural

    Fig. 9—Bond damage progression for Specimens F3 to F6.Fig. 8—Crack transverse to fiber direction in flexural specimen.

  • 8/19/2019 ACIMaterialsJournalJanFeb03IR.pdf

    9/10

    ACI Materials Journal/January-February 2003 71

    specimen. It is interesting to note that the decrease in bonded

    area was 10% or less. This indicates that small changes in

    bond, when considering flexure, can be an indication that abeam has seen or is under significant load.s

    Figure 10 shows the loss of bond for shear Specimens S1to S4. The initially unbonded area for each of the specimens was

    very near 20% of the total CFRP area. The repeatability of the

    inspection method is confirmed by the lack of variation amongthese similarly reinforced specimens. In addition, the loss of 

    bond increases at a relatively constant rate up to 75% of theload. There is a drastic increase in debonding and delaminationfrom 75 to 100%. This is due primarily to the explosive release

    of energy at failure of the system in shear, which causes a rapid

    and complete loss of bond on one side of the shear crack.

    Figure 11 shows the loss of bond for Specimens S5 and S8.

    Specimens S5 and S8 exhibited consistent changes in thedebonded area as the applied load increased. The two curves

    reflect the repeatability of the inspection method. Once

    again, the consistency of material and application are alsoevident. The increase in the debonded area at 65% of theactual capacity is also evident in the S5 and S8 specimens.

    This configuration provided the highest capacity combinedwith the highest amount of debonded area at failure. This

    supports the theory that a higher unbonded area at failure

    does not necessarily mean a decreased capacity.

    Figure 12 shows the loss of CFRP bond as a function of the

    applied load for the S6 and S7 shear specimens. Specimens

    S6 and S7 maintained the consistent behavior between

    configurations and show a sharp increase in debonded area

    near 65% of the actual beam capacity. This configuration

    provided multiple layers of CFRP with multiple signaturetypes in the thermogram. The consistency displayed here can

    be attributed to the development of signatures in single-layer

    systems with variable fiber orientation. Due to the subjectivenature of the inspection process, the ability to eliminate false

    signatures is critical in performing an accurate inspection.

    Figure 13 shows the loss of CFRP bond as a function of the

    applied load for the S9 and S10 shear specimens. The IR

    inspection of the specimens reinforced with CFRP laminateshowed initially unbonded areas of 8% of the total CFRP

    area for flexural members and 8 to 10% for the shear specimen.

    Specimens S9 and S10 displayed behavior consistent withthe other shear specimens. The debonded area increases atapproximately 70% of the capacity for the shear specimens

    reinforced with the CFRP laminate. The small, unbondedarea at failure displays a lack of redundancy in the strengthening

    system. If significant cracking occurs between the stirrups, a

    small percentage of the CFRP is engaged, whereas the fabricencapsulates the surface and engages all of the shear cracks

    that occur in the member.

    Table 5 summarizes the change in the bonded area when

    the load is taken to 75% of the capacity. It is unclear why the

    double-layer system of S5 and S8 have such a large changein bond area (31.5%) compared with that of S6 and S7.

    Perhaps there are more delaminations on S5 and S8 than

    were detected due to the double layer.

    Fig. 13—Bond damage progression for Specimens S9 and S10.Fig. 11—Bond damage progression for Specimens S5 and S8.

    Fig. 10—Bond damage progression for Specimens S1 to S4. Fig. 12—Bond damage progression for Specimens S6 and S7.

  • 8/19/2019 ACIMaterialsJournalJanFeb03IR.pdf

    10/10

    ACI Materials Journal/January-February 200372

    SUMMARY AND CONCLUSIONSReinforced concrete beams were strengthened with bonded

    CFRP composites and tested to failure in both flexure andshear failure modes. The beams were IR inspected for initialapplication quality and periodically during load testing to

    record loss of bond with load increase. Inspection procedureswere developed and damage signatures were defined for the

    various reinforcing configurations. The following conclusions

    have been supported by this research:• Infrared thermography can be used effectively for

    nondestructively evaluating CFRP strengtheningsystems for concrete;

    • Initially unbonded areas of CFRP composite on concrete

    substrates can exceed 20% of the total CFPR area;

    • Shear controlled failures can exhibit up to twice as much

    CFRP debonding as predominately flexural failures;

    • The amount of unbonded area present immediately

    after CFRP application can be significantly lower than

    after curing of the CFRP has taken place;

    • Manual methods of acoustic sounding can leave up to25% of the voids under the CFRP composite undetected.Acoustic sounding is inadequate for detecting small

    irregular voids and clearly defining defect and damage

    boundaries; and

    • Quality control inspections need to be performed on

    these systems to establish a baseline for unbonded

    areas. Routine inspections must be performed to determinethe status of the bond between the CFRP and the concrete

    and prevent unexpected failures.

    ACKNOWLEDGMENTSThe authors would like to acknowledge and thank the National Science

    Foundation (CAREER Grant CMS-9734227) for funding this project. They

    would also like to thank Tom Hurley of Hurley and Associates, Inc., for his

    expertise and input regarding infrared thermography. The views expressed in

    this paper are those of the authors and not necessarily those of the sponsor.

    REFERENCESACI Committee 440, 2002, “Guide for the Design and Construction of 

    Externally Bonded FRP Systems for Strengthening Concrete Structures

    (ACI 440.2R-02),” American Concrete Institute, Farmington Hills,

    Mich., 45 pp.

    Jackson, D. R.; Islam, M.; Hurley, T. J.; and Alvarez, F. J., 1999,

    “Feasibility of Evaluating Fiber Reinforced Plastic (FRP) Wrapped

    Reinforced Concrete Columns Using Ground Penetrating Radar (GPR)

    and Infrared (IR) Thermography,”  Demonstrat ion Project   No. 84-2, U.S.

    Department of Transportation-Federal Highway Administration,

    Washington, D.C.

    Mack, J. K., and Holt, E. E., 1999, “The Effect of Vapor Barrier

    Encapsulation of Concrete by FRP Composite Strengthening Systems,”

    44th International SAMPE Symposium and Exhibition , Long Beach, Calif.

    Witcher, D., 1996, “Application of Fiber Reinforced Plastics in New

    Construction and Rehabilitation of the Infrastructure,”  Intern ationa l

    Con ference on Composites in Infrastructure 1996 , (ICCI 96), pp. 774-779.