Page | 1 of 3 ADDENDUM 2 107 W. Lawrence St. Helena, MT 59601 Phone: 406.457.0360 www.slatearchitecture.com This Addendum is issued to inform bidders of clarifications to the plans & specifications. The additions, clarifications, and corrections contained herein shall be made to the Project Manual, Drawings, and Schedules for the above referenced project, and shall be included in the scope of work and proposals to be submitted. References made below to the Project Manual and Drawings shall be used as a general guide only. Bidder shall determine the extent of work affected by Addendum items. GENERAL NOTES: 1. There is an existing hose bib on the existing south exterior wall of the Museum that conflicts with the new addition. The plumbing contractor shall remove the existing hose bib and associated domestic cold water piping and cap the piping at the connection to the main. Coordinate any required wall patching with the general contractor. 2. The plumbing fixtures that are identified with demolition keynotes (D08, D09 & D10) and new construction keynotes (028, 029 & 030) are to be coordinated with the owner prior to any work being started on these items. DRAWING MODIFICATIONS/CLARIFICATIONS: 1) Sheet C4.0 – GRADING AND DRAINAGE DETAILS a. REVISE detail 2 – East Retention Basin, with the attached sketch ADD2.1 2) Sheet A2.0 – ARCHITECTURAL SITE PLAN a. REVISE the east storm water retention basin shown in detail 1 – SITE PLAN, with the attached sketch ADD2.1 Date: June 14, 2016 Addendum #: 2 Project: Museum of the Rockies Collections & Storage Facility Project #: Slate Architecture # : 15056 MSU PPA #: 13-0093 To: All Plan Holders of Record

Upload: ngotruc

Post on 06-Jul-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ADDENDUM 2 107 W. Lawrence St. Helena, MT 59601 2 107 W. Lawrence St. Helena, MT 59601 Phone: 406.457.0360 This Addendum is issued to inform bidders of clarifications to the plans

P a g e | 1 of 3

ADDENDUM 2

107 W. Lawrence St. Helena, MT 59601 Phone: 406.457.0360 w ww.s la tea rch i tec tu re .c om

This Addendum is issued to inform bidders of clarifications to the plans & specifications. The additions, clarifications, and corrections contained herein shall be made to the Project Manual, Drawings, and Schedules for the above referenced project, and shall be included in the scope of work and proposals to be submitted. References made below to the Project Manual and Drawings shall be used as a general guide only. Bidder shall determine the extent of work affected by Addendum items. GENERAL NOTES:

1. There is an existing hose bib on the existing south exterior wall of the Museum that conflicts with the new addition. The plumbing contractor shall remove the existing hose bib and associated domestic cold water piping and cap the piping at the connection to the main. Coordinate any required wall patching with the general contractor.

2. The plumbing fixtures that are identified with demolition keynotes (D08, D09 & D10) and new construction keynotes (028, 029 & 030) are to be coordinated with the owner prior to any work being started on these items.

DRAWING MODIFICATIONS/CLARIFICATIONS: 1) Sheet C4.0 – GRADING AND DRAINAGE DETAILS

a. REVISE detail 2 – East Retention Basin, with the attached sketch ADD2.1

2) Sheet A2.0 – ARCHITECTURAL SITE PLAN a. REVISE the east storm water retention basin shown in detail 1 – SITE PLAN, with the attached

sketch ADD2.1

Date: June 14, 2016 Addendum #: 2 Project: Museum of the Rockies Collections & Storage Facility Project #: Slate Architecture # : 15056

MSU PPA #: 13-0093 To: All Plan Holders of Record

Page 2: ADDENDUM 2 107 W. Lawrence St. Helena, MT 59601 2 107 W. Lawrence St. Helena, MT 59601 Phone: 406.457.0360 This Addendum is issued to inform bidders of clarifications to the plans

P a g e | 2 of 3

3) Sheet A6.1 – DOOR & WINDOW SCHEDULE, ELEVATIONS & DETAILS a. REPLACE the sheet in its entirety with the one attached.

4) Sheet A6.2 – DOOR DETAILS

a. Detail 5, REPLACE dimension 3 ¾” for adjacent walls with 4”

5) Sheet P0.1 – PLUMBING SCHEDULES & DETAILS a. REVISE the plumbing fixture schedule to include Hose Bib HB-2 see attached sketch SKP-01

6) Sheet P1.0 – LEVEL 1 PLUMBING AND PIPING PLAN

a. ADDED Hose Bib to Office 104, see sketch SKP-01.

7) Sheet P1.1 – LEVEL 2 PLUMBING AND PIPING PLAN a. ADDED note “3/4” DCW to Water Softener” see sketch SKP-01.

PRIOR APPROVALS Review for prior approval is for general conformance with the plans and specifications. This review does not take the place of shop drawing review. All requirements of the Plans and Specifications must be met. This review does not relieve the Contractor of the responsibility for furnishing equipment and materials that meet the requirements of the Contract Documents. Mechanical Prior Approvals

SECTION ITEM MANUFACTURER 23 3113 Round Spiral Ductwork Lewis & Lambert

Omni Duct None Roof Intake & Exhaust Hoods ACME

Electrical Prior Approvals

Section 265119 – The following manufacturers are approved for bidding purposes only. All products are subject to final approval during the submittal process. The Contractor is responsible for providing equipment that meets the project requirements and meets or exceeds the equipment specified in quality, appearance and performance:

Type Manufacturer Comments A1 LSI Industries SDL 8 LED LW WW UE CHS5 A1 Mercury Lighting LW4-8-6000-35K-HTA-SXX-UNI-90CRI A2 LSI Industries SDL 4 LED LW WW UE CHS5 A2 Mercury Lighting LW4-4-3800-35K-HTA-SXX-UNI-902CRI B1 LSI Industries LPASC22 LED SS WW UE W/INT OS 0-10V DIM

DAYLIGHTSENSOR B2 LSI Industries LPASC24 LED SS WW UE

Page 3: ADDENDUM 2 107 W. Lawrence St. Helena, MT 59601 2 107 W. Lawrence St. Helena, MT 59601 Phone: 406.457.0360 This Addendum is issued to inform bidders of clarifications to the plans

P a g e | 3 of 3

B2 Mercury Lighting LR10-24G-4200-35K-SXX-UNI E1 Mule Lighting AR 28 B UNV E1 DUALLITE EVHC12I-06L V1 Deco Lighting DACH-LED-4’ 25 35 UNV R DM CSC MS (DIM TO 50%) V1 COLUMBIA LIGHTING LBIL4-35LW-EDU W1 Deco Lighting D444 LED 20 40 UNV T2 BL PC277V EMB W1 HUBBELL LNC2-12L4-4K-2-1-PC4-BBU X1 Mule Lighting SQC LED U R WW SD X1 COMPASS CCR LTG CTLS Leviton LEVITON IRC SERIES LTG CTLS HUBBELL NXRC-1R-UNV, NXRC-2R-UNV, NXRD-2RD-UNV, NXRC-

1RD-UNV/NXRC-2R-UNV

ATTACHMENTS:

1) Sketch ADD2.1 – Revision to East Retention Basin

2) SHEET A6.1 – Door & Window Schedule, Elevations & Details – Attached

3) Sketch SKP-01

4) PRE-BID SIGN-IN SHEET – Attached END OF ADDENDUM 2

Page 4: ADDENDUM 2 107 W. Lawrence St. Helena, MT 59601 2 107 W. Lawrence St. Helena, MT 59601 Phone: 406.457.0360 This Addendum is issued to inform bidders of clarifications to the plans
jacoba
Text Box
ADD2.1
Page 5: ADDENDUM 2 107 W. Lawrence St. Helena, MT 59601 2 107 W. Lawrence St. Helena, MT 59601 Phone: 406.457.0360 This Addendum is issued to inform bidders of clarifications to the plans

AFTER WINDOWINSTALLATION

1

2

BEFOREWINDOWINSTALLATION

NOTES:1. WINDOW OPENING SHOWN. DOORS ARE SIMILAR.

SEE ASSOCIATED DETAILS.2. THE FOLLOWING NOTES OCCUR IN

CORRESPONDING NUMBER INSTALLATIONSEQUENCE.

3

5

6

7

9

8

1. WEATHER BARRIER BENEATH WINDOWAS SHOWN

2. FLEXIBLE MEMBRANE SILL PAN COVERINGSILL AND EXTENDING UP JAMB 4" TO 6"AS SHOWN

3. WEATHER BARRIER AROUND JAMBS ANDHEADER OVERLAPPING FLEXIBLEMEMBRANE SILL PAN 2" AS SHOWN

4. CAULK BEHIND NAILING FLANGE (EXCEPTAT SILL FLANGE) PRIOR TOINSTALLATION. LAP EXTERIOR FACE OFFLANGE.

5. WINDOW OR DOOR - WINDOW FLANGEUNDER FLEXIBLE MEMBRANE FLASHINGAS SHOWN.

6. FLEXIBLE MEMBRANE FLASHING.7. METAL DRIP FLASHING @ HEAD8. FLEXIBLE MEMBRANE FLASHING AT

HEADER OVERLAPPING JAMB FLEXIBLEMEMBRANE BY 2"

9. BUILDING PAPER BIB TUCKED UNDERSEAM IN PRIMARY BUILDING PAPERCOURSE & LAPPED OVER METALFLASHING

2"

SCHEDULE

SEE 2"

2"

SC

HE

DU

LE

SE

E

TYPE 'A'

SC

HE

DU

LE

SE

E

SCHEDULE

SEE

SC

HE

DU

LE

SE

E

SCHEDULE

SEE

TYPE 'B'

2"

SCHEDULE

SEE 2"

SC

HE

DU

LE

SE

E2"

TYPE 'C' TYPE 'D' TYPE 'E'

2"

SCHEDULE

SEE 2"

2"

SC

HE

DU

LE

SE

E

TYPE 'F'

2"

SCHEDULE

SEE 2"

SC

HE

DU

LE

SE

E2"

6" 6" 6"6" 6"

6"

1' -

0"

6"

6"

1' -

0"

2

8' - 6"

6' -

0"

2"

2' - 9"

2"

2' - 9"

2"

2' - 4"

2"

2"

3' -

9"

2"

1' -

9"

2"

6' -

0"

2"

5' -

8"

2"

3' -

0"

TYPE 'C'

5' -

6"

UN

O

1' -

8"

TYPE 'A'

6' -

0"

1' -

2"

TYPE 'B'

4' - 0"

2" 3' - 8" 2"

4' - 0"

2" 3' - 8" 2"

13' -

0"

TO

LA

ND

ING

3' -

0"

2"

4' -

1"

2"

4' -

2"

2"

4' -

1"

2"

TYPE 'D'

4' - 0"

2" 3' - 8" 2"

ALUMINUM WINDOWASSEMBLY

FACE BRICK BEYOND

SEALANT

FACE BRICK(SOLDIER COURSE

THRU-WALL FLASHING

WEEPS @ 24" O.C.

AIR SPACE

DRAINAGE MATERIAL

LEDGER ANGLE - SECURETO HEADER PER STRUCT.

ANCHOR ASSEMBLY -SECURED W/ SELFSEALING FASTENER

NOTCH BRICK

TOOLED MORTAR JOINT, TYP.

COMPRESSIBLEMATERIAL BEYOND

ICF BLOCK

5/8" GYPSUM WALL BOARD

SEALANT

TREATED 2X WINDOW BUCK

ANCHOR ASSEMBLY -SECURE W/ SELFSEALING FASTENERS

FACE BRICK

SEALANT

WINDOW ASSEMBLYFACE BRICK BEYOND

SEALANT & BACKER ROD

THRU-WALL FLASHING

SLOPED PRECASTSILL - 15° MIN.

MORTAR BED

AIR SPACE

TOOLED MORTAR JOINT

WEEPS @ 24" O.C.

SILL FLASHING

3/4" SOLID MATERIAL SILL

ICF BLOCK

TREATED 2X WINDOW BUCK

ALUMINUM WINDOW ASSEMBLY

SEALANT

DRIP EDGE WITHDIVERTER CHANNEL

ICF BLOCK

METAL PANEL SIDING,SEE ELEVATIONS

TREATED 2X WINDOW BUCK

5/8" GYPSUM BOARD

DRIP EDGE

SELF ADHESIVE ICE &WATER SHIELD

SEALANT

ICF BLOCK

METAL SIDING, SEE ELEVATIONS

J TRIM

THRU WALL FLASHINGDRIP EDGE

WINDOW ASSEMBLY

SELF ADHESIVE WEATHERMEMBRANE

SEALANT

3/4" SOLID MATERIAL SILL

TREATED 2X WINDOW BUCK

SEALANT

206

6"

6"

EXIT

6"

EXIT STAIRS

SN-3: ROOM NUMBER & WINDOW SN-4: ROOM NUMBER AND NAMESN-2: EXITSN-1: EXIT STAIRS

206

6"

6"

CONFERENCEROOM

6"

6"

6"

NOTE: COORDINATE WITH OWNER AND UNIVERSITY FOR ACTUAL STYLE AND FINAL APPROVAL

2 1

/2"

3/4

"

WINDOW FOR ROOM ID, SEE SPECS

THIS PLAN SET ISINTENDED FOR BID

TAKE-OFF/ESTIMATIONPURPOSES ONLY. NOTFOR CONSTRUCTION.

MO

NTA

NA

STA

TE U

NIV

ERSI

TY

Printe

d O

n:

PPA#13-0093

REV. DESCRIPTION DATEREVIEWED BY:DRAWN BY :

MU

SEU

M O

F T

HE

RO

CK

IES

NE

W C

OLL

ECT

ION

S +

STO

RAG

E F

ACI

LITY

DATE

100%

CO

NST

RUC

TIO

N D

OCU

MEN

TS

SHEET

SHEET TITLESLATE#15056

SLAT

E AR

CHIT

ECTU

RE, I

NC.

107

W. L

AWRE

NCE

STR

EET

HEL

ENA,

MON

TAN

A 59

601

T |

406.

457.

0360

WW

W.S

LATE

ARCH

ITEC

TURE

.COM

6/1

4/2

016 1

0:2

1:2

1 A

M

A6.1

MAY 27, 2016

DOOR & WINDOWSCHEDULE,

ELEVATIONS &DETAILS

JPASWC

3" = 1'-0"1 TYPICAL EXTERIOR FLASHING DETAIL

DOOR SCHEDULE

DOORNO.

ELEVATIONTYPE

DOOR FRAME GLAZINGTYPE

FIRERATING

HARDWARE(PER SPECS)

DETAILS

COMMENTSWIDTH HEIGHT THICKNESS MATERIAL FINISH MATERIAL FINISH WIDTH HEAD JAMB SILL

101 C 12' - 0" 10' - 0" COILINGDOOR

FACTORY METALTRACK

FACTORY 3 HR H13 8/A6.2 9/A6.2 10/A6.2

103 E 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT-3 HM PNT-3 0' - 8 3/8" G-3 H8 4/A6.2 5/A6.2 NA

104 E 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT-3 HM PNT-3 0' - 6" G-3 H8 4/A6.2 5/A6.2 NA

105 E 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT-3 HM PNT-3 0' - 6" G-3 H8 4/A6.2 5/A6.2 NA

107 E 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT-3 HM PNT-3 0' - 8 3/8" G-3 H8 4/A6.2 5/A6.2 NA

108A A 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT-3 HM PNT-3 0' - 8 3/8" 1 HR H9 4/A6.2 5/A6.2 NA

108B A 3' - 0" 7' - 0" 0' - 1 3/4" HM/GALV PNT-3 HM/GALV PNT-3 0' - 5 3/4" H1 5/A6.3 5/A6.3 6/A6.2

109A D 12' - 0" 10' - 0" 0' - 2" SECTIONAL FACTORY STEEL OHDOOR

FACTORY H11 6/A6.3 7/A6.3 NA

109B A 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT-3 HM PNT-3 0' - 5 3/4" H3 8/A6.3 8/A6.3 9/A6.3

109C A 3' - 0" 7' - 0" 0' - 1 3/4" HM/GALV PNT-3 HM/GALV PNT-3 0' - 5 3/4" H1 5/A6.3 5/A6.3 6/A6.2

110 F 6' - 0" 8' - 0" 0' - 1 3/4" HM PNT-3 HM PNT-3 0' - 6" G-3 H7 4/A6.2 5/A6.2 NA

111A A 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT-3 HM PNT-3 0' - 7 3/8" 3 HR H4 4/A6.2 5/A6.2 6/A6.2

111B A 3' - 0" 7' - 0" 0' - 1 3/4" HM/GALV PNT-3 HM/GALV PNT-3 0' - 5 3/4" H2 5/A6.3 5/A6.3 6/A6.2

111C EXISTING 3' - 0" 7' - 0" 0' - 1 3/4" EXISTING EXISTING EXISTING EXISTING H10 NA NA NA REUSING EXISTING DOOR, BUTREPLACE HARDWARE.

112A C 12' - 0" 10' - 0" COILINGDOOR

FACTORY METALTRACK

FACTORY 1 HR H12 3/A6.3 4/A6.3 NA

112B C 12' - 0" 10' - 0" COILINGDOOR

FACTORY METALTRACK

FACTORY 1 HR H13 11/A6.2 12/A6.2 13/A6.2

112C C 12' - 0" 10' - 0" COILINGDOOR

FACTORY METALTRACK

FACTORY 1 HR H12 3/A6.3 4/A6.3 NA

113A D 12' - 0" 10' - 0" 0' - 2" SECTIONAL FACTORY STEEL OHDOOR

FACTORY H11 1/A6.3 2/A6.3 1/A8.1

113B A 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT-3 HM PNT-3 0' - 5 3/4" 3 HR H4 10/A6.3 11/A6.3 12/A6.3

114 A 4' - 0" 7' - 0" 0' - 1 3/4" HM PNT-3 HM PNT-3 0' - 8 3/8" H6 4/A6.2 5/A6.2 NA

200A B 10' - 0" 10' - 0" 0' - 1 3/4" HM PNT-3 HM PNT-3 0' - 5 3/4" H5 1/A6.2 2/A6.2 3/A6.2

200B C 10' - 4" 10' - 0" COILINGDOOR

FACTORY METALTRACK

FACTORY 3 HR H14 1/A6.2 2/A6.2 3/A6.2

201 F 6' - 0" 8' - 0" 0' - 1 3/4" HM PNT-3 HM PNT-3 0' - 8 3/8" G-3 H7 4/A6.2 5/A6.2 NA

203 A 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT-3 HM PNT-3 0' - 8 3/8" 1 HR H9 4/A6.2 5/A6.2 NA

204A D 12' - 0" 10' - 0" 0' - 2" SECTIONAL PNT-3 STEEL OHDOOR

FACTORY H11 6/A6.3 7/A6.3 NA

204B A 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT-3 HM PNT-3 0' - 5 3/4" H3 8/A6.3 8/A6.3 NA

204C A 3' - 0" 7' - 0" 0' - 1 3/4" HM/GALV PNT-3 HM/GALV PNT-3 0' - 5 3/4" H1 5/A6.3 5/A6.3 6/A6.2 NO EXTERIOR HARDWARE

205 A 4' - 0" 7' - 0" 0' - 1 3/4" HM PNT-3 HM PNT-3 0' - 6" H6 4/A6.2 5/A6.2 NA

206 A 4' - 0" 7' - 0" 0' - 1 3/4" HM PNT-3 HM PNT-3 0' - 6" H6 4/A6.2 5/A6.2 NA

207 C 12' - 0" 10' - 0" COILINGDOOR

FACTORY METALTRACK

FACTORY 1 HR H12 3/A6.3 4/A6.3 NA

WINDOW SCHEDULE

MARK

FRAME DETAILS GLAZINGTYPE COMMENTSMATERIAL FINISH HEAD/JAMB SILL

A-1 ALUM WINDOW FACTORY 4/A6.1 5/A6/1 IG-1

A-2 ALUM WINDOW FACTORY 2/A6.1 3/A6/1 IG-1

B ALUM WINDOW FACTORY 4/A6.1 5/A6/1 IG-1

C ALUM STORE FRONT FACTORY 2/A6.1 3/A6/1 IG-1

D ALUM STORE FRONT FACTORY 4/A6.1 5/A6/1 IG-1

DOOR AND FRAME ELEVATION

WINDOW ELEVATIONS

3" = 1'-0"4 WINDOW HEAD DETAIL (JAMB SIM.)

3" = 1'-0"5 WINDOW SILL DETAIL

3" = 1'-0"2 WINDOW HEAD DETAIL METAL SIDING (JAMB SIM)

3" = 1'-0"3 WINDOW SILL DETAIL METAL SIDING

SIGNAGE SCHEDULE

DOOR NO.ROOM

NO. ROOM NAME TYPE SIGN TEXT BRAILLE SIGN COMMENTS

103 103 OFFICE SN-3 Yes PROVIDE CLEAR VIEW ROOM NAME INSERT

104 104 OFFICE SN-3 Yes PROVIDE CLEAR VIEW ROOM NAME INSERT

105 105 OFFICE SN-3 Yes PROVIDE CLEAR VIEW ROOM NAME INSERT

107 107 OFFICE SN-3 Yes PROVIDE CLEAR VIEW ROOM NAME INSERT

108A 108 STAIR SN-1 EXIT STAIR Yes

108B 108 STAIR SN-2 EXIT Yes

109B 109 COLLECTIONS SN2 & SN-4 COLLECTIONS Yes

109C 109 COLLECTIONS SN-2 EXIT Yes

110 110 SECURE WORK SN-4 SECURE WORK Yes

111A 111 VEST. SN-2 EXIT Yes

111B 111 VEST. SN-2 EXIT Yes

113B 113 LOADING DOCK VESTIBULE SN-4 LOADING DOCK Yes

114 114 MECHANICAL SN-4 MECHANICAL Yes

201 201 SECURE WORK SN-4 SECURE WORK Yes

203 203 STAIR SN-1 EXIT STAIR Yes

204B 204 COLLECTIONS SN2 & SN-4 COLLECTIONS Yes

204C 204 COLLECTIONS SN-2 EXIT Yes

205 205 MECHANICAL ROOM SN-4 MECHANICAL Yes

206 206 STORAGE SN-4 STORAGE Yes

SIGN TYPES

1

1 ADDENDUM #1 6/9/16

2 ADDENDUM #2 6/14/16

2

Page 6: ADDENDUM 2 107 W. Lawrence St. Helena, MT 59601 2 107 W. Lawrence St. Helena, MT 59601 Phone: 406.457.0360 This Addendum is issued to inform bidders of clarifications to the plans

PLUMBING FIXTURE SCHEDULE

MARK MFGRMODEL

NUMBERDESCRIPTION MATERIAL & FINISH TRIM

ROUGH-IN SIZEREMARKS

RL/ORL WASTE VENT COLD HOT

DS-1 JR SMITH 1771 ROOF DRAIN DOWN SPOUT NOZZLE POLISHED BRONZE NASEE

PLANS- - - - - - - -

PROVIDE CAST BRASS UNIT WITH MACHINED OUTLET WITH SET SCREWS, FLANGE, ANDJR SMITH QUAD CLOSE TRAP SEAL.

FS-1 ZURN Z1901 12"X12"X8" DEEP FLOOR SINK

PORCELAIN ENAMEL LINED CASTIRON BODY WITH NICKEL BRONZE

GRATENA - -

SEEPLANS

SEEPLANS

- - - -

PROVIDE COMPLETE WITH NO-HUB OUTLET, CAST IRON BODY WITH WHITE A.R.E.INTERIOR, 3_

4 GRATE, ALUMINUM DOME STRAINER AND JR SMITH QUAD CLOSE TRAP

SEAL.

HB-1 WOODFORD MODEL 24 ANTI-SIPHON WALL HYDRANT CHROME NA - - - - - - 3_4" - - COORDINATE MOUNTING HEIGHT IN FIELD

HB-2 WOODFORD MODEL 65ANTI-SIPHON, FREEZELESS WALL

HYDRANTCHROME NA - - - - - - 3_

4" - - COORDINATE MOUNTING HEIGHT AND STEM LENGTH IN FIELD

RD-1 JR SMITH 1800YROOF DRAIN AND OVER FLOW

DRAIN ASSEMBLYCAST IRON BODY WITH GALVANIZED

CAST IRON DOMENA

SEEPLANS

- - - - - - - -PRIMARY AND SECONDARY ROOF DRAIN ASSEMBLY WITH DECK PLATE, CAST IRON

DOME STRAINERS AND EXPANSION JOINTS ON OUTLETS. INSULATE DRAIN SUMPS ANDINTERIOR SIDE OF DECK PLATE.

SK-1 ELKAY DLRS332210PD33"X22"X10" SINGLE BOWL, TOP

MOUNT, SINK18 GAUGE 304 STAINLESS STEEL

MOEN MODEL#8289 FAUCET

- - 1-1/2" 1-1/2" 1_2" 1_

2"

PROVIDE COMPLETE 3 FAUCET MOUNTING HOLES, CHROME P-TRAP, QUARTER TURNSTOP VALVES AND ELKAY MODEL # LK335 REMOVABLE CONICAL BASKET STRAINER.

NOTES: PROVIDE ALL FIXTURE WITH APPROPRIATE COMMERCIAL GRADE SUPPORTS/CARRIERS, P-TRAPS, STOP VALVES, BRAIDED FLEXIBLE SUPPLIES, UNDER FIXTURE PIPING INSULATION AND HAMMER ARRESTORS. PROVIDE AND INSTALL TRAP PRIMERS FOR ALL FLOOR DRAINS ANDFLOOR SINKS UNLESS OTHERWISE INDICATED. INSTALL ALL TRAP PRIMERS IN RECESSED WALL MOUNTED BOXES IN AN ACCESSIBLE LOCATION. FIELD COORDINATE INSTALLATION LOCATION OF TRAP PRIMER WALL BOXES WITH ARCHITECT/ENGINEER.

5

AB

OF

FIC

E

103

OF

FIC

E

104

FC

-1

FC

-2

VE

ST

.

111

EW

H-1

2" S

AN

UP

2" S

AN

DN

3/4

" DC

W &

1/2

" DS

W U

P

4" R

OO

F D

RA

INO

VE

RF

LO

W O

UT

LE

T

4" R

WL T

OB

ELO

W G

RA

DE

DS

-1

HR

-1

HB

-2

3/4"ø DCW

1

AB

2

HR

V-1

HV

AC

-2

HP

-1

P-1

P-2

FS

-1

FS

-1

HB

-1

HE

LLE

NB

RA

ND

PR

OM

AT

E 7

.0T

AW

AT

ER

SO

FT

EN

ER

- INS

TA

LL P

ER

MA

NU

FA

CT

UR

ER

S IN

ST

RU

CT

ION

S

AS

-12"ø

HP

S2"ø

HP

R

1/2

"ø D

SW

3/4

"ø D

CW

3"ø

HP

R3"ø

HP

S1/2

"ø D

SW

3/4

"ø D

CW

HC

CC

-1

3/4

" DC

W T

O W

AT

ER

SO

FT

EN

ER

HPSHPR

DR

AW

N B

Y:

CH

K'D

BY

:

AP

PR

. BY

:

DA

TE

:

NE

W C

OL

LE

CT

ION

S +

ST

OR

AG

E F

AC

ILIT

Y

2880 Techno

logy Blvd W

Bozem

an, MT

59718

Phone: (406

) 587-0721F

ax: (406) 922-6702

©C

OP

YR

IGH

T M

OR

RIS

ON

-MA

IER

LE

, INC

.,

SK

P-01

MS

U P

PA

# 13-0

093

MU

SE

UM

OF

TH

E R

OC

KIE

S

AD

DE

ND

UM

#2

EC

R

EC

R

6-14-16

EC

R

N

1/8

" = 1

'-0"

2R

evis

ed L

eve

l 1 P

lum

bin

g S

KP

-01

N

1/8

" = 1

'-0"

3R

evis

ed L

eve

l 2 P

lum

bin

g S

KP

-01

Page 7: ADDENDUM 2 107 W. Lawrence St. Helena, MT 59601 2 107 W. Lawrence St. Helena, MT 59601 Phone: 406.457.0360 This Addendum is issued to inform bidders of clarifications to the plans

Phone: 406-542-9150 P.O. Box 967 Missoula, MT 59806 Fax: 406-542-3515

Phone: 406-577-2772

Phone: 406-234-5565

P.O. Box 6581

P.O. Box 1298

Bozeman, MT 59771

Miles City, MT 59301

Fax: 406-587-4282

Fax: 406-234-5566

Museum of the Rockies: Pre-Bid Walk-Through Sign-In

Name Company Email Phone

Brian Beck Jackson [email protected] (406) 493-4389

Taylor Erskine Jackson [email protected] (406) 880-3368

Jeff Geiger Precision Plumbing [email protected] (406) 589-7075

Sandi Bocher Townsend Electric [email protected] (406) 266-5279

Ben Ehlers Valley Electric [email protected] (406) 546-1671

James Clore Peak Painting & Drywall [email protected] (406) 580-5271

Jacob Augeustein Slate Architecture [email protected] (406) 457-0365

John Collet The Third Element [email protected] (406) 465-6945

Scott Cromwell Slate Architecture [email protected] (406) 459-1768

Scot Horning Williams Plumbing [email protected] (406) 922-3124

Dan Bokma Williams Plumbing [email protected] (406) 922-3136

Joe Dolan Central Excavation [email protected] (406) 570-5615

Erik Renna MMI [email protected] (406) 922-6841

Mike Hickman MMI [email protected] (406) 922-6829

Jamie Bigson S Conley [email protected] (406) 585-7333

Jay Fischer MMI [email protected] (406) 581-6603

Austin Hagel CK May Excavating [email protected] (406) 314-2962

Dave Yaggy Western States Fire Protection [email protected] (406) 539-5121