air handling units ris p eko 3 - salda - salda range ris p eko 3.0 presentation.pdf · air handling...
TRANSCRIPT
New range - 5 sizes, 20 models!
1 2 3 4
AIR HANDLING UNITS
RIS P EKO 3.0
E f f i c i e n c y up to 94%!
E x t r e m e l y low height !
Efficient ECfans!
Contents
Basic features 4
RIS P EKO 3.0 full range 5
RIS 400P EKO 3.0 6
RIS 700P EKO 3.0 9
RIS 1200P EKO 3.0 12
RIS 1900P EKO 3.0 15
RIS 2500P EKO 3.0 18
Accessories 21
Installation assembly 23
Controls 24
Type name codes 26
Article numbers of new AHU range 26
4
Basic features
Air handling units RIS P EKO are equipped with high efficiency cross - coun-
ter flow heat exchanger and EC motors. AHU range is used for ventilation of
houses, offices or other heated premises: classrooms, apartments, confer-
ence rooms and other.
•Air output range 200 - 2500 m3/h.
•Wide range – 5 sizes, 20 models !
•Extremely low height !
•EnergysavingandlownoiseECfanscompliantwithErPdirective2009/125/EC.
•Efficiencyofheatexchangerupto94%.
•Integrated electrical heater or optional water heater/cooler on the duct.
•Motorized 100% by-pass damper.
•EfficientandlowpressurelosspanelfiltersF7/F5.
•Designed for installation under the ceiling.
•FullintegratedPlug&Playcontrolsystem.
Construction
•Framelessconstructionfromdoubleskinnedpanels.
•Acoustic and thermal insulation of the walls - RIS 400 - 2500P EKO - 30/50 mm.
•RIS 400P - 700P EKO housing: powder coated white colour painting RAL 9016,
RIS 1200P – 2500P EKO - grey colour RAL 7040.
•Easyremovableorpluginelectricalheater(Plug&Play).
•Accesstointernalcomponentsbyhingeddoorwithlocks(removabledoorsalso).
•QuickandeasyaccesstocontrolboardandPlug&Playbyopeningseparate
compartment on the side of the unit.
•Stainless steel condensate tray.
•Fittedwithmountingbrackets.
5
Air flow [m3/h]
Airflow[m3/h]
Staticpressure[Pa]
Airflow[l/s]
Power[W
]
600
800
RIS 400P EKO 3.0
RIS 700P EKO 3.0
RIS 1200P EKO 3.0
RIS 1900P EKO 3.0
RIS 2500P EKO 3.0
PerformancePower consumption
400P EKO 3.0
700P EKO 3.0
1200P EKO 3.0
1900P EKO 3.0
2500P EKO 3.0
RIS P EKO 3.0 full range
6
DimensionsRIS 400P EKO 3.0
1014
1300
1361
200
712
670
330
148
31
304
148
7
0.9 EKO 3.0 1.6 EKO 3.0 3.0 EKO 3.0Heater -phase/voltage [50Hz/VAC] ~1, 230 ~1, 230 ~3, 400
-power consumption [kW] 0,9 1,6 3,0Fans -phase/voltage [50Hz/VAC] ~1, 230
exhaust -power/current [kW/A] 0,125 / 1,17-speed [min-1] 3490
supply -power/current [kW/A] 0,134 / 1,18-speed [min-1] 3490
Motor protection class IP-44Thermalefficiency 90%Max power consumption [kW/A] 1,16 / 6,39 1,86 / 9,39 3,26/15,39Automatic control integratedFilterclass-exhaust F7 -supply M5Thermal insulation [mm] 30Weight [kg] 74,0ComplywithERP2013 +
RIS 400PE EKO 3.0Performance
Power consumption
Extract airExhaust air Freshair Supply air
Temperature efficiency Airflow[l/s]
η[%
]
Airflow[m3/h]
Staticpressure[Pa]
Airflow[m3/h]
Airflow[l/s]
Power[W
]
Exhaust air
Specific fan power
Airflow[m3/h]
Staticpressure[Pa]
Airflow[l/s]
Power[W
]
Supply air
Airflow[l/s]
Staticpressure[Pa]
Airflow[m3/h]totalpowerforsupply&exhaustfanskWairflowm3/h x 3600SFP=
160
140
120
100
80
60
40
20
0
160
140
120
100
80
60
40
20
0
Viewfrominspectionside
RIS 400PE EKO 3.0
Airflowtemperaturerangefrom-7°Cto+40°CDesigned for operation indoors only
Technical data
RIS 400PE EKO 3.0 Lwa total, dB(A)
LWA,dB(A)125 Hz 250 Hz 500 Hz 1kHz 2kHz 4kHz 8kHz
Supply 67 54 59 64 58 57 54 47Extract 58 48 50 53 51 48 46 41Surrounding 51 40 43 46 45 40 39 36Measured at 443 m3/h, 100 Pa
Extractair=20°C/60%RH-Outdoorair=-7°C/90%RHBalancebetweensupplyair/extractair=1.0
Extractair=20°C/60%RH-Outdoorair=2°C/90%RHBalancebetweensupplyair/extractair=1.0
Extractair=20°C/60%RH-Outdoorair=7°C/90%RHBalancebetweensupplyair/extractair=1.0
8
Technical data
400PW EKO 3.0Heater -phase/voltage [50Hz/VAC] AVS200-power consumption [kW]Fans -phase/voltage [50Hz/VAC] ~1, 230
exhaust -power/current [kW/A] 0,125/1,17-speed [min-1] 3490
supply -power/current [kW/A] 0,134/1,18-speed [min-1] 3490
Motor protection class IP-44Thermalefficiency 90%Max power consumption [kW/A] 0,26/2,39Automatic control integratedFilterclass-exhaust F7 -supply M5Thermal insulation [mm] 30Weight [kg] 73,0ComplywithERP2013 +
RIS 400PW EKO 3.0Performance
Power consumption
Extract airExhaust air Freshair Supply air
Temperature efficiency Airflow[l/s]
η[%
]
Airflow[m3/h]
Staticpressure[Pa]
Airflow[m3/h]
Airflow[l/s]
Power[W
]
Exhaust air
Specific fan power
Airflow[m3/h]
Staticpressure[Pa]
Airflow[l/s]
Power[W
]
Supply air
Airflow[l/s]
Staticpressure[Pa]
Airflow[m3/h]totalpowerforsupply&exhaustfanskWairflowm3/h x 3600SFP=
160
140
120
100
80
60
40
20
0
160
140
120
100
80
60
40
20
0
Viewfrominspectionside
RIS 400PW EKO 3.0
Airflowtemperaturerangefrom-7°Cto+40°CDesigned for operation indoors only
Extractair=20°C/60%RH-Outdoorair=-7°C/90%RHBalancebetweensupplyair/extractair=1.0
Extractair=20°C/60%RH-Outdoorair=2°C/90%RHBalancebetweensupplyair/extractair=1.0
Extractair=20°C/60%RH-Outdoorair=7°C/90%RHBalancebetweensupplyair/extractair=1.0
RIS 400PW EKO 3.0 Lwa total, dB(A)
LWA,dB(A)125 Hz 250 Hz 500 Hz 1kHz 2kHz 4kHz 8kHz
Supply 67 54 59 64 58 57 54 47Extract 58 48 50 53 51 48 46 41Surrounding 51 40 43 46 45 40 39 36Measured at 443 m3/h, 100 Pa
9
DimensionsRIS 700P EKO 3.0
35
8
1461
241,7 486,6
1074
16
0
48
6,6
72
8,3
1422
97
0
85
6,6
10
Technical data
RIS 700PE EKO 3.0Performance
Power consumption
Extract airExhaust air Freshair Supply air
Temperature efficiency Airflow[l/s]
η[%
]
Airflow[m3/h]
Staticpressure[Pa]
Airflow[m3/h]
Airflow[l/s]
Power[W
]
Exhaust air
Specific fan power
Airflow[m3/h]
Staticpressure[Pa]
Airflow[l/s]
Power[W
]
Supply air
Airflow[l/s]
Staticpressure[Pa]
Airflow[m3/h]totalpowerforsupply&exhaustfanskWairflowm3/h x 3600SFP=
300
250
200
150
100
50
0
300
250
200
150
100
50
0
Viewfrominspectionside
RIS 700PE EKO 3.0
Airflowtemperaturerangefrom-7°Cto+40°CDesigned for operation indoors only
RIS 700PE EKO 3.0 Lwa total, dB(A)
LWA,dB(A)125 Hz 250 Hz 500 Hz 1kHz 2kHz 4kHz 8kHz
Supply 75 64 66 68 70 66 60 59Extract 62 53 55 57 56 52 49 45Surrounding 56 45 47 50 50 47 43 42Measured at 764 m3/h, 100 Pa
Extractair=20°C/60%RH-Outdoorair=-7°C/90%RHBalancebetweensupplyair/extractair=1.0
Extractair=20°C/60%RH-Outdoorair=2°C/90%RHBalancebetweensupplyair/extractair=1.0
Extractair=20°C/60%RH-Outdoorair=7°C/90%RHBalancebetweensupplyair/extractair=1.0
1.2 EKO 3.0 3.0 EKO 3.0 4.5 EKO 3.0Heater -phase/voltage [50Hz/VAC] ~1, 230 ~1, 230 ~3, 400
-power consumption [kW] 1,2 3,0 4,5Fans -phase/voltage [50Hz/VAC] ~1, 230
exhaust -power/current [kW/A] 0,218/1,9-speed [min-1] 3380
supply -power/current [kW/A] 0,237/2,07-speed [min-1] 3380
Motor protection class IP-44Thermalefficiency 90%Max power consumption [kW/A] 1,66/5,51 3,46/19,0 4,96/9,85Automatic control integratedFilterclass-exhaust F7 -supply M5Thermal insulation [mm] 50Weight [kg] 95,0ComplywithERP2013 +
11
RIS 700PW EKO 3.0Performance
Power consumption
Extract airExhaust air Freshair Supply air
Temperature efficiency Airflow[l/s]
η[%
]
Airflow[m3/h]
Staticpressure[Pa]
Airflow[m3/h]
Airflow[l/s]
Power[W
]
Exhaust air
Specific fan power
Airflow[m3/h]
Staticpressure[Pa]
Airflow[l/s]
Power[W
]
Supply air
Airflow[l/s]
Staticpressure[Pa]
Airflow[m3/h]totalpowerforsupply&exhaustfanskWairflowm3/h x 3600SFP=
300
250
200
150
100
50
0
300
250
200
150
100
50
0
Viewfrominspectionside
RIS 700PW EKO 3.0
Airflowtemperaturerangefrom-7°Cto+40°CDesigned for operation indoors only
RIS 700PW EKO 3.0 Lwa total, dB(A)
LWA,dB(A)125 Hz 250 Hz 500 Hz 1kHz 2kHz 4kHz 8kHz
Supply 75 64 66 68 70 66 60 59Extract 62 53 55 57 56 52 49 45Surrounding 56 45 47 50 50 47 43 42Measured at 764 m3/h, 100 Pa
Extractair=20°C/60%RH-Outdoorair=-7°C/90%RHBalancebetweensupplyair/extractair=1.0
Extractair=20°C/60%RH-Outdoorair=2°C/90%RHBalancebetweensupplyair/extractair=1.0
Extractair=20°C/60%RH-Outdoorair=7°C/90%RHBalancebetweensupplyair/extractair=1.0
700PW EKO 3.0Heater -phase/voltage [50Hz/VAC] AVS200-power consumption [kW]Fans -phase/voltage [50Hz/VAC] ~1, 230
exhaust -power/current [kW/A] 0,218/1,9-speed [min-1] 3380
supply -power/current [kW/A] 0,237/2,07-speed [min-1] 3380
Motor protection class IP-44Thermalefficiency 90%Max power consumption [kW/A] 0,46/2,5Automatic control integratedFilterclass-exhaust F7 -supply M5Thermal insulation [mm] 50Weight [kg] 95,0ComplywithERP2013 +
Technical data
12
DimensionsRIS 1200P EKO 3.0
500
686
39
1
355,5
25
0
51,5
1439
1653
1550
1319
17
2
13
25
90
90
100
1497
1439
1397
13
3.0 EKO 3.0 6.0 EKO 3.0 9.0 EKO 3.0Heater -phase/voltage [50Hz/VAC] ~1, 230 ~3, 400 ~3, 400
-power consumption [kW] 3,0 6,0 9,0Fans -phase/voltage [50Hz/VAC] ~1, 230
exhaust -power/current [kW/A] 0,37/2,5-speed [min-1] 3400
supply -power/current [kW/A] 0,45/2,95-speed [min-1] 3400
Motor protection class IP-44Thermalefficiency 90%Max power consumption [kW/A] 3,82/18,49 6,82/14,49 9,82/18,49Automatic control integratedFilterclass-exhaust F7 -supply M5Thermal insulation [mm] 50Weight [kg] 168,0ComplywithERP2013 +
RIS 1200PE EKO 3.0Performance
Power consumption
Extract airExhaust air Freshair Supply air
Temperature efficiency Airflow[l/s]
η[%
]
Airflow[m3/h]
Staticpressure[Pa]
Airflow[m3/h]
Airflow[l/s]
Power[W
]
Exhaust air
Specific fan power
Airflow[m3/h]
Staticpressure[Pa]
Airflow[l/s]
Power[W
]
Supply air
Airflow[l/s]
Staticpressure[Pa]
Airflow[m3/h]totalpowerforsupply&exhaustfanskWairflowm3/h x 3600SFP=
Viewfrominspectionside
RIS 1200PE EKO 3.0
Airflowtemperaturerangefrom-7°Cto+40°CDesigned for operation indoors only
Technical data
RIS 1200PE EKO 3.0 Lwa total, dB(A)
LWA,dB(A)125 Hz 250 Hz 500 Hz 1kHz 2kHz 4kHz 8kHz
Supply 76 58 69 71 69 67 64 56Extract 64 52 56 61 56 50 45 42Surrounding 56 42 48 50 49 48 46 40Measured at 1298 m3/h, 100 Pa
Extractair=20°C/60%RH-Outdoorair=-7°C/90%RHBalancebetweensupplyair/extractair=1.0
Extractair=20°C/60%RH-Outdoorair=2°C/90%RHBalancebetweensupplyair/extractair=1.0
Extractair=20°C/60%RH-Outdoorair=7°C/90%RHBalancebetweensupplyair/extractair=1.0
14
RIS 1200PW EKO 3.0Performance
Power consumption
Extract airExhaust air Freshair Supply air
Temperature efficiency Airflow[l/s]
η[%
]
Airflow[m3/h]
Staticpressure[Pa]
Airflow[m3/h]
Airflow[l/s]
Power[W
]
Exhaust air
Specific fan power
Airflow[m3/h]
Staticpressure[Pa]
Airflow[l/s]
Power[W
]
Supply air
Airflow[l/s]
Staticpressure[Pa]
Airflow[m3/h]totalpowerforsupply&exhaustfanskWairflowm3/h x 3600SFP=
Viewfrominspectionside
RIS 1200PW EKO 3.0
Airflowtemperaturerangefrom-7°Cto+40°CDesigned for operation indoors only
Technical data
Extractair=20°C/60%RH-Outdoorair=-7°C/90%RHBalancebetweensupplyair/extractair=1.0
Extractair=20°C/60%RH-Outdoorair=2°C/90%RHBalancebetweensupplyair/extractair=1.0
Extractair=20°C/60%RH-Outdoorair=7°C/90%RHBalancebetweensupplyair/extractair=1.0
1200PW EKO 3.0Heater -phase/voltage [50Hz/VAC] SVS500x250-power consumption [kW]Fans -phase/voltage [50Hz/VAC] ~1, 230
exhaust -power/current [kW/A] 0,37/2,5-speed [min-1] 3400
supply -power/current [kW/A] 0,45/2,95-speed [min-1] 3400
Motor protection class IP-44Thermalefficiency 90%Max power consumption [kW/A] 0,82/5,49Automatic control integratedFilterclass-exhaust F7 -supply M5Thermal insulation [mm] 50Weight [kg] 168,0ComplywithERP2013 +
RIS 1200PW EKO 3.0 Lwa total, dB(A)
LWA,dB(A)125 Hz 250 Hz 500 Hz 1kHz 2kHz 4kHz 8kHz
Supply 76 58 69 71 69 67 64 56Extract 64 52 56 61 56 50 45 42Surrounding 56 42 48 50 49 48 46 40Measured at 1298 m3/h, 100 Pa
15
DimensionsRIS 1900P EKO 3.0
88
30
0
39
9
44
44
0
18
92
10
6
16
Technical data
RIS 1900PE EKO 3.0Performance
Power consumption
Extract airExhaust air Freshair Supply air
Temperature efficiency Airflow[l/s]
η[%
]
Airflow[m3/h]
Staticpressure[Pa]
Airflow[m3/h]
Airflow[l/s]
Power[W
]
Exhaust air
Specific fan power
Airflow[m3/h]
Staticpressure[Pa]
Airflow[l/s]
Power[W
]
Supply air
Airflow[l/s]
Staticpressure[Pa]
Airflow[m3/h]totalpowerforsupply&exhaustfanskWairflowm3/h x 3600SFP=
600
500
400
300
200
100
0
600
500
400
300
200
100
0
Viewfrominspectionside
RIS 1900PE EKO 3.0
Airflowtemperaturerangefrom-7°Cto+40°CDesigned for operation indoors only
RIS 1900PE EKO 3.0 Lwa total, dB(A)
LWA,dB(A)125 Hz 250 Hz 500 Hz 1kHz 2kHz 4kHz 8kHz
Supply 77 53 64 69 73 70 65 61Extract 68 42 58 64 62 61 58 55Surrounding 60 50 52 54 54 50 48 41Measured at 1938 m3/h, 100 Pa
Extractair=20°C/60%RH-Outdoorair=-7°C/90%RHBalancebetweensupplyair/extractair=1.0
Extractair=20°C/60%RH-Outdoorair=2°C/90%RHBalancebetweensupplyair/extractair=1.0
Extractair=20°C/60%RH-Outdoorair=7°C/90%RHBalancebetweensupplyair/extractair=1.0
3.0 EKO 3.0 6.0 EKO 3.0 12.0 EKO 3.0Heater -phase/voltage [50Hz/VAC] ~1, 230 ~3, 400 ~3, 400
-power consumption [kW] 3,0 6,0 12,0Fans -phase/voltage [50Hz/VAC] ~1, 230
exhaust -power/current [kW/A] 0,488/3,16-speed [min-1] 2540
supply -power/current [kW/A] 0,485/3,12-speed [min-1] 2540
Motor protection class IP-54Thermalefficiency 90%Max power consumption [kW/A] 4,11/19,98 7,02/14,7 13,31/24,03Automatic control integratedFilterclass-exhaust F7 -supply M5Thermal insulation [mm] 50Weight [kg] 269,0 270,0 272,00ComplywithERP2013 +
17
Technical data
RIS 1900PW EKO 3.0Performance
Power consumption
Extract airExhaust air Freshair Supply air
Temperature efficiency Airflow[l/s]
η[%
]
Airflow[m3/h]
Staticpressure[Pa]
Airflow[m3/h]
Airflow[l/s]
Power[W
]
Exhaust air
Specific fan power
Airflow[m3/h]
Staticpressure[Pa]
Airflow[l/s]
Power[W
]
Supply air
Airflow[l/s]
Staticpressure[Pa]
Airflow[m3/h]totalpowerforsupply&exhaustfanskWairflowm3/h x 3600SFP=
600
500
400
300
200
100
0
600
500
400
300
200
100
0
Viewfrominspectionside
RIS 1900PW EKO 3.0
Airflowtemperaturerangefrom-7°Cto+40°CDesigned for operation indoors only
RIS 1900PW EKO 3.0 Lwa total, dB(A)
LWA,dB(A)125 Hz 250 Hz 500 Hz 1kHz 2kHz 4kHz 8kHz
Supply 77 53 64 69 73 70 65 61Extract 68 42 58 64 62 61 58 55Surrounding 60 50 52 54 54 50 48 41Measured at 1938 m3/h, 100 Pa
Extractair=20°C/60%RH-Outdoorair=-7°C/90%RHBalancebetweensupplyair/extractair=1.0
Extractair=20°C/60%RH-Outdoorair=2°C/90%RHBalancebetweensupplyair/extractair=1.0
Extractair=20°C/60%RH-Outdoorair=7°C/90%RHBalancebetweensupplyair/extractair=1.0
1900PW EKO 3.0Heater -phase/voltage [50Hz/VAC] SVS700x400-power consumption [kW]Fans -phase/voltage [50Hz/VAC] ~1, 230
exhaust -power/current [kW/A] 0,488/3,16-speed [min-1] 2540
supply -power/current [kW/A] 0,485/3,12-speed [min-1] 2540
Motor protection class IP-54Thermalefficiency 90%Max power consumption [kW/A] 1,21/5,03Automatic control integratedFilterclass-exhaust F7 -supply M5Thermal insulation [mm] 50Weight [kg] 265,0ComplywithERP2013 +
18
DimensionsRIS 2500 P EKO 3.0
481
185060
625,7 557,5 625,7
60
20
50
6,5
290
625,7 557,5 625,7
19
92
715 415,5715
10
5
40
0
145 700 261 700 145
18
8
44
49
9
19
RIS 2500PE EKO 3.0Performance
Power consumption
Extract airExhaust air Freshair Supply air
Temperature efficiency Airflow[l/s]
η[%
]
Airflow[m3/h]
Staticpressure[Pa]
Airflow[m3/h]
Airflow[l/s]
Power[W
]
Exhaust air
Specific fan power
Airflow[m3/h]
Staticpressure[Pa]
Airflow[l/s]
Power[W
]
Supply air
Airflow[l/s]
Staticpressure[Pa]
Airflow[m3/h]totalpowerforsupply&exhaustfanskWairflowm3/h x 3600SFP=
Viewfrominspectionside
RIS 2500PE EKO 3.0
Airflowtemperaturerangefrom-7°Cto+40°CDesigned for operation indoors only
Technical data
RIS 2500PE EKO 3.0 Lwa total, dB(A)
LWA,dB(A)125 Hz 250 Hz 500 Hz 1kHz 2kHz 4kHz 8kHz
Supply 80 60 68 72 75 74 71 65Extract 69 56 60 64 63 60 58 41Surrounding 62 46 54 56 57 54 50 45Measured at 2548 m3/h, 102 Pa
Extractair=20°C/60%RH-Outdoorair=-7°C/90%RHBalancebetweensupplyair/extractair=1.0
Extractair=20°C/60%RH-Outdoorair=2°C/90%RHBalancebetweensupplyair/extractair=1.0
Extractair=20°C/60%RH-Outdoorair=7°C/90%RHBalancebetweensupplyair/extractair=1.0
4.5 EKO 3.0 9.0 EKO 3.0 18.0 EKO 3.0Heater -phase/voltage [50Hz/VAC] ~3, 400 ~3, 400 ~3, 400
-power consumption [kW] 4,5 9,0 18,0Fans -phase/voltage [50Hz/VAC] ~1, 230
exhaust -power/current [kW/A] 0,725/3,24-speed [min-1] 2800
supply -power/current [kW/A] 0,675/3,0-speed [min-1] 2800
Motor protection class IP-54Thermalefficiency 90%Max power consumption [kW/A] 12,5/5,87 19,5/10,7 33,1/19,7Automatic control integratedFilterclass-exhaust F7 -supply M5Thermal insulation [mm] 50Weight [kg] 316,0 320,0 322,0ComplywithERP2013 +
20
RIS 2500PW EKO 3.0Performance
Power consumption
Extract airExhaust air Freshair Supply air
Temperature efficiency Airflow[l/s]
η[%
]
Airflow[m3/h]
Staticpressure[Pa]
Airflow[m3/h]
Airflow[l/s]
Power[W
]
Exhaust air
Specific fan power
Airflow[m3/h]
Staticpressure[Pa]
Airflow[l/s]
Power[W
]
Supply air
Airflow[l/s]
Staticpressure[Pa]
Airflow[m3/h]totalpowerforsupply&exhaustfanskWairflowm3/h x 3600SFP=
Viewfrominspectionside
RIS 2500PW EKO 3.0
Airflowtemperaturerangefrom-7°Cto+40°CDesigned for operation indoors only
Technical data
Extractair=20°C/60%RH-Outdoorair=-7°C/90%RHBalancebetweensupplyair/extractair=1.0
Extractair=20°C/60%RH-Outdoorair=2°C/90%RHBalancebetweensupplyair/extractair=1.0
Extractair=20°C/60%RH-Outdoorair=7°C/90%RHBalancebetweensupplyair/extractair=1.0
RIS 2500PW EKO 3.0 Lwa total, dB(A)
LWA,dB(A)125 Hz 250 Hz 500 Hz 1kHz 2kHz 4kHz 8kHz
Supply 80 60 68 72 75 74 71 65Extract 69 56 60 64 63 60 58 41Surrounding 62 46 54 56 57 54 50 45Measured at 2548 m3/h, 102 Pa
2500PW EKO 3.0Heater -phase/voltage [50Hz/VAC]
SVS700x400-power consumption [kW]
Fans -phase/voltage [50Hz/VAC] ~1, 230exhaust -power/current [kW/A] 0,725/3,24
-speed [min-1] 2800supply -power/current [kW/A] 0,675/3,0
-speed [min-1] 2800Motor protection class IP-54Thermalefficiency 90%Max power consumption [kW/A] 6,7/1,4Automatic control integratedFilterclass-exhaust F7 -supply M5Thermal insulation [mm] 50Weight [kg] 313,0ComplywithERP2013 +
21
2
5
1
7 10
4
8
3
1 - exhaust air fan2 - supply air fan3 - plate plate exchanger4 - filterforsupplyair5 - filterforextractair
6 - electrical heater7 - actuator of by-pass damper8 - temperature sensor for fresh air9 - humidity + temperature sensor
10 - control box
Accessories
6
9
View from inspection side
exhaust air fresh air
extract air supply air
22
Type Accessories
TPCUNI PROFLEX
1141RC02-F2KFF-U
SSB PS SupplySP
ExhaustSP
SVS SSK SKS RMG VVP/VXP SKG
AKS
AP
AVS
AVA
EKA
RIS 400PE EKO + + - LM230A-TP LM230A-TP - - - - - 200 200
RIS 400PW EKO + + 61 - NF230A LM230A-TP - - - + + 200 200
RIS 700PE EKO + + - LM230A-TP LM230A-TP - - - - - 250 250
RIS 700PW EKO + + 61 - NF230A LM230A-TP - - - + + 250 250
RIS 1200PE EKO + + int LM230A-TP LM230A-TP - 500x250 500x250 - - - -
RIS 1200PW EKO + + 61 int NF230A LM230A-TP 500x250 500x250 500x250 + + - -
RIS 1900PE EKO + + int LM230A-TP LM230A-TP - 700x400* 700x400 - - - -
RIS 1900PW EKO + + 61 int NF230A LM230A-TP 700x400* 700x400* 700x400 + + - -
RIS 2500PE EKO + + int LM230A-TP LM230A-TP - 700x400 700x400 - - - -
RIS 2500PW EKO + + 61 int NF230A LM230A-TP 700x400 700x400 700x400 + + - -
Remote controller
Differential pressureswitch
Circular duct silencer
2-3-way valve Shut-off damper
Pressure transmitterRemote controller CO2 transmitter
Thermic water valve actuator
Mounting clips
Water heater coil
Heating coil
Damper for rectangular duct
Circular ductwater cooler
Rectangular duct silencer
Electrical duct heater
1141 FLEX RC02-F2 KFF-U
Duct humidity sensorProgrammablecontroller
Programmablecontroller
UNI
PS
AKS
PRO TPC
Actuator for dampers
SP
SSB
AP
SVS
AVS
SSK
AVA
SKS
EKA
Mixing point
RMG VVP/VXP SKG
23
•Easyandquickinstallation.
•Ceilingmounted,suppliedwithrubbergaskets–vibrationabsorbers.
•Mounting position is shown above, another position mounting is prohibited.
•Unit designed for indoor installation only.
•RISPEKO3.0rangeequippedwithnewPRVV2.2controlboard.
•RISPEKO3.0versionscanbecontrolledwithUNI,PRO,TPCandFlexremotecontroldevices.
•Two RS485 ports – for remote controller and for MODBUS communication.
•The heat exchanger frost point is detected in two levels: temperature-controlled and pressure-controlled.
•Automaticdefrostingbyadjustmentofthefreshairfloworstoppingtheunitifnecessary.
•Optionalself-regulatingelectricalpre-heaterontheductforefficientfrostprotection.
•Accurateandefficientpulse-widthmodulation(PWM)electricalheatercontrol.
YES NO NO NO
Installation assembly
Controls
24
FUNCTIONS
Descriptions of the functionsPRV V2.2E W
Main functions and control of functional unitsUser and servicing control level
Week timer + Holidays + Digital timer channels8 events for each day or weekday group* per week.*1-7 entire week, 1-5 working days, 6-7 weekend.
START/STOP function,,START/STOP“ function for starting or stopping operation of the heat recovery unit. „STOP“ signisindicatedonaremotecontrol(Flex).Itcanbeusedwithdoorlock,motionsensor(PIR),outsideswitchorotherexternaldigitalsignal(potential-freecontacts).On a position ,,START“ heat recovery unit operates according to the last remote controller settings.
Year-round optimization of recovery unit regulationWinter –heat recovery; Summer – cold recovery; Autumn and spring – low rotor speed/half by-pass opened.
Free Cooling functionThe premises are cooled down by supplying fresh air, when exhaust air temperature is higher thenfreshair.(Nightcoolingfunction)
Cool recoveryThe heat exchanger recovers cold air from exhaust air when premises temperature is lower than outside.
ON/OFF rotor motor control0-10V DC rotor motor speed control
By-pass ON/OFFBy-pass three-positional control
Minimum and maximum limits for supply air temperatureByactivatingtemperaturecontrolaccordingtoextractedairsensor(Min.-15°C,Max.+40°Cadjustableinservicemenu).
ON/OFF control of electric post-heaterPulse-width modulation (PWM) control of electrical heater
Accuracyof0,5°Cforsupplyairtemperature.Electric heater’s control by stages
Forthebiggercapacityelectricheaters.ON/OFF control of DX coolers
Water cooler control with three-positional valve actuatorON/OFF control of circulation pump
Fans’ speed synchronous 0-10V controlSeparate fans’ speed asynchronous 0-10V control
4 speeds for easy end-user control.“Stop” – the unit is stopped; “Low”, “Medium”, and “High”. Service menu allows adjusting each speed individually.
BOOST functionFansoperateathighspeed(setinservicemenu).Operationtimeisalsosetinservicemenu.„Boost“functionisreflectedinFLEXremote.
CO2, constant pressure, humidity controlFanspeedcontrolonly.
CO2, constant pressure controlPossibilitytoconnectCO2ortwopressuretransmitters.
Supply air temperature control according to the extract air sensorExhaust air damper control
Supply air damper controlRemote control ModBus input
Web-based software control.Remote controller input
25
FUNCTIONS
Descriptions of the functionsPRV V2.2E W
Safety/emergency signal indicationsOverheat protection
Additional electrical heater overheat protection (software).Rotor fail alarm signal
Incaseofrotorbeltbreak-uporrotoroperationstoppingindication„RotorFail“appearsonFLEXremotecontroller.
Fire alarm signalFire and smoke alarm input
TheAHUstopstillserviceisrestoredinFLEXremotecontroller.Fans’ overheating alarm signal
Filter pollution indicator by pressure drop transmitterFilter pollution indicator by working hours
A possibility to choose period of time after which indication informs about necessity to changethefilters.(Min.168h,Max.6482h)Numberofworkinghourssetasdefault-2160h.Other indications
FanRun functionUnit in operation signal.
FanFail functionUnitoffoperationsignal.
Extracted air temperature sensorExhaust air temperature sensor
Returning water temperature sensorExtracted air relative humidity converter
Fresh air temperature sensorSupplied air temperature sensor
ControllersFLEX controller
Adjustmentofthenewcontrollerwithcontrolautomatics–Fullcontrol(servicecontrolincluded).
UNI PRO TPC*
• Absentcontrolfunctions:• Boostconfigurationmenu(time,fanspeed,nightcooling),temperatureandtimeconfiguration
ofwaterheater);• Servicemenu-PIconfiguration;• Reviewofseparatealarmsatonetime;• DXcoolingconfigurationpossibility;• Nightcoolingfastbuttonsetting;• Supplyandextractairfans’speedcontrol(3speedcanbeconfigured);• Functionalcomponents’typechoice.
DCV systems controlDemand-ControlledVentilationforextractedair.UsingonepressureoroneCO2transmitter.
DCV systems controlDemand-ControlledVentilationforextractedandsuppliedair.TwopressureoroneCO2transmitter.
UNI PRO TPC
26
RIS 400 P E 0.9 EKO 3.0EquippedwithnewPRVV2.2controlboard
AHUwithECmotorsandefficientcross-counterflowheatexchanger
ElectricalheaterpowerinkW
Heatertype(E-integratedelectricalheater;W-optionalwaterheater)
Housingtype(P-under-ceiling)
AHUsizeaccordingtoairflowrangem3/h
AHU with plate heat-exchanger
New control boardArticle No. RIS Date
GAGRIS1747_0017A 400 PE 0.9 EKO 3.0
From
01.10
.201
3
GAGRIS1746_0017A 400 PE 1.6 EKO 3.0
GAGRIS1692_0016A 400 PE 3.0 EKO 3.0GAGRIS1748_0019A 400 PW EKO 3.0GAGRIS1737_0008A 700 PE 1.2 EKO 3.0GAGRIS1736_0007A 700 PE 3.0 EKO 3.0GAGRIS1693_0005B 700 PE 4.5 EKO 3.0GAGRIS1738_0009A 700 PW EKO 3.0GAGRIS1744_0022A 1200 PE 3.0 EKO 3.0GAGRIS1745_0021B 1200 PE 6.0 EKO 3.0GAGRIS1701_0020B 1200 PE 9.0 EKO 3.0GAGRIS1721_0023A 1200 PW EKO 3.0GAGRIS1751_0025A 1900 PE 3.0 EKO 3.0GAGRIS1752_0024B 1900 PE 6.0 EKO 3.0GAGRIS1706_0001B 1900PE 12.0 EKO 3.0GAGRIS1753_0026A 1900 PW EKO 3.0GAGRIS1754_0027B 2500 PE 4.5 EKO 3.0GAGRIS1755_0028B 2500 PE 9.0 EKO 3.0GAGRIS1707_0015B 2500 PE 18.0 EKO 3.0GAGRIS1756_0029A 2500 PW EKO 3.0
Type name codes
Article numbers of new AHU range
http://new.salda.lt/en/selection/ahu/
Notes
UAB SALDA
Ragainės g. 100 LT-78109, Šiauliai Lithuania
Tel. +370 41 54 04 15 Fax. +370 41 54 04 17
www.salda.lt [email protected]