Alarmline II Analogue Linear Heat Sensor Cable Technical Manual P/N 20-8501-509-AHDS-02 • REV 2.1 • ISS 18NOV15

Upload: phamhanh

Post on 08-Jul-2018

252 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

P/N 20-8501-509-AHDS-02 • REV 2.1 • ISS 18NOV15

Page 2: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Copyright © 2015 UTC Fire & Security. All rights reserved.

Trademarks and

patents

Alarmline and Alarmline II Analogue Linear Heat Sensor Cable

Technical Manual name and logo are trademarks of

UTC Fire & Security.

Other trade names used in this document may be trademarks or

registered trademarks of the manufacturers or vendors of the

respective products.

Manufacturer Thermocable Flexible Elements Ltd.,

Pasture Lane, Clayton, Bradford

BD14 6LU

Authorized EU manufacturing representative:

UTC Fire & Security B.V.

Kelvinstraat 7, 6003 DH Weert, Netherlands

Version This document applies to the following Alarmline II analogue model

numbers:

AA

AAN

AAP

AASS

AASSN

AACULP

AACUSP

Certification UL and ULC listed, File number S35630, Categories UTHV & UTVH7 & UQGS & UQGS7: "Heat activated

devices for Special applications”,

FM approval: Fire Detection, Heat Activated

2012/19/EU (WEEE directive): Products marked with this symbol

cannot be disposed of as unsorted municipal waste in the European

Union. For proper recycling, return this product to your local supplier

upon the purchase of equivalent new equipment, or dispose of it at

designated collection points. For more information see:

www.recyclethis.info.

Contact information For contact information, see: www.utcfssecurityproducts.eu.

Technical helpline: +44 (0) 191 5136124

Sales enquiries: +44 (0) 1844 265003

e-mail: [email protected]

Page 3: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual i

Content

Important information ii

Chapter 1 Introduction to product 1

Introduction 2

Approvals 3

Technical Specifications 4

Chapter 2 Design and Installation overview 7

Design and installation 8

Chapter 3 Commissioning 35

Commissioning 36

Chapter 4 Application guidelines 37

Application guidelines 38

Index 48

Page 4: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

ii Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

Important information

Limitation of liability

To the maximum extent permitted by applicable law, in no event will UTCFS be

liable for any lost profits or business opportunities, loss of use, business

interruption, loss of data, or any other indirect, special, incidental, or

consequential damages under any theory of liability, whether based in contract,

tort, negligence, product liability, or otherwise. Because some jurisdictions do not

allow the exclusion or limitation of liability for consequential or incidental

damages the preceding limitation may not apply to you. In any event the total

liability of UTCFS shall not exceed the purchase price of the product. The

foregoing limitation will apply to the maximum extent permitted by applicable law,

regardless of whether UTCFS has been advised of the possibility of such

damages and regardless of whether any remedy fails of its essential purpose.

Installation in accordance with this manual, applicable codes, and the instructions

of the authority having jurisdiction is mandatory.

While every precaution has been taken during the preparation of this manual to

ensure the accuracy of its contents, UTCFS assumes no responsibility for errors

or omissions.

Advisory messages

Advisory messages alert you to conditions or practices that can cause unwanted

results. The advisory messages used in this document are shown and described

below.

WARNING: Warning messages advise you of hazards that could result in injury

or loss of life. They tell you which actions to take or to avoid in order to prevent

the injury or loss of life.

Caution: Caution messages advise you of possible equipment damage. They tell

you which actions to take or to avoid in order to prevent the damage.

Note: Note messages advise you of the possible loss of time or effort. They

describe how to avoid the loss. Notes are also used to point out important

information that you should read.

Note: Kidde Products Ltd has taken every care to ensure that Alarmline II

Analogue Linear Heat Detection systems are as simple to install as possible but

in case of difficulty, please contact our Help Line to ensure trouble free

installation and operation. Kidde Products Ltd takes no responsibility for damage

or injury occasioned as a result of failing to install or operate the equipment in

accordance with these instructions.

Page 5: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 1

Chapter 1 Introduction to product

Summary

This chapter gives an introduction to the product and product range.

Content

Introduction 2

Operation 2

Product range 3

Approvals 3

UL approval 3

Technical Specifications 4

Page 6: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 1: Introduction to product

2 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

Introduction Alarmline II Analogue Linear Heat detection systems are a flexible durable and

cost-effective form of fire detection, suitable for protecting a wide range of

commercial and industrial applications.

They provide flexibility in installation enabling them to be used for general area

protection or proximity detection close to a specific point of risk. A wide range of

alarm and pre-alarm temperatures, protective coatings and installation fixings

ensure system design and installation is specific to the risk. Alarmline II analogue

sensor cables are especially suited for confined areas and harsh environmental

conditions, which prohibit the use of other forms of detection.

Alarmline II analogue control unit provides monitoring of the sensor cable and

allows full integration with any fire alarm control system.

This manual provides technical information, installation guidelines and design

recommendations for some typical applications. This manual does not cover all

possible applications, therefore for any design and installation advice you require

please contact Kidde Products Ltd technical support on the first page (Contact

information).

Operation

Alarmline II analogue sensor cables consist of four cores. The two cores with the

clear outer coating consist of a copper conductor coated in a temperature

sensitive polymer whose resistance changes as a function of temperature. The

core with the white outer sheath provides the calibration resistance and the core

with the red outer sheath monitors the average ambient temperature. A foil shield

and protective outer coat is extruded over the twisted cores.

Figure 1: Cable construction

The Alarmline II analogue control unit monitors the resistance of the specially

doped polymers within the sensor cable which change as a function of

temperature. An abnormal change in the resistance along the detection cable

Calibration resistance

Copper cores with temperature sensitive polymer

Average ambient temperature monitor

Page 7: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 1: Introduction to product

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 3

triggers either pre-alarm or alarm conditions on the control unit. The pre-alarm

and alarm temperatures are programmed on the control unit through internal

controls or via a laptop installed with the programming software.

The control unit provides volt free contacts for pre-alarm and alarm signalling as

well as an opto-isolated photo transistor fault output, these enable simple

interfacing to any fire alarm control system.

Product range

The Alarmline II analogue sensor cable consists of one cable type with different

protective outer sheaths:

Table 1: Alarmline II product range

Part

number

Description Comments

AA Analogue sensor cable – Red PVC outer sheath

AAN Analogue sensor cable – Nylon Nylon outer sheath

AAP Analogue sensor cable – Polypropylene Polypropylene outer sheath

AASS Analogue sensor cable – Stainless

steel/PVC

Stainless steel braid over PVC

AASSN Analogue sensor cable – Stainless

steel/Nylon

Stainless steel braid over Nylon

The Alarmline II analogue control unit is provided in two versions:

AACUSP Analogue control unit – Self programmable Internal programming controls

AACULP Analogue control unit – PC programmable Requires programming software

Approvals

UL approval

The Alarmline II Analogue Linear Heat Detection system is fully UL521 approved.

The approved spacing for the sensor cable is as follows:

Table 2: UL approval

Alarmline II analogue LHD action

temperature Approved UL spacing

54°C (129.2°F) 64°C (147.2°F),

71°C (159.8°F), 72°C (161.6°F) 10m (35ft)

79°C (174.2°F), 86°C (186.8°F),

93°C (199.4°F), 100°C (212°F) 10m (35ft)

Page 8: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 1: Introduction to product

4 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

Technical Specifications

Table 3: Sensor cable

Sensor cable specification

Outer jacket PVC Nylon Polypropylene PVC outer

sheath &

stainless steel

braid

Nylon outer

sheath &

stainless steel

braid

Sensor cable

diameter

4.57 ±

0.075mm

(0.180” ±

0.003”)

5.50 ±

0.075mm

(0.217” ±

0.003”)

5.50mm ±

0.075mm

(0.217” ±

0.003”)

5.10mm ±

0.075mm

(0.200” ±

0.003”)

6.05mm ±

0.075mm

(0.238” ±

0.003”)

RFI Shielding Twisted and Foil shielding to reduce inductance and RF susceptibility

Function Colour

Sensor cable

cores

Calibration resistance White

Sensor core Red

Conductor and specially doped polymer

core

Clear

Maximum

sensor cable

length

500m (1640ft)

Minimum

sensor cable

length

30.5m (100ft)

Operating

temperature

range

-40ºC to 125ºC (-40°F to 257°F)

Continuous

ambient

temperature

range

-40ºC to 90ºC (-40°F to 194°F)

The following chart provides a chemical resistance comparison for the available

outer sheath materials on the Alarmline II analogue sensor cable.

Table 4: Outer sheath material

Outer sheath material

Chemical PVC Nylon Polypropylene

Ammonia, liquid

Butane

Copper Nitrate

Fuel Oils

Gasoline

Hydrofluoric Acid

Page 9: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 1: Introduction to product

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 5

Outer sheath material

Kerosene

Diesel Fuel

Acetic acid

Table 5: Control unit specification

Dimensions (w x h x d) 182 x 180 x 90mm (7.2” x 7.1” x 3.5”)

Enclosure material Polycarbonate with removable cover

Enclosure rating IP66 (IK08)

Enclosure finish Light grey

Supply voltage 20-28 VDC

Current consumption normal & Fault <70mA

Current Consumption, Prealarm OR

Alarm

<80mA

Current Consumption, Alarm (&

Prealarm)

<100mA

Current Consumption, Fault <70mA

Operating temperature 0ºC – 50ºC (32°F – 122°F)

Visual indicators Function Colour

Alarm Red

Pre-Alarm Red

Fault Amber

Power Green

Relay outputs ALARM, PREALARM (all Form C)

2A@30VDC load rating – resistive

0.25A@250VAC load rating – resistive

Fault output Opto-isolated Phototransistor Output

Max 50V @ 20mA

Remote reset Isolated input for resetting module remotely

(20-28VDC pulse for at least 5s)

Alarm/Pre-Alarm Temperature Range 54ºC – 100ºC (129ºF – 212ºF)

Note: 54ºC alarm or pre-alarm setting is for use in controlled ambient areas only. Specifically

when the overall sensor cable length is less than 75m (246ft) ensure the humidity and

temperature DO NOT exceed 75% and 30ºC respectively

Page 10: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical
Page 11: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 7

Chapter 2 Design and Installation overview

Summary

This chapter covers the information and guidelines required for installation.

Content

Design and installation 8

Design guidelines 8

Installation guidelines 10

Jointing 11

Hazardous area installation 15

Installation accessories 15

Alarmline II Control module configuration 24

Page 12: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

8 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

Design and installation The design and installation of an Alarmline II Analogue Linear Heat Detection

system is unique to every site and application, therefore it is recommended that

this work is only undertaken by trained and competent persons following the

guidelines in this manual. Further application specific information is provided in

section“ Application guidelines” on page 38.

Design guidelines

There are two main types of protection that can be provided by the Alarmline II

analogue sensor cable:

Proximity detection This is where the sensor cable is installed very close to the point of risk,

generally the sensor cable will be installed around the equipment to be

protected. There is no specific design criterion for these applications but

there are guidelines to be considered.

Area coverage This is where cable is distributed throughout the risk area allowing

protection of the general area as opposed to specific points. Alarmline II

analogue sensor cable offers an alternative to point type heat detectors

in this type of application

Guidelines for proximity detection

1. Selection of the appropriate sensor cable type is critical to ensure correct

performance of the system. The cable selection will be based on the

mechanical and environmental properties required.

2. The sensor cable should be installed close enough to the point of risk to give

an acceptable response, but not in a position where it can be damaged or foul

any moving parts. The location of the sensor cable should not restrict access

to any parts of the equipment which require maintenance.

3. The thermal path to the sensor cable should not be obstructed and a

minimum distance of 25mm (1”) should be left between the sensor cable and

any surface it is being mounted to.

4. It may be necessary in outdoor applications to shield the sensor cable from

direct sunlight to control the ambient temperature around the cable and

prevent the risk of false alarms.

5. For installation within a hazardous area suitable Ex ‘e’ junction box with

barrier glands are required.

6. Fixing of the cable will be determined by the application and the location at

which the cable is to be installed. The cable shall be supported at a sufficient

number of points to prevent sagging. The environmental conditions and

practicality of clips to be used needs to be taken into consideration. The

Page 13: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 9

Kidde Airsense range of standard fixing clips are show in section “Fixing clips”

on page 15.

Guidelines for Area coverage

In applications where the sensor cable is installed for general area coverage i.e.

as an alternative to point type heat detectors the positioning of the sensor cable

will generally follow the relevant local standards or approvals. The sensor cable

will generally be installed at ceiling height and laid out in such a way that

sufficient coverage is provided, see Fig 2.

Maximum spacing between cable runs will in general follow the same limits as

normal point type heat detectors and local standards for these should be

followed. The following recognised standards determine the maximum spacing

as follows:

BS5839: Maximum spacing between sensor cable runs 7.5m (25ft)

UL: Maximum spacing between sensor cable runs 10m (35ft)

Figure 2: Distributed sensor cable providing general area coverage

Note: d1=(d2/2), e.g. d1 = 5m (17.5ft), d2 = 10m (35ft)

Other design recommendations for general area coverage systems are as

follows:

1. Selection of the appropriate sensor cable type is critical to ensure correct

performance of the system. The cable selection will be based on the

mechanical and environmental properties required.

d1 – Spacing of sensor cable from the wall

d2 – Spacing between sensor cable runs

d2 d

1

Page 14: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

10 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

2. The recommended total area coverage for a single Alarmline II analogue

detection zone shall be no more than 2000m2 (6561sq feet).

3. The Alarmline II analogue sensor cable shall be installed no closer than

25mm (1”) and no further than 150mm (6”) from the fixing surface.

4. Fixing of the cable will be determined by the application and the location at

which the cable is to be installed. Sensor cable shall be supported at no

greater than 1m intervals, with additional supports where there are bends in

the cable. The environmental conditions and practicality of clips to be used

needs to be taken into consideration. Details of fixing clips provided in the

Kidde Airsense range are shown in section 2.7

5. The minimum bend radius when installing the sensor cable is 50mm (2”) for

ambient conditions of 0°C (32°F) and above. For areas where ambient

conditions are likely to be less than 0°C (32°F) the minimum bend radius is

100mm (4”).

6. For installation within hazardous areas suitable Ex ‘e’ junction boxes and

barrier glands must be used.

Installation guidelines

The installation of Alarmline II analogue sensor cable systems is specific to the

application and must be installed by trained and competent operators. This

section covers installation of the Alarmline II analogue control unit and sensor

cable.

Alarmline II analogue sensor cable installation guidelines

Note: It is highly recommended that a continuity test is carried out on the reeled

cable prior to installation to ensure no damage has occurred during transit.

As mentioned a number of times throughout this manual it is not possible to

provide definitive installation instructions as each application will be uniquely

different. The following provides some of the important requirements when

installing the analogue sensor cable.

1. Sensor cable must only be installed in the area to be protected. If the

equipment monitoring the sensor cable is not installed within the risk area

then a suitable interposing/leader cable can be connected between the

sensor cable and the monitoring equipment.

2. Sensor cables can be provided with various outer sheaths to suit the

environment such as PVC, Nylon, Polypropylene and Stainless steel braid. It

is important to select the correct protective outer sheath to suit the

environment.

3. Sensor cables should be terminated in junction boxes that are suitable to the

environment.

4. Sensor cable fixing clips should be suitable for the environment and the

surface they are being fitted to. There is no requirement for the sensor cable

Page 15: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 11

to be tensioned however on straight runs it is recommended to support the

cable at a distance of 1 metre to prevent sagging.

5. When using metal fixing clips it is necessary to protect the cable at the fixing

points by using the neoprene sleeve around the sensor cable.

6. The minimum bend radius for the sensor cable is 50mm (2”). This increases

to 100mm (4”) for areas with an ambient temperature below 0°C (32°F) i.e.

cold storage areas.

7. Cable is supplied on drums of 100m (328ft), 500m (1640ft) and 1000m

(3280ft), cables can be easily jointed to create the required sensor cable

length.

8. Sensor cable must not be painted.

9. Where possible fixing of the sensor cable should be the last stage in the

installation to prevent any damage to the cable during other installation works.

10. It is recommended to check the continuity of the cable before installation to

ensure it has not been damaged prior to installation being carried out.

11. Alarmline II analogue sensor cable should be pulled from the reel using a reel

stand. DO NOT pull the cable of the reel vertically as this will twist and may

damage the cable.

Jointing

One of the advantages of the Alarmline II analogue sensor cable is that damaged

sections of cable may be cut out and replaced without having to replace the

whole sensor cable. When a cable has been damaged the affected section of the

sensor cable may be cut away and a new section of sensor cable jointed into the

existing cable. Jointing the cable is done with a junction box and appropriate

cable glands to form a reliable, weatherproof connection.

It is important when jointing the sensor cable to ensure it is done correctly to

prevent any problems from bad connections etc. The cable can be jointed using

junction boxes or it can be soldered. It is important if the joints are to be soldered

that they are suitably protected using heat shrink sleeving, this will prevent short

circuits between the cores and also prevent any humidity getting into the joints.

Kidde Airsense can provide an In-line jointing kit (part number: 1-K82024) which

is a selection of heatshrink sleeves which will protect the soldered joint.

Interposing or leader cable

Alarmline II analogue sensor cable is to be installed only within the area it is

protecting. In some applications it is necessary to use an interposing or leader

cable to connect the sensor cable to the Alarmline II analogue control, unit. The

recommendations for interposing/leader cables are as follows:

Note: These recommendations are based on the maximum sensor cable length

of 500m (1640ft).

• Cable type: Fire rated, shielded cable

Page 16: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

12 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

• CSA e.g.: 1.3mm2 (16 AWG) Max length: 3500m (11.500ft)

0.5mm2 (20 AWG) Max length: 1000m (3.280ft)

Alarmline II analogue control unit installation guidelines

The Alarmline II analogue control unit is provided in a Polycarbonate IP66 (IK08)

enclosure therefore it is important when installing that the integrity of the control

unit is maintained. This section provides guidance on the installation of the

control unit and its associated end of line unit.

Mounting

The Alarmline II analogue control unit is designed to be wall mounted, four fixing

points are available. Fixing details are as follows:

• Minimum screw length: 20mm (0.8”)

• Maximum thread diameter: 4.5mm (10.2”)

• Maximum head diameter: 7mm (0.3”)

Figure 3. Alarmline II analogue control unit fixing centres

The end-of-line unit for the Alarmline II controller is a small metal enclosure this

should be mounted by drilling a hole no larger than 5mm (0.2”) through the base

of the enclosure, see Figure 4.

167mm (6.6”)

165m

m (

6.5

”)

Page 17: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 13

Figure 4: End of line unit

Use a suitable mounting screw of at least 19mm (0.75”) long and a washer to

secure the module.

Notes:

1. If installing the EOL unit in an external location the IP integrity of the

enclosure must be maintained.

2. If installing the sensor cable in a hazardous area the EOL unit must be

installed in a safe area. A leader cable can be used between the end of the

sensor cable and the EOL unit. The length of the leader cable is limited by the

total length of leader cable allowed on the system, see “Mounting” on page 12

Wiring connections

Figure 5 shows the internal terminal connections available on the Alarmline II

analogue control unit.

Figure 5: Control unit terminal connections

Cabling is terminated into plug-in connectors (not shown in Fig 3) the terminal

connections from left to right are detailed below.

Mounting hole location

Page 18: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

14 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

SCCR (Sensor cable connections which are Screen, Clear, Clear, Red)

Screen This is the connection for the un-insulated screen wire, the screen wire is only

terminated at the control unit end of the sensor cable.

Clear Two terminals which are used to connect the two cores coated in the transparent

insulation. It is not important which transparent insulation cable is connected to

which terminal marked clear.

Red Terminal connection for the core coated in the red insulation material.

Fault Two terminals marked + and – provide connections for the opto-isolated fault

output used signal fault status to the main fire alarm system. This is a failsafe fault

output and will be active while power is applied to the unit, a power fail will cause

the fault output to deactivate.

Alarm Three terminals marked NC (Normally closed), C (Common), NO (Normally Open)

provide volt free changeover outputs used to signal alarm activation to the main

fire alarm system.

Pre-Alarm Three terminals marked NC (Normally closed), C (Common), NO (Normally Open)

provide volt free changeover outputs used to signal pre-alarm activation to the

main fire alarm system.

In the control units normal state (no pre-alarm) the C and NC terminals are closed

circuit and the C and NO terminals are open circuit. When a pre-alarm is activated

the terminals change state C and NO become closed circuit and C and NC

become open circuit. Most fire alarm systems will connect to the C and NO

terminals and will use the change of state from open to closed circuit to indicate a

pre-alarm.

0v, 24v Two terminals for the connection of the external power supply, it is important that

the supply is connected to the correct terminals to prevent any potential damage

to the PCB.

In the self-programmable version of the control unit the supply terminals are wire

linked to the programming PCB and these connections must remain in place.

Figure 6 shows the terminal connections of the EOL monitoring unit.

Figure 6: End of Line (EOL) unit terminal connections

Connection of the sensor cable to the EOL unit is slightly different to the

Alarmline II control unit end. Four terminals are provided which are for the sensor

cable only:

Page 19: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 15

Clear Two terminals which are used to connect the two cores coated in the transparent insulation. It isnot important which transparent insulation cable is connected to which terminal marked clear.

White Terminal connection for the core coated in the white insulation material. The white core is only terminated at the EOL unit and has no termination at the Alarmline II control unit.

Red Terminal connection for the core coated in the red insulation material.

Caution: The screen (un-insulated) wire is not terminated at the EOL unit and

should be cut off.

Hazardous area installation

Alarmline II analogue sensor cable is classified as “simple apparatus” when it

comes to Hazardous areas and therefore does not require any certification. The

sensor cable can be installed within a hazardous area although the control unit

must be installed in a safe area.

All wiring must be carried out in accordance with BS EN 60079-14:2014 clause 9.

This essentially means the analogue controller and end-of-line unit must be

installed in the safe area

Analogue sensing cable can be run from the controller into a zone 0,1 or 2 area

and then back to the end-of-line unit with no special considerations are required.

It is recommended that a cable with a nylon extrusion on is used to meet the

requirements of BS EN 60079-14:2014 clause 9.3.1

All terminations within the hazardous area must be in a suitable Ex ‘e’ junction

box using barrier type cable glands which seal around the individual cores of the

sensing cable such as the HAWKE ICG 623 cable gland.

WARNING: When installing equipment in Hazardous areas close liaison with the

responsible site personnel is essential.

Installation accessories

Kidde Airsense provides a standard range of installation accessories which can

be used on many different types of application. The range of accessories

consists of fixing clips, junction boxes and cable reelers. This section provides

details of all installation accessories available within the Kidde Airsense range.

Fixing clips

Although Kidde Airsense provides an extensive range of fixing clips they may not

suit all applications. An assessment should be made to their suitability and an

alternative fixing solution may need to be investigated by the installer.

There are no specific requirements for fixing clips other than they should not

damage the sensor cable. It is recommended with most fixing clips that a

neoprene sleeve is positioned around the sensor cable at the fixing point to

Page 20: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

16 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

ensure no damage is caused by the clip or the cable tie. When installed it is not

necessary for the cable to be taut, recommendations are that the cable should be

supported every metre maximum with at least two fixing clips either side of a

cable bend.

The minimum bend radius for the sensor cable is 50mm (2”), in freezer/cold store

applications this would be extended to 100mm (4”).

T Clip

A common clip for fixing the analogue sensor cable to flat surfaces such as

ceilings, walls etc. The clip is fixed to the surface using a 6mm (0.24”)

countersunk screw with the sensor cable positioned in the channel of the clip as

shown in Fig 6. The sensor cable is held in place using a nylon cable tie (Part no.

1-B6782-121) wrapped around the clip in a figure of eight and tightened. It is

important to be careful when fixing as over tightening of the fixing screw may

cause the clip to split.

Figure 7 : T clip installation

1. Part no.: 1-B6782-004

2. Material: Plastic

3. Operating temperature: -50°C to +85°C (-58°F to +185°F) material degrades at 120°C

(248°F)

Tie wrap and cradle

The tie wrap and cradle are an alternative method for fixing Alarmline II analogue

sensor cable to flat surfaces. A cable tie is supplied with the cradle, although

larger cable ties up to 8mm (0.31”) wide can be used as alternatives. Neoprene

sleeve (Part no. 1-B6782-008) is recommended to protect the cable from being

damaged by the cable tie, as shown in Figure 8.

Page 21: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 17

Figure 8: Tie wrap and cradle installation

1. Part no. 1-27400-K245 2. Technical specification (for cradle and cable tie):

a. Material: Polyamide 6.6 b. Operating temperature: -40˚C to +85˚C c. Melting temperature: 260°C (500°F)

Edge clip

The edge clip is a quick and easy solution when fixing to a metal structure such

as a girder, angle bar etc. It is designed to be knocked onto any metal edge

using a hammer; four teeth bite into the metal edge securing it firmly with no

requirement for fixing screws. A range of clip sizes are available for various

thickness of metal, see part number list. A fixing hole in the clip allows the

securing of the sensor cable as shown in Fig 9, although it can also allow the

fixing of a distance piece (Part no. 1-B6782-210) to extend the position of the

sensor cable.

A neoprene sleeve (Part no. 1-B6782-008) is recommended to protect the cable

from being damaged by the cable tie and insulate it from the metal clip.

Figure 9: Edge clip installation

Page 22: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

18 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

1. Part nos.: 1-B6782-003: Suitable for 2-3mm thickness 1-B6782-024: Suitable for 3-8mm thickness 1-B6782-025: Suitable for 8-14mm thickness 1-B6782-026: Suitable for 14-20mm thickness 1-B6782-195: Suitable for 3-8mm, Stainless Steel version 2. Technical specification:

a. Material: Spring steel b. Max. operating temperature: Approx. 815°C (1499°F)

Pipe clip

The pipe clip is designed to utilise existing pipework which may run through the

protected area. It is designed to fit any size of pipe and should be fitted to the

underside of the pipe and be secured in place using cable ties or strapping. The

hole in the end of the clip allows for the securing of the cable using a neoprene

sleeve and cable tie, or a distance piece can be connected to extend the position

of the sensor cable. Without extending the clip the sensor cable will be supported

approx. 60mm (2.4”) below the pipe, see fig 10.

Figure 10: Pipe clip installation

1. Part no. 1-B6782-005 2. Technical specification:

a. Material: 304 Stainless Steel b. Max. operating temperature: approx. 815°C (1499°F)

V clip

The V clip is useful when installing sensor cables within cable tray installations.

Where multiple layers of cable tray exist the V clip can be fixed to the underside

of a cable tray supporting the sensor cable protecting the lower cable tray as

shown in Fig 11 and 12. The clip is designed to fit into the existing slots in the

tray itself making it quick and easy to install. The sensor cable is located in the V

channel which is approx. 60mm (2.4”) below the tray. The sensor cable is

secured using a neoprene sleeve and cable tie.

Page 23: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 19

Figure 11: V clip installation

1. Part no. 1-B6782-023 2. Technical specification:

a. Material: 304 Stainless Steel b. Max. operating temperature: approx. 815°C (1499°F)

Figure 12: V clip installation

L bracket c/w strain relief cable gland

The L bracket can be used to support Alarmline II analogue sensor cable either

above or below the risk. It is commonly used on cable trays to support the sensor

cable over the tray. A 6mm (0.24”) fixing hole is provided in the bottom of the L

bracket for securing it to its mounting surface. A strain relief cable gland is also

provided for securing the sensor cable to the bracket as shown in Figure 13.

Page 24: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

20 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

Figure 13: L bracket c/w strain relief cable gland

1. Part no. 1-B6782-154 2. Technical specification:

Bracket: a. Material: 18 swg Stainless Steel b. Max operating temperature: approx. 815°C c. Dimensions: Height 150mm Cable gland a. Material: Nylon 6.6 b. Maximum temperature: 105°C (221°F)

Channel bracket

The channel bracket is an alternative option for securing Alarmline II analogue

sensor cable to flat surfaces. Made from stainless steel the bracket has two 6mm

(0.24”) fixing holes and one 6mm (0.24”) hole for securing the sensor cable to it

as shown in Figure 14.

If necessary a distance piece can be attached to the bracket to extend the

position of the sensor cable.

Figure 14: Channel bracket

1. Part no. 1-B6782-142 2. Technical specification:

a. Material: 16 swg Stainless Steel b. Max operating temperature: approx. 815°C (1499°F) c. Dimensions: Height 60mm, Width 20mm, Depth 50mm (2.36” x 0.78” x 1.96”)

Page 25: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 21

L Bracket

The L bracket is primarily designed to be used with the edge clip as shown in Fig

14. This is a common type of clip arrangement used on floating roof tanks. Edge

clips can be connected to the foam dam around the edge of the floating roof tank

without any drilling or welding etc. A simple M6 nut and bolt arrangement is used

to attach the L bracket to the edge clip enabling the sensor to extend out over the

rim seal. The sensor cable is secured to the end of the L bracket using a cable tie

and neoprene sleeve through the 6mm (0.24”) hole. Note: this solution may not

be suitable for all floating roof tanks.

Figure 15: L bracket and edge clip

1. Part no. 1-B6782-194 2. Technical specification:

a. Material: 16 swg Stainless Steel b. Max operating temperature: approx. 815°C (1499°F) c. Dimensions: 200mm long

P Clip

The P clip is a general purpose clip which can be used to install the cable on to

any flat edge or surface it can also be used to secure the sensor cable to either

the edge clip, L bracket, channel bracket or distance piece. The clip is fitted with

a TPE sleeve insulating the cable from the metal clip and protecting it against

damage when clamped around the sensor cable. A 6.7mm (0.26”) diameter fixing

hole is provided, see Figure 16.

Figure 16: P clip

1. Part no. 1-27400-K244 2. Technical specification:

a. Material: Clamp Zinc electroplate, cold rolled steel b.Sleeve: TPE c. Max operating temperature: approx. 95°C (203°F)

Page 26: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

22 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

Distance piece

The distance piece is designed to be used in conjunction with any of the metal

clips within the Kidde Airsense range. In some installations the nearest fixing

point for the support clip may not be close enough to the point of risk therefore

the distance piece can be attached to extend the position of the sensor cable.

The distance piece is easily bolted to the clips using the 6mm (0.24”) fixing hole,

see Fig 17.

Figure 17: Distance piece

1. Part no. 1-B6782-120 2. Technical specification:

a. Material: Stainless steel 304 b. Max operating temperature: approx. 815°C (1499°F) c. Dimensions: 200mm (7.9”) long

Specialist application accessories

A significant application for Alarmline II analogue sensor cable is floating roof

storage tanks. Installation of sensor cables in this particular application provides

some significant challenges. The following accessories are specific to this type of

application to overcome the installation issues.

Retractable cable

On floating roof storage tanks where the roof moves up and down over a

considerable distance it is necessary to provide a flexible electrical connection

which can cope with the increased distance between the tank roof and tank top.

The coiled design of the retractable cable allows it to extend and contract as the

floating roof moves up and down, this maintains the electrical contact between

the junction boxes located on the tank top and the tank roof. The cable would be

used in conjunction with the cable collector, Part number 1-B6782-032. A range

of fixed length coils are provided by Kidde and the correct coil length should be

selected based upon the height of the storage tank.

Page 27: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 23

Figure 18: Retractable cable

Technical specification: Number of cores : 4 Core Colours: 1 Blue 2 Brown 3 Black 4 Yellow Core Size: 0.75 mm 2 (18AWG) Core Insulation: Hytrel Inner Sheath: Polyurethane Outer Sheath: Hytrel Cable OD: 10 mm (0.39”)

Coil OD Nom: 230 mm (9.1”)

Electrical characteristics Core to Ground Capacitance (Ci): 101 pF/m Core to Core capacitance (Cd): 83 pF/m Bus Capacitance (Cbus): 267 pF/m

Note: This cable should be overall shielded and the shield connected to the

shield wire of the analogue sensor cable.

Cable collector

The cable collector is used with the retractable cable on floating roof tank

applications. As the tank roof rises and falls the retractable cable will extend and

contract accordingly. The cable collector allows the cable to be neatly coiled

without getting caught as the tank roof rises. This prevents the retractable cable

from becoming snagged when the tank roof moves up and down.

Page 28: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

24 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

Figure 19: Cable collector

1. Part no. B6782-002 a. Material: 1.5mm BS.304 Stainless steel 304 b. Dimensions: Diameter 624 mm (25“) Height: 505 mm (20“)

Alarmline II Control module configuration

Setting up the control module is critical to ensure correct operation of the

Alarmline II Analogue Linear Heat Detection system. This section details the set-

up instructions for both the self-programmable and laptop programmable variants

of the control unit.

Note: The Alarmline II control unit will be in fault condition until configuration and

calibration has been completed.

Measuring the calibration resistance

Before the Alarmline II control unit can be configured it is necessary to measure

the calibration resistance of the sensor cable.

To measure the calibration resistance of the sensor cable it must be terminated

in the EOL unit, see section “Wiring connections” on page 13, but disconnected

from the control unit end. The calibration resistance must be measured between

the correct clear core (the clear core which is terminated within the EOL unit) and

the red and white cores as shown in Figure 20.

Page 29: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 25

Figure 20: Cable collector

1. At the Alarmline II control unit end of the sensor cable strip back the cores to

expose the internal conductors.

2. Connect an ohmmeter to one of the clear cores and the red and white core

in turn. If the resistances measured are greater than 3MΩ then switch the

ohmmeter to the other clear core. The resistance measured between the

correct clear core and the red and white cores should be within the following

ranges:

• Clear to Red: 100 - 2200Ω

• Clear to White: 520 - 8400Ω

Make a note of the resistance value between the clear and white core as this is

the calibration resistance that will be entered into the control unit.

Configuring the self-programmable control unit

The self-programmable control unit contains a programming module which

provides an LCD and internal pushbuttons to enable the user to configure without

a laptop, see Figure 21.

Page 30: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

26 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

Figure 21: Self-programmable control unit

• SELECT button: Allows the user to cycle through the available configuration

options

• SET button: Allows the user to select the option displayed on the LCD

The self-programmable control unit is also provided with a USB lead which is

required to connect the programming module to the main PCB.

The first part of configuring the control unit is to set the calibration resistance of

the sensor cable that is attached to the control unit.

1. Connect the sensor cable to the control unit and apply power.

2. The control unit when powered will display “Alarmline II Programmer” and the

unit will be in fault i.e. Fault LED on and Fault output active.

3. Press the SET button and the following screen will be displayed:

4. Using the SELECT buttons scroll through the function options until the

Commission option is displayed:

SELECT button (Black) SET button (Red)

Programming module

Page 31: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 27

Press the SET button to select this option.

5. The screen now prompts you to enter the Calibration resistance as shown:

6 Enter the calibration resistance into the control unit using the SELECT button

to cycle through the numbers and SET button to select the correct number,

each number must be entered separately followed by the SET button. The

calibration resistance is entered in kilo-ohms.

7. Once the calibration resistance is entered press SET to confirm.

8. The screen will display the following confirmation prompt:

Use the SELECT button to toggle between YES and NO options and press SET

to select the correct option.

If the NO option is selected the control unit will request the calibration

resistance again.

9. If the calibration resistance is correct select the YES option, the screen will

then display the calculated zone length. Zone length is the total length of the

sensor cable:

• This must be checked to ensure it matches the installed sensor cable length.

• Toggle between YES and NO options using SELECT button, then press SET

to select the relevant option. If the NO option is selected the control unit will

request the calibration resistance again.

Page 32: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

28 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

10. If the zone length is correct press the SET button. The display will request the

alarm temperature to be configured, see section “Configuring the self-

programmable control unit” on page 25

Setting the Alarm and Pre-Alarm temperature

Once the calibration resistance has been set, the display will prompt for the

Alarm temperature to be configured.

It is critical the alarm temperature is set correctly for the application, if the alarm

temperature is set too low there will be a risk of false alarms and if it is too high

the system may not respond quickly enough.

The Alarmline II Analogue Linear Heat Detection System is designed such that

when a section, equal to 3% of the total sensor cable length reaches a user-

defined temperature an alarm is triggered.

Example: A 30m (100ft) length of sensor cable has a configured alarm

temperature of 64ºC/147ºF. The alarm will be triggered when a 0.91m (3ft)

section of the sensor cable reaches 64ºC/174ºF.

• For a greater proportion of sensor cable subjected to an abnormal

temperature the activation temperature will be lower.

• For a smaller proportion of sensor cable subjected to an abnormal

temperature the activation temperature will be greater.

The table below shows the activation temperatures when a 1%, 2%, 3% or 5%

length of the sensor cable is subjected to an overheat condition.

Table 6: Relationship between % of cable subjected to overheat and activation

temperature

5% 3% (UL tested) 2% 1%

50°C (122°F) 54°C (129°F) 57°C (135°F) 63°C (145°f)

60°C (140°F) 64°C (147°F) 68°C (154°F) 74°C (165°F)

67°C (153°F) 71°C (160°F) 75°C (167°F) 83°C (181°F) Pre-Alarm only

68°C (154°F) 72°C (162°F) 76°C (169°F) 84°C (183°F) Alarm only

74°C (165°F) 79°C (174°F) 84°C (183°F) 95°C (203°F)

80°C (176°F) 86°C (187°F) 93°C (199°F) 103°C (217°F) Alarm only

86°C (187°F) 93°C (199°F) 100°C (212°F) 108°C (226°F) Pre-Alarm only

93°C (199°F) 100°C (212°F) 106°C (223°F) 113°C (235°F)

To set the Pre-Alarm and Alarm settings carry out the following steps:

1. The alarm temperature screen is displayed as below:

Page 33: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 29

2. Press SELECT to scroll through the alarm temperature options, when the

display shows the required alarm temperature press the SET button.

3. The display will show a prompt for the Pre-Alarm option:

Press the SELECT button to scroll between YES and NO options and press SET

when the required option is selected.

• If NO is selected then there will be no pre-alarm functionality on the control

unit.

• If YES is selected for any alarm settings where the pre-alarm option is not

available pre-alarm options will not be displayed and no pre-alarm

functionality will be provided on the unit.

4. To set the pre-alarm temperature press SELECT to scroll through the

available pre-alarm temperatures until the desired value is displayed and the

press the SET button.

The available pre-alarm settings will depend on the alarm level setting, the table

below shows the available pre-alarm settings for the respective alarm setting.

Table 7: Alarm settings

Selected alarm temperature(s) Available Pre-alarm temperature(s)

54°C (129.2°F) Not available

64°C (147.2°F) 54°C (129.2°F)

72°C (161.6°F) 54°C (129.2°F), 64°C (147.2°F)

79°C (174.2°F) 54°C (129.2°F), 64°C (147.2°F), 71°C (159.8°F)

86°C (186.8°F) 54°C (129.2°F), 64°C (147.2°F), 72°C (159.8°F),

79°C (174.2°F)

100°C (212°F) 54°C (129.2°F), 64°C (147.2°F), 72°C (159.8°F),

79°C (174.2°F), 93°C (199.4°F)

5. Following selection of the Pre-Alarm and Alarm threshold the display shows

the message “Connect Alarmline II controller”.

Page 34: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

30 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

6. Connect the USB lead between the programmer module and the main PCB

and press the SET button. This transfers the configured settings from the

programming module to the main PCB. Once complete the message

“Settings transferred ok” will appear on the display:

Diagnostic information

After configuration the display will automatically show diagnostic information.

This is useful for trained service personnel when diagnosing a problem or

confirming configuration has been performed correctly.

The display shows the ambient temperature measured by the cable in the bottom

left corner and this should be checked to ensure it closely matches the ambient

temperature around the cable ± 2.5°C (±4.5°F).

If the ambient temperature value is outside the above tolerance check the

calibration resistance and if different change the calibration resistance following

the steps 6-12 in section “Measuring the calibration resistance” on page 24.

If the calibration is the same as previously measured add or subtract 0.017kΩ to

the measured value and change the calibration value in the control unit.

To return to the “Choose functions” screen hold down the SET and SELECT

buttons together for several seconds.

Get settings

The configuration settings of the control unit can be viewed by carrying out the

following steps:

1. To access the “Choose functions” screen hold down the SET and SELECT

buttons together for several seconds.

2. Scroll the menu options using the SELECT button until the “Get Settings”

option appears on the display:

Page 35: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 31

3. Press the SET button and connect the USB cable between the programming

module and the main PCB when prompted.

4. Press the SET button and the current settings will be displayed as shown

below:

• AT = Alarm temperature

• PT = Pre-alarm temperature (-- indicates a pre-alarm value has not been set)

• Cable (m): = Sensor cable length

If the SET button is pressed again the unit will revert back to the diagnostic

information display.

Erase settings

The current configuration settings can be erased from the control unit by carrying

out the following steps:

1. To access the “Choose functions” screen hold down the SET and SELECT

buttons together for several seconds.

2. Scroll through the menu options using the SELECT button until the “Erase

Settings” option is shown on the display:

3. Connect the USB cable between the programming module and the main PCB

when prompted and press the SET button.

4. After several seconds the message “Settings Erased ok” will appear. The

control unit will go back into fault mode until the unit has been reconfigured.

Page 36: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

32 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

5. Press the SET button again and the following message will appear.

Caution: Erasing the configuration settings on the control unit will put the unit

into a fault condition and will not trigger any alarm or pre-alarms. DO NOT

LEAVE THE CONTROL UNIT IN THIS STATE. The control unit must be re-

configured as soon as possible.

Configuring the laptop programmable control Unit

The laptop programmable control unit provides LED indications only and

therefore configuration/commissioning must be carried out using a laptop and the

Alarmline II programming software. The following sections detail how to connect

and use the software.

Commissioning

1. Install and run the programming software on the laptop.

2. On the laptop software click on the green icon at the top left of the screen.

Alternatively click on the “File” menu and click on “Connect”. The following

“Connect to Device” screen will appear:

3. Connect the laptop to the Alarmline II control unit using the USB lead

provided.

4. Power on the Alarmline II control unit, the green power LED and the amber

fault LED should be illuminated.

Page 37: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 33

3. On the software “Connect to Device” screen click on the “Get Port List” button

the port number of the Alarmline II control unit should appear in the drop

down box.

6. Select the port number and click on connect, if connected the “Connect to

Device” screen will disappear and the main screen will appear.

7. Enter the measured calibration resistance in the allocated box and click the

“Set” button. See section “Measuring the calibration resistance” on page 24

for steps on measuring calibration resistance.

8. Check the calculated zone length matches the installed sensor cable length.

9. Select the required “ALARM Temperature” from the drop down box.

Page 38: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 2: Design and Installation overview

34 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

10. If using the pre-alarm temperature enable this by ticking the “PREALARM

Enabled” box and select the required “PREALARM Temperature” from the

drop down box.

11. Click the “Update settings” button to download the settings in to the Alarmline

II control unit.

12. Check the “PTC Temp” field on the software window to ensure it closely

matches the ambient temperature around the cable within ±2.5°C (±4.5°F). If

the “PTC Temp” value is outside of this tolerance disconnect the sensor cable

from the control unit and recheck the measured calibration resistance and

repeat steps 7-12. If the calibration resistance is the same as previous, add or

subtract 0.017kΩ to the calibration resistance value and repeat steps 7-12.

Get current settings

1. To access the current settings from the Alarmline II Control Unit establish

communications with the laptop/software.

2. Click on the “Get Current Settings” button and the current settings will be

displayed in the software window

3. These settings can be saved for future reference by clicking on the “File”

menu option at the top of the window and selecting “Save Configuration”

enter the required filename and press “OK”.

Erase settings

1. To erase the current settings within the Alarmline II control unit establish

communications with the laptop/software.

2. Click on the “Erase Settings” button.

3. All previous settings will be cleared and the Alarmline II control unit will show

a fault condition showing that it has not been commissioned.

Caution: Erasing the configuration settings on the control unit will put the unit

into a fault condition and will not trigger any alarm or pre-alarms. DO NOT

LEAVE THE CONTROL UNIT IN THIS STATE. The control unit must be re-

configured as soon as possible.

Page 39: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 35

Chapter 3 Commissioning

Summary

This chapter provides information on commissioning.

Content

Commissioning 36

Passive Checks 36

Functional testing 36

Page 40: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 3: Commissioning

36 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

Commissioning It is important that the cable is fully tested and inspected prior to handover the

following are recommendations to ensure this is carried out correctly.

Passive Checks

1. Visually inspect the cable to ensure correct installation in accordance with the

specification and system design.

2. Check that all clips are securely held in place and that the cable is correctly

installed within the clips.

3. Inspect all joints and terminations to ensure that they are correctly installed

and appropriate for the application and environment.

4. Check that no faults exist on the unit

5. Check that the control unit has been configured.

6. Ensure the correct pre-alarm and alarm settings are configured on the control

unit.

Functional testing

Alarmline II Analogue Linear Heat Detection system is resettable and provided

the sensor cable is not subjected to greater than 125°C (257°F) it is possible to

test the cable by applying heat to the sensor cable to confirm the pre-alarm and

alarm performance.

Functional alarm test

Caution: Testing of the cable will trigger an alarm at the monitoring equipment

therefore it may be necessary to isolate the monitoring equipment outputs.

1. Using a suitable heat source subject the cable to sufficient heat to trigger the

pre-alarm and alarm temperatures.

2. Confirm that the cable indicates the relevant alarm conditions and operates

the associated outputs.

Note: The type of functional test carried out must be agreed with the client. In

hazardous areas use of a heat source may not be possible and therefore if

agreed passive checks may be sufficient.

Page 41: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 37

Chapter 4 Application guidelines

Summary

This chapter provides guidance on most of the typical applications.

Content

Application guidelines 38

Conveyor belts 39

Escalators and moving walkways 41

Cable Trays and Racks 42

Floating roof storage tanks and bund areas 43

Cold storage/Freezer warehouses 45

Page 42: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 4: Application guidelines

38 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

Application guidelines Kidde Alarmline Analogue Linear Heat Detection Systems have been

successfully installed in a wide range of applications. Each application is different

and a thorough risk assessment must be carried out to determine the best type of

system and design. This section of the manual provides guidance on some of the

typical applications.

The following is a list of applications where Kidde Alarmline Analogue Linear

Heat Detection systems have been used:

• Cable trays and risers

• Boilers

• Conveyors

• Transformers

• Control room and computer suites - floor voids

• Cooling towers

• Alternator pits

• Control cubicle protection

• Ducting and pipework

• Radar

• Missile storage

• Engine bay protection

• Chemical/fuel storage tanks – fixed roof

• Fuel storage tanks - floating roof

• Well heads

• Power units and pumps

• Cold storage warehousing

• Service ducts

• Rolling stock

• Road and rail tunnels

• Dust extraction ducts

• Storage racking

• Grain silos and dryers

• Switchgear

• Cottages - Thatched roof

• Paint spray booths

• Paint storage

• Reactor vessels

• Extraction and ventilation systems

• Wet bench applications

• Food processing/preparation areas

• Car parks

• Passenger walkways

• Distilleries

• Baggage conveyors

Page 43: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 4: Application guidelines

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 39

• Escalators

• Industrial kitchens - Canopy protection

This list is for guidance only and other applications may exist which have not

been included.

Conveyor belts

Conveyor belts are used on many sites to transport materials/product around the

facility which can be anything ranging from coal, chemicals, luggage, minerals,

grain etc.

The main causes of fires on conveyor belts are as follows:

• Friction: Misaligned belts/Seized rollers

• Overheat: Drive motors

• Burning material: Combustible material being carried on conveyor

The effect of a fire on a conveyor can be significant as a moving conveyor could

assist with the spread of fire over a larger area.

A number of important issues need to be considered when carrying out the risk

assessment of the conveyor belt:

Table 8: Conveyor belt risk assessments

Assessment Considerations

Location If the conveyor belt is located outdoors and is not covered then the

detection system must be able to withstand being exposed to the

elements without any effect on performance or causing false alarms.

Accessibility If accessibility is likely to be an issue then a system which requires little or

no maintenance once installed is a significant advantage. Accessibility will

become more of an issue on covered conveyors.

Key risk areas Many of the key risk areas may be out of site i.e. roller bearings

underneath the belt, drive motor, cabinets etc.

Fuel type What type of material is being carried on the conveyor is it combustible, is

there the potential for a dust explosion. It may be necessary to provide a

detection system which is suitable for hazardous areas. The fuel type

would also help determine the requirement for any automatic fire-fighting

equipment and which type.

Interaction Should the detection system trigger an alarm what actions are to be taken

i.e. Automatic shutdowns, Visual/Audible warnings, activation of automatic

firefighting equipment etc.

Alarmline II Analogue Linear Heat Detection systems can provide a very effective

detection solution for the protection of conveyor belts. The flexibility of the sensor

cable allows it to be installed very close to the point of risk i.e. in close proximity

to the belt and the rollers. Once installed the cable should require no

maintenance and the system can be reset following an alarm activation provided

the sensor cable does not exceed 125°C (257°F). As it is a heat sensor the cable

Page 44: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 4: Application guidelines

40 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

is unaffected by the potential harsh environmental conditions, optional outer

sheaths prevent the cable from being damaged from exposure to the elements or

any chemicals which may be present.

Figure 22 shows the recommended areas for installing Alarmline II analogue

sensor cable on a conveyor belt.

Three locations are recommended for the sensor cable to provide complete

detection on the conveyor belt:

Table 9: Recommended locations

Location

Roller bearings Problems with friction from a misaligned belt or a seized bearing will

cause overheating. By placing the sensor cable as close as possible to

the roller bearings the earlier a potential incident can be detected. A

controlled shutdown can be implemented preventing a potential fire

incident. It is recommended that cable is run down both sides of the

conveyor.

Above the belt If the conveyor is covered it is recommended that sensor cable is fixed to

the canopy above the conveyor belt to detect for any fires on the belt,

enabling a controlled shutdown preventing potential fire spread by the

moving escalator.

Underneath It is a recommendation that sensor cable can also be installed underneath

the conveyor to detect any fires that may occur due to trash or

combustible fuel that may have fallen from the conveyor belt.

Figure 22: Alarmline II analogue sensor cable (shown in red) installed on a covered

conveyor

Page 45: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 4: Application guidelines

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 41

The sensor cable should be installed in such a way as not to interfere with

maintenance and to prevent mechanical damage. Fixing clips should be selected

based upon fixing location and available fixing surfaces, most commonly edge

clips have been used to fit to the metal framework of the conveyor.

Escalators and moving walkways

Escalators and moving walkways can be found in many buildings such as

shopping centres, airports, train stations etc. Underneath the escalator there are

many mechanical moving parts which if they become seized or damaged can

overheat due to friction. Due to the confined space under the escalator and the

harsh operating conditions i.e. dust, oil, grease it is a very difficult environment to

install any fire detection equipment.

Like the conveyor belts discussed previously Alarmline II analogue sensor cable

is flexible enough to be installed close to the main points of risk and be

unaffected by the environment. Once the cable has been installed there is no

need to access it for maintenance purposes.

Due to the number of moving parts within the escalator it may be advantageous

to use the stainless steel braided version of the cable which provides additional

mechanical protection. The recommended clip type for this application is the

edge clip making installation easier and quicker.

There are three key areas of an escalator that should be considered when

providing detection with Alarmline II analogue sensor cable:

• Bearings

• Trash collector trays

• Drive motor housings

Alarmline Analogue sensor cable can be used to protect all of these areas. Fig

23 shows the principle of protecting an escalator/moving walkway with Alarmline

II analogue sensor cable. A continuous run of cable around the bearings and the

trash collecting trays at either end provide significant coverage.

Page 46: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 4: Application guidelines

42 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

Figure 23: Protecting escalators/moving walkways using Alarmline II analogue sensor

cable

Cable Trays and Racks

In applications such as Petrochemical plants, Power generation plants etc. miles

and miles of cables are used transporting high voltages around the plant. These

can be external cable trays exposed to the elements or can be underground

cable trays hidden out of sight; either way overheating in a high voltage cable

can cause significant damage. Alarmline II Analogue Linear Heat Detection

systems are a recognised solution for being able to protect these cables close to

the point of risk.

As shown in Figure 23 sensor cable is run above the cable tray to be able to

detect an increase in temperature from the cables being protected. Generally one

length of sensor cable would be run down the cable tray but this may depend on

the width of the cable tray. Where multiple cable trays exist it is recommended

that sensor cable is run above each cable tray as shown in Figure 24.

In power generation plants and large industrial installations the general principle

of applying Alarmline II analogue sensor cable to cable tray and racks follows the

recommendations of the United Kingdom electricity generation companies.

1. A single sensor cable can be used to protect cable trays up to 600mm (24”)

wide.

2. Cable trays over 600mm (24”) wide will require multiple runs of sensor cable

to provide adequate coverage i.e. a cable tray up to 1200mm (48”) wide

requires two sensor cable runs, cable tray up to 1800mm (71”) wide would

require three sensor cable runs and so on.

Page 47: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 4: Application guidelines

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 43

3. Sensor cable should be installed between 150mm (5.9”) and 250mm (9.8”)

above the cable tray it is protecting.

The Alarmline II analogue sensor cable is supported at 1m spacing at a height of

between 150 (5.9”) and 250mm (9.8”) above each tray. This provides maximum

operating sensitivity without obstructing access to power cables etc. mounted on

tray work. It is recommended to install sensor cable on the underside of the

bottom tray or rack to further protect against "rubbish" fires.

Figure 24: Alarmline II analogue sensor cable providing cable tray protection

‘V’ clips are specially designed to support cables underneath layers of cable

trays, this is a spring steel clip designed to fit the standard holes on a cable tray,

see Figure 8: “V clip” on page 18 for further details.

Floating roof storage tanks and bund areas

Floating roof storage tanks are a high risk application and liaison with

experienced site personnel with regards to the design and installation

requirements is essential.

Floating roof storage tanks are specifically designed for the safe storage of

petroleum products such as crude oil or concentrates the roof is designed to

move up and down as the liquid content of the tank changes so there is no

vapour space. A rim seal system is provided between the tank shell and the roof

which prevents rim evaporation.

Alarmline II analogue sensor cable can be installed to detect an overheat

condition or fire around the rim seal and can be used to provide a control signal

Page 48: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 4: Application guidelines

44 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

to an automatic firefighting system such as a foam system. The Alarmline II

Analogue control unit must be installed in a safe area.

Sensor cable is installed close to the upper edge of the weather seal, using the

roof’s steel straps or the edge of the foam dam, where provided, as anchor

points. Alternatively, support clips may be provided to suit.

Sensor cable (or its interconnection wire) should be installed with consideration

of the rise and fall of the floating roof, preferably using an approved retractable

cable system, see “Installation accessories” on page 15.

Alarmline II analogue sensor cable is classified as a simple device therefore

requires no certification for use in hazardous areas. Unlike previous Alarmline

Analogue products Alarmline II Analogue systems do not require safety barriers

between the control unit and the hazardous area sensor cable although Ex ‘e’

junction boxes and barrier glands MUST be used. Figure 25 and Figure 26 show

the principles of installation.

Figure 25: Basic configuration of Floating roof tank

Page 49: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 4: Application guidelines

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 45

Figure 26: Detail of Floating tank roof detection system installation

Cold storage/Freezer warehouses

Cold storage areas and Freezer warehouses provide a difficult environment for

many types of fire detection due to the sub-zero operating temperatures of such

areas. Alarmline II analogue sensor cable can provide an acceptable solution

with its minimum operating temperature of -40°C (-40°F) allowing it to be installed

in the risk area without being effected by the environment, the analogue control

unit can be installed in a warm environment.

There are two ways Alarmline II analogue sensor cable can be used to provide

fire detection in such an application providing general area coverage or in-rack

detection.

General area coverage would follow the requirements detailed in section

“Guidelines for Area coverage” on page 9 .

The alternative type of installation for these applications is storage rack

detection. As with other applications such as conveyors, escalators etc. a

significant advantage of Alarmline II analogue sensor cable is the flexibility to be

able to install it close to the point of risk. In storage areas by being able to install

the cable within the storage racking itself it is closer to the risk and therefore able

to detect an overheat condition or fire condition considerably quicker than

general area heat sensors. This system also allows more accurate location of

where the condition occurs to provide quicker action. Installation of the Alarmline

II analogue sensor cable can be done quickly and easily by using edge clips to fix

the sensor cable to the framework of the racking. It is important to ensure the

Page 50: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Chapter 4: Application guidelines

46 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

cable is installed in a position where it is not likely to be damaged by loading and

unloading of the storage racks

There a number of precautionary measures that must be considered when

installing Alarmline II analogue sensor cable:

1. Installation should not occur in temperatures lower than -11°C (12°F) as this

can make the cable less flexible and more prone to damage. It may be

necessary to raise the temperature of the area for installation and return to

the normal operating temperature once installed.

2. Electronic interfaces and monitoring equipment must be installed outside the

low temperature area and therefore interposing/leader cables and IP66/67

junction boxes will be required.

3. The minimum bend radius at low temperatures is increased to 100mm (3.9”).

Page 51: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual 47

Page 52: Alarmline II Analogue Linear Heat Sensor Cable Technical ... · Alarmline II Analogue Linear Heat Sensor Cable Technical Manual ... Analogue Linear Heat Sensor Cable Technical

Index

48 Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

Index

A

Alarmline II Control module configuration,

23

Application guidelines, 38

Approvals, 3

C

Cable trays and racks, 42

Cold storage/Freezer warehouses, 45

Commissioning, 36

Conveyer belts, 39

D

Design and installation, 8

Design guidelines, 8

E

Escalators and moving walkways, 41

F

Floating roof storage tanks and bund areas, 43

Functional testing, 36

H

Hazardous area installation, 15

I

Important information, ii

Installation accessories, 15

Installation guidelines, 10

Introduction, 2

J

Jointing, 11

P

Passive checks, 36

S

SCCR (Sensor cable connections which are

Screen, Clear, Clear, Red), 13