aluminium or copper busbar trunking
DESCRIPTION
busbarTRANSCRIPT
![Page 1: Aluminium or Copper Busbar Trunking](https://reader031.vdocuments.net/reader031/viewer/2022020123/55cf9901550346d0339af87d/html5/thumbnails/1.jpg)
Aluminium or copper busbar trunking?
Myth busted!
Posted Oct 19 2011 by Edvard in Energy and Power with 9 Comments
On picture Canalis KTA (aluminium) busbar trunking 1250A to 3200A - Schneider Electric
Following years of copper being the material of choice for high power busbar trunking in the
UK, yet aluminium reigning supreme in the rest of the world, Schneider Electric takes a look at
the case for aluminium over copper busbar trunking at a time when cost of materials is having a
significant impact on specification choices.
The company addresses industry misperceptions and sheds light on some of the common
arguments against its widespread use including performance, weight, expansion and cost.
When it comes to performance and resistance many designers consider copper to offer a higher
performance than aluminium for the same rated bar. However, the differences are marginal as
Lee Jones from Schneider Electric explains:
“Tests show that in a 1400A load through 30 metres of 1600A of Canalis busbar trunking, the
voltage drop for aluminium was just 0.32 per cent compared to 0.30 per cent for copper. This
equates to a difference of only 5mV.
“On longer runs, we calculated a 250 metre run of Canalis 3200A aluminium busbar trunking at
2700A and at this level we found that the system had a volt drop percentage of 3.2%. According
![Page 2: Aluminium or Copper Busbar Trunking](https://reader031.vdocuments.net/reader031/viewer/2022020123/55cf9901550346d0339af87d/html5/thumbnails/2.jpg)
to the wiring regulations the maximum volt drop on power circuits on a privately owned supply
is 8%. As a guide, 40% of this 8% is lost in the sub-distribution and the balance in the final
circuit wiring. With a cable system, it’s standard practice with designers to increase the size of
cable to overcome volt drop issues. However, it seems with busbar trunking the preferred choice
is to use a copper conductor. In the calculations we then utilised a 4000A aluminium system and
compared this to a 3200A copper system.”
Tests showed that on a 250 metre length where the load is 2,700A, the voltage drop on a 4,000A
aluminium trunking is 2.70%, which is minimal when compared to a voltage drop of 2.53% on
3,200A copper trunking – equating to a difference of just 675mV or 0.17%.
Lee adds: “These examples at 250 metres were taking the product to the maximum volt drop in
sub-distribution. They were extremely long runs but indicated the length of the runs where volt
drop may become a concern.”
Following on from this point, Lee continues: “Installing aluminium busbar trunking with an
equivalent performance means that it is typically between 16% and 25% larger in volume than
copper busbar trunking. However, it is 40% lighter, offering contractors a trade-off as it’s easier
to handle, more manageable, requires less people to install it, offers a faster installation and
could eliminate the need for special lifting equipment – all saving time and money for the
contractor and the customer. In addition, the use of aluminium trunking over copper means the
building’s electrical support structures can be lighter.”
In response to the view that aluminium expands more than copper, Schneider Electric highlights
that an allowance for expansion and contraction has to be made at the point of manufacture to
ensure a reliable connection. For example, with Schneider Electric’s Canalis range, the joints
between each length feature an ‘elastic connection joint’ that automatically compensates for
expansion.
In addition, the joints on Schneider Electric’s busbar trunking range are silver plated not tin
plated as commonly used by other manufacturers. This metal offers the best electrical conduction
and resistance to abrasion when the bar is moving along the joint, providing longevity of the
installation. In fact ASEFA tests show that silver plating is 12 times better performing than tin.
In addition, copper and aluminium busbar trunking are both tested to BS EN 60439-2, so there is
no discrepancy in the standards used.
![Page 3: Aluminium or Copper Busbar Trunking](https://reader031.vdocuments.net/reader031/viewer/2022020123/55cf9901550346d0339af87d/html5/thumbnails/3.jpg)
What about the cost?
The final argument relates to cost
Even going to a higher rated aluminium trunking over copper, it still offers financial savings. In
cost comparisons between 3,200A copper versus 4,000A aluminium, there is a saving of 23%.
This increases to 35% when comparing a 3,200A rating like for like in material.
Lee Jones comments: “There are many benefits for choosing aluminium busbar trunking, which
means designers and contractors shouldn’t be put off from using it. On shorter runs the
performance difference between the two materials is marginal and on longer runs where volt
drop may be an issue, then designers can choose a higher rated aluminium bar. In addition, no
special tap-offs are required on our range because of the use of silver on the joints