Aluminium or copper busbar trunking? Myth busted! Posted Oct 19 2011 by Edvard in Energy and Power with 9 Comments On picture Canalis KTA (aluminium) busbar trunking 1250A to 3200A - Schneider Electric Following years of copper being the material of choice for high power busbar trunking in the UK, yet aluminium reigning supreme in the rest of the world, Schneider Electric takes a look at the case for aluminium over copper busbar trunking at a time when cost of materials is having a significant impact on specification choices. The company addresses industry misperceptions and sheds light on some of the common arguments against its widespread use including performance, weight, expansion and cost. When it comes to performance and resistance many designers consider copper to offer a higher performance than aluminium for the same rated bar. However, the differences are marginal as Lee Jones from Schneider Electric explains: “Tests show that in a 1400A load through 30 metres of 1600A of Canalis busbar trunking, the voltage drop for aluminium was just 0.32 per cent compared to 0.30 per cent for copper. This equates to a difference of only 5mV. “On longer runs, we calculated a 250 metre run of Canalis 3200A aluminium busbar trunking at 2700A and at this level we found that the system had a volt drop percentage of 3.2%. According

Upload: mang-porong

Post on 26-Nov-2015

29 views

Category:

Documents


3 download

DESCRIPTION

busbar

TRANSCRIPT

Page 1: Aluminium or Copper Busbar Trunking

Aluminium or copper busbar trunking?

Myth busted!

Posted Oct 19 2011 by Edvard in Energy and Power with 9 Comments

On picture Canalis KTA (aluminium) busbar trunking 1250A to 3200A - Schneider Electric

Following years of copper being the material of choice for high power busbar trunking in the

UK, yet aluminium reigning supreme in the rest of the world, Schneider Electric takes a look at

the case for aluminium over copper busbar trunking at a time when cost of materials is having a

significant impact on specification choices.

The company addresses industry misperceptions and sheds light on some of the common

arguments against its widespread use including performance, weight, expansion and cost.

When it comes to performance and resistance many designers consider copper to offer a higher

performance than aluminium for the same rated bar. However, the differences are marginal as

Lee Jones from Schneider Electric explains:

“Tests show that in a 1400A load through 30 metres of 1600A of Canalis busbar trunking, the

voltage drop for aluminium was just 0.32 per cent compared to 0.30 per cent for copper. This

equates to a difference of only 5mV.

“On longer runs, we calculated a 250 metre run of Canalis 3200A aluminium busbar trunking at

2700A and at this level we found that the system had a volt drop percentage of 3.2%. According

Page 2: Aluminium or Copper Busbar Trunking

to the wiring regulations the maximum volt drop on power circuits on a privately owned supply

is 8%. As a guide, 40% of this 8% is lost in the sub-distribution and the balance in the final

circuit wiring. With a cable system, it’s standard practice with designers to increase the size of

cable to overcome volt drop issues. However, it seems with busbar trunking the preferred choice

is to use a copper conductor. In the calculations we then utilised a 4000A aluminium system and

compared this to a 3200A copper system.”

Tests showed that on a 250 metre length where the load is 2,700A, the voltage drop on a 4,000A

aluminium trunking is 2.70%, which is minimal when compared to a voltage drop of 2.53% on

3,200A copper trunking – equating to a difference of just 675mV or 0.17%.

Lee adds: “These examples at 250 metres were taking the product to the maximum volt drop in

sub-distribution. They were extremely long runs but indicated the length of the runs where volt

drop may become a concern.”

Following on from this point, Lee continues: “Installing aluminium busbar trunking with an

equivalent performance means that it is typically between 16% and 25% larger in volume than

copper busbar trunking. However, it is 40% lighter, offering contractors a trade-off as it’s easier

to handle, more manageable, requires less people to install it, offers a faster installation and

could eliminate the need for special lifting equipment – all saving time and money for the

contractor and the customer. In addition, the use of aluminium trunking over copper means the

building’s electrical support structures can be lighter.”

In response to the view that aluminium expands more than copper, Schneider Electric highlights

that an allowance for expansion and contraction has to be made at the point of manufacture to

ensure a reliable connection. For example, with Schneider Electric’s Canalis range, the joints

between each length feature an ‘elastic connection joint’ that automatically compensates for

expansion.

In addition, the joints on Schneider Electric’s busbar trunking range are silver plated not tin

plated as commonly used by other manufacturers. This metal offers the best electrical conduction

and resistance to abrasion when the bar is moving along the joint, providing longevity of the

installation. In fact ASEFA tests show that silver plating is 12 times better performing than tin.

In addition, copper and aluminium busbar trunking are both tested to BS EN 60439-2, so there is

no discrepancy in the standards used.

Page 3: Aluminium or Copper Busbar Trunking

What about the cost?

The final argument relates to cost

Even going to a higher rated aluminium trunking over copper, it still offers financial savings. In

cost comparisons between 3,200A copper versus 4,000A aluminium, there is a saving of 23%.

This increases to 35% when comparing a 3,200A rating like for like in material.

Lee Jones comments: “There are many benefits for choosing aluminium busbar trunking, which

means designers and contractors shouldn’t be put off from using it. On shorter runs the

performance difference between the two materials is marginal and on longer runs where volt

drop may be an issue, then designers can choose a higher rated aluminium bar. In addition, no

special tap-offs are required on our range because of the use of silver on the joints