12-22
For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E
January 2001
Molded Case Circuit Breakers
12
10 – 225 AmperesF-Frame
Vol. 1, Ref. No. [0488]
Table 12-35. Type FD Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units
1 Not UL listed. 5 kAIC interrupting rating.2 UL listed for SWD applications, see NEC Article 240-83 (d).Note: Instruction Leaflet/FRED Number 29C101
Table 12-36. Types HFD and FDC Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units
3 UL listed for SWD applications, see NEC Article 240-83(d).Note: Instruction Leaflet/FRED Number 29C101
Max.Cont.AmpereRating@ 40°C
600V AC Maximum, 250V DC 277V AC Maximum, 125V DC
600V AC Maximum, 250V DC
14 kAIC @ 600V AC 25 kAIC @ 277V AC 25 kAIC @ 480V AC
Type FDB (Includes Terminals on Load End Only) Type FD (Includes Terminals on Load End Only)
2-Pole 3-Pole 4-Pole 1-Pole 2-Pole 3-Pole 4-Pole
Catalog Number
PriceU.S. $
Catalog Number
PriceU.S. $
Catalog Number
PriceU.S. $
Catalog Number
PriceU.S. $
Catalog Number
PriceU.S. $
Catalog Number
PriceU.S. $
Catalog Number
PriceU.S. $
10 1152025303540455060708090
100110125150175200225
FDB2010FDB2015FDB2020FDB2025FDB2030FDB2035FDB2040FDB2045FDB2050FDB2060FDB2070FDB2080FDB2090FDB2100FDB2110FDB2125FDB2150———
435.435.435.435.435.435.435.393.435.435.565.565.565.565.
1,260.1,260.1,260.
———
FDB3010FDB3015FDB3020FDB3025FDB3030FDB3035FDB3040FDB3045FDB3050FDB3060FDB3070FDB3080FDB3090FDB3100FDB3110FDB3125FDB3150———
570.570.570.570.570.570.570.570.570.570.695.695.695.695.
1,565.1,565.1,565.
———
FDB4010FDB4015FDB4020FDB4025FDB4030FDB4035FDB4040FDB4045FDB4050FDB4060FDB4070FDB4080FDB4090FDB4100FDB4110FDB4125FDB4150———
910.910.910.910.910.910.910.910.910.
1,110.1,110.1,110.1,110.1,110.2,495.2,495.2,495.
———
FD1010FD1015 2
FD1020 2
FD1025FD1030FD1035FD1040FD1045FD1050FD1060FD1070FD1080FD1090FD1100FD1110FD1125FD1150———
299.299.299.299.299.299.299.299.299.299.335.335.335.335.760.760.760.
———
—FD2015FD2020FD2025FD2030FD2035FD2040FD2045FD2050FD2060FD2070FD2080FD2090FD2100FD2110FD2125FD2150FD2175FD2200FD2225
735.735.735.735.735.735.735.735.735.855.855.855.855.
1,915.1,915.1,915.1,920.1,920.1,920.
—FD3015FD3020FD3025FD3030FD3035FD3040FD3045FD3050FD3060FD3070FD3080FD3090FD3100FD3110FD3125FD3150FD3175FD3200FD3225
865.865.865.865.865.865.865.865.865.975.975.975.975.
2,205.2,205.2,205.2,205.2,205.2,205.
—FD4015FD4020FD4025FD4030FD4035FD4040FD4045FD4050FD4060FD4070FD4080FD4090FD4100FD4110FD4125FD4150FD4175FD4200FD4225
1,360.1,360.1,360.1,360.1,360.1,360.1,360.1,360.1,360.1,495.1,495.1,495.1,495.3,080.3,080.3,080.3,080.3,080.3,080.
Max.Cont.AmpereRating@ 40°C
277V AC Maximum, 125V DC
600V AC Maximum, 250V DC 600V AC Maximum, 250V DC
65 kAIC @ 277V AC 65 kAIC @ 480V AC 100 kAIC @ 480V AC
Type HFD (Includes Terminals on Load End Only)
Type FDC Current Limiting (Includes Terminals on Load End Only)
1-Pole 2-Pole 3-Pole 4-Pole 2-Pole 3-Pole 4-Pole
Catalog Number
PriceU.S. $
Catalog Number
PriceU.S. $
Catalog Number
PriceU.S. $
Catalog Number
PriceU.S. $
Catalog Number
PriceU.S. $
Catalog Number
PriceU.S. $
Catalog Number
PriceU.S. $
152025303540455060708090
100110125150175200225
HFD1015 3
HFD1020 3
HFD1025HFD1030HFD1035HFD1040HFD1045HFD1050HFD1060HFD1070HFD1080HFD1090HFD1100HFD1110HFD1125HFD1150———
366.366.366.366.366.366.366.366.366.427.427.428.427.
1,001.1,001.1,005.
———
HFD2015HFD2020HFD2025HFD2030HFD2035HFD2040HFD2045HFD2050HFD2060HFD2070HFD2080HFD2090HFD2100HFD2110HFD2125HFD2150HFD2175HFD2200HFD2225
885.885.885.885.885.885.885.885.885.
1,130.1,130.1,130.1,130.2,510.2,510.2,510.2,720.2,720.2,720.
HFD3015HFD3020HFD3025HFD3030HFD3035HFD3040HFD3045HFD3050HFD3060HFD3070HFD3080HFD3090HFD3100HFD3110HFD3125HFD3150HFD3175HFD3200HFD3225
1,140.1,140.1,140.1,140.1,140.1,140.1,140.1,140.1,140.1,140.1,140.1,140.1,140.3,120.3,120.3,120.3,120.3,120.3,120.
HFD4015HFD4020HFD4025HFD4030HFD4035HFD4040HFD4045HFD4050HFD4060HFD4070HFD4080HFD4090HFD4100HFD4110HFD4125HFD4150HFD4175HFD4200HFD4225
1,940.1,940.1,940.1,940.1,940.1,940.1,940.1,940.1,940.2,445.2,445.2,445.2,445.4,405.4,405.4,405.4,370.4,370.4,370.
FDC2015FDC2020FDC2025FDC2030FDC2035FDC2040FDC2045FDC2050FDC2060FDC2070FDC2080FDC2090FDC2100FDC2110FDC2125FDC2150FDC2175FDC2200FDC2225
1,325.1,325.1,325.1,325.1,325.1,325.1,325.1,325.1,325.1,690.1,690.1,690.1,690.3,780.3,780.3,780.3,780.3,780.3,780.
FDC3015FDC3020FDC3025FDC3030FDC3035FDC3040FDC3045FDC3050FDC3060FDC3070FDC3080FDC3090FDC3100FDC3110FDC3125FDC3150FDC3175FDC3200FDC3225
1,710.1,710.1,710.1,710.1,710.1,710.1,710.1,710.1,710.2,095.2,095.2,095.2,095.4,685.4,685.4,685.4,685.4,685.4,685.
FDC4015FDC4020FDC4025FDC4030FDC4035FDC4040FDC4045FDC4050FDC4060FDC4070FDC4080FDC4090FDC4100FDC4110FDC4125FDC4150FDC4175FDC4200FDC4225
2,910.2,910.2,910.2,910.2,910.2,910.2,910.2,910.2,910.3,600.3,600.3,600.3,600.6,610.6,610.6,610.6,610.6,610.6,610.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CB-2
TAB1201.fm Page 22 Wednesday, October 25, 2000 9:37 PM
12-20
For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E
January 2001
Molded Case Circuit Breakers
12
10 – 225 AmperesF-Frame
Vol. 1, Ref. No. [0486]
Dimensions/WeightsTable 12-30. Dimensions in Inches (mm) Table 12-31. Approximate Shipping Weight, Lbs. (Kg)
Product SelectionThis information is presented only as an aid to understanding Catalog Numbers. It is not to be used to build Catalog Numbers for circuit breakers or trip units.
Table 12-32. Circuit Breaker Catalog Numbering System
Number of Poles
Width Height Depth
12
1.375 (35)2.75 (70)
6 (152)6 (152)
3.375 (86)3.375 (86)
34
4.125 (105)5.5 (140)
6 (152)6 (152)
3.375 (86)3.375 (86)
Breaker Type Number of Poles
1 2 3 4
ED, EDH, EDC — 3 (1.361) 4.5 (2.041) —
EHD, FDB, FD, HFD, FDC 2 (.907) 3 (1.361) 4.5 (2.041) 6 (2.721)
Circuit Breaker Type
EHDFDBFDHFDFDC
Number of Poles
1 = 1 Pole2 = 2 Poles3 = 3 Poles4 = 4 Poles
Trip Amperes
010015020025030035040045050060070080090100110125150175 (FD, HFD, FDC, 2-, 3-, 4-Pole Only)200 (FD, HFD, FDC, 2-, 3-, 4-Pole Only)225 (FD, HFD, FDC, 2-, 3-, 4-Pole Only)
Suffix
E = 100% Protected (4-Pole only) Neutral PoleEH = 50% Protected (4-Pole only)K = High Magnetic Molded Case SwitchL = Line and Load TerminalsS = Stainless Steel TerminalsV = 50°C CalibrationW = Without TerminalsY = Line Terminals OnlyZ = Aluminum Terminals (≤ 100 Amperes)
F D C 3 1 0 0 L
E D C 3 2 0 0 L
Circuit Breaker Type
EDEDHEDC
Number of Poles
2 = 2-Pole3 = 3-Pole
Trip Amperes
100125150175200225
Suffix
L = Line and Load TerminalsW = Without TerminalsY = Line Terminals OnlyZ = Aluminum Terminals (100 Amperes)
TAB1201.fm Page 20 Wednesday, October 25, 2000 9:37 PM
12-2
For more information contact Cutler-Hammer at:
www.ch.cutler-hammer.com/catalog
CAT.200.01.T.E
January 2001
Molded Case Circuit Breakers
12
Product Line Overview
Vol. 1, Ref. No. [0468]
Product Line Description
Cutler-Hammer Molded Case Circuit Breakers are designed to provide circuit protection for low voltage distribution systems. They are described by NEMA as, “. . . a device for closing and inter-rupting a circuit between separable contacts under both normal and abnormal conditions,” and furthermore as, “. . . a breaker assembled as an integral unit in a supporting and enclosing housing of insulating material.” The NEC describes them as, “A device designed to open and close a circuit by non-automatic means, and to open the circuit automatically on a predetermined overload of current, without injury to itself when properly applied within its rating.”
So designed, Cutler-Hammer circuit breakers protect conductors against overloads and conductors and con-nected apparatus, such as motors and motor starters, against short circuits.
In low voltage distribution systems, there are many varied applications of molded case circuit breakers. Cutler-Hammer offers the most comprehensive family of molded case circuit breakers in the industry.
This family of circuit breakers includes:
■
Thermal Magnetic Trip Breakers
■
Electronic rms Trip Breakers
■
Molded Case Switches
■
Motor Circuit Protectors
■
Current Limiting Breakers
■
Special Application Breakers
■
World Breakers
Special Calibration
Special non-UL-listed calibrations are available for certain ambient temperatures other than 40°C and for frequencies other than 50/60 Hz or DC. Reduced interrupting ratings will apply for 400 Hz applications. Maximum thermal calibration is limited to 135A at 400 Hz.
50°C Calibration
Add suffix
V
to Catalog Number for complete breaker, listed above, when ordering listed ampere ratings for breakers to be used in 50°C ambients.
Moisture-Fungus Treatment
All circuit breaker cases are molded from glass-polyester which does not support the growth of fungus. Any parts which are susceptible to the growth of fungus will require special treatment.
Freeze-Tested Circuit Breakers
The circuit breakers may be ordered with freeze testing. This option uses special lubrication and mechanical operation is verified at -40°C.
Marine Applications
F-Frame circuit breakers can be sup-plied to meet the following marine specifications:
■
U.S. Coast Guard CFR 46 ABS — American Bureau of Shipping IEEE 45
These specifications generally require molded case circuit breakers to be supplied with 50°C ambient calibration, special nameplating, and plug-in adapter kits. When plug-in adapter kits are used, no terminals need be supplied.
Circuit breakers can also be supplied to meet UL489 Supplement SA (Marine Use) and UL489 Supplement SB (Naval Use).
UL489 Supplement SA applies to vessels over 65 feet in length. Requirements include 40°C ambient calibration, spe-cial labeling, and no use of aluminum conductors or terminals.
UL 489 Supplement SB requires 50°C ambient calibration, vibration testings, special nameplating and no use of aluminum conductors or terminals.
Standards and Certifications
Molded case circuit breakers are designed to conform with the follow-ing standards:
■
Underwriters Laboratories, Inc., Standard UL489, Molded Case Circuit Breakers and Circuit Breaker Enclosures
■
National Electrical Manufacturers Association Standards Publication No. AB1-1993, Molded Case Circuit Breakers
■
Australian Standard AS 2184, Molded Case Circuit Breakers
■
British Standards Institution Standard BS 4752: Part 1, Switchgear and Control Gear Part 1: Circuit Breakers
■
Canadian Standards Association Standard C22.2 No. 5, Service Entrance and Branch Circuit Breakers
■
International Electrotechnical Commission Recommendations IEC 157-1, Circuit Breakers
■
Japanese T-Mark Standard Molded Case Circuit Breakers
■
South African Bureau of Standards, Standard SABS 156, Standard Specification for Molded Case Circuit Breakers
■
Swiss Electro-Technical Association Standard SEV 157-1, Safety Regula-tions for Circuit Breakers
■
Union Technique de l’Electricite Standard NF C 63-120, Low Voltage Switchgear and Control Gear Circuit Breaker Requirements
■
Verband Deutscher Elektrotechniker (Association of German Electrical Engineers) Standard VDE 0660, Low Voltage Switchgear and Control Gear, Circuit Breakers
Conformance with these standards satisfies most local and international codes, assuming user acceptability and simplified application.
Molded case circuit breakers equal or exceed Federal Specification Classifi-cation W-C-375b requirements for the particular class associated with the cir-cuit breaker frame being considered.
Note:
For further information, see Circuit Breaker, CD-ROM SA.74A.01.T.E.
Suffix
H01
400 Hz 20% Adder
Suffix
J01
Fungus Treated $325. + 20% Adder
Suffix
F01
Freeze Tested 20% Adder
Suffix
H08
“Marine” 10% Adder
Suffix
H09
“Naval” 10% Adder
TAB1201.fm Page 2 Wednesday, October 25, 2000 9:37 PM
CAT.200.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog
12-19January 2001
Molded Case Circuit Breakers
12
10 – 225 AmperesF-Frame
Vol. 1, Ref. No. [0485]
ContentsDescription Page
Product Description . . . . . . . . 12-19
Technical Dataand Specifications . . . . . . . . 12-19
Dimension/Weights . . . . . . . . 12-20
Product Selection . . . . . . . . . . 12-20
F-Frame
Typical F-Frame Breaker
Product Description■ All F-Frame Circuit Breakers are
HACR rated.■ All circuit breakers 10 through
50 amperes are suitable for HID (high intensity discharge) use.
■ All F-Frame circuit breakers are suitable for reverse feed use.
Technical Data and SpecificationsTable 12-28. UL489 Interrupting Capacity Ratings
1 DC ratings apply to substantially non-inductive circuits.2 2-pole circuit breaker, or two poles of 3-pole circuit breaker.3 Time constant is 3 milliseconds minimum at 10 kA and 8 milliseconds minimum at 22 kA.
Table 12-29. IEC 157-1 (P1) Interrupting Capacity Ratings (P1)
4 DC ratings apply to substantially non-inductive circuits.5 2-pole circuit breaker, or two poles of 3-pole circuit breaker.6 Time constant is 3 milliseconds minimum at 10 kA and 8 milliseconds minimum at 22 kA.
Circuit Breaker Type
Number of Poles
Interrupting Capacity (Symmetrical Amperes) (kA)
Volts AC (50/60 Hz) Volts DC 1
240 277 480 600 125 250 23
ED EDH EDC
2, 3 2, 3 2, 3
65 100200
———
———
———
101010
———
EHD 12, 3
—18
14—
—14
——
10—
—10
FDB 2, 3, 4 18 — 14 14 — 10
FD 12, 3, 4
—65
25—
—25
—18
10—
—10
HFD 12, 3, 4
—100
65—
—65
—25
10—
—22
FDC 2, 3, 4 200 — 100 35 — 22
Circuit Breaker Type
Number of Poles
Interrupting Capacity (Symmetrical Amperes) (kA)
Volts AC (50/60 Hz) Volts DC 4
220, 240 380, 415 440 500 125 250 56
ED EDH EDC
2, 32, 32, 3
65100200
———
———
———
101010
———
FDB 2, 3, 4 18 14 14 14 — 10
FD 12, 3, 4
25 65
—35
—35
—18
10—
—10
HFD 12, 3, 4
65 100
—65
—65
—25
10—
—22
FDC 2, 3, 4 200 100 100 35 — 22
TAB1201.fm Page 19 Wednesday, October 25, 2000 9:37 PM