2016 KEPIC - WEEK

Introduction of SSPC PA2 (2012 version)

2016. 09

한국전력기술㈜

도장 스페셜리스트 이철우

1

목 차

SSPC

SSPC PA2-1996

SSPC PA2-2012

Calibration, Verification, Adjustment

Procedure for Determining Conformance to DFT

Things To Do

2

SSPC

SSPC(Structural Steel Painting Council)

SSPC International(The Society of Protective

Coatings International)

3

SSPC

SSPC-PA2(1996, June 1st):

Paint Application Standard No.2, Measurement of

Dry Coating Thickness with Magnetic Gages

SSPC-PA2(2012, May 1st):

Paint Application Standard No.2, Procedure for

Determining Conformance to Dry Coating Thickness

Requirements

SSPC-PA2(2015):

4

SSPC PA2 - 1996

Type 1: Magnetic Gage

Type 1A: Pencil Type

Type 1B: Banana Gage, 영구자석 사용

5

SSPC PA2 - 1996

Type 2: Electro Magnetic Type, 전기를 이용

6

SSPC PA2 - 1996

측정개소(그림 SSPC PA2에서 발췌)

SSPC PA2 그림 인용

7

SSPC PA2 - 1996

도막두께 측정 개소

100 ft2(10 m2) 미만의 면적: 5.1항

1 spot = 최소 3 gage 리딩

Spot DFT: The average of the acceptable gage reading

5 spot

최소 15개의 게이지 리딩 필요

300 ft2(30 m2) 미만의 면적: 5.1.1항

Each 100 ft2(10 m2) 면적을 측정

최소 15 X 3 = 45개소

8

SSPC PA2 - 1996

도막두께 측정 개소

300 ft2(30 m2) ~1000 ft2(100 m2) 미만: 5.1.2항

3개소의 100 ft2(10 m2) 면적을 측정

최소 15 X 3 = 45개소

1000 ft2(100 m2) 초과: 5.1.3항

임의로 선정한 처음 1000 ft2(100 m2) 면적을 5.1.2항에 따라

측정

추가되는 1000 ft2(100 m2) 의 도막두께 측정은 임의로 선정한

100 ft2(10 m2) 을 측정하여 검사

9

SSPC PA2 - 2012

SSPC PA2-2012 Version의 주요 변경 내용:

불일치 부위를 확인하기 위하여 8개의 방사형

방향으로 5 ft 간격으로 spot measurements 를

측정한다(8.2.4.1항)

각각의 spot measuremen는 사업시방서 요건에

일치해야 한다

한 방향에서 연속으로 2회의 도막두께가 일치하면

측정을 중단한다.

불일치 부위를 문서화한다.

10

SSPC PA2 - 2012

ASTM D7091의 도막두께 측정기 사용 시의 도막두께

일치성 확인(Determining Conformance)을 위한 절차를

기술하고 있음

ASTM D7091-2013, Standard Practice for

Nondestructive Measurement of Dry Film Thickness of

Nonmagnetic Coatings Applied to Ferrous Metals and

Nonmagnetic, Nonconductive Coating Applied to Non-

Ferrous Metals

도막결함조사를 위한 도막두께 측정의 빈도에 사용되지

않음

11

SSPC PA2 - 2012

Non-mandatory appendices

Appendix 1: Numerical Example of Average Thickness

Measurement

Appendix 2: Methods for Measuring Dry Film Thickness on

Steel Beams(Girders)

Appendix 3: Methods for Measuring Dry Film Thickness for a

Laydown of Beams, Structural Steel, and Miscellaneous Parts

after Shop Coating

Appendix 4: Methods for Measuring Dry Film Thickness on

Coated Steel Test Panels

Appendix 5: Methods for Measuring Dry Film Thickness on Thin

Coatings on Coated Steel Test Panels that Have Been Abrasive

Blast Cleaned

12

SSPC PA2 - 2012

Non-mandatory appendices

Appendix 6: Method for Measuring Dry Film Thickness of

Coatings on Edges

Appendix 7: Methods for Measuring Dry Film Thickness on

Steel Pipe Exterior

Appendix 8: Example of the Adjustment of Type 2 Gages Using

Shimes

13

SSPC PA2 - 2012

Thermal spray coating에는 적용하지 않음:

SSPC-CS23.00/AWS C2.23N/NACE No.12:

Specification of Thermal Spray Coatings(metallizing) of

aluminum, Zinc, and Their Alloys and Composites for the

Corrosion Protection of Steel

14

SSPC PA2 - 2012

Gage Reading: A single instrument reading

Spot Reading

The average of the acceptable 3 gage reading is the

spot measurement.

At least three gage reading’s average

1.5 in.(4 cm) 내에서 측정: 시편의 크기 고려

Any unusually high or low gage readings are

discarded

Area measurement

5개의 spot measurement의 평균

Each 100 ft2 (10 m2)

15

Calibration/Verification/Adjustment

ASTM D7091

정확한 도막두께 측정을 위한 단계를 기술

각 스텝은 도막두께 측정 전에 완료

Calibration(검교정)

게이지 제작자 또는 시험소에서 수행

표준 검교정 주기는 없음: 보통 1년

Traceability: Nation metrology Institute(국가 도량형

기관) 요구 한국 예: KRISS(한국표준과학연구원)

원자력: International Laboratory Accreditation Cooperation (ILAC)

Mutual Recognition Arrangement(MRA), NRC RIS 2016-01, 안전성

관련 항목

16

Calibration/Verification/Adjustment

Verification

검교정의 정확도(Accuracy) 확인

Gage accuracy shall be verified at a minimum of the

beginning and end of each work shit according to the

procedures described in ASTM D7091

기기를 떨어뜨렸을 때, 또는 하나의 작업기간에

오차가 너무 큰 경우 등(절차서에서 확정)

ASTM D7091는 기기의 다양성으로 제작자 매뉴얼에

따라 수행하는 것으로 기술

기록: 게이지 시리얼 번호, reference standard used,

stated thk. of the reference standard, measured thk.

Method used to verify gage accuracy

17

Calibration/Verification/Adjustment

Adjust(조정)

Manufacturer’s instruction using one of the methods

described in ASTM D7091

또는 Appendix 8

Single point adjustment

Two point adjustment

Smooth surface adjustment

조정 작업 후에 8항에 따라서 spot의 도막두께를

측정

18

Calibration/Verification/Adjustment

Accuracy(정확도) Vs Precision(정밀도)

Accuracy(정확도)

How close a particular measurements is to the correct value.

Precision(정밀도)

Consistency of repeated measure.

The best measurements are accurate and

precision.

19

도막두께 확인을 위한 절차

불일치 지역 판정: 8.2.4항

모든 100 ft2(10 m2) 면적의 도막두께가 계약문서에서

규정된 도막두께와 상이할 때 불일치 지역을 확인해야

5 ft 간격으로 spot DFT reading을 확인

8개 방향으로 외부로 방사하는 형태

같은 방향에서 연속적으로 두 번의 spot

measurement(5ft 간격)가 계약문서의 최소/최대 두께

내에 있을 때 합격(single spot measurement로 끝냄)

No allowance is made for variant spot measurements

as is the practice when determining the area DFT.

20

도막두께 확인을 위한 절차

불일치 지역 판정: 8.2.4항

SSPC PA2 그림 인용

21

도막두께 확인을 위한 절차

불일치 지역 판정: 8.2.4항

불일치 지역 표시

Removal chalk 또는 기타 규정된 마킹 자재 사용:

시방서에 표기 필요(절차서에서 사업주에 승인)

Non-compliant area: Non-compliant spot 1.5 ft(1.5 m)

보수 후에 재검사

8.2.5항

App.2~App.7: 옵션(절차서에 적용 여부에 대한 기술이 필요)

Area size, frequency of spot measurement

22

도막두께 확인을 위한 절차

23

도막두께 확인을 위한 절차

일반적인 시방서 layer 및 system의 최소/최대치 규정

없는 경우 +/- 20%

Level 1: Most restrictive

Level 5: Least restrictive

시방서 작성자(specifier)는 특정 사업에서의

도막두께 관리 등급을 제공해야 한다(시방서 표기

필요)

만약 별도의 표기가 없을 경우에는 SSPC는 Level

3로 default한다고 기술

24

도막두께 확인을 위한 절차

SSPC PA2 그림 인용

25

Things to Do

신규 발행된 기술기준의 사업 적용 시 도장검사 및

도장시공 공정에 영향을 줄 수 있으므로 적용범위에

대하여 사업주와 협의 필요

적용범위에 대한 사업주와의 협의 결과를 시방서에

반영

현장발행 도막두께 불일치 보고서 확인 시 도막두께

검측의 정확성 및 절차의 적합성을 확인

Appendix의 사업 적용성 확인 후 반영

Calibration, Verification, Adjustment에 대한

검사기기 업체별 사용 매뉴얼 숙지 필요