PROJECT: AMBULATORY HEALTHCARE CENTRE REVISION 1MAIN CONTRACTOR: CPC DATE: 15/April/2012MEP CONTRACTOR: VERGER ET DELPORTE

STARTER PANEL

Equipment Reference MotorElectric heater Interface

BMS

AL YAHAR

1 AHU-3 (Supply Fan) Single 3.8 5.5 VFD - - - - - YES TOP TOP 54 Form 2

2 AHU-3 (Electric Heater) - 5 - 3 1.7 1.7 1.7 - YES

3 AHU-4 (Supply Fan) Single 9.2 11 VFD - - - - - YES TOP TOP 54 Form 2

4 AHU-4 (Electric Heater) - 8 - 3 2.7 2.7 2.7 - YES

5 AHU-5 (Supply Fan) Single 6.1 7.5 VFD - - - - - YES TOP TOP 54 Form 2

6 AHU-5 (Electric Heater) - 6 - 3 2 2 2 - YES

7 AHU-6 (Supply Fan) Single 4.6 5.5 VFD - - - - - YES TOP TOP 54 Form 2

8 AHU-6 (Electric Heater) - 5 - 3 1.7 1.7 1.7 - YES

9 AHU-7 (Supply Fan) Single 3.8 5.5 VFD - - - - - YES TOP TOP 54 Form 2

10 AHU-7 (Electric Heater) - 5 - 3 1.7 1.7 1.7 - YES

11 AHU-8 (Supply Fan) Single 3.6 5.5 VFD - - - - - YES TOP TOP 54 Form 2

12 AHU-8 (Electric Heater) - 5 - 3 1.7 1.7 1.7 - YES

13 AHU-9 (Supply Fan) Single 4.5 5.5 VFD - - - - - YES TOP TOP 54 Form 2

14 AHU-9 (Electric Heater) - 5 - 3 1.7 1.7 1.7 - YES

15 AHU-10 (Supply Fan) Single 6.9 9.2 VFD - - - - - YES TOP TOP 54 Form 2

16 AHU-10 (Electric Heater) - 6 - 3 2 2 2 - YES

EXF-21A TWIN 0.737 - - - - YES - BOTTOM BOTTOM GRP -

10 EXF-21B TWIN 0.737 - - - - YES - BOTTOM BOTTOM GRP -

11 CHWP-1 Single 11 FULL - - - - - YES TOP TOP 54 Form 4 EMCC-1

12 CHWP-2 Single 11 FULL - - - - - YES TOP TOP 54 Form 4 EMCC-1

13 CHWP-3 Single 11 FULL - - - - - YES TOP TOP 54 Form 4 EMCC-1

SWEIHAN

1 EXF-14 TWIN 0.737 - - - - YES - BOTTOM BOTTOM GRP - -

2 EXF-15A TWIN 0.588 - - - - YES - BOTTOM BOTTOM GRP - -

3 EXF-15B TWIN 0.588 - - - - YES - BOTTOM BOTTOM GRP - -

Note: Final Electrical Load shall be based on approved equipments details.

SL.No.

Motor Input

Power (Kw)

InstalledPower (Kw)

Motor Speed

Cable Entry

Cable Out

IP Rating

Panel TypeNo.

StagesStage-1 (KW)

Stage-2 (KW)

Stage-3 (KW)

Fire Alarm

FULL (1-DUTY / 1-STANBY)

FULL (1-DUTY / 1-STANBY)

FULL (1-DUTY / 1-STANBY)

FULL (1-DUTY / 1-STANBY)

FULL (1-DUTY / 1-STANBY)