jeff t. collins undulator support/mover system testingcollins@aps.anl.gov@aps.anl.gov 14 march 2008...

Post on 18-Dec-2015

219 Views

Category:

Documents

0 Downloads

Preview:

Click to see full reader

TRANSCRIPT

Jeff T. Collins

Undulator Support/Mover System Testing Collins@aps.anl.gov

14 March 2008

LLCCLLSSLCLS Undulator

Support/Mover System: Relay Rack Heat

Dissipation & the Effects on the Overall System

Jeff T. Collins

Jeff T. Collins

Undulator Support/Mover System Testing Collins@aps.anl.gov

14 March 2008

LLCCLLSS

Support/Mover System TestingThe Experiment:

• A Combination of Infrared Imaging and RTD Measurements were Used to Determine the Actual Undulator System Heating Effects from the Relay Rack Under Worst-Case Conditions where No Forced Air Flow is Present Along the Undulator.

• The LTT Set-Up at the APS was Used for the Experiments.

•A 400 Watt Heater Attached to Aluminum Channel Was Placed Inside of a Relay Rack and the Relay Rack was Placed in Position Under the Support/Mover System Girder.

• The 400 Watt Heater Was Turned On and Infrared Images Were Acquired every 1000 Seconds for a Total of 72 Hours (1200 Images).

• A Total of 12 RTD’s were Used to Monitor Various Points On and Around the Undulator System During the Heating and Cool Down Periods.

Jeff T. Collins

Undulator Support/Mover System Testing Collins@aps.anl.gov

14 March 2008

LLCCLLSS

Support/Mover System TestingThe Relay Rack:

Two 200 Watt Heaters Used for this Test, Attached to the Aluminum Channel and Placed Inside of the Relay Rack

Jeff T. Collins

Undulator Support/Mover System Testing Collins@aps.anl.gov

14 March 2008

LLCCLLSS

Support/Mover System Testing

Rack Heating 400 Watts.avi

The Thermal Imaging Results:

• Images Were Acquired Every 100 Seconds

• Over a 72 Hour Period 1200 Images Were Acquired

• The Data Was Converted into a Movie

• Time versus Temperature was Evaluated at Several Points on the System

PRESS BUTTON TO PLAY MOVIE

Jeff T. Collins

Undulator Support/Mover System Testing Collins@aps.anl.gov

14 March 2008

LLCCLLSS

Support/Mover System TestingThe Final Image After 72 Hours of Relay Rack 400W Heat Dissipation:

• Steady-State on the Relay Rack Surface is Reached in Approximately 4 Hours• Variations Beyond Steady-State Track with Air Temperature Fluctuations • ≈ 7°C Temperature Rise in the Center of the Relay Rack• ≈ 2.6°C Temperature Rise on the Gusset Center• ≈ 1.4°C Temperature Rise on the Girder Top Above the Relay Rack• Unmeasurable Temperature Variation on the Undulator Top

0.39°C per Division

Jeff T. Collins

Undulator Support/Mover System Testing Collins@aps.anl.gov

14 March 2008

LLCCLLSS

Support/Mover System TestingTemperature Measurements Taken at Various Points Using RTD’s

400W Relay Rack Heat Dissipation, Approximately Four Days of Heating Plus One Day Cool Down Period

Jeff T. Collins

Undulator Support/Mover System Testing Collins@aps.anl.gov

14 March 2008

LLCCLLSS

Support/Mover System Testing

Conclusions:

• With 400 Watt Power Dissipation from the Relay Rack there is Less Than 0.1°C Temperature Variation on the Undulator Jaws.

• These Tests were Conducted Under Worst-Case Conditions with No 0.43 m/sec Tunnel Air Flow Along the Undulator. In Actual Operation with Tunnel Air Flow Present the Effects of Relay Rack Heat Dissipation Would be Even Less.

• The K-Value of the Magnets in the Undulator Will be Unchanged as a Result of the Heat Dissipation from the Relay Rack Relative to Fluctuations in Tunnel Air Temperature.

top related