plc-vfd modbus communication

Post on 24-May-2015

6.438 Views

Category:

Technology

52 Downloads

Preview:

Click to see full reader

DESCRIPTION

This presentation shows step by step explanation of how to build communication between PLC & VFD using MODBUS Learn 5 PLC's in a Day full Course 155+ PLC Video Tutorials of Allen Bradley, Siemens, Delta, Omron & Schneider with FREE PLC Simulators and NFI Support Course Fee: $49 , Lifetime Validity | Limited Coupons only| Course url: https://www.udemy.com/nfi-plc-online-leaning/?couponCode=slideshare For LIVE Sessions and combo offers please visit: www.nfiautomation.org Connect us at: Facebook: https://www.facebook.com/nfiinnovation Website: http://www.nfiautomation.org Google Plus: https://plus.google.com/+RajvirSinghNFIAutomation E-mail: nfiautomation@gmail.com

TRANSCRIPT

PLC –VFD MODBUS Communication (ASCII)

Delta 14 SS PLC & Delta VFD M Series

What is MODBUS?

• MODBUS is the serial communication between various devices.

• It Read/Write the memory addresses directly

ASCII ModeBaud Rate: 9600

Parity: EvenData Length: 7

Stop Bit: 1

MODBUS Wiring Diagram

• MODBUS is the serial communication between various devices.

• It Read/Write the memory addresses directly

ASCII ModeBaud Rate: 9600

Parity: EvenData Length: 7

Stop Bit: 1

Configuring VFD with Communication Parameters

ASCII Mode Parity: EvenData Length: 7Stop Bit: 1

Source of Frequency Command : RS 485 (Pr. 00 - 3)Source of Operation Command : RS 485 (Pr. 01 - 3)

(Parameter 92 – 01)

Baud Rate: 9600 (Parameter 89 – 01)

1 0 0 0 0 1 1 0

b7 b6 b5 b4 b3 b2 b1 b0

B0 – Data Length0 = 71 = 8

B2-b1 : Parity0 0 = None0 1 = ODD1 1 = EVEN

B3 – Stop Bit0 = 1 bit1 = 2 bit

0 0 0 1 110

0 0 1 0 150

0 0 1 1 300

0 1 0 0 600

0 1 0 1 1200

0 1 1 0 2400

0 1 1 1 4800

1 0 0 0 9600

b7 b6 b5 b4

1 0 0 1 19200

1 0 1 0 38400

1 0 1 1 57600

1 1 0 0 115200

b7 b6 b5 b4

Configuring PLC with Communication Parameters

Configuring PLC with Communication Parameters

It is used to hold the communication even if the value in D1120 changed

Used to set time out value where K100 = 100 Ms.

M1143 = ON (RTU Mode)M1143 = OFF (ASCII Mode)

Configuring PLC with Communication Parameters

Data sending request

Logic for Generating Pulses

M1129 = Data Receiving Time Out Bit

M1140 = Data Received Error

M1127 = Data Receiving Complete

Configuring PLC with Communication Parameters

MODRW –Operation Control Command

MODWR = Writing value to VFD Memory register

Device AddressData Address

Data Value

0 0 0 0 0 1 K1 Stop

0 0 0 0 1 0 k2 RUN

0 0 0 0 1 1 k3 JOG

0 1 0 0 0 0 k16 FWD

1 0 0 0 0 0 K32 REV

1 1 0 0 0 0 k48 Toggle Direction

0 1 0 0 1 0 k18 FWD RUN

1 0 0 0 1 0 K34 REV RUN

b5 b4 b3 b2 b1 b0 D Function

MODRW – Frequency Control Command

MODWR = Writing value to VFD Memory register

Device AddressData Address

Data Value

H2001 = Frequency Command K1 = 0.01 HzK5000 = 50 Hz

MODRD – Feedback from Drive CommandFrequency

OutputFrequency

Learn 4 PLC’s in a Day100+ Video Tutorials

Life time Access

nfipresents

Lea

rn t

o C

od

e | C

od

e to

Lea

rn

Coupon Code https://www.udemy.com/nfi-plc-online-leaning/?couponCode=slideshare

in $99 $49

For more courses visit www.nfiautomation.org

Course Outline

• 100+ PLC Video Tutorials

• Doubt Clearing Complementary LIVE Sessions on Team Viewer

• Ladder Logic Programming

• PLC Presentations, PLC Circuits, PLC Codes

• FREE PLC Simulation Software for Practice

PLC – Programmable Logic Controller

Delta DVP 14 SS + 16 SP

Allen Bradley M1000

Siemens S7 200

Schneider

Analog Cards Programming

04 AD – Analog to Digital

04DA- Digital to Analog

PLC & VFD Advanced

Course4 PLC’s Training

Platforms

For more courses visit www.nfiautomation.org