Positron Insulator Testers for High Voltage Live Line Testing

Benefits

Detects the following types of problems

• Criticalfailurecancauselongtermdamagesaswellasequipmentandfinancialloses

• Live-lineworkrequiresthattheinsulatorsbeingoodconditionforlinemansafety

• Outagesduetoinsulatorfailurearecostly

• Surfacecontamination

• Captivemoisture

• Puncturedinsulators

• Carbontracking

• Leakinginsulators

• Allowsearlydetectionofleakinginsulators• Providesassessmentofrateofdegradationforfuturereferenceandanalysis

• Includesinsulatorcountingandlocationcoordination

• Nodirectelectricalcontactthereforedangerisminimized

• Singlebuttonoperationmakesiteasytouse

• Allowsforthetestingofalltypesandsizesofinsulators

• Enhancedoperatorsafety

Why is insulator testing so important?

ThePositron Insulator Testers are revolutionary, simple to use lightweight tools that record defects anddangerousconditionsonenergizedsuspensioninsulators,stationposts,bushingsandlightningarresters.Theymeasuretheelectricfieldalongthe insulators,recordtheelectricalfieldandallconductive insulatordefects. They can be used on all types of insulators (Porcelain, Composite, Glass* for contaminationassessment,etc.)andaresafe,simpleandaccurate.

Theoperationalintegrityofhighvoltageinsulatorsisapriority,particularlywhenyouconsiderthatadamaged,electricallydeficient insulatorcan leadtosystemfailure,serious injury,or lossof life.Positron’s InsulatorTesters are amajor advance in insulatormaintenance, they allow for the safe and reliable evaluation ofhighvoltageinsulators.Simplyslidethetestersledalongtheinsulatororinsulatorstringandtheresultsareautomaticallyprocessedandavailable.

Electric Field MethodologyPositron’sInsulatorTesterallowsforthediagnosticevaluationofbothPorcelainandCompositeinsulators.

• The Insulator Tester measures the AC electric field surroundingporcelainandcompositeinsulators

• Thefieldisproportionaltothevoltageacrossaninsulatoranddropsataconductivedefectlocation

• Theelectricfieldisreadandstoredoneachdiscorskirt

How it works(Stepstofollow)

1. Theoperatorpositionshimselfandpressesthepushbuttonontheprobeandthelogger(optional).

2. Thetesterisplacedonthestringafewinsulatorsbelowthegroundedend.

3. Thetesterisslidbacktothebeginningofthestringandkeptstation-aryforatleast10secondsuntilalongbeepingsoundisheard.

4. The tester isslid to the lineendof thestringandthenback to thestartingpoint.Thebuzzersoundseachtimeareadingistakenateachinsulator.

5. Thetester isremovedfromthestringbymakingsureacontinuoussoundisheard(indicatingasuccessfulscan)andthenthepushbut-tonispressedtostorethedata.

Safe, Simple and Accurate

TheimagebelowdepictstheuseofanInsulatorTesteronaVString

ElectricfieldmethodologyconfirmsthataleakingdiscisdetectedonaPorcelainstring

Microprocessor Based TechnologyTestresultsareacquiredandstoredbyanonboardmicroprocessor allowing readings to then beuploaded to any PC-based laptop for graphicaldisplay,analysisandlongtermcomparisons.Compatible with Standard Field EquipmentAll units include a universal hot stick mountingbracketcompatiblewithstandardindustryhotsticks.

Tests Porcelain, Composite, Glass, Station Post and other InsulatorsTesterunitsallowforthetestingofalltypesandsizesofinsulators.

Features

Lightweight and DurableThe Positron Insulator Testers are lightweight,durableandengineeredtowithstandfieldconditions.Theycomesecureinaruggedizedcarryingcaseforconvenientportabilityandfielddurability.

Optional Data Logger (Mini Laptop)The data logger is used to identify each insulatorstring to be tested, eliminating the need to takeon-sitehandwrittennoteswhile testing.The loggerstores the identification of each insulator stringtested.

Page2of6

*forcontaminationassessment

Composite Insulator Tester

DataPortRS-232-TheTesterunit’sdataportallowsuploadingofdatatoaPC-basedworkstationforgraphicaldisplay,analysisandstorage.ON/OFFPowerswitchlocatedundercover.

SinglebuttonoperationmakestheCompositeTestereasytouse.Theoperatorsimplyturnsontheunit,slidesthetesteralongtheinsulatorstring.Thereisnodirectelectricalcontactsodangerisminimizedonmarginalinsulators.

• UsedforPolymerorCompositeNCI(NonCeramicInsulators)• Sledmounted(customdesignsledavailable)• Bestforinsulatorsofmorethan10skirts• Capturesupto15,000readings• Rechargeablebattery• Adjustableskidfordifferentinsulatordiametersfrom4.3”to6.7”(10.9to17cm)• AlsoavailablewithGO/NO-GOfeaturecapableofdeterminingifitissafefortransmissionpersonnelto

performworkonliveACtransmissionpowerlines

SledFieldProbe

Skid-Adjustableskidfordifferentinsulatordiameters

UniversalHotStickMountingBracket

MiniLaptop

BluetoothTransmitter(Transferringofdatatotheminilaptop)

OperationActivationButton

StatusLED

Page3of6

UniversalHotStickMountingBracket

AlternateProbeAttachement

Porcelain Insulator Tester

DataPortRS-232-TheTesterunit’sdataportallowsuploadingofdatatoaPC-basedworkstationforgraphicaldisplay,analysisandstorage.ON/OFFPowerswitchlocatedundercover

SinglebuttonoperationmakesthePorcelainTesterveryeasytouse.Theoperatorsimplyturnsontheunit,slides the testeracross the insulatordiscs.There isnodirectelectrical contact sodanger isminimizedonmarginalinsulators.• UsedforPorcelainandGlass*insulators• Sledmounted(customdesignsledavailable)• Bestforinsulatorstringsof4bellsormore• Capturesupto15,000readings• Rechargeablebattery• Adjustableskidfordifferentinsulatordiametersfrom9”to13”(22.9to33cm)• Providesinstantstatusreportinganddangerconditions

Sled

FieldProbe

Skid-Adjustableskidfordifferentinsulatordiameters

OperationActivationButton

StatusLED

Page4of6

*forcontaminationassessment

Universal Insulator Tester

TheUniversalTestercanbeusedforvariousshapesofinsulatorsandonlowervoltageapplications(from7kVto115kV).TheUniversalTesterusesanactuatorswitchinsteadofasled.

• Usedonalltypesofinsulators(Porcelain,GlassorComposite)• Idealforsubstationenvironments(conicalshapedinsulators,bushings,stationposts,lightning

arresters,etc)

UniversalHotStickMountingBracket

DataPortRS-232andON/OFFPowerswitchlocatedundercover

ActuatorSwitch

Graphicaloutputofadamageddisc(on#15)ofastringofPorcelainInsulators

GraphicaloutputofadamagedCompositeInsulator(Carbontrackingof8skirtslongfrom#43to#51)

OperationActivationButton

StatusLED

FieldProbe

Examples of Insulator Test Result Graphs

Page5of6

Page6of6

PORCELAIN COMPOSITE UNIVERSAL Parameter Model #

3781301P/60-60Hz3781301P/50-50Hz

3782091C/60-60Hz3782091C/50-50Hz

3782651U/60-60Hz3782651U/50-50Hz

Maximumdiscs/skirtsperinsulatorstring

55discsperinsulatorstring

150skirtsperinsulatorstring

40testedpointsperinsulator(80readings)

Minimumdiscs/skirtsperinsulatorstring

4discsperinsulatorstring

10skirtsperinsulatorstring

3testedpointsperinsulator(6readings)

Maximumcoronaprotection

1millionVolts 1millionVolts 1millionVolts

Minimumelectricalfield 10kV/meter 10kV/meter 7kV/meterMaximummemorycapacity

300stringsofinsulatorsor15,000readings,whichevercomesfirst

300stringsofinsulatorsor15,000readings,whichevercomesfirst

300stringsofinsulatorsor15,000readings,whichevercomesfirst

Maximumscanningspeed 6discspersecond 5skirtspersecond(Max)0.5skirtspersecond(Min)

Manualscanning

Maximumtimebetweenuploadingofcumulativedata

12days 12days 12days

Maximumtimebetweenbatterycharges

12hours 12hours 10hours

Minimumtimeofbatteryrecharging

10hours(onenight) 10hours(onenight) 10hours(onenight)

Timetagupdateinterval 16seconds 16seconds 16secondsOperatingtemperaturerangefortheprobe

-22°Fto122°F(-30°Cto50°C)

-22°Fto122°F(-30°Cto50°C)

-22°Fto122°F(-30°Cto50°C)

Operatingtemperatureforthelogger

32°Fto122°F(0°Cto50°C)

32°Fto122°F(0°Cto50°C)

32°Fto122°F(0°Cto50°C)

Dimensions W:14”xH:19”xD:9”(35.5x48x23cm)

W:12”xH:11”xD:6”(30.5x28x15cm)

W:10.6”xH:4.7”xD:2“(27x12x5cm)

Weight(loggerexcluded) 3.5lbs(1.59kg) 2.4lbs(1.09kg) 1.76lbs(0.8kg)

Sizeofinsulator 9”to13”(23to33cm)

4.3“to6.7“(11to17cm)

Any

Calibration Calibratedatfactory,nosubsequentcalibrationrequired

Calibratedatfactory,nosubsequentcalibrationrequired

Calibratedatfactory,nosubsequentcalibrationrequired

Note:ApplicationonAClinesonly

Insulator Tester Specifications

Doc#: PID 103117

www.positronpower.comPositronInc.,5101Buchan,Suite220Montreal,Quebec,H4P2R9Canada•Tel:+1-514-345-2220