SOLANOVA - SOLANOVA - Symbiosis for SustainabilitySymbiosis for Sustainability Human NeedsHuman Needs Resource EfficiencyResource Efficiency Solar SupplySolar Supply
Andreas Hermelink | Coordinator SOLANOVA, Germany
ETAP Forum, Brussels, June 11, 2007
CO2-Emissions – Scenarios
0
50
100
150
200
250
1990 2000 2010 2020 2030 2040 2050
IEA BAU WorldIEA ALT World
EU Target World
ETAP Forum, Brussels, June 11, 2007
Carbon Reduction Demand
• EU 25, today: ca. 9.5 t/CO2 per capita• World, 2050 (-50%): ca. 1.2 t/CO2 per capita• This would mean a reduction in EU25 of 87%!
ETAP Forum, Brussels, June 11, 2007
Video message: Andris Piebalgs
ETAP Forum, Brussels, June 11, 2007
Green Buildings?
GREENGREEN
ENOUGH
Sufficient Insufficient
ETAP Forum, Brussels, June 11, 2007
Symbiosis
SolarEnergy
(Building, Quarter, Town)
Efficiency(buildings & dwellers,
supply systems)
ETAP Forum, Brussels, June 11, 2007
SOLANOVA – Factor 10 Philosophy
0
50
100
150
200
250
300
Before SOLANOVA
kWh
/m2a
Hot water
Space heat -79%
ETAP Forum, Brussels, June 11, 2007
SOLANOVA - Much More Solar …
0
50
100
150
200
250
300
Before SOLANOVA
kWh
/m2a
Renewable Energy
Fossile Energy
26%Share of
Renewables
ETAP Forum, Brussels, June 11, 2007
SOLANOVA – … Much Less Fossile
0
50
100
150
200
250
300
Before SOLANOVA
kWh
/m2a
Renewable Energy
Fossile Energy
-84%
ETAP Forum, Brussels, June 11, 2007
Measured Space Heat Consumption
20
39
220
0
50
100
150
200
250
Average before retrofit Heating season 2005/06 Heating season 2006/07
kWh/m2a
-82% -91%
ETAP Forum, Brussels, June 11, 2007
From European Worst Practice ….
ETAP Forum, Brussels, June 11, 2007
… to European Best Practice!
ETAP Forum, Brussels, June 11, 2007
Measures for European Best Practice
• Decentral ventilation units with 82% real heat recovery, one ventilation unit per flat
• Ca. 75 m² solar thermal area as canopy • Easy heating system solution with radiators• 10 cm insulation of cellar ceiling• Roof insulation: 30 cm with green roof • Wall insulation: 16 cm polystyrene (additional)• Flats’ windows: S and W: 2+1 glazing,
shading, UW = 1.1; N: 2-glazing, UW = 1.4
• Groundfloor windows: U-value: 1.4• TOTAL Cost: 240 EUR/m² + VAT
ETAP Forum, Brussels, June 11, 2007
Satisfaction with Temperature
ETAP Forum, Brussels, June 11, 2007
Before
Dec. 2006
very dissatisfieddissatisfied
neutralsatisfied
very satisfied
10,00
20,00
30,00
40,00
50,00
Satisfaction with Space Heat Cost
[%]
ETAP Forum, Brussels, June 11, 2007
Satisfaction with Flat
Before
Dec. 2006
[%]
very dissatisfieddissatisfied
neutralsatisfied
very satisfied
10,00
20,00
30,00
40,00
50,00
ETAP Forum, Brussels, June 11, 2007
Replication Potential for SOLANOVA
ETAP Forum, Brussels, June 11, 2007
Replication Potential for SOLANOVA
ETAP Forum, Brussels, June 11, 2007
Replication Potential for SOLANOVA
ETAP Forum, Brussels, June 11, 2007
Replication Potential for SOLANOVA
100 Mio people in Eastern Europe only!
ETAP Forum, Brussels, June 11, 2007
Conclusion
GermanyAndreas Hermelink
hermelink@solanova.org
• We have the obligation to master a triple challenge which is far beyond the usual marginal improvements.
• Let’s•satisfy occupants’ needs•within environmental limits•at reasonable cost!
• SOLANOVA proves: It is possible!