suggestion on how to use
Post on 17-Jan-2018
221 Views
Preview:
DESCRIPTION
TRANSCRIPT
1© 2015 Eaton. All Rights Reserved..
Suggestion on How to Use• Industry Trainers are encouraged to use this
material in their sessions• Download the presentation file• Print the Notes pages and read them as you
view the presentation in the “Slide Show” view. In this way you see the slides in large format and have animation (when available)
© 2015 Eaton. All Rights Reserved..
Motor and Motor Circuit Protection
3© 2015 Eaton. All Rights Reserved..
Motor and Motor Circuit Protection
• Agenda• Motor Circuit Characteristics
• Protection from Overcurrents
• Motor Circuit Requirements
• Sizing OCPD’s
• Back-up Overload Protection
• Type 2 Protection
4© 2015 Eaton. All Rights Reserved..
Motor and Motor Circuit Protection
• How does a motor operate?• Starting
• Normally
• What do we protect against?• Overload
• Short-Circuit
5© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
Motor Inrush Curve
Inrush Current
Normal Operating Current
6© 2015 Eaton. All Rights Reserved..
300 % Overload
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
7© 2015 Eaton. All Rights Reserved..
Short Circuit
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
8© 2015 Eaton. All Rights Reserved..
Motor Circuit Requirements(NEC®)
• 430.101- 430.113 (Part IX)• Disconnecting means
• 430.52• Branch-Circuit Short-Circuit Protection
• 430.32• Overload Protection
To Supply
M
MotorBranch
Motor Overload
9© 2015 Eaton. All Rights Reserved..
Motor and Motor Circuit Protection
• NEC® 430.102• Location(Of Disconnecting Means)
• (A) In sight from Controller
• Branch-Circuit Short-Circuit Disconnect
• (B) In sight from Motor
• Branch-Circuit Short-Circuit Disconnect
• Manual Motor Controller “Suitable as Motor Disconnect”
• Exceptions provided if (A) is lockable in open position.
10© 2015 Eaton. All Rights Reserved..
Barrier, wall or isle with an obstruction
Lockable Disconnecting Means
1999 NEC® Code
Controller
M
11© 2015 Eaton. All Rights Reserved..
In sight motor disconnecting means required per 430.102(B)
Barrier, wall or isle with an obstruction
In sight (of controller) disconnecting means ahead of controller required per 430.102(A)
Requirement since 2002 NEC® Code
Controller
M
12© 2015 Eaton. All Rights Reserved..
Motor and Motor Circuit Protection
• NEC® 430.52• Branch-Circuit Short-Circuit Protection
• (B) Must handle starting current
• (C) Rating or Setting• (1) Table 430.52
• Exception 1: Next Higher size is permitted if the values from table 430.52 do not correspond to a standard size
13© 2015 Eaton. All Rights Reserved..
Motor and Motor Circuit Protection
• Table 430.52 Maximum Rating*
Non time-delay Fuse1
Dual-Element (Time-Delay) Fuse
Instantaneous Trip Breaker
Inverse Time
Breaker
300% 175% 800% 250%
1Non-Time-Delay also applies to Class CC fuses
*Single-phase motors, AC polyphase motors other than wound-rotor, squirrel cage-other than Design B energy-efficient
14© 2015 Eaton. All Rights Reserved..
Motor and Motor Circuit Protection• NEC® 430.52(C)(1) Exception 2:
• If Motor Unable to Start, then size according to following, or next smaller size
400%300%225%400%
Inverse Time
Breaker<100A
Inverse Time
Breaker>100A
Dual-Element (Time-Delay) Fuse
Non time-delay Fuse1
300%
601-6000A Fuse
1Non-Time-Delay also applies to Class CC fuses
15© 2015 Eaton. All Rights Reserved..
Motor and Motor Circuit Protection
• NEC® 430.32 (Overload Protection)• (a) More than 1 Horsepower.
• (1) A separate overload device that is responsive to motor current. This device shall be selected to trip or rated at no more than the following percent of the motor nameplate full-load current rating.
Motors with a marked service factor 1.15 or greater - 125%
Motors with a marked temperature rise 40 °C or less - 125%
All other motors - 115%
© 2015 Eaton. All Rights Reserved..
MOTOR CIRCUIT DEVICES
17© 2015 Eaton. All Rights Reserved..
Motor and Motor Circuit Protection
• What OCPD(s) can be used in a motor circuit?• Fuse
• Circuit Breaker
• MCP
• Overload relay
18© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
Motor Inrush Curve
19© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
MCP at minimum setting
20© 2015 Eaton. All Rights Reserved..
Motor Inrush Curve
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
MCP at minimum setting
21© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
MCP at maximum setting
22© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
Motor Inrush Curve
MCP at maximum setting
23© 2015 Eaton. All Rights Reserved..
300 % Overload
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
24© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
Motor Damage Curve
25© 2015 Eaton. All Rights Reserved..
Motor Damage Curve
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
300 % Overload
26© 2015 Eaton. All Rights Reserved..
Motor Damage Curve
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
300 % Overload
MCP at maximum setting
27© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
15A Circuit Breaker
28© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
Motor Inrush Curve
15A Circuit Breaker
29© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
300 % Overload
Motor Damage Curve
15A Circuit Breaker
30© 2015 Eaton. All Rights Reserved..
NON-2 Amp
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
31© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
Motor Inrush Curve
NON-2 Amp
32© 2015 Eaton. All Rights Reserved..Current in Amperes
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
NON-5 Amp
33© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
Motor Inrush Curve
NON-5 Amp
34© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
300 % Overload
Motor Damage Curve
NON-5 Amp
35© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
Overload Relay
36© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
Motor Inrush Curve
Overload Relay
37© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
300 % Overload
Motor Damage Curve
Overload Relay
38© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
300 % Overload
MCP at maximum settingMotor Damage Curve
Overload Relay
39© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
300 % Overload
Motor Damage Curve
15A Circuit Breaker
Overload Relay
40© 2015 Eaton. All Rights Reserved..
Overload Relay
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
300 % Overload
Motor Damage Curve
NON-5 Amp
41© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
FRN-R-1-6/10
42© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
Motor Inrush Curve
FRN-R-1-6/10
43© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
300 % Overload
Motor Damage Curve
FRN-R-1-6/10
44© 2015 Eaton. All Rights Reserved..
Motor and Motor Circuit Protection
• Optimal Branch Circuit Protection (Back-up Overload Protection):
• 125% or up of FLA - FRN/FRS
• 130% or up of FLA- LPN/LPS
• 150% or up of FLA- LPJ
• 200% or up of FLA- LP-CC
45© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
FRN-R-1-8/10
46© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
Motor Damage Curve
FRN-R-1-8/10
Overload Relay
47© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
300 % Overload
Motor Damage Curve
FRN-R-1-8/10
Overload Relay
48© 2015 Eaton. All Rights Reserved..
Single-Phasing
• Single phasing is the opening of one phase of a three phase circuit.
49© 2015 Eaton. All Rights Reserved..
Primary Single Phasing
• Primary wire broken by:• Storm - Wind - Ice - Sleet - Hail - Lightning
• Vehicle or Plane Striking Pole
• Falling Tree Limbs
• Construction Mishaps
• Primary wire burned out from short-circuit created by animals(i.e. squirrel to ground)
50© 2015 Eaton. All Rights Reserved..
Primary Single Phasing
• Defective contacts on primary breaker - failure to make up on all 3 poles.
• Failure of 3 shot automatic reclosers to make up on all 3 poles.
• Open pole on 3Ø auto. voltage tap changer• Open winding in one phase of transformer• Primary fuse open
51© 2015 Eaton. All Rights Reserved..
Primary Single Phasing
Normal Condition
M
1.4 A
1.4 A
1.4 A
208V 1/3 HP Motor 40 C
F.L.A. = 1.4 Amperes
52© 2015 Eaton. All Rights Reserved..
Primary Single Phasing
Single Phase Condition
M
1.61 A
3.22 A
1.61 A208V 1/3 HP Motor 40 C
F.L.A. = 1.4 Amperes
(230%)
(115%)
Assume one phase lost on the primary side of transformer.
(115%)
53© 2015 Eaton. All Rights Reserved..
Secondary Single Phasing
• Damaged Motor Starter Contact - One Pole Open• Burned open overload relay (heater)• Damaged switch or circuit breaker on the main,
feeder, or branch circuit.• Open fuse or open pole in breaker on main,
feeder, or branch circuit.• Open cable or bus on secondary of transformer
terminals
54© 2015 Eaton. All Rights Reserved..
Secondary Single Phasing
• Open cable caused by overheated lug on secondary side-connection to service head.
• Open connection in wiring such as in motor junction box (caused by vibration) or any pull box
• Open winding in motor• Open winding in one phase of transformer
winding
55© 2015 Eaton. All Rights Reserved..
Secondary Single Phasing
Normal Condition
M
1.4 A
1.4 A
1.4 A
208V 1/3 HP Motor 40 C
F.L.A. = 1.4 Amperes
56© 2015 Eaton. All Rights Reserved..
Secondary Single Phasing
Single Phase Condition
M
0 A
2.4 A
2.4 A208V 1/3 HP Motor 40 C
F.L.A. = 1.4 Amperes
(173%)
(173%)
Contacts on one phase are worn out resulting in an open circuit
57© 2015 Eaton. All Rights Reserved..
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
Secondary Single Phasing
Motor Damage Curve
FRN-R-1-6/10
58© 2015 Eaton. All Rights Reserved..
Secondary Single Phasing
1000
100
10
1
0.1
0.0110 100 10001
Tim
e in
Sec
onds
Current in Amperes
Overload Relay
Motor Damage Curve
FRN-R-1-8/10
© 2015 Eaton. All Rights Reserved..
What about short circuit protection for a motor circuit?
60© 2015 Eaton. All Rights Reserved..
Motor and Motor Circuit Protection
• Short Circuit Condition
Current Source M
© 2015 Eaton. All Rights Reserved..
If the overcurrent protective devices are sized according to the maximums in NEC® 430.52, will the motor circuit components be protected from damage?
© 2015 Eaton. All Rights Reserved..
TYPE 1 PROTECTION vs. TYPE 2 PROTECTION
63© 2015 Eaton. All Rights Reserved..
TYPE 1 vs. TYPE 2 PROTECTION
• What is Type 1 and Type 2 Protection?• IEC 947-4-1 Standard
• Type 1 Protection(Damage)
• UL 508 Listing
• Type 2 Protection(No Damage)
• Type 2 Tables from Manufacturer
64© 2015 Eaton. All Rights Reserved..
TYPE 1 vs. TYPE 2 PROTECTION
• Type 1 Protection:• “Requires that, under short-circuit conditions,
the contactor or starter shall cause no danger to persons or installation and may not be suitable for further service without repair and replacement of parts.”
• Similar to UL 508 requirements
65© 2015 Eaton. All Rights Reserved..
TYPE 1 vs. TYPE 2 PROTECTION
• Type 2 Protection:• “Requires that, under short-circuit conditions, the
contactor or starter shall cause no danger to persons or installation and shall be suitable for further use. The risk of contact welding is recognized, in which case the manufacturer shall indicate the measure to be taken as regards the maintenance of the equipment.”
66© 2015 Eaton. All Rights Reserved..
Type 2 Protection Tables
67© 2015 Eaton. All Rights Reserved..
TYPE 1 vs. TYPE 2 PROTECTION
• Does NEC® require Type 2 protection?
68© 2015 Eaton. All Rights Reserved..
TYPE 1 vs. TYPE 2 PROTECTION
• NEC® section 110.10: Circuit Impedance, Short-Circuit Current Ratings, and Other Characteristics. The overcurrent protective devices, the total impedance, the equipment short-circuit current ratings, and other characteristics of the circuit to be protected shall be selected and coordinated to permit the circuit-protective devices used to clear a fault to do so without extensive damage to the electrical equipment of the circuit……Listed equipment applied in accordance with their listing shall be considered to meet the requirements of this section.
69© 2015 Eaton. All Rights Reserved..
TYPE 2 PROTECTION
• Why Is Total Protection Important?• Maximum Safety To Personnel And Equipment
• Minimum Cost To Stay In Service
• Maximum Productivity From The Equipment
70© 2015 Eaton. All Rights Reserved..
Motor and Motor Circuit Protection
• Overload Protection• Overload Relay
• Fuses for Backup
• Short Circuit Protection• Fuse, Circuit Breaker, MCP
• Type 2 Protection(No Damage)
71© 2015 Eaton. All Rights Reserved..
top related