an innovative control valve for improving steam …pamphlet u0408-1 cv-cos cv-cosr control valve...

Pamphlet U0408-1 CV-COS CV-COSR Control Valve Separator Steam Trap An Innovative Control Valve for Improving Steam Quality Electro-Pneumatic Control Valve for Steam NOTE: Pressure gauge is optional

Upload: others

Post on 10-Jun-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: An Innovative Control Valve for Improving Steam …Pamphlet U0408-1 CV-COS CV-COSR Control Valve Steam Separator Trap An Innovative Control Valve for Improving Steam Quality Electro-Pneumatic

Pamphlet U0408-1

CV-COSCV-COSR

ControlValve

SeparatorSteam Trap

An Innovative Control Valve forImproving Steam Quality

Electro-Pneumatic Control Valve for Steam

NOTE: Pressure gauge is optional

Page 2: An Innovative Control Valve for Improving Steam …Pamphlet U0408-1 CV-COS CV-COSR Control Valve Steam Separator Trap An Innovative Control Valve for Improving Steam Quality Electro-Pneumatic

CCopyright Pamphlet U0408-1 Rev. 5/2017(M) Specifications subject to change without notice.

Star Lodge, Montpellier Drive, Cheltenham, Gloucestershire, GL50 1TY, U.K.Tel: [44]-(0)1242-227223 Fax: [44]-(0)1242-223077http://www.tlv.com

● Flow Velocity and Efficiency

Actuator / Positioner

3-in-1 Control ValveCV-COS is a new type of compact electro-pneumaticcontrol valve with an integrated cyclone separator andsteam trap to improve steam quality.

ControlValve

SteamTrap

Separator

Compact and SimpleActuator with digital I/P positioner saves space and simplifies system layout, piping, and maintenance.Zero/span adjustment can beperformed by auto-tuning via the positioner menu.

Supplies Dry Steam and Prevents Scale Adhesion /Valve ErosionBuilt-in cyclone separator eliminates condensate, achieving separation efficiency as high as 98%. Built-in screen with large surface area prevents scale adhesion, ensuring trouble-free operation.

Steam Trap

Prevents Water Hammerby Eliminating CondensateSelf-modulating free floatsteam trap continuouslydischarges condensate as it is separated.

Usable with pressure/temperature sensors, flowmeters, and controllers.

Cyclone Separator

1009896949290 10 20 30

(Accuracy: ±2%; Condensation : 40~50kg/h)

Con

den

sati

on

Se

par

atio

n

Rat

e (%

)

Steam Flow Velocity (m/sec)

Separation rate (%) is given as:quantity of condensate dischargedquantity of incoming condensate

100×

● Equal Percentage

Cv / Kvs Value 00/

Val

ve T

rave

l00/

100

80

60

40

20

021 5 10 20 50 100

To avoid abnormal operation, accidents or serious injury, DO NOT use this product outside thespecification range. Local regulations may restrict this product below the conditions quoted.CAUTION

CV-COS

Cv & Kvs ValuesDN

Kvs (DIN)CV (UK)CV (US)

153.02.93.5

12

40232327

38

50343340

48

205.15.06.0

257.77.59.0

24Seat Diameter (mm)

CV-COSR

Like the CV-COS, the CV-COSR* is an electro-pneumatic control valve with a great price to performance value, ideal for applications where dry steam is already being supplied through use of a separator, etc.

* Does not include separator or steam trap functions.

Control Valve

Connection (Flange)DN Material

Max. Operating Press. PMO

Max. Operating Temp. TMO

Valve Character-

istic

Fail-Safe Position

Range-ability

DIN

ASME15,20,25,

40,50

Cast Iron

Ductile Cast IronStainless Steel

13 barg (DN 15 - 40)10 barg (DN 50)

16 barg (DN 15 - 40)10 barg (DN 50)

Equal Percentage

Valve CLOSED50 : 1

200°C

220°C

Note: Use only oil free air filtered to 5 µm for motive air supply. Pressure gauge shown in product images is optional.

Model

CV-COSCV-COSRSp

eci

fica

tion

s