anki a unified control strategy for three-phase inverter.pdf

Upload: ravi-kumar

Post on 02-Jun-2018

226 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 anki A Unified Control Strategy for Three-Phase Inverter.pdf

    1/16

    1176 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 3, MARCH 2014

    A Unified Control Strategy for Three-Phase Inverter

    in Distributed GenerationZeng Liu, Student Member, IEEE, Jinjun Liu, Senior Member, IEEE, and Yalin Zhao

    AbstractThis paper presents a unified control strategy that en-ablesboth islanded and grid-tied operations of three-phase inverterin distributed generation, with no need for switching between twocorresponding controllers or critical islanding detection. The pro-posed control strategy composes of an inner inductor current loop,and a novel voltage loop in the synchronous reference frame. Theinverter is regulated as a current source just by the inner induc-tor current loop in grid-tied operation, and the voltage controlleris automatically activated to regulate the load voltage upon theoccurrence of islanding. Furthermore, the waveforms of the gridcurrent in the grid-tied mode and the load voltage in the islandingmode are distorted under nonlinear local load with the conven-tional strategy. And this issue is addressed by proposing a unified

    load current feedforward in this paper. Additionally, this paperpresents the detailed analysis and the parameter design of thecontrol strategy. Finally, the effectiveness of the proposed controlstrategy is validated by the simulation and experimental results.

    Index TermsDistributed generation (DG), islanding, load cur-rent, seamless transfer, three-phase inverter, unified control.

    I. INTRODUCTION

    DISTRIBUTED generation (DG) is emerging as a viable

    alternative when renewable or nonconventional energy

    resources are available, such as wind turbines, photovoltaic ar-

    rays, fuel cells, microturbines [1], [3]. Most of these resourcesare connected to the utility through power electronic interfacing

    converters, i.e., three-phase inverter. Moreover, DG is a suitable

    form to offer high reliable electrical power supply, as it is able to

    operate either in the grid-tied mode or in the islanded mode [2].

    In the grid-tied operation, DG deliveries power to the utility

    and the local critical load. Upon the occurrence of utility outage,

    the islanding is formed. Under this circumstance, the DG must

    be tripped and cease to energize the portion of utility as soon as

    possible according to IEEE Standard 929-2000 [4]. However,

    in order to improve the power reliability of some local critical

    Manuscript received December 15, 2012; revised March 4, 2013; acceptedApril 21, 2013. Date of current version September 18, 2013. This work wassupported in part by the National Basic Research Program (973 Program) of

    China under Project 2009CB219705, and by the State Key Laboratory of Elec-trical Insulation and Power Equipment under Project EIPE09109. This paperwas presented in part at the 26th IEEE Applied Power Electronics Conferenceand Exposition, Fort Worth, TX, USA, March 611, 2011. Recommended forpublication by Associate Editor D. Xu.

    The authors are with the State Key Lab of Electrical Insulation andPower Equipment, School of Electrical Engineering, Xian Jiaotong Univer-sity, Xian 710049, China (e-mail: [email protected]; [email protected];[email protected]).

    Color versions of one or more of the figures in this paper are available onlineat http://ieeexplore.ieee.org.

    Digital Object Identifier 10.1109/TPEL.2013.2262078

    load, the DG should disconnect to the utility and continue to

    feed the local critical load [5]. The load voltage is key issue of

    these two operation modes, because it is fixed by the utility in

    the grid-tied operation, and formed by the DG in the islanded

    mode, respectively. Therefore, upon the happening of islanding,

    DG must take over the load voltage as soon as possible, in order

    to reduce the transient in the load voltage. And this issue brings

    a challenge for the operation of DG.

    Droop-based control is used widely for the power sharing of

    parallel inverters [11], [12], which is called as voltage mode

    control in this paper, and it can also be applied to DG to real-

    ize the power sharing between DG and utility in the grid-tied

    mode [13][16], [53]. In this situation, the inverter is always

    regulated as a voltage source by the voltage loop, and the qual-

    ity of the load voltage can be guaranteed during the transition

    of operation modes. However, the limitation of this approach is

    that the dynamic performance is poor, because the bandwidth

    of the external power loop, realizing droop control, is much

    lower than the voltage loop. Moreover, the grid current is not

    controlled directly, and the issue of the inrush grid current dur-

    ing the transition from the islanded mode to the grid-tied mode

    always exists, even though phase-locked loop (PLL) and the

    virtual inductance are adopted [15].

    The hybrid voltage and current mode control is a popularalternative for DG, in which two distinct sets of controllers

    are employed [17][40]. The inverter is controlled as a current

    source by one sets of a controller in the grid-tied mode, while

    as a voltage source by the other sets of controller in the islanded

    mode. As the voltage loop or current loop is just utilized in

    this approach, a nice dynamic performance can be achieved.

    Besides, the output current is directly controlled in the grid-tied

    mode, and the inrush grid current is almost eliminated.

    In the hybrid voltage and current mode control, there is a

    need to switch the controller when the operation mode of DG

    is changed. During the interval from the occurrence of utility

    outage and switching the controller to voltage mode, the load

    voltage is neither fixed by the utility, nor regulated by the DG,

    and the length of the time interval is determined by the islanding

    detection process. Therefore, the main issue in this approach is

    that it makes the quality of the load voltage heavily reliant on the

    speed and accuracy of the islanding detection method [6][10].

    Another issue associated with the aforementioned approaches

    is the waveform quality of the grid current and the load voltage

    under nonlinear local load. In the grid-tied mode, the output

    current of DG is generally desired to be pure sinusoidal [18].

    When the nonlinear local load is fed, the harmonic component

    of the load current will fully flow into the utility. A single-phase

    DG,which injects harmonic current into theutility for mitigating

    0885-8993 2013 IEEE

  • 8/10/2019 anki A Unified Control Strategy for Three-Phase Inverter.pdf

    2/16

    LIUet al.: UNIFIED CONTROL STRATEGY FOR THREE-PHASE INVERTER IN DISTRIBUTED GENERATION 1177

    Fig. 1. Schematic diagram of the DG based on the proposed control strategy.

    the harmonic component of the grid current, is presented in [41].

    The voltage mode control is enhanced by controlling the DG to

    emulate a resistance at the harmonic frequency, and then the

    harmonic current flowing into utility can be mitigated [42].

    In the islanded mode, the nonlinear load may distort the load

    voltage [43], and many control schemes have been proposed toimprove the quality of the load voltage, including a multiloop

    control method [43][46], resonant controllers[48], [49], sliding

    mode control [47]. However, existing control strategies, dealing

    with the nonlinear local load in DG, mainly focus on either the

    quality of the grid current in the grid-tied mode or the one of the

    load voltage in the islanded mode, and improving both of them

    by a unified control strategy is seldom.

    This paper proposes a unified control strategy that avoids

    the aforementioned shortcomings. First, the traditional induc-

    tor current loop is employed to control the three-phase inverter

    in DG to act as a current source with a given reference in the

    synchronous reference frame (SRF). Second, a novel voltagecontroller is presented to supply reference for the inner induc-

    tor current loop, where a proportional-plus-integral (PI) com-

    pensator and a proportional (P) compensator are employed in

    D-axis andQ-axis, respectively. In the grid-tied operation, the

    load voltage is dominated by the utility, and the voltage com-

    pensator inD-axis is saturated, while the output of the voltage

    compensator inQ-axis is forced to be zero by the PLL. There-

    fore, the reference of the inner current loop cannot regulated by

    the voltage loop, and the DG is controlled as a current source

    just by the inner current loop. Upon the occurrence of the grid

    outage, the load voltage is no more determined by the utility,

    and the voltage controller is automatically activated to regulate

    the load voltage. These happen naturally, and, thus the proposedcontrol strategy does not need a forced switching between two

    distinct sets of controllers. Further, there is no need to detect

    the islanding quickly and accurately, and the islanding detec-

    tion method is no more critical in this approach. Moreover,

    the proposed control strategy, benefiting from just utilizing the

    current and voltage feedback control, endows a better dynamic

    performance, compared to the voltage mode control.

    Third, the proposed control strategy is enhanced by introduc-

    ing a unified load current feedforward, in order to deal with

    the issue caused by the nonlinear local load, and this scheme

    is implemented by adding the load current into the reference

    of the inner current loop. In the grid-tied mode, the DG injects

    harmonic current into the grid for compensating the harmonic

    component of the grid current, and thus, the harmonic compo-

    nent of the grid current will be mitigated. Moreover, the benefit

    of the proposed load current feedforward can be extended into

    the islanded operation mode, due to the improved quality of the

    load voltage.The rest of this paper is arranged as follows. Section II de-

    scribes the proposed unified control strategy for three-phase

    inverter in DG, including the power stage of DG, the basic idea,

    and the control diagram. The detailed operation principle of DG

    with the proposed control strategy is illustrated in Section III.

    The parameter design and small signal analysis of the proposed

    control system are given in Section IV. Section V investigates

    the proposed control strategy by simulation and experimental

    results. Finally, the concluding remarks are given in Section VI.

    II. PROPOSED CONTROL STRATEGY

    A. Power Stage

    This paper presents a unified control strategy for a three-

    phase inverter in DG to operate in both islanded and grid-tied

    modes. The schematic diagram of the DG based on the proposed

    control strategy is shown by Fig. 1. The DG is equipped with

    a three-phase interface inverter terminated with aLCfilter. The

    primary energy is converted to the electrical energy, which is

    then converted to dc by the front-end power converter, and the

    output dc voltage is regulated by it. Therefore, they can be

    represented by the dc voltage source Vdc in Fig. 1. In the ac side

    of inverter, the local critical load is connected directly.

    It should be noted that there are two switches, denoted by Suand Si , respectively, in Fig. 1, and their functions are different.

    The inverter transfer switch Si is controlled by the DG, and the

    utility protection switch Su is governed by the utility. When the

    utility is normal, both switches Siand Su are ON, and the DG in

    the grid-tied mode injects power to the utility. When the utility is

    in fault, the switch Su is tripped by the utility instantly, and then

    the islanding is formed. After the islanding has been confirmed

    by the DG with the islanding detection scheme [6][10], the

    switch Si is disconnected, and the DG is transferred from the

    grid-tied mode to theislandedmode. When theutility is restored,

    the DG should be resynchronized with the utility first, and then

    the switch Si is turned ON to connect the DG with the grid.

  • 8/10/2019 anki A Unified Control Strategy for Three-Phase Inverter.pdf

    3/16

    1178 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 3, MARCH 2014

    Fig. 2. Overall block diagram of the proposed unified control strategy.

    B. Basic Idea

    With the hybrid voltage and current mode control [17][40],

    the inverter is controlled as a current source to generate the

    reference power PDG + jQDG in the grid-tied mode. And itsoutput power PDG + jQD G should be the sum of the powerinjected to the grid Pg + jQg and the load demand Pload +

    jQload , which can be expressed as follows by assuming that the

    load is represented as a parallel RLCcircuit:

    Pload = 3

    2 V

    2m

    R (1)

    Qload = 3

    2V2m

    1

    LC

    . (2)

    In (1) and (2), Vm and represent the amplitude and fre-

    quency of the load voltage, respectively. When the nonlinear

    local load is fed, it can still be equivalent to the parallel RLC

    circuit by just taking account of the fundamental component.

    During the time interval from the instant of islanding happen-

    ing to the moment of switching the control system to voltage

    mode control, the load voltage is neither fixed by the utility norregulated by the inverter, so the load voltage may drift from

    the normal range [6]. And this phenomenon can be explained

    as below by the power relationship. During this time interval,

    the inverter is still controlled as a current source, and its output

    power is kept almost unchanged. However, the power injected to

    utility decreases to zero rapidly, and then the power consumed

    by the load will be imposed to the output power of DG. If both

    active power Pg and reactive power Qg injected into the grid are

    positive in the grid-tied mode, then Ploadand Qload will increase

    after the islanding happens, and the amplitude and frequency of

    the load voltage will rise and drop, respectively, according to

    (1) and (2).

    With the previous analysis, if the output power of inverter

    PDG +jQD G could be regulated to match the load demand bychanging the current referencebeforethe islanding is confirmed,

    the load voltage excursion will be mitigated. And this basic idea

    is utilized in this paper. In the proposed control strategy, the

    output power of the inverter is always controlled by regulating

    the three-phase inductor currentiLabc , while the magnitude and

    frequency of the load voltage vC a b c are monitored. When theislanding happens, the magnitude and frequency of the load volt-

    agemay drift from thenormal range,and then they arecontrolled

    to recover to the normal range automatically by regulating the

    output power of the inverter.

    C. Control Scheme

    Fig. 2 describes the overall block diagram for the proposed

    unified control strategy, where the inductor current iLabc , the

    utility voltage vg ab c , the load voltage vC a b c , and the load current

    iL L ab care sensed. And the three-phase inverter is controlled in

    the SRF, in which, three phase variable will be represented

    by dc quantity. The control diagram is mainly composed bythe inductor current loop, the PLL, and the current reference

    generation module.

    In the inductor current loop, the PI compensator is employed

    in bothD- andQ-axes, and a decoupling of the cross coupling

    denoted by 0 Lf/kPW M is implemented in order to mitigate the

    couplings due to the inductor. The output of the inner current

    loopddq, together with the decoupling of the capacitor voltage

    denoted by 1/kPW M , sets the reference for the standard space

    vector modulation that controls the switches of the three-phase

    inverter. It should be noted thatkPW M denotes the voltage gain

    of the inverter, which equals to half of the dc voltage in this

    paper.

  • 8/10/2019 anki A Unified Control Strategy for Three-Phase Inverter.pdf

    4/16

    LIUet al.: UNIFIED CONTROL STRATEGY FOR THREE-PHASE INVERTER IN DISTRIBUTED GENERATION 1179

    Fig. 3. Block diagram of the current reference generation module.

    The PLL in the proposed control strategy is based on the

    SRF PLL [50], [51], which is widely used in the three-phasepower converter to estimate the utility frequency and phase.

    Furthermore, a limiter is inserted between the PI compensator

    GPL L and the integrator, in order to hold the frequency of the

    load voltage within the normal range in the islanded operation.

    In Fig. 2, it can be found that the inductor current is regulated

    to follow the current reference iL re fd q , and the phase of the

    current is synchronized to the grid voltage vg ab c . If the current

    referenceis constant, the inverter is just controlled to be a current

    source, which is the same with the traditional grid-tied inverter.

    The new part in this paper is the current reference generation

    module shown in Fig. 2, which regulates the current reference to

    guarantee the power match between the DG and the local loadand enables the DG to operate in the islanded mode. Moreover,

    the unified load current feedforward, to deal with the nonlinear

    local load, is also implemented in this module.

    The block diagram of the proposed current reference gen-

    eration module is shown in Fig. 3, which provides the current

    referencefor the inner current loop in both grid-tied and islanded

    modes. In this module, it can be found that an unsymmetrical

    structure is used in D- and Q-axes. The PI compensator is

    adopted in D-axes, while the P compensator is employed in

    Q-axis. Besides, an extra limiter is added in theD-axis. More-

    over, the load current feedforward is implemented by adding the

    load current iLLdqto thefinal inductor current reference iL re fd q .

    The benefit brought by the unique structure in Fig. 3 can be rep-resented by two parts: 1) seamless transfer capability without

    critical islanding detection; and 2) power quality improvement

    in both grid-tied and islanded operations. The current reference

    iL re d q composes of four parts in D- and Q-axes respectively:

    1) the output of voltage controller ir e f d q ; 2) the grid current

    referenceIg re fd q ; 3) the load currentiLLdq; and 4) the current

    flowing through the filter capacitor Cf.

    In the grid-tied mode, the load voltage vC dq is clamped by the

    utility. The current reference is irrelevant to the load voltage, due

    to the saturation of the PI compensator in D-axis, and the output

    of the P compensator being zero in Q-axis, and thus, the inverter

    operates as a current source. Upon occurrence of islanding, the

    voltage controller takes over automatically to control the load

    voltage by regulating the current reference, and the inverter acts

    as a voltage source to supply stable voltage to the local load;

    this relieves the need for switching between different control

    architectures.

    Another distinguished function of the current reference gen-

    eration module is the load current feedforward. The sensed

    load current is added as a part of the inductor current refer-

    ence iL re fd q to compensate the harmonic component in the grid

    current under nonlinearlocal load. In theislandedmode, theload

    current feedforward operates still, and the disturbance from the

    load current, caused by the nonlinear load, can be suppressed

    by the fast inner inductor current loop, and thus, the quality of

    the load voltage is improved.

    The inductor current control in Fig. 2 was proposed in pre-

    vious publications for grid-tied operation of DG [18], and the

    motivation of this paper is to propose a unified control strategy

    for DG in both grid-tied and islanded modes, which is repre-

    sented by the current reference generation module in Fig. 3.

    The contribution of this module can be summarized in two as-pects. First, by introducing PI compensator and P compensator

    in D-axis and Q-axis respectively, the voltage controller is inac-

    tivated in the grid-tied mode and can be automatically activated

    upon occurrence of islanding. Therefore, there is no need for

    switching different controllers or critical islanding detection,

    and the quality of the load voltage during the transition from

    the grid-tied mode to the islanded mode can be improved. The

    second contribution of this module is to present the load current

    feedforward to deal with the issue caused by the nonlinear local

    load, with which, not only the waveform of the grid current in

    grid-tied is improved, but also the quality of the load voltage in

    the islanded mode is enhanced.Besides, it should be noted that a three-phase unbalanced

    local load cannot be fed by the DG with the proposed control

    strategy, because there is no flow path for the zero sequence

    current of the unbalanced load, and the regulation of the zero

    sequence current is beyond the scope of the proposed control

    strategy.

    III. OPERATIONPRINCIPLE OFDG

    The operation principle of DG with the proposed unified

    control strategy will be illustrated in detail in this section, and

    there are in total four states for the DG, including the grid-tiedmode, transition from the grid-tied mode to the islanded mode,

    the islanded mode, and transition from the islanded mode to the

    grid-tied mode.

    A. Grid-Tied Mode

    When the utility is normal, the DG is controlled as a current

    source to supply given active and reactive power by the inductor

    current loop, and the active and reactive power can be given

    by the current reference ofD- andQ-axis independently. First,

    the phase angle of the utility voltage is obtained by the PLL,

    which consists of a Park transformation expressed by (3), a PI

  • 8/10/2019 anki A Unified Control Strategy for Three-Phase Inverter.pdf

    5/16

    1180 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 3, MARCH 2014

    compensator, a limiter, and an integrator

    xd

    xq

    =

    2

    3

    cos cos

    2

    3

    cos

    +

    2

    3

    sin sin

    23

    sin

    +

    2

    3

    xaxb

    xc

    . (3)Second, the filter inductor current, which has been trans-

    formed into SRF by the Park transformation, is fed back and

    compared with the inductor current reference iL re fd q , and the

    inductor current is regulated to track the reference iL re fd q by

    the PI compensatorGI.

    The reference of the inductor current loop iL re fd q seems

    complex andit is explained as below. It is assumed that theutility

    is stiff, and the three-phase utility voltage can be expressed as

    vga

    =Vgcos

    vgb =Vgcos

    2

    3

    vgc =Vgcos

    +

    2

    3

    (4)

    where Vgis the magnitude of the grid voltage, and is the actual

    phase angle. By the Park transformation, the utility voltage is

    transformed into the SRF, which is shown asvg d =Vgcos(

    )vg q =Vgsin(

    ).(5)

    vgq is regulated to zero by the PLL, sovgd equals the mag-nitude of the utility voltage Vg . As the filter capacitor voltage

    equals the utility voltage in the gird-tied mode,vC d equals the

    magnitude of the utility voltage Vg , andvC qequals zero, too.

    In the D-axis, the inductor current reference iL r e f d can be

    expressed by (6) according to Fig. 3

    iL r e f d =Ig r e f d + iLL d0 Cf vC q. (6)The first part is the output of the limiter. It is assumed that

    the given voltage reference Vma x is larger than the magnitude

    of the utility voltagevC d in steady state, so the PI compensator,

    denoted by GV D in the following part, will saturate, and the

    limiter outputs its upper value Ig r e f d . The second part is the

    load current ofD-axisiLL d , which is determined by the charac-teristic of the local load. The third part is the proportional part

    0 Cf vC q, where 0 is the rated angle frequency, and Cfis the capacitance of the filter capacitor. It is fixed as vC q de-

    pends on the utility voltage. Consequently, the current reference

    iL r e f d is imposed by the given reference Ig r e f d and the load

    currentiLL d , and is independent of the load voltage.

    In theQ-axis, the inductor current reference iL r e f q consists

    of four parts as

    iL r e f q =vC qkGv q+Ig r e f q + iLL q+0 Cf vC d (7)wherekGv q is the parameter of the P compensator, denoted by

    GV Q in the following part. The first part is the output ofGV Q ,

    Fig. 4. Simplified block diagram of the unified control strategy when DGoperates in the grid-tied mode.

    which is zero as thevC qhas been regulated to zero by the PLL.

    The second part is the given current reference Ig r e f q , and the

    third part represents the load current in Q-axis. The final part

    is the proportional part0 Cf vC d , which is fixed since vC ddepends on the utility voltage. Therefore, the current reference

    iL r e f q cannot be influenced by the external voltage loop and is

    determined by the given reference Ig r e f q and the load current

    iLL q.With the previous analysis, the control diagram of the inverter

    can be simplified as Fig. 4 in the grid-tied mode, and the inverter

    is controlled as a current source by the inductor current loop

    with the inductor current reference being determined by the

    current reference Ig r e f d q and the load current iLLdq. In other

    words, the inductor current tracks the current reference and the

    load current. If the steady state error is zero, Ig re fd q represents

    the grid current actually, and this will be analyzed in the next

    section.

    B. Transition From the Grid-Tied Mode to the Islanded Mode

    When the utility switch Su opens, the islanding happens, andthe amplitude and frequency of the load voltage will drift due

    to the active and reactive power mismatch between the DG and

    the load demand. The transition, shown in Fig. 5, can be divided

    into two time interval. The first time intervals is from the instant

    of turning off Su to the instant of turning off Si when islanding

    is confirmed. The second time interval begins from the instant

    of turning off inverter switch Si .

    During the first time interval, the utility voltage vg ab c is still

    the same with the load voltage vC a b c as the switch Si is in ON

    state. As thedynamic of theinductor current loop andthe voltage

    loop is much faster than the PLL [52], while the load voltage

    and current are varying dramatically, the angle frequency of the

  • 8/10/2019 anki A Unified Control Strategy for Three-Phase Inverter.pdf

    6/16

    LIUet al.: UNIFIED CONTROL STRATEGY FOR THREE-PHASE INVERTER IN DISTRIBUTED GENERATION 1181

    Fig. 5. Operation sequence during the transition from the grid-tied mode to

    the islanded mode.

    Fig. 6. Transient process of the voltage and current when the islandinghappens.

    load voltage can be considered to be not varied. The dynamicprocess in this time interval can be described by Fig. 6, and it is

    illustrated later.

    In the grid-tied mode, it is assumed that the DG injects ac-

    tive and reactive power into the utility, which can be expressed

    by (8) and (9), and that the local critical load, shown in (10),

    represented by a series connected RLCcircuit with the lagging

    power factor

    Pg = 3

    2(vC d igd + vC qigq) =

    3

    2vC d ig d (8)

    Qg = 3

    2(vC qigdvC d igq) =

    3

    2vC d igq (9)

    Zsload =Rs+ j Ls+ 1

    j Cs

    =Rs+ j

    Ls

    1

    Cs

    =Rs+ jXs . (10)

    When islanding happens, igd will decrease from positive to

    zero, and ig qwill increase from negative to zero. At the same

    time, the load current will vary in the opposite direction. The

    load voltage in D- andQ-axes is shown by (11) and (12), and

    each of them consists of two terms. It can be found that the

    load voltage inD-axisvC d will increase as both terms increase.However, the trend of the load voltage in Q-axis vC q is uncertain

    because the first term decreases and the second term increases,

    and it is not concerned for a while

    vC d =iLL dRsiLL qXs (11)vC q =iLL qRs+ iLL dXs . (12)

    With the increase of the load voltage in D-axis vC d , when

    it reaches and exceeds Vma x , the input of the PI compensator

    GV D will become negative, so its output will decrease. Then,

    the output of limiter will not imposed toIg r e f d any longer, and

    the current reference iL r e f d will drop. With the regulation of

    the inductor current loop, the load current in D-axisiLL d will

    decrease. As a result, the load voltage in D-axisvC d will drop

    and recover toVm ax . AfteriLL d has almost fallen to the normal

    value, the load voltage in Q-axis vC q will drop according to

    (12). AsvC q is decreased from zero to negative, then the input

    of the PI compensator GPL Lwill be negative, and its output will

    drop. In other words, the angle frequency will be reduced.

    If it falls to the lower value of the limiter mi n , then the angle

    frequency will be fixed at m in .

    Consequently, at the end of the first time interval, the load

    voltage in D -axis vC d will be increased to and fixed at Vm ax ,

    and the angle frequency of the load voltage will drop. If it is

    higher than the lower value of the limiter m in , the PLL can still

    operate normally, and the load voltage in Q-axis vC q will be

    zero. Otherwise, if it is fixed atm in , the load voltage inQ-axis

    vC qwill be negative. As the absolute values ofvC d and vC q,

    at least the one ofvC d , are raised, the magnitude of the load

    voltage will increase finally.

    The variation of the amplitude and frequency in the load volt-

    age can also be explained by the power relationship mentioned

    before. When the islanding happens, the local load must ab-sorb the extra power injected to the grid, as the output power

    of inverter is not changed instantaneously. According to (1), the

    magnitude of the load voltageVm will rise with the increase of

    Pload . At the same time, the angle frequency should drop, in

    order to consume more reactive power with (2). Therefore, the

    result through the power relationship coincides with the previ-

    ous analysis.

    The second time interval of the transition begins from the

    instant when the switch Si is open after the islanding has been

    confirmed by the islanding detection method. If the switch S iopens, the load voltage vC a b c is independent with the grid volt-

    age vgabc . At the same time, vg ab c will reduce to zero theo-retically as the switch Su has opened. Then, the input of the

    compensator GPL L becomes zero and the angle frequency is

    invariable and fixed to the value at the end of the first interval.

    Under this circumstance,vC dqis regulated by the voltage loop,

    and the inverter is controlled to be a voltage source.

    With the previous analysis, it can be concluded that the drift

    of the amplitude and frequency in the load voltage is restricted

    in the given range when islanding happens. And the inverter

    is transferred from the current source operation mode to the

    voltage source operation mode autonomously. In the hybrid

    voltage and current mode control [17][40], the time delay of

    islanding detection is critical to the drift of the frequency and

    magnitude in the load voltage, because the drift is worse withthe increase of the delay time. However, this phenomenon is

    avoided in the proposed control strategy.

    C. Islanded Mode

    In the islanded mode, switching Si and Su are both in OFF

    state. The PLL cannot track the utility voltage normally, and the

    angle frequency is fixed. In this situation, the DG is controlled as

    a voltage source, because voltage compensatorGV D andGV Qcan regulate the load voltage vC dq. The voltage references in D-

    andQ-axis areVma x and zero, respectively. And the magnitude

    of the load voltage equals to Vm ax approximately, which will

  • 8/10/2019 anki A Unified Control Strategy for Three-Phase Inverter.pdf

    7/16

    1182 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 3, MARCH 2014

    Fig. 7. Simplified block diagram of the unified control strategy when DG

    operates in the islanded mode.

    be analyzed in Section IV. Consequently, the control diagram of

    the three-phase inverter in the islanded mode can be simplified

    as shown in Fig. 7.

    In Fig. 7, the load current iLLdq is partial reference of the

    inductor current loop. So, if there is disturbance in the load

    current, it will be suppressed quickly by the inductor current

    loop, and a stiff load voltage can be achieved.

    D. Transition From the Islanded Mode to the Grid-Tied Mode

    If the utility is restored and the utility switch Su is ON, the

    DG should be connected with utility by turning on switch S i .

    However, several preparation steps should be performed before

    turning on switch Si .

    First, as soon as utility voltage is restored, the PLL will track

    the phase of the utility voltage. As a result, the phase angle of

    the load voltagevC a b c will follow the grid voltagevg ab c . If the

    load voltagevC a b c is in phase with the utility voltage,vg d will

    equal the magnitude of the utility voltage according to (5).

    Second, as the magnitude of the load voltage Vm ax is larger

    than the utility voltage magnitudeVg , the voltage referenceVre f

    will be changed to Vg by toggling the selector S from terminals 1to 2. As a result, the load voltage will equal to the utility voltage

    in both phase and magnitude.

    Third, the switch Si is turned on, and the selector S is reset

    to terminal 1. In this situation, the load voltage will be held by

    the utility. As the voltage reference Vre f equals Vm ax , which

    is larger than the magnitude of the utility voltage Vg , so the

    PI compensator GV D will saturate, and the limiter outputs its

    upper value Ig r e f d . At the same time,vC qis regulated to zero

    by the PLL according to (5), so the output of GV Q will be

    zero. Consequently, the voltage regulators GV D andGV Q are

    inactivated, and the DG is controlled as a current source just by

    the inductor current loop.

    IV. ANALYSIS ANDDESIGN

    In this section, the three-phase inverter with the proposed

    control strategy is analyzed and designed in both steady state

    and transient state. In the steady state, the operation points of

    DG in both grid-tied and islanded modes are analyzed, and

    the limiters and references are selected. In the transient state,

    compensators in both inductor current loop and the externalvoltage loop are designed based on the small-signal model, and

    the impact of the load current feedforward is analyzed as well.

    A. Steady State

    1) Analysis of Operation Points: As analyzed previously, in

    the grid-tied mode, the inverter is controlled as a current source,

    and the current reference for the inductor current loop iL re fd q is

    expressed by (6) and (7). The steady-state error will be zero with

    the PI compensator in the inductor current loop, so the inductor

    current in steady state can be expressed as follows:

    iLd =Ig r e f d0 Cf vC q+iLL diLq =vC qkGv q+ 0 Cf vC d+ Ig r e f q +iLL q. (13)

    In the SRF, the relationship between the voltage and the cur-

    rent of the filter capacitor in steady state can be expressed byiC d =vC qCfiC q =vC dCf

    (14)

    where represents the angle frequency of the DG and Cfdenotes capacitance of the filter capacitor. As a result, the output

    current of the inverter iod qcan be gained

    iod =iLdiC d =Ig r e f d(0)Cf vC q+iLL d

    ioq =iLqiC q =vC qkGv q+Ig r e f q + (0)Cf vC q+iLL q.

    (15)

    As angle frequency is very close to the rated angle fre-

    quency0 , the output currentiod qcan be simplified asiod =Ig r e f d + iLL d

    ioq =vC qkGv q+Ig r e f q +iLL q.(16)

    It can be found that the output current follows Ig r e f d q and the

    load current iLLdq, as vC qequals zero in the grid-tied mode. The

    active and reactive power injected into utility can be obtained

    as follows. Consequently, the active power and reactive power

    flowing from the inverter to utility can be given by Ig r e f d andIg r e f q , respectively

    Pg =3

    2[vC d(iodiLL d ) +vC q(ioqiLL q)]

    =3

    2vC d Ig re f d

    Qg = 3

    2[vC q(iodiLL d )vcC d(ioqiLL q)]

    =32vC d Ig r e f q .

    (17)

    In the islanded mode, the inverter is controlled as a volt-

    age source by the external voltage loop. In the D-axis,vC d is

  • 8/10/2019 anki A Unified Control Strategy for Three-Phase Inverter.pdf

    8/16

    LIUet al.: UNIFIED CONTROL STRATEGY FOR THREE-PHASE INVERTER IN DISTRIBUTED GENERATION 1183

    regulated by the PI compensatorGV D , so the steady state error

    will be zero andvC d can be expressed as follows:

    vC d =Vre f (18)

    whereVre fis the voltage reference inD-axis.

    In the Q-axis, the regulator GV Q is P compensator, so the

    steady state error may not be zero. As the load current is added

    to the inductor reference, the condition shown as below can be

    achieved

    vC qkGv q+Ig r e f q = 0. (19)And then, the load voltage in Q-axis can be expressed by

    (20). It should be noted that the absolute value ofvC qrises with

    the increase of the current reference Ig r e f q which is related to

    the reactive power injected into the utility

    vC q =Ig r e f q

    kGv q. (20)

    The magnitude of the load voltage Vm can be represented as

    follows. It equals toVre fapproximately, becausevC qshould bemuch lower thanVre fwith proper current reference Ig r e f q

    Vm =

    V2re f+

    Ig r e f q

    kGv q

    2Vre f. (21)

    When the islanding happens, the angle frequency is restricted

    in the given range by the limiter. As analyzed previously, the an-

    gle frequency in the islanded mode is determined in the first time

    interval of the transition from the grid-tied made to the islanded

    mode. According to (20), if the current reference Ig r e f q is set

    to zero, vC q is zero. Then, it means that the angle frequency

    does not vary in the first time interval of the transition, and

    it should equal g 0 , which denotes the angle frequency of theutility before islanding happens. Consequently, the angle fre-

    quency of the load voltage in the islanded mode is determined

    by the current referenceIg r e f q , and it can be expressed by (22),

    wherem in andm ax represent the upper and lower values of

    the limiter shown in Fig. 2, respectively

    =

    m in , Ig r e f q >0

    g 0 , Ig r e f q = 0

    m ax , Ig r e f q

  • 8/10/2019 anki A Unified Control Strategy for Three-Phase Inverter.pdf

    9/16

    1184 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 3, MARCH 2014

    TABLE IPARAMETERS OF THEPOWERSTAGE

    Fig. 8. Bode plot of the control-to-current transfer function in grid-tied andislanded modes.

    0 Cfin Fig. 3 [12]. Therefore, the small-signal model can be

    simplified into two identical SISO systems, which is representedby (28) and the subscriptd andqare ignored

    Vdc

    2 d= Lf

    d

    dtiL+Rl iL + vC

    iL =Cfd

    dtvC + iLL + ig .

    (28)

    2) Design and Analysis of the Current Loop: The inductor

    current loop should operate normally to regulate the inductor

    current loop in both islanded andgrid-tiedmodes. In the islanded

    mode, the small-signal model of the control-to-current can be

    obtained according to (28), which is shown as

    Gid 1 (s) =iL (s)

    d(s)=

    Vdc

    2 sCf

    s2 LfCf +sRl Cf + 1. (29)

    However, in the grid-tied mode, the dynamic of the capacitor

    Cfis ignored due to the stiff utility [34], and the small-signal

    model of the control-to-current is described by

    Gid 2 (s) =iL (s)

    d(s)=

    Vdc

    2 1

    sLf +Rl. (30)

    The parameters of the power stage in this paper are shown

    in Table I, and the Bode plot of the control-to-current transfer

    function in both of operation modes is shown in Fig. 8. It can

    be found that huge difference appears in the low and medium

    Fig. 9. Bode plot of the loop gain of the inner current loop.

    Fig. 10. Block diagram of the simplified voltage loop.

    frequency range, and it is difficult to design the compensator GIto achieve good performance in both of operation modes.

    The reason for this difference between the islanded mode

    and the grid-tied mode is that the inductor current is coupled

    with the capacitor voltage in the islanded mode. To mitigate

    this difference, the capacitor voltage is fed forward with the

    coefficient 1/kPW M in Fig. 2, and then the inductor current

    can be decoupled with the capacitor voltage. Consequently, thetransfer function of control to current in the islanded mode

    is changed to be close to the one in the grid-tied mode, and

    the current compensator GIcan be designed based on unified

    transfer function shown by (30).

    The PI compensatorGI in (31) is designed, and the digital

    delay caused by the pulse width modulation (PWM) and sample

    is considered as well. The loop gain of the current loop is shown

    in Fig. 9, with the crossover frequency of 1100 Hz, and the phase

    margin of 65

    Gi (s) =kGi1 + s

    G i

    s . (31)

    3) Design and Analysis of the Voltage Loop: The voltage

    loop just operates in the islanded mode to regulate the load

    voltage, and the simplified block diagram is shown in Fig. 10,

    where Gic (s) and Gv i (s) denote the closed-looptransfer function

    of an inductor loop and the impedance of the filter capacitor Cf,

    respectively.

    In theD-axis,GV D is a PI compensator shown in (32), while

    a P compensator GV Q expressed by (33) is used in Q-axis.

    These two compensators are designed, and the loop gain of the

    current loop is shown in Fig. 11. It can be found that there is a

    little difference in the low frequency range. The phase margin

    is set to 55, and the crossover frequency is around 600 Hz in

  • 8/10/2019 anki A Unified Control Strategy for Three-Phase Inverter.pdf

    10/16

    LIUet al.: UNIFIED CONTROL STRATEGY FOR THREE-PHASE INVERTER IN DISTRIBUTED GENERATION 1185

    Fig. 11. Bode plot of the loop gain of the voltage loop inD - andQ-axes.

    bothD- andQ-axes

    Gv d (s) =kGv d 1 + s G v d

    s (32)

    Gv q(s) =kGv q. (33)

    4) Impact of Load Current Feedforward: In Fig. 10, the load

    current iLL is a part of the inductor current reference, and thedisturbance from the load current can be suppressed by the

    inductor current loop directly. To evaluate the effect of the load

    current feedforward in the islanded mode, the transfer function

    of the output impedance is derived. The output impedances with

    and without load current feedforward are expressed by

    Zo1 (s) = vC(s)

    iLL (s) =

    Gv i (s)

    [1

    Gic (s)]

    1 +Gv (s)Gic (s)Gv i (s) (34)

    Zo2 (s) = vC(s)

    iLL (s)= Gv i (s)

    1 +Gv (s)Gic (s)Gv i (s). (35)

    Comparing (34) and (35), it can be found that an extra factor

    [1Gic (s)] appears in the output impedance with load currentfeedforward, and the magnitude of the output impedance will

    be reduced in the low frequency range because the gain of

    the closed-loop transfer function Gic (s) closes to unity in thebandwidth of the current loop. The Bode plot of the output

    impedance of these two conditions is shown in Fig. 12, and

    it can be seen that the magnitude of the output impedance is

    reduced from dc to 600 Hz with the load current feedforward.

    Consequently, the quality of the load voltage vC a b c will be

    improved with the load current feedforward.

    In the grid-tied mode, the inductor current is regulated by the

    inductor current loop directly, and the inductor current reference

    is mainly composed by the current reference Ig r e f d q , and the

    load current iLLdq. If the load current is not fed forward, the

    output currentiod qof the inverter will be fixed byIg r e f d q . As a

    result, the disturbance of the load current will be fully injected

    into the utility, and this can be represented by

    ig (s)

    iLL (s)

    =

    1. (36)

    Fig. 12. Bode plot of the output impedance with and without the load currentfeedforward, when DG operates in the islanded mode.

    Fig. 13. Bode plot of the transfer function from load current to grid current

    with andwithout theloadcurrent feedforward, when DGoperates inthe grid-tiedmode.

    With the load current feedforward, the disturbance of the

    load current can be compensated by the inverter, and the trans-

    fer function from the load current to the grid current can be

    described by (37). The Bode plots of transfer function [see (36)

    and (37)] are shown in Fig. 13, and the gain is mitigated up to

    1050 Hz with the load current feedforward and therefore, the

    quality of the grid current can be improved

    ig (s)

    iLL (s)=Gic (s)1. (37)

    V. SIMULATION ANDEXPERIMENTAL RESULTS

    A. Simulation Results

    To investigate the feasible of the proposed control strategy,

    the simulation has been done in PSIM. The power rating of a

    three-phase inverter is 3 kW in the simulation. The parameters in

    the simulation are shown in Tables I and II. The RMS of the rated

    phase voltage is 115 V, and the voltage reference Vm ax is set

    as 10% higher than the rated value. The rated utility frequency

  • 8/10/2019 anki A Unified Control Strategy for Three-Phase Inverter.pdf

    11/16

  • 8/10/2019 anki A Unified Control Strategy for Three-Phase Inverter.pdf

    12/16

    LIUet al.: UNIFIED CONTROL STRATEGY FOR THREE-PHASE INVERTER IN DISTRIBUTED GENERATION 1187

    Fig. 16. Diagram of the experimental prototype of DG.

    Fig. 17. Experimental waveforms when DG is in the islanded mode: CH1,load currentiL L a , 5 A/div; CH3, load voltage vC a , 100 V/div; CH4, inductorcurrentiL a , 5 A/div.

    Fig. 18. Experimental waveforms when DG is in the grid-tied mode: CH1,load current iL L a , 5 A/div;CH2, grid voltage vg a , 100 V/div; CH4,grid currentig a , 10 A/div.

    Comparing the simulation results above, it can be found that

    the voltage quality is improved deeply by the proposed con-

    trol strategy in the transition from the grid-tied mode to the

    islanded mode, and the speed of the islanding detection is no

    more critical.

    Fig. 19. Experimental waveforms when DG is transferred from the grid-tied

    mode to the islanded mode with (a) conventional hybrid voltage and currentmode control, and (b) proposed unified control strategy: CH2, load voltage

    vC a , 100 V/div; CH3, grid current ig a , 10 A/div; CH4, inductor current iL a ,10 A/div.

    B. Experimental Results

    To verify the proposed control strategy, an experimental pro-

    totype of DG has been established, which is shown in Fig. 16.

    The utility for the DG is emulated by a three-phase transformer

    and a voltage regulator connected with the actual utility. The

    rated line voltage of the actual utility is 380 V. The emulated

    utility is called as utility in the below. Moreover, the inverter

    in the DG is fed by a three-phase diode rectifier, and the

    dc-bus voltage is set to 400 V approximately by the voltage

  • 8/10/2019 anki A Unified Control Strategy for Three-Phase Inverter.pdf

    13/16

    1188 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 3, MARCH 2014

    Fig. 20. Experimental waveforms when DG is transferred from the islanded mode to the grid-tied mode: CH1, grid voltagevg a , 100 V/div; CH2, load voltagevC a , 100 V/div; CH3, grid currentig a , 10 A/div; CH4, inductor currentiL a , 10 A/div.

    regulator. Besides, the control system is implemented fully dig-

    itally by digital signal processor TMS320F28335 from Texas

    Instruments. The parameters in the experimental DG, shown in

    Tables I and II, are identical to the ones used in the simulation.Fig. 17 shows the experimental waveforms when DG is in

    the islanded mode, and it can be seen that the magnitude of the

    load voltage equals 180 V approximately, and the total harmonic

    distortion (THD) of the load voltage is 0.9%.

    Fig. 18 shows the experimental waveforms when DG is in the

    grid-tied mode. The magnitude of the grid current is closed to

    9 A, and the THD of the grid current is 3.6% approximately.

    When the DG is transferred from the grid-tied mode to the

    islanded mode, the experimental results with the traditional hy-

    brid voltage and current mode control and the proposed unified

    control strategy are given in Fig. 19. Before the islanding hap-

    pens, the magnitude of the load voltage is around 163 V. The

    current injected into the utility ig a is in phase with the utility

    voltage, and the magnitude ofiga is approximately 9 A. When

    the switch Su opens, the islanding happens, and the grid current

    ig a drops to zero. In the traditional hybrid voltage and current

    mode control, it can be found that the load voltage is seriously

    distorted upon the occurrence of islanding. And this condition

    lasts until the islanding is confirmed by DG and the control

    structure is changed to regulate the load voltage. However, with

    the proposed unified control strategy, the distortion of the load

    voltage is obviously improved, and the magnitude of the load

    voltage increases slightly and is close to 180 V.

    Fig. 20 shows the process when DG is transferred from the is-

    landed mode to the grid-tied mode. From 0 ms to around 300 ms,the phase of the load voltage is regulated to resynchronize with

    the utility voltage, and the phase difference is reduced gradually.

    Then, the magnitude of the load voltage is regulated to equal

    the utility voltage. At the moment of 350 ms, the switch Si is

    turned on, and the current injected into the grid ig a increases

    smoothly without huge inrush current, and the load voltage is

    stable during the transition.

    Fig. 21 shows the experimental waveforms when DG feeds

    nonlinear load in the islanded mode. It can be seen that the

    distortion of the load voltage is improved by the load current

    feedforward, and the THD of the load voltage is reduced from

    4.7% to 3.2%.

    Fig. 21. Experimental waveform when DG feeds nonlinear load in islandedmode (a) with load current feedforward and (b) without load current feedfor-ward: CH1, load current i L L a , 5 A/div; CH3, load voltage v C a , 100 V/div;CH4, inductor currentiL a , 5 A/div.

    When the power of the nonlinear load is varied, the THD of

    the load voltage is also changed, and the experimental results are

    shown in Fig. 22. It can be seen that with the load current feed-

    forward, the THD of the load voltage can always be mitigated

    under different power of the nonlinear load.

    Fig. 23 shows the experimental waveforms when DG feeds

    nonlinear load in the grid-tied mode. It can be seen that with the

    load current feedforward, there is harmonic component in the

  • 8/10/2019 anki A Unified Control Strategy for Three-Phase Inverter.pdf

    14/16

    LIUet al.: UNIFIED CONTROL STRATEGY FOR THREE-PHASE INVERTER IN DISTRIBUTED GENERATION 1189

    Fig. 22. Variation of the THD of the load voltage with the power of thenonlinear load when DG is in the islanded mode.

    Fig. 23. Experimental waveforms when DG feeds nonlinear load in the grid-tied mode (a) with load current feedforward and (b) without load current feed-

    forward: CH1, inductor current iL a , 10 A/div; CH2,load current iL L a , 5 A/div;CH3, grid voltagevg a , 100 V/div; CH4, grid currentig a , 10 A/div.

    inductor currentiLa , and the harmonics component in the grid

    current is reduced.

    The THD of the grid current under different power of the

    nonlinear load and different amplitude of the grid fundamental

    Fig. 24. Variation of the THD of the grid current when DG is in the grid-tiedmode with (a) the power of the nonlinear load, and (b) the amplitude of the gridcurrent.

    current is investigated, and the experimental results are shown

    in Fig. 24. In Fig. 24(a), the amplitude of the grid fundamental

    current is set at 7 A, and the power of nonlinear load is varied. It

    can be found that with the increaseof the load power, the THD of

    the grid current rises, and the THD of the grid current is reduced

    with the load current feedforward. In Fig. 24(b), the power ofthe nonlinear load is set at around 600 W, and the amplitude of

    the grid fundamental current is changed. It can be seen that the

    THD of the grid current can be mitigated at different magnitude

    of the grid fundamental current.

    VI. CONCLUSION

    A unified control strategy was proposed for three-phase in-

    verter in DG to operate in both islanded and grid-tied modes,

    with no need for switching between two different control ar-

    chitectures or critical islanding detection. A novel voltage con-

    troller was presented. It is inactivated in the grid-tied mode,

    and the DG operates as a current source with fast dynamic

  • 8/10/2019 anki A Unified Control Strategy for Three-Phase Inverter.pdf

    15/16

    1190 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 3, MARCH 2014

    performance. Upon the utility outage, the voltage controller can

    automatically be activated to regulate the load voltage. More-

    over, a novel load current feedforward was proposed, and it can

    improve the waveform quality of both the grid current in the

    grid-tied mode and the load voltage in the islanded mode. The

    proposed unified control strategy was verified by the simulation

    and experimental results.

    REFERENCES

    [1] R. C. Dugan and T. E. McDermott, Distributed generation, IEEE Ind.

    Appl. Mag., vol. 8, no. 2, pp. 1925, Mar./Apr. 2002.[2] R. H. Lasseter, Microgrids and distributed generation,J. Energy Eng.,

    vol. 133, no. 3, pp. 144149, Sep. 2007.[3] C. Mozina, Impact of green power distributed generation, IEEE Ind.

    Appl. Mag., vol. 16, no. 4, pp. 5562, Jul./Aug. 2010.[4] IEEE Recommended Practice for Utility Interface of Photovoltaic(PV)

    Systems, IEEE Standard 929-2000, 2000.[5] IEEE Standard for Interconnecting Distributed Resources with Electric

    Power Systems, IEEE Standard 1547-2003, 2003.[6] J. Stevens, R. Bonn, J. Ginn, and S. Gonzalez,Development and Testing

    of an Approach to Anti-Islanding in Utility-Interconnected PhotovoltaicSystems. Livermore, CA, USA: Sandia National Laboratories, 2000.[7] A. M. Massoud, K. H. Ahmed, S. J. Finney, and B. W. Williams, Har-

    monic distortion-based island detection technique for inverter-based dis-tributed generation,IET Renewable Power Gener., vol. 3, no. 4, pp. 493

    507, Dec. 2009.[8] T. Thacker, R. Burgos, F. Wang, and D. Boroyevich, Single-phase is-

    landing detection based on phase-locked loop stability, inProc. 1st IEEEEnergyConvers. Congr. Expo., SanJose,CA, USA, 2009,pp. 33713377.

    [9] S.-K. Kim, J.-H. Jeon, J.-B. Ahn, B. Lee, and S.-H. Kwon, Frequency-shift acceleration control for anti-islanding of a distributed-generationinverter,IEEE Trans. Ind. Electron., vol. 57, no. 2, pp. 494504, Feb.2010.

    [10] A. Yafaoui, B. Wu, and S. Kouro, Improved active frequency drift anti-islanding detection method for grid connected photovoltaic systems,

    IEEE Trans. Power Electron., vol. 27, no. 5, pp. 23672375, May 2012.[11] J. M. Guerrero, L. Hang, and J. Uceda, Control of distributed uninter-

    ruptible power supply systems,IEEE Trans. Ind. Electron., vol.55,no.8,pp. 28452859, Aug. 2008.

    [12] M. C. Chandorkar, D. M. Divan, and R. Adapa, Control of parallel con-nectedinverters in standalone ACsupply systems,IEEE Trans. Ind. Appl.,vol. 29, no. 1, pp. 136143, Jan./Feb. 1993.

    [13] Y. Li, D. M. Vilathgamuwa, and P. C. Loh, Design, analysis, and real-time testing of a controller for multibus microgrid system, IEEE Trans.Power Electron., vol. 19, no. 5, pp. 11951204, Sep. 2004.

    [14] F. Gao and M. R. Iravani, A control strategy for a distributed generationunit in grid-connected and autonomous modes of operation, IEEE Trans.Power Del., vol. 23, no. 2, pp. 850859, Apr. 2008.

    [15] S.-H. Hu, C.-Y. Kuo, T.-L. Lee, and J. M. Guerrero, Droop-controlledinverters with seamless transition between islanding and grid-connectedoperations, in Proc. 3rd IEEE Energy Convers. Congr. Expo. , Phoenix,

    AZ, USA, 2011, pp. 21962201.[16] L. Arnedo, S. Dwari, V. Blasko, and S. Park, 80 kW hybrid solar in-

    verter for standalone and grid connected applications, in Proc. 27thIEEEAppl. Power Electron. Conf. Expo., Orlando, FL, USA, 2012, pp. 270276.

    [17] R. Tirumala, N. Mohan, and C. Henze, Seamless transfer of grid-connected PWM inverters between utility-interactive and stand-alonemodes, inProc. 17th IEEE Appl. Power Electron. Conf. Expo. , Dallas,TX, USA, 2002, pp. 10811086.

    [18] R. Teodorescu and F. Blaabjerg, Flexible control of small wind turbineswith grid failure detection operating in stand-alone and grid-connectedmode,IEEE Trans. Power Electron., vol. 19, no. 5, pp. 13231332, Sep.2004.

    [19] H. Zeineldin, M. I. Marei, E. F. El-Saadany, and M. M. A. Salama, Safecontrolled islanding of inverterbased distributed generation,in Proc.35th

    IEEE Power Electron. Spec. Conf., Aachen, Germany, 2004, pp. 25152520.

    [20] H. Zeineldin, E. F. El-Saadany, and M. M. A. Salama, Intentional is-landing of distributed generation, in Proc. IEEE Power Eng. Soc. Gen.

    Meeting, San Francisco, CA, USA, 2005, pp. 14961502.

    [21] S. Jung, Y. Bae, S. Choi, andH. Kim, Alow cost utility interactiveinverterfor residential fuel cell generation,IEEE Trans. Power Electron., vol. 22,

    no. 6, pp. 22932298, Nov. 2007.[22] R. Majumder, A. Ghosh, G. Ledwich, and F. Zare, Control of parallel

    converters for load sharing with seamless transfer between grid connectedand islanded modes, inProc. IEEE Power Eng. Soc. Gen. Meeting, Pitts-burgh, PA, USA, 2008, pp. 17.

    [23] H. Tao, J. L. Duarte, and M. A. M. Hendrix, Line-interactive UPS usinga fuel cell as the primary source, IEEE Trans. Ind. Electron., vol. 55,

    no. 8, pp. 30123021, Aug. 2008.[24] D. N. Gaonkar, G. N. Pillai, and R. N. Patel, Seamless transfer of micro-

    turbine generation system operation between grid-connected and islandingmodes, Electr. Power Compon. Syst., vol. 37, no. 2, pp. 174188, Jan.2009.

    [25] N. Reza, G. Gevorg, A. Mehrdad, and M. Mishel, Grid-tied and stand-

    alone operation of distributed generation modulesaggregated by cascadedboost converters,J. Power Electron., vol.10, no. 1,pp. 97105, Jan.2010.

    [26] G. M. S. Azevedo, F. Bradaschia, M. C. Cavalcanti, F. A. S. Neves,J. Rocabert, and P. Rodriguez, Safe transient operation of microgridsbased on master-slave configuration, inProc. 3rd IEEE Energy Convers.Congr. Expo., Phoenix, AZ, USA, 2011, pp. 21912195.

    [27] I. J. Balaguer, Q. Lei, S. Yang, U. Supatti, and F. Z. Peng, Control forgrid-connected and intentional islanding operations of distributed powergeneration,IEEE Trans. Ind. Electron., vol. 58, no. 1, pp. 147157, Jan.2011.

    [28] S.-M. Lee, K.-N. Sung, T.-K. Lee, and W.-C. Lee, UPS/APF powerconversion equipment with a seamless mode transfer, in Proc. 8th IEEE

    Int. Conf. Power Electron., Jeju, Korea, 2011, pp. 27692776.[29] M. Ranjbar, H. Ebrahimirad, S. Mohaghegh, and A. Ghaleh, Seamless

    transfer of three-phasegrid-interactive microturbineinverter between grid-connected and stand-alone modes, in Proc. 19th Iranian Conf. Electr.

    Eng., Tehran, Iran, 2011, pp. 16.[30] T.-S. Hwang and S.-Y. Park, A seamless control strategy of distributed

    generation inverterfor critical load safety under strictgrid disturbance,inProc. 27th IEEE Appl. Power Electron. Conf. Expo. , Orlando, FL, USA,2012, pp. 254261.

    [31] F.-S. Pai, An improved utility interface for microturbine generation sys-tem with stand-alone operation capabilities, IEEE Trans. Ind. Electron.,vol. 53, no. 5, pp. 15291537, Oct. 2006.

    [32] F.-S. Pai and S.-J. Huang, Design and operation of power converterfor microturbine powered distributed generator with capacity expansion

    capability, IEEE Trans. Energy Convers., vol. 23, no. 1, pp. 110118,

    Mar. 2008.[33] D. Dong, T. Thacker, R. Burgos, D. Boroyevich, F. Wang,and B. Giewont,

    Control design and experimental verification of a multi-function single-phase bidirectional PWM converter for renewable energy systems, inProc. 13th Eur. Conf. Power Electron. Appl., Barcelona, Spain, 2009,pp. 110.

    [34] D. Dong, T. Thacker, I. Cvetkovic, R. Burgos, D. Boroyevich, F. F. Wang,and G. Skutt, Modes of operation and system-level control of single-phase bidirectional PWM converter for microgrid systems, IEEE Trans.Smart Grid, vol. 3, no. 1, pp. 93104, Mar. 2012.

    [35] G. Shen, D. Xu, and D. Xi, Novel seamless transfer strategies for fuelcell inverters from grid-tied mode to off-grid mode, in Proc. 20th IEEE

    Appl. Power Electron. Conf. Expo., Austin, TX,USA, 2005, pp. 109113.[36] G. Shen, D. Xu, and X. Yuan, A novel seamless transfer control strategy

    based on voltage amplitude regulation for utility-interconnected fuel cellinverters with an LCL-filter, in Proc. 37th IEEE Power Electron. Spec.

    Conf., Jeju, Korea, 2006, pp. 16.[37] G. Shen, D. Xu, and X. Yuan, Instantaneous voltage regulated seamlesstransfer control strategy for utility-interconnected fuel cell inverters withan LCL-filter, in Proc. 5th IEEE Int. Power Electron. Motion ControlConf., Shanghai, China, 2006, pp. 15.

    [38] S. Huang, L. Kong, and H. Xu, Control algorithm research on seamlesstransfer for distributed resource with a LCL filter, inProc. 3rd Int. Conf.

    Electr. Utility DRPT, Nanjing, China, 2008, pp. 28102814.[39] Q. Lei, S. Yang, and F. Peng, Multi-loop control algorithms for seamless

    transition of grid-connected inverter, in Proc. 25th IEEE Appl. PowerElectron. Conf. Expo., Palm Springs, CA, USA, 2010, pp. 844848.

    [40] J.-H. Jung, E.-C. Nho, I.-D. Kim, H.-G. Kim, T.-W. Chun, and N.-S. Choi,Seamless control mode transfer of a PCS for islanding mode operation,in Proc. 8th IEEEInt. Conf. PowerElectron., Jeju, Korea, 2011,pp. 26582662.

    [41] M. Cirrincione, M. Pucci, and G. Vitale, A single-phase DG generationunit with shunt active power filter capability by adaptive neural filtering,

    IEEE Trans. Ind. Electron., vol. 55, no. 5, pp. 20932110, May 2008.

  • 8/10/2019 anki A Unified Control Strategy for Three-Phase Inverter.pdf

    16/16

    LIUet al.: UNIFIED CONTROL STRATEGY FOR THREE-PHASE INVERTER IN DISTRIBUTED GENERATION 1191

    [42] J. He, Y. W. Li, and M. S. Munir, A flexible harmonic control approachthrough voltage-controlled DG-grid interfacing converters, IEEE Trans.

    Ind. Electron., vol. 59, no. 1, pp. 444455, Jan. 2012.[43] Q. Lei, F. Z. Peng, and S. Yang, Multiloop control method for high-

    performance microgrid inverter through load voltage and current decou-pling with only output voltage feedback, IEEE Trans. Power Electron.,vol. 26, no. 3, pp. 953960, Mar. 2011.

    [44] P. C. Loh and D. G. Holmes, Analysis of multiloop control strategies forLC/CL/LCL-filtered voltage-source and current-source inverters, IEEE

    Trans. Ind. Appl., vol. 41, no. 2, pp. 644654, Mar./Apr. 2005.[45] P. C. Loh, M. J. Newman, D. N. Zmood, and D. G. Holmes, A compar-

    ative analysis of multiloop voltage regulation strategies for single andthree-phase UPS systems, IEEE Trans. Power Electron., vol. 18, no. 5,pp. 11761185, Sep. 2003.

    [46] M. J. Ryan and R. D. Lorenz, A high performance sine wave inverter

    controller with capacitor current feedback and back-EMF decoupling,in Proc. 26thIEEE PowerElectron. Spec.Conf., Atlanta, GA,USA, 1995,pp. 507513.

    [47] M. N. Marwali and A. Keyhani, Control of distributed generationsystemsPart I: Voltages and cu rrents control,IEEE Trans. Power Elec-tron., vol. 19, no. 6, pp. 15411550, Nov. 2004.

    [48] A. Hasanzadeh, O. C. Onar, H. Mokhtari, and A. Khaligh, Aproportional-resonant controller-based wireless control strategy with a re-duced number of sensors for parallel-operated UPSs, IEEE Trans. Power

    Del., vol. 25, no. 1, pp. 468478, Jan. 2010.

    [49] M. Savaghebi, A. Jalilian, J. C. Vasquez, and J. M. Guerrero, Secondarycontrolfor voltage quality enhancementin microgrids,IEEE Trans. Smart

    Grid, vol. 3, no. 4, pp. 18931902, Dec. 2012.[50] S.-K. Chung, A phase tracking system for three phase utility interface

    inverters,IEEE Trans. Power Electron., vol. 15, no. 3, pp. 431438, May2000.

    [51] F. Blaabjerg, R. Teodorescu, M. Liserre, and A. V. Timbus, Overviewof control and grid synchronization for distributed power generation sys-tems, IEEE Trans. Ind. Electron., vol. 53, no. 5, pp. 13981409, Oct.2006.

    [52] D. Dong, J. Li, D. Boroyevich, P. Mattavelli, I. Cvetkovic, and Y. Xue,Frequency behavior and its stability of grid-interface converter in dis-tributed generation systems, in Proc. 27th IEEE Appl. Power Electron.Conf. Expo., Orlando, FL, USA, 2012, pp. 18871893.

    [53] Y. A. R. I. Mohamed, H. H. Zeineldin, M. M. A. Salama, andR. R. Seethapathy, Seamless formation and robust control of distributed

    generation microgrids via direct voltage control and optimized dynamic

    power sharing, IEEE Trans. Power Electron., vol. 27, no. 3, pp. 12831294, Mar. 2012.

    Zeng Liu (S09) received the B.S. degree in electri-cal engineering from Hunan University, Changsha,China, in 2006, and the M.S. degree in electricalengineering from Xian Jiaotong University, Xian,

    China, in 2009, where he is currently working towardthe Ph.D. degree.

    His research interests include control of single-phase and multiphase power converters for uninter-

    rupted power supply and utility application, model-ing, and analysis and control of distributed powersystem based on three-phase ac bus.

    Jinjun Liu (M97SM10) received the B.S. andPh.D. degrees in electrical engineering from Xian

    Jiaotong University (XJTU), Xian, China, in 1992and 1997, respectively.

    He then joined the XJTU Electrical EngineeringSchool as a teaching faculty. In 1998, he led thefounding of XJTU/Rockwell Automation Laboratoryand served as the Lab Director. From 1999 until early2002, he was with the Center for Power Electron-

    ics Systems, Virginia Polytechnic Institute and StateUniversity, USA, as a Visiting Scholar. He then came

    back to XJTU and in late 2002 was promoted to a Full Professor and the Headof the Power Electronics and Renewable Energy Center, XJTU. During 2005to early 2010, he served as the Associate Dean with the School of ElectricalEngineering, XJTU. He currently also servesas the Dean for Undergraduate Ed-

    ucation, XJTU. He coauthored three books, published more than 100 technicalpapers, holds 13 patents. His research interests include power quality control,renewable energy generation and utility applications of power electronics, andmodeling and control of power electronic systems.

    Dr. Liu is an AdCom member of the IEEE Power Electronics Society andserves as Region 10 Liaison. He received several national, provincial, or minis-terial awards for scientific or career achievements, and the 2006 Delta ScholarAward. He also serves as an Associate Editor for the IEEE T RANSACTIONS ON

    POWER ELECTRONICS. He is an AdCom member and the Chair of Student Ac-tivities Committee for IEEE Xian Section. He is on the Executive Board and

    serving as a Deputy Secretary-General for the China Power Electronics Society,and also on the Executive Board and serving as a Deputy Secretary-General forthe China Power Supply Society.

    Yalin Zhao received the B.S. degree in electricalengineering from Xian Jiaotong University, Xian,China, in 2011, where he is currently working towardthe M.S. degree.

    His research interests include dead-time compen-sation, stability analysis, and control of inverters.