Nº 9372/17.R1 Translation of original Spanish Report
English Version Page 1 of 20
APPLICANT :
RAYCHEM RPG (P) LTD
Test:
Determination and classification of Fire Resistance. Circuit integrity maintenance.
• Test standard: ...............DIN 4102-12:1998 • Specimen: .....................Junction box for electric cable systems required to
maintain circuit integrity. � Manufacturer: ..........RAYCHEM RPG (P) LTD � Reference: ................Fire rated junction box (FRJB/SE1035-A(FRJ01-FRJ06))
Test Report nr. 9372/17.R1 Translation of original Spanish Report English Version Page 2 of 20
The Test Report nr. 9372/17.R1_VI supersedes the Test Report nr. 9372/17.R1_VI dated 26th-Apr-2017.
This report is a translation of the Spanish Test Report nr 9372/17.R1 dated 26th-Apr-2017. In case of doubt, the Spanish version of the Test Report prevails.
The Test Report nr. 9372/17.R1 supersedes the Test Report nr. 9372/17.
The results of this Test Report make sole and exclusive reference to the specimen tested, and not to the product in general.
The information held in this Test Report is of a confidential nature, meaning the Laboratory will not provide information in relation to this report to third parties, except with the authorization of the Applicant.
It is not allowed to reproduce partially this Test Report without the Laboratory’s written approval.
APPLICANT
RAYCHEM RPG (P) LTD 1/62, Near Bharat Petrol Pump, Sativali, VASAI ( EAST ), INDIA PIN 401208.
TEST SPECIMENS (�) Information supplied by the applicant
Type of specimen: ......................... Junction box for electric cable systems required to maintain circuit integrity.
� Manufacturer: ............................ RAYCHEM RPG (P) LTD (Junction box) CONNECTWELL (terminal blocks)
PERFORMED TEST Fire resistance test of electric cables systems required to maintain circuit integrity according to DIN 4102-12:1998
Test date: ........................................ 21.04.2017 Place of test performance: .............. Arganda del Rey’s facilities (Madrid) SPAIN
Report Content
1.- Test specimens ........................................................................................ Page 3 2.- Test performed ........................................................................................ Page 5 3.- Specimens assembly ........................................................................................ Page 5 4.- Test conditions ........................................................................................ Page 6 5.- Results ........................................................................................ Page 6 6.- Classification and field of application ..................................................................... Page 7
ANNEX 1: Graphics of evolution of temperatures and ....................................................... Page 9
pressure inside the furnace. ANNEX 2: Photographs. ....................................................... Page 10
ANNEX 3: Technical Documentation ....................................................... Page 11
DIGITALLY SIGNED
DOCUMENT
English Version Test Report nr 9372/17.R1
It is not allowed to reproduce partially this Test Report without the Laboratory’s written approval. Page 3 of 20
1.- TEST SPECIMEN
Junction boxes reception: − Date: ......................................... 06.03.2017 and 18.04.2017 − Package ..................................... cardboard box − Sampling and delivery .............. sent and selected by the applicant. Documentation: − Date: ....................... 18.04.2017 (latest version) − Documentation ...... Junction box technical documentation (See annex 4)
Description:
The main characteristics of the specimen have been supplied by the applicant (See annex 4). The data cross-checked by the laboratory were:
NOTE: (�) This symbol marks the information supplied by the applicant and cannot be cross checked by the laboratory.
The tested specimen is a junction box for cables system with circuit integrity maintenance, consisting of fire resistant cables and its accessories.
Said elements are fixed to the furnace ceiling.
Two different sizes of junction boxes are tested with two types of E90 cables (acc. to DIN 4102-12:1998.), forming 4 different configurations. Two identical specimens of each configuration are tested, adding up to a total of 8 specimens.
Junction box Type of cable Muestra
Type 1 150 (length) × 150 (width) × 100 (height) mm
Type 1 � (N)HXH F180 E90 // 3 × 4 mm2
9372AA
9372AB
Type 2 � (N)HXH F180 E90 // 2 × 1,5 mm2
9372AC
9372AD
Type 2 350(length) × 250 (width) × 105 (height)mm
Type 1 � (N)HXH F180 E90 // 3 × 4 mm2
9372AE
9372AF
Type 2 � (N)HXH F180 E90 // 2 × 1,5 mm2
9372AG
9372AH
• Junction box
- Description: ....................................... metallic 5 sided junction box, fixed to the ceiling by 4 expansion anchors, and a metallic lid with screws on its four corners.
- Manufacturer: ................................... � RAYCHEM RPG (P) LTD - Reference: ......................................... � Fire rated junction Box (FRJB/SE1035-A (FRJ01-FRJ06)) - Material: ............................................ � Steel - Dimensions (mm):
- Type 1: ........................................... 150 (length) x 150 (width) x 100 (height) - Type 2: ........................................... 350 (length) x 250 (width) x 105 (height) - Furnace ceiling fixings: .................... 4 steel pieces to join to the anchors on the ceiling to the box
DIGITALLY SIGNED
DOCUMENT
English Version Test Report nr 9372/17.R1
It is not allowed to reproduce partially this Test Report without the Laboratory’s written approval. Page 4 of 20
- Box internal componentes: - Terminal blocks:
- Referencia: ........................ � CONNECTWELL - Material: ............................ ceramic - Clamps: ............................. 3 - Amount: ............................ one per box
- Structural board:
- Material: ............................ metallic - Thickness (mm): ................ 2 - Placement: ........................ bottom of the junction box - Fixings: ............................. 4 screws, one on each corner.
- Cable glands: - Material: ............................ metallic - Amount: ............................ 2 - Placement: ........................ opposite sides of junction box
- Box lid:
- Material: ............................ metallic - Fixings: ............................. 4 screws, one on each corner. - Seal joint: .......................... along the perimeter, dimensions 17 x 7 mm aprox.
Figure 1 – Junction box interior
• Cables (Technical data sheets in Annex 4)
- Description: .................................... fire rated electric cable, tagged as E90 acc. to DIN 4102-12:1998 - VDE Approval (See annex 4): .......... Yes (printed on cables) - Type: .............................................. (N) HXH (printed on cables) - Reference: ...................................... � DATWYLER KERAM (N) HXH FE180 E90.
Type 1 - Exterior diameter (mm): ................ 13,5 - Section (mm2): .................................. 3 x 4 (printed on cables) - Number of conductors: .................. 3
Type 2 - Exterior diameter (mm): ................ 11 - Section (mm2): .................................. 2 x 1,5 (printed on cables) - Number of conductors: .................. 2
Junction box
Structural board
Terminal block
Cable glands
Furnace anchor points
DIGITALLY SIGNED
DOCUMENT
English Version Test Report nr 9372/17.R1
It is not allowed to reproduce partially this Test Report without the Laboratory’s written approval. Page 5 of 20
• Wire protection
- Description: .................................... The cables are stripped of their existing protection to make the connections. The unprotected conductors are, once connected, and covered with mica tape and a ceramic blanket.
- Mica tape:
- Location: ........................... around the ustripped conductors connected to the terminal blocks
- Dimensions (mm): .............. 17 (width) - Ceramic blanket:
- Location: ........................... covering the mica tape, and around the electric cables passing through the cable glands.
- Thickness (mm): ................. 1
2.- TESTS PERFORMED Test according to DIN 4102-2:1977-09 “Fire behavior of building materials and building components. Building components. Concepts, requirements and testing.” And DIN 4102-12:1998-11 “Fire behavior of building materials and elements. Fire resistance test of electric cables systems required to maintain circuit integrity. Requirements and testing” section 7.3.3.5
3.- SPECIMEN ASSEMBLY
The specimens have been individually mounted on the furnace ceiling, made of concrete slabs. The boxes have been fixed to the ceiling as described above. Then the connections of the internal components of the boxes are made. In every tested box, one of the conductors has been connected to the ground through the structural board.. The remaining conductors (1 or 2 acc to each type of cable) are connected through the terminal blocks. The cables are then protected as described above, and the lid is placed and screwed on box. After the assembly, the laboratory proceeded to make the connections required to evaluate the circuit integrity of the system, according to DIN VDE 0472-814. The assembly has been carried out under the applicants´ responsibility.
Assembly conclusion date: 21.04.17
DIGITALLY SIGNED
DOCUMENT
English Version Test Report nr 9372/17.R1
It is not allowed to reproduce partially this Test Report without the Laboratory’s written approval. Page 6 of 20
4.- TEST CONDITIONS
Ambient temperature (ºC):
Prior to the test ....................................................
Average during the test ................................
18,5
19,4
Furnace temperature: (heating curve)
According to DIN 4102-2:1977-09
Average pressure in the furnace during the test:
(probe placed 100 mm under bottom side of specimen)
According to DIN 4102-2:1977-09
Type of fire and fuel used: 4 propane gas burners
5.- RESULTS
The duration of the test was 90 minutes. The test was stopped after maximum classification time was reached. No relevant observation were made during or after the test:
Observations during the test Minute ......... Observation
0 ........ Test starts. 13:30 h aprox.
30 ......... No relevant observations..
60 ......... No relevant observations.
65 ......... Short circuit in specimen 9272AE(*)
90 ......... End of test (*)
Not considered relevant for classification purposes because of short circuit circumstances are not attributed to specimens’ performance.
Expression of results
Circuit Integrity (E) Junction box and cable tested
Junction box- Type 1 150 (length) × 150 (width) × 100 (height) mm Cable – Type 1 � (N)HXH F180 E90 // 3 × 4 mm2 ...........................90 minutes (F)
Junction box- Type 1 150 (length) × 150 (width) × 100 (height) mm Cable – Type 2 � (N)HXH F180 E90 // 2 × 1,5 mm2 .................. 90 minutes (F)
Junction box- Type 2 350 (length) × 250 (width) × 105 (height) mm Cable – Type 1 � (N)HXH F180 E90 // 3 × 4 mm2 ...........................90 minutes (F)
Junction box- Type 2 350 (length) × 250 (width) × 105 (height) mm Cable – Type 2 � (N)HXH F180 E90 // 2 × 1,5 mm2 .................. 90 minutes (F)
(F)
End of test DIGITALLY SIGNED
DOCUMENT
English Version Test Report nr 9372/17.R1
It is not allowed to reproduce partially this Test Report without the Laboratory’s written approval. Page 7 of 20
6.- CLASSIFICACIÓN AND FIELD OF APPLICATION
The specimens have been classified in accordance with paragraph 3.2.2 of DIN 4102-12:1998, and taking into account section 7.3.3.5 of said standard. With the results of the test, and complying with every parameter specified in the classification standard, the use of the tested junction boxes installed as described in a system of type (N) HXH E90 cables with circuit integrity maintenance does not cause a decrease in their fire resistance performance, hence the following classifications apply:
Fire resistance classification Junction box for electric cable systems required to
maintain circuit integrity.
� Fire rated junction Box (FRJB/SE1035-A (FRJ01-FRJ06))
Dimensions: 150/350 (length) × 150/250 (width) × 100/105 (height) mm with connectors and �(N) HXH cables as described above.
E 90
The following additional classifications are allowed:
E 30 60
Arganda del Rey, 5th May of 2017 The developer: The Supervisor:
Signed: Cristina Pérez-Domper Signed: Magdalena Villegas Barranco Technician Technical Director Fire Resistance Laboratory Fire Resistance Laboratory
(The original Spanish version was signed in Arganda del Rey on 26th of April of 2017 by Sergio Nogueras Perona, Technician of Fire Resistance Laboratory and Magdalena Villegas Barranco, Technical Director of the Fire Resistance Laboratory.
DIGITALLY SIGNED
DOCUMENT
English Version Test Report nr 9372/17.R1
It is not allowed to reproduce partially this Test Report without the Laboratory’s written approval. Page 8 of 20
Annexes
DIGITALLY SIGNED
DOCUMENT
Annex 1. Graphics of evolution of temperatures and pressure inside the furnace.
Test Report nr 9372/17.R1 English Version
It is not allowed to reproduce partially this Test Report without the Laboratory’s written approval. Page 9 of 20
-10
0
10
20
30
40
50
60
70
80
90
0
100
200
300
400
500
600
700
800
900
1000
0 5 10 15 20 25 30 35 40 45 50 55 60
Pre
ssu
re (
Pa
)
Te
mp
era
ture
(ºC
)
Time (min)
Evolution of average furnace temperature, furnace pressure and heating curve during the test
Average furnace temperature Heating curve Pressure
NOTE: The pressure maintained during the test is considered valid for the classification obtained.
DIGITALLY SIGNED
DOCUMENT
Annex 2. Photographs.
Test Report nr 9372/17.R1 English Version
It is not allowed to reproduce partially this Test Report without the Laboratory’s written approval. Page 10 of 20
Photograph nº 1 Junction box and furnace ceiling anchor elements
Photograph nº 2 Terminal block
Photograph nº 3 Junction box type 2 lid.
Photograph nº 4 Junction boxes before test.
DIGITALLY SIGNED
DOCUMENT
Annex 3. Technical documentation.
Test Report nr 9372/17.R1 English Version
It is not allowed to reproduce partially this Test Report without the Laboratory’s written approval. Page 11 of 20
DIGITALLY SIGNED
DOCUMENT
Annex 3. Technical documentation.
Test Report nr 9372/17.R1 English Version
It is not allowed to reproduce partially this Test Report without the Laboratory’s written approval. Page 12 of 20
DIGITALLY SIGNED
DOCUMENT
Annex 3. Technical documentation.
Test Report nr 9372/17.R1 English Version
It is not allowed to reproduce partially this Test Report without the Laboratory’s written approval. Page 13 of 20
DIGITALLY SIGNED
DOCUMENT
Annex 3. Technical documentation.
Test Report nr 9372/17.R1 English Version
It is not allowed to reproduce partially this Test Report without the Laboratory’s written approval. Page 14 of 20
DIGITALLY SIGNED
DOCUMENT
Annex 3. Technical documentation.
Test Report nr 9372/17.R1 English Version
It is not allowed to reproduce partially this Test Report without the Laboratory’s written approval. Page 15 of 20
DIGITALLY SIGNED
DOCUMENT
Annex 3. Technical documentation.
Test Report nr 9372/17.R1 English Version
It is not allowed to reproduce partially this Test Report without the Laboratory’s written approval. Page 16 of 20
DIGITALLY SIGNED
DOCUMENT
Annex 3. Technical documentation.
Test Report nr 9372/17.R1 English Version
It is not allowed to reproduce partially this Test Report without the Laboratory’s written approval. Page 17 of 20
DIGITALLY SIGNED
DOCUMENT
Annex 3. Technical documentation.
Test Report nr 9372/17.R1 English Version
It is not allowed to reproduce partially this Test Report without the Laboratory’s written approval. Page 18 of 20
DIGITALLY SIGNED
DOCUMENT
Annex 3. Technical documentation.
Test Report nr 9372/17.R1 English Version
It is not allowed to reproduce partially this Test Report without the Laboratory’s written approval. Page 19 of 20
DIGITALLY SIGNED
DOCUMENT