back to basics chapter 5 - neboea.org ibc chapter 5.pdf · 2 table 503 table 503 this is the...
TRANSCRIPT
1
BACK TO BASICS – CHAPTER 5 GENERAL BUILDING HEIGHTS AND AREAS
Presented at UMass, October 2013
Christopher R. Laux, A.I.A. Architect/Building Official/Consultant
Contact Information
Christopher R. Laux, A.I.A.
PO Box 636
Woodbury, CT 06798-0636
(203) 263-5787
Applicability of discussion
This discussion is based on the provisions of Chapter 5 of the 2012 International Building Code (IBC) No State amendments included in
discussion
This discussion is conceptual and general by nature. Time allotted does not allow for in-depth analysis of salient points.
Disclaimer
This discussion does not pretend to include all items the code user needs to be aware of. Purchasing, opening and frequent, careful reading of the code is essential to understand its many intricacies.
The handout does not take the place of owning or reading the code.
501 - General
Applies to heights and areas of new buildings and additions to existing buildings (no existing building plus additions can exceed requirements)
You must also evaluate change of occ.
New 2012: new and existing buildings must have approved address identification in plainly visible location
503 – General Limitations
Heights and areas of buildings shall not exceed Table 503 except as modified herein…..so Table 503 is only a starting point!
Buildings separated by fire walls are separate buildings
2
Table 503 Table 503
This is the starting point in determining the actual allowable height and area of a building given its occupancy and construction type.
Can also be used to determine minimum construction type when height and area are known
General limitations
503.1.1: limited application for exemption from T. 503: applies to buildings housing special industrial processes that require large areas and unusual heights to accommodate craneways or special machinery or equipment. Examples include rolling mills, structural metal fabrication; foundries & power production.
General limitations
503.1.2: when multiple buildings on the same lot could be combined into a single building that complies with T. 503, you need not establish fire separation distances between them
Most restrictive construction type and occupancy regulates
Code provisions that are applicable to aggregate building apply to separate buildings
Example 1 Example 2
3
General limitations
503.1.3: Type 1 buildings permitted to be of unlimited height or area by Table 503 based on construction classification do not have to comply with other unlimited area building requirements.
Building height
504.1 exception to height limits: 1 story aircraft hangars; aircraft paint hangars; and aircraft manufacturing buildings not limited in height if sprinklered and surrounded by yards or public ways not less in width than 1 ½ times the building height.
Building height
504.2: sprinklered buildings receive a one story, 20 foot height increase over T. 503 limits
Group R with NFPA 13R systems limited to 60 feet and 4 stories
No increase for Group I-2 in IIB, III, IV or V buildings
No increase for H-1, H-2, H-3 or H-5 occ.
Building height – roof structures
504.3: unoccupied towers, spires, steeples and other roof structures shall be of same materials as building (unless permitted by 1509.2.5)
Unlimited in height if noncombustible
Max. 20’ above allowable building height if combustible
See Chapter 15 for additional requirements
Mezzanines & Equipment Platforms
Mezzanine is portion of story below
Does not contribute to building area
Not considered a story
Does contribute to fire area
Clear height above and below 7’ minimum
Mezzanine & Equipment Platform Area Limitations
Mezzanine limited to 1/3 area of room with which it shares a common atmosphere
Enclosed spaces in room below can’t be used in calculation
Multiple mezzanines in story; same 1/3
When mezzanine and equipment platform, limit is 2/3
4
Mezzanine example: Mezzanine & Equipment Platform Area Limitations
Exceptions:
Aggregate area for mezzanines in Construction Type I or Type II special industrial occupancies = 2/3
New 2012: mezzanines in Type I or Type II building with sprinklers and emergency voice/alarm communication system = 1/2
Mezzanines
505.2.3: mezzanine must be open and unobstructed to room below except for 42” walls, columns and posts (no glass)
Exceptions:
10 or fewer occupants
2 or more MOE; 1 of which is exit
10% of mezzanine may be enclosed
Group F control mezzanines may be glazed
New 2012: Other than H or I: 2 story sprinklered buildings: mezzanine not required to be open
Building area increases
Frontage: 1% additional area for each 1% frontage above 25%
If = [F/P - .25] W/30
If = area increase for frontage
F = building perimeter with 20’ min. width
P = entire building perimeter
W = width of public space (20’ min., 30’ max.)
Frontage example: Example:
100’ x 50’ building with 250’ (83%) OP, 100’ of which is only 25’ wide:
If = [250/300 - .25] 28/30 = .544 = 54.4%
Allowable area (w/o sprinklers) = 1.544 x Table 503
Note: W= 100x25 + 150x30 / 250 = 28
5
Sprinkler area increase
Only applies to NFPA 13 systems, not 13R or 13D
Not permitted in buildings with Group H-1 occupancy (entire building); buildings or portions of buildings with Group H-2 or H-3 occupancies (other portions can take increase); buildings where the sprinkler system was substituted for fire-resistance rated construction (see T. 601, note d)
Sprinkler area increase
200 % increase for multi-story buildings
300% increase for single story buildings
Permitted in addition to height increases for sprinklers and area increases for frontage
Only stories above grade count in this evaluation; not basements
Example One:
Group A-1 (theatre); 1 story, Type VB construction, 54.4% If, fully sprinklered. How big can it be?
Tabular area = 100% =1.00
OP = 54.4% = .544
Sprinklers = 300% = 3.00
Total = 454.4% = 4.544
5,500 s.f. x 4.544 = 24,992 allowable
Example two: Find the required construction type for a 30,000 s.f. per floor two story Group B, fully sprinklered with 100% OP (min 30’ wide):
Tabular = 100% = 1.00
If = 75% = .75
Sprinkler = 200% = 2.00
Total = 375% = 3.75
Equivalent area = 30,000/3.75 = 8,000
Per Table 503, any construction classification works, including VB
Maximum building area
506.4 - Multi story, single occupancy:
Determine allowable area per floor; for 2 story, multiple by 2; for 3 or more stories multiply by 3
No single story shall exceed the allowable area per story
A single basement that does not exceed the allowable area per floor does not count toward maximum area of the building
506.4 Example
Group B; Type IIA; fully sprinklered; 75% OP increase; 6 stories; basement:
37,500 x 3.75 = 140,625 per floor
140,625 x 3 = 421,875 total building
Distribute among 6 stories however you want but no story can be over 140,625
Single basement doesn’t count but can’t be over 140,625
6
Maximum building area
506.5 - Mixed occupancy:
1 story: see 508.1 (more on that later)
More than 1 story: each story shall comply with 508.1; more than 3 stories – total building area shall be such that sum of ratios of the actual area of each story divided by the allowable area of such stories shall not exceed 3.
Again, a single basement doesn’t count
506.5 example:
Unlimited area buildings
New 2012: 507.1 clarifies that unlimited area buildings can have accessory occupancies in them.
Yards: measured perpendicular from exterior wall to nearest lot line or face of opposing building on same lot
Public way: measure entire width (road, highway, railroad, etc.)
Unlimited area buildings 507.2: Non-sprinklered 1 story: F-2 or S-2 surrounded by 60’ yard/public way
507.3: Sprinklered 1 story: B, F, M, or S any const. type; or A-4 other than Type V surrounded by 60’ yard or public way
Type I or II with rack storage and no public access have no height limit
Sprinklers not req. over participant sport area with direct exits and alarm system (not considered fully sprinklered bldg.)
Mixed occupancy unlimited area w/ Groups A-1 and A-2 (507.3.1)
Other than Type V construction; sprinklered, 1 story; B, F, M or S occ.
A-1 and A-2 must be separated from other occupancies per T 508.4 with no reduction for sprinklers = 1 hour F-2 or S-2; 2 hours B, F-1, M, or S-1
A-1 or A-2 areas cannot exceed T. 503 w/ If & sprinkler increases
Exits from A-1 or A-2 must discharge directly to exterior
Unlimited area buildings
507.4: Two story B, F, M or S:
Must be sprinklered
Must be surrounded by min. 60’ yard or public way
7
Compliant? Unlimited area buildings
507.5: Reduced open space – open space can be reduced to 40’ when all of the following:
Reduced width for not more than 75% of the perimeter of the building
Exterior walls facing reduced width: 3 hour
Opening protectives facing reduced width must be 3 hour
Applies only to 507.2; 507.3; 507.4; 507.6 & 507.11 (not to A-3 Type III or IV, E, H or Aircraft paint hangar)
Unlimited area 1 story Type II, Group A-3 (507.6)
Allows place of religious worship, community hall, dance hall, exhibition hall, gymnasium, lecture hall, indoor swimming pool or tennis court
No stage; platform OK
Must be sprinklered
Minimum 60’ yards or public way
New 2012: Unlimited area 1 story Type III & IV, Group A-3 (507.7)
Same requirements as 507.6 plus:
Assembly floor must be at or within 21” of street or grade level and all exits must have compliant ramps
Means no mezzanines allowed
Group H occupancies in unlimited area buildings
See 507.8 for Group H occupancies in unlimited area buildings
See 507.9 for unlimited area aircraft paint hangars
Unlimited area buildings
507.10: Group E, 1 story of Type II, IIIA or IV construction:
2 MOE each classroom; one exit direct to outside
Must be sprinklered
Must have 60’ yards or public ways
8
Unlimited area buildings
507.11: Motion picture theatres
Must be Type II construction
Must be located on first story above grade
Must be sprinklered
Must be surrounded by minimum 60’ yards or public ways
507.12: covered malls & anchor buildings complying with 402 shall not be limited in area
Mixed Occupancies
New 2012: moved from Chapter 3 to Chapter 5, Section 508
Three ways to handle:
Accessory occupancies
Non-separated
Separated
Can be all 3 in same building
Can also use fire walls – separate bldgs.
Mixed occupancy exceptions
Special provisions of 510
H-1, H-2 & H-3 required to be in separate buildings by T. 415.5.2
Live/work units complying with 419 are not separate occupancies
Incidental uses
Accessory occupancies
Must be ancillary to main occupancy
Limited to 10% of story
Cannot exceed tabular area T. 503 (no increases)
Retain occupancy classification
Building height & area based on main occupancy
Accessory occupancy cannot exceed tabular height T. 503 (no increases)
Accessory occupancies
No separation required between main and accessory occupancies
Exceptions:
H-2, H-3, H-4, H-5 must be separated
I-1, R-1, R-2 & R-3 DU & SU separations required (generally 1 hour but exceptions for ½ hour floor/ceiling in sprinklered IIB, IIIB & VB – see 420, 708 & 711)
Nonseparated occupancies
Still individually classified
Code requirements apply per occupancy
Most restrictive provisions of Chapter 9 apply to entire nonseparated area
When in high-rise, most restrictive provisions of 403 apply to entire building
9
Nonseparated occupancies
Allowable height and area based on most restrictive occupancy
No separations required except:
H-2, H-3, H-4, H-5 must be separated
I-1, R-1, R-2 & R-3 DU & SU separations required (generally 1 hour but exceptions for ½ hour floor/ceiling in sprinklered IIB, IIIB & VB – see 420, 708 & 711)
Separated occupancies
Each occupancy individually classified
Code requirements apply to each separated space
Separations must be fire barriers (707) or horizontal assemblies (717) or both
All fire areas have 6 sides – like a box
Separation ratings per T. 508.4
Table 508.4 Allowable area and height
In each story the sum of the ratios of actual area divided by allowable area shall not exceed one.
Each separated occupancy’s height within the building shall comply with Section 503.1
Exception: special provisions of 510
Sum of ratios example Incidental Uses - 509
Ancillary functions that pose a greater risk – limited to those in T. 509
Incidental uses in DU need not comply
Option not available for storage rooms
Incidental use areas included in main occupancy
Limited to 10% of story
Separation/protection = T. 509 & 509.4
10
Table 509 Special provisions - 510
510.2: permits a 3 hour horizontal separation to create two buildings stacked on top of each other. Lots of conditions, among them: Lower building Type IA, sprinklered, one story
max.
Special rules for openings through horizontal separation
Occupancies above & below limited
Height in feet from grade plane
Special provisions - 510
510.3: permits 1 story S-2 enclosed parking garage below S-2 open parking garage of a different construction type
See code for specific requirements
510.4, 510.7 & 510.8 (new): provide special exceptions for parking structures beneath or above other occupancies that are less restrictive than T. 503
See code for specific requirements
Special provisions - 510
New 2012: 510.9 - allows multiple buildings above the horizontal assemblies prescribed in Sections 510.2, 510.3 or 510.8
The End
Questions????
Thanks for trying to stay awake!