basic relaying

Upload: tauseef-gillani

Post on 10-Apr-2018

238 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/8/2019 Basic Relaying

    1/35

    Florida Reliability Coordinating Council

    Relay ClassRelay Class

    John White

    System Protection Manager

    Ray Dawson

    System Protection Technician

    Introduction The reasons for protection

    Safety of the public and employees.

    Reliability of power supply to thecustomers.

    Prevent damage to equipment.

    What kind of equipment isprotected: generators, transformers,

    transmission lines, breakers anddistribution lines.

  • 8/8/2019 Basic Relaying

    2/35

    Types of faults

    Three phase, three phase to ground,phase to phase, phase to phase to groundand single phase to ground.

    Three phase faults have the highest faultcurrent.

    Single phase faults have the lowest faultcurrent.

    The fault current is determined by theimpedance of the fault path.

    Fault paths closer to the source will have

    less impedance. Faults caused by trees will have higherimpedance.

    Equipment used CT current transformer

    PT potential transformer

    Transducers

    Time overcurrent relay/51

    Instantaneous Over current relay/50

    Undervoltage relay/27

    Recloser relay/79 Under frequency relay/81

  • 8/8/2019 Basic Relaying

    3/35

    CT current transformer The secondary winding has a standard

    rating of 5 amp. Its indicated as 400/200/5the 400 and 200 are the primary currentwhich gives us an 80 to 1 and 40 to 1 ratiorespectably.

    It is important that CTs be accurate at faultlevels which may be 10 times normal loadcurrent. Standard classifications of CTsallow 10% error for current flow up to 20times rated value. They are marked ClassC ###. The higher the number the highercurrent that can flow though the CT and

    still be 10% accurate. Never open a live CT circuit without firstshorting the secondary side. Without thesecondary side shorted very high voltagewill be seen on the secondary circuit.

    Potential Transformers PTs The secondary voltage is usually

    69V for relaying and 120V formetering.

    There is no problem with errorreadings as during a fault thevoltage will drop.

    At above 115KV coupling capacitorsare used. This is called CCVT. Theyare connected in series causing a

    voltage drop across each cap. PTs should never be shorted.

  • 8/8/2019 Basic Relaying

    4/35

    Transducers Measure voltages and currents and

    converts them to a 0 to 1 milliamp dcoutput.

    A scaling is used in SCADA(supervisory control and dataacquisition) to convert the milliampsignal to a numerical number.

    Time Over current relay/51

    Operate on the electromagnetic inductionprinciple. The protective relay isessentially a small AC motor. Usingshaded pole produce two fluxes that are atdifferent phase angles.

    When current is passed through theelectromagnet coil,a magnetic field isproduced, which applies a torque to thedisc. When the magnetic field becomesstrong enough to overcome friction in the

    damping magnet, bearing and tension inthe spiral spring, the disc rotates to movethe moving contact. Eventually the movingand fixed contacts close, completing thetrip coil circuit to the breaker.

  • 8/8/2019 Basic Relaying

    5/35

    Time Over current relay/51 The disc rotates at a speed directly

    proportional to the amount of fluxinduced into it by the electromagnet.

    The time dial provides adjustment forhow long it takes the moving contact andstationary contact to make contact. Witha higher number on the time dial, thisincreases traveling distance and contacttime.

    The spiral spring is use to set minimumpickup, resets the disc in normal

    conditions or after a trip and provides atemporary path for the DC trip current.The spiral spring is not designed to carrythe trip current for very long. A seal-inbypass is used.

  • 8/8/2019 Basic Relaying

    6/35

    Time Over current relay/51 The seal in coil is in series with the

    contacts on the spiral spring. Theseal in coil contacts are in parallelwith the spiral spring contacts. Theseal in contacts shunt the currentaway from the spiral spring contacts.

    The seal in coil also has a flag that

    drops to indicate which relay had theovercurrent condition.

  • 8/8/2019 Basic Relaying

    7/35

    Instantaneous Over current relays/50 Instantaneous relays have no time

    delay. With a high level fault theinstantaneous unit will operatebefore time overcurrent relay.

    Its a simple clapper relay with acore screw on top to adjust thepickup range.

    The contacts are two moving contacton a bridge and two stationarycontacts. The contacts are directlyacross the trip circuit for thebreaker.

    Undervoltage relays/27 The construction of a undervoltage relay

    is very similar to an overcurrent relay. Themain different is the operating coil. Anovercurrent relays operating coil iswound with a few turns of heavy wire. Avoltage relays operating coil is woundwith many turns of fine wire.

    The disc rotates in the counterclockwisedirection.

    The contact closing torque for an

    undervoltage relay is provided by thetension in the spiral spring. A time delay is the same as for an over

    current relay.

  • 8/8/2019 Basic Relaying

    8/35

    DEVICES USED AT OUC 21 Distance relay

    25 Synchronizing-check device 27 Undervoltage relay 43 Manual transfer or selector device 50 Instantaneous overcurrent relay 51 Time overcurrent relay 52 AC circuit breaker 57 Grounding device 59 Overvoltage relay 63 Gas pressure relay 64 Ground protective relay 67 AC directional overcurrent relay 69 Permissive control device 74 Alarm relay 79 Reclosing relay 81 Frequency relay 86 Locking-out relay 87 Differential protective relay

    The right man for the job

    Mr. Bill Douglas

  • 8/8/2019 Basic Relaying

    9/35

    OUC SYSTEM

    OUC Protective Relay Statistics

    60 Transmission Lines

    4000 Protective Relays

    36 Substations

    14 Generators

    400 Breakers 200 Transformers

    200 Feeder Breakers

  • 8/8/2019 Basic Relaying

    10/35

    OUC Protective Relaymain schemes

    Protects Transmission Lines

    Protects Distribution Lines

    Protects Transformers

    Protects Generators

    Protects Busses Protects Reactors

  • 8/8/2019 Basic Relaying

    11/35

    Stanton Substation

  • 8/8/2019 Basic Relaying

    12/35

    S**t Happens

  • 8/8/2019 Basic Relaying

    13/35

  • 8/8/2019 Basic Relaying

    14/35

    FAULTCHARACTERISTICS

    Two Phase to Ground

    Three Phase to Ground

    Phase to Phase

    Phase to Phase to Phase

    Single Phase to Ground

    TYPES of FAULTS :

    Test Question # 11

    Impedance Diagram

    Voltage= 22800 volts Load Z (one leg)= 70 ohms I= 300 amps

    FAULT

    Test Question # 12: 22800 volts / 3 ohms of fault impedance= 7600 amps.

  • 8/8/2019 Basic Relaying

    15/35

    Ground current possibly damages generator before 50 G relay

    operates.

    Ground Fault Current circulates from the load to the generator

    stator unimpeded.

  • 8/8/2019 Basic Relaying

    16/35

    Resistance, Reactance, ImpedanceResistance, Reactance, Impedance

    ResistanceResistance--(R)(R) The opposition to the flow ofThe opposition to the flow of

    current in an electrical circuitcurrent in an electrical circuit..

    ReactanceReactance--(X)(X) A measure of opposition to aA measure of opposition to asinusoidal current made up of Capacitance and inductancesinusoidal current made up of Capacitance and inductance

    ImpedanceImpedance-- (Z)(Z)Combination of Resistance andCombination of Resistance andReactance that opposes flow of current.Reactance that opposes flow of current.

    Test Question # 13Test Question # 13

    Test Question #14: Reactor/Resistor limits fault currentto about 10 amps preventing damage to stator.

  • 8/8/2019 Basic Relaying

    17/35

    Utility standard of Delta Wye configuration for GSU

    transformer prevents fault current from circulating through

    stator.

    GSU boosts voltage for ease of transmission- 20kV to230kV.

    During fault Voltage A-n collapses and Current A-n increases dramatically.

    Voltages and Currents are 120 degrees between phases.

  • 8/8/2019 Basic Relaying

    18/35

    Disturbance recording

    File: J:\System Protection\Faults and oscillographys\SECA 6,20,03\SECA,6,20,03.

    VA

    VB

    VC

    IA

    IB

    IC

    R1 Trip Brkr 757

    R2 Trip Brkr 759

    R3 SCADA RS1 Op

    R6 757 RI N/A

    R7 759 RI N/A

    R9 757 BF Init

    Part of System Protections

    responsibilities is to analyze faultdata acquired from the

    microprocessor based protective

    relays such as the examplesshown.

    Generator Protection

    507

    509

    150,000 volt

    Breaker

    OUC uses high speed generator schemes that isolates the fault inthe Generator in approximately 2 cycles clearance (.033seconds).

    150,000 volt

    Breaker

    FAULT

    Generator GSU

    Transformer

    To OUC

    system

    Generator Relay

  • 8/8/2019 Basic Relaying

    19/35

    GENERATORPROTECTION

    Rotor Ground

    Excitation Failure

    Over-voltage/ Over-excitation

    Turbine Trip

    Motoring by loss of Prime Mover

    TYPES of Generator Faults :

    Test Question # 15

    Stator Fault

    87G- Generator

    Differential

    87T- GSU Transformer

    Differential

    87ST- Reserve

    Auxiliary Differential.

  • 8/8/2019 Basic Relaying

    20/352

    40- Loss of Field Relay

    81- Under frequency

    Relay59-Under Voltage

    Relay.With loss of field condition, Generator cannot

    produce VARS, lowering terminal voltage and

    overheating of the stator.

    Test Question #16:

    VAR= Volt Ampere

    Reactive

    46- Negative Sequence

    Relay

  • 8/8/2019 Basic Relaying

    21/352

    59G- Generator GroundRelay

    27G- Third harmonicsupervision Relay

    Test Question #

    17:

    Third Harmonic is

    at 180 HZ

    TRANSFORMER

    PROTECTION

    Core Movement

    Bushing Failure

    Arrestor Failure

    Through Fault

    Winding to Ground Fault

    Types of Transformer Faults :

    Test Question # 18

    Winding to Winding Fault

  • 8/8/2019 Basic Relaying

    22/352

    Transformer Protection Relay Set 1 and 2 are high speed current differential schemes isolates

    the faulted transformer. Approximately 2 cycle clearance (33milliseconds)

    KBCH digital Current Differential relays for RS1.

    T60 GE microprocessor Current Differential for RS2

    Also uses Backup Overcurrent Protection in RS2

    XFMR

    FAULT

    SWGR

    Differential relay

    10

    507

    509

    Transformer Damage Curve

    Test Question # 19:

    Transformer damaged in 50seconds at 20,000 Amps

  • 8/8/2019 Basic Relaying

    23/352

    Transformer Differential Relay

    General Electric

    T60 UR Differential

    relay

    Primary Current Flow

    Normal Operation

  • 8/8/2019 Basic Relaying

    24/352

    Fault Current Flow

    Fault Condition

    Transformer Protection

    OUC uses a high speed current differentialscheme that isolates faulted substationtransformers in approximately 2 cyclesclearance (.033 seconds)

    FAULT

    Differential relay

    10

    507

    509

    150,000 volt

    Breaker

    13,000 volt

    Breaker

    150,000 volt

    Breaker

    To customersswitchgear

    transformer

  • 8/8/2019 Basic Relaying

    25/35

  • 8/8/2019 Basic Relaying

    26/352

    TRANSMISSION LINE

    PROTECTION

    Arrestor Failure

    Types of Transmission Line Faults :

    Test Question # 22

    Two Phase to Ground

    Three Phase to Ground

    Phase to Phase

    Phase to Phase to Phase

    Single Phase to Ground

    Through Fault

  • 8/8/2019 Basic Relaying

    27/352

    Transmission Line Protection

    Relay Set 1 is high speed current differential schemes isolates

    the faulted segment of a transmission line. Approximately 2 cycleclearance (33 milliseconds)

    L90 digital Current Differential relays used by OUC.

    Also uses Direct Transfer Trip for Breaker Failure

    L90

    FAULT

    L90Fiber communication

    501

    503

    507

    509

    Transmission Line Protection OUC uses high speed current differential

    schemes that isolates the faulted segmentof a transmission line in approximately 2cycles clearance (.033 seconds).

    FAULT

    Fiber communication

    501

    503

    507

    509

    The relays communicate over the OUC fiberOptic Network

    Transmission BreakerTransmission Breaker

    Transmission BreakerTransmission Breaker

    Transmission Line

    Protective Relay Protective Relay

  • 8/8/2019 Basic Relaying

    28/352

    Transmission Line Protection Relay Set 2 is high speed directional impedance relay that isolates the

    faulted segment of a transmission line using Permissive OvereachTransfer Trip

    P442

    FAULT

    P442Zone 1 95 % of line

    501

    503

    507

    509

    T1T1

    Zone 2 125 % of line

    Test Question # 23:

    Zone 1 set at 95% of transmission line

    Zone 2 set at 125% of transmission line

    Directional distance relay

    Substation

    Remote Substation

    Length of Line = 10. 7 miles

    Line Impedance Positive sequence - .20 + j 1.11Zero sequence - 1.97 + j 3.55

  • 8/8/2019 Basic Relaying

    29/352

    Under Load Conditions no Tripoutside of zone.

    During fault, impedance moves into trip zone

    For short transmission lines we use Reactance Relays that operate

    at 90 degrees between voltage and current.

  • 8/8/2019 Basic Relaying

    30/353

    Line Current Differential Relay

    General Electric L90 UR Relay

    Line Current Differential Relay

  • 8/8/2019 Basic Relaying

    31/353

    Line Current Differential Relay Trip Conditions

    Fault

  • 8/8/2019 Basic Relaying

    32/353

    Description of Substation Automation

    REMOTE TERMINALUNITS

    RELAYS

    ENERGYMANAGEMENT

    SYSTEM

    OUC

    INTRANET

    REMOTE TERMINALUNITS

    RELAYS

    PROGRAMMABLELOGIC

    CONTROLLERS

    MODEM

    LINE

    PERSHING OPERATION S CONTROL CENTER

    CORPORATEUSER

    OUC

    CUSTOMER

    INTERNET

    Firewall

    CORPORATE NETWORK

    SUBSTATION

    SUBSTATIONAUTOMATION

    SYSTEM

    REMOTE(EMERGENCY)

    CONTROL ROOM

    MODEMLINE

    BACKUP ENERGYMANAGEMENT

    SYSTEM

    ENERGYMANAGEMENT

    SYSTEM

    FUTURESYSTEMS

    Firewall

    TRANSMISSION

    SYSTEM

    WIDE AREA NETWORK

    (ALL SUBSTATIONS)

    Comparison of Electro-Mechanical to Microprocessor-Based Protective

    Relays

  • 8/8/2019 Basic Relaying

    33/353

    Lower Cost

    Easier to Test

    Advantages of Electromechanical

    Disadvantages of Electromechanical

    Need three individual relays

    Maintain more often

    Moving Parts

    Usually performs only one protective function

    Slower operating than Micro-Processor Based

    Test Question # 24:

    Performs hundreds of protective functions

    Only one relay needed for all phases

    Advantages of Micro-Processor Based

    Disadvantages Micro-Processor Based

    Higher Cost

    Complex training for testing

    Faster operating than Electromechanical

    Self-Monitoring

    Takes up less space

    Longer maintenance cycle

    Test Question # 25:

  • 8/8/2019 Basic Relaying

    34/353

    How a Micro-Processor Based Relay works.

    It takes an analog signal from PTs and CTs and convertsit into digital data for analysis.

    Test Question # 26:

    How a Micro-Processor Based Relay works.

    Analog data under Sine Wave isconverted to digital data andanalyzed by the processor

  • 8/8/2019 Basic Relaying

    35/35

    How a Micro-Processor Based Relay works.

    Analog dataConverted into Digital samples

    The microprocessor in the relay analyzes millions of bitsof data per second and determines if the amplitude issufficient to trip. All in 18 milliseconds or less.

    Customer Feeder Protection

    FAULT

    Main relay

    1011

    Feeder relay

    501

    503

    13,000 volt

    Breaker

    150,000 volt

    Breaker

    150,000 volt

    Breaker

    13,000 volt

    Breaker

    transformer

    switchgear

    OUC uses a high speed microprocessor feederrelay that isolates faulted customer feeder inapproximately 3 cycles clearance (.050 seconds)