basic relaying
TRANSCRIPT
-
8/8/2019 Basic Relaying
1/35
Florida Reliability Coordinating Council
Relay ClassRelay Class
John White
System Protection Manager
Ray Dawson
System Protection Technician
Introduction The reasons for protection
Safety of the public and employees.
Reliability of power supply to thecustomers.
Prevent damage to equipment.
What kind of equipment isprotected: generators, transformers,
transmission lines, breakers anddistribution lines.
-
8/8/2019 Basic Relaying
2/35
Types of faults
Three phase, three phase to ground,phase to phase, phase to phase to groundand single phase to ground.
Three phase faults have the highest faultcurrent.
Single phase faults have the lowest faultcurrent.
The fault current is determined by theimpedance of the fault path.
Fault paths closer to the source will have
less impedance. Faults caused by trees will have higherimpedance.
Equipment used CT current transformer
PT potential transformer
Transducers
Time overcurrent relay/51
Instantaneous Over current relay/50
Undervoltage relay/27
Recloser relay/79 Under frequency relay/81
-
8/8/2019 Basic Relaying
3/35
CT current transformer The secondary winding has a standard
rating of 5 amp. Its indicated as 400/200/5the 400 and 200 are the primary currentwhich gives us an 80 to 1 and 40 to 1 ratiorespectably.
It is important that CTs be accurate at faultlevels which may be 10 times normal loadcurrent. Standard classifications of CTsallow 10% error for current flow up to 20times rated value. They are marked ClassC ###. The higher the number the highercurrent that can flow though the CT and
still be 10% accurate. Never open a live CT circuit without firstshorting the secondary side. Without thesecondary side shorted very high voltagewill be seen on the secondary circuit.
Potential Transformers PTs The secondary voltage is usually
69V for relaying and 120V formetering.
There is no problem with errorreadings as during a fault thevoltage will drop.
At above 115KV coupling capacitorsare used. This is called CCVT. Theyare connected in series causing a
voltage drop across each cap. PTs should never be shorted.
-
8/8/2019 Basic Relaying
4/35
Transducers Measure voltages and currents and
converts them to a 0 to 1 milliamp dcoutput.
A scaling is used in SCADA(supervisory control and dataacquisition) to convert the milliampsignal to a numerical number.
Time Over current relay/51
Operate on the electromagnetic inductionprinciple. The protective relay isessentially a small AC motor. Usingshaded pole produce two fluxes that are atdifferent phase angles.
When current is passed through theelectromagnet coil,a magnetic field isproduced, which applies a torque to thedisc. When the magnetic field becomesstrong enough to overcome friction in the
damping magnet, bearing and tension inthe spiral spring, the disc rotates to movethe moving contact. Eventually the movingand fixed contacts close, completing thetrip coil circuit to the breaker.
-
8/8/2019 Basic Relaying
5/35
Time Over current relay/51 The disc rotates at a speed directly
proportional to the amount of fluxinduced into it by the electromagnet.
The time dial provides adjustment forhow long it takes the moving contact andstationary contact to make contact. Witha higher number on the time dial, thisincreases traveling distance and contacttime.
The spiral spring is use to set minimumpickup, resets the disc in normal
conditions or after a trip and provides atemporary path for the DC trip current.The spiral spring is not designed to carrythe trip current for very long. A seal-inbypass is used.
-
8/8/2019 Basic Relaying
6/35
Time Over current relay/51 The seal in coil is in series with the
contacts on the spiral spring. Theseal in coil contacts are in parallelwith the spiral spring contacts. Theseal in contacts shunt the currentaway from the spiral spring contacts.
The seal in coil also has a flag that
drops to indicate which relay had theovercurrent condition.
-
8/8/2019 Basic Relaying
7/35
Instantaneous Over current relays/50 Instantaneous relays have no time
delay. With a high level fault theinstantaneous unit will operatebefore time overcurrent relay.
Its a simple clapper relay with acore screw on top to adjust thepickup range.
The contacts are two moving contacton a bridge and two stationarycontacts. The contacts are directlyacross the trip circuit for thebreaker.
Undervoltage relays/27 The construction of a undervoltage relay
is very similar to an overcurrent relay. Themain different is the operating coil. Anovercurrent relays operating coil iswound with a few turns of heavy wire. Avoltage relays operating coil is woundwith many turns of fine wire.
The disc rotates in the counterclockwisedirection.
The contact closing torque for an
undervoltage relay is provided by thetension in the spiral spring. A time delay is the same as for an over
current relay.
-
8/8/2019 Basic Relaying
8/35
DEVICES USED AT OUC 21 Distance relay
25 Synchronizing-check device 27 Undervoltage relay 43 Manual transfer or selector device 50 Instantaneous overcurrent relay 51 Time overcurrent relay 52 AC circuit breaker 57 Grounding device 59 Overvoltage relay 63 Gas pressure relay 64 Ground protective relay 67 AC directional overcurrent relay 69 Permissive control device 74 Alarm relay 79 Reclosing relay 81 Frequency relay 86 Locking-out relay 87 Differential protective relay
The right man for the job
Mr. Bill Douglas
-
8/8/2019 Basic Relaying
9/35
OUC SYSTEM
OUC Protective Relay Statistics
60 Transmission Lines
4000 Protective Relays
36 Substations
14 Generators
400 Breakers 200 Transformers
200 Feeder Breakers
-
8/8/2019 Basic Relaying
10/35
OUC Protective Relaymain schemes
Protects Transmission Lines
Protects Distribution Lines
Protects Transformers
Protects Generators
Protects Busses Protects Reactors
-
8/8/2019 Basic Relaying
11/35
Stanton Substation
-
8/8/2019 Basic Relaying
12/35
S**t Happens
-
8/8/2019 Basic Relaying
13/35
-
8/8/2019 Basic Relaying
14/35
FAULTCHARACTERISTICS
Two Phase to Ground
Three Phase to Ground
Phase to Phase
Phase to Phase to Phase
Single Phase to Ground
TYPES of FAULTS :
Test Question # 11
Impedance Diagram
Voltage= 22800 volts Load Z (one leg)= 70 ohms I= 300 amps
FAULT
Test Question # 12: 22800 volts / 3 ohms of fault impedance= 7600 amps.
-
8/8/2019 Basic Relaying
15/35
Ground current possibly damages generator before 50 G relay
operates.
Ground Fault Current circulates from the load to the generator
stator unimpeded.
-
8/8/2019 Basic Relaying
16/35
Resistance, Reactance, ImpedanceResistance, Reactance, Impedance
ResistanceResistance--(R)(R) The opposition to the flow ofThe opposition to the flow of
current in an electrical circuitcurrent in an electrical circuit..
ReactanceReactance--(X)(X) A measure of opposition to aA measure of opposition to asinusoidal current made up of Capacitance and inductancesinusoidal current made up of Capacitance and inductance
ImpedanceImpedance-- (Z)(Z)Combination of Resistance andCombination of Resistance andReactance that opposes flow of current.Reactance that opposes flow of current.
Test Question # 13Test Question # 13
Test Question #14: Reactor/Resistor limits fault currentto about 10 amps preventing damage to stator.
-
8/8/2019 Basic Relaying
17/35
Utility standard of Delta Wye configuration for GSU
transformer prevents fault current from circulating through
stator.
GSU boosts voltage for ease of transmission- 20kV to230kV.
During fault Voltage A-n collapses and Current A-n increases dramatically.
Voltages and Currents are 120 degrees between phases.
-
8/8/2019 Basic Relaying
18/35
Disturbance recording
File: J:\System Protection\Faults and oscillographys\SECA 6,20,03\SECA,6,20,03.
VA
VB
VC
IA
IB
IC
R1 Trip Brkr 757
R2 Trip Brkr 759
R3 SCADA RS1 Op
R6 757 RI N/A
R7 759 RI N/A
R9 757 BF Init
Part of System Protections
responsibilities is to analyze faultdata acquired from the
microprocessor based protective
relays such as the examplesshown.
Generator Protection
507
509
150,000 volt
Breaker
OUC uses high speed generator schemes that isolates the fault inthe Generator in approximately 2 cycles clearance (.033seconds).
150,000 volt
Breaker
FAULT
Generator GSU
Transformer
To OUC
system
Generator Relay
-
8/8/2019 Basic Relaying
19/35
GENERATORPROTECTION
Rotor Ground
Excitation Failure
Over-voltage/ Over-excitation
Turbine Trip
Motoring by loss of Prime Mover
TYPES of Generator Faults :
Test Question # 15
Stator Fault
87G- Generator
Differential
87T- GSU Transformer
Differential
87ST- Reserve
Auxiliary Differential.
-
8/8/2019 Basic Relaying
20/352
40- Loss of Field Relay
81- Under frequency
Relay59-Under Voltage
Relay.With loss of field condition, Generator cannot
produce VARS, lowering terminal voltage and
overheating of the stator.
Test Question #16:
VAR= Volt Ampere
Reactive
46- Negative Sequence
Relay
-
8/8/2019 Basic Relaying
21/352
59G- Generator GroundRelay
27G- Third harmonicsupervision Relay
Test Question #
17:
Third Harmonic is
at 180 HZ
TRANSFORMER
PROTECTION
Core Movement
Bushing Failure
Arrestor Failure
Through Fault
Winding to Ground Fault
Types of Transformer Faults :
Test Question # 18
Winding to Winding Fault
-
8/8/2019 Basic Relaying
22/352
Transformer Protection Relay Set 1 and 2 are high speed current differential schemes isolates
the faulted transformer. Approximately 2 cycle clearance (33milliseconds)
KBCH digital Current Differential relays for RS1.
T60 GE microprocessor Current Differential for RS2
Also uses Backup Overcurrent Protection in RS2
XFMR
FAULT
SWGR
Differential relay
10
507
509
Transformer Damage Curve
Test Question # 19:
Transformer damaged in 50seconds at 20,000 Amps
-
8/8/2019 Basic Relaying
23/352
Transformer Differential Relay
General Electric
T60 UR Differential
relay
Primary Current Flow
Normal Operation
-
8/8/2019 Basic Relaying
24/352
Fault Current Flow
Fault Condition
Transformer Protection
OUC uses a high speed current differentialscheme that isolates faulted substationtransformers in approximately 2 cyclesclearance (.033 seconds)
FAULT
Differential relay
10
507
509
150,000 volt
Breaker
13,000 volt
Breaker
150,000 volt
Breaker
To customersswitchgear
transformer
-
8/8/2019 Basic Relaying
25/35
-
8/8/2019 Basic Relaying
26/352
TRANSMISSION LINE
PROTECTION
Arrestor Failure
Types of Transmission Line Faults :
Test Question # 22
Two Phase to Ground
Three Phase to Ground
Phase to Phase
Phase to Phase to Phase
Single Phase to Ground
Through Fault
-
8/8/2019 Basic Relaying
27/352
Transmission Line Protection
Relay Set 1 is high speed current differential schemes isolates
the faulted segment of a transmission line. Approximately 2 cycleclearance (33 milliseconds)
L90 digital Current Differential relays used by OUC.
Also uses Direct Transfer Trip for Breaker Failure
L90
FAULT
L90Fiber communication
501
503
507
509
Transmission Line Protection OUC uses high speed current differential
schemes that isolates the faulted segmentof a transmission line in approximately 2cycles clearance (.033 seconds).
FAULT
Fiber communication
501
503
507
509
The relays communicate over the OUC fiberOptic Network
Transmission BreakerTransmission Breaker
Transmission BreakerTransmission Breaker
Transmission Line
Protective Relay Protective Relay
-
8/8/2019 Basic Relaying
28/352
Transmission Line Protection Relay Set 2 is high speed directional impedance relay that isolates the
faulted segment of a transmission line using Permissive OvereachTransfer Trip
P442
FAULT
P442Zone 1 95 % of line
501
503
507
509
T1T1
Zone 2 125 % of line
Test Question # 23:
Zone 1 set at 95% of transmission line
Zone 2 set at 125% of transmission line
Directional distance relay
Substation
Remote Substation
Length of Line = 10. 7 miles
Line Impedance Positive sequence - .20 + j 1.11Zero sequence - 1.97 + j 3.55
-
8/8/2019 Basic Relaying
29/352
Under Load Conditions no Tripoutside of zone.
During fault, impedance moves into trip zone
For short transmission lines we use Reactance Relays that operate
at 90 degrees between voltage and current.
-
8/8/2019 Basic Relaying
30/353
Line Current Differential Relay
General Electric L90 UR Relay
Line Current Differential Relay
-
8/8/2019 Basic Relaying
31/353
Line Current Differential Relay Trip Conditions
Fault
-
8/8/2019 Basic Relaying
32/353
Description of Substation Automation
REMOTE TERMINALUNITS
RELAYS
ENERGYMANAGEMENT
SYSTEM
OUC
INTRANET
REMOTE TERMINALUNITS
RELAYS
PROGRAMMABLELOGIC
CONTROLLERS
MODEM
LINE
PERSHING OPERATION S CONTROL CENTER
CORPORATEUSER
OUC
CUSTOMER
INTERNET
Firewall
CORPORATE NETWORK
SUBSTATION
SUBSTATIONAUTOMATION
SYSTEM
REMOTE(EMERGENCY)
CONTROL ROOM
MODEMLINE
BACKUP ENERGYMANAGEMENT
SYSTEM
ENERGYMANAGEMENT
SYSTEM
FUTURESYSTEMS
Firewall
TRANSMISSION
SYSTEM
WIDE AREA NETWORK
(ALL SUBSTATIONS)
Comparison of Electro-Mechanical to Microprocessor-Based Protective
Relays
-
8/8/2019 Basic Relaying
33/353
Lower Cost
Easier to Test
Advantages of Electromechanical
Disadvantages of Electromechanical
Need three individual relays
Maintain more often
Moving Parts
Usually performs only one protective function
Slower operating than Micro-Processor Based
Test Question # 24:
Performs hundreds of protective functions
Only one relay needed for all phases
Advantages of Micro-Processor Based
Disadvantages Micro-Processor Based
Higher Cost
Complex training for testing
Faster operating than Electromechanical
Self-Monitoring
Takes up less space
Longer maintenance cycle
Test Question # 25:
-
8/8/2019 Basic Relaying
34/353
How a Micro-Processor Based Relay works.
It takes an analog signal from PTs and CTs and convertsit into digital data for analysis.
Test Question # 26:
How a Micro-Processor Based Relay works.
Analog data under Sine Wave isconverted to digital data andanalyzed by the processor
-
8/8/2019 Basic Relaying
35/35
How a Micro-Processor Based Relay works.
Analog dataConverted into Digital samples
The microprocessor in the relay analyzes millions of bitsof data per second and determines if the amplitude issufficient to trip. All in 18 milliseconds or less.
Customer Feeder Protection
FAULT
Main relay
1011
Feeder relay
501
503
13,000 volt
Breaker
150,000 volt
Breaker
150,000 volt
Breaker
13,000 volt
Breaker
transformer
switchgear
OUC uses a high speed microprocessor feederrelay that isolates faulted customer feeder inapproximately 3 cycles clearance (.050 seconds)