R TECHNICAL INFORMATION 314 [email protected] SOUTH EAST Erith (Head Office) Tel: 01322 441165 Fax: 01322 440492 SOUTH WEST Bristol Tel: 0117 966 6333 Fax: 0117 953 3602 MIDLANDS Birmingham Tel: 0121 313 2870 Fax: 0121 313 3415 NORTH Leeds Tel: 0113 2533565 Fax: 0113 253 6373 EASTERN Peterborough Tel: 01733 558485 Fax: 01733 562015 NORTH WEST Manchester Tel: 01204 793111 Fax: 01204 797977 WALES Cardiff Tel: 02920 450044 Fax: 02920 464724 General Information Minimum Internal Radii of bends for cables subject to flexing and of bends in cables for fixed wiring - low voltage MINIMUM INTERNAL RADIUS OF BEND (TIME OVERALL DIAMETER OF CABLE) OVERALL DIAMETER FINISH INSULATION Minimum internal radii of bends for flexible cables and flexible cords in a fixed situation. Minimum internal radii of bends for flexible cables and flexible cords and subject of flexing. Minimum internal radii of bends in cables for fixed wiring Not exceeding 10mm Exceeding 10mm but not exceeding 25mm Exceeding 25mm Not exceeding 25mm Exceeding 25mm Not exceeding 25mm Exceeding 25mm Not exceeding 10mm Exceeding 10mm but not exceeding 25mm Exceeding 25mm Any Not exceeding 12.5mm Exceeding 12.5mm but not exceeding 20mm Exceeding 20mm but not exceeding 30mm Exceeding 30mm but not exceeding 50mm Exceeding 50mm Any Not exceeding 30mm Exceeding 30mm but not exceeding 50mm Exceeding 50mm Any 2 3 4 6 8 8 10 3 4* 6* 6* 8† 10† 12† 15† 18† 12 12† 15† 18† 6 Non-metallic sheath and / or textile braid Non-metallic sheath and / or textile braid Non-metallic sheath with textile reinforcement screen or flexible armour ‡ Non-armoured (excluding smooth aluminium sheath) Armoured (excluding smooth aluminium sheath) Smooth aluminium sheath with or without armour Lead or corrugated aluminium sheath with or without armour Smooth aluminium sheath with or without armour Copper sheath with or without PVC covering Rubber, PVC or XLPE Rubber, PVC or XLPE Rubber , PVC or XLPE Impregnated paper Mineral At temperatures approaching 0°C, standard grade PVC becomes rigid and brittle, therefore, care should be taken when bending cables at low temperature. * For circular conductors only. For shaped conductors, the minimum bending radius factor is 8. Otherwise this table applies to both circular and shaped conductors. †The factors applied are applied to the diameter over the aluminium sheath. ‡Armoured flexible cables are suitable for use over reels or pulleys only when the movements are slow and intermittent.

Upload: baskaranjay5502

Post on 14-Jul-2016

215 views

Category:

Documents


2 download

DESCRIPTION

cable data

TRANSCRIPT

Page 1: bendingradii_1227548493

R

TECH

NIC

AL

INFO

RM

ATION

[email protected]

SOUTH EASTErith (Head Office)

Tel: 01322 441165Fax: 01322 440492

SOUTH WESTBristol

Tel: 0117 966 6333Fax: 0117 953 3602

MIDLANDSBirmingham

Tel: 0121 313 2870Fax: 0121 313 3415

NORTHLeeds

Tel: 0113 2533565Fax: 0113 253 6373

EASTERNPeterborough

Tel : 01733 558485Fax: 01733 56 2 0 1 5

NORTH WESTManchester

Tel: 01204 793111Fax: 01204 797977

WALESCardiff

Tel: 02920 450044Fax: 02920 464724

General Information

Minimum Internal Radii of bends for cables subject to flexing and of bends in cables for fixed wiring - low voltage

MINIMUM INTERNALRADIUS OF BEND(TIME OVERALL

DIAMETER OF CABLE)

OVERALL DIAMETERFINISHINSULATION

Minimum internal radii ofbends for flexible cablesand flexible cords in a fixedsituation.

Minimum internal radii ofbends for flexible cablesand flexible cords and subject of flexing.

Minimum internal radii ofbends in cables for fixed wiring

Not exceeding 10mm

Exceeding 10mm but notexceeding 25mm

Exceeding 25mm

Not exceeding 25mm

Exceeding 25mm

Not exceeding 25mm

Exceeding 25mm

Not exceeding 10mm

Exceeding 10mm but notexceeding 25mm

Exceeding 25mm

Any

Not exceeding 12.5mm

Exceeding 12.5mm but notexceeding 20mm

Exceeding 20mm but notexceeding 30mm

Exceeding 30mm but notexceeding 50mm

Exceeding 50mm

Any

Not exceeding 30mm

Exceeding 30mm but not exceeding 50mm

Exceeding 50mm

Any

2

3

4

6

8

8

10

3

4*

6*

6*

8†

10†

12†

15†

18†

12

12†

15†

18†

6

Non-metallic sheath and / ortextile braid

Non-metallic sheath and / ortextile braid

Non-metallic sheath withtextile reinforcement screenor flexible armour ‡

Non-armoured(excluding smooth aluminiumsheath)

Armoured (excluding smooth aluminium sheath)

Smooth aluminium sheathwith or without armour

Lead or corrugatedaluminium sheath with orwithout armour

Smooth aluminium sheathwith or without armour

Copper sheath with orwithout PVC covering

Rubber, PVC or XLPE

Rubber, PVC or XLPE

Rubber , PVC or XLPE

Impregnated paper

Mineral

At temperatures approaching 0°C, standard grade PVC becomes rigid and brittle, therefore, care should be taken when bending cables at low temperature.

* For circular conductors only. For shaped conductors, the minimum bending radius factor is 8. Otherwise this table applies to bothcircular and shaped conductors.

†The factors applied are applied to the diameter over the aluminium sheath.‡Armoured flexible cables are suitable for use over reels or pulleys only when the movements are slow and intermittent.