Minimum Internal Radii of bends for cables subject to flexing and of bends in cables for fixed wiring - low voltage

MINIMUM INTERNALRADIUS OF BEND(TIME OVERALL

DIAMETER OF CABLE)

OVERALL DIAMETERFINISHINSULATION

Minimum internal radii ofbends for flexible cablesand flexible cords in a fixedsituation.

Minimum internal radii ofbends for flexible cablesand flexible cords and subject of flexing.

Minimum internal radii ofbends in cables for fixed wiring

Not exceeding 10mm

Exceeding 10mm but notexceeding 25mm

Exceeding 25mm

Not exceeding 25mm

Exceeding 25mm

Not exceeding 25mm

Exceeding 25mm

Not exceeding 10mm

Exceeding 10mm but notexceeding 25mm

Exceeding 25mm

Any

Not exceeding 12.5mm

Exceeding 12.5mm but notexceeding 20mm

Exceeding 20mm but notexceeding 30mm

Exceeding 30mm but notexceeding 50mm

Exceeding 50mm

Any

Not exceeding 30mm

Exceeding 30mm but not exceeding 50mm

Exceeding 50mm

Any

2

3

4

6

8

8

10

3

4*

6*

6*

8†

10†

12†

15†

18†

12

12†

15†

18†

6

Non-metallic sheath and / ortextile braid

Non-metallic sheath and / ortextile braid

Non-metallic sheath withtextile reinforcement screenor flexible armour ‡

Non-armoured(excluding smooth aluminiumsheath)

Armoured (excluding smooth aluminium sheath)

Smooth aluminium sheathwith or without armour

Lead or corrugatedaluminium sheath with orwithout armour

Smooth aluminium sheathwith or without armour

Copper sheath with orwithout PVC covering

Rubber, PVC or XLPE

Rubber, PVC or XLPE

Rubber , PVC or XLPE

Impregnated paper

Mineral

At temperatures approaching 0°C, standard grade PVC becomes rigid and brittle, therefore, care should be taken when bending cables at low temperature.

* For circular conductors only. For shaped conductors, the minimum bending radius factor is 8. Otherwise this table applies to bothcircular and shaped conductors.

†The factors applied are applied to the diameter over the aluminium sheath.‡Armoured flexible cables are suitable for use over reels or pulleys only when the movements are slow and intermittent.