ANALYSIS AND IMPROVEMENT OF POWER FACTOR AT BOSCH SHOP FLOOR BY
INSTALLING CAPACITOR BANK
BY External Guide
Lingaraju.Ky(Sptd.Eng)
P.Sreelekha Internal Guide
Akash Roy A.M.Leela(Asct.Professor)
Sunith Kumar.A
![Page 2: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/2.jpg)
SCOPE
Introduction to Problem Definition.Possible Solutions & Remedy Chosen. Present Situation & Conclusion.
![Page 3: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/3.jpg)
Terminologies Power Triangle
![Page 4: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/4.jpg)
Terminologies
Power Factor:
Cosine of the angle between the voltage & the current.
Types of Power Factor:• Unity• Lagging• Leading
![Page 5: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/5.jpg)
Causes for Low Power Factor
Most A.C motors are of induction type having low lagging power factor.
Magnetizing current drawn by transformers lead to lagging current at low loads(specially during morning & evening).
Typical characteristics of Arc lamp in Cinema Induction furnace ,Short transmission lines.
Current limiting reactors used to minimize fault currents work at low power factor.
![Page 6: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/6.jpg)
Disadvantages of Low Power Factor
Large KVA rating of equipment .Greater conductor size .Large copper losses .Poor voltage regulation .Reduced handling capacity of system.Unnecessary penalty is imposed (during
billing).
![Page 7: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/7.jpg)
Different PF Correction Methods Available
Reduce the amount of reactive energy.Compensate artificially for the consumption
of reactive energy. ROTARY EQUIPMENT STATIC CAPACITORS
![Page 8: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/8.jpg)
Remedy Chosen
STATIC CAPACITORS
![Page 9: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/9.jpg)
Specification of the Capacitors
![Page 10: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/10.jpg)
Specification of the Capacitors
![Page 11: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/11.jpg)
Capacitors
![Page 12: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/12.jpg)
Advantages Of Capacitors Over Other Method(s)
Capacitor banks ensures very low initial cost.
The running costs are minimal and they can be used with the same high efficiency on all sizes of installation.
Compact, reliable, highly efficient & convenient to install .
![Page 13: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/13.jpg)
Present Situation At BOSCH
![Page 14: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/14.jpg)
Present Situation At BOSCH
![Page 15: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/15.jpg)
Procedure Followed• Calculations
![Page 16: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/16.jpg)
Procedure Followed
![Page 17: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/17.jpg)
Procedure Followed
![Page 18: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/18.jpg)
Procurement List
![Page 19: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/19.jpg)
Procurement List
![Page 20: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/20.jpg)
Brief Installation List
,
![Page 21: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/21.jpg)
Brief Installation List
,
![Page 22: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/22.jpg)
Savings in Power
• Resistance of the cable 0.15ohm / km load ; Length= 175mt.• Resistance of the cable = 0.15 *0.175km = 0.026 ohm.
• P= √3 *VL*IL* Cos Φ1
• Current drawn by the load at 0.763 P.F , IL1= P/ (√3 *VL*Cos Φ1 )
=171.83/( √3 *430.52*0.763)
=302.009A.
• PF after correction Cos Φ2 = 0.96
• Current drawn by the load at 0.96 P.F , IL2 = P/ ( √3 *VL*Cos Φ2 )
= 171.83/( √3*430.52*0.96)
= 240.03A.
![Page 23: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/23.jpg)
Savings in Power
• Power loss P1= 3*I12R = 7.114KW
• Power loss P2= 3*I22R = 4.493KW
• Saving in power = 7.114KW – 4.493KW = 2.621KW.• Time= 18Hours * 25 Days = 450.• KWh loss in P1 = 3201.3KWh.• KWh loss in P2 = 2021.85KWh.• Reduction in KWh (units) = 1179.45• Cost saving = 1179.45 *12 months * Rs. 6/-unit =
RS.84920.4
![Page 24: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/24.jpg)
Installation Work
![Page 25: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/25.jpg)
Single Line Diagram
![Page 26: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/26.jpg)
Installation Work
Monday
Tuesday
Wedesd
ay
Thursday
Friday
Satu
rday
Sunday
0
0.2
0.4
0.6
0.8
1
1.2
0.57 0.54 0.54 0.6 0.550.67
0.575
0.94 0.93 0.93 0.96 0.90.98 0.93
Feeder 307
BeforeAfter
![Page 27: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/27.jpg)
Installation Work
Monday
Tuesday
Wednesd
ay
Thursday
Friday
Satu
rday
Sunday
00.10.20.30.40.50.60.70.80.9
1
0.6820.7070000000000
010.673000000000002
0.7070000000000010.698 0.6670000000000
020.6680000000000
02
0.90.9500000000000
010.90.9500000000000
010.92 0.92 0.92
Feeder 504
BeforeAfter
![Page 28: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/28.jpg)
,
106 307 312 402 501 415 504 505 5110
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
0.650.57
0.8090.73
0.82 0.86
0.70.78 0.736
0.320.37
0.120.22
0.1 0.050.23 0.1 0.174
Previous Improvement
![Page 29: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/29.jpg)
ALGORITHM • Identify the feeder to be worked based on the
difference of power factor• p= Power in KW• a= Power factor(current) • b= Target power factor • Find out the Reactive power Compensation required
for achieving target power factor• Compare the current and targeted P.F• Improvement done is displayed
Simulation using MATLAB
![Page 30: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/30.jpg)
FLOW CHART
![Page 31: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/31.jpg)
FLOW CHART
![Page 32: Bosch Project](https://reader036.vdocuments.net/reader036/viewer/2022081501/55d2f863bb61eb781b8b4716/html5/thumbnails/32.jpg)
CONCLUSION
• Improved the power factor from the range of 0.65-0.85 to an existing range of 0.95-0.99 effectively.
• Significant decline in the rating of current flow & reduced I2R losses also leading to reduced stress on the cable there by increased durability of the cable.
• Finally reduced on the KVA demand there by reducing the penalty imposed ,also the total KWh consumption as a whole has been reduced. Thus
creating savings of 27.5lakhs p.a