Product Catalogue PVC Insulated Cables BDS-900 and BS-6004 Type: BYA Specification: BDS-900 and BS-6004 Voltage: 450/750 volts 1. Copper Cond ucto r 2. PVC Insulation Nominal Cross Sectional Area of Conductor No. and Nominal Diameter of Wires Maximum Resistance of Conductor at 20 o  C Nominal Thicknes s of Insulation Approx Overall Diameter Approx Weight of Cable Current Rating Bunched and Enclosed in Conduits Two Cables Single Phase at 35 o C Clipped to a Surface or on a Cable Tray Bunched & Unenclosed 2 Cables Single Phase at 35 o C mm 2 no./mm ohm/km mm mm kg/km amp amp 1.0 re 1/1.13 18.1 0.7 2.8 17 13 16 1.5 re 1/1.38 12.1 0.7 3.3 22 16 20 1.5 rm 7/0.52 12.1 0.7 3.5 23 16 20 2.5 re 1/1.78 7.41 0.8 3.9 35 22 28 2.5 rm 7/0.67 7.41 0.8 4.2 36 22 28 4.0 rm 7/0.85 4.61 0.8 4.8 55 30 37 6.0 rm 7/1.05 3.08 0.8 5.4 75 38 47 10 rm 7/1.35 1.83 1.0 6.8 115 52 63 16 rm 7/1.71 1.15 1.0 8.0 178 70 85 16 rm 19/1.04 1.15 1.0 8.1 180 70 85 25 rm 7/2.14 0.727 1.2 9.8 275 91 110 25 rm 19/1.30 0.727 1.2 9.9 280 91 110 35 rm 19/1.53 0.524 1.2 11.0 375 112 136 50 rm 19/1.83 0.387 1.4 13.0 530 136 164 70 rm 19/2.17 0.268 1.4 15.0 720 173 207 95 rm 19/2.52 0.193 1.6 17.0 1000 216 253 120 rm 37/2.03 0.153 1.6 19.0 1225 244 291 150 rm 37/2.27 0.124 1.8 21.0 1530 - 333 185 rm 37/2.52 0.0991 2.0 23.5 1890 - 381 240 rm 61/2.25 0.0754 2.2 26.5 2450 - 452 300 rm 61/2.52 0.0601 2.4 29.5 3060 - 526 400 rm 61/2.89 0.0470 2.6 33.5 4050 - 639 500 rm 61/3.23 0.0366 2.8 37.0 5000 - 752 630 rm 127/2.52 0.0283 2.8 41.0 6350 - 855

Upload: morsed-al-mamun

Post on 11-Oct-2015

184 views

Category:

Documents


6 download

DESCRIPTION

Brb Cables Pvc

TRANSCRIPT

  • Product CataloguePVC Insulated Cables

    BDS-900 and BS-6004

    Type: BYASpecification: BDS-900 and BS-6004Voltage: 450/750 volts

    1. Copper Conductor

    2. PVC Insulation

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current Rating

    Bunched andEnclosed inConduits TwoCables SinglePhase at35oC

    Clipped to aSurface or ona Cable TrayBunched &Unenclosed 2Cables SinglePhase at 35oC

    mm2 no./mm ohm/km mm mm kg/km amp amp1.0 re 1/1.13 18.1 0.7 2.8 17 13 161.5 re 1/1.38 12.1 0.7 3.3 22 16 201.5 rm 7/0.52 12.1 0.7 3.5 23 16 202.5 re 1/1.78 7.41 0.8 3.9 35 22 282.5 rm 7/0.67 7.41 0.8 4.2 36 22 284.0 rm 7/0.85 4.61 0.8 4.8 55 30 376.0 rm 7/1.05 3.08 0.8 5.4 75 38 4710 rm 7/1.35 1.83 1.0 6.8 115 52 6316 rm 7/1.71 1.15 1.0 8.0 178 70 8516 rm 19/1.04 1.15 1.0 8.1 180 70 8525 rm 7/2.14 0.727 1.2 9.8 275 91 11025 rm 19/1.30 0.727 1.2 9.9 280 91 11035 rm 19/1.53 0.524 1.2 11.0 375 112 13650 rm 19/1.83 0.387 1.4 13.0 530 136 16470 rm 19/2.17 0.268 1.4 15.0 720 173 20795 rm 19/2.52 0.193 1.6 17.0 1000 216 253120 rm 37/2.03 0.153 1.6 19.0 1225 244 291150 rm 37/2.27 0.124 1.8 21.0 1530 - 333185 rm 37/2.52 0.0991 2.0 23.5 1890 - 381240 rm 61/2.25 0.0754 2.2 26.5 2450 - 452300 rm 61/2.52 0.0601 2.4 29.5 3060 - 526400 rm 61/2.89 0.0470 2.6 33.5 4050 - 639500 rm 61/3.23 0.0366 2.8 37.0 5000 - 752630 rm 127/2.52 0.0283 2.8 41.0 6350 - 855

  • Type: BYFYSpecification: BDS-900 and BS-6004Voltage: 300/500 volts

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Sheath

    NominalCrossSectionalArea ofConductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalThicknessof Seath

    ApproxOverallDimension

    ApproxWeightof Cable

    Current RatingEnclosed inConduitsSinglePhase at35oC

    Clipped to aSurface or ona Cable TrayOne CableSingle Phaseat 35oC

    mm2 no./mm ohm/km mm mm mm x mm kg/km amp amp2 x 1.0 re 1/1.13 18.1 0.6 0.9 6.8 x 4.4 55 13 152 x 1.5 re 1/1.38 12.1 0.7 0.9 7.7 x 4.8 70 16 182 x 2.5 re 1/1.78 7.41 0.8 1.0 9.2 x 5.7 100 22 262 x 4.0 rm 7/0.85 4.61 0.8 1.0 10.8 x 6.5 155 30 332 x 6.0 rm 7/1.05 3.08 0.8 1.1 12.1 x 7.3 205 37 433 x 1.0 re 1/1.13 18.1 0.6 0.9 9.2 x 4.4 80 11 123 x 1.5 re 1/1.38 12.1 0.7 0.9 10.6 x 4.8 100 15 163 x 2.5 re 1/1.78 7.41 0.8 1.0 12.6 x 5.7 150 20 223 x 4.0 rm 7/0.85 4.61 0.8 1.1 15.2 x 6.7 235 28 333 x 6.0 rm 7/1.05 3.08 0.8 1.1 17.0 x 7.5 310 35 40

    Type: BYFYESpecification: BDS-900 and BS-6004Voltage: 300/500 volts

    1. Copper Conductor

    2. PVC Insulation

    3. Earth Continuity Conductor

    4. PVC Sheath

    NominalCrossSectionalArea ofConductor

    No. andNominalDiameterof Wires

    MaximumResistanceof Conductorat 20o C

    NominalThicknessofInsulation

    NominalThicknessof Seath

    ApproxOverallDimension

    No. andNominalDiameterof Wires ofECC

    ApproxWeightof Cable

    Current Rating

    EnclosedinConduitsSinglePhase at35oC

    Clipped toa Surfaceor on aCable TrayOne CableSinglePhase at35oC

    no. x mm2 no./mm Ohm/km mm mm mm x mm no./mm kg/km amp amp2 x 1.0 re 1/1.13 18.1 0.6 0.9 7.9 x 4.4 1/1.13 70 13 152 x 1.15 re 1/1.38 12.1 0.7 0.9 8.8 x 4.8 1/1.13 85 16 182 x 1.5 re 1/1.78 7.41 0.8 1.0 11.0 x 5.7 1/1.13 120 22 262 x 4.0 rm 7/0.85 4.61 0.8 1.0 12.1 x 6.5 1/1.38 180 30 332 x 6.0 rm 7/1.05 3.08 0.8 1.1 13.9 x 7.3 1/1.78 250 37 43

  • 3 x 1.0 re 1/1.13 18.1 0.6 0.9 10.3 x 4.4 1/1.13 90 11 123 x 1.5 re 1/1.38 12.1 0.7 0.9 11.5 x 4.8 1/1.13 120 15 163 x 2.5 re 1/1.78 7.41 0.8 1.0 14.0 x 5.7 1/1.13 160 20 22

    Type: BYFYESpecification: BDS-900 and BS-6004Voltage: 300/500 volts

    1. Copper Conductor

    2. PVC Insulation

    3. Earth Continuity Conductor

    4. PVC Sheath

    NominalCrossSectionalArea ofConductor

    No. andNominalDiameterof Wires

    MaximumResistanceof Conductorat 20o C

    NominalThicknessofInsulation

    NominalThicknessof Seath

    ApproxOverallDimension

    No. andNominalDiameterof Wires ofECC

    ApproxWeightof Cable

    Current Rating

    EnclosedinConduitsSinglePhase at35oC

    Clipped toa Surfaceor on aCable TrayOne CableSinglePhase at35oC

    no. x mm2 no./mm ohm/km mm mm mm x mm no./mm kg/km amp amp2 x 1.0 re 1/1.13 18.1 0.6 0.9 7.9 x 4.4 1/1.13 70 13 152 x 1.15 re 1/1.38 12.1 0.7 0.9 8.8 x 4.8 1/1.13 85 16 182 x 1.5 re 1/1.78 7.41 0.8 1.0 11.0 x 5.7 1/1.13 120 22 262 x 4.0 rm 7/0.85 4.61 0.8 1.0 12.1 x 6.5 1/1.38 180 30 332 x 6.0 rm 7/1.05 3.08 0.8 1.1 13.9 x 7.3 1/1.78 250 37 433 x 1.0 re 1/1.13 18.1 0.6 0.9 10.3 x 4.4 1/1.13 90 11 123 x 1.5 re 1/1.38 12.1 0.7 0.9 11.5 x 4.8 1/1.13 120 15 163 x 2.5 re 1/1.78 7.41 0.8 1.0 14.0 x 5.7 1/1.13 160 20 22

    Type: BYMSpecification: BDS-900 and BS-6004Voltage: 300/500 volts

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Sheath

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalThicknessof Seath

    ApproxOverallDiameter

    ApproxWeightof Cable

    Current RatingIn ConduitSinglePhase at35oC

    Clipped to aSurface or ona Cable TraySingle Phaseat 35oC

    no. x mm2 no./mm ohm/km mm mm mm kg/km amp amp1 x 1.0 re 1/11.13 18.1 0.6 0.8 4.5 27 13 161 x 1.5 re 1/1.38 12.1 0.7 0.8 4.9 34 16 20

  • 1 x 2.5 re 1/1.78 7.41 0.8 0.8 5.8 49 22 281 x 4 rm 7/0.85 4.61 0.8 0.9 6.8 73 30 371 x 6 rm 7/1.05 3.08 0.8 0.9 7.4 94 38 471 x 10 rm 7/1.35 1.83 1.0 0.9 8.8 144 52 631 x 16 rm 7/1.71 1.15 1.0 1.0 10.2 220 70 851 x 16 rm 19/1.04 1.15 1.0 1.0 10.5 225 70 851 x 25 rm 7/2.14 0.727 1.2 1.1 12.0 325 91 1101 x 25 rm 19/1.30 0.727 1.2 1.1 12.2 330 91 1101 x 35 rm 19/1.53 0.524 1.2 1.1 13.4 440 112 1362 x 1.0 re 1/1.13 18.1 0.6 1.2 8.6 100 13 152 x 1.5 re 1/1.38 12.1 0.7 1.2 9.5 117 16 182 x 2.5 re 1/1.78 7.41 0.8 1.2 11.0 175 22 262 x 4.0 rm 7/0.85 4.61 0.8 1.2 12.0 228 30 332 x 6.0 rm 7/1.05 3.08 0.8 1.2 13.5 290 37 432 x 10 rm 7/1.35 1.83 1.0 1.4 17.0 475 50 602 x 16 rm 7/1.71 1.15 1.0 1.4 19.0 673 66 802 x 25 rm 7/2.14 0.727 1.2 1.4 23.0 1000 75 882 x 35 rm 19/1.53 0.524 1.2 1.6 26.5 1345 92 108

    BDS-901 and VDE-0271/3.69

    Type: NYYSpecification: BDS-901 and VDE-0271/3.69Voltage: 600/1000 volts

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Sheath

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalThickness ofSeath

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current RatingUnderGround at30oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm mm kg/km amp amp1 x 1.5 re 1/1.38 12.1 0.8 1.8 7.0 65 27 221 x 2.5 re 1/1.78 7.41 0.9 1.8 7.7 80 36 301 x 4 rm 7/0.85 4.61 1.0 1.8 8.6 110 47 391 x 6 rm 7/1.05 3.08 1.0 1.8 9.0 138 59 501 x 10 rm 7/1.35 1.83 1.0 1.8 10.1 185 78 691 x 16 rm 7/1.71 1.15 1.0 1.8 11.2 252 100 941 x 25 rm 7/2.14 0.727 1.2 1.8 13.0 364 130 1251 x 35 rm 19/1.53 .0524 1.2 1.8 14.2 470 155 1601 x 50 rm 19/1.83 0.387 1.4 1.8 15.8 625 185 1951 x 70 rm 19/2.17 0.268 1.4 1.8 17.8 850 225 2451 x 95 rm 19/2.52 0.193 1.6 1.8 20.0 1110 270 3001 x 120 rm 37/2.03 0.153 1.6 1.8 21.6 1360 310 3501 x 150 rm 37/2.27 .0124 1.8 1.8 23.7 1710 350 4051 x 185 rm 37/2.52 0.0991 2.0 2.0 26.3 2080 390 4601 x 240 rm 61/2.25 0.0754 2.2 2.0 29.3 2710 450 555

  • 1 x 300 rm 61/2.52 0.0601 2.4 2.0 32.2 3400 515 6401 x 400 rm 61/2.89 0.0470 2.6 2.2 35.6 4400 585 7701 x 500 rm 61/3.23 0.0366 3.0 2.2 40.3 5420 680 9001 x 630 rm 127/2.2 0.0283 3.0 2.2 44.2 6750 800 1030

    Type: NYYSpecification: BDS-901 and VDE-0271/3.69Voltage: 600/1000 volts

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Common Covering

    4. PVC Sheath

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalThickness ofSeath

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current RatingUnderGround at30oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm mm kg/km amp amp2 x 1.5 re 1/1.38 12.1 0.8 1.8 11.9 170 25 192 x 2.5 re 1-/1.78 7.41 0.9 1.8 13.1 230 34 272 x 4.0 rm 7/0.85 4.61 1.0 1.8 15.1 310 44 352 x 6.0 rm 7/1.05 3.08 1.0 1.8 16.3 380 55 452 x 10 rm 7/1.35 1.83 1.0 1.8 18.1 512 74 622 x 16 rm 7/1.71 1.15 1.0 1.8 20.2 690 97 842 x 25 rm 7/2.14 0.727 1.2 1.8 24.5 1050 125 1102 x 35 rm 19/1.53 0.524 1.2 2.0 27.4 1350 150 1403 x 1.5 re 1/1.38 12.1 0.8 1.8 12.3 200 22 163 x 2.5 re 1/1.78 7.41 0.9 1.8 13.6 266 30 233 x 4.0 rm 7/0.85 4.61 1.0 1.8 15.8 365 38 323 x 6.0 rm 7/1.05 3.08 1.0 1.8 17.0 460 48 413 x 10 rm 7/1.35 1.83 1.0 1.8 19.0 620 64 563 x 16 rm 7/1.71 1.15 1.0 1.8 21.4 925 83 753 x 25 rm 7/2.14 0.727 1.2 2.0 25.8 1350 110 983 x 35 sm Min 6 wire 0.524 1.2 2.0 23.5 1340 130 1203 x 50 sm Min 6 wire 0.387 1.4 2.0 27.0 1820 155 1503 x 70 sm Min 12 wire 0.268 1.4 2.0 30.0 2460 190 1903 x 95 sm Min 15 wire 0.193 1.6 2.0 34.5 3350 225 2303 x 120 sm Min 18 wire 0.153 1.6 2.2 37.0 4100 260 2703 x 150 sm Min 18 wire 0.124 1.8 2.2 41.0 5050 295 3053 x 185 sm Min 30 wire 0.0991 2.0 2.2 44.5 6200 330 3503 x 240 sm Min 34 wire 0.0754 2.2 2.6 50.5 7500 385 4103 x 300 sm Min 34 wire 0.0601 2.4 2.6 56.0 10100 524 470

    Type: NYY-1Specification: BDS-901 and VDE-0271/3.69Voltage: 600/1000 volts

  • 1. Copper Conductor

    2. PVC Insulation

    3. PVC Common Covering

    4. PVC Sheath

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalThickness ofSeath

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current RatingUnderGround at30oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm mm kg/km amp amp5 x 1.5 re 1/1.38 12.1 0.8 1.8 13.0 210 18 137 x 1.5 re 1/1.38 12.1 0.8 1.8 13.5 258 16 1210 x 1.5 re 1/1.38 12.1 0.8 1.8 17.0 360 13 1012 x 1.5 re 1/1.38 12.1 0.8 1.8 17.5 400 12 916 x 1.5 re 1/1.38 12.1 0.8 1.8 19.0 516 11 821 x 1.5 re 1/1.38 12.1 0.8 1.8 21.0 643 9 724 x 1.5 re 1/1.38 12.1 0.8 2.0 23.0 720 9 730 x 1.5 re 1/1.38 12.1 0.8 2.0 24.5 870 8 65 x 2.5 re 1/1.78 7.41 0.9 1.8 14.6 290 24 197 x 2.5 re 1/1.78 7.41 0.9 1.8 15.7 370 21 1710 x 2.5 re 1/1.78 7.41 0.9 1.8 19.4 507 18 1412 x 2.5 re 1/1.78 7.41 0.9 1.8 19.9 570 16 1316 x 2.5 re 1/1.78 7.41 0.9 1.8 21.9 730 14 1121 x 2.5 re 1/1.78 7.41 0.9 2.0 24.5 940 13 1024 x 2.5 re 1/1.78 7.41 0.9 2.0 27.0 1060 12 930 x 2.5 re 1/1.78 7.41 0.9 2.0 28.5 1280 10 85 x 4 rm 7/0.85 4.61 1.0 1.8 17.2 410 31 257 x 4 rm 7/0.85 4.61 1.0 1.8 18.6 540 27 2210 x 4 rm 7/0.85 4.61 1.0 1.8 23.3 720 23 1912 x 4 rm 7/0.85 4.61 1.0 1.8 24.0 840 21 17

    Type: NYCYSpecification: BDS-901 and VDE-0271/3.69Voltage: 600/1000 volts

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Common Covering

    4. Concentric Neutral:Copper

    5. PVC Sheath

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalThickness ofSeath

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current RatingUnderGround at30oC

    In Airat35oC

  • no. x mm2 no./mm ohm/km mm mm mm kg/km amp amp3 x 25 rm / 1 x16 C

    7 / 2.1472 / 0.54

    0.7270.15 1.2 2.0 27.0 1550 110 98

    3 x 35 sm / 1 x16 C

    Min 6 wire72 / 0.54

    0.5241.15 1.2 2.0 24.0 1545 130 120

    3 x 50 sm / 1 x25C

    Min 6 wire50 / 0.8

    0.3870.727 1.4 2.0 29.0 2145 155 150

    3 x 70 sm / 1 x35 C

    Min 12 wire70 / 0.8

    0.2680.524 1.4 2.0 31.0 2860 190 190

    3 x 95 sm / 1 x35 C

    Min 15 wire59 / 1.05

    0.1930.387 1.6 2.2 36.0 3900 225 230

    3 x 120 sm / 1x 70 C

    Min 18 wire71 / 1.13

    0.1530.268 1.6 2.2 38.6 4890 260 270

    3 x 150 sm / 1x 70 C

    Min 18 wire71 / 1.13

    0.1240.268 1.8 2.2 42.5 5830 295 305

    3 x 185 sm / 1x 95 C

    Min 30 wire67 / 1.53

    0.09910.193 2.0 2.6 47.5 7370 330 350

    3 x 240 sm / 1x 120 C

    Min 34 wire67 / 1.53

    0.07540.153 2.2 2.6 52.5 9380 385 410

    3 x 300 sm / 1x 150 C

    Min 34 wire1.63

    0.06010.124 2.4 3.0 58.0 11700 425 470

    Type: NYFGbYSpecification: BDS-901 and VDE-0271/3.69Voltage: 600/1000 volts

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Common Covering

    4. Flat Galvanising steel with helical steel tape binder

    5. PVC Sheath

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalThickness ofSeath

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current RatingUnderGround at30oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm mm kg/km amp amp3 x 16 rm 7/1.71 1.15 1.0 1.8 24.0 1360 83 753 x 25 rm 7/2.14 0.727 1.2 2.0 28.0 1890 110 983 x 35 sm Min 6 wire 0.524 1.2 2.0 25.0 1850 130 1203 x 50 sm Min 6 wire 0.387 1.4 2.0 28.0 2410 155 1503 x 70 sm Min 12 wire 0.268 1.4 2.0 31.0 3100 190 1903 x 95 sm Min 15 wire 0.193 1.6 2.2 36.0 4370 225 2303 x 120 sm Min 18 wire 0.153 1.6 2.2 38.6 5220 260 2703 x 150 sm Min 18 wire 0.124 1.8 2.2 42.5 6340 295 3053 x 185 sm Min 30 wire 0.0991 2.0 2.6 47.0 7700 330 3503 x 240 sm Min 34 wire 0.0754 2.2 2.6 52.5 9950 385 4103 x 300 sm Min 34 wire 0.601 2.4 30. 58.0 12210 425 470

  • Type: NYFGbYSpecification: BDS-901 and VDE-0271/3.69Voltage: 3500/6000 volts

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Common Covering

    4. Flat galvanising steel with helical steel tape binder

    5. PVC Sheath

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalThickness ofSeath

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current RatingUnderGround at30oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm mm kg/km amp amp3 x 25 rm 7/2.14 .0727 304 2.2 37.0 2900 105 1053 x 35 sm Min 6 wire 0.524 3.4 2.2 39.0 3450 125 1253 x 50 sm Min 6 wire 0.387 3.4 2.2 42.0 4150 145 1553 x 70 sm Min 12 wire 0.268 3.4 2.6 46.0 5230 180 1903 x 95 sm Min 15 wire 0.193 3.4 2.6 49.0 6080 215 2353 x 120 sm Min 18 wire 0.153 3.4 2.6 52.0 7150 245 2703 x 150 sm Min 18 wire 0.124 3.4 2.6 54.5 8250 275 3053 x 185 sm Min 30 wire 0.0991 3.4 3.0 59.5 10200 305 3503 x 240 sm Min 34 wire 0.0754 3.4 3.0 63.8 12000 350 4053 x 300 sm Min 34 wire 0.0601 3.4 3.4 70.0 15700 390 460

    Type: NYSYSpecification: BDS-901 and VDE-0271/3.69Voltage: 3500/6000 volts

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Common Covering

    4. Metallic Shield with Copper

    5. PVC Sheath

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalThickness ofSeath

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current RatingUnderGround at30oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm mm kg/km amp amp1 x25 7/2.14 0.727 3.4 1.8 18.0 645 131 1201 x 35 19/1.53 0.524 3.4 1.8 19.5 770 156 150

  • 1 x 50 19/1.83 0.387 3.4 1.8 20.5 860 183 1801 x 70 19/2.17 0.268 3.4 1.8 22.5 1105 223 2301 x 95 19/2.52 0.193 3.4 1.8 24.5 1410 268 2801 x 120 37/2.03 0.153 3.4 1.8 26.0 1670 300 3251 x 150 37/2.27 0.124 3.4 1.8 27.5 1980 335 3651 x 185 37/2.52 0.0991 3.4 2.0 29.5 2400 380 4201 x 240 61/2.25 0.0754 3.4 2.0 32.1 3010 450 5001 x 300 61/2.52 0.0601 3.4 2.0 34.5 3660 490 5801 x 400 61/2.89 0.0470 3.4 2.2 38.0 4570 570 6901 x 500 61/3.23 0.0366 3.4 2.4 41.5 5640 645 7751 x 630 127/2.52 0.0283 3.4 2.4 45.5 7140 730 9003 x 25 rm 7/2.14 0.727 3.4 2.2 36.2 1800 105 1053 x 35 rm 19/1.53 .0524 3.4 2.2 38.8 2300 125 1253 x 50 rm 19/1.83 0.387 3.4 2.2 42.0 3150 145 1553 x 70 rm 19/2.52 0.193 3.4 2.6 51.0 4500 215 2353 x 95 rm 19/2.17 0.268 3.4 2.6 47.0 3850 180 1903 x 120 rm 37/2.03 0.153 3.4 2.6 54.5 5750 245 2703 x 150 rm 37/2.27 0.124 3.4 3.0 59.0 6970 275 3053 x 185 rm 37/2.52 0.0991 3.4 3.0 63.0 8400 305 3503 x 240 rm 61/2.25 0.0754 3.4 3.4 69.0 10600 350 4053 x 300 rm 61/2.52 0.0601 3.4 3.4 74.5 13200 390 460

    Type: NYSEYFGbYSpecification: BDS-901 and VDE-0271/3.69Voltage: 5800/10000 volts

    1. Copper Conductor

    2. Conducting Screen: Extruded Semiconductor

    3. PVC Insulation

    4. Insulating Screen: Extruded Semiconductor

    5. Copper Screen

    6. PVC Inner Sheath

    7. Flat glav. steel wire with helical ateel tape

    8. PVC Sheath

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalThickness ofSeath

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current RatingUnderGround at30oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm mm kg/km amp amp3 x 25 rm 7/2.14 0.727 4.0 2.6 53.0 5000 100 1003 x 35 rm 19/1.53 0.524 4.0 2.6 56.0 5700 120 1203 x 50 rm 19/1.83 0.387 4.0 3.0 59.5 6500 140 1453 x 70 rm 19/2.17 0.268 4.0 3.0 64.0 7700 170 1803 x 95 rm 19/2.52 0.193 4.0 3.0 68.0 9100 200 2203 x 120 rm 37/2.03 0.153 4.0 3.4 72.5 10400 230 2503 x 150 rm 37/2.27 0.124 4.0 3.4 76.0 11900 260 290

  • 3 x 185 rm 37/2.52 0.0991 4.0 3.8 81.0 13800 290 3253 x 240 rm 61/2.25 0.0754 4.0 308 88.0 15000 320 3703 x 300 rm 61/2.52 0.0601 4.0 4.2 95.0 18000 365 425

    Type: NYASpecification: VDE-0250/3.69Voltage: 600/1000 volts

    1. Copper Conductor

    2. PVC Insulation

    Nominal CrossSectional Area ofConductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at 20o C

    NominalThickness ofInsulation

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current RatingIn Conduitat 35oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm kg/km amp amp1 x 0.5 re 1/0.80 36.00 0.6 2.3 8 - 121 x 0.75 re 1/0.98 24.50 0.6 2.5 11 - 141 x 1.0 re 1/1.13 18.10 0.6 2.6 14 10 171 x 1.5 re 1/1.38 12.10 0.6 2.9 18 14 221 x 2.5 re 1/1.78 7.41 0.7 3.5 30 18 301 x 4.0 re 1/2.26 4.61 0.8 4.2 50 23 391 x 6.0 re 1/2.77 3.08 0.8 4.7 67 30 501 x 10 re 1/3.57 1.83 1.0 6.0 110 42 691 x 16 re 1/4.52 1.15 1.0 6.9 170 57 92

    Type: NYIFYSpecification: VDE-0250/3.69Voltage: 220/380 volts

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Sheath

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalThickness ofSeath

    ApproxOverallDimension

    ApproxWeight ofCable

    Current Ratingat 35 oCAmbient Temp.Under Plaster

    no. x mm2 no./mm ohm/km mm mm mm x mm kg/km amp2 x 1.5 re 1/1.38 12.1 0.4 0.8 4.4 x 12.0 70 172 x 2.5 re 1/1.78 7.41 0.5 0.9 5.2 x 13.5 105 232 x 4.0 re 1/2.26 4.61 0.6 0.9 6.0 x 15.5 146 313 x 1.5 re 1/1.38 12.1 0.4 0.8 4.4 x 19.0 105 173 x 2.5 re 1/1.78 7.41 0.5 0.9 5.2 x 21.5 160 233 x 4.0 re 1/2.26 4.61 06 0.9 6.0 x 25.0 225 31

  • Type: NYMTSpecification: VDE-0250/3.69Voltage: 300/500 volts

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Common Covering

    4. PVC Sheath

    5. Galvanised Steel Wire Rope

    Nominal CrossSectional Areaof Conductor

    No. and NominalDiameter of WiresCopperWire

    SteelWire

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalThickness ofSeath

    MaximumOuterDiameter

    ApproxWeight ofCable

    CurrentRating at 35oC AmbientTemp. in Air

    no. x mm2 no./mm no./mm ohm/km mm mm mm kg/km amp2 x 1.5 re 1/1.38 19/0.6 12.1 0.6 1.4 9.8 205 172 x 2.5 re 1/1.78 18/0.6 7.41 0.7 1.4 11.0 250 232 x 4 re 1/2.26 19/0.6 4.61 0.8 1.4 12.5 330 312 x 6 re 1/2.77 19/0.6 3.08 0.8 1.4 13.5 400 413 x 1.5 re 1/1.38 19/0.6 12.1 0.6 1.4 10.5 225 173 x 2.5 re 1/1.78 19/0.6 7.41 0.7 1.4 11.5 280 233 x 4 re 1/2.26 19/06 4.61 0.8 1.4 13.0 176 313 x 6 re 1/2.77 19/0.6 3.08 0.8 1.6 15.0 507 414 x 1.5 re 1/ 1.38 19/0.6 12.1 0.6 1.4 11.0 250 174 x 2.5 re 1/1.78 19/0.6 7.41 0.7 1.4 12.5 320 234 x 4 re 1/2.26 19/0.6 4.61 0.8 1.6 14.5 460 314 x 6 re 1/2.77 19/0.6 3.08 0.8 1.6 16.5 590 41

    BDS-833, BS-2004 & BS-6500

    Type: IYALSpecification: BS-2004Voltage: 250/440 volts

    1. Copper Conductor

    2. PVC Insulation

    Nominal CrossSectional Area ofConductor

    No. and NominalDiameter of Wires

    NominalThickness ofInsulation

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current Rating

    Bunched andEnclosed inConduits TwoCables SinglePhase at35oC

    Clipped to aSurface or ona Cable TrayBunched &Unenclosed 2Cables SinglePhase at 35oC

    mm2 no./inchno./mm mm mm kg/km amp amp

    1.0 1 / 0.0441 / 1.12 0.89 2.03 18 13 161.3 3 / 0.029 0.89 3.48 24 16 20

  • 3 / 0.741.9 3 / 0.0363 / 0.91 0.89 3.89 33 20 25

    2.9 7 / 0.0297 / 0.74 0.89 4.11 44 26 31

    4.5 7 / 0.0367 / 0.91 1.016 4.90 62 35 41

    6.5 7 / 0.0447 / 1.12 1.016 5.51 88 42 51

    9.5 7 / 0.0527 / 1.32 1.016 6.10 116 53 65

    14.5 7 / 0.0647 /1.63 1.016 7.00 170 70 83

    Type: IYALSpecification: BS-2004Voltage: 660/1100 volts

    1. Copper Conductor

    2. PVC Insulation

    Nominal CrossSectional Area ofConductor

    No. and NominalDiameter of Wires

    NominalThickness ofInsulation

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current Rating

    Bunched andEnclosed inConduits TwoCables SinglePhase at35oC

    Clipped to aSurface or ona Cable TrayBunched &Unenclosed 2Cables SinglePhase at 35oC

    mm2 no./inchno./mm mm mm kg/km amp amp

    1.0 1 / 0.0441 / 1.12 1.143 3.53 22 13 16

    1.3 3 / 0.0293 / 0.74 1.143 3.96 28 16 20

    1.9 3 / 0.0363 / 0.91 1.143 4.39 37 21 26

    2.9 7 / 0.0297 / 0.74 1.143 4.62 48 27 32

    4.5 7 / 0.0367 / 0.91 1.27 5.41 70 36 42

    6.5 7 / 0.0447 / 1.12 1.27 6.02 94 43 52

    9.5 7 / 0.0527 / 1.32 1.27 6.63 120 54 66

    14.5 7 / 0.0647 / 1.63 1.27 7.55 175 72 85

    Type: IYYLSpecification: BS-2004Voltage: 250/440 volts

  • 1. Copper Conductor

    2. PVC Insulation

    3. PVC Sheath

    Nominal CrossSectional Area ofConductor

    No. andNominalDiameter ofWires

    NominalThickness ofInsulation

    NominalThickness ofSheath

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current Rating

    Bunched andEnclosed inConduits TwoCables SinglePhase at35oC

    Clipped to aSurface or ona Cable TrayBunched &Unenclosed 2Cables SinglePhase at 35oC

    mm2 no./inchno./mm mm mm mm kg/km amp amp

    1.0 1 / 0.0441 / 1.12 0.635 0.89 4.28 29 13 16

    1.3 3 / 0.0293 / 0.74 0.635 0.89 4.80 35 16 20

    1.9 3 / 0.0363 / 0.91 0.635 0.89 5.16 46 20 25

    2.9 7 / 0.0297 / 0.74 0.635 0.89 5.46 57 26 31

    4.5 7 / 0.0367 / 0.91 0.762 0.89 6.29 78 35 41

    6.5 7 / 0.0447 / 1.12 0.762 0.89 6.85 1.5 42 51

    9.5 7 / 0.0527 / 1.32 0.89 0.89 7.80 140 53 65

    14.5 7 / 0.0647 / 1.63 0.89 1.143 9.20 205 70 83

    Type: IYFYSpecification: BS-2004Voltage: 250/440 volts

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Sheath

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    NominalThickness ofInsulation

    NominalThickness ofSheath

    ApproxOverallDimension

    ApproxWeight ofCable

    Current RatingEnclosed inConduits OneCable SinglePhase at35oC

    Clipped to aSurface or ona Cable Tray 1Cable SinglePhase at 35oC

    mm2 no./inchno./mm mm mm mm x mm kg/km amp amp

    2 x 1.0 1 / 0.0441 / 1.12 0.635 0.89 6.81 x 4.42 52 12 15

    2 x 1.3 3 / 0.0293 / 0.74 0.635 0.89 7.78 x 4.88 68 15 18

    2 x 1.9 3 / 0.036 0.635 0.143 9.04 x 5.79 95 20 23

  • 3 / 0.912 x 2.9 7 / 0.0297 / 0.74 0.635 1.143 9.50 x 6.02 120 23 28

    2 x 4.5 7 / 0.0367 / 0.91 0.762 0.143 11.07 x 6.81 166 32 38

    2 x 6.5 7 / 0.0447 / 1.12 0.762 1.143 12.30 x 7.42 218 38 46

    2 x 9.5 7 / 0.0527 / 1.32 0.890 1.143 14.15 x 8.41 298 50 57

    2 x 14.5 7 / 0.0647 / 1.63 0.890 1.397 16.48 x 9.83 422 65 76

    3 x 1.0 1 / 0.0441 / 1.12 0.635 0.89 9.19 x 4.42 76 11 14

    3 x 1.3 3 / 0.0293 / 0.74 0.635 0.89 10.57 x 4.88 97 14 17

    3 x 1.9 3 / 0.0363 / 0.91 0.635 1.143 12.29 x 5.79 140 18 20

    3 x 2.9 7 / 0.0297 / 0.74 0.635 1.143 13.10 x 6.15 174 21 26

    3 x 4.5 7 / 0.0367 / 0.91 0.762 1.143 15.46 x 6.93 246 30 35

    3 x 6.5 7 / 0.0447 / 1.12 0.762 1.143 17.30 x 7.54 335 36 44

    Type: Flexible CordsSpecification: BDS-899 and BS-6500Voltage: 300/500 volts

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Sheath

    NominalCrossSectionalArea ofConductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalThicknessof Sheath

    ApproxOverallDiameter

    ApproxWeightof Cable

    Current RatingIn Conduit at35oC

    InSurface/CableTray at 35oC

    mm2 no./mm ohm/km mm mm mm kg/km amp amp2 x 0.5 16/0.20 39.00 0.6 0.8 6.5 50 3 42 x 0.75 24/0.20 26.00 0.6 0.8 7.0 65 6 72 x 1.0 32/0.20 19.50 0.6 0.8 7.5 70 10 112 x 1.5 30 /0.25 13.30 0.6 0.8 8.0 95 15 162 x 2.5 50/0.25 9.98 0.7 1.0 9.5 150 20 212 x 4.0 56/0.30 4.95 0.8 1.0 11.5 220 25 263 x 0.5 16/0.20 39.00 0.6 0.8 7.0 60 3 43 x 0.75 24/0.20 26.00 0.6 0.8 8.0 75 6 73 x 1.0 32/0.20 19.50 0.6 0.8 8.5 90 10 113 x 1.5 30/0.25 13.30 0.6 0.9 9.8 120 15 163 x 2.5 50/0.25 7.98 0.7 1.1 11.0 180 20 213 x 4.0 56/0.30 4.95 0.8 1.1 13.0 270 25 264 x 0.5 16/0.20 39.00 0.6 0.8 8.0 70 3 44 x 0.75 24/ 0.20 26.00 0.6 0.9 9.0 90 6 74 x 1.0 32/0.20 19.50 0.6 0.9 9.5 110 10 11

  • 4 x 1.5 30/.0.25 13.30 0.6 1.0 10.5 150 15 164 x 2.5 50/0.25 7.98 0.7 1.1 12.5 220 20 214 x 4.0 56/0.30 4.95 0.8 1.1 14.0 330 25 26

    IEC-60502-1

    Type: YYSpecification: IEC-60502-1Voltage: 600/1000 volts

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Sheath

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalThickness ofSeath

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current RatingUnderGround at30oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm mm kg/km amp amp1 x 1.5 re 1 / 1.38 12.1 0.8 1.4 6.5 55 27 22.1 x 2.5 re 1 / 1.78 7.41 0.8 1.4 7.0 70 36 301 x 4 rm 7 / 0.85 4.61 1.0 1.4 8.2 105 47 391 x 6 rm 7 / 1.05 3.08 1.0 1.4 8.5 120 59 501 x 10 rm 7 / 1.35 1.83 1.0 1.4 9.6 170 78 691 x 16 rm 7 / 1.71 1.15 1.0 1.4 10.5 240 100 941 x 25 rm 7 / 2.14 0.727 1.2 1.4 12.2 345 130 1251 x 35 rm 19 / 1.53 0.524 1.2 1.4 13.5 450 155 1601 x 50 rm 19 / 1.83 0.387 1.4 1.4 15.5 610 185 1951 x 70 rm 19 / 2.17 0.268 1.4 1.4 17.2 820 225 2451 x 95 rm 19 / 2.52 0.193 1.6 1.5 19.4 1100 270 3001 x 120 rm 37 / 2.03 .0153 1.6 1.5 21.0 1350 310 3501 x 150 rm 37 / 2.27 0.124 1.8 1.6 23.0 1680 350 4051 x 185 rm 37 / 2.52 0.0991 2.0 1.7 26.0 2040 390 4601 x 240 rm 61 / .25 0.0754 2.2 1.8 29.0 2675 450 5551 x 300 rm 61 / 2.52 0.0601 2.4 1.9 32.0 3300 515 6401 x 400 rm 61 / 2.89 0.0470 2.6 2.0 35.5 4300 585 7701 x 500 rm 61 / 3.23 0.0366 2.8 2.1 40.0 5350 640 9001 x 630 rm 127 / 2.52 0.0283 2.8 2.2 44.0 6600 800 10301 x 800 rm 127 / 2.85 0.0221 2.8 2.3 49.0 8400 945 11601 x 1000 rm 127 / 3.20 0.0176 3.0 2.5 54.0 10500 1095 1310

    Type: YYSpecification: IEC-60502-1Voltage: 600/1000 volts

  • 1. Copper Conductor

    2. PVC Insulation

    3. PVC Inner Covering

    4. PVC Oversheath

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalThickness ofSeath

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current RatingUnderGround at30oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm mm kg/km amp amp2 x 1.5 re 1 / 1.38 12.1 0.8 1.8 11.9 170 25 192 x 2.5 re 1 / 1.78 7.41 0.8 1.8 13.0 228 34 272 x 4 rm 7 / 1.05 3.08 1.0 1.8 16.3 380 55 452 x 6 rm 7 / 1.05 3.08 1.0 1.8 16.3 380 55 452 x 10 rm 7 / 1.35 1.83 1.0 1.8 18.1 512 74 622 x 16 rm 7 / 1.71 1.15 1.0 1.8 20.2 690 97 842 x 25 rm 7 / 2.14 0.727 1.2 1.8 24.5 1050 125 1102 x 35 rm 19 / 1.53 0.524 1.2 1.8 27.0 1340 150 1403 x 1.5 re 1 / 1.38 12.1 0.8 1.8 12.3 200 22 163 x 2.5 re 1 / 1.78 7.41 0.8 1.8 13.6 266 30 233 x 4 rm 7 / 0.85 4.61 1.0 1.8 15.8 365 38 323 x 6 rm 7 / 1.05 3.08 1.0 1.8 17.0 460 48 413 x 10 rm 7 / 1.35 1.83 1.0 1.8 19.0 620 64 563 x 16 rm 7 / 1.71 1.15 1.0 1.8 21.4 925 83 753 x 25 sm Min 6 wire 0.727 1.2 1.8 22.5 1100 110 983 x 35 sm Min 6 wire 0.524 1.2 1.8 23.5 1340 130 1203 x 50 sm Min 6 wire 0.387 1.4 1.8 26.5 1800 155 1503 x 70 sm Min 12 wire 0.268 1.4 2.0 30.0 2460 190 1903 x 95 sm Min 15 wire 0.193 1.6 2.1 35.0 3400 225 2303 x 120 sm Min 18 wire 0.153 1.6 2.2 37.0 4100 260 2703 x 150 sm Min 18 wire 0.124 1.8 2.3 41.2 5100 295 3053 x 185 sm Min 30 wire 0.0991 2.0 2.5 45.5 6250 330 3503 x 240 sm Min34 wire 0.0754 2.2 2.7 51.0 8000 385 4103 x 300 sm Min34 wire 0.0601 2.4 2.9 56.5 10300 425 470

    Type: YRaYSpecification: IEC-60502-1Voltage: 600/1000 volts

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Inner Covering

    4. Round Galvanising Steel Wire Armoured

    5. PVC Oversheath

  • NominalCrossSectionalArea ofConductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalDiameter ofRoundArmourWire

    NominalThicknessof Seath

    ApproxOverallDiameter

    ApproxWeightof Cable

    Current RatingUnderGroundat 30oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm mm mm kg/km amp amp1 x 35 rm 19 / 1.53 0.524 1.2 1.25 1.8 17.0 600 155 1601 x 50 rm 19 / 1.83 0.387 1.4 1.25 1.8 19.0 755 185 1951 x 70 rm 19 / 2.17 0.268 1.4 1.25 1.8 20.5 975 225 2451 x 95 rm 19 / 2.52 1.193 1.6 1.25 1.8 23.0 1260 270 3001 x 120 rm 37 / 2.03 0.153 1.6 1.6 1.8 25.5 1560 310 3501 x 150 rm 37 / 2.27 0.124 1.8 1.6 1.8 28.0 1900 350 4051 x 185 rm 37 / 2.52 0.0991 2.0 1.6 1.8 30.0 2300 390 4601 x 240 rm 61 / 2.25 0.0754 2.2 1.6 1.9 33.0 2900 450 5551 x 300 rm 61 / 2.52 0.0601 2.4 2.0 2.0 36.5 3600 515 6401 x 400 rm 61 / 2.89 0.0470 2.6 2.0 2.1 41.0 4660 585 7701 x 5000 rm 61 / 3.23 0.0366 2.8 2.0 2.2 44.5 5700 680 9001 x 630 rm 127 / 2.52 0.0283 2.8 2.0 2.3 48.5 7000 800 10301 x 800 rm 127 / 2.85 0.0221 2.8 2.5 2.5 55.0 8900 945 11601 x 1000 rm 127 / 3.20 0.0176 3.0 2.5 2.6 60.0 11000 1095 1310

    Type: YRGYSpecification: IEC-60502-1Voltage: 600/1000 volts

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Inner Covering

    4. Round galvanising steel wires armouring

    5. Helical steel tape binder(Optional)

    6. PVC Oversheath

    NominalCrossSectionalArea ofConductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalDiameter ofRoundArmourWire

    NominalThicknessof Seath

    ApproxOverallDiameter

    ApproxWeightof Cable

    Current RatingUnderGroundat 30oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm mm mm kg/km amp amp3 x 4 rm 7 / 0.85 4.61 1.0 1.25 1.8 19.0 716 38 323 x 6 rm 7 / 1.05 3.08 1.0 1.25 1.8 20.5 840 48 413 x 10 rm 7 / 1.35 1.83 1.0 1.25 1.8 22.5 1050 64 563 x 16 rm 7 / 1.71 1.15 1.0 1.25 1.8 25.0 1340 83 753 x 25 sm Min 6 wire 0.727 1.2 1.6 1.8 26.0 1750 110 983 x 35 sm Min 6 wire 0.524 1.2 1.6 1.8 27.5 2070 130 1203 x 50 sm Min 6 wire 0.387 1.4 1.6 2.0 30.5 2650 155 1503 x 70 sm Min 12 wire 0.268 1.4 2.0 2.1 34.5 3700 190 1903 x 95 sm Min 15 wire 0.193 1.6 2.0 2.2 38.5 4760 225 2303 x 120 sm Min 18 wire 0.153 1.6 2.0 2.3 42.0 5675 260 2703 x 150 sm Min 18 wire 0.124 1.8 2.5 2.5 47.0 7250 295 305

  • 3 x 185 sm Min 30 wire 0.0991 2.0 2.5 2.7 51.0 8650 330 3503 x 240 sm Min 34 wire 0.0754 2.2 2.5 2.9 57.0 10800 385 4103 x 330 sm Min 34 wire 0.0601 2.4 2.5 3.1 61.0 13050 425 470

    Type: YFGYSpecification: IEC-60502-1Voltage: 600/1000 volts

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Inner Covering

    4. Round galvanising steel wires armouring

    5. Helical steel tape binder(Optional)

    6. PVC Oversheath

    NominalCrossSectionalArea ofConductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalDiameter ofFlat ArmourWire

    NominalThicknessof Seath

    ApproxOverallDiameter

    ApproxWeightof Cable

    Current RatingUnderGroundat 30oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm mm mm kg/km amp amp3 x 25 sm Min 6 wire 0.727 1.2 0.8 1.8 25.0 1600 110 983 x 35 sm Min 6 wire 0.524 1.2 0.8 1.8 24.8 1840 130 1203 x 50 sm Min 6 wire 0.387 1.4 0.8 1.9 28.0 2410 155 1503 x 95 sm Min 12 wire 0.268 1.4 0.8 2.0 31.0 3100 190 1903 x 70 sm Min 15 wire 0.193 1.6 0.8 2.2 36.0 4370 225 2303 x 120 sm Min 18 wire 0.153 1.6 0.8 2.3 39.0 5250 260 2703 x 150 sm Min 18 wire 0.124 1.8 0.8 2.4 43.0 6400 295 3053 x 185 sm Min 30 wire 0.0991 2.0 0.8 2.6 47.0 7700 330 3503 x 240 sm Min 34 wire 0.754 2.2 0.8 2.8 53.0 10000 385 4103 x 300 sm Min 34 wire 0.0601 2.4 0.8 2.9 57.8 12200 425 4704 x 25 sm Min 6 wire 0.727 1.2 0.8 1.8 27.6 2000 110 984 x 35 sm Min 6 wire 0.524 1.2 0.8 1.9 28.2 2320 130 1204 x 50 sm Min 6 wire 0.387 1.4 0.8 2.0 33.0 3300 155 1504 x 70 sm Min 12 wire 0.268 1.4 0.8 2.1 37.0 4300 190 1904 x 95 sm Min 15 wire 0.193 1.6 0.8 2.3 42.5 5650 225 2304 x 120 sm Min 18 wire 0.153 1.6 0.8 2.4 45.5 7500 260 2704 x 150 sm Min 18 wire 0.124 1.8 0.8 2.6 50.0 8220 295 3054 x 185 sm Min 30 wire 0.0991 2.0 0.8 2.7 56.2 10350 330 3504 x 240 sm Min 34 wire 0.0754 2.2 0.8 3.0 64.0 13000 385 4104 x 300 sm Min 34 wire 0.0601 2.4 0.8 3.2 70.2 15500 425 470

    Type: Control Cable(YY)Specification: IEC-60502-1Voltage: 600/1000 volts

  • 1. Copper Conductor

    2. PVC Insulation

    3. PVC Inner Covering

    4. PVC Oversheath

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalThickness ofSeath

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current RatingUnderGround at30oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm mm kg/km amp amp5 x 1.5 re 1 / 1.38 12.1 0.8 1.8 13.0 210 18 137 x 1.5 re 1 / 1.38 12.1 0.8 1.8 13.5 258 16 1210 x 1.5 re 1 / 1.38 12.1 0.8 1.8 17.0 360 13 1012 x 1.5 re 1 / 1.38 12.1 0.8 1.8 17.5 400 12 919 x 1.5 re 1 / 1.38 12.1 0.8 1.8 20.5 620 10 737 x 1.5 re 1 / 1.38 12.1 0.8 1.8 29.0 1100 8 55 x 2.5 re 1 / 1.78 7.41 0.8 1.8 14.6 290 24 197 x 2.5 re 1 / 1.78 7.41 0.8 1.8 15.7 370 21 1710 x 2.5 re 1 / 78 7.41 0.8 1.8 19.4 507 18 1412 x 2.5 re 1 / 1.78 7.41 0.8 1.8 19.9 570 16 1319 x 2.5 re 1 / 1.78 7.41 0.8 1.8 24.0 900 14 1237 x 2.5 re 1 / 1.78 7.41 0.8 1.9 31.5 1550 9 7

    Type: Control Cable(YRGY)Specification: IEC-60502-1Voltage: 600/1000 volts

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Inner Covering

    4. Round galvanising steel wires armouring

    5. Helical steel tape binder(Optional)

    6. PVC Sheath

    NominalCrossSectionalArea ofConductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalDiameter ofArmourWire

    NominalThicknessof Seath

    ApproxOverallDiameter

    ApproxWeightof Cable

    Current RatingUnderGroundat 30oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm mm mm kg/km amp amp5 x 1.5 re 1 / 1.38 12.1 0.8 1.25 1.8 16.5 500 18 137 x 1.5 re 1 / 1.38 12.1 0.8 1.25 1.8 17.5 575 16 1210 x 1.5 re 1 / 1.38 12.1 0.8 1.25 1.8 20.5 750 13 1012 x 1.5 re 1 / 1.38 12.1 0.8 1.25 1.8 21.5 840 12 919 x 1.5 re 1 / 1.38 12.1 0.8 1.6 1.8 25.0 1200 10 737 x 1.5 re 1 / 1.38 12.1 0.8 1.6 1.9 32.0 1850 8 5

  • 5 x 2.5 re 1 / 1.78 7.41 0.8 1.25 1.8 17.5 590 24 197 x 2.5 re 1 / 1.78 7.41 0.8 1.25 1.8 18.5 675 21 1710 x 2.5 re 1 / 1.78 7.41 0.8 1.25 1.8 22.5 900 18 1412 x 2.5 re 1 / 1.78 7.41 0.8 1.25 1.8 23.0 980 16 1319 x 2.5 re 1 / 1.78 7.41 0.8 1.60 1.8 27.0 1450 14 1237 x 2.5 re 1 / 1.78 7.41 0.8 1.60 2.0 35.0 2350 9 7

    Type: YSYSpecification: IEC-60502-1Voltage: 1.8/3.0 KV

    1. Copper Conductor

    2. PVC Insulation

    3. Copper Screened

    4. PVC Oversheath

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalThickness ofSeath

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current RatingUnderGround at30oC

    In Airat 35oC

    no. x mm2 no./mm ohm/km mm mm mm kg/km amp amp1 x 25 rm 7 / 2.14 0.727 2.2 1.8 16.5 475 130 1251 x 35 rm 19 / 1.53 0.524 2.2 1.8 17.0 590 155 1601 x 50 rm 19 / 1.83 0.387 2.2 1.8 18.5 760 185 1951 x 70 rm 19 / 2.17 0.268 2.2 1.8 20.5 975 225 2451 x 95 rm 19 / 2.52 0.193 2.2 1.8 22.5 1230 270 3001 x 120 rm 37 / 2.03 0.153 2.2 1.8 24.0 1490 310 3501 x 150 rm 37 / 2.27 0.124 2.2 1.8 26.0 1800 350 4051 x 185 rm 37 / 2.52 0.0991 2.2 1.8 28.0 2150 390 4601 x 240 rm 61 / 2.25 0.0754 2.2 1.8 30.5 2700 450 5551 x 300 rm 61 / 2.52 0.0601 2.4 1.9 33.5 3350 515 6401 x 400 rm 61 / 2.89 0.0470 2.6 2.0 38.0 4350 585 7701 x 500 rm 61 / 2.23 0.0366 2.8 2.1 41.5 5350 680 9001 x 630 rm 127 / 2.52 0.0283 2.8 2.2 45.0 6650 800 10301 x 800 rm 127 / 2.85 0.0221 2.8 2.3 50.0 8400 945 116101 x 1000 rm 127 / 3.20 0.0176 3.0 2.5 56.0 10500 1095 1310

    Type: YSYSpecification: IEC-60502-1Voltage: 3.6/6 KV

    1. Copper Conductor

    2. PVC Insulation

    3. Copper Screened

  • 4. PVC Oversheath

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalThickness ofSeath

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current RatingUnderGround at30oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm mm kg/km amp amp1 x 25 rm 7 / 2.14 0.727 3.4 1.8 18.0 645 131 1201 x 35 rm 19 / 1.53 0.524 3.4 1.8 19.5 770 156 1501 x 50 rm 19 / 1.83 0.387 3.4 1.8 20.5 860 183 1801 x 70 rm 19 / 2.17 0.268 3.4 1.8 22.5 1105 223 2301 x 95 rm 19 / 2.52 0.193 3.4 1.8 24.5 1410 268 2801 x 120 rm 37 / 2.03 0.153 3.4 1.8 26.0 1670 300 3251 x 150 rm 37 / 2.27 0.124 3.4 1.8 27.5 1980 335 3651 x 185 rm 37 / 2.52 0.0991 3.4 1.8 29.2 2380 380 4201 x 240 rm 61 / 2.25 0.0754 3.4 1.9 32.0 3000 450 5001 x 300 rm 61 / 2.52 0.0601 3.4 1.9 34.3 3600 490 5801 x 400 rm 61 / 2.89 0.0470 3.4 2.0 37.8 4550 570 3901 x 500 rm 61 / 3.23 0.0366 3.4 2.1 41.0 5600 645 7751 x 630 rm 127 / 2.52 0.283 3.4 2.2 45.3 7100 730 9001 x 800 rm 127 / 2.85 0.0221 3.4 2.4 51.0 8500 910 10351 x 1000 rm 127 / 3.20 0.0176 3.4 2.5 56.0 10500 1060 1185

    Type: YSYSpecification: IEC-60502-1Voltage: 1.8/3.0 KV

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Inner Covering

    4. Copper Screen

    5. PVC Oversheath

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalThickness ofSeath

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current RatingUnderGround at30oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm mm kg/km amp amp3 x 25 sm Min 6 wire 0.727 2.2 1.8 28.0 1380 110 983 x 35 sm Min 6 wire 0.524 2.2 1.9 29.0 1750 130 983 x 50 sm Min 6 wire 0.387 2.2 2.0 32.0 2190 155 1503 x 70 sm Min 12 wire 0.268 2.2 2.1 35.0 2900 190 1903 x 95 sm Min 15 wire 0.193 2.2 2.2 38.5 3770 225 2303 x 120 sm Min 18 wire 0.153 2.2 2.3 41.5 4650 260 2703 x 150 sm Min 18 wire 0.124 2.2 2.4 44.0 5550 295 3053 x 185 sm Min 30 wire 0.0991 2.2 2.5 46.5 6700 330 3503 x 240 sm Min 34 wire 0.0754 2.2 2.7 52.0 8600 385 4103 x 300 sm Min 34 wire 0.0601 2.4 2.9 53.5 10500 425 470

  • Type: YSYSpecification: IEC-60502-1Voltage: 3.6/6 KV

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Inner Covering

    4. Copper Screen

    5. PVC Oversheath

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalThickness ofSeath

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current RatingUnderGround at30oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm mm kg/km amp amp3 x 25 sm Min 6 wire 0.727 3.4 2.0 34.0 1760 105 1053 x 35 sm Min 6 wire 0.524 3.4 2.1 35.0 2130 125 1253 x 50 sm Min 6 wire 0.387 3.4 2.1 37.5 2570 145 1553 x 70 sm Min 12 wire 0.268 3.4 2.3 41.0 3350 180 1903 x 95 sm Min 15 wire 0.193 3.4 2.4 44.5 4300 215 2353 x 120 sm Min 18 wire 0.153 3.4 2.5 48.0 5200 245 2703 x 150 sm Min 18 wire 0.124 3.4 2.6 50.5 6100 275 3053 x 185 sm Min 30 wire 0.0991 3.4 2.7 53.0 7350 305 3503 x 240 sm Min 34 wire 0.0754 3.4 2.9 58.0 9300 350 4053 x 300 sm Min 34 wire 0.601 3.4 3.0 61.5 11200 390 460

    Type: YSYRGYSpecification: IEC-60502-1Voltage: 1.8/3.5 KV

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Inner Covering

    4. Copper Screened

    5. PVC Separation Sheath

    6. Round galvanising steel wires armouring

    7. Helical steel tape binder(Optional)

    8. PVC Oversheath

  • NominalCrossSectionalArea ofConductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalDiameter ofRoundArmourWire

    NominalThicknessof Seath

    ApproxOverallDiameter

    ApproxWeightof Cable

    Current RatingUnderGroundat 30oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm mm mm kg/km amp amp3 x 25 sm Min 6 wire 0.727 2.2 1.6 2.0 34.0 2400 110 983 x 35 sm Min 6 wire 0.524 2.2 2.0 2.1 36.0 3050 130 1203 x 50 sm Min 6 wire 0.387 2.2 2.0 2.2 39.0 3600 155 1503 x 70 sm Min 12 wire 0.268 2.2 2.0 2.3 42.0 4450 190 1903 x 95 sm Min 15 wire 0.193 2.2 2.5 2.5 47.0 5880 225 2303 x 120 sm Min 18 wire 0.153 2.2 2.5 2.6 50.5 6900 260 2703 x 150 sm Min 18 wire 0.124 2.2 2.5 2.7 53.0 7950 295 3053 x 185 sm Min 30 wire 0.0991 2.2 2.5 2.8 56.0 9300 330 3503 x 240 sm Min 34 wire 0.0754 2.2 2.5 3.0 61.5 11450 385 4103 x 300 sm Min 34 wire 0.0601 2.4 2.5 3.2 66.0 13750 425 470

    Type: YSYRGYSpecification: IEC-60502-1Voltage: 3.6/6 KV

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Inner Covering

    4. Copper Screened

    5. PVC Separation Sheath

    6. Round galvanising steel wires armouring

    7. Helical steel tape binder(Optional)

    8. PVC Oversheath

    NominalCrossSectionalArea ofConductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalDiameter ofRoundArmourWire

    NominalThicknessof Seath

    ApproxOverallDiameter

    ApproxWeightof Cable

    Current RatingUnderGroundat 30oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm mm mm kg/km amp amp3 x 25 sm Min 6 wire 0.727 3.4 2.0 2.2 41.0 3200 105 1053 x 35 sm Min 6 wire 0.524 3.4 2.0 2.3 42.0 3630 125 1253 x 50 sm Min 6 wire 0.387 3.4 2.5 2.4 46.0 4550 145 1553 x 70 sm Min 12 wire 0.268 3.4 2.5 2.5 49.0 5480 180 1903 x 95 sm Min 15 wire 0.193 3.4 2.5 2.6 53.0 6640 215 2353 x 120 sm Min 18 wire 0.153 3.4 2.5 2.8 56.0 7700 245 2703 x 150 sm Min 18 wire 0.124 3.4 2.5 2.9 59.0 8770 275 3053 x 185 sm Min 30 wire 0.0991 3.4 2.5 3.0 61.5 10200 305 3503 x 240 sm Min 34 wire 0.0754 3.4 2.5 3.2 67.0 12370 350 4053 x 300 sm Min 34 wire 0.0601 3.4 3.15 3.4 72.0 15300 390 460

  • Type: YSYFGYSpecification: IEC-60502-1Voltage: 1.8/3.0 KV

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Inner Covering

    4. Copper Screened

    5. PVC Separation Sheath

    6. Flat galvanising steel wires armouring

    7. Helical steel tape binder(Optional)

    8. PVC Oversheath

    NominalCrossSectionalArea ofConductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalDiameter ofFlat ArmourWire

    NominalThicknessof Seath

    ApproxOverallDiameter

    ApproxWeightof Cable

    Current RatingUnderGroundat 30oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm mm mm kg/km amp amp3 x 25 sm Min 6 wire 0.727 2.2 0.8 1.9 32.5 2100 110 983 x 35 sm Min 6 wire 0.524 2.2 0.8 2.0 33.5 2500 130 1203 x 50 sm Min 6 wire 0.387 2.2 0.8 2.1 36.0 3000 155 1503 x 70 sm Min 12 wire 0.268 2.2 0.8 2.2 39.5 3800 190 1903 x 95 sm Min 15 wire 0.193 2.2 0.8 2.3 43.5 4800 225 2303 x 120 sm Min 18 wire 0.153 2.2 0.8 2.4 46.5 5700 260 2703 x 150 sm Min 18 wire 0.124 2.2 0.8 2.6 50.0 6800 295 3053 x 185 sm Min 30 wire 0.0991 2.2 0.8 2.7 52.5 8000 330 3503 x 240 sm Min 34 wire 0.0754 2.2 0.8 2.9 57.0 10150 385 4103 x 300 sm Min 34 wire 0.0601 2.4 0.8 3.1 60.0 12000 425 470

    Type: YSYFGYSpecification: IEC-60502-1Voltage: 3.6/6 KV

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Inner Covering

    4. Copper Screened

    5. PVC Separation Sheath

    6. Flat galvanising steel wires armouring

    7. Helical steel tape binder(Optional)

  • 8. PVC Oversheath

    NominalCrossSectionalArea ofConductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalDiameter ofFlat ArmourWire

    NominalThicknessof Seath

    ApproxOverallDiameter

    ApproxWeightof Cable

    Current RatingUnderGroundat 30oC

    In Airat35oC

    no. x mm2 no./mm ohm/km mm mm mm mm kg/km amp amp3 x 25 sm Min 6 wire 0.727 3.4 0.8 2.1 38.0 2600 105 1053 x 35 sm Min 6 wire 0.524 3.4 0.8 2.2 39.5 3100 125 1253 x 50 sm Min 6 wire 0.387 3.4 0.8 2.3 43.0 3590 145 1553 x 70 sm Min 12 wire 0.268 3.4 0.8 2.4 46.0 4450 180 1903 x 95 sm Min 15 wire 0.193 3.4 0.8 2.5 50.0 5500 215 2353 x 120 sm Min 18 wire 0.153 3.4 0.8 2.7 53.5 6500 245 2703 x 150 sm Min 18 wire 0.124 3.4 0.8 2.8 56.0 7500 275 3053 x 185 sm Min 30 wire 0.0991 3.4 0.8 2.9 59.0 8800 305 3503 x 240 sm Min 34 wire 0.0754 3.4 0.8 3.1 64.0 10950 350 4053 x 300 sm Min 34 wire 0.0601 3.4 0.8 3.2 98.0 13200 390 460

    Other Cables

    Type: NYABVoltage: 600/1000 volts

    1. Plain Annealed Flexible Copper Conductor

    2. PVC/Cotton Tape Binder

    3. PVC Insulation

    Nominal CrossSectional Area ofConductor

    No. and NominalDiameter ofWires

    MaximumResistance ofConductor at 20o C

    NominalThickness ofInsulation

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current Ratingat 350C AmbientTemp.

    no. x mm2 no./mm ohm/km mm mm kg/km amp1 x 0.75 rm 7/0.40 24.50 0.8 2.5 14 171 x 4.0 rm 19/0.53 4.470 1.0 4.7 50 411 x 6.0 rm 19/0.65 2.920 1.0 5.3 75 521 x 10 rm 49/0.55 1.770 1.2 7.2 125 721 x 16 rm 49/0.63 1.120 1.2 8.1 185 981 x 25 rm 84/0.62 0.708 1.4 10.5 285 1311 x 35 rm 133/0.59 0.514 1.4 12.0 396 1671 x 50 rm 133/0.70 0.379 1.6 14.5 560 2041 x 70 rm 189/0.70 0.262 1.6 16.5 760 2561 x 95 rm 259/0.70 0.189 1.8 19.0 1030 3141 x 120 rm 336/0.68 .150 1.8 20.5 1260 3661 x 150 rm 392/0.70 0.122 2.0 23.0 1580 423

  • Type: BYAFlame Retardant CablesSpecification: BDS-900 and BS-2004Voltage: 450/750 volts

    1. Copper Conductor

    2. FR-PVC Insulation

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current Rating

    Bunched andEnclosed inConduits TwoCables SinglePhase at35oC

    Clipped to aSurface or ona Cable TrayBunched &Unenclosed 2Cables SinglePhase at 35oC

    no. x mm2 no./mm ohm/km mm mm kg/km amp amp1 x 1.0 re 1/1.13 18.1 0.7 2.8 17 13 161 x 1.5 re 1/1.38 12.1 0.7 3.3 22 16 201 x 1.5 rm 7/0.52 12.1 0.7 3.5 23 16 201 x 2.5 re 7/1.78 7.41 0.8 3.9 35 22 281 x 2.5 rm 7/0.67 7.41 0.8 4.2 36 22 281 x 4.0 rm 7/0.85 4.61 0.8 4.8 55 30 371 x 6.0 rm 7/1.05 3.08 0.8 5.4 75 38 471 x 10 rm 7/1.35 1.83 1.0 6.8 115 52 631 x 16 rm 7/1.71 1.15 1.0 8.0 178 70 851 x 25 rm 7/2.14 0.727 1.2 9.8 275 91 1101 x 35 rm 19/1.53 0.524 1.2 11.0 375 112 1361 x 50 rm 19/1.83 0.387 1.4 12.5 530 136 1641 x 70 rm 19/2.17 0.268 1.4 14.5 720 173 2071 x 95 rm 19/2.52 0.193 1.6 17.0 1000 216 253

    Type: Service Drop CablesVoltage: 600/1000 volts

    1. Copper Conductor

    2. PVC Insulation

    Nominal CrossSectional Areaof Conductor

    No. and Nominal Diameter of WiresMaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    ApproxOverallDiameter

    ApproxWeight ofCable

    CurrentRating at350CAmbientTemp.

    no. x mm2 no./mm ohm/km mm mm kg/km amp2.5 re / 2.5 re 1 x 1.78 / 1 x 1.78 7.41 / 7.41 1.6 10.0 90 274 rm / 4 re 7 x 0.85 / 1 x 2.26 4.61 / 4.61 1.6 11.7 135 354 rm / 6 rm 7 x 0.85 / 7 x 1.05 4.61 / 3.08 1.6 12.0 165 354 rm / 6 re 7 x 0.85 / 1 x 2.77 4.61 / 3.08 1.6 12.0 160 356 rm / 6 re 7 x 1.05 / 1x 2.77 3.08 / 3.08 1.6 12.3 180 4510 rm / 10 rm 7 x 1.35 / 7 x 1.35 1.83 / 1.83 1.6 14.5 270 62

  • 16 rm / 16 rm 7 x 1.71 / 7x 1.71 1.15 /1.15 1.6 16.6 396 8425 rm / 25 rm 7 x 2.14 / 7 x 2.14 0.727 / 0.727 1.6 19.2 595 110

    Type: Service Drop CablesVoltage: 600/1000 volts

    1. Copper Conductor

    2. PVC Insulation

    Nominal Cross Sectional Area ofConductor

    No. and Nominal Diameter ofWires

    MaximumResistanceofConductorat 20o C

    NominalThicknessofInsulation

    ApproxOverallDiameter

    ApproxWeightofCable

    CurrentRating at350CAmbientTemp.

    no. x mm2 no./mm ohm/km mm mm kg/km amp

    3 x 4 rm / 4 re 7 x 0.85 / 1 x 2.26 4.61 /4.61 1.6 15.0 275 32

    3 x 4 rm / 6 re 7 x 0.85 / 1.2.77 4.61 /3.08 1.6 15.5 290 32

    3 x 6 rm / 6 rm 7 x 1.05 / 7 x 1.05 3.08 /3.08 1.6 16.0 370 41

    3 x 10 rm / 10 rm 7 x 1.35 / 7 x 1.35 1.83 /1.83 1.6 18.5 538 56

    3 x 16 rm x 16 rm 7 x 1.71 / 7 x 1.71 1.15 /1.15 1.6 21.0 792 75

    3 x 25 rm / 25 rm 7 x 2.14 / 7 x 2.14 0.727 /0.727 1.6 24.5 1180 98

    Type: Welding CablesVoltage: 200 volts

    1. Copper Conductor

    2. PVC Insulation

    Nominal CrossSectional Area ofConductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at 20o C

    NominalThickness ofSheath

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current Rating atMaximum DutyCycle of 60%

    no. x mm2 no./mm ohm/km mm mm kg/km amp1 x 25 rm 850 / 0.193 0.780 2.1 12.0 320 1691 x 35 rm 1196 / 0.193 0.554 2.1 13.2 430 2151 x 50 rm 1708 / 0.193 0.386 2.1 15.0 590 2641 x 70 rm 2392 / 0.193 0.272 2.2 17.0 790 3301 x 95 rm 3247 / 0.193 0.206 2.2 19.0 950 4051 x 120 rm 4101 / 0.193 0.161 2.2 23.0 1300 473

  • Type: NYYF (Co_Axial Cables)Voltage: 600/1000 volts

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Common Covering

    4. PVC Sheath

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    MaximumResistance ofConductor at20o C

    NominalThickness ofInsulation

    NominalThickness ofSheath

    ApproxOverallDiameter

    ApproxWeight ofCable

    CurrentRating at350C AmbientTemp.

    no. x mm2 no./mm ohm/km mm mm mm kg/km amp1 x 4 rm 19 / 0.53 4.470 1.0 1.4 7.5 90 411 x 6 rm 19 / 0.65 2.920 1.0 1.4 8.5 120 521 x 10 rm 49 / 0.53 1.770 1.2 1.4 10.0 180 721 x 16 rm 49 / 0.65 1.120 1.2 1.4 11.2 250 981 x 25 rm 84 / 0.62 0.708 1.4 1.4 13.0 360 1311 x 35 rm 133 / 0.59 0.514 1.4 1.4 14.5 480 1671 x 50 rm 133 / 0.70 0.379 1.6 1.6 17.5 680 2041 x 70 rm 189 / 0.70 0.262 1.6 1.6 19.5 880 2561 x 95 rm 259 / 0.70 0.189 1.8 1.6 22.0 1164 3141 x 120 rm 336 / 0.68 0.150 1.8 1.8 24.6 1437 3661 x 150 rm 392 / 0.70 0.122 2.0 1.8 27.1 1840 4233 x 1.5 rm 7 / 0.53 12.10 0.8 1.4 11.7 175 173 x 2.5 rm 7 / 0.69 7.28 0.9 1.4 12.0 220 243 x 4 rm 19 / 0.53 4.56 1.0 1.4 13.5 270 333 x 6 rm 19 / 0.65 3.03 1.0 1.6 15.4 408 433 x 10 rm 49 / 0.53 1.81 1.2 1.6 19.6 637 583 x 16 rm 49 / 0.65 1.44 1.2 1.6 22.9 955 783 x 25 rm 84 / 0.62 0.722 1.4 1.8 28.9 1320 1023 x 35 rm 133 / 059 0.524 1.4 1.8 32.0 1900 1254 x 1.5 rm 7 / 0.53 12.10 0.8 1.4 12.0 200 174 x 2.5 rm 7 / 0.69 7.28 0.9 1.4 13.1 270 244 x 4 rm 19 / 0.53 4.56 1.0 1.6 15.3 340 334 x 6 rm 19 / 0.65 3.03 1.0 1.6 17.0 500 434 x 10 rm 49 / 0.53 1.81 1.2 1.6 21.7 780 584 x 16 rm 49 / 0.65 1.44 1.2 1.6 25.5 1135 784 x 25 rm 84 / 0.62 0.722 1.4 1.8 32.2 1640 1024 x 35 rm 133 / 0.59 0.524 1.4 1.8 35.5 2360 125

    Type: PVC Ins. Flexible CableVoltage: 250/440 volts

    1. Copper Conductor

    2. PVC Insulation

  • Nominal CrossSectional Area ofConductor

    No. and NominalDiameter ofWires

    NominalThickness ofInsulation

    Approx OverallDiameter of EachCore

    ApproxWeight ofCable

    Current RatingIn Conduit at35oC AmbientTemp

    In Air at 35oCAmbientTemp.

    no. x mm2 no./inch mm mm kg/km amp amp1 x 0.4 14 / 0.0076 0.635 2.26 9 2 31 x 0.65 23 / 0.0076 0.635 2.57 13 5 61 x 1.1 40 / 0.0076 0.635 2.84 17 11 131 x 2.0 70 / 0.0076 0.635 3.43 25 16 182 x 0.4 14 / 0.0076 0.635 2.26 19 2 32 x 0.65 23 / 0.0076 0.635 2.57 27 5 62 x 2.0 40 / 0.0076 0.635 2.84 35 11 132 x 2.0 70 / 0.0076 0.635 2.26 51 16 18

    Type: PVC Ins. Flexible Flat CableVoltage: 250/440 volts

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Sheath

    Nominal CrossSectional Areaof Conductor

    No. andNominalDiameter ofWires

    NominalThickness ofInsulation

    NominalThickness ofSheath

    ApproxOverallDimension

    ApproxWeight ofCable

    Current RatingIn Conduit at35oC AmbientTemp

    In Air at 35oCAmbientTemp.

    no. x mm2 no./inch mm mm mm kg/km amp amp2 x 0.40 14 / 0.0076 0.635 0.762 6.05 x 3.91 34 3 42 x 0.65 23 / 0.0076 0.635 0.762 6.65 x 4.22 43 6 8

    Type: PVC Ins. FlexibleCircular CableVoltage: 250/440 volts

    1. Copper Conductor

    2. PVC Insulation

    3. PVC Sheath

    Nominal CrossSectional Area ofConductor

    No. andNominalDiameter ofWires

    NominalThickness ofInsulation

    NominalThickness ofSheath

    ApproxOverallDiameter

    ApproxWeight ofCable

    Current Rating

    In ConduitSingle Phaseat 35oCAmbientTemp

    Clipped to aSurface or ona Cable TraySingle Phaseat 35oCAmbientTemp.

    no. x mm2 no./mm mm mm mm kg/km amp amp2 x 0.4 14 / 0.0076 0.635 1.016 6.55 55 3 4

  • 2 x 0.65 23 / 0.0076 0.635 1.016 7.16 68 6 82 x 1.10 40 / 0.0076 0.635 1.016 7.72 83 13 162 x 2.0 70 / 0.0076 0.635 1.27 9.09 119 18 222 x 3.2 110 / 0.0076 0.635 1.27 10.16 155 24 263 x 0.4 14 / 0.0076 0.635 1.016 6.88 64 2 33 x 0.65 23 / 0.0076 0.635 1.016 7.54 78 5 73 x 1.10 40 / 0.0076 0.635 1.016 8.15 100 11 143 x 2.0 70 / 0.0076 0.635 1.27 9.60 145 16 203 x 3.2 110 / 0.0076 0.635 1.27 10.92 195 21 244 x 0.4 14 / 0.0076 0.635 1.016 7.32 70 2 34 x 0.65 23 / 0.0076 0.635 1.016 8.10 93 5 74 x 1.10 40 / 0.0076 0.635 1.27 9.30 129 11 144 x 2.0 70 / 0.0076 0.635 1.27 10.40 175 16 204 x 3.2 110 / 0.0076 0.635 1.27 11.38 225 21 24