  • smart solutions for combustion and environment

    Oil Fired Igniters, Pilots and Oil Guns for Power Plants and Utility Boilers

  • Oil Fired Igniters, Pilots and Oil Guns for Power Plants and Utility Boilers

    2

    Selection Table based on Heat Release, Flame Length, Tube Diameter and Mode of Operation

    Hegwein Fuel Oil Igniters with Lower Heat ReleaseHegwein Dual Fuel IgnitersHegwein Fuel Oil Igniters for Hazardous Areas

    l Compact design with integrated ignition transformer and flame monitor/burner control

    l Built-in flame ionization electrode, ideally locatedl No high-voltage cable required on sitel Guaranteed electromagnetic compatibilityl Rugged, low-maintenance designl Sizes ranging from 100 kW to 3.6 MW

    (333,000 BTU/hr to 12,000,000 BTU/hr)l Custom tube lengths available in 10-mm incrementsl For extra light fuel oil (diesel). Dual fuel igniters can also handle

    either propane/butane or natural gasl Extremely tight and long pilot flame - no automatic retraction

    system typically requiredl Class 1, 2 or 3 igniters according to NFPA also availablel Smoke free flamel Also available for marine diesel operation.

    Please request our detailed brochure on oil and dual fuel fired ignitors.

    Hegwein Oil Guns

    l Immediate light-upl Even spray pattern due to a special nozzle design proved in various

    applicationsl Optimized mixing of fuel oil and combustion air for complete burn-

    outl Stable flame with almost smoke-free combustion and low emissionsl Taylor-made to clients requirements:

    - length - wirler diameter - mounting plate dimensions

    l Reliable operation.

    Questions regarding the proper selection of an igniter?Request our Basic Technical Information. You will find valuable references to the selection of a suitable igniter and its integration into the main burner. Vari-ous plant photographs show the broad palette of the possible applications of our igniters and pilots in all fields of the industry.

    Heat release in oil mode max. 100 kW max. 300 kW max. 1000 kW max. 3600 kW max. 1000 kW max. 1000 kW

    Heat release in gas mode - - - - max. 400 kW max. 1000 kW

    Flame length in oil mode max. 500 mm max. 750 mm max. 2200 mm max. 3000 mm max. 2000 mm max. 2500 mm

    Flame length in gas mode - - - - max. 1500 mm max. 2000 mm

    Tube diameter 50 mm 70 mm 90 mm 160 mm 90 mm 135 mm

    inoilmodeairatomization l l l l l l

    withintegratedsparktransformerand flame monitor

    forintermittentoperation (in oil mode)

    forcontinuousoperation (in gas mode)

    ZAEL0... ZAEL1... ZAEL2... ZAEL4... ZAZL2... ZAZL3...

    explosionproofigniterhead frZone1/forzone1,IP65

    standardZAVEX/EL0... ZAVEX/EL1...

    explosionproofigniterhead inII3GEExnCIICT5

    forzone2,IP65standardZXAEL0... ZXAEL1... ZXAEL2... ZXAEL4...

    Overview

  • Oil Fired Igniters

    Check List for an Igniter Inquiry

    Plant Specification

    Kind of boiler or furnace: ..................................................................................................................................

    Combustionsystem ...................................................................................................................................

    (e.g.fluidizedbed,fluegasreheating/ductburnersetc.)

    Kind of burner (single fuel or multi fuel): ..................................................................................................................................

    Furnace atmosphere: corrosive ( ) yes

    ( ) no

    temperature range from................. to.................

    Burner/igniterinstalledinEx-zone ()yes

    ( ) no

    Applicablestandardsandcodesofpractice: ()EN676(forceddraughtburners) ()EN746/2(ind.thermoproc.equipm.) ()TRD411/412(steamboilers) ()IEC79-10(Ex-zones) ()EN161(shut-oftvalves),gas ()EN298(burnercontrolsforgas) ()EN230(burnercontrolsforoil) ()NFPA

    Igniter Specification

    Requiredheatrelease: oil:..................................kW

    gas:................................kW

    Required flame length: .................... mm

    Oil ( ) extra light fuel oil (diesel)

    ( ) marine diesel

    Gastype(fordualfueligniters): ()naturalgas

    ( ) propane/butane

    Available oil pressure: .................... bar

    Available gas pressure: .................... mbar

    Available combustion air pressure: .................... mbar

    Availableatomizationairpressure: ....................bar

    Furnacepressure,+/- ....................mbar

    Tubelengthofigniter: ....................mm

    Flame monitor for continuous operation required: ( ) yes

    (only ZAZL... in gas mode) ( ) no

    Supplyvoltageandfrequency: ....................V50/60Hz

    IP65protectionrequired: ()yes

    ( ) no

    Transformerpartwithspecialpainting: ()yes

    ( ) no

    Burner arrangement drawing available: ( ) yes

    ( ) no

    HazardousareaInstallation ()Zone1(Div1)

    ()Zone2(Div2) 3

  • Oil Fired Igniters for Extra Light Fuel Oil (Diesel)

    Heat Release max. 1000 kW Heat Release max. 3600 kW Model ZAEL2... Model ZAEL4...Nozzlesizes 40-80kg/h Fuel oil flow max.300kg/h

    Tube 90 mm Tube 160 mm

    Flame length 600 2200 mm Flame length max. 3000 mm

    IgnitertubelengthL 360 5000 mm IgnitertubelengthL 360 5000 mm

    Fuel oil inlet 3/8 Oil inlet 3/8

    Fuel oil pressure 5 bar Fuel oil pressure 5 bar

    Compressedairinlet 1/4 Compressedairinlet 1/2

    Compressedair 5 bar Compressedair 5 bar

    Air inlet 2,mayberotated4timesinstepsof90 Air inlet DN100,mayberotated4timesinstepsof90

    Air pressure 5mbar,dependingontubelength Air pressure 5mbar,dependingontubelength

    Features withintegratedsparktransformerandflame monitor for intermittent operation Featureswithintegratedsparktransformerandflame monitor for intermittent operation

    Transformer part Transformer part

    Ignition 2x5kV,electrodetoelectrode Ignition 2x5kV,electrodetoelectrode

    Ambient temperature -20Cupto+60C Ambient temperature -20Cupto+60C

    Protection IP54 Protection IP54

    Operation Example Operation Example

    Heat release 800kW Heat release 3600kW

    Oil pressure 3.5 barg Oil pressure 3.5 barg

    Compressedair 3 barg Compressedair 3 barg

    Ignitionair 120 m3/h @ 10 mbarg Ignitionair 300 m3/h @ 10 mbarg

    3000 mm2000 mm

    Fuel Oil Flow Fuel Oil Flow

    For ignition of large coal or heavy fuel oil fired burners in utility boilers

    4

  • Oil Guns

    OilGunRetraction

    OilInlet

    HESITip

    OilGunAssembly

    Swirler

    Mounting Plate Assembly

    HESIAssemblywithRetraction

    HESIElectronics

    Diffuser/ Swirler View

    Our experience gathered in several decades of ig-niter manufacturing has gone into the design of these products.

    Featuresl Immediatelight-up

    l Evenspraypatternduetoaspecialnozzledesignprovedinvariousap-plications

    l Optimizedmixingoffueloilandcombustionairforcompleteburnout

    l Stableflamewithalmostsmoke-freecombustionandlowemissions

    l Reliable operation.

    Oil Gun Series D with Mechanical Atomization Oil Gun Series L with Air or Steam Assisted Atomization

    Oil gun model D I D II D III

    Fueloilflowinkg/h 1300 2000 3000

    HeatreleaseMW 15 24 36

    Fuel Oil Flow

    Oil gun ,odel L I L II L III

    Fueloilflowinkg/h 1200 2000 3500

    HeatreleaseMW 14 24 42

    Fuel Oil Flow

    5

    Spra

    y A

    ngle

  • 6Oil Gun Specification

    Requiredheatrelease ........................kW

    orcapacity ........................kg/h

    Atomizationby ()mechanical,oilpressure................bar

    ( ) air and oil pressure ................................ bar/bar

    ( ) steam and oil pressure ................................ bar/bar

    steamtemperature................C

    ( ) other

    Oil type ( ) extra light fuel oil

    ()lightfueloil,viscosity........................cSt

    ( ) heavy fuel oil

    Sprayangle ()standard80

    ()other........................

    Length of oil gun from mounting plate ........................ mm

    Swirler(diffuser)diameter ........................mm

    Flexible version required (tilting) ( ) yes

    ( ) no

    Oil Gun Retraction Unit ( )

    Force ()2800N

    ()other........................N

    Stroke ()300mm

    ( ) other ........................ mm

    Limitswitches ()1xSPDT

    ()1xDPDT

    ()2xDPDT(option)

    HESI Electronics ( )

    Supplyvoltage ........................V,50/60Hz

    ()12J/spark

    ()16J/spark

    ()20J/spark

    HESI Retraction Unit ( )

    Force ()600N

    ()other........................N

    Stroke ()300mm

    ( ) other ........................ mm

    Limitswitches ()1xSPDT

    ()1xDPDT

    ()2xDPDT(option)

    Optical Flame Monitor ( )

    Mountedonbackplate

    Check List for an Oil Gun Inquiry

    Oil Guns

  • Basic Components

    Operation withfueloil#0,#1or#2(diesel)

    Pressureatomization at 30 bar nominal

    Turndown 1:1.5 (with oil pressure)

    Spray angle 82

    Diffuserorswirlerdiameter according to specification 200 to 300 mm

    Cylinder 21/40/80mm

    Force 300upto3000N

    Stroke 200/300/500mm(8/12/20)

    Air pressure 5 to 7 barg (70-100 psig)

    Limit switches 2limitswitchesSPDT,dualairsolenoidcoils

    Voltage 115or230VAC,50/60Hz

    Output energy 16J/sparkat4sparks/s

    Output voltage 1800V

    Dutycycle 300 s / 50%

    Transformerhousingprotection class IP65

    Flexible cable operating voltage 5000 V

    Cylinder 21/40mm

    Force 300upto1000N

    Stroke 200/300mm(8/12)

    Air pressure 5 to 7 barg (70-100psig)

    Limit switches 2limitswitchesSPDT,singleairsolenoidcoil

    Oil Guns

    Rigid Oil Gun with Mechanical Atomization

    Pneumatic Retraction Unit for Oil Gun

    High Energy Spark Igniter D-HG 1600

    Pneumatic Retraction Unit for HESI

    Design compactdesign,flamesensorandcontrolunitbuiltas one unit

    Spectral ranges UV,VIS,IR

    Operation intermittentoperation,permanentoperationand72-hour operation without continuous supervision

    Outputs flamerelay,statusrelay,flameintensity0/4...20mA

    Threshold 10-stage adjustable

    Optical Flame Monitor

    7

    OilGun

    SprayCone

    Spra

    y A

    ngle

    D-LX100

  • smart solutions for combustion and environment

    Hegwein GmbHAm Boschwerk 770469 StuttgartTel. +49 711 135 788-0Fax +49 711 135 788-5E-Mail: [email protected]

    DURAG GmbHKollaustrae 10522453 Hamburg, GermanyTel. +49 40 55 42 18-0Fax +49 40 58 41 54E-Mail: [email protected]

    DURAG Niederlassung NordKollaustrae 10522453 Hamburg, GermanyTel. +49 40 55 42 18-0Fax +49 40 58 41 54E-Mail: [email protected]

    DURAG Niederlassung OstHalsbrcker Strae 3409599 Freiberg, GermanyTel. +49 3731 30 04-0Fax +49 3731 30 04-22E-Mail: [email protected]

    DURAG Niederlassung SdWeidenweg 1673087 Bad Boll, GermanyTel. +49 7164 912 25-0Fax +49 7164 912 25-50 E-Mail: [email protected]

    DURAG Niederlassung WestAn der Pnt 53a40885 Ratingen, GermanyTel. +49 2102 74 00-0Fax +49 2102 74 00 28E-Mail: [email protected]

    InternationalDURAG, Inc., USA1355 Mendota Heights Road Suite 200Mendota Heights MN 55120, USA Tel. +1 651 451-1710Fax +1 651 457-7684E-Mail: [email protected]

    DURAG India Instrumentation Ltd#27/30, 2nd Main RoadIndustrial Town, RajajinagarBengaluru 560 044, IndiaTel. +91 80 2314 5626 / 4215 1191Fax +91 80 2314 5627E-Mail: [email protected]

    DURAG Italia S.r.l.

    28100 Novara, ItalyTel. +39 0321 679569Fax +39 0321 474165E-Mail: [email protected]

    DURAG Instrumentation (Shanghai) Co., Ltd.Room 706, Dibao Plaza, No. 3998 Hongxin Rd.Minhang District, Shanghai , 201103 PR ChinaTel. +21 60732979-206Fax +21 60732980E-Mail: [email protected]

    c/o TMS Planning Inc. 291-2 Umena, Mishima-shi, Shizuoka-ken,411-0816 JapanTel./Fax +81 55 977 3994E-Mail: [email protected]

    RM #1131, Manhattan Building, 36-2, Yeouido-Dong, Yeongdeungpo-Gu, Seoul, KoreaTel. +82 2 761 8970 Fax +82 2 761 8971 E-Mail: [email protected]

    Rua Jos Amaro Pecanha, 5805126-150 Sao Paulo - SP, BrazilTel. +55 11 3902 3306Fax +55 11 3902 2382E-Mail: [email protected]

    DURAG data systems GmbHKollaustrae 105,22453 Hamburg, GermanyTel. +49 40 55 42 18-3000Fax +49 40 55 42 18-3099E-Mail: [email protected]

    DURAG process & systems technology gmbhKollaustrae 10522453 Hamburg, GermanyTel. +49 40 55 42 18-0Fax +49 40 58 41 54E-Mail: [email protected]

    VEREWA Umwelt- und Prozessmesstechnik GmbHKollaustrae 10522453 Hamburg, GermanyTel. +49 40 55 42 18-0Fax +49 40 58 41 54E-Mail: [email protected]

    SMITSVONK Holland B.V.P.O. Box 180, 2700 AD ZoetermeerLoodstraat 57, 2718 RV ZoetermeerNetherlandsTel. +31 79 361 35 33Fax +31 79 361 13 78E-mail: [email protected]

    www.durag.de