bt cables building infrastructure systems catalogue

53
www.btcables.com Cables for BUILDING INFRASTRUCTURE SYSTEMS Edition 1 2015

Upload: sentor-electrical

Post on 24-Jul-2016

281 views

Category:

Documents


9 download

DESCRIPTION

 

TRANSCRIPT

Page 1: Bt cables building infrastructure systems catalogue

www.btcables.com

Cables for BUILDING INFRASTRUCTURE SYSTEMS

Edition 1 2015

Page 2: Bt cables building infrastructure systems catalogue

CONTENTS

CABLE FINDER

BT CABLES – BELDEN EQUIVALENTS

SECTION 1 BT BMS-TECTM - Paired Cables

SECTION 2 BT BMS-TECTM - Multi-Conductor Cables

SECTION 3 BT FIREPRO-TEC™ – Fire Detection and Alarm System Cables

SECTION 4 BT FIREPRO-TEC™ – Fire Resistant Cables

SECTION 5 BT Security-Tec ™– Coaxial Cables

SECTION 6 BT Data-Tec™ - Category LAN Cables

SECTION 7 BT Industrial-Tec™ - DEF Standard Cables

SECTION 8 BT Industrial-Tec™ - Industrial Cables

SECTION 9 BT Industrial-Tec™ – Control Cables

GENERALTECHNICAL INFORMATION

COMPARISON BETWEEN EUROPEAN AND UNITED STATES CABLE DESIGN BASICS

CONVERSIONS

GLOSSARY

BT CABLES PART NUMBER INDEX

[email protected] 2

Page 3: Bt cables building infrastructure systems catalogue

Cable Finder BT BMS-TECTM - Paired Cables

Application Cond.-Size ↓

No. of pairs → 1 2 3 4 5 6 7 8 § Page Screen Sheath

RS-485

24 AWG Foil+ braid

PVC C1189 C1190 C1191 C1192 1.1 24 AWG HFFR C1318 C1319 C1320 C1321 1.1 22 AWG PVC C1080 C1295 C1296 C1297 1.1 22AWG HFFR C1401 C1402 C1403 C1404 1.1

RS-422 24 AWG every pair

a foil

PVC C1382 C1383 C1384 C1386 1.2 G.P. Bus

22 AWG PVC C1196 C1197 C1298 C1299 C1214 1.6 22 AWG HFFR C1281 C1282 C1314 1.6

RS-232 24 AWG Foil PVC C1181 C1182 C1183 C1184 C1185 C1186 C1187 C1188 1.3

Lon Works

0.64 mm no scrn HFFR C1346 C1347 1.5

0.64 mm every

pair a foil HFFR C1348 C1349 1.5

KNX 0.8 mm

Foil PVC C1219 C1217 1.4

0.8 mm HFFR C1220 C1218 1.4

Security & Alarm

18 AWG Foil HFFR C1171 C1172 C1173 C1174 C1175 C1176 1.8

Foil + Braid

HFFR C1418 C1419 C1420 C1421 C1422 C1423 1.8

BMS 0.6 mm² Foil PVC C1381 1.9

Application No. of pairs ↓

AWG conductor size → 22 20 18 16 14 12 Section Page

Screen ↓ Sheath ↓

G.P Bus

1 Yes PVC C1199 C1195 C1193 C1213 C1224 C1313 1.7 1 Yes HFFR C1310 C1308 C1272 C1270 C1305 C1303 1.7 1 No PVC C1301 C1300 C1203 C1198 C1222 C1302 1.7 1 No HFFR C1311 C1309 C1271 C1307 C1306 C1304 1.7

BT BMS-TECTM - Multi-Conductor Cables

Cond. Size AWG↓

No. of conductors → 2 3 4 6 8 Section Page

Sheath ↓ Screen

22 PVC

Yes C1226 C1228 C1230 C1264 C1232 2.1 No C1227 C1278 C1231 C1265 C1233 2.1

HFFR Yes C1741 C1743 C1745 C1747 C1749 2.2 No C1742 C1744 C1746 C1748 C1750 2.2

20 PVC

Yes C1019 C1021 C1023 C1260 C1262 2.1 No C1020 C1022 C1024 C1261 C1263 2.1

HFFR Yes C1731 C1733 C1735 C1737 C1739 2.2 No C1732 C1734 C1736 C1738 C1740 2.2

18

PVC Yes C1013 C1015 C1017 C1211 C1258 2.1 No C1014 C1016 C1018 C1212 C1259 2.1

HFFR Yes C1721 C1723 C1725 C1727 C1729 2.2 No C1722 C1724 C1726 C1728 C1730 2.2

UV-HFFR Yes C1351 C1352 C1353 C1354 C1355 2.3

16

PVC Yes C1007 C1009 C1011 C1252 C1254 2.1 No C1008 C1010 C1012 C1253 C1255 2.1

HFFR Yes C1711 C1713 C1715 C1717 C1719 2.2 No C1712 C1714 C1716 C1718 C1720 2.2

UV-HFFR Yes C1391 C1392 C1393 C1394 C1395 2.3

14 PVC

Yes C1001 C1003 C1005 C1248 C1250 2.1 No C1002 C1004 C1006 C1249 C1251 2.1

HFFR Yes C1701 C1703 C1705 C1707 C1709 2.2 No C1702 C1704 C1706 C1708 C1710 2.2

12 PVC

Yes C1322 C1324 C1326 C1330 C1332 2.1 No C1323 C1325 C1327 C1331 C1333 2.1

HFFR Yes C1334 C1336 C1338 C1342 C1344 2.2 No C1335 C1337 C1339 C1343 C1345 2.2

No. of conductors

Conductor size → 22 AWG 20 AWG 18 AWG Section Page

Sheath ↓ Screen 3 PVC Yes C1215 C1245 C1225 ?

Multi-Conductor Power Limited Tray Cables (PLTC) are available on request

[email protected] 3

Page 4: Bt cables building infrastructure systems catalogue

BT FIREPRO-TEC™ – Fire Detection and Alarm System Cables

Application No. of pairs ↓

Cond. size → AWG 18

AWG 16

AWG 14

AWG 12

Section Page Screen ↓ Sheath ↓

Fire Alarm 1 Yes PVC C1040 C1041 C1042 C1043 3 1 No PVC C1135 C1136 C1137 C1138 3

BT FIREPRO-TEC™ – Fire Resistant Cables

Application No. of

cores ↓ Cond. size → 0.75

mm2 1.0

mm2 1.5

mm2 2.5

mm2 4.0

mm2 Section Page

Screen ↓ Sheath ↓

Circuit integrity

1 No HFFR C1760 C1761 4 2 Yes HFFR C1284 C1283 C1044 C1045 C1289 4 2 No HFFR C1139 C1140 C1141 C1142 C1143 4 3 Yes HFFR C1159 C1160 C1161 C1162 C1163 4 3 No HFFR C1149 C1150 1151 C1152 C1153 4

BT Security-Tec ™– Coaxial Cables

Application Inner

Conductor Screen Sheath RG-59 RG-6 RG-11 Section Page

CCTV Solid BC Braid BC PVC C1028 C1029 C1030 5.1 Solid BC Braid BC HFFR C1428 C1429 C1430 5.1 Flex BC Braid BC PVC C1275 C1276 C1277 5.1

SMATV CATV

CCS Foil+Alu Braid PVC C1025 C1026 C1027 5.2 CCS Quad screen PVC C1256 C1257 C1241 5.2

HDTV Solid BC Foil+TC Braid PVC C1229 C1279 C1280 5.3 Solid BC Foil+TC Braid HFFR C1378 C1379 C1380 5.3

50 Ohm Coaxial cables are available on request BT Data-Tec™ - Category LAN Cables

Cat. type Sheath 2 pairs 6 prs 12 prs 25 prs 50 prs 100 prs 150 prs 200 prs section Page Cat 3 PVC C1031 C1266 C1267 C1032 C1033 C1034 C1268 C1269 6.4

Cat. types Sheath UTP UTP-UL FTP FTP-UL U-FTP S-FTP Section Page

Cat 5e PVC C1035 C1285 C1036 C1286 6.1

HFFR C1235 C1236 6.1

Cat 5e-patch

PVC C1500 C1520 6.3 HFFR C1510 C1530 6.3

Cat 6 PVC C1037 C1287 C1038 C1288 6.1

HFFR C1237 C1238 6.1 Cat 6-patch PVC C1540 C1560 6.3

HFFR C1550 C1570 6.3

Cat 6a PVC C1055 C1056 C1057 6.2

HFFR C1200 C1052 C1053 6.2 Cat 7 HFFR C1039 6.2 Cat 7a HFFR C1201 6.2

[email protected] 4

Page 5: Bt cables building infrastructure systems catalogue

BT Industrial-Tec™ - DEF Standard Cables

Conductor 7 x 0.1 mm = 0.055 mm² No. of cores 2 3 4 6 9 15 25 36 50 section Page Screened C1164 C1165 C1166 C1168 C1169 C1365 7 Unscreened C1360 C1361 C1362 C1144 C1145 C1146 C1147 C1148 C1364 7

Conductor 7 x 0.2mm = 0.22 mm² No. of cores 2 3 4 6 8 12 20 36 section Page Screened C1171 C1172 C1173 C1174 C1175 C1176 7 Unscreened C1366 C1367 C1368 C1369 C1154 C1155 C1156 C1157 7

Conductor 16 x 0.2mm = 0.5 mm² No. of cores 2 3 4 6 12 18 section Page Screened C1177 C1178 C1375 C1180 7 Unscreened C1158 C1370 C1371 C1372 C1373 C1374 7

BT Industrial-Tec™ - Industrial Cables

BS(PAS) 5308 – Part 2 – Type 1 – Collectively Screened – Unarmoured cables No. of pairs 1 2 5 10 20 section Page Conductor 0.5 mm² (16x0.2 mm) C1081 C1082 C1083 C1084 C1085 8 Conductor 0.75 mm² (24x0.2 mm) C1086 C1087 C1088 C1089 C1090 8 Conductor 1.5 mm² (7x0.53 mm) C1091 C1092 C1093 C1094 C1095 8

BS(PAS) 5308 – Part 2 – Type 1 – Collectively Screened – Armoured cables No. of pairs 1 2 5 10 20 section Page Conductor 0.5 mm² (16x0.2 mm) C1096 C1097 C1098 C1099 C1100 8 Conductor 0.75 mm² (24x0.2 mm) C1101 C1102 C1103 C1104 C1105 8 Conductor 1.5 mm² (7x0.53 mm) C1106 C1107 C1108 C1109 C1110 8

BS(PAS) 5308 – Part 2 – Type 1 – Individually & Collectively Screened – Unarmoured cables No. of pairs 2 5 10 20 section Page Conductor 0.5 mm² (16x0.2 mm) C1111 C1112 C1113 C1114 8 Conductor 0.75 mm² (24x0.2 mm) C1115 C1116 C1117 C1118 8 Conductor 1.5 mm² (7x0.53 mm) C1119 C1120 C1121 C1122 8

BS(PAS) 5308 – Part 2 – Type 1 – Individually & Collectively Screened – Armoured cable No. of pairs 2 5 10 20 section Page Conductor 0.5 mm² (16x0.2 mm) C1123 C1124 C1125 C1126 8 Conductor 0.75 mm² (24x0.2 mm) C1127 C1128 C1129 C1130 8 Conductor 1.5 mm² (7x0.53 mm) C1131 C1132 C1133 C1134 8

[email protected] 5

Page 6: Bt cables building infrastructure systems catalogue

BT Industrial-Tec™ - Control Cables

YY Series (N stranded cores surrounded by a PVC sheath) No. of cores 3 4 5 7 8 12 18 section Page Conductor 0.75 mm² (24x0.2 mm) C1631 C1635 C1645 C1648 9 Conductor 1.0 mm² (32x0.2 mm) C1632 C1636 9 Conductor 1.5 mm² (30x0.24 mm) C1633 C1637 C1639 C1641 C1643 C1646 C649 9 Conductor 2.5 mm² (50x0.24 mm) C1634 C1638 C1640 C1642 C1644 C1647 C1650 9

CY Series (N stranded cores surrounded by a braiding plus a PVC sheath) No. of cores 3 4 5 section Page Conductor 0.75 mm² (24x0.2 mm) C1620 C1624 9 Conductor 1.0 mm² (32x0.2 mm) C1621 C1625 9 Conductor 1.5 mm² (30x0.24 mm) C1622 C1626 C1628 9 Conductor 2.5 mm² (50x0.24 mm) C1623 C1627 C1629 9

SY Series (N stranded cores surrounded by Steel Wire Armouring plus a PVC sheath) No. of cores 2 3 4 5 7 12 18 25 section Page Conductor 0.75 mm² (24x0.2 mm) C1655 9 Conductor 1.0 mm² (32x0.2 mm) C1651 C1656 C1660 C1665 C1669 C1671 C1673 C1675 9 No. of cores 2 3 4 5 6 7 12 18 Conductor 1.5 mm² (30x0.24 mm) C1652 C1657 C1661 C1666 C1668 C1670 C1672 C1674 9 Conductor 2.5 mm² (50x0.24 mm) C1658 C1662 9 Conductor 4.0 mm² (56x0.29 mm) C1659 C1663 9 Conductor 6.0 mm² (84x0.29 mm) C1664 9

[email protected] 6

Page 7: Bt cables building infrastructure systems catalogue

BT Cables - Belden equivalents

Belden P/N BT Cables P/N Conductor SizeNo. of

ConductorsNo. of Pairs

Individually shielded

pairs

Collective shield

Jacket BT Cables Brand and Additional Data

1030A C1223 16(7*24) AWG 1 Yes PVC 300V PL Tray Cable1043A C1078 16 (7*24) AWG 16 Yes Yes PVC 600V Tray Cable1044A C1077 16 (7*24) AWG 20 Yes Yes PVC 600V Tray Cable1064A C1076 18 (7*26) AWG 4 Yes Yes PVC 600V Tray Cable1067A C1074 18 (7*26) AWG 16 Yes Yes PVC 600V Tray Cable1467A C1075 18 (7*26) AWG 8 Yes Yes PVC 300V PL Tray Cable1505A C1229 20 AWG 1 Yes PVC RG-59 Coaxial Cable (BC)1523A C1027 14 AWG 1 Yes PVC RG11 Coaxial Cable (CCS)1583A C1035 24 AWG 4 CAT 5E UTP Cable1617A C1241 14 AWG 1 Yes PVC RG-11 Quad Shield Coaxial Cable (CCS)1633E C1036 24 AWG 4 yes PVC CAT 5E FTP Cable1694A C1279 18 AWG 1 Yes PVC RG-6 Coaxial Cable (BC)

1885ENH C1039 23 AWG 4 Yes Yes PVC CAT 7 ISTP Cable3079E C1315 22 (7*30) AWG 1 Yes PVC Profibus DP 3105A C1080 22 (7*30) AWG 2 Yes PVC RS-485 Computer Cable3107A C1295 22 (7*30) AWG 2 Yes PVC RS-485 Low Cap Computer Cable3108A C1296 22 (7*30) AWG 3 Yes PVC RS-485 Computer Cable3109A C1297 22 (7*30) AWG 4 Yes PVC RS-485 Computer Cable4000FE C1334 12 (19*25) AWG 2 Yes HFFR BMS-HFFR cables

4000UE C1335 12 (19*25) AWG 2 HFFR BMS-HFFR cables

4001UE C1337 12 (19*25) AWG 3 HFFR BMS-HFFR cables

4100FE C1701 14 (19*27) AWG 2 Yes HFFR BMS-HFFR cables

4100UE C1702 14 (19*27) AWG 3 HFFR BMS-HFFR cables

4101UE C1704 14 (19*27) AWG 3 HFFR BMS-HFFR cables

4102UE C1706 14 (19*27) AWG 4 HFFR BMS-HFFR cables

4200FE C1711 16 (19*29) AWG 2 Yes HFFR BMS-HFFR cables

4200UE C1712 16 (19*29) AWG 2 HFFR BMS-HFFR cables

4201FE C1713 16 (19*29) AWG 3 Yes HFFR BMS-HFFR cables

4201UE C1714 16 (19*29) AWG 3 HFFR BMS-HFFR cables

4202FE C1715 16 (19*29) AWG 4 Yes HFFR BMS-HFFR cables

4202UE C1716 16 (19*29) AWG 4 HFFR BMS-HFFR cables

4300FE C1721 18 (7*26) AWG 2 Yes HFFR BMS-HFFR cables

4300UE C1722 18 (7*26) AWG 2 HFFR BMS-HFFR cables

4301FE C1723 18 (7*26) AWG 3 Yes HFFR BMS-HFFR cables

4301UE C1724 18 (7*26) AWG 3 HFFR BMS-HFFR cables

4302FE C1725 18 (7*26) AWG 4 Yes HFFR BMS-HFFR cables

4302UE C1726 18 (7*26) AWG 4 HFFR BMS-HFFR cables

4304FE C1727 18 (7*26) AWG 6 Yes HFFR BMS-HFFR cables

4304UE C1728 18 (7*26) AWG 6 HFFR BMS-HFFR cables

4306FE C1729 18 (7*26) AWG 8 Yes HFFR BMS-HFFR cables

4306UE C1730 18 (7*26) AWG 8 HFFR BMS-HFFR cables

4400FE C1731 20 (7*28) AWG 2 Yes HFFR BMS-HFFR cables

4400UE C1732 20 (7*28) AWG 2 HFFR BMS-HFFR cables

4401FE C1733 20 (7*28) AWG 3 Yes HFFR BMS-HFFR cables

4402FE C1735 20 (7*28) AWG 4 Yes HFFR BMS-HFFR cables

4402UE C1736 20 (7*28) AWG 4 HFFR BMS-HFFR cables

4500FE C1741 22 (7*30) AWG 2 Yes HFFR BMS-HFFR cables

4500UE C1742 22 (7*30) AWG 2 HFFR BMS-HFFR cables

4501FE C1743 22 (7*30) AWG 3 Yes HFFR BMS-HFFR cables

4501UE C1744 22 (7*30) AWG 3 HFFR BMS-HFFR cables

4502FE C1745 22 (7*30) AWG 4 Yes HFFR BMS-HFFR cables

4502UE C1746 22 (7*30) AWG 4 HFFR BMS-HFFR cables

4504FE C1747 22 (7*30) AWG 6 Yes HFFR BMS-HFFR cables

4504UE C1748 22 (7*30) AWG 6 HFFR BMS-HFFR cables

4506FE C1749 22 (7*30) AWG 8 Yes HFFR BMS-HFFR cables

4506UE C1750 22 (7*30) AWG 8 HFFR BMS-HFFR cables

5100FE C1001 14 (19*27) AWG 2 Yes PVC BMS-PVC cables5100UE C1002 14 (19*27) AWG 2 PVC BMS-PVC cables5101FE C1003 14 (19*27) AWG 3 Yes PVC BMS-PVC cables5101UE C1004 14 (19*27) AWG 3 PVC BMS-PVC cables5102FE C1005 14 (19*27) AWG 4 Yes PVC BMS-PVC cables5102UE C1006 14 (19*27) AWG 4 PVC BMS-PVC cables5200FE C1007 16 (19*29) AWG 2 Yes PVC BMS-PVC cables5200UE C1008 16 (19*29) AWG 2 PVC BMS-PVC cables5201FE C1009 16 (19*29) AWG 3 Yes PVC BMS-PVC cables5201UE C1010 16 (19*29) AWG 3 PVC BMS-PVC cables5202FE C1011 16 (19*29) AWG 4 Yes PVC BMS-PVC cables5202UE C1012 16 (19*29) AWG 4 PVC BMS-PVC cables5300FE C1013 18 (7*26) AWG 2 Yes PVC BMS-PVC cables5300UE C1014 18 (7*26) AWG 2 PVC BMS-PVC cables5301FE C1015 18 (7*26) AWG 3 Yes PVC BMS-PVC cables5301UE C1016 18 (7*26) AWG 3 PVC BMS-PVC cables5302FE C1017 18 (7*26) AWG 4 Yes PVC BMS-PVC cables5302UE C1018 18 (7*26) AWG 4 PVC BMS-PVC cables5305FE C1239 18 (7*26) AWG 7 PVC BMS-PVC cables5400FE C1019 20 (7*28) AWG 2 Yes PVC BMS-PVC cables5400UE C1020 20 (7*28) AWG 2 PVC BMS-PVC cables5401FE C1021 20 (7*28) AWG 3 Yes PVC BMS-PVC cables5401UE C1022 20 (7*28) AWG 3 PVC BMS-PVC cables5402FE C1023 20 (7*28) AWG 4 Yes PVC BMS-PVC cables5402UE C1024 20 (7*28) AWG 4 PVC BMS-PVC cables7731A C1280 14 AWG 1 Yes PVC RG-11 Coaxial Cable (BC)7860E C1038 23 AWG 4 Yes CAT6 FTP Cable7965E C1037 23 AWG 4 CAT 6 UTP Cable 8205 C1300 20 (7*28) AWG 1 PVC High Conductivity Speaker and BMS-PVC-TC Cable

8205NH C1415 20 (7*28) AWG 1 HFFR High Conductivity Speaker and BMS-PVC-TC Cable8259 C1046 20 (10*33) AWG 1 Yes PVC RG-58 Coaxial Cable8442 C1301 22 (7*30) AWG 1 PVC High Conductivity Speaker and BMS-PVC-TC Cable

8442NH C1416 22 (7*30) AWG 1 HFFR BMS-HFFR cables

8471 C1198 16 (19*29) AWG 1 PVC High Conductivity Speaker and BMS-PVC-TC Cable8471NH C1307 16 (19*29) AWG 1 HFFR BMS-HFFR cables

8473 C1222 14 (19*27) AWG 2 PVC High Conductivity Speaker and BMS-PVC-TC Cable8473NH C1306 14 (19*27) AWG 2 HFFR BMS-HFFR cables

[email protected] 7

Page 8: Bt cables building infrastructure systems catalogue

BT Cables - Belden equivalents

Belden P/N BT Cables P/N Conductor SizeNo. of

ConductorsNo. of Pairs

Individually shielded

pairs

Collective shield

Jacket BT Cables Brand and Additional Data

8477 C1302 12 (19*25) AWG 1 PVC High Conductivity Speaker and BMS-PVC-TC Cable8477NH C1417 12 (19*25) AWG 1 HFFR BMS-HFFR cables

8718NH C1303 12 (19*25) AWG 1 Yes HFFR BMS-HFFR cables

8719 C1213 16 (19*29) AWG 2 Yes PVC High Conductivity Speaker and BMS-PVC-TC Cable8719NH C1270 16 (19*29) AWG 2 HFFR BMS-HFFR cables

8720 C1224 14 (19*27) AWG 2 Yes PVC High Conductivity Speaker and BMS-PVC-TC Cable8720NH C1305 14 (19*27) AWG 2 Yes HFFR BMS-HFFR cables

8723 C1196 22 (7*30) AWG 2 Yes PVC Individually Shielded TP BMS-PVC-TC Cable8723NH C1281 22 (7*30) AWG 2 Yes HFFR Individually Shielded TP BMS-HFFR-TC Cable8723PE C1316 22 (7*30) AWG 2 Yes PE Individually Shielded TP BMS-PE-TC Cable

8760 C1193 18 (7*26) AWG 1 Yes PVC High Conductivity Speaker and BMS-PVC-TC Cable8760NH C1272 18 (7*26) AWG 1 Yes HFFR BMS-HFFR cables

8761 C1199 22 (7*30) AWG 1 Yes PVC High Conductivity Speaker and BMS-PVC-TC Cable8761NH C1310 22 (7*30) AWG 1 Yes HFFR BMS-HFFR cables

8762 C1195 20 (7*28) AWG 1 Yes PVC High Conductivity Speaker and BMS-PVC-TC Cable8762NH C1308 20 (7*28) AWG 1 Yes HFFR BMS-HFFR cables

8770 C1225 18 (7*26) AWG 3 Yes PVC High Conductivity Speaker and BMS-PVC-TC Cable8772 C1245 20 (7*28) AWG 3 Yes PVC High Conductivity Speaker and BMS-PVC-TC Cable8777 C1197 22 (7*30) AWG 3 Yes PVC Individually Shielded TP BMS-PVC-TC Cable

8777NH C1282 22 (7*30) AWG 3 Yes HFFR Individually Shielded TP BMS-HFFR-TC Cable8777PE C1317 22 (7*30) AWG 3 Yes PE Individually Shielded TP BMS-PE-TC Cable

8778 C1214 22 (7*30) AWG 6 Yes PVC Individually Shielded TP BMS-PVC-TC Cable8778NH C1314 22 (7*30) AWG 6 Yes HFFR Individually Shielded TP BMS-HFFR-TC Cable

9100 C1025 20 AWG 1 Yes PVC RG-59 Coaxial Cable (CCS)9116 C1026 18 AWG 1 Yes PVC RG-6 Coaxial Cable (CCS)9259 C1275 20 (19*33) 1 Yes PVC RG-59 Coaxial CCTV cable

9463F C1079 20 (42*36) AWG 1 Yes PVC Twinax - Blue Hose cable9501 C1181 24 (7*32) AWG 1 Yes PVC RS-232 Computer Cable

9501NH C1441 24 (7*32) AWG 1 Yes HFFR RS-232 Computer Cable9501PE C1451 24 (7*32) AWG 1 Yes PE RS-232 Computer Cable

9502 C1182 24 (7*32) AWG 2 Yes PVC RS-232 Computer Cable9502NH C1442 24 (7*32) AWG 2 Yes HFFR RS-232 Computer Cable9502PE C1452 24 (7*32) AWG 2 Yes PE RS-232 Computer Cable

9503 C1183 24 (7*32) AWG 3 Yes PVC RS-232 Computer Cable9503NH C1443 24 (7*32) AWG 3 Yes HFFR RS-232 Computer Cable9503PE C1453 24 (7*32) AWG 3 Yes PE RS-232 Computer Cable

9504 C1184 24 (7*32) AWG 4 Yes PVC RS-232 Computer Cable9504NH C1444 24 (7*32) AWG 4 Yes HFFR RS-232 Computer Cable9504PE C1454 24 (7*32) AWG 4 Yes PE RS-232 Computer Cable

9505 C1185 24 (7*32) AWG 5 Yes PVC RS-232 Computer Cable9505NH C1445 24 (7*32) AWG 5 Yes HFFR RS-232 Computer Cable9505PE C1455 24 (7*32) AWG 5 Yes PE RS-232 Computer Cable

9506 C1186 24 (7*32) AWG 6 Yes PVC RS-232 Computer Cable9506NH C1446 24 (7*32) AWG 6 Yes HFFR RS-232 Computer Cable9506PE C1456 24 (7*32) AWG 6 Yes PE RS-232 Computer Cable

9507 C1187 24 (7*32) AWG 7 Yes PVC RS-232 Computer Cable9507NH C1447 24 (7*32) AWG 7 Yes HFFR RS-232 Computer Cable9507PE C1457 24 (7*32) AWG 7 Yes PE RS-232 Computer Cable

9508 C1188 24 (7*32) AWG 8 Yes PVC RS-232 Computer Cable9508NH C1448 24 (7*32) AWG 8 Yes HFFR RS-232 Computer Cable9508PE C1458 24 (7*32) AWG 8 Yes PE RS-232 Computer Cable9510NH C1206 24 (7*32) AWG 10 Yes PVC RS-232 Computer Cable9510NH C1449 24 (7*32) AWG 10 Yes HFFR RS-232 Computer Cable9536 NH C1358 24 (7*32) AWG 6 Yes HFFR RS-232 Computer Cable

9536 C1398 24 (7*32) AWG 6 Yes PVC RS-232 Computer Cable9538 C1399 24 (7*32) AWG 8 Yes PVC RS-232 Computer Cable

9538NH C1359 24 (7*32) AWG 8 Yes HFFR RS-232 Computer Cable9540 C1400 24 (7*32) AWG 10 Yes PVC RS-232 Computer Cable9571 C1135 18 AWG 1 PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed

9572 C1136 16 AWG 1 PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed

9574 C1040 18 AWG 2 Yes PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed

9575 C1041 16 AWG 2 Yes PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed

9580 C1137 14 AWG 1 PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed

9581 C1042 14 AWG 2 Yes PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed

9582 C1138 12 AWG 1 PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed

9583 C1043 12 AWG 2 Yes PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed

9728 C1384 24 (7*32) AWG 4 Yes PVC Low Cap Computer Cable9729 C1382 24 (7*32) AWG 2 Yes PVC Low Cap Computer Cable9730 C1383 24 (7*32) AWG 1 Yes PVC Low Cap Computer Cable9740 C1203 18 (7*26) AWG 1 PVC High Conductivity Speaker and BMS-PVC-TC Cable

9740NH C1271 18 (7*26) AWG 1 HFFR BMS-HFFR cables

9773 C1298 22 (7*30) AWG 4 Yes PVC Individually Shielded TP BMS-PVC-TC Cable9774 C1299 22 (7*30) AWG 5 Yes PVC Individually Shielded TP BMS-PVC-TC Cable9841 C1189 24 (7*32) AWG 1 PVC RS-485 Low Cap Computer Cable

9841NH C1318 24 (7*32) AWG 1 HFFR RS-485 Low Cap Computer Cable9841PE C1409 24 (7*32) AWG 1 PE RS-485 Low Cap Computer Cable

9842 C1190 24 (7*32) AWG 2 PVC RS-485 Low Cap Computer Cable9842NH C1319 24 (7*32) AWG 2 HFFR RS-485 Low Cap Computer Cable

9843 C1191 24 (7*32) AWG 3 PVC RS-485 Low Cap Computer Cable9843NH C1320 24 (7*32) AWG 3 HFFR RS-485 Low Cap Computer Cable

9844 C1192 24 (7*32) AWG 4 PVC RS-485 Low Cap Computer Cable9844NH C1321 24 (7*32) AWG 4 HFFR RS-485 Low Cap Computer Cable

9913 C1047 10 AWG 1 Yes PVC RG-8 Series Coaxial Cable1227A1 C1031 24 AWG 2 PVC CAT 3 UTP Cable1232A1 C1032 24 AWG 25 PVC CAT 3 UTP Cable43051 C1208 0.4 mm 8 Yes PVC 8 Pair/0.4 Braided Telecoms Cable43113 C1207 26 AWG 1 Yes HFFR TELCO 75 Ohm Coaxial Cable

513945 C1030 14 AWG 1 Yes PVC RG-11 Coaxial Cable (BC)533945 C1029 18 AWG 1 Yes PVC RG6 Series Coaxial Cable (BC)543945 C1028 20 AWG 1 Yes PVC RG-59 Coaxial Cable (BC)9842NH C1319 24 (7*32) AWG 2 Yes HFFR 2 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket9842PE C1410 24 (7*32) AWG 2 Yes PE 2 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket9843NH C1320 24 (7*32) AWG 3 Yes HFFR 3 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket

[email protected] 8

Page 9: Bt cables building infrastructure systems catalogue

BT Cables - Belden equivalents

Belden P/N BT Cables P/N Conductor SizeNo. of

ConductorsNo. of Pairs

Individually shielded

pairs

Collective shield

Jacket BT Cables Brand and Additional Data

9843PE C1411 24 (7*32) AWG 3 Yes PE 3 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket9844NH C1321 24 (7*32) AWG 4 Yes HFFR 4 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket9844PE C1412 24 (7*32) AWG 4 Yes PE 4 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket

MRG2130 C1048 2.25 (7*0.75) mm 1 Yes PVC RG213 Series Coaxial cableMRG214 C1049 2.25 (7*0.75) mm 1 Yes PVC RG214 Series Coaxial CableYE00819 C1219 0.8 1 Yes PVC KNX (was EIB) CABLEYE00820 C1217 0.8 2 Yes PVC KNX (was EIB) CABLEYE00905 C1220 0.8 1 Yes HFFR KNX (was EIB) CABLEYE00906 C1218 0.8 2 Yes HFFR KNX (was EIB) CABLE

[email protected] 9

Page 10: Bt cables building infrastructure systems catalogue

Section 1 - BT BMS-TECTM - Paired Cables PVC, PE or HFFR sheathed cables for BUS and Interface Systems 1. Application RS-232, RS-422, RS-485, KNX (EIB or Instabus), LonWorks, ModBus, M-Bus, CAN-bus, BACnet, BMS (Building Management Systems) or general interface systems. 2. Basic Construction of the cables Wire = conductor without or with insulation. With insulation sometimes also indicated as core. Conductor: may be solid = one single rod or flexible = twisted bare or tinned copper strands, ranging from 12 to 24AWG.

Conductor (AWG)

Configuration(AWG)

Configuration(mm)

DC Resistance (Ohm/km)

24 7 x 32 7 x 0.20 ≤ 88 22 7 x 30 7 x 0.25 ≤ 57.4 20 7 x 28 7 x 0.32 ≤ 32.16 18 7 x 26 7 x 0.40 ≤ 22.7 16 19 x 29 19 x 0.28 ≤ 15.47 14 19 x 27 19 x 0.36 ≤ 9.36 12 19 x 25 19 x 0.45 ≤ 5.61

Insulation: Polyethylene (PE) or Foam PE (FPE) for PVC (Polyvinyl Chloride) or Halogen-Free (HFFR) sheathed cables. And Halogen-Free (HFFR) for HFFR sheathed cables. All insulations are in accordance with BS EN 50290-2, good strippable and coloured. The colours are not interchangeable. Pair = two twisted – colour coded – wires. Individually screened pair (if applicable): one pair wrapped with an Aluminium/Polyester foil under which a drain wire. Cable core: two or more (individually screened) pairs stranded. Good twisting (lay-length < 30 ~ 40D) is necessary otherwise the cable can hardly be bending and will break after a few bends. Drain wire (only in combination with a screen): stranded tinned copper wires. In order to avoid corrosion, it is recommended that drain wires are tinned. Screen (if applicable): Helically applied (= as a spiral) Aluminium/Polyester (Alpet) foil. For the flexibility of a cable a helically applied foil is to be preferred. A longitudinally applied foil act more as a stiff tube = more difficult to bend. Braiding (if applicable): tinned copper wires. Sheath: grey PVC , black PE or purple HFFR, all in accordance with BS EN 50290-2.

Cable Configuration Cable Retardancy

LowSmoke

Halogen-free (non acid, non toxic)

RoHScompliant Insulation Sheath

PE, FPE or PVC PVC according to IEC 60332-1

No No Yes

PE, FPE or PVC PE No No Only with (F)PE insulation Yes

PE, FPE or HFFR HFFR according to IEC 60332-3-24

according to IEC 61034-1-2

according to IEC 60754-1 & 2

Yes

Operating temperature range: -25 to +75 °C and Rated Voltage: 300 Vrms

[email protected] 10

Page 11: Bt cables building infrastructure systems catalogue

RS-232: Hand shake interface used for low data rates. Computer to printer or to modem or to another device.

RS-422: Balanced digital circuit. Medium speed data exchange. Long line modems and Daisy chain configuration.

RS-485: Balanced digital circuit. Medium speed fieldbus interfaces.

RS-232 RS-422 RS-485

Differential no yes yesMax. number of drivers Max. number of receivers

11

110

132

Modes of operation full duplex half duplex half duplexNetwork topology point-to-point multidrop multidropMax. distance acc. to standard 15 m 1200 m 1200 mMax. speed at 12 m. Max. speed at 1200 m.

20 kbs1 kbs

10 Mbs 100 kbs

35 Mbs100 kbs

Cables used

Conductor size mainly 24 AWG mainly 24 AWG mainly 24 AWGNumber of conductors 6 to 25 2 pairs or more 1 pair or moreImpedance not defined 100 Ohm 120 OhmBT Cables main part numbers see section 1.3 section 1.2 section 1.1 KNX is a standardised (EN 50090, ISO/IEC 14543), OSI-based network communications protocol for intelligent buildings. KNX is the successor to, and convergence of, three previous standards: the European Home Systems Protocol (EHS), BatiBUS, and the European Installation Bus (EIB or Instabus). BT Cables main part numbers for KNX cables: C1217 (quad – PVC) – C1218 (quad – HFFR) – C1219 (1 pair – PVC) – C1220 (1 pair – HFFR). LonWorks is a networking platform specifically created to address the needs of control applications. The platform is built on a protocol created by Echelon Corporation for networking devices over media such as twisted pair, power lines, fibre optics, and RF. It is used for the automation of various functions within buildings such as lighting and HVAC. BT Cables main part numbers for LonWorks: C1198 (PVC) - C1203 (PVC) – C1307 (HFFR) – C1271 (HFFR) – C1346 (HFFR) – C1347 (HFFR) – C1348 (HFFR) and C1349 (HFFR). Modbus is a serial communications protocol published by Modicon in 1979 for use with its programmable logic controllers (PLCs). Simple and robust, it has since become one of the de facto standard communications protocols in the industry. BT Cables main part numbers for Modbus: C1197 (PVC) - C1193 (PVC) – C1282 (HFFR) – C1272 (HFFR). M-Bus (Meter-Bus) is a European standard (EN 13757-2 physical and link layer, EN 13757-3 application layer) for the remote reading of gas or electricity meters. M-Bus is also usable for other types of consumption meters. BT Cables main part number for M-bus: C1020 – C1193. Controller–area network (CAN or CAN-bus) is a vehicle bus standard designed specifically for automotive applications but now also used in other areas such as industrial automation and medical equipment. CAN bus utilize TIA/EIA-485 cables. BT Cables main part numbers for CAN-bus: C1080 - C1189 – C1190 – C1191 – C1192 – C1295 – C1296 – C1297 and HFFR cables C1318 – C1319 – C1320 – C1321. BACnet is a communications protocol for building automation and control networks. It is was designed to allow communication of building automation and control systems for applications such as heating, ventilating, and air-conditioning control, lighting control, access control, and fire detection systems and their associated equipment. BACnet over IP can utilize Cat 6. BT Cables main part numbers for BACnet: C1228 (PVC) – C1189 (PVC) – C1190 (PVC) - C1318 (HFFR) and C1319 (HFFR).

[email protected] 11

Page 12: Bt cables building infrastructure systems catalogue

Section 1.1 Paired Cables for TIA/EIA-485 = RS-485 applications 22 and 24AWG conductors – PE or FPE insulation – Dual Screen - PVC or HFFR sheath CABLE DESCRIPTION

1. Conductor Flexible Tinned Copper

2. Insulation Polyethylene (PE) or Foam PE (FPE)

3. Pair Impedance 120 Ω

4. Tinned Copper Drain Wire 24 AWG(7 x 32)

5. Screen Aluminium/Polyester

6. Braiding Tinned Copper wires

7. Sheath Material Grey PVC or Purple HFFR

Standard Put Up Length 305 or 500 meters Standard References TIA/EIA-485 (BS) EN 50290-2 IEC 60332-1 (PVC sheath) or IEC 60332-3-24 (3C) (HFFR sheath) IEC 61034 (HFFR sheath) IEC 60754-1 & 2 (HFFR sheath) RoHS directives

Cables with 24 AWG conductors – PE insulation - PVC sheath

BTCL Part

Number

No of pairs

Conductor (AWG)

Max. DC Resistance Conductor

(Ω/km)

Coverage braiding

(%)

Sheath Overall

Diameter (mm)

Capacitance

(pF/m)

Weight

(kg/km) C1189 1 24 (7 x 32) 88 90 PVC 5.9 41 49C1190 2 24 (7 x 32) 88 90 PVC 8.5 41 80.5C1191 3 24 (7 x 32) 88 90 PVC 9.0 41 92.6C1192 4 24 (7 x 32) 88 90 PVC 9.9 41 114.4

C1318 1 24 (7 x 32) 88 90 HFFR 5.9 41 49C1319 2 24 (7 x 32) 88 90 HFFR 8.5 42 80.5C1320 3 24 (7 x 32) 88 90 HFFR 9.0 42 92.6C1321 4 24 (7 x 32) 88 90 HFFR 9.9 42 114.4

Cables with 22 AWG conductors – Foam PE insulation - Halogen-free (HFFR) sheath

BTCL Part

Number

No of pairs

Conductor (AWG)

Max. DC Resistance Conductor

(Ω/km)

Coverage braiding

(%)

Sheath

Overall

Diameter (mm)

Capacitance

(pF/m)

Weight

(kg/km)

C1080 1 22 (7 x 30) 57.4 65 PVC 6.1 36 63.7C1295 2 22 (7 x 30) 57.4 65 PVC 9.1 37 75.6C1296 3 22 (7 x 30) 57.4 65 PVC 10.5 38 97C1297 4 22 (7 x 30) 57.4 65 PVC 11.4 38 119.1

C1401 1 22 (7 x 30) 57.4 65 HFFR 6.1 36 63.7C1402 2 22 (7 x 30) 57.4 65 HFFR 9.1 37 75.6C1403 3 22 (7 x 30) 57.4 65 HFFR 10.5 38 97C1404 4 22 (7 x 30) 57.4 65 HFFR 11.4 38 119.1

Colour scheme Pair 1 Pair 2 Pair 3 Pair 4

Wire a (insulation colour / colour of stripe) White / blue White / orange White / green White / brown

Wire b (insulation colour / colour of stripe) Blue / white Orange / white Green / white Brown /white

For more details, please see the respective detailed datasheet(s)

[email protected] 12

Page 13: Bt cables building infrastructure systems catalogue

Section 1.2 Cables with 2 to 6 pairs for RS-422 applications 24AWG conductors – FPE insulation – every pair screened - PVC sheath CABLE DESCRIPTION

1. Conductor Flexible Tinned Copper

2. Insulation Foam Polyethylene (FPE)

3. Pair Two twisted wires

4. Drain Wire Flexible Tinned Copper 24 AWG (7 x 32)

5. Screen Aluminium/Polyester Wrapped around each

Pair

6. Cable core 2 or more individually

screened pairs stranded

7. Sheath Material Grey PVC

Standard Put Up Length 305 or 500 metres Standard References ANSI/TIA/EIA-422-B

(BS) EN 50290-2 IEC 60332-1 RoHS directives

Cables with 24 AWG conductors – PE insulation – PVC sheath

BTCL Part Number

No. of

Pairs

Conductor and

Drain Wire (AWG)

Max. DC Resistance Conductor

(Ω/km)

Overall

Diameter (mm)

Capacitance

(pF/m)

Impedance

(Ohm)

Weight

(kg/km)

C1382 2 24 (7 x 32) 88 6.7 41 100 41.8C1383 3 24 (7 x 32) 88 8.4 41 100 59.4C1384 4 24 (7 x 32) 88 9.2 41 100 75.5C1386 6 24 (7 x 32) 88 10.6 41 100 104.8

Colour scheme Pair 1 Pair 2 Pair 3 Pair 4 Pair 5 Pair 6C1382 to C1386 Black/Red Black/White Black/Green Black/Blue Black/Yellow Black/Brown

For more details, please see the respective detailed datasheet(s)

[email protected] 13

Page 14: Bt cables building infrastructure systems catalogue

Section 1.3 Cables with 2 to 8 pairs for RS-232 applications 24AWG conductors – PVC insulation – overall screen – PVC, PE or HFFR sheath CABLE DESCRIPTION

1. Conductor Flexible Tinned Copper 24AWG(7x32)

2. Insulation PVC or HFFR

3. Pair Two twisted wires

4. Cable core 2 or more pairs stranded

5. Tinned Copper Drain Wire 24 AWG(7 x 32)

6. Screen Aluminium/Polyester

7. Sheath Material Grey PVC

Purple HFFR Black PE

Standard Put Up Length 305 or 500 metres

Standard References ANSI/TIA/EIA-232-F (BS) EN 50290-2

IEC 60332-1 (PVC sheath) IEC 60332-3-24 (3C) (HFFR sheath) IEC 61034 (HFFR sheath) RoHS directives

BTCL Part Number

No. of Pairs

Insulation Sheath Conductor

and Drain Wire

Max. DCR Conductor

(Ω/km) Overall

Diameter

Capacitance

Weight

C1181 1 PVC PVC 24 (7 x 32) 88 4.0 135 18C1182 2 PVC PVC 24 (7 x 30) 88 5.6 76 28C1183 3 PVC PVC 24 (7 x 30) 88 5.9 76 39C1184 4 PVC PVC 24 (7 x 30) 88 6.7 80 48C1185 5 PVC PVC 24 (7 x 30) 88 7.3 80 57C1186 6 PVC PVC 24 (7 x 30) 88 7.4 80 65C1187 7 PVC PVC 24 (7 x 30) 88 7.5 80 68C1188 8 PVC PVC 24 (7 x 30) 88 8.3 80 76

BTCL Part Number

No. of Pairs

Insulation Sheath Conductor

and Drain Wire

Max. DCR Conductor

(Ω/km) Overall

Diameter

Capacitance

Weight

C1441 1 HFFR HFFR 24 (7 x 32) 88 4.0 95 18C1442 2 HFFR HFFR 24 (7 x 30) 88 5.6 55 28C1443 3 HFFR HFFR 24 (7 x 30) 88 5.9 55 39C1444 4 HFFR HFFR 24 (7 x 30) 88 6.7 60 48C1445 5 HFFR HFFR 24 (7 x 30) 88 7.3 60 57C1446 6 HFFR HFFR 24 (7 x 30) 88 7.4 60 65C1447 7 HFFR HFFR 24 (7 x 30) 88 7.5 60 73C1448 8 HFFR HFFR 24 (7 x 30) 88 8.3 60 85C1449 10 HFFR HFFR 24 (7 x 30) 88 9.2 60 95

BTCL Part Number

No. of Pairs

Insulation Sheath Conductor

and Drain Wire

Max. DCR Conductor

(Ω/km) Overall

Diameter

Capacitance

Weight

C1451 1 PVC PE 24 (7 x 32) 88 4.0 135 14.5C1452 2 PVC PE 24 (7 x 30) 88 5.6 76 24.5C1453 3 PVC PE 24 (7 x 30) 88 5.9 76 31C1454 4 PVC PE 24 (7 x 30) 88 6.7 80 39C1455 5 PVC PE 24 (7 x 30) 88 7.3 80 47C1456 6 PVC PE 24 (7 x 30) 88 7.4 80 55C1457 7 PVC PE 24 (7 x 30) 88 7.5 80 59C1458 8 PVC PE 24 (7 x 30) 88 8.3 80 67

Colour scheme of the pairs

Pair number Pair 1 Pair 2 Pair 3 Pair 4 Pair 5 Pair 6 Pair 7 Pair 8 Pair 10

Wire a Black Black Black Black Black Black Black Red Red

Wire b Red White Green Blue Yellow Brown Orange White Blue

For more details, please see the respective detailed datasheet(s)

[email protected] 14

Page 15: Bt cables building infrastructure systems catalogue

Section 1.4 Cables for KNX (was EIB or Instabus) applications 0.8 mm conductors – PE insulation – overall screen - PVC or HFFR sheath CABLE DESCRIPTION

1. Conductor Solid Bare Copper

0.8 mm = 0.5 mm2

2. Insulation Polyethylene (PE) Black-Red-

White-Green

3. Cable Core Quad or Pair

4. Polyester tape

5. Drain Wire 0.4 mm Tinned Copper

6. Screen Aluminium/Polyester

7 Sheath Material Green PVC or Green HFFR

Standard Put Up Length 305 or 500 metres Standard References EN 50090 (BS) EN 50290-2

IEC 60332-1 (PVC sheath) or IEC 60332-3-24 (3C) (HFFR sheath) IEC 61034 (HFFR sheath)

IEC 60754-1 & 2 (HFFR sheath) RoHS directives

BTCL Part Number

No. of wires

Lay-Up Sheath

Material Diameter Insulation

(mm)

Overall Diameter

(mm)

Max. DC Resistance Conductor

(Ω/km)

Capacitance

(pF/m)

Weight

(kg/km) C1217 1 x 4 quad PVC 1.45 6.1 37 ≤ 100 51C1218 1 x 4 quad HFFR 1.45 6.1 37 ≤ 100 53C1219 1 x 2 pair PVC 1.45 5.5 37 ≤ 100 37C1220 1 x 2 pair HFFR 1.45 5.5 37 ≤ 100 39

BTCL Part Number

Wire a Wire b Wire c Wire d

C1217 Black White Red GreenC1218 Black White Red GreenC1219 Black White C1220 Black White

For more details, please see the respective detailed datasheet(s)

[email protected] 15

Page 16: Bt cables building infrastructure systems catalogue

Section 1.5 Cables for LonWorks applications 0.64 mm conductors – PE or FPE insulation Individually screened pairs or unscreened pairs - HFFR sheath CABLE DESCRIPTION

1. Conductor Solid Bare Copper

0.64 mm = 0.32 mm²

2. Insulation Polyethylene (PE) or Foam Polyethylene (FPE)

3. Pairs with no screen two twisted wires

4. Individually screened pair

two twisted wires plus drain wire wrapped with an Aluminium/Polyester foil

5. Cable core one pair or two

pairs stranded

6 Sheath Material Purple HFFR

Standard Put Up Length 305 or 500 metres Standard References EN 50090 (BS) EN 50290-2

IEC 60332-3C IEC 61034 IEC 60754-1 & 2

RoHS directives

BTCL Part Number

No. of

pairs

Insulation Material

Indiv. screened

pairs

Overall

Diameter (mm)

Max. DC Resistance Conductor

(Ω/km)

Capacitance

(pF/m)

Weight

(kg/km)

C1346 1 Solid PE No 3.5 61 46 17.1C1347 2 Solid PE No 5.2 61 46 27.7C1348 1 Foam PE Yes 4.6 61 46 24.2C1349 2 Foam PE Yes 7.6 61 46 56.1

For more details, please see the respective detailed datasheet(s)

[email protected] 16

Page 17: Bt cables building infrastructure systems catalogue

Section 1.6 Cables for General Interface applications 2 to 6 pairs – 22AWG conductors – PE or HFFR insulation Individually screened pairs – PVC or HFFR sheath CABLE DESCRIPTION

1. Conductor Flexible Tinned Copper

22AWG(7 x 30)

2. Insulation Polyethylene (PE) or

Halogen-free (HFFR)

3. Pair Two twisted wires

4. Tinned Copper Drain Wire 24 AWG(7 x 32)

5. Screen Aluminium/Polyester foil wrapped around each

pair

6. Cable core 2 or more individually

screened pairs stranded

7. Sheath Material Grey PVC or

Purple HFFR

Standard Put Up Length 305 or 500 metres Standard References (BS) EN 50290-2

IEC 60332-1 (PVC sheath) IEC 60332-3-24 (3C) (HFFR sheath)

IEC 61034 (HFFR sheath) IEC 60754-1 & 2 (HFFR sheath) RoHS directives

BTCL Part Number

No. of

pairs

Insulation Material

Sheath Material

Overall Diameter

(mm)

Max. DC Resistance Conductor

(Ω/km)

Capacitance

(pF/m)

Weight

(kg/km) C1196 2 PE PVC 6.0 57.4 90 36.1C1281 2 HFFR HFFR 6.5 57.4 150 50.8C1197 3 PE PVC 6.5 57.4 98 49.1C1282 3 HFFR HFFR 7.5 57.4 155 67.4C1298 4 PE PVC 7.0 57.4 98 62C1299 5 PE PVC 7.7 57.4 99 74.2C1214 6 PE PVC 8.9 57.4 99 87.2C1314 6 HFFR HFFR 9.5 57.4 155 115.6

Colour scheme Pair 1 Pair 2 Pair 3 Pair 4 Pair 5 Pair 6

C1196 and C1281 Black/ Red Green/White

C1197 and C1282 Black/ Red Black/White Black/Green

C1298 Black/ Red Black/White Black/Green Black/Blue

C1299 Black/ Red Black/White Black/Green Black/Blue Black/Yellow

C1214 and C1314 Black/ Red Black/White Black/Green Black/Blue Black/Yellow Black/Brown

For more details, please see the respective detailed datasheet(s)

[email protected] 17

Page 18: Bt cables building infrastructure systems catalogue

Section 1.7 Cables for General Interface applications One pair – 22 to 12AWG conductors – PE insulation Collective (overall) screen – PVC or HFFR sheath CABLE DESCRIPTION

1. Conductor Flexible Tinned Copper

2. Insulation PVC or Polyethylene (PE) or Halogen-free (HFFR)

3. Pair Two wires twisted

4. T.C. Drain Wire (only with screen)

24 AWG(7 x 32)

5. Screen (if applicable) Aluminium/Polyester

6. Sheath Material Grey PVC or

Purple HFFR

Standard Put Up Length 305 or 500 metres

Standard References (BS) EN 50290-2 IEC 60332-1 (PVC sheath) IEC 60332-3-24 (3C) (HFFR sheath) IEC 61034 (HFFR sheath) IEC 60754-1 & 2 (HFFR sheath) RoHS directives

DC Resistance 12 to 22 AWG conductors

Conductor AWG 22 20 18 16 14 12

No. of strands x gauge AWG 7 x 30 7 x 28 7 x 26 19 x 29 19 x 27 19 x 25

No. of strands x mm Mm 7 x 0.25 7 x 0.32 7 x 0.40 19 x 0.28 19 x 0.36 19 x 0.45

Max. DC resistance conductor Ω/km 57.4 35.75 22.7 15.47 9.36 5.61

One pair cables with PE insulation and PVC sheath

Screened Unscreened BTCL Part Number

Cond.

(AWG)

OverallDiameter

(mm)

Capacity

(pF/m)

Weight

(kg/km)

BTCL Part Number

Cond.

(AWG)

Overall Diameter

(mm)

Capacity

(pF/m)

Weight

(kg/km) C1199 22 4.4 75 25 C1301 22 4.0 70 19.5C1195 20 5.0 75 36.4 C1300 20 4.3 80 23C1193 18 5.6 75 43.2 C1203 18 5.1 85 38.6C1213 16 7.9 60 75.7 C1198 16 6.9 90 63.3C1224 14 9.0 76 104.9 C1222 14 8.6 108 91.8C1313 12 10.2 77 124.7 C1302 12 9.8 115 115

One pair cables with HFFR insulation and HFFR sheath

Screened Unscreened BTCL Part Number

Cond.

(AWG)

OverallDiameter

(mm)

Capacity

(pF/m)

Weight

(kg/km)

BTCL Part Number

Cond.

(AWG)

Overall Diameter

(mm)

Capacity

(pF/m)

Weight

(kg/km) C1310 22 4.8 140 27.1 C1311 22 4.7 48 24.7C1308 20 5.3 158 37.2 C1309 20 5,2 52 34.7C1272 18 6.0 165 48.4 C1271 18 5.9 65 45.9C1270 16 7.8 150 74.3 C1307 16 7.7 48 71.8C1305 14 8.8 180 97.9 C1306 14 8.7 55 95.3C1303 12 9.8 195 132.6 C1304 12 9.7 57 128.2

For more details, please see the respective detailed datasheet(s)

[email protected] 18

Page 19: Bt cables building infrastructure systems catalogue

Section 1.8 Cables for Security & Alarm applications 1 to 6 pairs – 18AWG conductors – polyolefin insulation foil or foil + braid overall screen –HFFR sheath CABLE DESCRIPTION

Design

1. Conductor Flexible Bare Copper

2. Insulation Polyolefin

3. Pair Two twisted wires

4. Cable core N pairs stranded

5. Drain Wire Flexible Tinned Copper

24 AWG (7 x 32)

6. Overall Screen 1 Aluminium/Polyester foil

7. Overall Screen 2 braid coverage

8. Sheath Material Purple Halogen-free (HFFR)

Standard Put Up Length 305 or 500 metres Standard References (BS) EN 50290-2

IEC 60332-3-24 IEC 61034 IEC 60754-1 & 2 RoHS directives

Cables with 18AWG conductors – Polyolefin insulation – Collective Screen and HFFR sheath

BTCL Part Number

No. of

Pairs

Conductor

(AWG)

Screen

Max. DC Resistance Conductor

(Ω/km)

Overall

Diameter (mm)

Capacitance

(pF/m)

Weight

(kg/km)

C1171 1 18 (7 x 26) foil 22.7 5.1 115 4.1C1172 2 18 (7 x 26) foil 22.7 7.7 115 7.41C1173 3 18 (7 x 26) foil 22.7 8.1 115 9.64C1174 4 18 (7 x 26) foil 22.7 8.9 115 12.37C1175 5 18 (7 x 26) foil 22.7 9.9 115 14.92C1176 6 18 (7 x 26) foil 22.7 10.2 115 17.11

BTCL Part Number

No. of

Pairs

Conductor (AWG)

Screen

Max. DC Resistance Conductor

(Ω/km)

Overall Diameter

(mm)

Capacitance (pF/m)

Weight (kg/km)

C1418 1 18 (7 x 26) foil + braid 22.7 5.8 115 4.7C1419 2 18 (7 x 26) foil + braid 22.7 8.4 115 10.5C1420 3 18 (7 x 26) foil + braid 22.7 8.8 115 11.6C1421 4 18 (7 x 26) foil + braid 22.7 9.6 115 13.7C1422 5 18 (7 x 26) foil + braid 22.7 10.5 115 16.5C1423 6 18 (7 x 26) foil + braid 22.7 10.9 115 18.6

Colour scheme Pair 1 Pair 2 Pair 3 Pair 4 Pair 5 Pair 6

C1171 to C1176 Black/Red Black/White Black/Green Black/Blue Black/Yellow Black/Brown

For more details, please see the respective detailed datasheet(s)

[email protected] 19

Page 20: Bt cables building infrastructure systems catalogue

Section 1.9 Cable for Building Management Systems 1 pair – 0.6 mm² conductors – polyolefin insulation Collective overall screen –PVC sheath CABLE DESCRIPTION

1. Conductor Flexible Bare Copper

7 x 0.35 mm = 0.6 mm²

2. Insulation Polyolefin Core 1: Black Core 2: Red

3. Pairs two twisted wires

4. Tinned Copper Drain Wirer 7 x 0.20 mm

5. Screen Aluminium/Polyester

foil

6 Sheath Material Grey PVC

Standard Put Up Length

305 or 500 metres Standard References (BS) EN 50290-2

IEC 60332-1 RoHS directives

BTCL Part Number

No. of pairs

Overall Diameter

(mm)

Max. DC ResistanceConductor

(Ω/km)

Capacitance (pF/m)

Weight (kg/km)

C1381 1 3.9 61 110 14.6 For more details, please see the respective detailed datasheet(s)

[email protected] 20

Page 21: Bt cables building infrastructure systems catalogue

Section 2 - BT BMS-TECTM - Multi-Conductor Cables Application and Construction 1. Application All PVC and HFFR sheathed multi-conductor cables are suitable for Building Management Systems (BMS), Sound, Audio, Security, Safety, Control and Instrumentation. 2. Basic Construction of the cables Wire = Conductor without or with insulation. With insulation sometimes also indicated as core. Conductor: flexible = twisted bare or tinned copper strands, ranging from 12 to 22AWG.

Conductor (AWG)

configuration (AWG)

configuration (mm)

DC Resistance (Ohm/km)

24 7 x 32 7 x 0.2 ≤ 88 22 7 x 30 7 x 0.25 ≤ 57.4 20 7 x 28 7 x 0.32 ≤ 32.16 18 7 x 26 7 x 0.40 ≤ 22.7 16 19 x 29 19 x 0.28 ≤ 15.47 14 19 x 27 19 x 0.36 ≤ 9.36 12 19 x 25 19 x 0.45 ≤ 5.61

Insulation: Polypropylene (PP) for PVC (Polyvinyl Chloride) sheathed cables and Halogen-Free (HFFR) for HFFR sheathed cables. Both insulations are in accordance with BS EN 50290-2. Good strippable and coloured insulation. The colours are not interchangeable. Colour scheme of wires with 12 or 14 AWG conductors: black-white-red-green-brown-blue-orange-yellow-purlpe-grey-pink-tan. Colour scheme of wires with ≥ 16AWG conductors: black-red-white-green-brown-blue-orange-yellow-purlpe-grey-pink-tan. Cable core: two or more wires, twisted. Good twisting (lay-length < 30 – 40D) is necessary otherwise the cable can hardly be bending and will break after a few bends. Drain wire (only in combination with a screen): stranded tinned copper wires. In order to avoid corrosion, it is recommended that drain wires are tinned. Screen (if applicable): Helically applied (= as a spiral) Aluminium/Polyester (Alpet) foil. For the flexibility of a cable a helically applied foil is to be preferred. A longitudinally applied foil act more as a stiff tube = more difficult to bend. Sheath: grey PVC or purple HFFR or black UV-resistant HFFR, all in accordance with BS EN 50290-2.

Cable configurations Cables with PVC sheath Halogen-Free cables Insulation PP acc. to (BS)EN 50290-2 HFFR acc. to (BS)EN 50290-2 Sheath PVC acc. to (BS)EN 50290-2 HFFR acc. to (BS)EN 50290-2 Retardancy Flame Retardant Fire Retardant Retardant acc. to IEC 60332-1 / UL1581 IEC 60332-3-24 / UL 1685 Low Smoke emission acc. to Not applicable IEC 61034 Halogen-free acc. to Not applicable IEC 60754 RoHS compliant Yes yes

Operating temperature range: -25 to +75 °C and Rated Voltage: 300 Vrms. Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.

[email protected] 21

Page 22: Bt cables building infrastructure systems catalogue

Section 2.1 – Multi-Conductor Cables PVC sheathed cables with 12AWG to 22AWG conductors for Audio, Control, Instrumentation and Building Management Systems (BMS) CABLE DESCRPTION Design

1. Conductor Stranded

Bare Copper

2. Insulation Polypropylene (PP)

3 Cable Core Two or more wires stranded

4 Drain Wire (only with screen) 24 AWG (7 x 32) Tinned Copper 5 Screen (if applicable)

Aluminium/Polyester > 100% Coverage

6. Sheath Material

Grey PVC

Standard Put Up Length 305 and 500 metres Standard References (BS) EN 50290-2

IEC 60332-1 RoHS directives

No of wires

Cond.

(AWG)

BT Cables Part

Number Scrn

Diam.

(mm)

Weight

(kg/km)

BT Cables Part

Number Scrn

Diam.

(mm)

Weight

(kg/km) 2 22 C1226 Yes 3.3 16.5 C1227 No 3.3 14.6 3 22 C1228 Yes 3.5 21.4 C1278 No 3.5 19.7 4 22 C1230 Yes 3.8 26 C1231 No 3.8 23.9 6 22 C1264 Yes 4.5 35.7 C1265 No 4.5 33.6 8 22 C1232 Yes 4.9 45.1 C1233 No 4.9 43

2 20 C1019 Yes 3.5 22 C1020 No 3.4 19.7 3 20 C1021 Yes 3.7 28.5 C1022 No 3.6 26.2 4 20 C1023 Yes 4.1 35.4 C1024 No 4.0 33.1 6 20 C1260 Yes 5.0 49.9 C1261 No 4.9 47.9 8 20 C1262 Yes 5.4 62.9 C1263 No 5.3 60.6

2 18 C1013 Yes 4.0 29.6 C1014 No 3.9 27.3 3 18 C1015 Yes 4.2 39.2 C1016 No 4.1 36.9 4 18 C1017 Yes 4.6 49.4 C1018 No 4.55 47.2 6 18 C1211 Yes 5.75 70.9 C1212 No 5.7 68.2 8 18 C1258 Yes 6.0 89.5 C1259 No 5.9 87

2 16 C1007 Yes 4.6 37.3 C1008 No 4.5 35 3 16 C1009 Yes 4.9 50 C1010 No 4.75 47.7 4 16 C1011 Yes 5.3 63.5 C1012 No 5.25 61.1 6 16 C1252 Yes 6.8 91.6 C1253 No 6.7 89 8 16 C1254 Yes 7.6 120.8 C1255 No 7.5 118.1

2 14 C1001 Yes 6.0 57 C1002 No 5.75 53.3 3 14 C1003 Yes 6.5 77.9 C1004 No 6.35 72.5 4 14 C1005 Yes 6.9 102.5 C1006 No 6.75 97.1 6 14 C1248 Yes 8.6 151 C1249 No 8.4 148.2 8 14 C1250 Yes 9.8 197.3 C1251 No 9.7 194.5

2 12 C1322 Yes 6.9 85.7 C1323 No 6.7 79.8 3 12 C1324 Yes 7.4 118.1 C1325 No 7.2 112.1 4 12 C1326 Yes 8.2 151.1 C1327 No 8.0 145.3 6 12 C1330 Yes 9.8 215.5 C1331 No 9.6 209.7 8 12 C1332 Yes 10.7 279.5 C1333 No 10.5 273.7

Scrn = Screen, Diam. = overall diameter. For more details, please see the respective detailed datasheet(s

[email protected] 22

Page 23: Bt cables building infrastructure systems catalogue

Section 2.2 – Multi-Conductor Cables Halogen-Free (HFFR) cables with 12AWG to 22AWG conductors for Audio, Control, Instrumentation and Building Management Systems (BMS) CABLE DESCRIPTION Design

1. Conductor Stranded

Bare Copper

2. Insulation HFFR

3. Drain Wire (only with screen) 24 AWG (7 x 32)

Tinned Copper

4. Screen (if applicable) Aluminium/Polyester

> 100% Coverage

5. Ripcord

6. Sheath Material Purple Halogen-Free

(HFFR)

Standard Put Up Length 305 metres Standard References (BS) EN 50290-2

IEC 60332-3C IEC 61034 IEC 60754-1 & 2 RoHS directives

No of wires

Cond.

(AWG)

BT Cables Part

Number Scrn

Diam.

(mm)

Weight

(kg/km)

BT Cables Part

Number Scrn

Diam.

(mm)

Weight

(kg/km) 2 22 C1741 Yes 3.9 22.4 C1742 No 3.9 20.5 3 22 C1743 Yes 4.1 27.6 C1744 No 4.1 26.0 4 22 C1745 Yes 4.4 33.7 C1746 No 4.4 31.7 6 22 C1747 Yes 5.2 45.8 C1748 No 5.2 43.9 8 22 C1749 Yes 5.6 56.4 C1750 No 5.6 54.4

2 20 C1731 Yes 4.7 32.6 C1732 No 4.6 30.1 3 20 C1733 Yes 4.9 40.2 C1734 No 4.8 37.7 4 20 C1735 Yes 5.3 48.7 C1736 No 5.2 46.2 6 20 C1737 Yes 6.2 66.2 C1738 No 6.1 63.7 8 20 C1739 Yes 6.7 81.9 C1740 No 6.6 79.4

2 18 C1721 Yes 5.1 41.0 C1722 No 5.0 38.5 3 18 C1723 Yes 5.4 52.3 C1724 No 5.3 49.8 4 18 C1725 Yes 5.8 64.1 C1726 No 5.7 61.6 6 18 C1727 Yes 6.8 88.6 C1728 No 6.7 86.1 8 18 C1729 Yes 7.3 110.8 C1730 No 7.2 108.2

2 16 C1711 Yes 5.4 49.3 C1712 No 5.4 46.8 3 16 C1713 Yes 5.7 63.8 C1714 No 5.7 61.3 4 16 C1715 Yes 6.2 79.3 C1716 No 6.2 78.2 6 16 C1717 Yes 7.3 108.2 C1718 No 7.3 107.0 8 16 C1719 Yes 7.9 137.0 C1720 No 7.9 135.9

2 14 C1701 Yes 6.5 67.7 C1702 No 6.4 65.2 3 14 C1703 Yes 6.9 92.8 C1704 No 6.8 89.1 4 14 C1705 Yes 7.5 115.4 C1706 No 7.4 112.9 6 14 C1707 Yes 8.9 163.7 C1708 No 8.8 162.8 8 14 C1709 Yes 9.6 210.8 C1710 No 9.5 208.3

2 12 C1334 Yes 7.7 102.2 C1335 No 7.5 97.0 3 12 C1336 Yes 8.1 135.0 C1337 No 7.9 129.7 4 12 C1338 Yes 8.9 170.9 C1339 No 8.7 165.7 6 12 C1342 Yes 10.6 243.3 C1343 No 10.4 237.1 8 12 C1344 Yes 11.6 314.6 C1345 No 11.4 306.2

Scrn = Screen, Diam. = overall diameter. For more details, please see the respective detailed datasheet(s

[email protected] 23

Page 24: Bt cables building infrastructure systems catalogue

Section 2.3 – Multi-Conductor Cables UV-Resistant Halogen-Free (HFFR) cables with 12AWG to 22AWG conductors for Audio, Control, Instrumentation and Building Management Systems (BMS) CABLE DESCRIPTION

Design 1. Conductor Stranded

Bare Copper

2. Insulation HFFR

3. Drain Wire (only with screen) 24 AWG (7 x 32)

Tinned Copper

4. Screen (if applicable) Aluminium/Polyester

> 100% Coverage

5. Ripcord 6. Sheath Material Black UV-resistant Halogen-Free (HFFR)

Standard Put Up Length 305 metres Standard References (BS) EN 50290-2

IEC 60332-3C IEC 61034 IEC 60754-1 & 2 RoHS directives

No of wires

Cond.

(AWG)

BT Cables Part

Number Screen

Diameter

(mm)

Weight

(kg/km) 2 18 C1351 Yes 5.1 41.0

3 18 C1352 Yes 5.4 52.3

4 18 C1353 Yes 5.8 64.1

6 18 C1354 Yes 6.8 88.6

8 18 C1355 Yes 7.3 110.8

10 18 C1356 Yes 8.4 135.7

20 18 C1357 Yes 10.7 249.6

No of wires

Cond.

(AWG)

BT Cables Part

Number Screen

Diameter

(mm)

Weight

(kg/km) 2 16 C1391 Yes 5.5 49.3 3 16 C1392 Yes 5.8 63.8 4 16 C1393 Yes 6.3 79.3 6 16 C1394 Yes 7.4 108.2 8 16 C1395 Yes 8.0 137.0

10 16 C1396 Yes 9.5 173.1 20 16 C1397 Yes 12.1 316.6

For more details, please see the respective detailed datasheet(s)

[email protected] 24

Page 25: Bt cables building infrastructure systems catalogue

Section 3 - BT FIREPRO-TEC™ – Fire Detection and Alarm System Cables Bare Copper 12 to 18AWG, one pair, PVC insulation and Sheath, Screened and Unscreened ©UL Certification: type FPLR rated 105°C - ©UL listed APPLICATION Fire Detection and Alarm Systems Fire Retardancy: UL 1666 Operating temperature range: -40 to +105 °C and Rated Voltage: 300 Vrms CABLE DESCRIPTION

1. Conductor Solid Bare Copper

2. Insulation PVC acc. to UL444 Black and Red

3. Pair Two wires twisted

4. TC Drain Wire (only under screen)

22 AWG (7 x 30) 5. Screen (if applicable)

Aluminium/Polyester > 100% Coverage

6. Sheath Material

Red PVC acc. to UL444

Standard Put Up Length 305 metres Standard References UL1424 UL444

UL1666 RoHS directives

BT Cables Part

Number

No. of

Pairs

Conductor

( AWG)

Screen

Overall

Diameter (mm)

Max. DC Resistance Conductor

(Ω/km)

Capacitance

(pF/m)

Weight

(kg/km)

C1040 1 18 Yes 5.9 22.7 160 19.2 C1135 1 18 No 5.8 22.7 60 16.0 C1041 1 16 Yes 6.1 15.47 189 28.5 C1136 1 16 No 6.0 15.47 71 25.0 C1042 1 14 Yes 7.8 9.36 160 43.0 C1137 1 14 No 7.7 9.36 69 40.0 C1043 1 12 Yes 8.7 5.61 216 66.0 C1138 1 12 No 8.6 5.61 65 63.0

Non-standard cable constructions, colours, details and/or additional information are available on request.

For more details, please see the respective detailed datasheet(s).

Please note that technical specifications are subject to change without notice.

POWER-LIMITED CIRCUIT CABLE NO. 000001 1000 FEET F ORM 3

[email protected] 25

Page 26: Bt cables building infrastructure systems catalogue

Section 4 - BT FIREPRO-TEC™ – Fire Resistant Cables Bare and Flexible Copper Conductors 0.75 to 4.0 mm2, Silicon insulation and Halogen-free Sheath, Screened and Unscreened 1. Application All Fire Resistant cables are suitable for Security, Safety, Control and Instrumentation with special requirements for circuit integrity in case of a fire. 2. Fire Resistance confirming with BS6387 CWZ: Fire Resistant to BS 6387, Cat. C: exposed to fire at 950°C for 3 hours Fire Resistant to BS 6387, Cat. W: exposed to fire at 650°C for 15 minutes, then exposed to fire at 650°C with water for 15 minutes Fire Resistant to BS 6387, Cat. Z: exposed to fire at 650°C for 15 minutes, then exposed to fire at 650°C with mechanical shock for 15 minutes 3. Fire Retardancy confirming with IEC 60332-3-24 (was 3C) 4. Basic Construction of the cables Wire = Conductor with Insulation Conductor: solid bare copper wires, ranging from 0.75 to 2.5 mm² and the 4.0 mm² conductor consists of stranded bare copper wires = flexible

Cross Section

(mm²)

Diameter

(mm)

DC Resistance

(Ohm/km)

Recommended Current (Amp)

0.75 1 x 1.0 ≤ 24.5 ≤ 12 1.0 1 x 1.13 ≤ 18.1 ≤ 18 1.5 1 x 1.4 ≤ 12.1 ≤ 21 2.5 1 x 1.8 ≤ 7.41 ≤ 30 4.0 7 x 0.85 = 2.55 ≤ 4.61 ≤ 40

Insulation: Silicon Rubber blends acc. to BS 7655. Good strippable and coloured insulation. The colours are not interchangeable. Colour scheme: 2 cores: brown – blue, 3 cores: brown – black – grey, 4 and more cores: brown – blue – black – grey – others black numbered. Cable core: two or more cores, twisted. Good twisting is necessary otherwise the cable can hardly be bending and will break after a few bends. Drain wire (only in combination with a screen): solid bare copper. Screen (if applicable): Helically applied (= as a spiral) Aluminium/Polyester (Alpet) foil. For the flexibility of a cable a helically applied foil is to be preferred. A longitudinally applied foil act more as a stiff tube = more difficult to bend. Sheath: red HFFR in accordance with BS EN 50290-2 Operating temperature range: -20 to +90 °C. Rated Voltage: 300/500 Vrms Non-standard cable constructions, colours, details and/or additional information are available on request.

For more details, please see the respective detailed datasheet(s).

Please note that technical specifications are subject to change without notice.

[email protected] 26

Page 27: Bt cables building infrastructure systems catalogue

Section 4 - BT FIREPRO-TEC™ – Fire Resistant Cables CABLE DESCRIPTION 1. Conductor

Solid or Flexible Bare Copper

2. Insulation Silicon Rubber blend

3. Cable core Two or three wires Twisted

4. BC Drain Wire (only under screen) 5. Screen (if applicable)

Aluminium/Polyester > 100% Coverage 6. Sheath Material

Red HFFR

Standard Put Up Length 305 and 500 metres Standard References BS 6387 CWZ BS 7655

IEC 60332-3C IEC 60754-1 & 2 RoHS directives

BT Cables Part Number

No. of wires

Conductor

(mm²)

Screen

Drain Wire

(mm²)

Overall

Diameter (mm)

Max. DC Resistance Conductor

(Ω/km)

Weight

(kg/km)

C1284 2 0.75 Yes 0.75 7.5 24.5 67.0 C1139 2 0.75 No 7.4 24.5 61.7 C1159 3 0.75 Yes 0.75 7.9 24.5 83 C1149 3 0.75 No 7.8 24.5 75 C1283 2 1.0 Yes 1.0 7.8 18.1 73.4 C1140 2 1.0 No 7.7 18.1 65.5 C1160 3 1.0 Yes 1.0 8.1 18.1 93 C1150 3 1.0 No 8.0 18.1 83 C1044 2 1.5 Yes 1.5 8.7 12.1 98.1 C1141 2 1.5 No 8.6 12.1 87.6 C1161 3 1.5 Yes 1.5 8.95 12.1 123 C1151 3 1.5 No 8.85 12.1 108 C1045 2 2.5 Yes 2.5 9.9 7.41 134.3 C1142 2 2.5 No 9.8 7.41 119.4 C1162 3 2.5 Yes 2.5 10.3 7.41 174 C1152 3 2.5 No 10.2 7.41 151 C1289 2 4.0 Yes 4.0 12.0 4.61 197.1 C1143 2 4.0 No 11.9 4.61 172.6 C1163 3 4.0 Yes 4.0 12.95 4.61 270 C1153 3 4.0 No 12.85 4.61 234

For more details, please see the respective detailed datasheet(s)

[email protected] 27

Page 28: Bt cables building infrastructure systems catalogue

Section 5 - BT Security-Tec ™– Coaxial Cables Application and Construction of Coax Cables for 75 Ohm Video Systems Applications. CCTV: Closed Circuit Television is the use of video cameras to transmit a signal to a specific place, on a limited set of monitors SMATV: Satellite Master Antenna Television used to deliver signals to multiple dwelling units (e.g., apartment buildings and trailer parks). CATV: Central Antenna Television = Cable television is a system of providing television to consumers via radio frequency signals transmitted to televisions. Nowadays also used for internet and telephone. HDTV: High-definition television refers to video having resolution substantially higher than traditional television systems. Telecom and networking: a number of special cable constructions. Basic Cable Design. Coaxial cables are designed to carry radio frequency current of a much higher frequency than the 50 or 60 Hz used in low voltage cables. And this requires special construction to prevent power losses. If an ordinary wire is used to carry high frequency currents, the wire acts as an antenna, and the high frequency currents radiate off the wire as radio waves, causing power losses. To prevent this, in coaxial cable one of the conductors is formed into a tube and encloses the other conductor. This confines the radio waves from the central conductor to the space inside the tube. To prevent the outer conductor, or shield, from radiating, it is connected to electrical ground, keeping it at a constant potential. The dimensions and spacing of the conductors must be uniform throughout the length of the cable. Any abrupt change in the spacing of the two conductors along the cable tends to reflect radio frequency power back toward the source. This acts as a bottleneck, reducing the amount of power reaching the destination end of the cable. Choosing the correct 75 ohm coax cable. Most coaxial cables for video applications have a nominal impedance of 75 ohms. Their differing electrical and physical characteristics make it important to select the correct type of cable to suit the application.

Analogue TV

RG59 Acceptable performance on cable runs < 225 metres

RG6 Gives superior performance on cable runs < 225 metres. Used for cable runs > 225 metres but < 545 metres.

RG11 For cable runs greater than 545 metres.

CCTV

RG59 Acceptable performance on cable runs < 225 metres

RG6 Gives for superior performance on cable runs < 225 metres. Used for cable runs > 225 metres but < 545 metres.

RG11 For cable runs greater than 545 metres. This table is for reference only.

BT Cables survey of Part Numbers.

Application Tested Speciality RG-59 RG-6 RG-11 CCTV – PVC sheath 1000 MHz Solid conductor C1028 C1029 C1030 CCTV – HFFR sheath 1000 MHz Solid conductor C1428 C1429 C1430 CCTV 1000 MHz Flexible conductor C1275 C1276 C1277 CATV / SMATV 3000 MHz Dual screen C1025 C1026 C1027 CATV / SMATV 3000 MHz Quad screen C1256 C1257 C1241 HDTV – PVC sheath 4500 MHz Dual Screen 95% C1229 C1279 C1280 HDTV – HFFR sheath 4500 MHz Dual Screen 95% C1378 C1379 C1380

Operating temperature range: -25 to +75 °C and Rated Voltage: 300 Vrms

[email protected] 28

Page 29: Bt cables building infrastructure systems catalogue

Section 5.1 – BT Security-Tec ™– 75 ohm coax cables CCTV and Video Applications, sweep tested 1to 1000 MHz CABLE DESCRIPTION 1. Conductor Solid or Flexible Bare Copper 2. Dielectric Foamed Polyethylene (FPE) 3. Braid Bare Copper

4. Sheath Material Polyvinyl Chloride (PVC) or Halogen-Free (HFFR) Standard Put Up Length 305 or 500 metres

Standard References

IEC 61196 (BS) EN 50117 (BS) EN 50290-2 IEC 60332-1 (PVC sheath) or IEC 60332-3-24 (HFFR cable) IEC 61034 (only HFFR cable) IEC 60754-1 & 2 (HFFR cable) RoHS directives

Physical Characteristics

BT Cables Part

Number RG-Type

Conductor

(mm)

Diameter Dielectric

(mm)

Coverage braid (%)

Sheath Material

Overall Diameter

(mm)

Weight

(kg/km)

C1028 RG-59 0.81 solid 3.71 95 PVC 6.0 47.12 C1428 RG-59 0.81 solid 3.71 95 HFFR 6.0 48.5 C1275 RG-59 19x0.18TC 3.71 95 PVC 6.0 47.12 C1029 RG-6 1.02 solid 4.60 95 PVC 6.8 55.5 C1429 RG-6 1.02 solid 4.60 95 HFFR 6.8 58.2 C1276 RG-6 19x0.22 4.60 95 PVC 6.8 54.66 C1030 RG-11 1.63 solid 7.11 90 PVC 10.0 115.9 C1480 RG-11 1.63 solid 7.11 90 HFFR 10.0 120 C1277 RG-11 19x0.34 7.11 90 PVC 10.0 115.9

Electrical and Physical Characteristics (at 20°C)

BT Cables Part

Number RG-Type

Impedance (Ω)

Max. DC Resistance Conductor

(Ω/km)

Max. DC Resistance

screen (Ω/km)

Nominal

Capacitance (pF/m)

Min. Return Loss

1 to 1000 MHZ (dB)

C1028 RG-59 75 ± 3 33.5 10.1 53.5 20 C1428 RG-59 75 ± 3 33.5 10.1 53.5 20 C1275 RG-59 75 ± 3 40 10.1 53.5 20 C1029 RG-6 75 ± 3 21.5 10.8 53.5 20 C1429 RG-6 75 ± 3 21.5 10.8 53.5 20 C1276 RG-6 75 ± 3 30 10.8 53.5 20 C1030 RG-11 75 ± 3 8.8 6.5 52.8 20 C1480 RG-11 75 ± 3 8.8 6.5 52.8 20 C1277 RG-11 75 ± 3 8.8 6.5 52.8 20

Nominal Attenuation in dB/100m

MHz 5 10 50 100 200 300 400 450 550 700 750 870 1000 RG-59 1.9 2.95 6.23 8.53 11.81 15.3 16.41 18.92 21.03 22.97 24.8 26.84 27.89 RG-6 1.78 2.36 4.92 6.56 9.51 12.43 13.78 15.14 17.15 18.37 19.73 20.26 21.96 RG-11 0.99 1.51 2.96 4.27 6.23 8.27 9.51 10.31 11.51 13.45 13.95 14.87 17.06 For more details, please see the respective detailed datasheet(s).

[email protected] 29

Page 30: Bt cables building infrastructure systems catalogue

Section 5.2 – BT Security-Tec ™– 75 ohm coax cables SMATV - CATV and Video applications, sweep tested1to 3000 MHz CABLE DESCRIPTION 1. Conductor Solid Copper Covered Steel (CCS) 2. Dielectric

Foamed Polyethylene (FPE) 3. Screen 1

Bonded Aluminium/ Polyester foil 100% coverage

4. Braid 1

Aluminium

5. Braid 2 (Quad scrn only) Aluminium/Polyester foil 100% coverage

6. Screen 2 (Quad scrn only)

Aluminium

7. Sheath Polyvinyl Chloride (PVC)

Standard Put Up Length 305 or 500 metres

Standard References IEC 61196 (BS) EN 50117 (BS) EN 50290-2 IEC 60332-1 RoHS directives

Physical Characteristics

BT Cables Part

Number RG-Type

Conductor

(mm)

Diameter Dielectric

(mm)

Type of

Screen

Coverage braid (%)

Sheath Material

Overall Diameter

(mm)

Weight

(kg/km)

C1025 RG-59-3 GHz 0.81 3.71 Dual scrn 54 PVC 6.0 32.42 C1256 RG-59-3 GHz 0.81 3.71 Quad scrn 54 + 46 PVC 6.73 39.4 C1026 RG-6-3 GHz 1.02 4.60 Dual scrn 60 PVC 6.8 41.32 C1257 RG-6-3 GHz 1.02 4.60 Quad scrn 60 + 40 PVC 7.52 49.5 C1027 RG-11-3 GHz 1.63 7.11 Dual scrn 61 PVC 10.0 86.6 C1241 RG-11-3 GHz 1.63 7.11 Quad scrn 60 +40 PVC 10.3 90.6

Dual Screen = Screen 1 + Braid 1 Quad Screen = Screen 1 + Braid 1 + Screen 2 + Braid 2

Electrical and Physical Characteristics (at 20°C)

BT Cables Part

Number RG-Type Imped.

(Ω)

Max. DC Resistance Conductor

(Ω/km)

Max. DC Resistance

Screen (Ω/km)

Nominal Capacitance

(pF/m)

Min. Return Loss (dB)

< 1000 MHz

< 2000 MHz

< 3000 MHz

C1025 RG-59-3 GHz 75 ± 3 146.5 52 53 20 18 16 C1256 RG-59-3 GHz 75 ± 3 146.5 26 53 20 20 20 C1026 RG-6-3 GHz 75 ± 3 92.2 30 53 20 20 20 C1257 RG-6-3 GHz 75 ± 3 92.2 17 53 20 20 20 C1027 RG-11-3 GHz 75 ± 3 36.5 25 53 20 20 20 C1241 RG-11-3 GHz 75 ± 3 36.5 12 53 20 20 20

Nominal Attenuation in dB/100m

MHz 5 10 50 100 200 400 550 870 1250 1750 2150 2500 3000 RG-59 2.92 3.45 5.40 8.21 12.56 16.01 19.36 24.74 30.62 36.71 40.82 44.72 48.64 RG-6 2.2 2.48 5.15 6.6 9.56 13.12 15.45 19.69 24.25 29.26 32.88 35.88 39.83 RG-11 1.25 2.03 3.75 5.01 6.85 7.05 9.65 12.6 16.66 20.28 22.93 25.12 28.08 For more details, please see the respective detailed datasheet(s)

[email protected] 30

Page 31: Bt cables building infrastructure systems catalogue

Section 5.3 – BT Security-Tec ™– 75 ohm coax cables HDTV and HD Video applications, sweep tested1to 4500 MHz CABLE DESCRIPTION 1. Conductor Solid Bare Copper 2. Dielectric Foamed Polyethylene 3. Screen Bonded Aluminium/ Polyester foil 100% coverage

4. Braid Tinned Copper 5. Sheath Material Polyvinyl Chloride (PVC) or Halogen-free (HFFR) Colour: Orange Standard Put Up Length 305 or 500 metres

Standard References IEC 61196 (BS) EN 50117 (BS) EN 50290-2 IEC 60332-1(PVC sheath) or IEC 60332-3C ( HFFR cable) IEC 61034 (HFFR cable) IEC 60754-1 & 2 (HFFR cable) RoHS directives

Physical Characteristics

BT Cables Part

Number RG-Type

Conductor

(mm)

Diameter Dielectric

(mm)

Coverage braid (%)

Sheath Material

Overall Diameter

(mm)

Weight

(kg/km)

C1229 RG-59-4.5 GHz 0.81 3.71 95 PVC 6.0 46.72 c1378 RG-59-4.5 GHz 0.81 3.71 95 HFFR 6.0 48.2 C1279 RG-6-4.5 GHz 1.02 4.60 95 PVC 6.8 56.2 c1379 RG-6-4.5 GHz 1.02 4.60 95 HFFR 6.8 59 C1280 RG-11-4.5 GHz 1.63 7.11 95 PVC 10.0 114.5 C1380 RG-11-4.5 GHz 1.63 7.11 95 HFFR 10.0 117

Electrical and Physical Characteristics (at 20°C)

BT Cables Part

Number RG-Type Imp.

(Ω)

Max. DC Resistance Conductor

(Ω/km)

Max. DC Resistance

Screen (Ω/km)

Nom. Cap.

(pF/m)

Min. Return Loss (dB)

<1000 MHz

< 2000 MHz

< 3000 MHz

< 4500 MHz

C1229 RG-59-4.5 GHz 75 ± 3 33.5 12.5 53 23 22 16 15 c1378 RG-59-4.5 GHz 75 ± 3 33.5 12.5 53 23 22 16 15 C1279 RG-6-4.5 GHz 75 ± 3 21.5 10.6 53 23 22 16 15 c1379 RG-6-4.5 GHz 75 ± 3 21.5 10.6 53 23 22 16 15 C1280 RG-11-4.5 GHz 75 ± 3 8.8 6.6 53 23 22 16 15 C1380 RG-11-4.5 GHz 75 ± 3 8.8 6.6 53 23 22 16 15

Nominal Attenuation in dB/100m

MHz 1 5 10 50 100 300 550 750 1000 2000 3000 4500 RG-59 0.98 2.07 2.95 6.23 7.55 13.68 18.83 22.23 25.96 38.24 46.13 56.50 RG-6 0.79 1.71 2.33 4.57 6.40 11.96 15.76 18.05 21.36 31.44 39.76 50.46 RG-11 0.53 1.12 1.51 2.96 4.20 7.49 10.41 12.38 14.57 21.84 27.93 35.98

For more details, please see the respective detailed datasheet(s).

[email protected] 31

Page 32: Bt cables building infrastructure systems catalogue

Section 6 – BT Data-Tec™ - Category LAN Cables Application and Construction of Category Cables for Local Area Networks and Structured Wiring Systems 1. Application

Horizontal or Building Wiring for one of the following categories of twisted pair cabling systems

Category Max. data rate

Usual application Standard(s)

TIA/EIA ISO/IEC EN Cat 1 1 Mbps Analogue voice

De facto, never a standard Cat 2 4 Mbps Token ring of IBM Cat 3 16 Mbps Voice, 10MbE(thernet) TIA/EIA 568-B Cat 4 20 Mbps 16 Mbps Token Ring Was only a standard briefly Cat 5 100 MHz 10/100/1000 MbE

155 Mbps ATM, 4/16 Mbps Token Ring

Replaced by 5e

Cat 5e 100 MHz

TIA/EIA 568-C.2

ISO/IEC 11806, 2nd edition IEC 61156

EN 50173-1 EN 50288

Cat 6 250 MHz as Cat5e plus 10Gb Ethernet over ≤ 55 m.

Cat 6a 500 MHz As Cat 6 plus 10Gb Ethernet over 100 m.

Cat 7 600 MHz As Cat 6a plus supporting 100GbE

ISO/IEC 11801: 2002, category 7 / class F

Cat 7a 1000 MHz CATV (862 MHz), 40GBASE-T over 50 m. 100GbE over 15 m.

Cat 7a is not recognised in TIA/EIA-569

ISO/IEC 11801, amendment 1 (2008) and amendment 2 (2010).

2. Basic Cable Construction of the standard cables (not being patch cables) Wire = Conductor with Insulation Insulation: will be good strippable, suitable for insulation displacement and coloured. The colours are not interchangeable. Pair = two twisted – colour coded – wires. Individually screened pair (if applicable): one pair wrapped with an Aluminium/Polyester foil under which a drain wire. Braiding (if applicable): tinned copper wires.

Ripcord: to ease removal of the sheath. Sheath: PVC or Halogen-Free (HFFR).

Cat 3 Cat 5e Cat 6 Cat 6a Cat 7 Cat 7a

Type UUTP UUTP FUTP UUTP FUTP UUTP UFTP &

FUTP S-FTP S-FTP

Conductor Solid BC Solid BC Solid BC Solid BC Solid BC Solid BC Insulation Polyolefin PE PE Skin-foam-skin PE Cable core 6 to 200 pairs 4 pairs 4 Individually screened pairs Core wrapping Yes No Drain wire No No Yes No Yes No Central drain wire Overall screen No No Foil No Foil Braiding Sheath PVC PVC or HFFR HFFR

[email protected] 32

Page 33: Bt cables building infrastructure systems catalogue

Section 6 – BT Data-Tec™ - Category LAN Cables 3. Basic Cable Construction of the standard patch cables

Cat 5e Cat 6 Type UUTP FUTP UUTP FUTP Conductor Flexible BC Insulation PE PE Cable core 4 pairs 4 pairs Core wrapping no yes no yes Drain wire (TC) no yes no yes Overall Screen no foil no foil Rip cord yes Sheath PVC or HFFR

4. General Characteristics

Cat 3 Cat 5e Cat 6 Cat 6a Cat 7 Max. DCR conductor Ω/100m 9.6 9.38 9.38 7.7 7.7 Impedance Ω 100 100 100 100 100

Standard Colour scheme of Cat 5e – 6 – 6a and 7:

Pair number Pair 1 Pair 2 Pair 3 Pair 4 a-wire Blue Orange Green Brown

b-wire White

with blue stripe White

with orange stripe White

with green stripe White

with brown stripe Operating temperature range: -20 to +80 °C and Rated Voltage: 300 Vrms. 5. Cable Range of BT Cables:

2 pairs 6 pairs 12 pairs 25 pairs 50 pairs 100 pairs 150 pairs 200 pairs Cat3 - PVC C1031 C1266 C1267 C1032 C1033 C1034 C1268 C1269

Category Cat 5e Cat 5e Cat 5e Cat 5e Cat 5e Cat 5e Type UTP UTP-UL listed UTP FTP FTP-UL listed FTP Sheath PVC PVC HFFR PVC PVC HFFR BT P/N C1035 C1285 C1235 C1036 C1286 C1236

Category Cat 6 Cat 6 Cat 6 Cat 6 Cat 6 Cat 6 Type UUTP UUTP-UL listed UUTP FUTP FUTP-UL listed FUTP Sheath PVC PVC HFFR PVC PVC HFFR BT P/N C1037 C1287 C1227 C1038 C1288 C1238

Category Cat 6a Cat 6a Cat 7 Cat 7a Type U-UTP U-FTP S-FTP S-FTP Sheath PVC HFFR HFFR HFFR BT P/N C1200 C1053 C1039 C1201

Category Cat 5e Cat 5e Cat 5e Cat 5e Cat 6 Cat 6 Cat 6 Cat 6 Type UTP-Patch UTP-Patch FTP-Patch FTP-Patch UTP-Patch UTP-Patch FTP-Patch FTP-Patch Sheath PVC HFFR PVC HFFR PVC HFFR PVC HFFR BT P/N C1500 C1510 C1520 C1530 C1540 C1550 C1560 C1570

Non-standard cable constructions, colours, details and/or additional information are available on request.

For more details, please see the respective detailed datasheet(s).

Please note that technical specifications are subject to change without notice.

[email protected] 33

Page 34: Bt cables building infrastructure systems catalogue

Section 6.1 – BT Data-Tec™ - Category LAN Cables Cat 5e and 6 UTP and FTP cables Cat 5e cables

Cat 5e Variants BT Cables

Part Number Type Sheath

Overall Diameter (mm)

Weight (kg/km)

C1035 UUTP PVC 5.0 30 C1285 UUTP-UL PVC 5.0 30 C1235 UUTP HFFR 5.0 29 C1036 FUTP PVC 6.3 42 C1286 FUTP-UL PVC 6.3 42 C1236 FUTP HFFR 6.3 42

Main Transmission Characteristics of Cat 5e cables

Frequency (MHz)

Min. Return Loss

(dB/100m)

Maximum Attenuation (dB/100m)

Minimum NEXT (dB)

Maximum Time Delay (ns/100m)

Minimum PSNEXT

(dB)

Minimum ELFEXT

(dB)

Minimum PSELFEXT

(dB)

1 20.0 2.0 65.3 570.00 62.3 64.0 61.0 4 23.0 4.1 56.3 552.00 53.3 52.0 49.0 8 24.5 5.8 51.8 546.73 48.8 45.9 42.9

10 25.0 6.5 50.3 545.38 47.3 44.0 41.0 16 25.0 8.2 47.2 543.00 44.4 39.9 36.9 20 25.0 9.3 45.8 542.05 42.8 38.0 35.0 25 24.3 10.4 44.3 541.20 41.3 35.8 33.0

31.25 23.6 11.7 42.9 540.44 39.9 34.1 31.1 62.5 21.5 17.0 38.4 538.55 35.4 28.1 25.1 100 20.1 22.0 35.3 537.60 32.3 24.0 21.0

Cat 6 cables

Cat 6 Variant BT Cables

Part Number Type Sheath

Overall Diameter (mm)

Weight (kg/km)

C1037 UUTP PVC 6.2 42 C1287 UUTP-UL PVC 6.2 42 C1237 UUTP HFFR 6.2 42 C1038 FUTP PVC 7.4 56 C1288 FUTP-UL PVC 7.4 56 C1238 FUTP HFFR 7.4 54.1

Main Transmission Characteristics of Cat 6 cables

Frequency (MHz)

Return Loss

(dB/100m)

Maximum Attenuation (dB/100m)

Minimum NEXT (dB)

Maximum Time Delay (ns/100m)

Minimum PSNEXT

(dB)

Minimum ELFEXT

(dB)

Minimum PSELFEXT

(dB)

1 20.0 2.0 74.3 570.00 72.3 67.8 64.8 4 23.0 3.8 65.3 552.00 63.3 55.8 52.8 8 24.5 5.3 60.8 546.73 58.8 49.7 46.7

10 25.0 6.0 59.3 545.38 57.3 47.8 44.8 16 25.0 7.6 56.2 543.00 54.2 43.7 40.7 20 25.0 8.5 54.8 542.05 52.8 41.8 38.8 25 24.3 9.5 53.3 541.20 51.3 39.8 36.8

31.25 23.6 10.7 51.9 540.44 49.9 37.9 34.9 62.5 21.5 15.4 47.4 538.55 45.4 31.9 28.9 100 20.1 19.8 44.3 537.80 42.3 27.8 24.8 200 18.0 29.0 39.8 536.54 37.8 21.8 18.8 250 17.3 32.8 38.3 536.27 36.3 19.8 16.8

For more details, please see the respective detailed datasheet(s).

[email protected] 34

Page 35: Bt cables building infrastructure systems catalogue

Section 6.2 – BT Data-Tec™ - Category LAN Cables Cat 6a U-FTP and Cat 7 S-FTP cables Cat 6a U-FTP cables

Cat 6a Variants BT Cables

Part Number Type Sheath

Overall Diameter (mm)

Weight (kg/km)

C1200 U-UTP PVC 8.3 61.2 C1053 U-FTP HFFR 7.2 49.9

Main Transmission Characteristics of Cat 6a U-FTP cables

Freq.

(MHz) Return Loss (dB/100m)

Attenuation (dB/100m)

NEXT (dB/100m)

PSNEXT (dB/100m)

ELFEXT (dB/100m)

Impedance (Ohm))

1 20.0 3.7 74.3 72.3 55.9 100 ± 15 10 25.0 5.8 59.3 57.3 47.8 100 ± 15

31.25 23.6 10.4 51.9 49.9 37.9 100 ± 15 100 20.1 19.0 44.3 42.3 27.8 100 ± 15 300 17.3 34.2 37.1 35.1 18.1 100 ± 25 500 17.3 45.2 33.8 31.8 14.0 100 ± 15

Cat 7 cables

Cat 7 Variants BT Cables

Part Number Type Sheath

Overall Diameter (mm)

Weight (kg/km)

C1039 S-FTP HFFR 7.8 67.5 Main Transmission Characteristics of Cat 7 S-FTP cables

Frequency (MHz)

Return Loss (dB/100m)

Attenuation (dB/100m)

NEXT (dB)

PSNEXT (dB)

ELFEXT (dB)

Impedance (Ohm)

1 20.0 2.5 78 75 78.0 100 ± 15 10 25.0 6.5 78 75 56.5 100 ± 15 20 25.0 8.9 78 75 56.5 100 ± 15

62.5 21.5 14.9 75.5 72.5 56.8 100 ± 15 300 14.5 35.2 65.2 62.2 25.0 100 ± 25 600 12.5 50.1 60.7 57.7 16.0 100 ± 25

Cat 7a cables

Cat 7a Variants BT Cables

Part Number Type Sheath

Overall Diameter (mm)

Weight (kg/km)

C1201 S-FTP HFFR 8.5 71.1 Main Transmission Characteristics of Cat 7a S-FTP cables

Frequency (MHz)

Return Loss (dB/100m)

Attenuation (dB/100m)

NEXT (dB)

PSNEXT (dB)

ACR (dB)

Impedance (Ohm)

4 23.0 4.0 80.0 77.0 78.0 100 ± 15 10 25.0 5.8 80.0 77.0 74.3 100 ± 15 20 25.0 8.2 80.0 77.0 71.0 100 ± 15

62.5 21.5 14.6 80.0 77.0 60.6 100 ± 15 300 17.3 32.7 71.2 68.2 38.6 100 ± 25 600 17.3 47.1 66.7 63.7 19.6 100 ± 25 900 17.3 54.9 64.9 61.9 9.93 100 ± 25

1000 16.0 61.9 63.4 60.4 1.47 100 ± 25

For more details, please see the respective detailed datasheet(s).

[email protected] 35

Page 36: Bt cables building infrastructure systems catalogue

Section 6.3 – BT Data-Tec™ - Category LAN Cables Cat 5e and Cat 6 UTP and FTP PATCH Cables Cat 5e and Cat6 Patch cables

Cat 5e Variants BT Cables

Part Number Type Sheath

Overall Diameter (mm)

Weight (kg/km)

C1500 UUTP PVC 5.2 30.7 C1510 UUTP HFFR 5.2 31.4 C1520 FUTP PVC 5.1 31.2 C1530 FUTP HFFR 5.1 31.1

Main Transmission Characteristics of Cat 5e Patch cables

Cat 5e - Patch UTP / FTP UTP FTP UTP / FTP UTP / FTP UTP / FTP UTP / FTP

Frequency (MHz)

Return Loss

(dB/100m)

Maximum Attenuation (dB/100m)

Minimum NEXT (dB)

Minimum PSNEXT

(dB)

Minimum ELFEXT

(dB)

Minimum PSELFEXT

(dB)

1 20.0 2.4 3.1 65.3 62.3 63.8 60.8 4 23.0 4.9 6.1 56.3 53.3 51.8 48.8 8 24.5 6.9 8.6 51.8 48.8 45.7 42.7

10 25.0 7.8 9.7 50.3 47.3 43.8 40.8 16 25.0 9.9 12.4 47.2 44.2 39.7 36.7 20 25.0 11.1 13.9 45.8 42.8 37.8 34.8 25 24.2 12.5 15.6 44.3 41.3 35.8 32.8

31.25 23.3 14.1 17.6 42.9 39.9 33.9 30.9 62.5 20.7 20.4 25.5 38.4 35.4 27.9 24.9 100 19.0 26.4 33.0 35.3 32.3 23.8 20.8

Cat 6 Patch cables

Cat 6 Variants BT Cables

Part number Type Sheath

Overall Diameter (mm)

Weight (kg/km)

C1540 UUTP PVC 5.9 31.6 C1550 UUTP HFFR 5.9 32.4 C1560 FUTP PVC 6.2 34.6 C1570 FUTP HFFR 6.2 35.8

Main Transmission Characteristics of Cat 6 Patch cables

Cat 6 - Patch UTP / FTP UTP FTP UTP / FTP UTP / FTP UTP / FTP UTP / FTP

Frequency (MHz)

Return Loss

(dB/100m)

Maximum Attenuation (dB/100m)

Minimum NEXT (dB)

Minimum PSNEXT

(dB)

Minimum ELFEXT

(dB)

Minimum PSELFEXT

(dB)

1 20.0 2.4 3.1 74.3 72.3 67.8 64.8 4 23.0 4.6 6.1 65.3 63.3 56.0 53.0

10 25.0 7.2 8.6 59.3 57.3 48.0 45.0 16 25.0 9.1 12.4 56.2 54.2 43.9 40.9 20 25.0 10.2 13.9 54.8 52.8 42.0 39.0

31.25 23.3 12.9 17.6 51.9 49.9 38.1 35.1 62.5 20.7 18.6 25.5 47.4 45.4 32.1 29.1 100 19.0 23.9 33.0 44.3 42.3 28.0 25.0 200 16.4 35.0 48.6 39.8 37.8 22.0 19.0 250 15.5 39.4 55.3 38.3 36.3 20.0 17.0

For more details, please see the respective detailed datasheet(s).

[email protected] 36

Page 37: Bt cables building infrastructure systems catalogue

Section 6.4 – BT Data-Tec™ - Category LAN Cables Cat 3 multi pair Cables Cat 3 cables

Cat 3 cables

BT Cables Part

Number

No. of pairs

Nom. Diameter Conductor

(mm)

Nom. Diameter Insulation

(mm)

Nom. Overall Diameter

(mm)

Weight

(kg/km)

C1031 2 0.5 0.9 3.6 16 C1266 6 0.5 0.9 5.5 39 C1267 12 0.5 0.9 7.4 73 C1032 25 0.5 0.9 11.8 154 C1033 50 0.5 0.9 15.5 280 C1034 100 0.5 0.9 21.6 530 C1268 150 0.5 0.9 26.8 800 C1269 200 0.5 0.9 29.4 1040

Electrical Characteristics Cat 3 cables at 20°

Frequency Max. Attenuation Max. NEXT Min. Return Loss Impedance

MHz (dB/100m) (dB) (dB) (Ohm) 1 2.6 41.3 12.0 100 ± 15 4 5.6 32.3 12.0 100 ± 15 8 8.5 27.8 12.0 100 ± 15

10 9.7 26.3 12.0 100 ± 15 16 13.1 23.3 10.0 100 ± 15

Cable Make-Up Cat 3 cables

BT Cables Part Number C1031 C1266 C1267 C1032 C1033 C1034 C1268 C1269

No of pairs 2 6 12 25 50 100 150 200

Number of pairs per unit 25 10 25 25 25

Number of units in the centre 1 5 4 1 1

Number of units in the 1e layer 5 7

Pair Colour Code Cat 3 cables

Pair No.

Pair Colours in

2 – 6 -12 or 25 pairs

cables

Pair No.

Pair Colours in

Unit of 12 or 25 pairs Pair No.

Pair Colours in

Unit of 25 pairs

1 White / Blue 11 Black / Blue 21 Purple / Blue

2 White / Orange 12 Black / Orange 22 Purple / Orange

3 White / Green 13 Black / Green 23 Purple / Green

4 White / Brown 14 Black / Brown 24 Purple / Brown

5 White / Grey 15 Black / Grey 25 Purple / Grey

6 Red / Blue 16 Yellow / Blue

7 Red / Orange 17 Yellow / Orange

8 Red / Green 18 Yellow / Green

9 Red / Brown 19 Yellow / Brown

10 Red / Grey 20 Yellow / Grey

For more details, please see the respective detailed datasheet(s).

[email protected] 37

Page 38: Bt cables building infrastructure systems catalogue

Section 7 – BT Industrial-Tec™ - DEF Standard Cables DEF Standard 51-12 Parts 4 & 5 1. Application Originally developed for military use, these flexible multi-conductor cables are now widely used within the industry. They are designed for high density wiring between and within instruments and electronic equipment and/or components and especially used in process control systems, computers, data processors, sound systems and of course in military equipment. 2. Main Standard DEF standard 61-12, part 4 and 5. 2. Basic Construction of the cables Wire = Conductor with Insulation. Conductor: flexible = stranded tinned copper wires.

Size mm2 0.055 0.22 0.5 configuration mm 7 x 0.1 7 x 0.2 16 x 0.20 Max. DC Resistance Ω/km 345 86.2 37.7 Max. recommended current Amps 0.25 1 2.5 Rated Voltage Vrms 250 440 440

Insulation: PVC (Polyvinyl Chloride). Good strippable and coloured insulation. The colours are not interchangeable. Cable core: two or more wires, stranded. Colour scheme:

Core No.

Color Core No.

Color Core No.

Color Core No.

Color

1 Red 11 Turquoise 21 BLUE/Black 31 WHITE/Brown 2 Blue 12 Grey 22 ORANGE/Blue 32 BROWN/Black 3 Green 13 RED/Blue 23 GREEN/Blue 33 GREY/Brown 4 Yellow 14 GREEN/Red 24 GREY/Blue 34 YELLOW/Violet 5 White 15 YELLOW/Red 25 YELLOW/Green 35 VIOLET/Black 6 Black 16 WHITE/Red 26 WHITE/Green 36 WHITE/Violet 7 Brown 17 RED/Black 27 GREEN/Black

50 Special scheme,

on request available 8 Violet 18 RED/Brown 28 ORANGE/Green 9 Orange 19 YELLOW/Blue 29 GREY/Green

10 Pink 20 WHITE/Blue 30 YELLOW/Brown Drain wire (only in combination with a screen): twisted (= flexible) tinned copper wires. Screen (if applicable): Braiding of tinned copper wires, coverage 91%. Sheath: grey PVC. Flame Retardancy: IEC 60332-1 (Vertical Wire test). Operating temperature range: -20 to +70 °C. Non-standard cable constructions, colours, details and/or additional information are available on request.

For more details, please see the respective detailed datasheet(s).

Please note that technical specifications are subject to change without notice.

[email protected] 38

Page 39: Bt cables building infrastructure systems catalogue

Section 7 – BT Industrial-Tec™ - DEF Standard Cables CABLE DESCRIPTION 1. Conductor

Stranded Tinned Copper

2. Insulation PVC

3. Cable core) Two or more wires stranded

4. Screen (if required)

Tinned Copper 91% Coverage

5. Ripcord

6. Sheath Material Flame-Retardant

Polyvinyl Chloride (PVC) Standard colour: grey

Standard Put Up Length

305 metres Standard References DEF standard 61-12, part 4 & 5 IEC 60332-1

RoHS directives

Conductor 7 x 0.1 mm = 0.055 mm² No of wires

BT Cables Part Number

Screen Diameter

(mm)

BT Cables Part Number

Screen Diameter

(mm) 2 C1164 Yes 3.2 C1360 No 2.3 3 C1165 Yes 3.6 C1361 No 2.4 4 C1362 No 2.6 6 C1166 Yes 4.2 C1144 No 3.1 9 C1145 No 3.7

15 C1146 No 4.2 25 C1168 Yes 6.3 C1147 No 5.5 36 C1169 Yes 6.9 C1148 No 6.1 50 C1365 Yes 8.0 C1364 No 7.2

Conductor 7 x 0.2 mm = 0.22 mm² No of wires

BT Cables Part Number

Screen Diameter

(mm)

BT Cables Part Number

Screen Diameter

(mm) 2 C1366 No 3.4 3 C1367 No 3.6 4 C1471 Yes 4.4 C1368 No 3.9 6 C1472 Yes 5.6 C1369 No 4.6 8 C1473 Yes 6.1 C1154 No 5.6

12 C1474 Yes 6.9 C1155 No 6.1 20 C1475 Yes 8.6 C1156 No 7.8 36 C1476 Yes 10.8 C1157 No 9.8

Conductor 16 x 0.2 mm = 0.5 mm² No of wires

BT Cables Part Number

Screen Diameter

(mm)

BT Cables Part Number

Screen Diameter

(mm) 2 C1158 No 5.5 3 C1370 No 5.8 4 C1177 Yes 7.3 C1371 No 6.3 6 C1178 Yes 8.3 C1372 No 7.3

12 C1375 Yes 10.5 C1373 No 9.5 18 C1180 Yes 12.0 C1374 No 11.0

For more details, please see the respective detailed datasheet(s)

[email protected] 39

Page 40: Bt cables building infrastructure systems catalogue

Section 8 – BT Industrial-Tec™ - Industrial Cables Application and Construction 1. Application These cables are generally used to transmit analogue or digital signals in industrial process plants where chemical and mechanical protections are needed (chemical and petrochemical industries). The unarmoured versions (Type 1) are generally use for indoor installation. 2. Main Standard BS(PAS) 5308 – Part 2 – Type 1 & 2. 2. Basic Construction of the cables Wire = Conductor with Insulation. Conductor: flexible = stranded tinned copper wires. Pair: two twisted wires.

Conductor Size mm2 0.5 0.75 1.5 configuration mm 16 x 0.2 24 x 0.2 7 x 0.53 Max. DC Resistance at 20°C Ω/km 39.7 26.5 12.3 Max. conductor temperature °C 65 65 65 Min. operating temperature °C -20 -20 -20 Max. recommended current Amps 6 8 12 Max. mutual capacitance at 1 kHz pF/m 250 250 250 Max. L/R ratio μH/Ω 25 25 40 Rated Voltage Vrms 300 / 500 300 / 500 300 / 500

Insulation: PVC (Polyvinyl Chloride) in accordance with BS 7655. Good strippable and coloured insulation. The colours are not interchangeable. Cable core: two or more pairs, stranded. Colour scheme:

Pair No. 1 2 3 4 5 6 7 8 9 10 a-wire White White White White White Red Red Red Red Red b-wire Blue Orange Green Brown Grey Blue Orange Green Brown Grey Pair No. 11 12 13 14 15 16 17 18 19 20 a-wire Black Black Black Black Black Yellow Yellow Yellow Yellow Yellow b-wire Blue Orange Green Brown Grey Blue Orange Green Brown Grey

Drain wire (only in combination with an individual or collective screen): stranded tinned copper wires. Individual Screen (if applicable): Aluminium/Polyester (Alpet) tape. Coverage ≥ 115%. Collective Screen (if applicable): Aluminium/Polyester (Alpet) tape. Coverage ≥ 115%. Bedding (if applicable): Flame Retardant PVC. Armour (if applicable): galvanised steel wires. Sheath: Flame Retardant PVC. Flame Retardancy: IEC 60332-1 (Vertical Wire test). Non-standard cable constructions, colours, details and/or additional information are available on request.

For more details, please see the respective detailed datasheet(s).

Please note that technical specifications are subject to change without notice.

[email protected] 40

Page 41: Bt cables building infrastructure systems catalogue

Section 8 – BT Industrial-Tec™ - Industrial Cables BS(PAS) 5308 - Part 2 – Type 1 – Collectively Screened Cables

Conductor 0.5 mm² (16 x 0.2 mm)

No of pairs

BT Cables

Part Number

Armour

Diameter (mm)

Weight (kg/km

BT Cables

Part Number

Armour

Diameter (mm)

Weight (kg/km)

1 C1081 No 7.0 50 C1096 Yes 11.4 240 2 C1082 No 7.9 72 C1092 Yes 12.3 290 5 C1083 No 13.1 170 C1093 Yes 17.9 510

10 C1084 No 17.2 290 C1094 Yes 22.9 880 20 C1085 No 22.3 500 C1095 Yes 29.1 1500

Conductor 0.75 mm² (24 x 0.2 mm)

No of pairs

BT Cables

Part Number

Armour

Diameter (mm)

Weight (kg/km

BT Cables

Part Number

Armour

Diameter (mm)

Weight (kg/km)

1 C1086 No 7.3 60 C1101 Yes 11.7 270 2 C1087 No 8.3 100 C1102 Yes 12.9 310 5 C1088 No 14.3 210 C1103 Yes 19.8 710

10 C1089 No 18.7 350 C1104 Yes 25.3 1200 20 C1090 No 24.5 750 C1105 Yes 31.3 1700

Conductor 1.5 mm² (7 x 0.53 mm)

No of pairs

BT Cables

Part Number

Armour

Diameter (mm)

Weight (kg/km

BT Cables

Part Number

Armour

Diameter (mm)

Weight (kg/km)

1 C1091 No 8.3 90 C1106 Yes 12.9 300 2 C1092 No 9.7 140 C1107 Yes 14.3 390 5 C1093 No 16.4 330 C1108 Yes 22.1 870

10 C1094 No 20.6 580 C1109 Yes 28.4 1500 20 C1095 No 28.5 1100 C1110 Yes 35.7 2400

For more details, please see the respective detailed datasheet(s)

[email protected] 41

Page 42: Bt cables building infrastructure systems catalogue

Section 8 – BT Industrial-Tec™ - Industrial Cables BS(PAS) 5308 - Part 2 – Type 1 – Individually & Collectively Screened Cables

Conductor 0.5 mm² (16 x 0.2 mm)

No of pairs

BT Cables

Part Number

Armour

Diameter (mm)

Weight (kg/km

BT Cables

Part Number

Armour

Diameter (mm)

Weight (kg/km)

2 C1111 No 12.0 100 C1123 Yes 16.8 450 5 C1112 No 15.2 250 C1124 Yes 20.9 750

10 C1113 No 21.1 480 C1125 Yes 27.9 1300 20 C1114 No 27.3 780 C1126 Yes 34.4 1900

Conductor 0.75 mm² (24 x 0.2 mm)

No of pairs

BT Cables

Part Number

Armour

Diameter (mm)

Weight (kg/km

BT Cables

Part Number

Armour

Diameter (mm)

Weight (kg/km)

2 C1115 No 12.8 190 C1127 Yes 17.6 490 5 C1116 No 16.3 270 C1128 Yes 22.0 801

10 C1117 No 22.7 550 C1129 Yes 29.5 1800 20 C1118 No 29.8 960 C1130 Yes 37.8 2200

Conductor 0.75 mm² (24 x 0.2 mm)

No of pairs

BT Cables

Part Number

Armour

Diameter (mm)

Weight (kg/km

BT Cables

Part Number

Armour

Diameter (mm)

Weight (kg/km)

2 C1119 No 14.7 250 C1131 Yes 20.4 660 5 C1120 No 18.8 460 C1132 Yes 25.4 1000

10 C1121 No 26.5 760 C1133 Yes 33.5 1700 20 C1122 No 34.4 1350 C1134 Yes 42.6 2800

For more details, please see the respective detailed datasheet(s)

[email protected] 42

Page 43: Bt cables building infrastructure systems catalogue

Section 9 - BT Industrial-Tec™ -– Control Cables Application and Construction 1. Application These cables are commonly used as interconnecting cables to control, measure and regulate processor aided production within the industry and also as flexible power control cables suitable for robotic and automated equipment. 2. Main Standard VDE 0250/VDE 0255 2. Basic Construction of the cables Wire = Conductor with Insulation. Conductor: flexible = stranded tinned copper wires.

Conductor Size mm2 0.75 1.0 1.5 2.5 4 6 Conductor material bare copper configuration mm 24x0.2 32x0.2 30x0.24 50x0.24 56x0.29 84x0.29 Max. DC Resistance at 20°C Ω/km 27 20.2 14 8.4 4.95 3.3

Insulation: Flame Retardant PVC (Polyvinyl Chloride). Insulation Resistance > 500 MΩ/km. Good strippable insulation.

Conductor Size mm2 0.75 1.0 1.5 2.5 4 6 Radial thickness insulation mm 0.5 0.5 0.4 0.5 0.8 0.7

Cable core: three or more wires stranded. In case of 5 wires with a central filler. Colour scheme: Green/yellow - black with printed numbers. Collective Screen (CY series): braiding of tinned copper wires with a coverage of 70%. Bedding (SY series): Flame Retardant PVC. Armour (SY series): galvanised steel wires. Sheath: Flame Retardant PVC. Flame Retardancy: IEC 60332-1 (Vertical Wire test). Operating temperature range: -20 to +70 °C. Rated Voltage: 300 V. Cable Types: YY series: three or more stranded cores, surrounded by a PVC sheath.

CY series: as YY series plus a collective screen between cable core and PVC sheath.

SY series: as YY series plus a Steel Wire Armouring between cable core and transparent PVC sheath. Non-standard cable constructions, colours, details and/or additional information are available on request.

For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.

[email protected] 43

Page 44: Bt cables building infrastructure systems catalogue

Section 9 - BT Industrial-Tec™ -– Control Cables YY Series: Cable core of stranded cores surrounded by a PVC sheath

No of wires

BT Cables

Part Number

Conductor

(mm² / mm)

Diameter

(mm)

BT Cables Part Number

Conductor

(mm² / mm)

Diameter

(mm) 3 C1631 0.75 / 24x0.2 5.6 C1632 1.0 / 32X0.2 6.2 4 C1635 0.75 / 24x0.2 6.6 C1636 1.0 / 32X0.2 7.1

12 C1645 0.75 / 24x0.2 10.4 18 C1648 0.75 / 24x0.2 12.4

No of wires

BT Cables

Part Number

Conductor

(mm² / mm)

Diameter

(mm)

BT Cables Part Number

Conductor

(mm² / mm)

Diameter

(mm) 3 C1633 1.5 / 30X0.24 6.5 C1634 2.5 / 50X0.24 6.5 4 C1637 1.5 / 30X0.24 7.6 C1638 2.5 / 50X0.24 9.1 5 C1639 1.5 / 30X0.24 8.4 C1640 2.5 / 50X0.24 10.3 7 C1641 1.5 / 30X0.24 9.5 C1642 2.5 / 50X0.24 11.8 8 C1643 1.5 / 30X0.24 10.4 C1644 2.5 / 50X0.24 12.6

12 C1646 1.5 / 30X0.24 12.4 C1647 2.5 / 50X0.24 14.9 18 C1649 1.5 / 30X0.24 14.5 C1650 2.5 / 50X0.24 14.5

CY Series: Cable core of stranded cores surrounded by a braiding of tinned copper wires plus a PVC sheath

No of wires

BT Cables

Part Number

Conductor

(mm² / mm)

Diameter

(mm)

BT Cables Part Number

Conductor

(mm² / mm)

Diameter

(mm) 3 C 1620 0.75 / 24x0.2 6.0 C1621 1.0 / 32X0.2 6.4 4 C1624 0.75 / 24x0.2 6.7 C1625 1.0 / 32X0.2 7.0

No of wires

BT Cables

Part Number

Conductor

(mm² / mm)

Diameter

(mm)

BT Cables Part Number

Conductor

(mm² / mm)

Diameter

(mm) 3 C1622 1.5 / 30X0.24 6.8 C1623 2.5 / 50X0.24 8.0 4 C1626 1.5 / 30X0.24 7.6 C1627 2.5 / 50X0.24 9.0 5 C1628 1.5 / 30X0.24 8.2 C1629 2.5 / 50X0.24 9.8

For more details, please see the respective detailed datasheet(s)

[email protected] 44

Page 45: Bt cables building infrastructure systems catalogue

Section 9 - BT Industrial-Tec™ -– Control Cables SY Series: Cable core of stranded cores surrounded by a bedding, a Steel Wire Armouring plus a PVC sheath

No of wires

BT Cables

Part Number

Conductor

(mm² / mm)

Diameter

(mm)

BT Cables Part Number

Conductor

(mm² / mm)

Diameter

(mm) 3 C1655 0.75 / 24x0.2 7.8 C1658 2.5 / 50X0.24 4 C1662 2.5 / 50X0.24

No of wires

BT Cables

Part Number

Conductor

(mm² / mm)

Diameter

(mm)

BT Cables Part Number

Conductor

(mm² / mm)

Diameter

(mm) 2 C1651 1.0 / 32X0.2 8.2 C1652 1.5 / 30X0.24 9.4 3 C1656 1.0 / 32X0.2 8.2 C1657 1.5 / 30X0.24 9.4 4 C1660 1.0 / 32X0.2 8.2 C1661 1.5 / 30X0.24 9.4 5 C1665 1.0 / 32X0.2 10.6 C1666 1.5 / 30X0.24 11.2 6 C1668 1.5 / 30X0.24 12.3 7 C1669 1.0 / 32X0.2 11.7 C1670 1.5 / 30X0.24 12.4

12 C1671 1.0 / 32X0.2 13.8 C1672 1.5 / 30X0.24 14.3 18 C1673 1.0 / 32X0.2 15.8 C1674 1.5 / 30X0.24 16.8 25 C1675 1.0 / 32X0.2 19.7

No of wires

BT Cables

Part Number

Conductor

(mm² / mm)

Diameter

(mm)

BT Cables Part Number

Conductor

(mm² / mm)

Diameter

(mm) 3 C1659 4.0 / 56x0.29 13.4 4 C1663 4.0 / 56x0.29 13.4 C1664 6.0 / 84X0.29 16.0

For more details, please see the respective detailed datasheet(s)

[email protected] 45

Page 46: Bt cables building infrastructure systems catalogue

GENERAL TECHNICAL INFORMATION American Wire Gauge (AWM) Conductors (of bare or tinned copper)

Flexible Conductors AWG 24 22 20 18 16 14 12 Number of strands 7 7 7 7 19 19 19

Gauge single strand AWG 32 30 28 26 29 27 25

Diameter single strand mm 0.2 0.25 0.32 0.40 0.28 0.36 0.45

Solid Conductors AWG 24 22 20 18 16 14 12

Diameter mm 0.51 0.64 0.81 1.02 1.29 1.63 2.05

All Conductors AWG 24 22 20 18 16 14 12

Cross section mm² 0.20 0.32 0.52 0.82 1.37 2.08 3.31

Max. DC resistance Ω/km 88 57.4 32.16 22.7 15.47 9.36 5.61

Max. Recommended current 2 or 3 core cable

Amps 2.7 2.8 3.75 5 6.25 8 12

Max. Recommended current 4 or 5 core cable

Amps 2.2 2.25 3 4 5 6.4 9.6

Max. Recommended current 6 to 19 core cable

Amps 1.9 1.95 2.6 3.5 4.35 5.6 8.4

Max. Recommended current 20 to 36 core cable

Amps 1.35 1.4 1.65 2.5 3.12 4 6

Metric Conductors (of bare copper according to IEC 60228)

Conductor mm² 0.75 1.0 1.5 2.5 4.0 Max. Recommended current 2 or 3 core cable

Amps ≤ 5 ≤ 5.70 ≤ 6.25 ≤ 8 ≤ 12

Flexible Conductors, class 2 mm² 0.055 0.22 0.50 0.75 1.0 1.5 2.5 4.0 6.0

Number of strands 7 7 7 7 7 7 7 7 7

Diameter single strand mm 0.1 0.2 0.53

Max. DC resistance Ω/km 345 86.2 36.0 24.5 18.1 12.1 7.41 4.61 3.08

Flexible Conductors, class 5 mm² 0.055 0.22 0.50 0.75 1.0 1.5 2.5 4.0 6.0

Number of strands 16 24 32 30 50 56 84

Diameter single strand mm 0.2 0.2 0.2 0.24 0.24 0.29 0.29

Max. DC resistance Ω/km 39.0 26.0 19.5 13.3 7.98 4.95 3.30

Max. Recommended current 2 or 3 core cable

Amps 2.7 2.8 3.75 5 6.25 8

12

Max. Recommended current 4 or 5 core cable

Amps 2.2 2.25 3 4 5 6.4

9.6

Max. Recommended current 6 to 19 core cable

Amps 1.9 1.95 2.6 3.5 4.35 5.6

8.4

Max. Recommended current 20 to 36 core cable

Amps 1.35 1.4 1.65 2.5 3.12 4

6

All conductors in BT Cables are in accordance with above tables unless otherwise stated in the respective section of this publication or datasheets.

[email protected] 46

Page 47: Bt cables building infrastructure systems catalogue

Pairs: all pairs consist of two twisted wires with a lay-length < 40 D. Cable Cores: all cable cores consist of stranded wires or pairs Foil screens for multi-core and multi-pair cables, screens or shields mostly consist of an aluminium foil laminated to polyester, broadly known as Alpet. These foils are helically (as a spiral) applied with sufficient overlap to guarantee 115 % or more coverage. . For the flexibility of a cable a helically applied foil is to be preferred. A longitudinally applied foil act more as a stiff tube = more difficult to bend. A drain wire or continuity wire, contacting the aluminium side of the foil, is used for the termination of the screen and also to ground electrostatic discharges. In case the screen of a coaxial cable where the screen may be a foil, this foil will be applied longitudinally and will also be bonded to the dielectric around the conductor. Braided screens consist of 16 or 24 groups of strands. One set of 8 or 12 strands is woven clockwise and the other set of 8 or 12 strands anti-clockwise. Strands can consist of tinned or bare copper or aluminium wires. Braided screens provide good screening efficiency and flexibility. Higher coverage provides better screening. Sheaths: grey PVC, purple HFFR or black for PE, all in accordance with BS EN 50290-2.

Sheath PVC PVC

Alarm cables HFFR PE

Physical properties BS EN 50290-2-22 UL444 BS EN 50290-2 BS EN 50290-2 Retardancy Flame Fire Fire Not applicable Retardancy acc. to IEC 60332-1 UL1666 IEC 60332-3C Not applicable Low Smoke Not applicable Not applicable IEC 61034 Not applicable Halogen-free (non acid, non toxic) Not applicable Not applicable IEC 60754 Not applicable RoHS compliant YES YES YES YES Installation ** INDOOR INDOOR INDOOR OUTDOOR

** on request cables with a sheath for in- & outdoor = universal use available. RoHS Limits for Hazardous Substances

Substance Max. Concentration Unless so marked, all BT Cables do not contain restricted or hazardous substances and are compliant with the European Regulations or Directives for RoHS (Restriction of Hazardous Substances), REACH (Regulation Registration, Evaluation, Authorisation and Restriction of Chemical substances), WEEE (Waste Electrical and Electronic Equipment ), ELV (End of Life Vehicles) and BFR (Brominated Flame Retardants).

Lead (Pb) 0.03% Mercury (Hg) 0.10% Cadmium (Cd) 0.01% Chromium 6 0.1% PBB 0.1% PBDE 0.1%

RS Protocol

RS-232 RS-422 RS-485

Differential no yes yes

Max. number of drivers Max. number of receivers

1 1

1 10

1 32

Modes of operation full duplex half duplex half duplex Network topology point-to-point multidrop multidrop Max. distance acc. to standard 15 m 1200 m 1200 m Max. speed at 12 m. Max. speed at 1200 m.

20 kbs 1 kbs

10 Mbs 100 kbs

35 Mbs 100 kbs

Cables used 6 to 25 conductors.

No impedance specified

mainly 24AWG conductors. Two pairs or more.

100 ohm

mainly 24AWG conductors. One pair or more.

120 ohm BT Cables main part numbers see section 1.3 section 1.2 section 1.1

[email protected] 47

Page 48: Bt cables building infrastructure systems catalogue

Nominal Attenuation in dB/100m for RG Coaxial Cables

MHz 1 5 10 50 100 300 550 750 1000 2000 3000 4500 RG-59 0.98 2.07 2.95 6.23 7.55 13.68 18.83 22.23 25.96 38.24 46.13 56.50 RG-6 0.79 1.71 2.33 4.57 6.40 11.96 15.76 18.05 21.36 31.44 39.76 50.46 RG-11 0.53 1.12 1.51 2.96 4.20 7.49 10.41 12.38 14.57 21.84 27.93 35.98

COMPARISON BETWEEN EUROPEAN AND UNITED STATES CABLE DESIGN BASICS

Europe USA Focus on SAFETY = SAVING LIVES Focus Focus on REDUCING INSURANCE CLAIMS Low Voltage Directive Directives National Electrical Code 220 Volt, 50 Hz Power supply system 120 Volt, 60 Hz More radial thickness of insulation Cable basics More copper in conductors IEC-EN and National Standards Standards UL standards Cable specs. in mm, N, etc. Units Cable specs. in inches, lbs, etc. 70 °C (is equal to 80 °C in USA) Temperature Ratings 80 °C (Is equal to 70 °C in Europe) 300 / 500 Vrms

Voltage Ratings 300 Vrms

450 / 750 Vrms 600 Vrms IEC 60332-1

Retardancy levels UL1581 – VW-1

IEC 60332-3-24 (former 3C) UL1685

RoHS compliant Environmental requirements

A number of states banned Hg and PBDE

CE Marking The CE marking certifies that a product has met EU consumer safety, health or environmental requirements. By affixing the CE marking to a product, the manufacturer – on his sole responsibility – declares that it meets EU safety, health and environmental requirements or, if stipulated in the directive(s), it had to be examined by a notified conformity assessment body.

Quality assurance

UL Approval / Listing UL does not approve products. Rather it evaluates products for compliance to specific requirements, and permits acceptable products to carry a UL certification mark, as long as they remain compliant with the standards. Products under its listing service are said to be “UL Listed,” identified by the distinctive UL mark.

CONVERSIONS

Europe USA 1 mm = 0.03937 inches 1 inch = 25,4 mm

1 m = 3.2808 feet (305 m = 1000 feet) 1 feet = 0.3048 m 1 m = 1.0936 feet 1 yard = 0.9144m

1 km = 0.6214 miles 1 mile = 1.6093 km 1 kg/km = 0.6719 lbs/1000 ft 1 lbs/1000 ft = 1.488 kg/km

1 ohm/km = 0.3048 ohm/1000 ft 1 ohm/1000 ft = 3.2808 ohm/km 1 N = 0.2248 lbs force 1 lbs force = 0.2248 N

-40 °C = -40 °F -40 °F = -40 °C -30 °C = -22 °F -22 °F = -30 °C

0 °C = 32 °F 32 °F = 0 °C 60 °C = 90 °F 90 °F = -60 °C

75 °C = 167 °F 167 °F = -75 °C 90 °C = 194 °F 194 °F = -90 °C

[email protected] 48

Page 49: Bt cables building infrastructure systems catalogue

Area Conversions

From To Multiply by To Multiply by To Multiply by Circular mils Square inches 0.0000007854 Square mils 0.7854 mm² 0.0005067 Square inches

Circular mils 1,273.240

Square mils 1,000,000.00

mm² 645.16

mm² Square inches 0.00155 Square mils 1550.01 Circular mils 1,973.53 Square feet Square meters 0.0929

Common Wire Conversions

AWG 24 22 20 19/18 18 18/17 Cir. mils 404 640 987 1029 1481 1620 1974 mm² 0.205 0.324 0.5 0.521 0.75 0.821 1.0

AWG 16 15/16 14 14/13 12 11 Cir. mils 2580 2961 4110 4935 6530 7896 8230 mm² 1.371 1.5 2.082 2.5 3.309 4.0 4.170

Force, Mass and Weight Conversion

From To Multiply by From To Multiply by Pounds Kilograms 0.4535 Kilograms Pounds 2.205

Pound per 1000 ft Kilogram per kilometre

1.488 Kilogram per kilometre

Pound per 1000 ft 0.6719

Pound-force Newton 4.4482 Newton Pound-force 0.2248

[email protected] 49

Page 50: Bt cables building infrastructure systems catalogue

GLOSSARY A = Amp: Ampere = unit of electric current. AC: Alternating current, e.g. 50 or 60 Hz AC power. ACR: Attenuation Crosstalk Ratio. The difference between attenuation and crosstalk. Important characteristic in transmission to assure that the transmitted signal is stronger at the receiving end of the cable than are any interference signals imposed on that same pair by crosstalk from other pairs. Alpet: aluminium foil covered with polyester. Alu braid: braiding of woven aluminium wires ANSI: American National Standards Institute Attenuation: The gradual loss in intensity of signals in electrical circuits. AWG: American wire gauge, is a standardized wire gauge system used since 1857 predominantly in the United States and Canada for the diameters of round, solid, nonferrous, electrically conducting wire. BT Cables: a leading manufacturer of communication cables. B.C. = BC: Bare Copper, mostly referring to a conductor or braid. Bending radius: the radius that a cable can be bent without any detrimental effects on transmission performance. Braid or Braiding: is a structure or pattern formed by intertwining of commonly 16 or 24 strands of wires. B.S: British Standards are the standards produced by BSI Group which is incorporated under a Royal Charter (and which is formally designated as the National Standards Body (NSB) for the UK). Cable core: two or more wires or pairs stranded. Good twisting is necessary otherwise the cable can hardly be bent and will lose performance after a few bends. Category cables: high performance twisted pair cables for local area networking = structured wiring or cabling. Cables range from Cat 3 to Cat 7a. The higher the number, the greater the bandwidth and the better the performance. Cat 3 Cable supports 10 Base-T Standard for bandwidths up to 10 Mbps over a maximum distance of 100 meters. They can support frequencies up to 10 Mhz. Cat 5/5e Cable supports 100 Base-T Standard for bandwidths up to 100 Mbps over a maximum distance of 100 meters. They can support frequencies up to 100 Mhz. Cat 5e cables can also support 1000 Base-T. Cat 6 Cable supports 1000 Base-T Standard for bandwidths up to 1000 Mbps over a maximum distance of 100 meters. Cat 6 standard can support frequencies up to 250 Mhz. They also support 10GE (10Gig Ethernet) bandwidth over limited distances. Cat 6A Cable supports 10G Base-T standard for bandwidths up to 10 Gbps over a maximum distance of 100 meters. Cat 6A standard can support frequencies up to 500 Mhz. Cat 7 Cable supports 10G Base-T standard for bandwidths up to 10 Gbps over a maximum distance of 100 meters. Cat 7 standard can support frequencies up to 600 Mhz. It offers better performance and improved cross talk suppression over the Cat 6A cables. Cat 7A Cable supports 10G Base-T standard for bandwidths up to 10 Gbps over a maximum distance of 100 meters. In addition to this, they can also support 40 Gbps bandwidth for around 50 meters and 100 Gbps bandwidth for around 15 meters. They support frequencies up to 1000 Mhz.

Cat 8 Cable supports frequencies up to 1200 Mhz. Under development. No applications yet. CATV: Community Antenna Television, also often used to mean Cable TV. It is a system of providing television to consumers through or optical fibre cables. High-speed Internet, telephony, and similar non-television services may also be provided. CCTV: Closed-circuit television is the use of video cameras to transmit a signal to a specific place, on a limited set of monitors. Circuit integrity refers to the operability of electrical circuits during a fire. It is a form of fire-resistance rating. Coaxial Cable or coax: an electrical cable with a centre conductor surrounded by a tubular insulating layer = the dielectric, surrounded by a tubular conducting screen = the outer conductor, surrounded by an outer sheath. The term coaxial comes from the centre conductor and the outer screen sharing the same geometric axis. Conductor: most familiar conductors are metallic. Copper or tinned copper is the most common material used for electrical wiring. Silver is also in use as a conductor and out performs copper, but is more expensive. Continuity Wire: see Drain Wire. Crosstalk (XT): any phenomenon by which a signal transmitted on one circuit of a transmission system creates an undesired effect in another circuit. Crosstalk is usually caused by undesired capacitive, inductive, or conductive coupling from one circuit (mostly a pair) to another (pair). Current: electric current is a flow of electric charge through a medium. This flowing electric charge is typically carried by moving electrons in a conductor such as wire. The unit of current is Ampere. DC Resistance: the resistance of an object is defined as the ratio of voltage across it to the direct current through it. The unit of resistance is Ohm. Dielectric: the insulation between centre and outer conductor (screen) of coaxial cables. Mostly solid or foam (= cellular) polyethylene (PE). Distortion: the alteration of the original shape (or other characteristic) of an object, image, sound, waveform or other form of information or representation. Distortion is usually unwanted, and often many methods are employed to minimize it in practice. Drain wire: a conductor in contact with the foil (of a screen) in order to terminate the screen. Also referred to as a Continuity Wire. The preferred drain wire is tinned copper wire or wires. Decibel (dB): is a logarithmic unit that indicates the ratio of a physical quantity (usually power or intensity) relative to a specified or implied reference level. A ratio in decibels is ten times the logarithm to base 10 of the ratio of two power quantities. ELFEXT: the Equal-Level Far-End Crosstalk (ELFEXT) test measures Far-End Crosstalk (FEXT). FEXT is very similar to NEXT, but happens at the receiver side of the connection. Due to impedance on the line, crosstalk diminishes the signal as it gets further away from the transmitter. Because of this, FEXT is usually less detrimental to a signal than NEXT, but still important nonetheless. EIA: the Electronic Industri8es Association ceased operations on 28 February 2011. The former sectors of EIA are the Electronic Components Association (ECA), JEDEC, Government Electronics and Information Technology Association (GEIA), now part of TechAmerica, Telecommunications Industry Association (TIA), and Consumer Electronics Association (CEA).

[email protected] 50

Page 51: Bt cables building infrastructure systems catalogue

EN: European Norms maintained by CEN (European Committee for Standardization), CENELEC (European Committee for Electrotechnical Standardization) and ETSI (European Telecommunications Standards Institute). Farad: the unit of capacitance. FPE: Foam Polyethylene (PE) = closed cells with gas in PE in order to reduce the dielectric constant. Often used as dielectric in coaxial cables. The gas may be generated by chemical decomposition during extrusion of the insulation (dielectric) referred to as chemical foaming or blowing, or by injection into the polymer melt within the extruder (physical foaming or blowing). FAS Cables: cables for fire detection and alarm systems Far end crosstalk (FEXT): Interference between two pairs of a cable measured at the other end of the cable from the transmitter. FR: can mean Flame Retardant or Fire Retardant or Fire Resistant. Flame Retardant: are cables passing the vertical wire test of IEC 60332-1 or UL 1581 VW-1). Fire Retardant: are cables passing the bundle test of IEC 60332-2-24 or UL 1685 Vertical Tray. Fire Resistant are cables with a circuit integrity of a specified time. Frequency: is the number of occurrences of a repeating event per unit time. The unit of frequency is Hertz (Hz). G.P. Bus: General Purpose Bus Application Headroom: in case of testing category cables this is the average of the difference between worst case margin and the specified value. Henry (H): unit of inductance. Hertz (Hz): unit of frequency. 1 Hz means that an event repeats once per second. HFFR = Halogen-Free, Flame or Fire Retardant Impedance: the ratio of voltage applied to the current is called the input impedance. The input impedance of the infinite line is called the characteristic impedance. Insertion Loss: also referred to as attenuation, refers to the loss of signal strength at the far end of a line compared to the signal that was introduced into the line. This loss is due to the electrical resistance of the copper cable, the loss of energy through the cable insulation and the impedance caused by the connectors. Insertion loss is usually expressed in decibels dB with a minus sign. Insertion loss increases with distance and frequency. For every 6dB of loss, the original signal will be half the original amplitude. Inductance: is the property of an electrical circuit causing voltage to be generated proportional to the rate of change in current in a circuit. This property also is called self inductance to discriminate it from mutual inductance, describing the voltage induced in one electrical circuit by the rate of change of the electric current in another circuit. Insulation: insulations are coatings applied to wires to isolate the conductors. Insulation materials are applied to provide good strippable and interchangeable colour. The physical properties are in accordance with BS EN 50290-2. Individually screened pair: a pair with a helically applied (= as a spiral) Aluminium/Polyester (Alpet) foil. A drain wire is normally applied under the screen to provide continuity and ease of tern=miantion.

Jacket = sheath. This is the outer protective polymer surrounding the cable core. Lay-length: The length measured along the axis of a wire or cable required for a single strand (in stranded wire) or conductor (in cable) to make one complete turn about the axis of the conductor or cable. In a twisted pair cable, the lay length is the distance it takes for the two wires to completely twist around each other. Lay length is also known as pitch length. Local Area Network (LAN): any communication network for connecting computers within a building or small group of buildings. m = metre: S. I. unit of measure of length. MHz = MegaHertz: . 1 MHz = one million Hertz. Near End Crosstalk (NEXT): Interference between two pairs in a cable measured at the same end of the cable as the transmitter. Operating temperature (range): the temperature range at which the cable can operate. Polyolefin: is a polymer produced by polymerisation of a simple olefin (also called an alkene) as a monomer, for example Polyethylene or Polypropylene. PA = Polyamide PE = Polyethylene. PP = Polypropylene. PVC = Polyvinyl Chloride. Power Sum ELFEXT (PSELFEXT): is the sum of FEXT values from 3 wire pairs as they affect the other wire pair. Pair: two twisted insulated wires, normally colour coded. Quad: a four conductor cable core or unit, symmetrical stranded or twisted together. Rated Temperature: the maximum continuous temperature that the cable can withstand during its lifetime. It is generally limited by the thermal aging characteristics of the plastics used to insulate and/or sheath the wire. Rated Voltage: the maximum voltage at which a cable can operate for extended periods without undue degradation or safety hazard. Resistance: the electrical resistance of a conductor measures its opposition to the passage of an electric current; the inverse quantity is electrical conductance, measuring how easily electricity flows along a certain path. The unit of electrical resistance is the ohm (Ω), while electrical conductance is measured in Siemens (S). Return Loss (RL): the Return or Reflection Loss of a line is the ratio of the power reflected back from the line to the power transmitted into the line. RL is expressed in decibels (dB). The RL of coaxial cables is the loss of signal power resulting from the reflection caused at a discontinuity in the cable. This discontinuity can be fluctuations in dimensions and/or dielectric. Return Loss is also one of many parameters regulated by the requirements established for Category 5e and onwards cables. It is a measure of the reflected energy from a transmitted signal. The larger the value, the less energy that is reflected. Poor Return Loss figures of a circuit are quite often caused by poor termination (connectors). Screen: a cable screen acts as a Faraday cage to reduce electrical noise from affecting the signals, and to reduce electromagnetic radiation that may interfere with other parts in a cable or other cables. The screen minimizes capacitive coupled noise from other electrical sources. For more info regarding screens: see also the Technical Information section.

[email protected] 51

Page 52: Bt cables building infrastructure systems catalogue

Sheath: the outer covering of a cable, standard in accordance with BS EN 50290-2 and grey for PVC, purple for HFFR and black for PE. Shield = screen. SMATV = Satellite Master Antenna Television, and refers to a system that uses multiple satellite and broadcast signals to create a single integrated cable signal for distribution to a cabling network Solid BC: one solid conductor of bare copper. Solid TC: one solid conductor of tinned copper T.C. = TC = Tinned Copper Conductor TIA: the Telecommunications Industry Association is accredited by the American National Standards Institute (ANSI) to develop voluntary industry standards for a wide variety of telecommunications products. Twisted pair: a type of wiring in which two conductors are twisted together for the purposes of cancelling out electromagnetic interference (EMI) from external sources; for instance, electromagnetic radiation from unshielded twisted pair (UTP) cables, and crosstalk between neighbouring pairs. Volt = Voltage = unit of electric, expressed with the symbol V. Wire = Conductor with Insulation. Sometimes also indicated as Core.

[email protected] 52

Page 53: Bt cables building infrastructure systems catalogue

www.btcables.com

UNITED KINGDOM Delaunays Road, Blackley Manchester, M9 8FP Tel: +44 161 740 9151 Fax: +44 161 795 8393 Email: [email protected]

EUROPE Madrid 28 28027 Spain Tel: +34 611370897 Fax: +44 161 795 8393 Email: [email protected]

MIDDLE EAST Rawdah - Riyadh Kingdom of Saudi Arabia Tel: +966 500333786 Fax: +44 161 795 8393 Email: [email protected]

ASIA Shenzhen – Guangdong Province People’s Republic of China Tel: +86 13923775251 Fax: +44 161 795 8393 Email: [email protected]