busbar diffrential protection reb611

Upload: fiatraj1

Post on 03-Jun-2018

235 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/12/2019 Busbar Diffrential Protection REB611

    1/72

  • 8/12/2019 Busbar Diffrential Protection REB611

    2/72

  • 8/12/2019 Busbar Diffrential Protection REB611

    3/72

    Document ID: 1MRS757455

    Issued: 2011-11-18

    Revision: A

    Product version: 1.0

    Copyright 2011 ABB. All rights reserved

  • 8/12/2019 Busbar Diffrential Protection REB611

    4/72

    CopyrightThis document and parts thereof must not be reproduced or copied without written

    permission from ABB, and the contents thereof must not be imparted to a thirdparty, nor used for any unauthorized purpose.

    The software or hardware described in this document is furnished under a license

    and may be used, copied, or disclosed only in accordance with the terms of such

    license.

    TrademarksABB and Relion are registered trademarks of the ABB Group. All other brand or

    product names mentioned in this document may be trademarks or registered

    trademarks of their respective holders.

    WarrantyPlease inquire about the terms of warranty from your nearest ABB representative.

    http://www.abb.com/substationautomation

    http://http//WWW.ABB.COM/SUBSTATIONAUTOMATION
  • 8/12/2019 Busbar Diffrential Protection REB611

    5/72

    DisclaimerThe data, examples and diagrams in this manual are included solely for the concept

    or product description and are not to be deemed as a statement of guaranteedproperties. All persons responsible for applying the equipment addressed in this

    manual must satisfy themselves that each intended application is suitable and

    acceptable, including that any applicable safety or other operational requirements

    are complied with. In particular, any risks in applications where a system failure and/

    or product failure would create a risk for harm to property or persons (including but

    not limited to personal injuries or death) shall be the sole responsibility of the

    person or entity applying the equipment, and those so responsible are hereby

    requested to ensure that all measures are taken to exclude or mitigate such risks.

    This document has been carefully checked by ABB but deviations cannot be

    completely ruled out. In case any errors are detected, the reader is kindly requested

    to notify the manufacturer. Other than under explicit contractual commitments, in

    no event shall ABB be responsible or liable for any loss or damage resulting from

    the use of this manual or the application of the equipment.

  • 8/12/2019 Busbar Diffrential Protection REB611

    6/72

    ConformityThis product complies with the directive of the Council of the European

    Communities on the approximation of the laws of the Member States relating toelectromagnetic compatibility (EMC Directive 2004/108/EC) and concerning

    electrical equipment for use within specified voltage limits (Low-voltage directive

    2006/95/EC). This conformity is the result of tests conducted by ABB in

    accordance with the product standards EN 50263 and EN 60255-26 for the EMC

    directive, and with the product standards EN 60255-1 and EN 60255-27 for the low

    voltage directive. The product is designed in accordance with the international

    standards of the IEC 60255 series.

  • 8/12/2019 Busbar Diffrential Protection REB611

    7/72

    Table of contentsSection 1 Introduction.......................................................................3

    This manual........................................................................................3

    Intended audience..............................................................................3

    Product documentation.......................................................................4

    Product documentation set............................................................4

    Document revision history.............................................................5

    Related documentation..................................................................6

    Symbols andconventions...................................................................6

    Symbols.........................................................................................6

    Document conventions..................................................................6

    Functions, codes and symbols......................................................7

    Section 2 REB611 overview.............................................................9Overview.............................................................................................9

    Product version history..................................................................9

    PCM600 and IED connectivity package version............................9

    Operation functionality......................................................................10

    Optional functions........................................................................10

    Physical hardware............................................................................10

    Local HMI.........................................................................................11Display.........................................................................................12

    LEDs............................................................................................12

    Keypad........................................................................................13

    Web HMI...........................................................................................13

    Authorization.....................................................................................14

    Communication.................................................................................15

    Section 3 REB611 standard configuration ....................................17Standard configuration.....................................................................17

    Switch groups...................................................................................18Input switch group ISWGAPC.....................................................18

    Output switch group OSWGAPC.................................................19

    Selector switch group SELGAPC................................................19

    Connection diagrams........................................................................21

    Presentationof standard configuration.............................................23

    Standard configuration A..................................................................24

    Applications.................................................................................24

    Functions.....................................................................................25

    Default I/O connections..........................................................26

    Predefined disturbance recorder connections........................26

    Table of contents

    REB611 1Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    8/72

    Functional diagrams....................................................................27

    Functional diagrams for protection.........................................27

    Functional diagrams for disturbance recorder........................30

    Functional diagrams for control and interlocking....................32Switch groups..............................................................................34

    Binary inputs...........................................................................34

    Internal signal.........................................................................35

    Binary outputs and LEDs........................................................36

    GOOSE..................................................................................47

    Section 4 Requirements for measurement transformers................51Current transformers........................................................................51

    Current transformer requirements for differential

    protection ....................................................................................51

    Section 5 IED physical connections...............................................57Inputs................................................................................................57

    Energizing inputs.........................................................................57

    Differential currents................................................................57

    Residual current.....................................................................57

    Auxiliary supply voltage input......................................................57

    Binary inputs................................................................................58

    Outputs.............................................................................................58

    Outputs for tripping and controlling..............................................58

    Outputs for signalling...................................................................59

    IRF...............................................................................................59

    Section 6 Glossary.........................................................................61

    Table of contents

    2 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    9/72

    Section 1 Introduction

    1.1 This manualThe application manual contains application descriptions and setting guidelines

    sorted per function. The manual can be used to find out when and for what purpose

    a typical protection function can be used. The manual can also be used when

    calculating settings.

    1.2 Intended audienceThis manual addresses the protection and control engineer responsible for

    planning, pre-engineering and engineering.

    The protection and control engineer must be experienced in electrical power

    engineering and have knowledge of related technology, such as communication

    and protocols.

    1MRS757455 A Section 1Introduction

    REB611 3Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    10/72

    1.3 Product documentation1.3.1 Product documentation set

    Planning&purchase

    Engineering

    Installing

    Commissioning

    Operation

    Maintenance

    Decommissioning

    deinstalling&disposal

    Application manual

    Operation manual

    Installation manual

    Service manual

    Engineering manual

    Commissioning manual

    Communication protocolmanual

    Technical manual

    Planning&purchase

    Engineering

    Installing

    Commissioning

    Operation

    Maintenance

    Decommissioning

    deinstalling&disposal

    Planning&purchase

    Engineering

    Installing

    Commissioning

    Operation

    Maintenance

    Decommissioning

    deinstalling&disposal

    Application manualApplication manual

    Operation manualOperation manual

    Installation manualInstallation manual

    Service manualService manual

    Engineering manualEngineering manual

    Commissioning manualCommissioning manual

    Communication protocolmanualCommunication protocolmanual

    Technical manualTechnical manual

    en07000220.vsd

    IEC07000220 V1 EN

    Figure 1: The intended use of manuals in different lifecycles

    The engineering manual contains instructions on how to engineer the IEDs using

    the different tools in PCM600. The manual provides instructions on how to set up a

    PCM600 project and insert IEDs to the project structure. The manual also

    recommends a sequence for engineering of protection and control functions, LHMI

    functions as well as communication engineering for IEC 61850 and othersupported protocols.

    The installation manual contains instructions on how to install the IED. The

    manual provides procedures for mechanical and electrical installation. The chapters

    are organized in chronological order in which the IED should be installed.

    The commissioning manual contains instructions on how to commission the IED.

    The manual can also be used by system engineers and maintenance personnel for

    assistance during the testing phase. The manual provides procedures for checking

    of external circuitry and energizing the IED, parameter setting and configuration as

    Section 1 1MRS757455 AIntroduction

    4 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    11/72

    well as verifying settings by secondary injection. The manual describes the process

    of testing an IED in a substation which is not in service. The chapters are organized

    in chronological order in which the IED should be commissioned.

    The operation manual contains instructions on how to operate the IED once it hasbeen commissioned. The manual provides instructions for monitoring, controlling

    and setting the IED. The manual also describes how to identify disturbances and

    how to view calculated and measured power grid data to determine the cause of a

    fault.

    The service manual contains instructions on how to service and maintain the IED.

    The manual also provides procedures for de-energizing, de-commissioning and

    disposal of the IED.

    The application manual contains application descriptions and setting guidelines

    sorted per function. The manual can be used to find out when and for what purpose

    a typical protection function can be used. The manual can also be used when

    calculating settings.

    The technical manual contains application and functionality descriptions and lists

    function blocks, logic diagrams, input and output signals, setting parameters and

    technical data sorted per function. The manual can be used as a technical reference

    during the engineering phase, installation and commissioning phase, and during

    normal service.

    The communication protocol manual describes a communication protocol

    supported by the IED. The manual concentrates on vendor-specific implementations.

    The point list manual describes the outlook and properties of the data points

    specific to the IED. The manual should be used in conjunction with the

    corresponding communication protocol manual.

    Some of the manuals are not available yet.

    1.3.2 Document revision historyDocument revision/date Product series version HistoryA/2011-11-18 1.0 First release

    Download the latest documents from the ABB Web site

    http://www.abb.com/substationautomation.

    1MRS757455 A Section 1Introduction

    REB611 5Application Manual

    http://http//WWW.ABB.COM/SUBSTATIONAUTOMATION
  • 8/12/2019 Busbar Diffrential Protection REB611

    12/72

    1.3.3 Related documentationName of the document Document IDModbus Communication Protocol Manual 1MRS757461

    IEC 61850 Engineering Guide 1MRS757465

    Installation Manual 1MRS757452

    Operation Manual 1MRS757453

    Technical Manual 1MRS757454

    1.4 Symbols and conventions

    1.4.1 SymbolsThe electrical warning icon indicates the presence of a hazard

    which could result in electrical shock.

    The warning icon indicates the presence of a hazard which could

    result in personal injury.

    The caution icon indicates important information or warning relatedto the concept discussed in the text. It might indicate the presence

    of a hazard which could result in corruption of software or damage

    to equipment or property.

    The information icon alerts the reader of important facts and

    conditions.

    The tip icon indicates advice on, for example, how to design your

    project or how to use a certain function.

    Although warning hazards are related to personal injury, it is necessary to

    understand that under certain operational conditions, operation of damaged

    equipment may result in degraded process performance leading to personal injury

    or death. Therefore, comply fully with all warning and caution notices.

    1.4.2 Document conventionsA particular convention may not be used in this manual.

    Section 1 1MRS757455 AIntroduction

    6 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    13/72

    Abbreviations and acronyms in this manual are spelled out in the glossary. The

    glossary also contains definitions of important terms.

    Push-button navigation in the LHMI menu structure is presented by using the

    push-button icons.

    To navigate between the options, use and .

    HMI menu paths are presented in bold.

    Select Main menu/Settings.

    LHMI messages are shown in Courier font.

    To save the changes in non-volatile memory, select Yesand press .

    Parameter names are shown in italics.

    The function can be enabled and disabled with the Operationsetting.

    Parameter values are indicated with quotation marks.

    The corresponding parameter values are "On" and "Off".

    IED input/output messages and monitored data names are shown in Courier font.

    When the function starts, the STARToutput is set to TRUE.

    1.4.3 Functions codes and symbolsTable 1: REB611 functions codes and symbolsFunction IEC 61850 IEC 60617 IEC-ANSIProtectionHigh-impedance differential

    protection, instance 1HIPDIF1 dHi>(1) 87(1)

    High-impedance differential

    protection, instance 2HIPDIF2 dHi>(2) 87(2)

    High-impedance differential

    protection, instance 3HIPDIF3 dHi>(3) 87(3)

    Non-directional earth-fault protection,

    low stage, instance 1EFLPTOC1 Io> (1) 51N-1 (1)

    Non-directional earth-fault protection,

    high stage, instance 1EFHPTOC1 Io>> (1) 51N-2 (1)

    Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF

    Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)

    Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)

    Switch groupsInput switch group 1) ISWGAPC ISWGAPC ISWGAPC

    Output switch group 2) OSWGAPC OSWGAPC OSWGAPC

    Selector switch group 3) SELGAPC SELGAPC SELGAPC

    Configurable timersMinimum pulse timer (2 pcs) 4) TPGAPC TP TP

    ControlCircuit-breaker control CBXCBR1 I O CB I O CB

    SupervisionTrip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)

    Table continues on next page

    1MRS757455 A Section 1Introduction

    REB611 7Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    14/72

    Function IEC 61850 IEC 60617 IEC-ANSITrip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)

    CT supervision for high-impedance

    protection scheme, instance 1HZCCRDIF1 MCS 1I(1) MCS 1I(1)

    CT supervision for high-impedance

    protection scheme, instance 2HZCCRDIF2 MCS 1I(2) MCS 1I(2)

    CT supervision for high-impedance

    protection scheme, instance 3HZCCRDIF3 MCS 1I(3) MCS 1I(3)

    MeasurementDisturbance recorder RDRE1 - -

    Three-phase current measurement,

    instance 1 5)CMMXU1 3I 3I

    Residual current measurement,

    instance 1RESCMMXU1 Io In

    1) 10 instances

    2) 20 instances3) 6 instances

    4) 10 instances

    5) In REB611, CMMXU is used for measuring differential phase currents.

    Section 1 1MRS757455 AIntroduction

    8 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    15/72

    Section 2 REB611 overview

    2.1 OverviewREB611 is a dedicated busbar protection IED (intelligent electronic device)

    designed for phase-segregated short-circuit protection, control, and supervision of

    single busbars. REB611 is intended for use in high-impedance-based applications

    within utility substations and industrial power systems. In addition, the IED can be

    utilized in restricted earth-fault and residual earth-fault applications for the

    protection of generators, motors, transformers and reactors.

    REB611 is a member of ABBs Relionproduct family and part of the 611

    protection and control product series. The 611 series IEDs are characterized by

    their compactness and withdrawable-unit design.

    The 611 series is designed to offer simplified but powerful functionality intended

    for most applications. Once the application-specific parameters have been entered,

    the installed IED is ready to be put into service. The further addition of

    communication functionality and interoperability between substation automation

    devices offered by the IEC 61850 standard adds flexibility and value to end users

    as well as electrical system manufacturers.

    2.1.1 Product version historyProduct version Product history1.0 Product released

    2.1.2 PCM600 and IED connectivity package version Protection and Control IED Manager PCM600 Ver. 2.4 or later

    REB611 Connectivity Package Ver. 1.0 or later

    Parameter Setting

    Firmware Update

    Disturbance Handling

    Signal Monitoring

    Lifecycle Traceability

    Signal Matrix

    Communication Management

    IED Configuration Migration

    Configuration Wizard

    1MRS757455 A Section 2REB611 overview

    REB611 9Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    16/72

    Label Printing

    IED User Management

    Differential Characteristics Tool

    Download connectivity packages from the ABB web site http://

    www.abb.com/substationautomation

    2.2 Operation functionality2.2.1 Optional functions

    Modbus TCP/IP or RTU/ASCII

    2.3 Physical hardwareThe IED consists of two main parts: plug-in unit and case. The content depends on

    the ordered functionality.

    Table 2: Plug-in unit and caseMain unit Slot ID Content optionsPlug-in

    unit

    - HMI Small (4 lines, 16 characters)

    X100 Auxiliary power/

    BO module

    48-250 V DC/100-240 V AC; or 24-60 V DC

    2 normally-open PO contacts

    1 change-over SO contacts

    1 normally-open SO contact

    2 double-pole PO contacts with TCS

    1 dedicated internal fault output contact

    X120 AI/BI module Configuration A:

    3 differential phase current inputs (1/5 A)

    1 residual current input (1/5 A or 0.2/1 A)1)

    4 binary inputs

    Case X000 Optional

    communicationmodule

    See technical manual for details about different type of

    communication modules.

    1) The 0.2/1 A input is normally used in applications requiring sensitive earth-fault protection and

    featuring core-balance current transformers.

    Rated values of the current and voltage inputs are basic setting parameters of the

    IED. The binary input thresholds are selectable within the range 18176 V DC by

    adjusting the binary input setting parameters.

    The connection diagrams of different hardware modules are presented in this manual.

    Section 2 1MRS757455 AREB611 overview

    10 REB611Application Manual

    http://http//WWW.ABB.COM/SUBSTATIONAUTOMATIONhttp://http//WWW.ABB.COM/SUBSTATIONAUTOMATION
  • 8/12/2019 Busbar Diffrential Protection REB611

    17/72

    See the installation manual for more information about the case and

    the plug-in unit.

    T ab le 3: N um be r of p hysica l co nne ction s in sta nda rd co nfig ura tio nConf. Analog channels Binary channels CT VT BI BOA 4 - 4 6

    2.4 Local HMI

    REF611

    Overcurrent

    Earth-fault

    Phase unbalance

    Thermal overload

    AR sequence in progress

    Disturb.rec.trigged

    Trip circuit failure

    Breaker failure

    GUID-E15422BF-B3E6-4D02-8D43-D912D5EF0360 V1 EN

    Figure 2: Example of 611 series LHMI

    The LHMI of the IED contains several elements.

    1MRS757455 A Section 2REB611 overview

    REB611 11Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    18/72

    Display

    Buttons

    LED indicators

    Communication port

    The LHMI is used for setting, monitoring and controlling.

    2.4.1 DisplayThe LHMI includes a graphical display that supports two character sizes. The

    character size depends on the selected language. The amount of characters and

    rows fitting the view depends on the character size.

    Table 4: Characters and rows on the viewCharacter size Rows in view Characters on rowSmall, mono-spaced (6x12 pixels) 5 rows 20

    Large, variable width (13x14 pixels) 4 rows min 8

    The display view is divided into four basic areas.

    1

    3 4

    2

    GUID-24ADB995-439A-4563-AACE-1FAA193A8EF9 V1 EN

    Figure 3: Display layout

    1 Header

    2 Icon

    3 Content

    4 Scroll bar (displayed when needed)

    2.4.2 LEDsThe LHMI includes three protection indicators above the display: Ready, Start and

    Trip.

    Section 2 1MRS757455 AREB611 overview

    12 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    19/72

    There are also 8 programmable LEDs on front of the LHMI. The LEDs can be

    configured with the LHMI, WHMI or PCM600.

    2.4.3 KeypadThe LHMI keypad contains push-buttons which are used to navigate in different

    views or menus. With the push-buttons you can give open or close commands to

    one object in the primary circuit, for example, a circuit breaker, a contactor or a

    disconnector. The push-buttons are also used to acknowledge alarms, reset

    indications, provide help and switch between local and remote control mode.

    GUID-B681763E-EC56-4515-AC57-1FD5349715F7 V1 EN

    Figure 4: LHMI keypad with object control, navigation and command push-

    buttons and RJ-45 communication port

    2.5 Web HMIThe WHMI enables the user to access the IED via a web browser. The supported

    web browser version is Internet Explorer 7.0 or 8.0.

    WHMI is disabled by default.

    WHMI offers several functions.

    Programmable LEDs and event lists

    System supervision

    Parameter settings

    Measurement display

    Disturbance records

    Phasor diagram

    Signal configuration

    The menu tree structure on the WHMI is almost identical to the one on the LHMI.

    1MRS757455 A Section 2REB611 overview

    REB611 13Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    20/72

    GUID-CD531B61-6866-44E9-B0C1-925B48140F3F V1 EN

    Figure 5: Example view of the WHMI

    The WHMI can be accessed locally and remotely.

    Locally by connecting your laptop to the IED via the front communication port.

    Remotely over LAN/WAN.

    2.6 AuthorizationThe user categories have been predefined for the LHMI and the WHMI, each with

    different rights and default passwords.

    The default passwords can be changed with Administrator user rights.

    User authorization is disabled by default but WHMI always usesauthorization.

    Section 2 1MRS757455 AREB611 overview

    14 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    21/72

    Table 5: Predefined user categoriesUsername User rightsVIEWER Read only access

    OPERATOR Selecting remote or local state with (only locally) Changing setting groups

    Controlling

    Clearing indications

    ENGINEER Changing settings

    Clearing event list

    Clearing disturbance records

    Changing system settings such as IP address, serial baud rate

    or disturbance recorder settings

    Setting the IED to test mode

    Selecting language

    ADMINISTRATOR All listed above

    Changing password Factory default activation

    For user authorization for PCM600, see PCM600 documentation.

    2.7 CommunicationFor application specific situations where communication between IEDs and remote

    systems are needed, the 611 series IEDs also support IEC 61850 and Modbus

    communication protocols. Operational information and controls are available

    through these protocols. Some communication functionality, for example,

    horizontal communication between the IEDs, is only enabled by the IEC 61850

    communication protocol.

    The IEC 61850 communication implementation supports monitoring and control

    functionality. Additionally, parameter settings and disturbance and fault records

    can be accessed using the IEC 61850 protocol. Disturbance records are available to

    any Ethernet-based application in the standard COMTRADE file format. The IEDcan send and receive binary signals from other IEDs (so called horizontal

    communication) using the IEC 61850-8-1 GOOSE profile, where the highest

    performance class with a total transmission time of 3 ms is supported. The IED

    meets the GOOSE performance requirements for tripping applications in

    distribution substations, as defined by the IEC 61850 standard. The IED can

    simultaneously report events to five different clients on the station bus.

    The IED can support five simultaneous clients. If PCM600 reserves one client

    connection, only four client connections are left, for example, for IEC 61850 and

    Modbus.

    1MRS757455 A Section 2REB611 overview

    REB611 15Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    22/72

    All communication connectors, except for the front port connector, are placed on

    integrated optional communication modules. The IED can be connected to Ethernet-

    based communication systems via the RJ-45 connector (100Base-TX) or the fibre-

    optic LC connector (100Base-FX). An optional serial interface is available for

    RS-485 communication.

    Managed Ethernet switch

    with RSTP support

    Managed Ethernet switch

    with RSTP support

    Network

    Network

    REF611

    Overcurrent

    Earth-fault

    Phaseunbalance

    Thermaloverload

    ARsequenceinprogress

    Disturb.rec. trigged

    Tripcircuit failure

    Breakerfailure

    REF611

    Overcurrent

    Earth-fault

    Phaseunbalance

    Thermaloverload

    ARsequenceinprogress

    Disturb.rec. trigged

    Tripcircuitfailure

    Breakerfailure

    REF611

    Overcurrent

    Earth-fault

    Phaseunbalance

    Thermaloverload

    ARsequenceinprogress

    Disturb.rec. trigged

    Tripcircuit failure

    Breakerfailure

    REM611

    Short circuit

    Combinedprotec tion

    Thermaloverload

    Motorrestartinhibit

    Emergencys tart enabled

    Disturb.rec.trigged

    Supervisionalarm

    Breakerfailure

    REB611

    High-impedance1operate

    High-impedance2operate

    High-impedance3operate

    High-impedancestart

    Segregatedsupervision

    Disturb.rec.trigged

    Tripcircuit failure

    Breakerfailure

    REF611 REF611 REF611 REM611 REB611

    Client BClient A

    GUID-A19C6CFB-EEFD-4FB2-9671-E4C4137550A1 V1 EN

    Figure 6: Self-healing Ethernet ring solution

    The Ethernet ring solution supports the connection of up to thirty

    611 series IEDs. If more than 30 IEDs are to be connected, it is

    recommended that the network is split into several rings with no

    more than 30 IEDs per ring.

    Section 2 1MRS757455 AREB611 overview

    16 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    23/72

    Section 3 REB611 standard configuration

    3.1 Standard configurationREB611 is available in one standard configuration.

    To increase the user-friendliness of the IEDs standard configuration and to

    emphasize the IED's simplicity of usage, only the application-specific parameters

    need setting within the IED's intended area of application.

    The standard signal configuration can be altered by LHMI (human-machineinterface), WHMI (Web browser-based user interface) or the optional application

    functionality of the Protection and Control IED Manager PCM600.

    Table 6: Standard configurationDescription Std. conf.High-impedance differential A

    Table 7: Supported functionsFunctionality Conf. AProtection1)High-impedance differential protection, instance 1

    High-impedance differential protection, instance 2

    High-impedance differential protection, instance 3

    Non-directional earth-fault protection, low stage, instance 1 2)

    Non-directional earth-fault protection, high stage, instance 1 2)

    Circuit breaker failure protection

    Master trip, instance 1

    Master trip, instance 2

    Switch groupsInput switch group

    Output switch group

    Selector switch group

    Configurable timerMinimum pulse timer (2 pcs)

    ControlCircuit-breaker control

    SupervisionTable continues on next page

    1MRS757455 A Section 3REB611 standard configuration

    REB611 17Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    24/72

    Functionality Conf. ATrip circuit supervision, instance 1

    Trip circuit supervision, instance 2

    CT supervision for high-impedance protection scheme, instance 1

    CT supervision for high-impedance protection scheme, instance 2

    CT supervision for high-impedance protection scheme, instance 3

    MeasurementDisturbance recorder

    Three-phase current measurement, instance 1 3)

    Residual current measurement, instance 1

    = Included

    1) The instances of a protection function represent the number of identical function blocks available in

    a standard configuration.

    2) Io selectable by parameter, Io measured as default.

    3) In REB611, CMMXU is used for measuring differential phase currents.

    3.2 Switch groupsThe default application configurations cover the most common application cases,

    however, changes can be made according to specific needs through LHMI, WHMI

    and PCM600.

    Programming is easily implemented with three switch group functions including

    input switch group (ISWGAPC), output switch group (OSWGAPC) and selectorswitch group (SELGAPC). Each switch group has several instances.

    Connections of binary inputs to functions, GOOSE signals to functions, functions

    to functions, functions to binary outputs and functions to LEDs have been

    preconnected through corresponding switch groups.

    Change the parameter values of the switch groups to modify the real connection

    logic and the application configuration.

    3.2.1 Input switch group ISWGAPCThe input switch group ISWGAPC has one input and a number of outputs. Every

    input and output has a read-only description. ISWGAPC is used for connecting the

    input signal to one or several outputs of the switch group. Each output can be set to

    be connected or not connected with the input separately via the OUT_x

    connection setting.

    Section 3 1MRS757455 AREB611 standard configuration

    18 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    25/72

    GUID-2D549B56-6CF7-4DCB-ACDE-E9EF601868A8 V1 EN

    Figure 7: Input switch group ISWGAPC

    3.2.2 Output switch group OSWGAPCThe output switch group OSWGAPC has a number of inputs and one output. Every

    input and output has a read-only description. OSWGAPC is used for connecting

    one or several inputs to the output of the switch group via OR logic. Each input can

    be set to be connected or not connected with the OR logic via the IN_x

    connection settings. The output of OR logic is routed to switch group output.

    GUID-1EFA82D5-F9E7-4322-87C2-CDADD29823BD V1 EN

    Figure 8: Output switch group OSWGAPC

    3.2.3 Selector switch group SELGAPCThe selector switch group SELGAPC has a number of inputs and outputs. Every

    input and output has a read-only description. Each output can be set to beconnected with one the of inputs via the OUT_x connection setting. An output

    can also be set to be not connected with any of the inputs. In SELGAPC, one

    output signal can only be connected to one input signal but the same input signal

    can be routed to several output signals.

    1MRS757455 A Section 3REB611 standard configuration

    REB611 19Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    26/72

    GUID-E3AEC7AB-2978-402D-8A80-C5DE9FED67DF V1 EN

    Figure 9: Selector switch group SELGAPC

    Section 3 1MRS757455 AREB611 standard configuration

    20 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    27/72

    3.3 Connection diagrams

    L1

    L2L3

    REB611

    16

    17

    1918

    X100

    6

    7

    89

    10

    111213

    15

    14

    2

    1

    3

    4

    5

    22

    2123

    24

    SO2

    TCS2

    PO4

    SO1

    TCS1

    PO3

    PO2

    PO1

    IRF

    +

    -

    Uaux

    20

    1) The IED f eatures an automatic short-circuit

    mechanism in the CT connector when plug-in

    unit is detached

    1)

    X120

    1

    2

    3

    4

    5

    6

    7

    89

    1011

    12

    14Io

    IL1

    IL2

    BI 4

    BI 3

    BI 2

    BI 1

    IL3

    1/5A

    N

    1/5A

    N

    1/5A

    N

    1/5A

    N

    13

    L1

    L2L3

    N

    Ru Ru Ru Rs Rs Rs

    GUID-72C26156-5904-4F37-B2CB-B2AD5F710BAC V1 EN

    Figure 10: Connection diagram for configuration A when used as busbar

    differential protection

    1MRS757455 A Section 3REB611 standard configuration

    REB611 21Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    28/72

    L1

    L2L3

    REB611

    16

    17

    1918

    X100

    67

    8910

    111213

    15

    14

    2

    1

    3

    4

    5

    22

    2123

    24

    SO2

    TCS2

    PO4

    SO1

    TCS1

    PO3

    PO2

    PO1

    IRF

    +

    -

    Uaux

    20

    1) The IED features an automatic short-circuit

    mecha nism in the CT connector when plug-in unit is detached

    1)

    X120

    1

    2

    3

    4

    5

    6

    7

    89

    1011

    12

    14Io

    IL1

    IL2

    BI 4

    BI 3

    BI 2

    BI 1

    IL3

    1/5A

    N

    1/5A

    N

    1/5A

    N

    1/5A

    N

    13

    3~

    Ru RsRu Ru Rs

    G

    Rs

    GUID-000FA2D5-6D6C-4A66-9772-7741A0BA3E91 V1 EN

    Figure 11: Connection diagram for configuration A when used as rotating

    machine phase differential protection

    Section 3 1MRS757455 AREB611 standard configuration

    22 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    29/72

    L1L2L3

    REB611

    16

    17

    1918

    X100

    67

    8910

    1112

    13

    15

    14

    2

    1

    3

    4

    5

    22

    2123

    24

    SO2

    TCS2

    PO4

    SO1

    TCS1

    PO3

    PO2

    PO1

    IRF

    +

    -

    Uaux

    20

    1) The IED f eatures an automatic short-circuit

    mechan ism in the CT connector when plug-in

    unit is detached

    1)

    X120

    1

    2

    3

    4

    5

    6

    7

    89

    1011

    12

    14

    Io

    IL1

    IL2

    BI 4

    BI 3

    BI 2

    BI 1

    IL3

    1/5A

    N

    1/5A

    N

    1/5A

    N

    1/5A

    N

    13

    3~

    G

    Ru Rs

    GUID-00968A99-E6A2-4649-A50F-28E52CB8F484 V1 EN

    Figure 12: Connection diagram for configuration A when used as rotating

    machine restricted earth-fault protection

    3.4 Presentation of standard configurationFunctional diagramsThe functional diagrams describe the IED's functionality from the protection,

    measuring, condition supervision, disturbance recording, control and interlockingperspective. Diagrams show the default functionality with simple symbol logics

    forming principle diagrams.

    The functional diagrams are divided into sections with each section constituting

    one functional entity.

    Protection function blocks are part of the functional diagram. They are identified

    based on their IEC 61850 name but the IEC based symbol and the ANSI function

    number are also included. Some function blocks, such as HIPDIF, are used several

    times in the configuration. To separate the blocks from each other, the IEC 61850

    name, IEC symbol and ANSI function number are appended with a running

    1MRS757455 A Section 3REB611 standard configuration

    REB611 23Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    30/72

    number, that is an instance number, from one upwards. If the block has no suffix

    after the IEC or ANSI symbol, the function block has been used, that is,

    instantiated, only once.

    Switch groupsSwitch group information can be divided into three levels.

    The first level is a configuration overview. All switch groups in the

    configuration are presented in an overview figure. The figure provides general

    information about the relationship between different switch groups.

    The second level presents function group information. It explains how the

    switch groups belong to a special function as well as related function blocks.

    The third level presents detailed information about the switch groups. It

    provides information about a specific switch group including the logic

    connection of the input and output, default connection and port description.

    Conventions used in switch group figures:

    The text in the symbol indicates the logic connections of the function's

    inputs or outputs. The text is a combination of a function block name and the

    input or output name. They are connected with a _ symbol.

    If there are many lines of text in an output symbol , each line indicates a

    signal. The switch group output is routed to all these signals.

    If there are many lines of text in an input symbol , each line indicates a

    signal. All signals are routed to a switch group input via an OR logic.

    The text above the connection line is the description of the port.

    If there is no text in the connection line, the port description is the same as thetext in the symbol.

    A dashed arrow within the switch group function box indicate the default

    connection of the switch group.

    3.5 Standard configuration A3.5.1 Applications

    The standard configuration for phase-segregated high-impedance differential

    protection and non-directional earth-fault protection is mainly intended for use in

    high-impedance-based applications within utility substations and industrial power

    systems. In addition, the IED can also be used in restricted earth-fault and residual

    earth-fault applications for the protection of generators, motors, transformers and

    reactors.

    The IED with a standard configuration is delivered from the factory with default

    settings and parameters. The end-user flexibility for incoming, outgoing and

    internal signal designation within the IED enables this configuration to be further

    Section 3 1MRS757455 AREB611 standard configuration

    24 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    31/72

    adapted to different primary circuit layouts and the related functionality needs by

    modifying the internal functionality using PCM600.

    3.5.2 FunctionsTable 8: Functions included in the standard configuration AFunction IEC 61850 IEC 60617 IEC-ANSIProtectionHigh-impedance differential protection,

    instance 1HIPDIF1 dHi>(1) 87(1)

    High-impedance differential protection,

    instance 2HIPDIF2 dHi>(2) 87(2)

    High-impedance differential protection,

    instance 3HIPDIF3 dHi>(3) 87(3)

    Non-directional earth-fault protection, lowstage, instance 1 EFLPTOC1 Io> (1) 51N-1 (1)

    Non-directional earth-fault protection, high

    stage, instance 1EFHPTOC1 Io>> (1) 51N-2 (1)

    Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF

    Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)

    Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)

    Switch groupsInput switch group ISWGAPC ISWGAPC ISWGAPC

    Output switch group OSWGAPC OSWGAPC OSWGAPC

    Selector switch group SELGAPC SELGAPC SELGAPC

    Configurable timerMinimum pulse timer (2 pcs) TPGAPC TP TP

    ControlCircuit-breaker control CBXCBR1 I O CB I O CB

    SupervisionTrip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)

    Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)

    CT supervision for high-impedance

    protection scheme, instance 1HZCCRDIF1 MCS 1I(1) MCS 1I(1)

    CT supervision for high-impedance

    protection scheme, instance 2 HZCCRDIF2 MCS 1I(2) MCS 1I(2)

    CT supervision for high-impedance

    protection scheme, instance 3HZCCRDIF3 MCS 1I(3) MCS 1I(3)

    MeasurementDisturbance recorder RDRE1 - -

    Three-phase current measurement,

    instance 11)CMMXU1 3I 3I

    Residual current measurement, instance 1 RESCMMXU1 Io In

    1) In REB611, CMMXU is used for measuring differential phase currents.

    1MRS757455 A Section 3REB611 standard configuration

    REB611 25Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    32/72

    3.5.2.1 Default I/O connectionsTable 9: Default connections for binary inputsBinary input Default usage Connector pinsX120-BI1 - X120-1,2

    X120-BI2 Circuit breaker closed position indication X120-3,2

    X120-BI3 Circuit breaker open position indication X120-4,2

    X120-BI4 - X120-5,6

    Table 10: D efault connections for binary outputsBinary input Default usage Connector pinsX100-PO1 Close circuit breaker X100-6,7

    X100-PO2 Circuit breaker failure protection trip to upstream

    breaker

    X100-8,9

    X100-PO3 Open circuit breaker/trip coil 1 X100-15,16,17,18,19

    X100-PO4 Open circuit breaker/trip coil 2 X100-20,21,22,23,24

    X100-SO1 General start indication X100-10,11,12

    X100-SO2 General operate indication X100-13,14,15

    Table 11: Default connections for LEDsLED Default usage1 High-impedance differential protection stage 1 operate

    2 High-impedance differential protection stage 2 operate

    3 High-impedance differential protection stage 3 operate

    4 High-impedance differential protection start

    5 Dedicated phase-segregated supervision function alarm

    6 Disturbance recorder triggered

    7 Trip circuit supervision alarm

    8 Circuit-breaker failure operate

    3.5.2.2 Predefined disturbance recorder connectionsTable 12: Predefined analog channel setupChannel Selection and text1 IL1

    2 IL2

    3 IL3

    4 Io

    Section 3 1MRS757455 AREB611 standard configuration

    26 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    33/72

    Additionally, all the digital inputs that are connected by default are also enabled

    with the setting. Default triggering settings are selected depending on the

    connected input signal type. Typically all protection START signals are selected to

    trigger the disturbance recorded by default.

    3.5.3 Functional diagramsThe functional diagrams describe the default input, output, programmable LED,

    switch group and function-to-function connections. The default connections can be

    viewed and changed with switch groups in PCM600, LHMI and WHMI according

    to the application requirements.

    The analog channels have fixed connections towards the different function blocks

    inside the IEDs standard configuration. Exceptions from this rule are the four

    analog channels available for the disturbance recorder function. These channels are

    freely selectable and a part of the disturbance recorders parameter settings.

    3.5.3.1 Functional diagrams for protectionThe functional diagrams describe the IEDs protection functionality in detail and

    picture the factory default connections.

    LED 4

    HIGH-IMPEDANCE DIFFERENTIAL PROTECTION

    HIPDIF1

    dHi>(1)

    87(1)

    BLOCK

    OPERATEI_A

    START

    HIPDIF2dHi>(2)

    87(2)

    BLOCK

    OPERATEI_B

    START

    HIPDIF3dHi>(3)

    87(3)

    BLOCK

    OPERATEI_C

    START

    OSWGAPC4

    OR OUT

    IN_1

    IN_2

    IN_3

    SELGAPC4

    OUT_4IN_6

    LED 1

    LED 2

    LED 3

    OSWGAPC10

    OUTIN_3

    OSWGAPC9

    OUTIN_2

    OSWGAPC8

    OUTIN_1

    SELGAPC4

    OUT_3IN_12

    SELGAPC4

    OUT_2IN_11

    SELGAPC4

    OUT_1IN_10

    HZCCRDIF1_ALARM

    HZCCRDIF2_ALARM

    HZCCRDIF3_ALARM

    GUID-4D5EE676-4AC1-4E46-B4C8-641B149B3C83 V1 EN

    Figure 13: High-impedance differential protection

    1MRS757455 A Section 3REB611 standard configuration

    REB611 27Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    34/72

    Three high-impedance differential protection instances are offered. By default,

    HIPDIF1 is for phase A current channel, HIPDIF2 is for phase B current channel,

    and HIPDIF3 is for phase C current channel. The ALARM outputs of the phase-

    segregated current transformer supervision (HZCCRDIF) block HIPDIF.

    HIPDIF1 operate signal is connected to LED 1, HIPDIF2 operate signal is

    connected to LED 2, HIPDIF3 operate signal is connected to LED 3. All the start

    signals from HIPDIF1...HIPDIF3 are connected to LED 4.

    HZCCRDIF3MCS 1I(3)

    MCS 1I(3)

    BLOCK

    ALARMI_C

    HZCCRDIF2

    MCS 1I(2)

    MCS 1I(2)

    BLOCK

    ALARMI_B

    HZCCRDIF1

    MCS 1I(1)

    MCS 1I(1)

    BLOCK

    ALARMI_A

    LED 5

    SELGAPC4

    OUT_5IN_13

    OSWGAPC11

    OR OUT

    IN_1

    IN_2

    IN_3

    PHASE SEGREGATED CT SUPERVISION

    GUID-2777A166-E375-4BC4-90D7-87A80E477393 V1 EN

    Figure 14: Phase segregated CT supervision

    Three phase-segregated current transformer supervision instances are offered. By

    default, HZCCRDIF1 is for phase A current channel, HZCCRDIF 2 is for phase B

    current channel, and HZCCRDIF 3 is for phase C current channel.

    All the ALARM output signals are connected to LED 5.

    Section 3 1MRS757455 AREB611 standard configuration

    28 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    35/72

    EARTH-FAULT PROTECTION

    EFLPTOC1

    Io>(1)

    51N-1(1)

    BLOCK START

    OPERATEIo

    ENA_MULT

    EFHPTOC1

    Io>>(1)

    51N-2(1)

    BLOCK START

    OPERATEIo

    ENA_MULT

    GUID-A45C3D99-3B0D-48D9-B152-6BEEBBC29A82 V1 EN

    Figure 15: Earth-fault protection

    Two stages are offered for non-directional earth-fault protection. The operate

    signals of the earth-fault protections are connected to the Master Trip.

    X120-BI2

    X100 PO2

    LED 8

    OR

    SELGAPC3

    OUT_2IN_4

    CIRCUIT BREAKER FAILURE PROTECTION

    SELGAPC1

    OUT_2IN_2

    CB Closed Position

    SELGAPC4

    OUT_8IN_16

    OSWGAPC14

    OUTIN_7

    EFLPTOC1_OPERATE

    HIPDIF3_OPERATE

    HIPDIF1_OPERATE

    HIPDIF2_OPERATE

    EFHPTOC1_OPERATE

    51BF/51NBF(1)

    3I

    Io

    START TRRET

    TRBU

    POSCLOSE

    CB_FAULT

    BLOCK

    CB_FAULT_AL

    CCBRBRF1

    3I>/Io>BF(1)

    GUID-03078895-719E-4704-84A7-EDFFBE60DD4A V1 EN

    Figure 16: Circuit breaker failure protection

    The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input

    by a number of different protection stages in the IED. CCBRBRF1 offers different

    operating modes associated with the circuit breaker position and the measured

    phase and residual currents. CCBRBRF1 has two operating outputs: TRRET and

    TRBU. The TRRET operate output is used for retripping its own circuit breaker

    through Master Trip 2. The TRBU output is used to give a backup trip to the circuit-

    breaker feeding upstream. For this purpose, the TRBU operate output signal is

    1MRS757455 A Section 3REB611 standard configuration

    REB611 29Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    36/72

    connected to the output PO2 (X100: 8-9). LED 8 is used for backup (TRBU)

    operate indication.

    3.5.3.2 Functional diagrams for disturbance recorderDISTURBANCE RECORDER

    LED 6

    OR

    HIPDIF1_OPERATE

    HIPDIF2_OPERATE

    HIPDIF3_OPERATE

    EFLPTOC1_OPERATE

    EFHPTOC1_OPERATE

    OR

    RDRE1C1

    C2

    C3

    C4

    C5

    C6

    C7

    C8

    C9

    C10

    C11C12

    C13

    C14C15

    C16

    C17

    C18

    C19

    C20

    C21

    C22

    TRIGGERED

    OSWGAPC12

    OUTIN_4

    SELGAPC4

    OUT_6IN_14HIPDIF1_START

    HIPDIF2_START

    HIPDIF3_START

    EFHPTOC1_START

    EFLPTOC1_START

    SELGAPC1_ Blocking

    SELGAPC1_ CB Closed Position

    SELGAPC1_ CB Open Position

    CCBRBRF1_TRRET

    CCBRBRF1_TRBU

    HZCCRDIF1_ALARM

    HZCCRDIF2_ALARMHZCCRDIF3_ALARM

    SELGAPC1_External Trip

    SG_1_ACT

    SG_2_ACT

    SG_3_ACT

    SG_4_ACT

    SG_5_ACT

    SG_6_ACT

    GUID-76A45579-A1D9-4048-8A86-BB2AFC0CE8C7 V1 EN

    Figure 17: Disturbance recorder

    All start and operate signals from the protection stages are routed to trigger the

    disturbance recorder or alternatively only to be recorded by the disturbance

    recorder depending on the parameter settings. Additionally, the selectedautoreclosing output signals and the three binary inputs from X120 are also

    connected. The active setting group is also to be recorded via SG_1_ACT to

    SG_6_ACT. The disturbance recorder triggered signal indication is connected to

    LED 6.

    T ab le 13 : D istu rb anc e re co rd er bin ary ch an nel de fa ult v alu eChannel number Channel id text Level trigger modeBinary channel 1 HIPDIF1_START 1=positive or rising

    Binary channel 2 HIPDIF2_START 1=positive or rising

    Binary channel 3 HIPDIF3_START 1=positive or rising

    Binary channel 4 EFLPTOC1_START 1=positive or rising

    Binary channel 5 EFHPTOC1_START 1=positive or rising

    Binary channel 6 HIPDIF1/2/3_OPERATE 4=level trigger off

    Binary channel 7 EFxPTOC1_OPERATE 4=level trigger off

    Binary channel 8 SELGAPC1_Blocking 4=level trigger off

    Binary channel 9 SELGAPC1_CB_Closed 4=level trigger off

    Binary channel 10 SELGAPC1_CB_Open 4=level trigger off

    Binary channel 11 CCBRBRF1_TRRET 4=level trigger off

    Binary channel 12 CCBRBRF1_TRBU 4=level trigger off

    Table continues on next page

    Section 3 1MRS757455 AREB611 standard configuration

    30 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    37/72

    Channel number Channel id text Level trigger modeBinary channel 13 HZCCRDIF1_ALARM 1=positive or rising

    Binary channel 14 HZCCRDIF2_ALARM 1=positive or rising

    Binary channel 15 HZCCRDIF3_ALARM 1=positive or rising

    Binary channel 16 SELGAPC1_External Trip 4=level trigger off

    Binary channel 17 SG_1_ACT 4=level trigger off

    Binary channel 18 SG_2_ACT 4=level trigger off

    Binary channel 19 SG_3_ACT 4=level trigger off

    Binary channel 20 SG_4_ACT 4=level trigger off

    Binary channel 21 SG_5_ACT 4=level trigger off

    Binary channel 22 SG_6_ACT 4=level trigger off

    X120-BI3

    OR

    LED 7

    TRIP CIRCUIT SUPERVISION

    SELGAPC1

    OUT_3IN_3

    TRPPTRC1_TRIP

    TRPPTRC2_TRIP

    TCSSCBR1

    BLOCK ALARM

    TCSSCBR2

    BLOCK ALARM

    SELGAPC2

    OUT_1

    IN_2 OUT_2

    OSWGAPC13

    OR OUT

    IN_5

    IN_6

    SELGAPC4

    OUT_7IN_15

    CB Open Position

    GUID-535EAC11-8657-4F5B-BAB2-E91FF795C817 V1 EN

    Figure 18: Trip circuit supervision

    Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3

    (X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked

    by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open

    position. The TCS alarm indication is connected to LED 7.

    1MRS757455 A Section 3REB611 standard configuration

    REB611 31Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    38/72

    3.5.3.3 Functional diagrams for control and interlocking

    X100 PO3

    X100 PO4

    MASTER TRIP #1

    MASTER TRIP #2

    OR

    OR

    SELGAPC3

    OUT_6IN_2

    SELGAPC3

    OUT_5IN_1TRIP

    CL_LKOUT

    BLOCK

    RST_LKOUT

    TRPPTRC1

    OPERATE

    TRIP

    CL_LKOUT

    BLOCK

    RST_LKOUT

    TRPPTRC2

    OPERATE

    SELGAPC1_RST_LKOUT

    CBXCBR1_EXE_OP

    SELGAPC1_External Trip

    SELGAPC1_External Trip

    SELGAPC1_RST_LKOUT

    HIPDIF1_OPERATE

    HIPDIF2_OPERATE

    HIPDIF3_OPERATE

    EHLPTOC1_OPERATE

    EFHPTOC1_OPETATE

    CCBRBRF1_TRRET

    HIPDIF1_OPERATE

    HIPDIF2_OPERATE

    HIPDIF3_OPERATE

    EHLPTOC1_OPERATE

    EFHPTOC1_OPETATE

    OSWGAPC2

    OR

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    IN_6

    OUT

    OR

    OSWGAPC1

    OR

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    OUT

    GUID-AFCBCEC5-678B-4F8B-9963-FFE91A7F1233 V1 EN

    Figure 19: Master trip

    The operate signals from the protections and an external trip are connected to the

    two trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the

    corresponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commands

    to the circuit breaker from local or remote CBXCBR1_EXE_OP or from the

    autoreclosing DARREC1_OPEN_CB are connected directly to the output contact

    PO3 (X100:15-19).

    TRPPTRC1 and 2 provide the lockout/latching function, event generation and the

    trip signal duration setting. One binary input through SELGAPC1 can be connected

    to the RST_LKOUT input of Master Trip. If the lockout operation mode is

    selected, it is used to enable external reset.

    Section 3 1MRS757455 AREB611 standard configuration

    32 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    39/72

    X120-BI2

    X120-BI3

    ANDTRPPTRC1_TRIP

    TRPPTRC2_TRIP

    CBXCBR1_EXE_OP

    X100 PO1

    CIRCUIT BREAKER CONTROL

    Always True

    CBXCBR1

    ENA_OPEN

    SELECTED

    EXE_OP

    EXE_CL

    ENA_CLOSE

    BLK_OPEN

    BLK_CLOSE

    AU_OPEN

    AU_CLOSE

    POSOPEN

    POSCLOSE

    OPENPOS

    CLOSEPOS

    OKPOS

    OPEN_ENAD

    CLOSE_ENAD

    ITL_BYPASS

    SELGAPC3

    OUT_1IN_3

    CB Closed Position

    CB Open Position

    SELGAPC1

    OUT_2

    IN_3

    IN_2

    OUT_3

    IN_5 OUT_4

    GUID-F781E05E-B262-4A46-BDF7-CD977EE33086 V1 EN

    Figure 20: Circuit breaker control

    The ENA_CLOSE input, which enables the closing of the circuit breaker, is a

    status of the Master Trip in the circuit breaker control function block CBXCBR.An always true signal is also connected to ENA_CLOSE via SELGAPC1 by

    default. The open operation is always enabled.

    X100 SO1

    X100 SO2

    COMMON ALARM INDICATION 1 & 2

    SELGAPC3

    OUT_3IN_5

    OUT_4IN_9

    TPGAPC1

    IN1 OUT1

    TPGAPC3

    IN1 OUT1

    PHLPTOC1_OPERATE

    PHHPTOC1_OPERATE

    PHHPTOC2_OPERATE

    PHIPTOC1_OPERATE

    EFHPTOC1_OPERATE

    OSWGAPC7

    OR

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    OUT

    PHLPTOC1_START

    PHHPTOC1_START

    PHHPTOC2_START

    PHIPTOC1_START

    EFHPTOC1_START

    OSWGAPC3

    OR

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    OUT

    GUID-59A0BE26-527F-475F-AF43-2F1A2BD7FC14 V1 EN

    Figure 21: Common alarm indication

    The signal outputs from the IED are connected to give dedicated information on:

    Start of any protection function SO1 (X100:10-12).

    Operation (trip) of any protection function SO2 (X100: 13-15).

    TPGAPC are timers and used for setting the minimum pulse length for the outputs.

    There are seven generic timers (TPGAPC17) available in the IED.

    1MRS757455 A Section 3REB611 standard configuration

    REB611 33Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    40/72

    3.5.4 Switch groupsIn standard configuration A, the switch group function blocks are organized in four

    groups: binary inputs, internal signal, GOOSE as well as binary outputs and LEDs.

    GOOSE

    Binary Inputs Protection and Control

    GOOSE

    GOOSE

    GOOSE

    Binary Inputs

    (1...4)

    Received GOOSE

    (0...19)

    Binary Outputs and LEDs

    OSWGAPC2

    OSWGAPC1

    OSWGAPC16

    OSWGAPC15

    OSWGAPC14

    OSWGAPC13

    OSWGAPC12

    OSWGAPC11

    SELGAPC4

    LEDs

    SELGAPC3

    Binary Outputs

    OSWGAPC10

    OSWGAPC9

    OSWGAPC8

    OSWGAPC7

    OSWGAPC6

    OSWGAPC5

    OSWGAPC4

    OSWGAPC3

    Binary Outputs

    (1...6)

    LEDs

    (18)

    HIPDIF1 HIPDIF2

    HIPD IF 3 E FLP TO C1

    EFHPTOC1 HZCCRDIF1

    HZCCRDIF2 HZCCRDIF3

    CBXCBR1

    TCSSCBR1 TCSSCBR2

    CCBRBRF1

    SELGAPC1

    Binary Inputs

    ISWGAPC1

    SELGAPC2

    Blocking

    TCS Blocking

    ISWGAPC9

    GOOSE Blocking

    ISWGAPC10

    GOOSE Block CBAlarm

    Trip

    Start

    Master trip

    Internal Signal

    GUID-E6D66B73-6C09-4979-9E08-49CEFEC60BD3 V1 EN

    Figure 22: Standard configuration A switch group overview

    3.5.4.1 Binary inputsThe binary inputs group includes one SELGAPC and one ISWGAPC. SELGAPC1

    is used to route binary inputs to ISWGAPC or directly to IED functions.

    ISWGAPC1 is used to configure the signal to block the protection functions.

    SELGAPC1 ISWGAPC1Blocking 1

    HIPDIF1_BLOCK

    HIPDIF2_BLOCK

    HIPDIF3_BLOCK

    EFLPTOC1_BLOCK

    EFHPTOC1_BLOCK

    HZCCRDIF1_BLOCK

    HZCCRDIF2_BLOCK

    HZCCRDIF3_BLOCK

    X120-BI1

    X120-BI2

    X120-BI3

    X120-BI4

    GUID-77ACA5A9-62F9-43BB-835B-016DE800A3C4 V1 EN

    Figure 23: Binary inputs

    SELGAPC1SELGAPC1 has inputs from IED binary inputs. IN_1 to IN_4 are binary inputs

    from X100. An always true signal is connected to IN_5. SELGAPC1 outputs are

    used to route inputs to different functions. By setting SELGAPC1, binary inputs

    can be configured for different purposes.

    Section 3 1MRS757455 AREB611 standard configuration

    34 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    41/72

    SELGAPC1

    CB Closed Position

    CB Open Position CBXCBR1_POSOPEN

    SELGAPC2_IN_2

    Blocking 1

    External Trip

    PROTECTION_BI_SG_2Setting Group 2

    PROTECTION_BI_SG_3Setting Group 3

    PROTECTION_BI_SG_4Setting Group 4

    ISWGAPC1_INX120/1-2 BI1

    X120/3-2 BI2

    X120/4-2 BI3

    X120/5-6 BI4

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    TRPTTRC1_OPERATE

    TRPTTRC2_OPERATE

    X120-BI1

    X120-BI2

    X120-BI3

    X120-BI4

    Always True

    OUT_1

    OUT_2

    OUT_3

    OUT_4

    OUT_5

    OUT_6

    OUT_7

    OUT_8

    OUT_9

    CBXCBR1_ENA_CLOSE

    TRPTTRC1_RST_LKOUT

    TRPTTRC2_RST_LKOUT

    TRPTTRC1/2_

    RST_LKOUT

    CB Close Enable

    CBXCBR1_POSCLOSE

    SELGAPC2_IN_1

    GUID-C41611AC-B385-438D-AF2F-DACEC6B69B48 V1 EN

    Figure 24: SELGAPC1

    ISWGAPC1ISWGAPC1 is used for general blocking. ISWGAPC1 input is from SELGAPC1

    output OUT_1 Blocking 1. ISWGAPC1 outputs are connected to BLOCK inputs of

    protection functions. Select which protection functions are to be blocked by

    changing ISWGAPC1 parameters.

    ISWGAPC1

    IN

    OUT_1

    OUT_2

    OUT_3

    OUT_4

    OUT_5

    OUT_6

    OUT_7

    OUT_8

    Blocking 1SELGAPC1_OUT_1

    HIPDIF1_BLOCK

    HIPDIF2_BLOCK

    HIPDIF3_BLOCK

    EFLPTOC1_BLOCK

    EFHPTOC1_BLOCK

    HZCCRDIF1_BLOCK

    HZCCRDIF2_BLOCK

    HZCCRDIF3_BLOCK

    GUID-404D31F7-C132-46B4-8AFA-321C80881FA3 V1 EN

    Figure 25: ISWGAPC1

    3.5.4.2 Internal signalThe internal signal group is used to configure the logic connections between

    function blocks. There is one SELGAPC in this group.

    SELGAPC2 is used to configure trip circuit supervision blocking from the circuit

    breaker open or close position.

    1MRS757455 A Section 3REB611 standard configuration

    REB611 35Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    42/72

    SELGAPC2 TCSSCBR1_BLOCK

    TCSSCBR2_BLOCK

    SELGAPC1_OUT_2

    SELGAPC1_OUT_3

    CB Closed Position

    CB Open Position

    GUID-DB5EA70F-6249-400F-90B2-DB7D1758B4BC V1 EN

    Figure 26: Internal signal

    SELGAPC2SELGAPC2 inputs are circuit breaker closed and open positions from SELGACP1.

    SELGAPC2 outputs are routed to the BLOCK input of the trip circuit supervision

    TCSSCBR1 and TCSSCBR2.

    By default, X100 PO3 and PO4 are both used for the open circuit breaker.

    TCSSCBR1 and TCSSCBR2 are both blocked by the circuit breaker open position.

    If X100-PO3 is used for closing the circuit breaker, TCSSCBR1 needs to be

    blocked by the circuit breaker close position (OUT_1 connection=IN_1). If X100-

    PO4 is used for closing the circuit breaker, TCSSCBR2 needs to be blocked by the

    circuit breaker close position (OUT_2 connection=IN_1).

    SELGAPC2

    IN_1

    IN_2

    OUT_1

    OUT_2

    TCSSCBR1_BLOCK

    TCSSCBR2_BLOCK

    SELGAPC1_OUT_2

    SELGAPC1_OUT_3

    CB Closed Position

    CB Open Position

    GUID-9F97A340-1373-49E8-A0D1-F0FBDFB9B753 V1 EN

    Figure 27: SELGAPC2

    3.5.4.3 Binary outputs and LEDsIn standard configuration A, the signals route to binary outputs, and LEDs are

    configured by OSWGAPCs. There are totally 15 OSWGAPC instances. They can

    be categorized to four groups, including one Master trip, four start, four trip and six

    alarm signals. The OSWGAPC output is connected to binary outputs and LEDs via

    SELGAPC3 and SELGAPC4.

    SELGAPC3 is used to configure OSWGAPC signals to IED binary outputs.

    SELGAPC4 is used to configure OSWGAPC signals to LEDs.

    OSWGAPC1 is used for Master trip. The inputs are from protection functions

    operate and circuit-breaker failures re-trip. OSWGAPC2 is not in used.

    OSWGAPC3 to OSWGAPC6 are used for the start signal. The inputs are start

    signals from the protection functions.

    OSWGAPC7 to OSWGAPC10 are used for the trip signal. The inputs are

    operation signals from the protection functions.

    OSWGAPC11 to OSWGAPC16 are used for the alarm signal. The inputs are

    alarm signals from the protection and monitoring functions.

    Section 3 1MRS757455 AREB611 standard configuration

    36 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    43/72

    Master Trip 1

    Trip 1

    Trip 2

    Trip 3

    Trip 4

    HZCCRDIF1_ALARM

    HZCCRDIF2_ALARM

    HZCCRDIF3_ALARM

    RDRE_TRIGGERED

    TCSSCBR1_ALARM

    TCSSCBR2_ALARM

    CCBRBRF1_TRBU

    CCBRBRF1_TRRET

    SELGAPC1_OUT_6

    TRPPTRC1_CL_LKOUT

    TRPPTRC2_CL_LKOUT

    OSWGAPC12 Alarm 2

    OSWGAPC13 Alarm 3

    OSWGAPC14 Alarm 4

    OSWGAPC1

    OSWGAPC3

    OSWGAPC11 Alarm 1

    TRPPTRC1

    TPGAPC3

    TPGAPC4

    TPGAPC5

    TPGAPC6

    SELGAPC3

    HIPDIF1_OPERATE

    HIPDIF2_OPERATE

    HIPDIF3_OPERATE

    EFLPTOC1_OPERATE

    EFHPTOC1_OPERATE

    CCBRBRF1_TRRET

    HIPDIF1_START

    HIPDIF2_START

    HIPDIF3_START

    EFLPTOC1_START

    EFHPTOC1_START

    OSWGAPC8

    OSWGAPC7

    OSWGAPC10

    OSWGAPC9

    X100 PO1

    X100 PO2

    X100 SO1

    X100 SO2

    X100 PO3

    X100 PO4

    Start 1

    Start 2

    TPGAPC1

    OSWGAPC4

    OSWGAPC5 Start 3

    Start 4

    TPGAPC2

    OSWGAPC6

    OSWGAPC15 Alarm 5

    OSWGAPC16 Alarm 6

    TPGAPC7

    IN1 OUT1

    IN2 OUT2

    IN1 OUT1

    IN2 OUT2

    IN1 OUT1

    IN2 OUT2

    IN1 OUT1

    IN2 OUT2

    IN1 OUT1

    IN2 OUT2

    IN1 OUT1

    IN2 OUT2

    IN1 OUT1

    IN2 OUT2

    Master Trip 2OSWGAPC2 TRPPTRC2

    HIPDIF1_OPERATE

    HIPDIF2_OPERATE

    HIPDIF3_OPERATE

    EFLPTOC1_OPERATE

    EFHPTOC1_OPERATE

    GUID-9968F50A-8710-4EF7-A980-78A82488B59D V1 EN

    Figure 28: Binary outputs

    1MRS757455 A Section 3REB611 standard configuration

    REB611 37Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    44/72

    Trip 1

    Trip 2

    Trip 3

    Trip 4

    OSWGAPC3

    OSWGAPC11 Alarm 1

    SELGAPC4

    OSWGAPC8

    OSWGAPC7

    OSWGAPC10

    OSWGAPC9

    Start 1

    Start 2OSWGAPC4

    OSWGAPC5 Start 3

    Start 4OSWGAPC6

    LED1

    LED2

    LED3

    LED4

    LED5

    LED6

    LED7

    LED8

    OSWGAPC12 Alarm 2

    OSWGAPC13 Alarm 3

    OSWGAPC14 Alarm 4

    OSWGAPC15 Alarm 5

    OSWGAPC16 Alarm 6

    HZCCRDIF1_ALARM

    HZCCRDIF2_ALARM

    HZCCRDIF3_ALARM

    RDRE_TRIGGERED

    TCSSCBR1_ALARM

    TCSSCBR2_ALARM

    CCBRBRF1_TRBU

    CCBRBRF1_TRRET

    SELGAPC1_OUT_6

    TRPPTRC1_CL_LKOUT

    TRPPTRC2_CL_LKOUT

    HIPDIF1_OPERATE

    HIPDIF2_OPERATE

    HIPDIF3_OPERATE

    EFLPTOC1_OPERATE

    EFHPTOC1_OPERATECCBRBRF1_TRRET

    HIPDIF1_START

    HIPDIF2_START

    HIPDIF3_START

    EFLPTOC1_START

    EFHPTOC1_START

    HIPDIF1_OPERATE

    HIPDIF2_OPERATE

    HIPDIF3_OPERATE

    EFLPTOC1_OPERATE

    EFHPTOC1_OPERATE

    Master Trip 1OSWGAPC1 TRPPTRC1

    Master Trip 2OSWGAPC2 TRPPTRC2

    GUID-DC07ECE8-4492-4836-A9DF-53696F581F9B V1 EN

    Figure 29: LEDs

    SELGAPC3SELGAPC3 is used to configure the OSWGAPC outputs to the IED binary

    outputs. The Master trip signals are connected to SELGAPC3 via TRPPTRC. Start,

    trip and alarm signals are connected to SELGAPC3 via TPGAPC. TPGAPC are

    timers and used for setting the minimum pulse length for the outputs.

    SELGAPC3 outputs are connected with X100 binary outputs.

    Section 3 1MRS757455 AREB611 standard configuration

    38 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    45/72

    SELGAPC3

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    IN_6

    IN_7

    IN_8

    IN_9

    IN_10

    IN_11

    IN_12

    IN_13

    OUT_1

    OUT_2

    OUT_3

    OUT_4

    OUT_5

    OUT_6

    IN_14

    IN_15

    IN_16

    IN_17

    IN_18

    X100 PO1

    X100 PO2

    X100 SO1

    X100 SO2

    X100 PO3

    X100 PO4

    OSWGAPC11_OUT

    OSWGAPC12_OUT

    OSWGAPC13_OUT

    OSWGAPC14_OUT

    OSWGAPC15_OUT

    OSWGAPC16_OUT

    OSWGAPC5_OUT

    OSWGAPC6_OUT

    OSWGAPC7_OUT

    OSWGAPC8_OUT

    OSWGAPC9_OUT

    OSWGAPC10_OUT

    OSWGAPC3_OUT

    OSWGAPC4_OUT

    Start 1

    Start 2

    Start 3

    Start 4

    Trip 1

    Alarm 1

    Trip 2

    Trip 3

    Trip 4

    Alarm 2

    Alarm 3

    Alarm 4

    Alarm 5

    Alarm 6

    Backup Trip

    CBXCBR_EXE_OP

    TRPPTRC1_TRIP

    TRPPTRC2_TRIP

    CCBRBRF1_TRBU

    CB Open 1

    CB Close

    TPGAPC1

    IN1 OUT1

    IN2 OUT2

    TPGAPC7

    IN1 OUT1

    IN2 OUT2

    TPGAPC6

    IN1 OUT1

    IN2 OUT2

    TPGAPC5

    IN1 OUT1

    IN2 OUT2

    TPGAPC4

    IN1 OUT1

    IN2 OUT2

    TPGAPC3

    IN1 OUT1

    IN2 OUT2

    TPGAPC2

    IN1 OUT1

    IN2 OUT2

    CBXCBR_EXE_CL

    CB Open 2

    GUID-7460958A-CAC2-40A0-917E-AAFD885C806B V1 EN

    Figure 30: SELGAPC3

    SELGAPC4SELGAPC4 is used to configure the OSWGAPC outputs to LEDs. Master trip

    signals are connected to SELGAPC4 via TRPPTRC. Start, trip and alarm signals

    are connected to SELGAPC4 directly. SELGAPC4 outputs are connected toprogrammable LED1 to LED8.

    1MRS757455 A Section 3REB611 standard configuration

    REB611 39Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    46/72

    SELGAPC4

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    IN_6

    IN_7

    IN_8

    IN_9

    IN_10

    IN_11

    IN_12

    IN_13

    OUT_1

    OUT_2

    OUT_3

    OUT_4

    OUT_5

    OUT_6

    OUT_7

    OUT_8

    IN_14

    IN_15

    IN_16

    IN_17

    IN_18

    LED1

    LED2

    LED3

    LED4

    LED5

    LED6

    LED7

    LED8

    Start 1

    Start 2

    Start 3

    Start 4

    Trip 1

    Alarm 1

    Trip 2

    Trip 3

    Trip 4

    Alarm 2

    Alarm 3

    Alarm 4

    Alarm 5

    Alarm 6

    OSWGAPC11_OUT

    OSWGAPC12_OUT

    OSWGAPC13_OUT

    OSWGAPC14_OUT

    OSWGAPC15_OUT

    OSWGAPC16_OUT

    OSWGAPC5_OUT

    OSWGAPC6_OUT

    OSWGAPC7_OUT

    OSWGAPC8_OUT

    OSWGAPC9_OUT

    OSWGAPC10_OUT

    OSWGAPC3_OUT

    OSWGAPC4_OUT

    CCBRBRF1_TRBU Backup Trip

    CB Close

    CB Open 1CBXCBR_EXE_OP

    TRPPTRC1_TRIP

    CBXCBR_EXE_CL

    TRPPTRC2_TRIP CB Open 2

    GUID-ACEEEFCD-3CA8-4157-BD3E-1A3A6FD8AD1B V1 EN

    Figure 31: SELGAPC4

    Master trip OSWGAPCsOSWGAPC1 and OSWGAPC2 are used to route the protection function operate

    signals to Master trip. OSWGAPC1 and OSWGAPC2 have the same inputs from

    the protection function operates. The output is connected to the TRPPTRCfunction. The default connections for OSWGAPC1 and OSWGAPC2 are different.

    Section 3 1MRS757455 AREB611 standard configuration

    40 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    47/72

    OSWGAPC1

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    IN_6

    OUT

    EFHPTOC1_OPERATE

    CCBRBRF1_TRRET

    HIPDIF1_OPERATE

    EFLPTOC1_OPERATE

    HIPDIF3_OPERATE

    HIPDIF2_OPERATE

    TRPPTRC 1_OPERATEMaster trip 1

    GUID-C9E4582D-E2A6-4F08-9F45-E2DDF5549526 V1 EN

    Figure 32: OSWGAPC1

    OSWGAPC2

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    IN_6

    OUT

    EFHPTOC1_OPERATE

    CCBRBRF1_TRRET

    HIPDIF1_OPERATE

    EFLPTOC1_OPERATE

    HIPDIF3_OPERATE

    HIPDIF2_OPERATE

    TRPPTRC 2_OPERATEMaster trip 2

    GUID-58E5C510-F4F4-48A6-A334-C463F463FAB5 V1 EN

    Figure 33: OSWGAPC2

    Start OSWGAPCsOSWGAPC instances 3 to 6 are used to configure the protection start signals.

    These four OSWGAPCs have the same inputs from the protection function start

    signals. The output is routed to SELGAPC3 via TPGAPC timer and to SELGAPC4

    directly.

    OSWGAPC3

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    OUT

    EFHPTOC1_START

    HIPDIF1_START

    EFLPTOC1_START

    HIPDIF3_START

    HIPDIF2_START

    TPGAPC1_IN1

    SELGAPC4_IN_5Start 1

    GUID-3E6D87B9-F5F4-45E6-BD3D-180132AB6953 V1 EN

    Figure 34: OSWGAPC3

    1MRS757455 A Section 3REB611 standard configuration

    REB611 41Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    48/72

    Start 2 TPGAPC1_IN2

    SELGAPC4_IN_6

    OSWGAPC4

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    OUT

    EFHPTOC1_START

    HIPDIF1_START

    EFLPTOC1_START

    HIPDIF3_START

    HIPDIF2_START

    GUID-96AAE2FE-0993-4797-AF9A-A59E1BDB1557 V1 EN

    Figure 35: OSWGAPC4

    Start 3 TPGAPC2_IN1

    SELGAPC4_IN_7

    OSWGAPC5

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    OUT

    EFHPTOC1_START

    HIPDIF1_START

    EFLPTOC1_START

    HIPDIF3_START

    HIPDIF2_START

    GUID-EB5F5E18-7137-4ED8-9D38-B5676EA20C67 V1 EN

    Figure 36: OSWGAPC5

    Start 4 TPGAPC2_IN2

    SELGAPC4_IN_8

    OSWGAPC6

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    OUT

    EFHPTOC1_START

    HIPDIF1_START

    EFLPTOC1_START

    HIPDIF3_START

    HIPDIF2_START

    GUID-C924A4BA-AC97-420E-B676-C8C176D19B62 V1 EN

    Figure 37: OSWGAPC6

    Trip OSEGAPCsOSWGAPC instances 7 to 10 are used to configure the protection operate signals

    that belong to the trip group. These four OSWGAPCs have the same inputs from

    the operate signals of the protection functions. The output is routed to SELGAPC3

    via TPGAPC timer and to SELGAPC4 directly.

    Section 3 1MRS757455 AREB611 standard configuration

    42 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    49/72

    Trip 1 TPGAPC3_IN1

    SELGAPC4_IN_9

    OSWGAPC7

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    OUT

    EFHPTOC1_OPERATE

    HIPDIF1_OPERATE

    EFLPTOC1_OPERATE

    HIPDIF3_OPERATE

    HIPDIF2_OPERATE

    GUID-578079DE-E1D7-4F59-A45F-9809AEE5D316 V1 EN

    Figure 38: OSWGAPC7

    Trip 2 TPGAPC3_IN2

    SELGAPC4_IN_10

    OSWGAPC8

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    OUT

    EFHPTOC1_OPERATE

    HIPDIF1_OPERATE

    EFLPTOC1_OPERATE

    HIPDIF3_OPERATE

    HIPDIF2_OPERATE

    GUID-4FC22392-CF64-4B6E-B015-A41720B2155F V1 EN

    Figure 39: OSWGAPC8

    Trip 3 TPGAPC4_IN1

    SELGAPC4_IN_11

    OSWGAPC9

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    OUT

    EFHPTOC1_OPERATE

    HIPDIF1_OPERATE

    EFLPTOC1_OPERATE

    HIPDIF3_OPERATE

    HIPDIF2_OPERATE

    GUID-A21FDE7D-FC0E-4957-B55A-E372C4622BA0 V1 EN

    Figure 40: OSWGAPC9

    1MRS757455 A Section 3REB611 standard configuration

    REB611 43Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    50/72

    Trip 4 TPGAPC4_IN2

    SELGAPC4_IN_12

    OSWGAPC10

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    OUT

    EFHPTOC1_OPERATE

    HIPDIF1_OPERATE

    EFLPTOC1_OPERATE

    HIPDIF3_OPERATE

    HIPDIF2_OPERATE

    GUID-AB3796EF-B15B-4007-B4CA-FD7CEA0C111A V1 EN

    Figure 41: OSWGAPC10

    Alarm OSEGAPCsOSWGAPC instances 11 to 16 are used to configure the alarm signals that belongto the alarm group. These six OSWGAPCs have the same inputs from the alarm

    signals. The output is routed to SELGAPC3 via TPGAPC timer and to SELGAPC4

    directly.

    Alarm 1 TPGAPC5_IN1

    SELGAPC4_IN_13

    OSWGAPC11

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    IN_6

    IN_7

    IN_8

    IN_9

    IN_10

    IN_11

    OUT

    TCSSCBR1_ALARM

    TCSSCBR2_ALARM

    TRPPTRC1_CL_LKOUT

    TRPPTRC2_CL_LKOUT

    HZCCRDIF1_ALARM

    RDRE_TRIGGERED

    CCBRBRF1_TRBU

    CCBRBRF1_TRRET

    SELGAPC1_OUT_6

    HZCCRDIF3_ALARM

    HZCCRDIF2_ALARM

    External Trip

    GUID-5ADF1ED1-B09A-45E0-9CBB-B51884694F25 V1 EN

    Figure 42: OSWGAPC11

    Section 3 1MRS757455 AREB611 standard configuration

    44 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    51/72

    Alarm 2 TPGAPC5_IN2

    SELGAPC4_IN_14

    OSWGAPC12

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    IN_6

    IN_7

    IN_8

    IN_9

    IN_10

    IN_11

    OUT

    TCSSCBR1_ALARM

    TCSSCBR2_ALARM

    TRPPTRC1_CL_LKOUT

    TRPPTRC2_CL_LKOUT

    HZCCRDIF1_ALARM

    RDRE_TRIGGERED

    CCBRBRF1_TRBU

    CCBRBRF1_TRRET

    SELGAPC1_OUT_6

    HZCCRDIF3_ALARM

    HZCCRDIF2_ALARM

    External Trip

    GUID-34F14C25-B0E0-4F04-8497-79F61F419523 V1 EN

    Figure 43: OSWGAPC12

    Alarm 3 TPGAPC6_IN1

    SELGAPC4_IN_15

    OSWGAPC13

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    IN_6

    IN_7

    IN_8

    IN_9

    IN_10

    IN_11

    OUT

    TCSSCBR1_ALARM

    TCSSCBR2_ALARM

    TRPPTRC1_CL_LKOUT

    TRPPTRC2_CL_LKOUT

    HZCCRDIF1_ALARM

    RDRE_TRIGGERED

    CCBRBRF1_TRBU

    CCBRBRF1_TRRET

    SELGAPC1_OUT_6

    HZCCRDIF3_ALARM

    HZCCRDIF2_ALARM

    External Trip

    GUID-EAAD4D7D-53DB-4B8B-BB92-4ECD6D0E577F V1 EN

    Figure 44: OSWGAPC13

    1MRS757455 A Section 3REB611 standard configuration

    REB611 45Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    52/72

    Alarm 4 TPGAPC6_IN2

    SELGAPC4_IN_16

    OSWGAPC14

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    IN_6

    IN_7

    IN_8

    IN_9

    IN_10

    IN_11

    OUT

    TCSSCBR1_ALARM

    TCSSCBR2_ALARM

    TRPPTRC1_CL_LKOUT

    TRPPTRC2_CL_LKOUT

    HZCCRDIF1_ALARM

    RDRE_TRIGGERED

    CCBRBRF1_TRBU

    CCBRBRF1_TRRET

    SELGAPC1_OUT_6

    HZCCRDIF3_ALARM

    HZCCRDIF2_ALARM

    External Trip

    GUID-41241979-58B4-4C96-8B31-5560C6EC5D53 V1 EN

    Figure 45: OSWGAPC14

    Alarm 5 TPGAPC7_IN1

    SELGAPC4_IN_17

    OSWGAPC15

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    IN_6

    IN_7

    IN_8

    IN_9

    IN_10

    IN_11

    OUT

    TCSSCBR1_ALARM

    TCSSCBR2_ALARM

    TRPPTRC1_CL_LKOUT

    TRPPTRC2_CL_LKOUT

    HZCCRDIF1_ALARM

    RDRE_TRIGGERED

    CCBRBRF1_TRBU

    CCBRBRF1_TRRET

    SELGAPC1_OUT_6

    HZCCRDIF3_ALARM

    HZCCRDIF2_ALARM

    External Trip

    GUID-11D24650-BED9-487F-B267-2290293D9541 V1 EN

    Figure 46: OSWGAPC15

    Section 3 1MRS757455 AREB611 standard configuration

    46 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    53/72

    Alarm 6 TPGAPC7_IN2

    SELGAPC4_IN_18

    OSWGAPC16

    IN_1

    IN_2

    IN_3

    IN_4

    IN_5

    IN_6

    IN_7

    IN_8

    IN_9

    IN_10

    IN_11

    OUT

    TCSSCBR1_ALARM

    TCSSCBR2_ALARM

    TRPPTRC1_CL_LKOUT

    TRPPTRC2_CL_LKOUT

    HZCCRDIF1_ALARM

    RDRE_TRIGGERED

    CCBRBRF1_TRBU

    CCBRBRF1_TRRET

    SELGAPC1_OUT_6

    HZCCRDIF3_ALARM

    HZCCRDIF2_ALARM

    External Trip

    GUID-FD9EDBEE-F36B-4128-8D8C-3BFCB7E6967F V1 EN

    Figure 47: OSWGAPC16

    3.5.4.4 GOOSEIn the configuration, there are 20 GOOSERCV_BIN functions. Each

    GOOSERVC_BIN function can be connected to one received binary GOOSEsignal. The signal connection can be configured in PCM600.

    GOOSERCV_BIN instances 0 and 1 are used for blocking protection

    functions. Signals from these two GOOSERCV_BINs are connected to

    ISWGAPC9. ISWGAPC9 is used to configure which protection function block

    is blocked.

    GOOSERCV_BIN instances 2 and 3 are used for tripping from GOOSE.

    Signals from these two GOOSERCV_BINs are connected to TRPPTRC1 and

    TRPPTRC2 trip.

    GOOSERCV_BIN instances 4 to 19 are used for blocking the circuit breaker

    operation. Signals from these 16 GOOSERCV_BINs are connected to

    ISWGAPC10. ISWGAPC10 is used to configure the GOOSE input signal to

    block the circuit breaker open or close operation.

    1MRS757455 A Section 3REB611 standard configuration

    REB611 47Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    54/72

    GOOSERCV_BIN:1

    GOOSERCV_BIN:0

    OR ISWGAPC9GOOSE Blcoking

    GOOSERCV_BIN:3

    GOOSERCV_BIN:2

    OR

    GOOSE

    External Trip

    GOOSERCV_BIN:5

    GOOSERCV_BIN:4

    GOOSERCV_BIN:19

    OR ISWGAPC10GOOSE Block CB

    HIPDIF1_BLOCK

    HIPDIF2_BLOCK

    HIPDIF3_BLOCK

    EFLPTOC1_BLOCK

    EFHPTOC1_BLOCK

    HZCCRDIF1_BLOCK

    HZCCRDIF2_BLOCK

    HZCCRDIF3_BLOCK

    CBXCBR1_BLK_CLOSE

    CBXCBR1_BLK_OPEN

    TRPPTRC1_OPERATE

    TRPPTRC2_OPERATE

    GUID-F0B9A987-3F7E-4180-BA29-99A3F602B38E V1 EN

    Figure 48: GOOSE overview

    ISWGAPC9ISWGAPC9 is used to configure which protection functions can be blocked by thereceived GOOSE signals. ISWGAPC9 inputs are received GOOSE signals from

    GOOSERCV_BIN:0 and GOOSERCV_BIN:1. The outputs are connected to the

    block inputs of the protection functions.

    GOOSE Blocking

    ISWGAPC9

    IN

    OUT_1

    OUT_2

    OUT_3

    OUT_4

    OUT_5

    OUT_6

    OUT_7

    OUT_8

    HIPDIF1_BLOCK

    HIPDIF2_BLOCK

    HIPDIF3_BLOCK

    EFLPTOC1_BLOCK

    EFHPTOC1_BLOCK

    HZCCRDIF1_BLOCK

    HZCCRDIF2_BLOCK

    HZCCRDIF3_BLOCK

    GOOSERCV_BIN:0_OUT

    GOOSERCV_BIN:1_OUT

    GUID-C0121EA1-DD3D-428C-BEB9-2B7613F1DC46 V1 EN

    Figure 49: ISWGAPC9

    Section 3 1MRS757455 AREB611 standard configuration

    48 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    55/72

    ISWGAPC10ISWGAPC10 is used to block the circuit breaker operation from the received

    GOOSE signals. ISWGAPC10 inputs are received GOOSE signals from

    GOOSERCV_BIN:4 to GOOSERCV_BIN:19. The outputs are connected to block

    the circuit breaker close and open operation.

    ISWGAPC10

    INOUT_1

    OUT_2

    CBXCBR1_BLK_CLOSE

    CBXCBR1_BLK_OPEN

    GOOSERCV_BIN:4_OUT

    GOOSERCV_BIN:5_OUT

    GOOSERCV_BIN:6_OUT

    ...

    GOOSERCV_BIN:19_OUT

    GOOSE Blocking CB

    GUID-8A11DD7B-6921-48B4-8AA6-5077E822E3BD V1 EN

    Figure 50: ISWGAPC10

    1MRS757455 A Section 3REB611 standard configuration

    REB611 49Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    56/72

    50

  • 8/12/2019 Busbar Diffrential Protection REB611

    57/72

    Section 4 Requirements for measurementtransformers

    4.1 Current transformers4.1.1 Current transformer requirements for differential protection

    The sensitivity and the reliability of the protection depends on the characteristics of

    the current transformers. The CTs must have an identical transformation ratio. It is

    recommended that all the CTs have an identical constructions, that is, they have an

    equal burden and characteristics and are of the same type, preferably from the same

    manufacturing batch. If the CT characteristics and burden values are not equal,

    calculations for each branch in the scheme should be performed separately and the

    worst-case results should be used. In Figure 51, the CT winding resistance and the

    burden of the branches are not equal, and hence, the maximum burden equal to 3.2

    should be used for calculating the stabilized voltage.

    1MRS757455 A Section 4Requirements for measurement transformers

    REB611 51Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    58/72

    GUID-125D0534-32F1-4E09-8A34-CBF36D547735 V1 EN

    Figure 51: High-impedance busbar differential protection with different CT

    burden value on each feeder

    First, the stabilizing voltage, that is, the voltage appearing across the measuring

    branch during the out-of-zone fault, is calculated assuming that one of the CTs

    connected in parallel is fully saturated. The stabilizing voltage can be calculated

    using the formula:

    U I

    nR Rs

    kin m= +

    max ( )

    GUID-6A4C58E7-3D26-40C9-A070-0D99BA209B1A V1 EN (Equation 1)

    Ikmax the highest through-fault current in primary amps. The highest earth-fault or short circuit current

    during the out-of-zone fault.

    n the turns ratio of the CT

    Rin the secondary winding resistance of the CT in ohms

    Rm the resistance (maximum of Rin+ Rm) of the CT secondary circuit in ohms

    Section 4 1MRS757455 ARequirements for measurement transformers

    52 REB611Application Manual

  • 8/12/2019 Busbar Diffrential Protection REB611

    59/72

    The current transformers must be able to