  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    1/90

    Cabinet Interfaces and External

    Cables of MGW and RNC

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 1 (90)

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    2/90

    The information in this document is subject to change without notice and describes only theproduct defined in the introduction of this documentation. This document is not an officialcustomer document and Nokia Siemens Networks does not take responsibility for any errors oromissions in this document. This document is intended for the use of Nokia Siemens Networkscustomers only for the purposes of the agreement under which the document is submitted. Nopart of this documentation may be used, reproduced, modified or transmitted in any form ormeans without the prior written permission of Nokia Siemens Networks. The documentation hasbeen prepared to be used by professional and properly trained personnel, and the customerassumes full responsibility when using it. Nokia Siemens Networks welcomes customercomments as part of the process of continuous development and improvement of thedocumentation.

    The information or statements given in this documentation concerning the suitability, capacity orperformance of the mentioned hardware or software products are given as is and all liabilityarising in connection with such hardware or software products shall be defined conclusively andfinally in a separate agreement between Nokia Siemens Networks and the customer.

    IN NO EVENT WILL Nokia Siemens Networks BE LIABLE FOR ERRORS IN THISDOCUMENTATION OR FOR ANY DAMAGES, INCLUDING BUT NOT LIMITED TO SPECIAL,DIRECT, INDIRECT, INCIDENTAL OR CONSEQUENTIAL OR ANY LOSSES SUCH AS BUTNOT LIMITED TO LOSS OF PROFIT, REVENUE, BUSINESS INTERRUPTION, BUSINESSOPPORTUNITY OR DATA, that might arise from the use of this document or the information in it.

    THE CONTENTS OF THIS DOCUMENT ARE PROVIDED "AS IS". EXCEPT AS REQUIREDBY APPLICABLE MANDATORY LAW, NO WARRANTIES OF ANY KIND, EITHER EXPRESSOR IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OFMERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE AND NON-INFRINGEMENT,ARE MADE IN RELATION TO THE ACCURACY, RELIABILITY OR CONTENTS OF THISDOCUMENT. NOKIA SIEMENS NETWORKS RESERVES THE RIGHT TO REVISE THISDOCUMENT OR WITHDRAW IT AT ANY TIME WITHOUT PRIOR NOTICE.

    This document and the product it describes are considered protected by copyrights and otherintellectual property rights according to the applicable laws.

    The wave logo is a trademark of Nokia Siemens Networks Oy. Nokia is a registered trademark ofNokia Corporation. Siemens is a registered trademark of Siemens AG.

    Other product names mentioned in this document may be trademarks of their respective owners,and they are mentioned for identification purposes only.

    Copyright Nokia Siemens Networks 2008. All rights reserved.

    2 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    3/90

    Contents

    Contents 3

    List of tables 5

    List of figures 7

    Summary of changes 9

    1 Cabinet interfaces and cabling overview 131.1 Power supply interfaces 151.2 Interfaces from the front of the plug-in units 16

    1.3 Interfaces from the back interface units 171.4 Interfaces from the cabling cabinet panels 201.5 Network Management Unit (NEMU) and service terminal interfaces 23

    2 Network interfaces 252.1 PDH/TDM connector panels for E1 interfaces 252.1.1 CPETS-G, CPETS-E and CPETS 272.1.2 CPETC-E and CPETC-B 292.1.3 BIE1T-A, BIE1T and BIE1C 312.1.4 E1T48-A and E1C48-A 312.2 STM-1/OC-3 interfaces 322.2.1 Front panels of the NP8S1/-A/-B, NI4S1-B, IW1S1A and IW1S1 plug-in

    units 322.2.2 Connector panel CPLC36 352.2.3 Connector panel CPRLC-B 362.3 LAN/Ethernet interfaces 372.3.1 Front panel of the NP2GE/-A plug-in unit 382.3.2 Front panel of the IPFGE plug-in unit 402.3.3 Front panels of the ESA24 and ESA12 plug-in units 422.3.4 Connector panel CPLAN-A 43

    3 Maintenance interfaces 453.1 NEMU-specific maintenance interfaces 453.1.1 VDU (VGA) interface pinout 463.1.2 USB interface pinout 463.1.3 Keyboard and mouse pinout 473.1.4 SCSI interface pinout 473.1.5 LAN interface pinout 483.2 Service terminal interface 49

    4 Connector panels for external alarm and synchronisationinterfaces 51

    4.1 CPAL/-A and CPSAL/-B for alarm interfaces 514.2 CPSY-A, CPSY-B, CPSY and CPSAL/-B for synchronisation

    interfaces 554.2.1 External inputs and outputs 57

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 3 (90)

    Contents

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    4/90

    5 Requirement specification for external cables 595.1 E1 and T1 balanced (symmetrical) PCM 595.2 E1 unbalanced (coaxial) cables 625.2.1 E1 unbalanced (coaxial) cables with the CPETC-E panel 625.2.2 E1 unbalanced (coaxial) cables with the BIE1C panels 645.2.3 E1 unbalanced (coaxial) cables with the E1C48-A or CPETC-B panel 655.3 Alarm output to EXAU/-A 675.4 Alarm input cable 715.5 Voltage-controlled alarm input 745.6 Current-controlled alarm input 775.7 Asymmetrical external synchronisation 795.8 Symmetrical external synchronisation 805.9 10Base-T/100Base-TX 835.10 1000Base-T 84

    5.11 Optical STM-1 865.12 1000Base-LX (optical) 875.13 Reference standards and directions 89

    4 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    5/90

    List of tables

    Table 1. Interfaces at the NP2GE/-A plug-in unit 39

    Table 2. Interfaces at the IPFGE plug-in unit 41

    Table 3. Interfaces at the ESA24/ESA12 units 42

    Table 4. Interfaces on the NEMU units 45

    Table 5. SVGA interface pinout (D15) 46

    Table 6. USB interface pinout (4 pins) 46

    Table 7. Keyboard and mouse pinout (6 pins) 47

    Table 8. SCSI interface pinout (D68) 47

    Table 9. LAN/Ethernet interface pinouts (RJ-45) for CPU, AL2S, CDSP and ESA24/ESA12 plug-in units 48

    Table 10. Service terminal interface pinout (RJ-45) 49

    Table 11. Voltage-controlled alarm inputs 1 (D37) 52

    Table 12. Voltage-controlled alarm inputs 2 (D37) 53

    Table 13. Current-controlled alarm inputs (D25) 53

    Table 14. Alarm outputs to the External Alarm Unit (EXAU/-A) (D25) 54

    Table 15. Alarm outputs (D37) 55

    Table 16. External synchronisation inputs and outputs 57

    Table 17. Synchronisation interface pinout (RJ-45) 57

    Table 18. Synchronisation (OUT 2M) interface pinout (RJ-45) 58

    Table 19. Cable CNIA E1 (120) component codes 60

    Table 20. Cable CNIS T1 (100 ) component codes 60

    Table 21. Cable CNIB (120) component codes 60

    Table 22. RJ-45 connector pinouts (CNIA/CNIS) 60

    Table 23. RJ-45 connector pinouts (CNIB) 61

    Table 24. Component codes for the unbalanced (coaxial) CPRD cable 63

    Table 25. D37 connector pinouts 64

    Table 26. Component codes for unbalanced (coaxial) cable 65

    Table 27. Component codes for unbalanced (coaxial) cable 66

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 5 (90)

    List of tables

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    6/90

    Table 28. Cable CNDC (version A01) component codes 68

    Table 29. Cable CNDC (version A02) component codes 68

    Table 30. Connector pinouts for a cable from CPSAL/-B to EXAU/-A or EXAU-A 1 toEXAU-A 2 with a direct cable 69

    Table 31. Connector pinouts for a cable from EXAU-A 1 to EXAU-A 2 with acrossover cable 70

    Table 32. Component codes for alarm output cable 72

    Table 33. Connection pinouts for voltage-controlled alarm input 72

    Table 34. Component codes for voltage-controlled alarm input cable 75

    Table 35. Connection diagram for voltage-controlled alarm input 75

    Table 36. Component codes for cable CNDC 77

    Table 37. Connection diagram for current-controlled alarm input 78

    Table 38. Component codes for asymmetrical external synchronisation cable 80

    Table 39. Cable CNIA E1 component codes (120, receive and transmit signalsconnected) 81

    Table 40. 64K / 2M / 1.5M symmetrical synchronisation input connector pinouts 81

    Table 41. 2M / 1.5M symmetrical synchronisation output connector pinouts 81Table 42. Component codes for CNIX (cross-connected) or CNI (straight) cable 83

    Table 43. Cross-connected cable 83

    Table 44. Connector pinouts 85

    Table 45. Cable types for single-mode optical cables 87

    Table 46. Cable types for single-mode optical cables 89

    6 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    7/90

    List of figures

    Figure 1. External interfaces of the MGW 14

    Figure 2. External interfaces of the RNC 15

    Figure 3. Interfaces from the front of the plug-in units of the MGW and RNC (IPFGEand IW1S1/A used in MGW only) 17

    Figure 4. Interfaces from the back interface units of the equipment cabinet: CPSY-A(clock TSS3 0), CPSY-B (clock TSS3 1) and CPAL-A 18

    Figure 5. Interfaces from the back interface units of the equipment cabinet: CPRLC-B, BIE1C, BIE1T, and BIE1T-A 20

    Figure 6. Cabling cabinet panels 22

    Figure 7. Network interfaces on the NEMU plug-in units MCPC2/-A and MCP18/-B 23

    Figure 8. Back interface unit and connector panel equipping options 26

    Figure 9. Connector panel CPETS-G for the cabling cabinet 27

    Figure 10. Connector panel CPETS-E for the cabling cabinet 28

    Figure 11. Connector panel CPETS for the cabling cabinet 29

    Figure 12. Connector panel CPETC-E for the cabling cabinet 30

    Figure 13. Connector panel CPETC-B for the cabling cabinet 31

    Figure 14. E1T48-A (upper) and E1C48-A (lower) connector panels for the IC186equipment cabinet 32

    Figure 15. Front panel of the NP8S1 plug-in unit 33

    Figure 16. Front panel of the NI4S1-B plug-in unit 34

    Figure 17. Front panel of the IW1S1/A plug-in unit 35

    Figure 18. Connector panel CPLC36 in the cabling cabinet 36

    Figure 19. Equipping the connector panel CPRLC-B 37

    Figure 20. Front panel of the NP2GE plug-in unit 39

    Figure 21. Front panel of the IPFGE plug-in unit 41

    Figure 22. Front panel of the ESA24 plug-in unit 42

    Figure 23. Connector panel CPLAN-A 43

    Figure 24. Connector panels CPAL/-A and CPSAL/-B for alarm interfaces 52

    Figure 25. Connector panels CPSY-A, CPSY-B, CPSY and CPSAL/-B for alarm and

    synchronisation interfaces 56

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 7 (90)

    List of figures

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    8/90

    Figure 26. Example of CNIA cable assembly 61

    Figure 27. Connecting a PCM E1 cable to a connector, CNIS (example) 62

    Figure 28. D37 connector body with unbalanced (coaxial) contacts (1=pin,2=ring) 63

    Figure 29. Example of E1 multicoaxial cable with SMB connectors 65

    Figure 30. Example of E1 multicoaxial cable with BT43 connectors 67

    Figure 31. Example of alarm cable to the EXAU/-A 71

    Figure 32. Example of alarm output cable 74

    Figure 33. Example of voltage-controlled alarm input cable 76

    Figure 34. Example of current-controlled alarm input cable 79

    Figure 35. Example of asymmetrical external synchronisation cable 80

    Figure 36. Example of symmetrical external synchronisation cable 82

    Figure 37. Example of LAN cable 84

    Figure 38. Example of LAN cable 85

    Figure 39. Example of a single-mode optical cable 87

    Figure 40. Example of a single-mode optical cable 89

    8 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    9/90

    Summary of changes

    Changes between document issues are cumulative. Therefore, the latest

    document issue contains all changes made to previous issues.

    Changes for issue 9-4

    Added new plug-in unit variants:

    . MX1G6-A, ATM multiplexer 1.6 Gbits/s variant A. New variant for

    MXU.

    . NP2GE-A, network interface and processing 2X1000Base-T/LX

    variant A

    . NP8S1-A/-B, network interface and processing 8xSTM-1 variant A

    or B.

    Some corrections and editorial changes.

    Changes for issue 9-3

    Some editorial changes and minor corrections.

    Changes for issue 9-2

    Two new panels to ETSI configuration introduced:

    . BIE1T-A back interface panel

    . CPETS-G connector panel

    A new external site cable CNIB for the new panel types BIE1T-A and

    CPETS-G introduced.

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 9 (90)

    Summary of changes

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    10/90

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    11/90

    Five new connector panel types introduced: CPAL-A, CPSY-A, and CPSY-

    B for the rear of the cabinet, as well as the PDH/TDM connector panelsCPETS-E, and CPETC-E added.

    Two new cables introduced: the external CPRD cable and the internal

    CPSM cable.

    Changes for issue 7-3

    Added information on the RoHS-compliant External Alarm Unit EXAU-A.SectionAlarm output to EXAU/-A updated.

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 11 (90)

    Summary of changes

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    12/90

    12 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    13/90

    1 Cabinet interfaces and cabling overviewCabinet Interfaces and External Cables of MGW and RNCcontains

    information on the network interfaces and cables for IPA2800 networkelements, namely Multimedia Gateway (MGW) and Radio Network

    Controller (RNC). This document applies to all releases of both MGW and

    RNC.

    The external cables of the MGW and RNC connect the network element to

    its environment, the mobile network it is used in. The MGW and RNC

    network elements have the following interfaces to the environment:

    . Power supply interfaces

    . PDH/E1 T1 interfaces

    . SDH/STM-1 OC-3 interfaces

    . External synchronisation and alarm inputs and outputs

    . LAN/Ethernet interfaces

    . Service terminal interfaces from various plug-in units (for temporary

    service operations; not covered by this manual)

    . Interfaces of the Network Management Unit (NEMU) to accessoriesand peripherals: mouse, keyboard, and VDU

    The external cables connect to the front panels of the plug-in units, to theback interface units at the rear of the equipment cabinets, or to the

    connector panels in the cabling cabinet.

    For more information, see the Cable Lists, Equipment Lists, Installation

    Site Requirements for MGW and RNCand Engineering Descriptions.

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 13 (90)

    Cabinet interfaces and cabling overview

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    14/90

    MGW

    Figure 1. External interfaces of the MGW

    External timing

    - 2.048 MBIT/s- 2.048 MHz- 64 kHz +8 kHz- 1.544 MHz

    Service terminal RS232

    -48V, 120A

    NEMU- Ethernet 10/100 Mbit/s- SCSI

    - USB- serial ports- keyboard, mouse- monitor (SVGA)

    DN02179402

    External alarms- general current/voltage outputs- voltage controlled inputs- current controlled inputs

    MGW

    Network interfaces Operating interfaces

    EXAU, EXAU-A- alarm indicator lamp panel

    Ethernet10/100 Mbit/s

    - STM-1/ OC-3- E1 /T1/JT1 (IMA)

    Iu

    ATM Core

    ATM

    A-interfacePSTN

    IWF

    TDM

    - E1/T1/JT1

    - STM-1/OC-3

    H.248 controlIP Core /userplaneSIGTRAN

    IP

    - Ethernet

    AterTDM

    - E1/T1/JT1- STM-1/OC-3

    14 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    15/90

    RNC

    Figure 2. External interfaces of the RNC

    1.1 Power supply interfaces

    The MGW and RNC operate on a -48V DC supply system. The voltage

    limits are -40V DC to -57V DC. Each equipment cabinet has two mutually

    redundant power entry connectors. Power feed cables can be routed

    through from the top or bottom of the cabinet.

    When using the CPD120-A cabinet power distributor, the maximum

    current is 120A per cabinet, the maximum thickness of the power supply

    cable is 70 mm2, and the maximum voltage drop is 1.5V.

    SDH

    STM-1

    PDHE1/T1/JT1

    ATM

    ATM

    Network interfaces

    DN01128587

    RNC

    Operating interfaces

    -48V, 120A

    External alarms:

    general current/voltage outputsvoltage-controlled inputscurrent-controlled inputs

    EXAU, EXAU-A:alarm indicator lamp panel

    NEMU:printer, monitor, keyboard, mouse

    Ethernet:

    10/100 Mbit/s

    Service terminal RS232

    External timing

    2.048 Mbit/s or2.048 MHz64 kHz + 8 kHz1.544 MHz

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 15 (90)

    Cabinet interfaces and cabling overview

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    16/90

    When using the CPD80-B/-A cabinet power distributor, the maximum

    current is 80A per cabinet, the maximum thickness of the power supplycable is 50 mm2, and the maximum voltage drop is 1.5V.

    1.2 Interfaces from the front of the plug-in units

    The front panels of the plug-in units house several connectors:

    . STM-1/OC-3 interfaces from NP8S1/-A/-B (NPS1P/NPS1), NI4S1-B

    (NIS1P/NIS1) and IW1S1/A (IW1SE, IWS1T; used in MGW only)

    .

    Optical LAN 1000 BASE-LX (NPGEP/NPGE), IPGOP), electricalLAN 1000 BASE-T (NPGEP/NPGE), IPGEP), and electrical LAN

    100 BASE-T (IPFEP) interfaces from IPFGE (IPNIUP used in MGW

    only)

    . LAN 100 BASE-T interface(s) from the ESA24 plug-in unit (two front

    panel connectors for external use)

    . LAN 100 BASE-T interface(s) from the ESA12 plug-in unit (twoupper front panel connectors for external use)

    16 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    17/90

    Figure 3. Interfaces from the front of the plug-in units of the MGW and RNC

    (IPFGE and IW1S1/A used in MGW only)

    1.3 Interfaces from the back interface units

    It is possible to route cables to the environment directly from the back

    interface units of the equipment cabinet, when the network element does

    not include a cabling cabinet.

    LAN

    Serviceterminal

    ESA24

    100BASE-T

    LAN(not used)

    Serviceterminal

    IPFGE

    1000BASE-T

    1000BASE-LX

    STM-1

    Serviceterminal

    NI4S1-B

    DN02179683

    LED

    LAN (not used)

    Service terminal

    STM-1

    STM-1 Redundant

    IW1S1/A

    NP2GE

    Service terminal

    1000BASE-LX

    1000BASE-T

    NP8S1

    Service terminal

    STM-1

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 17 (90)

    Cabinet interfaces and cabling overview

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    18/90

    . CPSY-A and CPSY-B

    CPSY-A is used for synchronisation of clock 0 (TSS3 0) and CPSY-B

    is used for synchronisation of clock 1 (TSS3 1). CPSY-A and CPSY-

    B have two BNC connectors and three RJ-45 connectors for external

    synchronisation inputs and outputs, and they are equipped in the

    same network element. CPSY-A has a RJ-45 connector for service

    terminal for NEMU use.

    . CPAL-A

    CPAL-A is a connector panel used for alarms. It has a horizontal

    layout and one D25 connector for EXAU/-A control, one D37

    connector for general current or voltage outputs, two D37connectors for voltage-controlled inputs, and one D25 connector for

    current-controlled alarm inputs.

    Figure 4. Interfaces from the back interface units of the equipment cabinet:

    CPSY-A (clock TSS3 0), CPSY-B (clock TSS3 1) and CPAL-A

    IN

    64kIN

    2MOUT2M

    OUT 2M IN 2M

    SYM ASYMEXT2

    IN

    64kIN

    2MOUT2M

    OUT 2M IN 2M

    SYM ASYMEXT1

    CPSY-A

    CPSY-B

    CPAL-A

    TOEXAU

    ETH

    ALARM OUTPUTS

    CURRENT

    CONTROLLEDALARM INPUT

    VOLTAGE CONTROLLED ALARM INPUTS

    1

    2

    DN05160581

    18 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    19/90

    . CPSAL-B (in RNC only)

    A connector panel type for external synchronisation and HW alarm

    interfaces.

    . CPRLC-B (in RNC only)

    A connector panel for STM-1/OC-3 interfaces with 16 pieces of LC

    connectors.

    . BIE1T

    A back interface unit for E1/T1 balanced interfaces with 16 pieces of

    RJ-45 connectors.

    . BIE1T-A (in MGW only)

    A back interface unit for E1 balanced interfaces with 8 pieces of RJ-

    45 connectors, two E1 interfaces via each RJ-45 connector.

    . BIE1C

    A back interface unit for E1 unbalanced interfaces with 32 pieces of

    SMB connectors.

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 19 (90)

    Cabinet interfaces and cabling overview

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    20/90

    Figure 5. Interfaces from the back interface units of the equipment cabinet:

    CPRLC-B, BIE1C, BIE1T, and BIE1T-A

    1.4 Interfaces from the cabling cabinet panels

    In configurations that include a cabling cabinet, the connector panels for

    the PDH/TDM interfaces are located on the panels of the cabling cabinet.

    The numbers of the PDH/TDM lines and the plug-in unit connectors they

    connect to are listed in Cable Lists for MGW and Cable Lists for RNC.

    The cabling cabinet can be used for routing cables from the network

    element to the environment. Cables to the environment are routed through

    from the front of the cabling cabinet.

    BIE1T-A

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    1213

    14

    15

    CPRLC-B BIE1C BIE1T

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    0

    1

    2

    3

    4

    5

    6

    78

    9

    10

    11

    12

    13

    14

    15

    -

    -

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    DN70461848

    20 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    21/90

    The cabling cabinet can be equipped with several panel types:

    . CPBP

    A blank panel for empty panel positions.

    . CPLC36

    A connector panel for STM-1/OC-3 and 1000 BASE-LX interfaces

    with 36 pieces of LC connectors.

    . CPSY

    A connector panel for synchronisation with four BNC connectors and

    six RJ-45 connectors for external synchronisation inputs andoutputs.

    . CPAL

    A connector panel for alarms with a vertical layout and one D25

    connector for EXAU/-A control, one D37 connector for generalcurrent/voltage outputs, two D37 connectors for voltage-controlled

    inputs, and one D25 connector for current-controlled alarm inputs.

    . CPLAN-A

    A connector panel for Local Area Network interfaces (10/100 BASE-

    T/TX and 1000 BASE-T), 32 pieces of RJ-45 connectors.

    . CPETS-G (in MGW only)

    A connector panel with 24 pieces of RJ-45 connectors. The panel

    supports forty-eight E1 interfaces, two interfaces via each RJ-45

    connector.

    . CPETS-E

    A connector panel for 48 pieces of E1/T1 balanced (symmetrical)interfaces (twelve connector modules, each with four RJ-45

    connectors).

    . CPETS

    A connector panel for 32 pieces of E1/T1 balanced interfaces with

    32 pieces of RJ-45 connectors.

    . CPETC-E

    A connector panel for 48 pieces of E1 unbalanced interfaces, that is,

    twelve multicoaxial D-sub connectors, each with eight coaxial

    contacts.

    . CPETC-B

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 21 (90)

    Cabinet interfaces and cabling overview

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    22/90

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    23/90

    1.5 Network Management Unit (NEMU) and service

    terminal interfaces

    . VDU (SVGA/VGA) interface

    VDU monitor connected to the front panel of the MCPC18/-B or

    MCPC2/-A plug-in unit; Windows 2000 compatible VGA connector

    interface.

    . USB interface

    The Windows 2000 compatible USB interface accepts the printer,

    mouse, or keyboard.

    . Keyboard and mouse

    Keyboard connected to the front panel of the NEMU plug-in unit

    MCPC2/-A; Windows 2000 compatible keyboard connector. Mouse

    connected to the front panel of the NEMU plug-in unit MCPC2/-A;

    Windows 2000 compatible (serial) mouse connector.

    . SCSI interface

    External SCSI device (for instance, HD or MOD) connected to the

    front panel of NEMU MCPC2/-A; external VDHCI connector

    interface.

    Figure 7. Network interfaces on the NEMU plug-in units MCPC2/-A and

    MCP18/-B

    DN05160418

    NEMUMCPC2/-A

    LAN

    VDU

    USB

    MOUSE/KEYBOARD

    SCSI

    (EXTERNAL)

    NEMUMCP18/-B

    SVGA

    USB

    RESETSWITCH

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 23 (90)

    Cabinet interfaces and cabling overview

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    24/90

    24 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    25/90

    2 Network interfaces

    2.1 PDH/TDM connector panels for E1 interfaces

    There are five types of connector panels for the cabling cabinet:

    . CPETS-G for E1 balanced PDH interfaces, ETSI

    . CPETS-E for E1/T1 balanced PDH lines, ANSI

    . CPETS for E1/T1 balanced PDH lines

    . CPETC-E for E1 unbalanced PDH lines

    .

    CPETC-B for E1 unbalanced PDH lines

    There are three types of back interface units for connecting PDH lines:

    . BIE1T-A for E1 balanced PDH interfaces, ETSI

    . BIE1T for E1/T1 balanced PDH interfaces, ANSI

    . BIE1C for E1 unbalanced PDH interfaces, ETSI

    The back interface units BIE1T-A, BIE1T and BIE1C are located at the rear

    of the equipment cabinet, directly behind the NIWU or NIP1 units that they

    serve.

    For information on cabling, see section Requirement specification for

    external cables.

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 25 (90)

    Network interfaces

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    26/90

    Figure 8. Back interface unit and connector panel equipping options

    DN70462765

    Equipping option with only the connector panel for cabling cabinet

    Equipping option withonly the back interface unit

    Equipping option with both connector panel and back interface unit

    26 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    27/90

    2.1.1 CPETS-G, CPETS-E and CPETS

    CPETS-G is a connector panel for the cabling cabinet, for 48 E1 balanced

    interfaces. It consists of 4 connector bodies, each with six RJ-45

    connectors, each of which supports two E1 interfaces. The internal cable

    type connecting the NIWU or NIP1 to CPETS-G is CPSM. The external

    cable for CPETS-G is CNIB.

    Figure 9. Connector panel CPETS-G for the cabling cabinet

    CPETS-E is a connector panel for the cabling cabinet, for 48 pieces of E1/

    T1 balanced interfaces. The panel fitted to the panel plate consists of

    twelve connector bodies, each with four RJ-45 connectors. The internal

    cable type connecting the NIWU or NIP1 to CPETS-E is CPSM. The

    external cable for CPETS-E is CNIA or CNIS.

    DN70453111

    CPETS-G

    00

    01

    0809

    16

    17

    24

    25

    32

    33

    40

    41

    02

    03

    1011

    18

    19

    26

    27

    34

    35

    42

    43

    04

    05

    1213

    20

    21

    28

    29

    36

    37

    44

    45

    06

    07

    14

    15

    22

    23

    30

    31

    38

    39

    46

    47

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 27 (90)

    Network interfaces

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    28/90

    Figure 10. Connector panel CPETS-E for the cabling cabinet

    CPETS is a connector panel for the cabling cabinet, for E1/T1 balanced

    PDH interfaces. It consists of 32 pieces of RJ-45 connectors. The internal

    cable type between BIE1T and CPETS is CPT. The external cable for

    CPETS is CNIA or CNIS.

    00

    DN05160351

    01 02 03 04 05 06 07 08 09 10 11

    12 13 14 15 16 17 18 19 20 21 22 23

    24 25 26 27 28 29 30 31 32 33 34 35

    36 37 38 39 40 41 42 43 44 45 46 47

    CPETS-E

    28 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    29/90

    Figure 11. Connector panel CPETS for the cabling cabinet

    2.1.2 CPETC-E and CPETC-B

    CPETC-E is a connector panel for the cabling cabinet for 48 pieces of E1

    unbalanced interfaces, providing isolation voltage of 500V. The panel fitted

    to the panel plate consists of twelve D-sub connector bodies, each with

    eight coaxial contacts. The internal cable type connecting NIWU or NIP1

    unit to CPETC-E is CPSM. The external cable for CPETC-E is CPRD.

    DN98618022

    00

    08

    16

    24

    01

    09

    17

    25

    02

    10

    18

    26

    03

    11

    19

    27

    04

    12

    20

    28

    05

    13

    21

    29

    06

    14

    22

    30

    07

    15

    23

    31

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 29 (90)

    Network interfaces

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    30/90

    Figure 12. Connector panel CPETC-E for the cabling cabinet

    CPETC-B is a connector panel for the cabling cabinet, for E1 unbalanced

    PDH interfaces. It consists of 64 pieces of BT43 coaxial connectors. The

    internal cable type between BIE1C and CPETC-B (SMB/BT43) is CBTC

    (internal cabling).

    00

    02

    04

    06

    08

    10

    01

    03

    05

    07

    09

    11

    DN05160363 CPETC-E

    RxTx RxTx RxTx RxTx

    00

    78 56 34 12

    01 02 03

    30 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    31/90

    Figure 13. Connector panel CPETC-B for the cabling cabinet

    2.1.3 BIE1T-A, BIE1T and BIE1C

    BIE1T-A is a back interface unit for E1 balanced interfaces with eight RJ-

    45 connectors, two E1 interfaces via each RJ-45 connector.

    BIE1T is a back interface unit for E1/T1 balanced interfaces that consists

    of 16 pieces of RJ-45 connectors for 16 physical PDH lines.

    BIE1C is a back interface unit for E1 unbalanced interfaces, with 32 pieces

    of SMB connectors for 16 physical PDH lines.

    2.1.4 E1T48-A and E1C48-A

    E1T48-A or E1C48-A are connector panels for PDH interfaces at the rear

    of the IC186 equipment cabinet. Connector panel E1T48-A contains 48

    pieces of RJ-45 connectors for 48 physical E1/T1 balanced interfaces to

    the environment. Connector panel E1C48-A consists of 96 pieces of BT43

    coaxial connectors for 48 physical E1 unbalanced interfaces to the

    environment.

    Tx

    Rx

    Tx

    Rx

    Tx

    Rx

    Tx

    Rx

    00

    08

    16

    24

    01

    09

    17

    25

    02

    10

    18

    26

    03

    11

    19

    27

    04

    12

    20

    28

    05

    13

    21

    29

    06

    14

    22

    30

    07

    15

    23

    31

    DN0445768

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 31 (90)

    Network interfaces

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    32/90

    Figure 14. E1T48-A (upper) and E1C48-A (lower) connector panels for the

    IC186 equipment cabinet

    Both E1T48-A and E1C48-A panels can be equipped and in the same

    equipment cabinet at the same time, as long as each panel supports three

    network interface plug-in units that have same type of connector interfaces

    (RJ-45 or BT43). This means that all of the three NIP1 or NIWU units that

    the E1T48-A or E1C48-A panel serves must use the connector type thatthe selected panel type serves.

    The RNAC and RNBC/CAMA and CAMB cabinets have only five panel

    places for the PDH lines. The panels are numbered sequentially from top

    to bottom, starting from number 1. The connectors for the outgoing PDH

    lines on the panels also have numbers that run from left to right and top to

    bottom.

    2.2 STM-1/OC-3 interfaces

    2.2.1 Front panels of the NP8S1/-A/-B, NI4S1-B, IW1S1A and IW1S1 plug-in units

    The NP8S1/-A/-B (NPS1P/NPS1), NI4S1-B (NIS1P/NIS1) and IW1S1A/

    IW1S1 (IWS1E/T) plug-in units have ITU-T G.957 S-1.1 STM-1/OC-3

    optical interfaces on the front panel. The transmission interface uses

    single-mode fibre. The connector type is fibre optic LC duplex. The STM-1/

    DN0136686

    Tx

    Tx

    Rx

    Rx

    32 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    33/90

    OC-3 interfaces are connected either directly from the front panel of the

    plug-in units or via connector panel CPLC36 in the cabling cabinet. In theRNC, it is also possible to route the connections via the CPRLC-B panel at

    the rear of the RNAC.

    Figure 15. Front panel of the NP8S1 plug-in unit

    DN70182603 NP8S1

    1

    2

    3

    4

    5

    6

    7

    8

    STM-1 / STM-4

    Tx

    Rx

    Tx

    Rx

    Tx

    Rx

    Tx

    Rx

    Tx

    Rx

    Tx

    Rx

    Tx

    Rx

    Tx

    Rx

    STM-1

    SERVICE TERMINAL

    INTERFACES:

    BACKPLANE:

    - TIMING & SYNC

    - HMS

    - POWER SUPPLY

    - SFU- CLOCK REFERENCE

    OUTPUT TO TSS3- LAN 1-5

    CLASS 1 LASER PRODUCTIEC/EN 60825-1

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 33 (90)

    Network interfaces

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    34/90

    Figure 16. Front panel of the NI4S1-B plug-in unit

    NI4S1-B DN02179368

    INTERFACES:

    BACKPLANE:

    - TIMING & SYNC- HMS- POWER SUPPLY- SFU

    - CLOCKREFERENCEOUTPUT TO TSS3

    LAN (NOT USED)

    STM-1

    SERVICE TERMINAL

    34 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    35/90

    Figure 17. Front panel of the IW1S1/A plug-in unit

    2.2.2 Connector panel CPLC36

    CPLC36 is a connector panel in the cabling cabinet for optical interfaces,

    such as STM-1/OC-3. It has 36 pieces of duplex LC connectors. The

    external and internal cable type used is CLCS or CSMA.

    DN0490465

    LAN (NOT USED)

    SERVICE TERMINAL

    BACK PLANE:

    - TIMING & SYNC- HMS

    - POWER SUPPLY- MXU

    INTERFACES:

    STM-1

    STM-1 REDUNDANT

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 35 (90)

    Network interfaces

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    36/90

    Figure 18. Connector panel CPLC36 in the cabling cabinet

    2.2.3 Connector panel CPRLC-B

    CPRLC-B is a connector panel in the RNC for STM-1/OC-3 interfaces. It

    has 16 pieces of LC connectors. CPRLC-B is equipped in the SRBI at the

    rear of the cabinet, as shown in the figure below.

    06 07 08 09 10 11

    12 13 14 15 16 17

    18 19 20 21 22 23

    24 25 26 27 28 29

    30 31 32 33 34 35

    00 01 02 03 0504

    CLASS

    1LASER

    PRODUCT

    EN

    60825-11994

    DN0445732

    Opticalproduct

    LC connector

    36 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    37/90

    Figure 19. Equipping the connector panel CPRLC-B

    2.3 LAN/Ethernet interfaces

    The local area network (LAN) interface using RJ-45 connectors is located

    on the front panels of the plug-in units of the MGW or RNC and the

    connector panel of the cabling cabinet.

    . Two optical LAN 1000 BASE-LX and two electrical LAN 1000 BASE-

    T interfaces from NP2GE (NPGEP/NPGE)

    . One optical LAN 1000 BASE-LX (IPGOP), one electrical LAN 1000

    BASE-T (IPGEP), and eight electrical LAN 100 BASE-T (IPFEP)

    interfaces from IPFGE (IPNIUP, in MGW only)

    . Twenty-four interfaces provided by the ESA24 plug-in unit

    . Twelve interfaces provided by the ESA12 plug-in unit

    SRBI-B

    -

    -

    8 0

    9 1

    10 2

    11 3

    12 4

    13 5

    14 6

    15 7

    CPRLC-B

    DN03463441

    08

    715

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 37 (90)

    Network interfaces

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    38/90

    2.3.1 Front panel of the NP2GE/-A plug-in unit

    The NP2GE/-A plug-in unit is a network interface unit providing two optical

    or electrical gigabit Ethernet interfaces. The connector type for

    1000BASE-LX is LC, whereas 1000BASE-T uses the RJ-45 connector.

    The optical 1000BASE-LX interfaces are connected either directly from the

    front panel of the plug-in units or via connector panel CPLC36 in the

    cabling cabinet. The electrical 1000BASE-T interfaces are connected

    either directly from the front panel of the plug-in units or via connector

    panel CPLAN-A in the cabling cabinet.

    Specifications for optical 1000-Base-LX interface:

    . Optical output power: min -9dBm, max -3dBm

    . Minimum input optical power: min -20dBm

    . Maximum input optical power: min -3dBm

    38 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    39/90

    Figure 20. Front panel of the NP2GE plug-in unit

    Table 1. Interfaces at the NP2GE/-A plug-in unit

    FU Front panel connector Use

    NPGE / NPGEP F (1000_BASE-T) 1000 BASE-T

    NPGE / NPGEP F (1000_BASE-LX) 1000 BASE-LX

    DN70182857 NP2GE

    0

    1

    SERVICETERMINAL

    CLASS 1 LASER PRODUCTIEC/EN 60825-1

    1000BASE-T

    1000BASE-LX

    1000BASE-T

    1000BASE-LX0

    1

    Tx

    Rx

    Tx

    Rx

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 39 (90)

    Network interfaces

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    40/90

    2.3.2 Front panel of the IPFGE plug-in unit

    The IPFGE plug-in unit is a network interface unit providing eight electrical

    Fast Ethernet (100 Mbps) interfaces, one optical and one electrical gigabit

    Ethernet. Only one of the gigabit interfaces can be used at a time (8 x fast

    Ethernet, 1 x gigabit optical, or 1 x gigabit electrical). The connector type

    for 1000BASE-LX is LC, whereas 1000BASE-T uses the RJ-45 connector.

    Specifications for optical 1000-Base-LX interface:

    . Optical output power: min -9dBm, max -3dBm

    . Minimum input optical power: min -20dBm

    . Maximum input optical power: min -3dBm

    40 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    41/90

    Figure 21. Front panel of the IPFGE plug-in unit

    Table 2. Interfaces at the IPFGE plug-in unit

    FU Front panel connector Use

    IPGO / IPGOP 0 F (1000_BASE-LX) 1000 BASE-LX

    IPGE / IPGEP 0 F (1000_BASE-T) 1000 BASE-T

    IPFE / IPFEP 0 F 0-7 10/100 BASE-T/TX

    IPFGE

    LAN(Not used)

    100BASE-TX

    1000BASE-T

    LED

    1000BASE-LX/LH

    DN02180131

    SERVICETERMINAL

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 41 (90)

    Network interfaces

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    42/90

    2.3.3 Front panels of the ESA24 and ESA12 plug-in units

    An equipment cabinet is configured with either the ESA24 or ESA12 plug-

    in unit.

    Figure 22. Front panel of the ESA24 plug-in unit

    Table 3. Interfaces at the ESA24/ESA12 units

    FU Connectors and their use

    ESA24

    (NEMU)

    There are two front panel connectors for external use (out of the NE).

    The other 22 LAN interfaces are in the backplane connectors, and they are

    for the internal use of the NE.

    ESA24 DN03451956

    INTERFACES:

    LAN

    BACKPLANE:

    - HMS (NOT USED)- POWER SUPPLY

    - LAN

    SERVICE TERMINAL

    - TIMING & SYNC(NOT USED)

    42 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    43/90

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    44/90

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    45/90

    3 Maintenance interfaces

    3.1 NEMU-specific maintenance interfaces

    Table 4. Interfaces on the NEMU units

    Plug-in unit/interface (connector) Use

    MCP18/-B MCPC2/-A

    ETH0

    (back panel connector)

    ETH0

    (RJ-45)

    For LAN use

    ex to eth SW

    ETH1

    (back panel connector)

    ETH1

    (RJ-45)

    for LAN use

    ex to eth SW

    4 X USB - for bootable device

    for mouse, keyboard

    for printer

    - 1 x USB for printer

    - 1 x PS/2 for keyboard and mouse

    SVGA SVGA for VDU

    - SCSI

    (D68)

    for bootable device

    - RS1

    (back panel connector)

    serial port 1

    - RS2

    (back panel connector)

    serial port 2

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 45 (90)

    Maintenance interfaces

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    46/90

    3.1.1 VDU (VGA) interface pinout

    VDU monitor connected to the front panel of the MCPC2/-A; Windows NT-

    compatible VGA connector interface.

    Table 5. SVGA interface pinout (D15)

    Pin Signal Pin Signal

    1 Red 9 NC

    2 Green 10 GND

    3 Blue 11 NC

    4 NC 12 DDCDAT

    5 GDN 13 H-sync

    6 DACGND 14 V-sync

    7 DACGND 15 DDCCLK

    8 DACGND

    3.1.2 USB interface pinout

    The Windows NT-compatible USB interface accepts a printer, mouse or

    keyboard.

    Table 6. USB interface pinout (4 pins)

    Pin Signal

    Mechanical solder lug Shield ground

    1 +5 V

    2 Data -

    3 Data +

    4 GND

    Mechanical solder lug Shield ground

    46 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    47/90

    3.1.3 Keyboard and mouse pinout

    Keyboard connected to the front panel of (NEMU) MCPC2/-A; Windows

    NT-compatible keyboard connector. Mouse connected to the front panel of

    (NEMU) MCPC2/-A; Windows NT compatible (serial) mouse connector.

    Table 7. Keyboard and mouse pinout (6 pins)

    Pin Signal

    1 Mouse data

    2 Keyboard data

    3 GND

    4 +5 V

    5 Mouse clock

    6 Keyboard clock

    3.1.4 SCSI interface pinout

    External SCSI device (example HD or MOD) connected to the front panelof (NEMU) MCPC2/-A; external VHDCI connector interface.

    Table 8. SCSI interface pinout (D68)

    Pin Signal Pin Signal Pin Signal

    1 +DB (12) 24 +ACK 47 -DB(7)

    2 +DB (13) 25 +RST 48 -DB(P)

    3 +DB (14) 26 +MSG 49 GND

    4 +DB (15) 27 +SEL 50 GND

    5 +DB (P1) 28 +C/D 51 TERMPWR

    6 +DB(0) 29 +REQ 52 TERMPWR

    7 +DB(1) 30 +I/O 53 RESERVED

    8 +DB(2) 31 +DB(8) 54 GND

    9 +DB(3) 32 +DB(9) 55 -ATM

    10 +DB(4) 33 +DB(10) 56 GND

    11 +DB(5) 34 +DB(11) 57 -BSY

    12 +DB(6) 35 -DB(12) 58 -ACK

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 47 (90)

    Maintenance interfaces

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    48/90

    Table 8. SCSI interface pinout (D68) (cont.)

    Pin Signal Pin Signal Pin Signal

    13 +DB(7) 36 -DB(13) 59 -RST

    14 +DB(P) 37 -DB(14) 60 -MSG

    15 GND 38 -DB(15) 61 -SEL

    16 DIFFSENS 39 -DB(P1) 62 -C/D

    17 TERMPWR 40 -DB(0) 63 -REQ

    18 TERMPWR 41 -DB(1) 64 -I/O

    19 RESERVED 42 -DB(2) 65 -DB(8)

    20 GND 43 -DB(3) 66 -DB(9)

    21 +ATN 44 -DB(4) 67 -DB(10)

    22 GND 45 -DB(5) 68 -DB(11)

    23 +BSY 46 -DB(6)

    3.1.5 LAN interface pinout

    Table 9. LAN/Ethernet interface pinouts (RJ-45) for CPU, AL2S, CDSP and

    ESA24/ESA12 plug-in units

    Pin Signal

    1 Transmit + (Tx+)

    2 Transmit - (Tx-)

    3 Receive + (Rx+)

    4

    5

    6 Receive - (Rx-)

    7

    8

    48 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    49/90

    3.2 Service terminal interface

    The RS232 interface using the RJ-45 connector is located on the front

    panel of certain units. The interface is used for logging into and for

    accessing the service terminal.

    . One interface provided by NP2GE/-A, NI16P1A, NP8S1/-A, CDSP,

    NI4S1-B, IW16P1, IW16P1A, IW1S1, IW1S1A, AL2S and SF20H

    plug-in units

    . Two interfaces provided by CPU plug-in units, SF10, MX1G6/-A,

    MX622, and MCPC2/-A

    Table 10. Service terminal interface pinout (RJ-45)

    Pin Signal

    1 DTR Data terminal ready

    2 TxD Transmit data

    3 GND

    4 GND

    5 RxD Receive data

    6 DSR Data set ready

    7 CTS Clear to send

    8 RTS Request to send

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 49 (90)

    Maintenance interfaces

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    50/90

    50 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    51/90

    4 Connector panels for external alarm andsynchronisation interfaces

    Depending on the equipment installed, the external alarm andsynchronisation interfaces are provided by different types of connector

    panels:

    . CPAL-A and CPAL are for external alarm signals and for the external

    alarm unit, EXAU/-A

    . CPSY-A, CPSY-B and CPSY are for synchronisation

    . CPSAL/-B is for both alarms and synchronisation

    CPAL-A, CPSY-A, CPSY-B and CPSAL/-B are back panels of the

    equipment cabinet.

    CPAL and CPSY are equipped in the cabling cabinet.

    4.1 CPAL/-A and CPSAL/-B for alarm interfaces

    Connector panels CPAL/-A and CPSAL/-B for alarms have one D25

    connector for EXAU/-A control, one D37 connector for general current orvoltage outputs, two D37 connectors for voltage-controlled inputs, and one

    D25 connector for current-controlled alarm inputs.

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 51 (90)

    Connector panels for external alarm and synchronisation interfaces

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    52/90

    Figure 24. Connector panels CPAL/-A and CPSAL/-B for alarm interfaces

    Table 11. Voltage-controlled alarm inputs 1 (D37)

    Pin Signal Pin Signal Pin Signal

    1 VAL0 14 GND 27 VAL13

    2 GND 15 VAL7 28 GND

    3 VAL1 16 GND 29 VAL14

    4 GND 17 VAL8 30 GND

    5 VAL2 18 GND 31 VAL15

    CPAL ALARMOUTPUTTO EXAU

    ALARMOUTPUT

    VOLTAGECONTROLLED

    ALARM INPUTS

    CURRENTCONTROLLEDALARM INPUT

    1 2

    DN05160636

    1 2 1 2

    1 23 4 3 4

    SYM SYM

    ASYM ASYMSYM

    IN 2M OUT 2MIN 64k

    ALARMOUTPUT

    TO EXAU

    ALARMOUTPUT

    VOLTAGECONTROLLED

    ALARM INPUTS

    CURRENTCONTROLLED

    ALARM INPUT21

    CPSAL/-B

    CPAL-A

    TOEXAU

    ALARMOUTPUTS

    CURRENTCONTROLLEDALARM INPUT

    VOLTAGE CONTROLLEDALARM INPUTS

    1

    2

    52 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    53/90

    Table 11. Voltage-controlled alarm inputs 1 (D37) (cont.)

    Pin Signal Pin Signal Pin Signal

    6 GND 19 VAL9 32 GND

    7 VAL3 20 GND 33

    8 GND 21 VAL10 34

    9 VAL4 22 GND 35

    10 GND 23 VAL11 36

    11 VAL5 24 GND 37

    12 GND 25 VAL12

    13 VAL6 26 GND

    Table 12. Voltage-controlled alarm inputs 2 (D37)

    Pin Signal Pin Signal Pin Signal

    1 VAL16 14 GND 27 VAL29

    2 GND 15 VAL23 28 GND

    3 VAL17 16 GND 29 VAL30

    4 GND 17 VAL24 30 GND

    5 VAL18 18 GND 31 VAL31

    6 GND 19 VAL25 32 GND

    7 VAL19 20 GND 33

    8 GND 21 VAL26 34

    9 VAL20 22 GND 35

    10 GND 23 VAL27 36

    11 VAL21 24 GND 37

    12 GND 25 VAL28

    13 VAL22 26 GND

    Table 13. Current-controlled alarm inputs (D25)

    Pin Signal Pin Signal

    1 CAL0 14 GND

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 53 (90)

    Connector panels for external alarm and synchronisation interfaces

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    54/90

    Table 13. Current-controlled alarm inputs (D25) (cont.)

    Pin Signal Pin Signal

    2 GND 15 CAL7

    3 CAL1 16 GND

    4 GND 17

    5 CAL2 18

    6 GND 19

    7 CAL3 20

    8 GND 21

    9 CAL4 22

    10 GND 23

    11 CAL5 24

    12 GND 25

    13 CAL6 26

    Table 14. Alarm outputs to the External Alarm Unit (EXAU/-A) (D25)

    Pin Signal Pin Signal

    1 AL0 14 GND

    2 GND 15 AL7

    3 AL1 16 GND

    4 GND 17 AL8

    5 AL2 18 GND

    6 GND 19 AL9

    7 AL3 20 GND

    8 GND 21 AL10

    9 AL4 22 GND

    10 GND 23 AL11

    11 AL5 24 GND

    12 GND 25

    13 AL6 26

    54 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    55/90

    Table 15. Alarm outputs (D37)

    Pin Signal Pin Signal Pin Signal

    1 ALO0 14 GND 27 ALO13

    2 GND 15 ALO7 28 GND

    3 ALO1 16 GND 29 ALO14

    4 GND 17 ALO8 30 GND

    5 ALO2 18 GND 31 ALO15

    6 GND 19 ALO9 32 GND

    7 ALO3 20 GND 33

    8 GND 21 ALO10 34

    9 ALO4 22 GND 35

    10 GND 23 ALO11 36

    11 ALO5 24 GND 37

    12 GND 25 ALO12

    13 ALO6 26 GND

    4.2 CPSY-A, CPSY-B, CPSY and CPSAL/-B forsynchronisation interfaces

    Connector panels CPSY-A, CPSY-B, CPSY and CPSAL/-B consist of BNC

    connectors and RJ-45 connectors for external synchronisation inputs and

    outputs.

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 55 (90)

    Connector panels for external alarm and synchronisation interfaces

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    56/90

    Figure 25. Connector panels CPSY-A, CPSY-B, CPSY and CPSAL/-B for alarm

    and synchronisation interfaces

    DN05160648

    CPSY-B

    IN

    64kIN

    2MOUT2M

    OUT 2M IN 2M

    SYM ASYMEXT2

    Default

    CPSY

    1 2 1 2

    SYM SYM

    3 4 1 2 3 4

    SYM ASYMASYM

    2M 64k 2MIN IN OUT

    Default

    1 2 1 2

    1 23 4

    3 4

    SYM SYM

    ASYM ASYMSYM

    IN 2M OUT 2MIN 64k

    ALARMOUTPUTTO EXAU

    ALARMOUTPUT

    VOLTAGECONTROLLED

    ALARM INPUTS

    CURRENTCONTROLLEDALARM INPUT

    21

    CPSAL/-B

    Default

    CPSY-A

    IN

    64kIN

    2MOUT2M

    OUT2M IN 2M

    SYM ASYMEXT1

    ETH

    Default

    56 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    57/90

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    58/90

    OUT 2M synchronisation interface

    . Coaxial BNC connectors (unbalanced)

    Two BNC connectors OUT 2M provide two unbalanced (ASYM)

    output interfaces.

    . RJ-45 connectors (balanced)

    Two RJ-45 connectors provide two balanced output interfaces for

    2M signals OUT 2M.

    Table 18. Synchronisation (OUT 2M) interface pinout (RJ-45)

    Pin Signal

    13 No signal

    4 2M OUT A / Transmit + (Tx+)

    5 2M OUT B / Transmit - (Tx-)

    68 No signal

    58 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    59/90

    5 Requirement specification for externalcables

    5.1 E1 and T1 balanced (symmetrical) PCM

    If the cabling cabinet is not used, E1 balanced (symmetrical) PCM cables

    are connected to the BIE1T-A, BIE1T or E1T48-A interface panel, and if

    the cabling cabinet is used, the cables are connected to the CPETS-G,

    CPETS-E or CPETS interface panel.

    Cable specifications

    .

    Connector:. RJ-45 connector

    . Shielded construction

    . Gold plating on the contacts (0.76 m)

    . UL94 V-0 materials

    . Cable:

    . Multi-cable (4 or more) bundled assembly

    . Nominal impedance: 120 15 for E1 and 100 15 for T1

    . E1 data transmission protocol specifies 6 dB as maximum

    attenuation

    . AWG 26 or AWG 24 conductors

    . Continuous pair twisting

    . VW-1 materials

    . Flammability: IEC 332-1 or IEC 332-3

    . Operating temperature from 0 C to 70 C

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 59 (90)

    Requirement specification for external cables

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    60/90

    Table 19. Cable CNIA E1 (120 ) component codes

    Item Code

    Connector 5461630

    Plastic part 7333689

    Cable (multi-cable) 7131850

    Table 20. Cable CNIS T1 (100 ) component codes

    Item Code

    Connector 5461630

    Plastic part 7333689

    Cable (single-cable) 7131860

    Table 21. Cable CNIB (120) component codes

    Item Code

    Connector 5461630

    Plastic part 7333689

    Cable (multi-cable) 7131851

    Table 22. RJ-45 connector pinouts (CNIA/CNIS)

    Position Signal, generic names Wire pair #

    1 Receive - (Rx-) 2

    2 Receive + (Rx+) 2

    3 n.c.

    4 Transmit - (Tx-) 1

    5 Transmit + (Tx+) 1

    6 n.c.

    7 n.c.

    8 n.c.

    60 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    61/90

    Table 22. RJ-45 connector pinouts (CNIA/CNIS) (cont.)

    Position Signal, generic names Wire pair #

    n.c. = not connected

    Table 23. RJ-45 connector pinouts (CNIB)

    Position Signal, generic names Wire pair #

    1 Receive - (Rx-) 2

    2 Receive + (Rx+) 2

    3 Receive - (Rx-) 3

    4 Transmit - (Tx-) 1

    5 Transmit + (Tx+) 1

    6 Receive + (Rx+) 3

    7 Transmit - (Tx-) 4

    8 Transmit + (Tx+) 4

    Figure 26. Example of CNIA cable assembly

    CONNECTOR

    DN00206525

    1 2 3 4

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 61 (90)

    Requirement specification for external cables

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    62/90

    Figure 27. Connecting a PCM E1 cable to a connector, CNIS (example)

    5.2 E1 unbalanced (coaxial) cables

    There are three different connector types of unbalanced (coaxial) cables

    depending on the interface panel. SMB connectors are used with BIE1C

    interface panel and BT43 connectors are used with the CPETC-B and

    E1C48-A panels. Multicoaxial D-sub connectors are used with CPETC-E.

    The BIE1C panel is equipped in the equipment cabinet, whereas the

    CPETC-B and CPETC-E panels are equipped in the cabling cabinet. The

    E1C48-A panel is equipped in the equipment cabinet.

    5.2.1 E1 unbalanced (coaxial) cables with the CPETC-E panel

    There are twelve D37 multicoaxial connector bodies on the CPETC-E

    interface panel. Each D37 connector body has eight unbalanced (coaxial)

    connector contacts. Balanced (120) to unbalanced (75) transformation

    is carried out on the CPETC-E panel.

    8

    MODULAR CONNECTOR

    SLEEVE

    CABLE

    IDENTIFICATIONSTICKER

    DN98339941

    62 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    63/90

    Cable specifications

    . Connector:

    . Connector D37 body with unbalanced (coaxial) contacts

    . Gold plating on the contacts (minimum for centre contact 1.27

    m, minimum for outer contact 0.76 m)

    . UL94 V-0 materials

    . Cable:

    . Impedance 75 3

    . Multicoaxial cable

    . E1 data transmission protocol specifies 6dB as maximum

    attenuation. VW-1 material

    . Flammability: IEC 332-1 or IEC 332-3

    . Operating temperature from 0 C to 70 C

    Table 24. Component codes for the unbalanced (coaxial) CPRD cable

    Item Code

    Connector body 5436732

    Connector contact 5463552

    Jack screw 5461696

    Case 5461984

    Multicoaxial cable 7134984

    Figure 28. D37 connector body with unbalanced (coaxial) contacts (1=pin,

    2=ring)

    A7A8 A5A6 A3A4 A1A2

    DN05160651

    1

    2

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 63 (90)

    Requirement specification for external cables

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    64/90

    Table 25. D37 connector pinouts

    Pin Function

    A8-1 TxTip_0

    A8-2 TxRing_0

    A7-1 RxTip_0

    A7-2 RxRing_0

    A6-1 TxTip_1

    A6-2 TxRing_1

    A5-1 RxTip_1

    A5-2 RxRing_1

    A4-1 TxTip_2

    A4-2 TxRing_2

    A3-1 RxTip_2

    A3-2 RxRing_2

    A2-1 TxTip_3

    A2-2 TxRing_3

    A1-1 RxTip_3

    A1-2 RxRing_3

    5.2.2 E1 unbalanced (coaxial) cables with the BIE1C panels

    If the cabling cabinet is not used, E1 unbalanced (coaxial) cables are

    connected to the BIE1C interface panel. The BIE1C interface panels have

    SMB connectors and are located at the rear of the cabinet behind the

    NI16P1A and/or IW16P1 plug-in units.

    Cable specifications

    . Connector:

    . SMB connector, 50

    . Gold plating on the contacts (minimum for centre contact 1.27

    m, minimum for outer contact 0.76 m)

    . UL94 V-0 materials

    . Cable:

    . Impedance 75 3

    . Single or multicoaxial cable

    64 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    65/90

    . E1 data transmission protocol specifies 6dB as maximum

    attenuation. VW-1 material

    . Flammability: IEC 332-1 or IEC 332-3

    . Operating temperature from 0 C to 70 C

    Table 26. Component codes for unbalanced (coaxial) cable

    Item Code

    Connector 5426008

    Connector sleeve 5421434

    Cable 7134962

    Multicoaxial cable 7134984

    Figure 29. Example of E1 multicoaxial cable with SMB connectors

    5.2.3 E1 unbalanced (coaxial) cables with the E1C48-A or CPETC-B panel

    The E1C48-A interface panels are located at the rear of the cabinet. If the

    cabling cabinet is used, E1 unbalanced (coaxial) cables are connected to

    the CPETC-B interface panel. The CPETC-B interface panels have BT43

    connectors, and are located in the cabling cabinet.

    CONNECTOR 1 2 3 4 5 6 7 8

    DN0557322

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 65 (90)

    Requirement specification for external cables

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    66/90

    Cable specifications

    . Connector:

    . BT43 connector, 75

    . Gold plating on the contacts (minimum for centre contact 1.27

    m, minimum for outer contact 0.76 m)

    . Recommended: UL94 V-0 materials

    . Cable:

    . Impedance 75 3

    . Single or multicoaxial cable

    . E1 data transmission protocol specifies 6dB as maximum

    attenuation. VW-1 material

    . Flammability: IEC 332-1 or IEC 332-3

    . Operating temperature from 0 C to 70 C

    Table 27. Component codes for unbalanced (coaxial) cable

    Item Code

    Connector 5425506

    Connector sleeve 5421434

    Cable 7134962

    Multicoaxial cable 7134984

    66 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    67/90

    Figure 30. Example of E1 multicoaxial cable with BT43 connectors

    5.3 Alarm output to EXAU/-A

    If the cabling cabinet is not used, the alarm output cable to the EXAU/-A is

    connected to the CPAL-A or CPSAL/-B panel, whereas if the cabling

    cabinet is used, the cable is connected to the CPAL panel.

    Cable specifications

    . Connector:

    . 25 pos. D-sub male connector

    . Shielded construction

    . Gold plating on the contacts (0.76 m)

    .

    UL94 V-0 materials

    . Connector hood:

    . Connector hood must be shielded

    . Side entry for cable

    . UNC 4/40 thumb screws

    . Maximum height of hood 50 mm

    . Cable:

    . AWG 26 or AWG 24 conductors

    . Minimum 12 twisted pairs

    CONNECTOR 1 2 3 4 5 6 7 8

    DN0557334

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 67 (90)

    Requirement specification for external cables

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    68/90

    . Shielded construction, screening effectiveness > 35dB at

    1GHz. VW-1 materials

    . Flammability: IEC 332-1 or IEC 332-3

    . Operating temperature from 0 C to 70 C

    Table 28. Cable CNDC (version A01) component codes

    Item Code Note

    Connector 5433649

    Connector shell 5438878

    Cable bushing 5438884

    Cable 8 x 2 7131862 1)

    1) Due to the 8 x 2 cable, only AL07 AL7 alarm signals are connected.

    Table 29. Cable CNDC (version A02) component codes

    Item Code Note

    Connector 5433649

    Connector shell 5438878

    Cable bushing 5438884

    Cable 12 x 2 7131864 1)

    1) Due to the 12 x 2 cable, alarm signal AL0 AL11 are connected.

    Version A02 cable is needed when alarm signals AL6 AL11 need to be

    chained. Only EXAU-A has the chaining feature.

    The EXAU-A unit has an alarm output connector, allowing it to chain two or

    more EXAU-A units so that alarms coming from the network element canbe displayed on two or more EXAU-A units.

    The tables below describe the connector pinouts for the following cases:

    68 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    69/90

    . Displaying alarms on EXAU-A or EXAU: connecting the alarm cable

    from CPSAL/-B to EXAU/-A. Displaying the same alarms on two EXAU-A units: chaining EXAU-A

    1 to EXAU-A 2 with a direct cable

    . Displaying alarms AL00 to AL05 on EXAU 1 and alarms AL06 to

    AL11 on EXAU-A 2: chaining EXAU-A 1 to EXAU-A 2 with a

    crossover cable

    For more information on EXAU-A and the chaining principles, see the

    EXAU-A plug-in unit description in MGW product documentation.

    Table 30. Connector pinouts for a cable from CPSAL/-B to EXAU/-A or EXAU-

    A 1 to EXAU-A 2 with a direct cable

    Position -

    CPSAL or

    EXAU-A 1

    Signal Position -

    EXAU/-A or

    EXAU-A 2

    Wire pair #

    1 AL0 1 1

    2 GND 2 1

    3 AL1 3 2

    4 GND 4 2

    5 AL2 5 3

    6 GND 6 3

    7 AL3 7 4

    8 GND 8 4

    9 AL4 9 5

    10 GND 10 5

    11 AL5 11 6

    12 GND 12 6

    13 AL6 13 7

    14 GND 14 7

    15 AL7 15 8

    16 GND 16 8

    17 AL8 17 9

    18 GND 18 9

    19 AL9 19 10

    20 GND 20 10

    21 AL10 21 11

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 69 (90)

    Requirement specification for external cables

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    70/90

    Table 30. Connector pinouts for a cable from CPSAL/-B to EXAU/-A or EXAU-

    A 1 to EXAU-A 2 with a direct cable (cont.)

    Position -

    CPSAL or

    EXAU-A 1

    Signal Position -

    EXAU/-A or

    EXAU-A 2

    Wire pair #

    22 GND 22 11

    23 AL11 23 12

    24 GND 24 12

    25 25

    Table 31. Connector pinouts for a cable from EXAU-A 1 to EXAU-A 2 with a

    crossover cable

    Position -

    EXAU-A 1

    Signal Position -

    EXAU-A 2

    Wire pair #

    1 AL0 13 1

    2 GND 14 1

    3 AL1 15 2

    4 GND 16 2

    5 AL2 17 3

    6 GND 18 3

    7 AL3 19 4

    8 GND 20 4

    9 AL4 21 5

    10 GND 22 5

    11 AL5 23 6

    12 GND 24 6

    13 AL6 1 7

    14 GND 2 7

    15 AL7 3 8

    16 GND 4 8

    17 AL8 5 9

    18 GND 6 9

    19 AL9 7 10

    20 GND 8 10

    70 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    71/90

    Table 31. Connector pinouts for a cable from EXAU-A 1 to EXAU-A 2 with a

    crossover cable (cont.)

    Position -

    EXAU-A 1

    Signal Position -

    EXAU-A 2

    Wire pair #

    21 AL10 9 11

    22 GND 10 11

    23 AL11 11 12

    24 GND 12 12

    25 25

    Figure 31. Example of alarm cable to the EXAU/-A

    5.4 Alarm input cable

    If the cabling cabinet is not used, the alarm output cable is connected to

    the CPAL-A or CPSAL/-B panel, and if the cabling cabinet is used, thecable is connected to the CPAL panel.

    Cable specifications

    . Connector:

    . 37 pos. D-sub male connector

    . Shielded construction

    . Gold plating on the contacts (0.76 m)

    . Recommended: UL94 V-0 materials

    DN0557346

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 71 (90)

    Requirement specification for external cables

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    72/90

    . Connector hood:

    .

    Shielded construction. Side entry for cable

    . UNC 4/40 thumb screws

    . Maximum height of hood 55 mm (cable exits from side of

    hood)

    . Cable:

    . AWG 26 or AWG 24 conductors

    . Minimum 16 twisted pairs

    . Shielded construction, screening effectiveness > 35dB at

    1GHz

    . VW-1 materials

    . Flammability: IEC 332-1 or IEC 332-3

    . Operating temperature from 0 C to 70 C

    Table 32. Component codes for alarm output cable

    Item Code

    Connector 5437752

    Connector shell 5461980

    Strain relief 5434144

    Cable 20 x 2 7131866

    Table 33. Connection pinouts for voltage-controlled alarm input

    Position Signal Wire pair #

    1 ALO0 1

    2 GND 1

    3 ALO1 2

    4 GND 2

    5 ALO2 3

    6 GND 3

    7 ALO3 4

    8 GND 4

    9 ALO4 5

    10 GND 5

    72 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    73/90

    Table 33. Connection pinouts for voltage-controlled alarm input (cont.)

    Position Signal Wire pair #

    11 ALO5 6

    12 GND 6

    13 ALO6 7

    14 GND 7

    15 ALO7 8

    16 GND 8

    17 ALO8 9

    18 GND 9

    19 ALO9 10

    20 GND 10

    21 ALO10 11

    22 GND 11

    23 ALO11 12

    24 GND 12

    25 ALO12 13

    26 GND 13

    27 ALO13 14

    28 GND 14

    29 ALO14 15

    30 GND 15

    31 ALO15 16

    32 GND 16

    33

    34

    35

    36

    37

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 73 (90)

    Requirement specification for external cables

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    74/90

    Figure 32. Example of alarm output cable

    5.5 Voltage-controlled alarm input

    If the cabling cabinet is not used, the voltage-controlled alarm input cable

    is connected to the CPAL-A or CPSAL/-B panel, and if the cabling cabinet

    is used, the cable is connected to the CPAL panel. The panels have two

    D37 connectors for voltage-controlled alarm inputs.

    Cable specifications

    . Connector:

    . 37 pos. D-sub male connector

    . Shielded construction

    . Gold plating on the contacts (0.76 m)

    . Recommended: UL94 V-0 materials

    . Connector hood:

    .

    Shielded construction. Side entry for cable

    . UNC 4/40 thumb screws

    . Maximum height of hood 55 mm (cable exits from side of

    hood)

    . Cable:

    . AWG 26 or AWG 24 conductors

    . Minimum 16 twisted pairs

    . Shielded construction, screening effectiveness > 35dB at

    1GHz

    DN0557361

    74 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    75/90

    . VW-1 materials

    .

    Flammability: IEC 332-1 or IEC 332-3. Operating temperature from 0 C to 70 C

    Table 34. Component codes for voltage-controlled alarm input cable

    Item Code

    Connector 5437752

    Connector shell 5461980

    Strain relief 5434144

    Cable 20x2 7131866

    Table 35. Connection diagram for voltage-controlled alarm input

    Position Signal Wire pair #

    1 VAL0 / VAL16 1

    2 GND 1

    3 VAL1 / VAL17 2

    4 GND 2

    5 VAL2 / VAL18 3

    6 GND 3

    7 VAL3 / VAL19 4

    8 GND 4

    9 VAL4 / VAL20 5

    10 GND 5

    11 VAL5 / VAL21 6

    12 GND 6

    13 VAL6 / VAL22 7

    14 GND 7

    15 VAL7 / VAL23 8

    16 GND 8

    17 VAL8 / VAL24 9

    18 GND 9

    19 VAL9 / VAL25 10

    20 GND 10

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 75 (90)

    Requirement specification for external cables

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    76/90

    Table 35. Connection diagram for voltage-controlled alarm input (cont.)

    Position Signal Wire pair #

    21 VAL10 / VAL26 11

    22 GND 11

    23 VAL11 / VAL27 12

    24 GND 12

    25 VAL12 / VAL28 13

    26 GND 13

    27 VAL13 / VAL29 14

    28 GND 14

    29 VAL14 / VAL30 15

    30 GND 15

    31 VAL15 / VAL31 16

    32 GND 16

    33

    34

    35

    36

    37

    Figure 33. Example of voltage-controlled alarm input cable

    DN0557361

    76 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    77/90

    5.6 Current-controlled alarm input

    If the cabling cabinet is not used, the current-controlled alarm input cable is

    connected to the CPAL-A or CPSAL/-B panel, and if the cabling cabinet is

    used, the cable is connected to the CPAL panel.

    Cable specifications

    . Connector:

    . 25 pos. D-sub male connector

    . Shielded construction

    . Gold plating on the contacts (0.76 m)

    . Recommended: UL94 V-0 materials

    . Connector hood:

    . Shielded construction

    . Side entry for cable

    . UNC 4/40 thumb screws

    . Maximum height of hood 50 mm

    . Cable:

    . AWG 26 or AWG 24 conductors

    .

    Minimum 8 twisted pairs. Shielded construction, screening effectiveness > 35dB at

    1GHz

    . VW-1 materials

    . Flammability: IEC 332-1 or IEC 332-3

    . Operating temperature from 0 C to 70 C

    Table 36. Component codes for cable CNDC

    Item CodeConnector 5433649

    Connector shell 5438878

    Cable bushing 5438884

    Cable 8 x 2 7131862

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 77 (90)

    Requirement specification for external cables

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    78/90

    Table 37. Connection diagram for current-controlled alarm input

    Position Signal Wire pair #

    1 CAL0 1

    2 GND 1

    3 CAL1 2

    4 GND 2

    5 CAL2 3

    6 GND 3

    7 CAL3 4

    8 GND 4

    9 CAL4 5

    10 GND 5

    11 CAL5 6

    12 GND 6

    13 CAL6 7

    14 GND 7

    15 CAL7 8

    16 GND 8

    17 n.c.

    18 n.c.

    19 n.c.

    20 n.c.

    21 n.c.

    22 n.c.

    23 n.c.

    24 n.c.

    25 n.c.

    n.c. = not connected

    78 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    79/90

    Figure 34. Example of current-controlled alarm input cable

    5.7 Asymmetrical external synchronisation

    If the cabling cabinet is not used, the asymmetrical external

    synchronisation cable is connected to the CPSY-A, CPSY-B or CPSAL/-B

    panel, and if the cabling cabinet is used, the cable is connected to the

    CPSY panel. The panels have input connectors for 2M or 1.5M

    asymmetrical synchronisation signals and output connectors for 2M or

    1.5M asymmetrical synchronisation signals.

    Cable specifications

    . Connector:

    . Male BNC

    . Shielded construction

    . Gold plating on the contacts (minimum centre contact 1.27 m,

    minimum outer contact 0.76 m)

    . Recommended: UL94 V-0 materials

    . Cable:

    . Unbalanced (coaxial) (for example BT 3002)

    . Impedance 75 3

    . VW-1 materials

    . Flammability: IEC 332-1 or IEC 332-3

    . Operating temperature from 0 C to 70 C

    DN0557346

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 79 (90)

    Requirement specification for external cables

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    80/90

    Table 38. Component codes for asymmetrical external synchronisation cable

    Item Code

    Connector 5420160

    Cable 7130200

    Figure 35. Example of asymmetrical external synchronisation cable

    5.8 Symmetrical external synchronisation

    If the cabling cabinet is not used, the symmetrical external synchronisation

    cable is connected to the CPSY-A, CPSY-B or CPSAL/-B panel, and if the

    cabling cabinet is used, the cable is connected to the CPSY panel. The

    panels have input connectors for 2M or 1.5M and 64K symmetrical

    synchronisation signals and output connectors for 2M or 1.5M symmetrical

    synchronisation signals.

    Cable specifications

    . Connector:

    . Shielded RJ-45

    . Gold plating on the contacts (0.76 m)

    . Recommended: UL94 V-0 materials

    . Cable:

    . Minimum 1 twisted pair

    .

    Nominal impedance: 120 15

    for E1 and 100 15

    for T1

    DN0557373

    80 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    81/90

    . E1 data transmission protocol specifies 6dB as maximum

    attenuation. AWG 26 or AWG 24 solid conductors

    . Continuous pair twisting

    . VW-1 materials

    . Flammability: IEC 332-1 or IEC 332-3

    . Operating temperature from 0 C to 70 C

    Table 39. Cable CNIA E1 component codes (120, receive and transmit

    signals connected)

    Item Code

    Connector 5461630

    Plastic part 7333689

    Cable 7131850

    Table 40. 64K / 2M / 1.5M symmetrical synchronisation input connector

    pinouts

    Position Signal, generic names Wire pair #

    1 64K/2M IN A / Receive + (Rx+) 1

    2 64K/2M IN B / Receive - (Rx-) 1

    3 n.c.

    4 n.c.

    5 n.c.

    6 n.c.

    7 n.c.

    8 n.c.

    n.c. = not connected

    Table 41. 2M / 1.5M symmetrical synchronisation output connector pinouts

    Position Signal, generic names Wire pair #

    1 n.c.

    2 n.c.

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 81 (90)

    Requirement specification for external cables

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    82/90

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    83/90

    5.9 10Base-T/100Base-TX

    Cable specifications

    . Connector:

    . Shielded RJ-45

    . Gold plating on the contacts (1.27 m)

    . UL94 V-0 materials

    . Cable:

    . S-FTP (foil shield twisted pair) construction

    . Category 5

    . AWG 26 (or AWG 24) conductors

    . Meets EN 50288-2-2 standard

    . VW-1 materials

    . Flammability: IEC 332-1 or IEC 332-3

    . Halogen-free materials

    . Operating temperature from 0 C to 70 C

    Table 42. Component codes for CNIX (cross-connected) or CNI (straight)

    cable

    Item Code

    Connector 5461634

    Cable 7131860

    Table 43. Cross-connected cable

    Pos. Signal, generic

    names

    EIA/TIA 568A

    crossed wiring

    Pos. Signal, generic

    names

    1 Receive + (Rx+) White/green 3 Transmit + (Tx+)

    2 Receive - (Rx-) Green/white 6 Transmit - (Tx-)

    3 Transmit + (Tx+) White/orange 1 Receive + (Rx+)

    4 Blue/white 7

    5 White/blue 8

    6 Transmit - (Tx-) Orange/white 2 Receive - (Rx-)

    7 White/brown 4

    8 Brown/white 5

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 83 (90)

    Requirement specification for external cables

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    84/90

    Figure 37. Example of LAN cable

    5.10 1000Base-T

    Gigabit Ethernet cabling is connected to the IPFGE plug-in unit or

    connector panel CPLAN-A.

    Cable specifications

    . Connector:

    . Shielded RJ-45

    . Gold plating on the contacts (1.27 m)

    . Recommended: UL94 V-0 materials

    . Cable:

    . S-FTP construction

    . Category 5e

    . AWG 26 (or AWG 24) conductors

    . Meets the EN 50288-2-2 standard

    . VW-1 materials

    . Flammability: IEC 332-1 or IEC 332-3

    8

    MODULAR CONNECTOR

    SLEEVE

    CABLE

    IDENTIFICATIONSTICKER

    DN98339941

    84 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    85/90

    . Halogen-free materials

    .

    Operating temperature from 0 C to 70 C

    Table 44. Connector pinouts

    Pos. No. Signal Wire colour (EIA 568-B)

    1 TP0+ White/orange

    2 TP0- Orange

    3 TP1+ White/green

    4 TP2+ Blue

    5 TP2- White/blue

    6 TP1- Green

    7 TP3+ White/brown

    8 TP3- Brown

    Figure 38. Example of LAN cable

    8

    MODULAR CONNECTOR

    SLEEVE

    CABLE

    IDENTIFICATIONSTICKER

    DN98339941

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 85 (90)

    Requirement specification for external cables

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    86/90

    5.11 Optical STM-1

    If the cabling cabinet is not used, optical STM-1 fiber is connected to the

    CPRLC-B panel (RNC), or directly to the front panel of the plug-in unit

    (MGW). If the cabling cabinet is used, the fiber is connected to the

    CPLC36 connector panel or to the front panel of the plug-in unit in the

    equipment cabinet.

    Cable specifications

    . Connector:

    . Duplex LC according to GR-326 and IEC 60874

    .

    Mating durability for 200 reconnects, insertion loss change 45dB

    . Zirconia ferrule

    . Efficiency of strain relief > 80N

    . UL94V-0

    . Boot:

    .

    90 angle boot (minimum requirement at the MGW or RNCconnection end)

    . Maximum installation height 70 mm

    . UL94V-0

    . Cable:

    . 9/125 m single mode fibre

    . Attenuation: 0,5 dB / Km at = 1310 nm and 0.4 dB / Km at

    = 1550 nm

    . Cable must fulfill ITU-T G.652 for interface type STM-1 optical

    (ITU-T G.957, table 1)

    . Cable must fulfill ATM 155 Mb/s

    . Duplex type

    . UL VW-1 or UL94V-0

    . Fibre cables must be provided with a common secondary

    overall jacket which will not slide along the cables

    . Maximum cable outer diameter 6.6 mm

    . Minimum bending radius during installation < 65 mm

    . Minimum bending radius in service < 43 mm (according to IEC

    794-1-E11)

    86 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    87/90

    . Crush resistance (briefly) > 500 N/cm. According to IEC 794-1-

    E3. Crush resistance (continuous) > 100 N/cm

    . Operating temperature from 0 C to 70 C

    Table 45. Cable types for single-mode optical cables

    Cable type Boot Connection

    CSM One end with straight boot and the

    other with 90 angle boot

    straight

    CSMA Both boots are 90 straight

    Figure 39. Example of a single-mode optical cable

    5.12 1000Base-LX (optical)

    Gigabit Ethernet cabling is connected to the IPFGE plug-in unit. If the

    cabling cabinet is used, the Ethernet cable is connected to the CPLC36

    interface panel.

    A

    B

    30 5

    AB

    30 5 DN01130619

    Dust caps to LC connectors

    Dustcaps to LCconnectors

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 87 (90)

    Requirement specification for external cables

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    88/90

    Cable specifications

    . Connector

    . Duplex LC according to GR-326 and IEC 60874

    . Mating durability for 200 reconnects, insertion loss change 45dB

    . Zirconia ferrule

    . Blue colour

    .

    Efficiency of strain relief > 80N. UL94V-0

    . Boot

    . 90 angle boot

    . Maximum installation height 70 mm

    . UL94V-0

    . Cable

    . 9/125 m single mode fibre

    . Attenuation: 0,5 dB / Km at = 1310 nm and 0.4 dB / Km at

    = 1550 nm. Cable must fulfill ITU-T G.652 for interface type STM-1 optical

    (ITU-T G.957, table 1)

    . Cable must fulfill ATM 155 Mb/s

    . Duplex type

    . UL VW-1 or UL94V-0

    . Fibre cables must be provided with a common secondary

    overall jacket which will not slide along the cables

    . Maximum cable outer diameter 6.6 mm

    . Minimum bending radius during installation < 65 mm

    . Minimum bending radius in service < 43 mm (according to IEC

    794-1-E11)

    . Crush resistance (briefly) > 500 N/cm. According to IEC 794-1-

    E3

    . Crush resistance (continuous) > 100 N/cm

    . Operating temperature from 0 C to 70 C

    88 (90) # Nokia Siemens Networks DN0127056Issue 9-4 en draft

    Cabinet Interfaces and External Cables of MGW and RNC

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    89/90

    Table 46. Cable types for single-mode optical cables

    Cable type Boot Connection

    CSM One end with straight boot and the

    other with 90 angle boot

    straight

    CSMA Both boots are 90 straight

    Figure 40. Example of a single-mode optical cable

    5.13 Reference standards and directions

    . ATM 155 Mb/s

    . EN 50288-2-2

    . GR-326

    . IEC 332-1

    A

    B

    30 5

    AB

    30 5 DN01130619

    Dust caps to LC connectors

    Dustcaps to LCconnectors

    DN0127056Issue 9-4 en draft

    # Nokia Siemens Networks 89 (90)

    Requirement specification for external cables

  • 8/10/2019 Cab Inter Ext Cables MGW RNC

    90/90

    . IEC 332-3

    . IEC 754-1

    . IEC 794-1

    . IEC 874-1

    . IEC 60874

    . IEC 61754-20-4

    . ITU-T G.652

    . TIA/EIA-568

    . UL94V-0

    . UL VW-1

    . GR253

    Cabinet Interfaces and External Cables of MGW and RNC