General rights Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights. Users may download and print one copy of any publication from the public portal for the purpose of private study or research. You may not further distribute the material or use it for any profit-making activity or commercial gain You may freely distribute the URL identifying the publication in the public portal If you believe that this document breaches copyright please contact us providing details, and we will remove access to the work immediately and investigate your claim. Downloaded from orbit.dtu.dk on: Dec 20, 2017 Can crawl space temperature and moisture conditions be calculated with a whole- building hygrothermal simulation tool? Vanhoutteghem, Lies; Morelli, Martin; Sørensen, Lars Schiøtt Published in: Energy Procedia Link to article, DOI: 10.1016/j.egypro.2017.10.007 Publication date: 2017 Document Version Publisher's PDF, also known as Version of record Link back to DTU Orbit Citation (APA): Vanhoutteghem, L., Morelli, M., & Sørensen, L. S. (2017). Can crawl space temperature and moisture conditions be calculated with a whole-building hygrothermal simulation tool? Energy Procedia, 132, 688-693. DOI: 10.1016/j.egypro.2017.10.007

Upload: others

Post on 06-Sep-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Can crawl space temperature and moisture conditions be calculated with a whole ... · 2017. 12. 20. · BSim (Building Simulation) [9] was used to calculate the hygrothermal behaviour

General rights Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights.

• Users may download and print one copy of any publication from the public portal for the purpose of private study or research. • You may not further distribute the material or use it for any profit-making activity or commercial gain • You may freely distribute the URL identifying the publication in the public portal

If you believe that this document breaches copyright please contact us providing details, and we will remove access to the work immediately and investigate your claim.

Downloaded from orbit.dtu.dk on: Dec 20, 2017

Can crawl space temperature and moisture conditions be calculated with a whole-building hygrothermal simulation tool?

Vanhoutteghem, Lies; Morelli, Martin; Sørensen, Lars Schiøtt

Published in:Energy Procedia

Link to article, DOI:10.1016/j.egypro.2017.10.007

Publication date:2017

Document VersionPublisher's PDF, also known as Version of record

Link back to DTU Orbit

Citation (APA):Vanhoutteghem, L., Morelli, M., & Sørensen, L. S. (2017). Can crawl space temperature and moisture conditionsbe calculated with a whole-building hygrothermal simulation tool? Energy Procedia, 132, 688-693. DOI:10.1016/j.egypro.2017.10.007

Page 2: Can crawl space temperature and moisture conditions be calculated with a whole ... · 2017. 12. 20. · BSim (Building Simulation) [9] was used to calculate the hygrothermal behaviour

ScienceDirect

Available online at www.sciencedirect.comAvailable online at www.sciencedirect.com

ScienceDirectEnergy Procedia 00 (2017) 000–000

www.elsevier.com/locate/procedia

1876-6102 © 2017 The Authors. Published by Elsevier Ltd.Peer-review under responsibility of the Scientific Committee of The 15th International Symposium on District Heating and Cooling.

The 15th International Symposium on District Heating and Cooling

Assessing the feasibility of using the heat demand-outdoor temperature function for a long-term district heat demand forecast

I. Andrića,b,c*, A. Pinaa, P. Ferrãoa, J. Fournierb., B. Lacarrièrec, O. Le Correc

aIN+ Center for Innovation, Technology and Policy Research - Instituto Superior Técnico, Av. Rovisco Pais 1, 1049-001 Lisbon, PortugalbVeolia Recherche & Innovation, 291 Avenue Dreyfous Daniel, 78520 Limay, France

cDépartement Systèmes Énergétiques et Environnement - IMT Atlantique, 4 rue Alfred Kastler, 44300 Nantes, France

Abstract

District heating networks are commonly addressed in the literature as one of the most effective solutions for decreasing the greenhouse gas emissions from the building sector. These systems require high investments which are returned through the heatsales. Due to the changed climate conditions and building renovation policies, heat demand in the future could decrease, prolonging the investment return period. The main scope of this paper is to assess the feasibility of using the heat demand – outdoor temperature function for heat demand forecast. The district of Alvalade, located in Lisbon (Portugal), was used as a case study. The district is consisted of 665 buildings that vary in both construction period and typology. Three weather scenarios (low, medium, high) and three district renovation scenarios were developed (shallow, intermediate, deep). To estimate the error, obtained heat demand values were compared with results from a dynamic heat demand model, previously developed and validated by the authors.The results showed that when only weather change is considered, the margin of error could be acceptable for some applications(the error in annual demand was lower than 20% for all weather scenarios considered). However, after introducing renovation scenarios, the error value increased up to 59.5% (depending on the weather and renovation scenarios combination considered). The value of slope coefficient increased on average within the range of 3.8% up to 8% per decade, that corresponds to the decrease in the number of heating hours of 22-139h during the heating season (depending on the combination of weather and renovation scenarios considered). On the other hand, function intercept increased for 7.8-12.7% per decade (depending on the coupled scenarios). The values suggested could be used to modify the function parameters for the scenarios considered, and improve the accuracy of heat demand estimations.

© 2017 The Authors. Published by Elsevier Ltd.Peer-review under responsibility of the Scientific Committee of The 15th International Symposium on District Heating and Cooling.

Keywords: Heat demand; Forecast; Climate change

Energy Procedia 132 (2017) 688–693

1876-6102 © 2017 The Authors. Published by Elsevier Ltd.Peer-review under responsibility of the organizing committee of the 11th Nordic Symposium on Building Physics10.1016/j.egypro.2017.10.007

10.1016/j.egypro.2017.10.007 1876-6102

Available online at www.sciencedirect.com

ScienceDirect Energy Procedia 00 (2017) 000–000

www.elsevier.com/locate/procedia

1876-6102 © 2017 The Authors. Published by Elsevier Ltd. Peer-review under responsibility of the organizing committee of the 11th Nordic Symposium on Building Physics.

11th Nordic Symposium on Building Physics, NSB2017, 11-14 June 2017, Trondheim, Norway

Can crawl space temperature and moisture conditions be calculated with a whole-building hygrothermal simulation tool?

Lies Vanhoutteghema,*, Martin Morellia, Lars Schiøtt Sørensenb aDanish Building Research Institute, Aalborg University, A.C.Meyers Vænge 15, DK-2450 Copenhagen SV, Denmark

bTechnical University of Denmark, Brovej Building 118, DK-2800 Kgs. Lyngby, Denmark

Abstract

The hygrothermal behaviour of an outdoor ventilated crawl space with two different designs of the floor structure was investigated. The first design had 250 mm insulation and visible wooden beams towards the crawl space. The second design had 300 mm insulation and no visible wooden beams. One year of measurements was compared with simulations of temperature and moisture condition in the floor structure and crawl space. The measurements showed that the extra 50 mm insulation placed below the beams reduced moisture content in the beams below 20 weight% all year. A reasonable agreement between the measurements and simulations was found; however, the evaporation from the soil was a dominant parameter affecting the hygrothermal response in the crawl space and floor structure. © 2017 The Authors. Published by Elsevier Ltd. Peer-review under responsibility of the organizing committee of the 11th Nordic Symposium on Building Physics.

Keywords: Outdoor ventilated crawl space; measurements; whole building simulation; large instulation thickness; temperature; moisture content

1. Introduction

Crawl spaces are understood as ventilated floor structures towards ground. In Denmark, traditional crawl spaces are constructed with foundations and an outdoor ventilated cavity between the floor structure and the soil. This type of crawl space is also widely used in other Nordic countries and was considered a good solution in old buildings with limited insulation thickness. However, compliance with stricter energy requirements resulting in increased insulation

* Corresponding author. Tel.: +45 99 40 23 47.

E-mail address: [email protected]

2 Author name / Energy Procedia 00 (2017) 000–000

thicknesses in floor structures entails that the ventilated crawl space must be considered a high risk construction with respect to mould growth [1, 2]. It is well known that the moisture conditions (relative humidity) in outdoor ventilated crawl spaces can become problematic, especially in summer, because the crawl space remains cold due to the soil thermal inertia, while warm outdoor air with higher moisture content enters the crawl space – the larger insulation thicknesses only increase this problem as the heat loss from the house is reduced. Investigations showed that an increase in floor insulation from 100 mm to 200 mm might lead to an annual temperature drop of 2 C in the crawl space [3]. Comparison of simulations on a crawl space with 100, 200, 300 and 500 mm insulation in the floor structure, and a plastic foil on the soil [4], has shown that an increase in insulation thickness increases the period (summer) where the relative humidity is higher than 80 %, which increases the risk for mould growth. In Denmark, it is now recommended only to use inorganic materials in outdoor ventilated (cold) crawl spaces, if the crawl space is ventilated with 1/500 of the ground floor area and a U-value that fulfils today’s requirement [5]. If organic materials are used, they should be protected from moisture by placing at least 100 mm of non-moisture absorbing insulation below the organic material [6]. Furthermore, it is recommended to either increase the ventilation rate to 1/50 or even construct the crawl space as a warm crawl space.

A research project [7] on moisture problems in constructions with large insulation thicknesses was conducted by the Danish Building Research Institute on several typical constructions used in Denmark. In this paper, measurements of temperature and moisture content in the crawl space and in the floor structure from above-mentioned project are compared with simulations conducted in BSim [8], which is a whole-building simulation tool. Two different designs of the floor structure above the crawl space are investigated; a design with 50 mm insulation under the wooden support beams facing the crawl space, and a design without insulation under the beams.

2. Method

2.1. Crawl space design and temperature and relative humidity measurements

In part of a 110 m2 outdoor ventilated crawl space, temperature and relative humidity was measured in the indoor air, crawl space air and different places in the floor structure, as shown in Fig 1. The crawl space had approx. 700 mm of free height and was placed above ground, i.e., the crawl space walls were not covered with soil on the outside. Ten ventilation openings were placed 300-500 mm above ground in the crawl space, each with a dimension of 50 x 300mm. The crawl space was un-insulated towards the soil and no moisture membrane was laid out on the soil; however, 100 mm of gravel was used as capillary material. As typical for outdoor ventilated crawl spaces, the outer walls of the crawl space facing the exterior climate are also un-insulated. Originally, the floor structure above the crawl space was insulated with 300 mm mineral wool, of which 50 mm was installed under the wooden support beams facing the crawl space, see Fig. 1b. In part of the floor structure, the insulation under the beams was removed; see Fig. 1a.

The measurement of temperature was made with a thermo-couple, whereas the moisture content was measured in a wood sample with two pins to measure electric resistance. The electric resistance was converted to wood moisture content in weight%. All sensors were calibrated against each other in an indoor environment. The sensors showed maximum deviations on the reference temperature of 20 ºC +/- 1 ºC and on the reference wood moisture content of 9 weight% +/- 0.1 weight%, corresponding to 40 % RH. The sensors were placed 1) in the house above the test area, 2) in the floor structure, where two sensors were placed at the upper edge of the wooden floor beams, and two sensors were placed under the wooden floor beams, but on top of the wind barrier (cf. Fig 1), and 3) in the crawl space on the gravel, but placed on a ceramic tile for protection from moisture evaporation from the soil. Data were collected every 30 minutes from 15 March 2015, and in this paper one year of data from 15 April 2015 to 15 April 2016 are reported.

2.2. Simulation model in BSim

BSim (Building Simulation) [9] was used to calculate the hygrothermal behaviour in the crawl space and the floor structure. BSim is a transient whole-building simulation tool to calculate; among others, thermal indoor climate, energy consumption and synchronous simulation of moisture and energy transport in constructions and spaces.

Page 3: Can crawl space temperature and moisture conditions be calculated with a whole ... · 2017. 12. 20. · BSim (Building Simulation) [9] was used to calculate the hygrothermal behaviour

Lies Vanhoutteghem et al. / Energy Procedia 132 (2017) 688–693 689

Available online at www.sciencedirect.com

ScienceDirect Energy Procedia 00 (2017) 000–000

www.elsevier.com/locate/procedia

1876-6102 © 2017 The Authors. Published by Elsevier Ltd. Peer-review under responsibility of the organizing committee of the 11th Nordic Symposium on Building Physics.

11th Nordic Symposium on Building Physics, NSB2017, 11-14 June 2017, Trondheim, Norway

Can crawl space temperature and moisture conditions be calculated with a whole-building hygrothermal simulation tool?

Lies Vanhoutteghema,*, Martin Morellia, Lars Schiøtt Sørensenb aDanish Building Research Institute, Aalborg University, A.C.Meyers Vænge 15, DK-2450 Copenhagen SV, Denmark

bTechnical University of Denmark, Brovej Building 118, DK-2800 Kgs. Lyngby, Denmark

Abstract

The hygrothermal behaviour of an outdoor ventilated crawl space with two different designs of the floor structure was investigated. The first design had 250 mm insulation and visible wooden beams towards the crawl space. The second design had 300 mm insulation and no visible wooden beams. One year of measurements was compared with simulations of temperature and moisture condition in the floor structure and crawl space. The measurements showed that the extra 50 mm insulation placed below the beams reduced moisture content in the beams below 20 weight% all year. A reasonable agreement between the measurements and simulations was found; however, the evaporation from the soil was a dominant parameter affecting the hygrothermal response in the crawl space and floor structure. © 2017 The Authors. Published by Elsevier Ltd. Peer-review under responsibility of the organizing committee of the 11th Nordic Symposium on Building Physics.

Keywords: Outdoor ventilated crawl space; measurements; whole building simulation; large instulation thickness; temperature; moisture content

1. Introduction

Crawl spaces are understood as ventilated floor structures towards ground. In Denmark, traditional crawl spaces are constructed with foundations and an outdoor ventilated cavity between the floor structure and the soil. This type of crawl space is also widely used in other Nordic countries and was considered a good solution in old buildings with limited insulation thickness. However, compliance with stricter energy requirements resulting in increased insulation

* Corresponding author. Tel.: +45 99 40 23 47.

E-mail address: [email protected]

2 Author name / Energy Procedia 00 (2017) 000–000

thicknesses in floor structures entails that the ventilated crawl space must be considered a high risk construction with respect to mould growth [1, 2]. It is well known that the moisture conditions (relative humidity) in outdoor ventilated crawl spaces can become problematic, especially in summer, because the crawl space remains cold due to the soil thermal inertia, while warm outdoor air with higher moisture content enters the crawl space – the larger insulation thicknesses only increase this problem as the heat loss from the house is reduced. Investigations showed that an increase in floor insulation from 100 mm to 200 mm might lead to an annual temperature drop of 2 C in the crawl space [3]. Comparison of simulations on a crawl space with 100, 200, 300 and 500 mm insulation in the floor structure, and a plastic foil on the soil [4], has shown that an increase in insulation thickness increases the period (summer) where the relative humidity is higher than 80 %, which increases the risk for mould growth. In Denmark, it is now recommended only to use inorganic materials in outdoor ventilated (cold) crawl spaces, if the crawl space is ventilated with 1/500 of the ground floor area and a U-value that fulfils today’s requirement [5]. If organic materials are used, they should be protected from moisture by placing at least 100 mm of non-moisture absorbing insulation below the organic material [6]. Furthermore, it is recommended to either increase the ventilation rate to 1/50 or even construct the crawl space as a warm crawl space.

A research project [7] on moisture problems in constructions with large insulation thicknesses was conducted by the Danish Building Research Institute on several typical constructions used in Denmark. In this paper, measurements of temperature and moisture content in the crawl space and in the floor structure from above-mentioned project are compared with simulations conducted in BSim [8], which is a whole-building simulation tool. Two different designs of the floor structure above the crawl space are investigated; a design with 50 mm insulation under the wooden support beams facing the crawl space, and a design without insulation under the beams.

2. Method

2.1. Crawl space design and temperature and relative humidity measurements

In part of a 110 m2 outdoor ventilated crawl space, temperature and relative humidity was measured in the indoor air, crawl space air and different places in the floor structure, as shown in Fig 1. The crawl space had approx. 700 mm of free height and was placed above ground, i.e., the crawl space walls were not covered with soil on the outside. Ten ventilation openings were placed 300-500 mm above ground in the crawl space, each with a dimension of 50 x 300mm. The crawl space was un-insulated towards the soil and no moisture membrane was laid out on the soil; however, 100 mm of gravel was used as capillary material. As typical for outdoor ventilated crawl spaces, the outer walls of the crawl space facing the exterior climate are also un-insulated. Originally, the floor structure above the crawl space was insulated with 300 mm mineral wool, of which 50 mm was installed under the wooden support beams facing the crawl space, see Fig. 1b. In part of the floor structure, the insulation under the beams was removed; see Fig. 1a.

The measurement of temperature was made with a thermo-couple, whereas the moisture content was measured in a wood sample with two pins to measure electric resistance. The electric resistance was converted to wood moisture content in weight%. All sensors were calibrated against each other in an indoor environment. The sensors showed maximum deviations on the reference temperature of 20 ºC +/- 1 ºC and on the reference wood moisture content of 9 weight% +/- 0.1 weight%, corresponding to 40 % RH. The sensors were placed 1) in the house above the test area, 2) in the floor structure, where two sensors were placed at the upper edge of the wooden floor beams, and two sensors were placed under the wooden floor beams, but on top of the wind barrier (cf. Fig 1), and 3) in the crawl space on the gravel, but placed on a ceramic tile for protection from moisture evaporation from the soil. Data were collected every 30 minutes from 15 March 2015, and in this paper one year of data from 15 April 2015 to 15 April 2016 are reported.

2.2. Simulation model in BSim

BSim (Building Simulation) [9] was used to calculate the hygrothermal behaviour in the crawl space and the floor structure. BSim is a transient whole-building simulation tool to calculate; among others, thermal indoor climate, energy consumption and synchronous simulation of moisture and energy transport in constructions and spaces.

Page 4: Can crawl space temperature and moisture conditions be calculated with a whole ... · 2017. 12. 20. · BSim (Building Simulation) [9] was used to calculate the hygrothermal behaviour

690 Lies Vanhoutteghem et al. / Energy Procedia 132 (2017) 688–693 Author name / Energy Procedia 00 (2017) 000–000 3

Fig. 1. The floor structure above the crawl space and indication of measurement points. (a) without 50 mm insulation installed under the wooden beams; (b) with 50 mm insulation installed under the wooden beams.

In BSim, the whole house was modelled, with the 110 m2 crawl space as the thermal zone, and the room above as a zone with a well described temperature and relative humidity based on measurement data in the house. The crawl space walls were modelled as external walls exposed to outside climate. The floor structure above the crawl space is treated as a 1D model in the hygrothermal calculations in BSim. Therefore, the floor structure was modelled with insulation instead of wooden beams. With due respect for limitations, 1D simulation can in this case be used to give an indication of the differences in moisture content for both designs. However, to be able to evaluate the moisture content in the beams for comparison with measurements, a thin layer of wood was inserted at the surfaces representing the top and bottom of the wooden beams.

The outside climate was described by hourly values of temperature, relative humidity, wind speed, wind direction and atmospheric pressure. The weather data were collected at a nearby located private weather station.

Evaporation from the ground to the crawl space was included in the simulation by assuming 100 % relative humidity in the soil under the crawl space. The ventilation of the crawl space was modelled as infiltration where the amount of inlet air equalled the outlet air. The ventilation rate was set to 1.4 h-1 during summer and 0.35 h-1 during winter. The aforementioned description of the model produced the best convergence between the measured and calculated temperature and moisture content. The ventilation rate and evaporations from the soil are decisive factors in predicting the temperature and moisture behaviour in the floor structure and the crawl space.

3. Results

3.1. Measurement in crawl space and floor structure

Fig. 2 shows the measured temperature and Fig. 3 shows the moisture content in the crawl space, the floor structure (M1-M4), indoor climate and outdoor climate. In Fig. 2 the temperature in the different points behaves as expected, where the measuring points above the beams (M3, M4) are warmer than the measuring points below the beams (M1, M2). The measuring point (M1) without the extra 50 mm insulation is colder than the measuring point (M2) with insulation. Similar trends are seen for the moisture content in Fig. 3, where measuring point (M1) has a wood moisture content of 15-21 weight% compared to measuring point M2, where the wood moisture content never exceeds 15 weight%. Critical levels of moisture content in the case without extra 50 mm insulation are especially reached during summer and autumn.

a) b) Tiles (10 mm Terracotta)

100 mm concrete with vapor barrier just below

50 mm hard mineral wool insulation

200 mm flexi mineral wool insulation, between 50 x 200 mm wooden beams

Wind barrier (bitumen coated cardboard)

21 mm wooden furring (c/c=300 mm)

50 mm mineral wool

700 mm ventilated crawl space

Terrain with 100 mm gravel

M1 M2

M4 M3

4 Author name / Energy Procedia 00 (2017) 000–000

Fig. 2. Temperature in the crawl space, floor structure and indoor and outdoor climate in the period 15/4/2015-15/4/2016.

Fig. 3. Moisture content in the crawl space, floor structure and indoor and outdoor climate in the period 15/4/2015-15/4/2016.

3.2. Validation of model with measurements

Fig. 4 shows a comparison of the measured and simulated temperatures and relative humidity in the crawl space. The temperature in the crawl space shows good agreement, especially, from 12 September 2015 to 15 April 2016. The relative humidity has not similar good agreement between measurements and simulations. In the first six month the simulation results are approx. 20 % RH below the measured data. In the last six months a better convergence is achieved.

Fig. 4. Comparison of measured and simulated temperatures and relative humidity in the crawl space in the period 15/4/2015-15/4/2016.

0

5

10

15

20

25

30

Tem

pera

ture

[o C]

Indoor Outdoor Crawl space M1 M2 M3 M4

8,010,012,014,016,018,020,022,024,026,028,030,032,0

Moi

stur

e co

nten

t [W

eigh

t%]

Indoor Outdoor Crawl space M1 M2 M3 M4

5060708090100

05

10152025

Relative hum

idity [%]

Tem

pera

ture

[o C]

Crawl space - measured temperature Crawl space - simulated temperatureCrawl space - measured RH Crawl space - simulated RH

Page 5: Can crawl space temperature and moisture conditions be calculated with a whole ... · 2017. 12. 20. · BSim (Building Simulation) [9] was used to calculate the hygrothermal behaviour

Lies Vanhoutteghem et al. / Energy Procedia 132 (2017) 688–693 691 Author name / Energy Procedia 00 (2017) 000–000 3

Fig. 1. The floor structure above the crawl space and indication of measurement points. (a) without 50 mm insulation installed under the wooden beams; (b) with 50 mm insulation installed under the wooden beams.

In BSim, the whole house was modelled, with the 110 m2 crawl space as the thermal zone, and the room above as a zone with a well described temperature and relative humidity based on measurement data in the house. The crawl space walls were modelled as external walls exposed to outside climate. The floor structure above the crawl space is treated as a 1D model in the hygrothermal calculations in BSim. Therefore, the floor structure was modelled with insulation instead of wooden beams. With due respect for limitations, 1D simulation can in this case be used to give an indication of the differences in moisture content for both designs. However, to be able to evaluate the moisture content in the beams for comparison with measurements, a thin layer of wood was inserted at the surfaces representing the top and bottom of the wooden beams.

The outside climate was described by hourly values of temperature, relative humidity, wind speed, wind direction and atmospheric pressure. The weather data were collected at a nearby located private weather station.

Evaporation from the ground to the crawl space was included in the simulation by assuming 100 % relative humidity in the soil under the crawl space. The ventilation of the crawl space was modelled as infiltration where the amount of inlet air equalled the outlet air. The ventilation rate was set to 1.4 h-1 during summer and 0.35 h-1 during winter. The aforementioned description of the model produced the best convergence between the measured and calculated temperature and moisture content. The ventilation rate and evaporations from the soil are decisive factors in predicting the temperature and moisture behaviour in the floor structure and the crawl space.

3. Results

3.1. Measurement in crawl space and floor structure

Fig. 2 shows the measured temperature and Fig. 3 shows the moisture content in the crawl space, the floor structure (M1-M4), indoor climate and outdoor climate. In Fig. 2 the temperature in the different points behaves as expected, where the measuring points above the beams (M3, M4) are warmer than the measuring points below the beams (M1, M2). The measuring point (M1) without the extra 50 mm insulation is colder than the measuring point (M2) with insulation. Similar trends are seen for the moisture content in Fig. 3, where measuring point (M1) has a wood moisture content of 15-21 weight% compared to measuring point M2, where the wood moisture content never exceeds 15 weight%. Critical levels of moisture content in the case without extra 50 mm insulation are especially reached during summer and autumn.

a) b) Tiles (10 mm Terracotta)

100 mm concrete with vapor barrier just below

50 mm hard mineral wool insulation

200 mm flexi mineral wool insulation, between 50 x 200 mm wooden beams

Wind barrier (bitumen coated cardboard)

21 mm wooden furring (c/c=300 mm)

50 mm mineral wool

700 mm ventilated crawl space

Terrain with 100 mm gravel

M1 M2

M4 M3

4 Author name / Energy Procedia 00 (2017) 000–000

Fig. 2. Temperature in the crawl space, floor structure and indoor and outdoor climate in the period 15/4/2015-15/4/2016.

Fig. 3. Moisture content in the crawl space, floor structure and indoor and outdoor climate in the period 15/4/2015-15/4/2016.

3.2. Validation of model with measurements

Fig. 4 shows a comparison of the measured and simulated temperatures and relative humidity in the crawl space. The temperature in the crawl space shows good agreement, especially, from 12 September 2015 to 15 April 2016. The relative humidity has not similar good agreement between measurements and simulations. In the first six month the simulation results are approx. 20 % RH below the measured data. In the last six months a better convergence is achieved.

Fig. 4. Comparison of measured and simulated temperatures and relative humidity in the crawl space in the period 15/4/2015-15/4/2016.

0

5

10

15

20

25

30

Tem

pera

ture

[o C]

Indoor Outdoor Crawl space M1 M2 M3 M4

8,010,012,014,016,018,020,022,024,026,028,030,032,0

Moi

stur

e co

nten

t [W

eigh

t%]

Indoor Outdoor Crawl space M1 M2 M3 M4

5060708090100

05

10152025

Relative hum

idity [%]

Tem

pera

ture

[o C]

Crawl space - measured temperature Crawl space - simulated temperatureCrawl space - measured RH Crawl space - simulated RH

Page 6: Can crawl space temperature and moisture conditions be calculated with a whole ... · 2017. 12. 20. · BSim (Building Simulation) [9] was used to calculate the hygrothermal behaviour

692 Lies Vanhoutteghem et al. / Energy Procedia 132 (2017) 688–693 Author name / Energy Procedia 00 (2017) 000–000 5

In Fig 5, the temperature in the floor structure under the beams is given. Deviations up to 5 C are seen, especially in the last six months for the design with insulation applied under the beams (M2-S2). Compared to measurements, simulated temperatures under the wooden beams follow the outdoor temperature more closely. Similar trends are found at the top of the wooden beams, however with higher temperature due to influence from the indoor climate.

The moisture content in the floor structure is shown in Fig 6, where results for both the top and bottom of the beam are shown. Generally, the convergence between measurements and simulations is not as good as for the temperature. The best representation is obtained at the top of the beams, where the graphs follow the same trend, but moisture content is overestimated by the simulations during summer. The moisture content at the bottom of the beams has no convergence, and similar trends for the measured and simulated data are difficult to find.

Fig. 5. Comparison of measured (M) and simulated (S) temperatures in the floor structure under the wooden beams (15/4/2015-15/4/2016).

Fig. 6. Comparison of measured (M) and simulated (S) moisture content in the floor structure in the period 15/4/2015-15/4/2016.

4. Discussion

As the behaviour in a crawl space cannot simply be described based on boundary conditions from the outdoor climate, there exist specific calculations tools, e.g. CRAWL to determine the heat and moisture conditions in crawl spaces [9]. Instead of using a specific calculation tool developed for only crawl spaces, the whole building hygrothermal simulation tool BSim was used in this paper.

Comparison between measurements and simulations of temperature and moisture content/relative humidity in the floor structure and the crawl space has shown both good and poor convergences. Large deviations between measured and simulated results were found for relative humidity and moisture content in the crawl space and floor structure. Of note is that BSim is not originally developed to perform moisture simulations. BSim’s moisture module includes calculation of the dynamic moisture balance in a zone (crawl space) and the moisture accumulation in the constructions (floor structure). The moisture accumulation in the constructions is based on vapour diffusion (including hysteresis) with the surrounding zones.

05

10152025

Tem

pera

ture

[o C]

M1 M2 S1 S2

7891011121314

810121416182022

Moisture content

above beam [w

eight%]

Moi

stur

e co

nten

t un

der

beam

[Wei

ght%

]

M1 M2 S1 S2 M3 M4 S3 S4

6 Author name / Energy Procedia 00 (2017) 000–000

The relative humidity and moisture content in the crawl space and floor structure is strongly affected by the interaction between evaporation from the soil and ventilation rate in the crawl space. Exact figures for the evaporation from the soil to the crawl space depend on the climate, the construction etc. and are hard to obtain. In this preliminary study for using BSim, evaporation from the soil was included by assuming 100 % relative humidity in the soil under the crawl space. This is done in BSim by assigning a time-dependent (cosinus-profile) moisture load to the properties of the soil under the crawl space. Instead of this simplification, an advanced model for evaporation can be used in BSim. Preliminary simulations performed with both approaches showed better convergence with the measurements when assuming 100 % relative humidity in the soil instead of using the advanced model. However, it would definitely be worth to further investigate both approaches for further validation of BSim.

The amount of ventilation with outdoor air in the crawl space depends on wind conditions, location of the vents, location and surroundings of the building, obstructions in front of the vents, etc. Since no measurements on air change rates in the crawl space were available, a ventilation rate of 1.4h-1/0.35h-1 was used in the modelling. The lower ventilation rate was chosen during the winter period, as the ventilation rate showed little influence on the relative humidity in the crawl space during winter and best agreement with temperature was found with a lower ventilation rate. The higher ventilation rate was chosen during the summer period, in order to increase the simulated relative humidity in the crawl space. Further investigations showed that increasing the ventilation rate even more did not help in increasing moisture content below the wooden beams and in the crawl space during summer. Instead, it was found that evaporation from the soil has larger influence.

5. Conclusion

Measurements and simulations showed that applying 50 mm insulation under the wooden beams in the floor structure above the investigated crawl space is a good option for raising the temperature and reducing the moisture content in the beams. The wood moisture content was for this design below 20 weight%. Comparison of the measured and calculated temperature and moisture content in the crawl space and floor structure showed that the temperature has a good convergence while the relative humidity in the crawl space has good convergence the last six months compared to the first six months. Simulations of the wood moisture content above the wooden beams followed the same trend as the measurements, but with an overestimation in summer. Similar trends for the measured and simulated wood moisture content at the bottom of the beams are, however, difficult to find.

All things considered, it is the authors understanding that BSim can be used to evaluate the temperature and moisture conditions in an outdoor ventilated crawl space, on the condition that further work is carried out to obtain a more validated BSim with regards to moisture simulation.

References

[1] Bok G, Hallenberg N, Åberg O. Mass occurence of Penicillium corylophilum in crawl spaces, south Sweden. Building and Environment 44 (2009) 2413-2417.

[2] Sandberg P I, Samuelson I, Uteluftsventilerade kryprum – en riskkonstruktion? SP Provnings- och Forskningsinstitut, Borås, Sweden, 2006. [in Swedish].

[3] Matilainen M, Kurnitski J. Moisture conditions in highly insulated outdoor ventilated crawl spaces. Energy and Buildings 35 (2003) 175-187. [4] Geving S, Holme J. Høyisolerte konstruksjoner og fukt. Analyse av fukttekniske konsekvenser av økt isolasjonstykkelse i yttervegger, tak,

kryperom og kalde loft. Sintef prosjektrapport 53, Trondheim, Norge; 2010. [in Norwegian]. [5] Brandt E. Fugt i bygninger (Moisture in buildings), SBi guideline 224. 2nd ed. Copenhagen: Danish Building Research Institute, Aalborg

University. 2013. [in Danish]. [6] Møller EB, Brandt E, Pedersen ES. Småhuse – Klimaskærmen (Small houses – Building envelope), SBi guideline 267. Copenhagen: Danish

Building Research Institute, Aalborg University. 2016. [in Danish and accessible on www.anvisninger.dk]. [7] Vanhoutteghem L, Morelli M, Nielsen A. Moisture problems in highly insulated constructions, Literary study, measurements and calculation.

Copenhagen: Danish Building Research Institute, Aalborg University. 2017. [Under publication and in Danish]. [8] http://www.sbi.dk/indeklima/simulering/bsim-building-simulation/copy_of_artikler-og-papers/artikler-og-papers [accessed on 1 February

2017], last updated 19 November 2009. [9] Hagentoft C, Blomberg T. Design rules for crawl spaces – CRAWL 2.0. http://www.buildingphysics.com/crawl.htm [[accessed on 1 February

2017], last updated September 2003.

Page 7: Can crawl space temperature and moisture conditions be calculated with a whole ... · 2017. 12. 20. · BSim (Building Simulation) [9] was used to calculate the hygrothermal behaviour

Lies Vanhoutteghem et al. / Energy Procedia 132 (2017) 688–693 693 Author name / Energy Procedia 00 (2017) 000–000 5

In Fig 5, the temperature in the floor structure under the beams is given. Deviations up to 5 C are seen, especially in the last six months for the design with insulation applied under the beams (M2-S2). Compared to measurements, simulated temperatures under the wooden beams follow the outdoor temperature more closely. Similar trends are found at the top of the wooden beams, however with higher temperature due to influence from the indoor climate.

The moisture content in the floor structure is shown in Fig 6, where results for both the top and bottom of the beam are shown. Generally, the convergence between measurements and simulations is not as good as for the temperature. The best representation is obtained at the top of the beams, where the graphs follow the same trend, but moisture content is overestimated by the simulations during summer. The moisture content at the bottom of the beams has no convergence, and similar trends for the measured and simulated data are difficult to find.

Fig. 5. Comparison of measured (M) and simulated (S) temperatures in the floor structure under the wooden beams (15/4/2015-15/4/2016).

Fig. 6. Comparison of measured (M) and simulated (S) moisture content in the floor structure in the period 15/4/2015-15/4/2016.

4. Discussion

As the behaviour in a crawl space cannot simply be described based on boundary conditions from the outdoor climate, there exist specific calculations tools, e.g. CRAWL to determine the heat and moisture conditions in crawl spaces [9]. Instead of using a specific calculation tool developed for only crawl spaces, the whole building hygrothermal simulation tool BSim was used in this paper.

Comparison between measurements and simulations of temperature and moisture content/relative humidity in the floor structure and the crawl space has shown both good and poor convergences. Large deviations between measured and simulated results were found for relative humidity and moisture content in the crawl space and floor structure. Of note is that BSim is not originally developed to perform moisture simulations. BSim’s moisture module includes calculation of the dynamic moisture balance in a zone (crawl space) and the moisture accumulation in the constructions (floor structure). The moisture accumulation in the constructions is based on vapour diffusion (including hysteresis) with the surrounding zones.

05

10152025

Tem

pera

ture

[o C]

M1 M2 S1 S2

7891011121314

810121416182022

Moisture content

above beam [w

eight%]

Moi

stur

e co

nten

t un

der

beam

[Wei

ght%

]

M1 M2 S1 S2 M3 M4 S3 S4

6 Author name / Energy Procedia 00 (2017) 000–000

The relative humidity and moisture content in the crawl space and floor structure is strongly affected by the interaction between evaporation from the soil and ventilation rate in the crawl space. Exact figures for the evaporation from the soil to the crawl space depend on the climate, the construction etc. and are hard to obtain. In this preliminary study for using BSim, evaporation from the soil was included by assuming 100 % relative humidity in the soil under the crawl space. This is done in BSim by assigning a time-dependent (cosinus-profile) moisture load to the properties of the soil under the crawl space. Instead of this simplification, an advanced model for evaporation can be used in BSim. Preliminary simulations performed with both approaches showed better convergence with the measurements when assuming 100 % relative humidity in the soil instead of using the advanced model. However, it would definitely be worth to further investigate both approaches for further validation of BSim.

The amount of ventilation with outdoor air in the crawl space depends on wind conditions, location of the vents, location and surroundings of the building, obstructions in front of the vents, etc. Since no measurements on air change rates in the crawl space were available, a ventilation rate of 1.4h-1/0.35h-1 was used in the modelling. The lower ventilation rate was chosen during the winter period, as the ventilation rate showed little influence on the relative humidity in the crawl space during winter and best agreement with temperature was found with a lower ventilation rate. The higher ventilation rate was chosen during the summer period, in order to increase the simulated relative humidity in the crawl space. Further investigations showed that increasing the ventilation rate even more did not help in increasing moisture content below the wooden beams and in the crawl space during summer. Instead, it was found that evaporation from the soil has larger influence.

5. Conclusion

Measurements and simulations showed that applying 50 mm insulation under the wooden beams in the floor structure above the investigated crawl space is a good option for raising the temperature and reducing the moisture content in the beams. The wood moisture content was for this design below 20 weight%. Comparison of the measured and calculated temperature and moisture content in the crawl space and floor structure showed that the temperature has a good convergence while the relative humidity in the crawl space has good convergence the last six months compared to the first six months. Simulations of the wood moisture content above the wooden beams followed the same trend as the measurements, but with an overestimation in summer. Similar trends for the measured and simulated wood moisture content at the bottom of the beams are, however, difficult to find.

All things considered, it is the authors understanding that BSim can be used to evaluate the temperature and moisture conditions in an outdoor ventilated crawl space, on the condition that further work is carried out to obtain a more validated BSim with regards to moisture simulation.

References

[1] Bok G, Hallenberg N, Åberg O. Mass occurence of Penicillium corylophilum in crawl spaces, south Sweden. Building and Environment 44 (2009) 2413-2417.

[2] Sandberg P I, Samuelson I, Uteluftsventilerade kryprum – en riskkonstruktion? SP Provnings- och Forskningsinstitut, Borås, Sweden, 2006. [in Swedish].

[3] Matilainen M, Kurnitski J. Moisture conditions in highly insulated outdoor ventilated crawl spaces. Energy and Buildings 35 (2003) 175-187. [4] Geving S, Holme J. Høyisolerte konstruksjoner og fukt. Analyse av fukttekniske konsekvenser av økt isolasjonstykkelse i yttervegger, tak,

kryperom og kalde loft. Sintef prosjektrapport 53, Trondheim, Norge; 2010. [in Norwegian]. [5] Brandt E. Fugt i bygninger (Moisture in buildings), SBi guideline 224. 2nd ed. Copenhagen: Danish Building Research Institute, Aalborg

University. 2013. [in Danish]. [6] Møller EB, Brandt E, Pedersen ES. Småhuse – Klimaskærmen (Small houses – Building envelope), SBi guideline 267. Copenhagen: Danish

Building Research Institute, Aalborg University. 2016. [in Danish and accessible on www.anvisninger.dk]. [7] Vanhoutteghem L, Morelli M, Nielsen A. Moisture problems in highly insulated constructions, Literary study, measurements and calculation.

Copenhagen: Danish Building Research Institute, Aalborg University. 2017. [Under publication and in Danish]. [8] http://www.sbi.dk/indeklima/simulering/bsim-building-simulation/copy_of_artikler-og-papers/artikler-og-papers [accessed on 1 February

2017], last updated 19 November 2009. [9] Hagentoft C, Blomberg T. Design rules for crawl spaces – CRAWL 2.0. http://www.buildingphysics.com/crawl.htm [[accessed on 1 February

2017], last updated September 2003.