canadian fire alarm association (cfaa) presentations/can ul… · installation of fire alarm...

59
Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems Canadian Fire Alarm Association (CFAA) D. GOODYEAR FIRE CONSULTING

Upload: tranthuy

Post on 06-Mar-2018

236 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

An Overview of Changes in the New

CAN/ULC-S524-06

Installation of

Fire Alarm Systems

Canadian Fire Alarm Association (CFAA) D. GOODYEAR FIRE CONSULTING

Page 2: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

CAN/ULC - S524 - 01

STANDARD FOR THE INSTALLATION

OF

FIRE ALARM SYSTEMS

Page 3: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems
Page 4: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

• Why is the 2006 Edition Important ?

• Clarifies some items in the 2001 Edition

• Corrects some errors

• Offers some options

• States items that were good practice

• More clearly defines the intent of the 2001 Edition with respect to

Data Communication Links and system survivability

Installation of Fire Alarm

Systems

Page 5: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

Installation of Fire Alarm

Systems – CAN/ULC-S524-01 & CAN/ULC-S524-06

– Review current changes from old standard to new standard

2001 2006

QuickTime™ and aTIFF (LZW) decompressor

are needed to see this picture.

Page 6: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006 Glossary Update

• Air Sampling Type Detector

Page 7: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

Air Sampling Type Detector

Page 8: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006 Glossary Update

• Air Sampling Type Detector

• DCLC Data Communications Link Style C

• Manual Station

Page 9: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006 Glossary Update

• Status Change Confirmation (Smoke Detector Alarm Verification)

• Temporary or Intermittent Sound Sources

Page 10: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006 Glossary Update

• Data Communication Link Style C

2001 2006

DCLR DCLC

Page 11: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

•Data Communication Link Style C

A FAULT WITHIN ONE

FLOOR AREA:

• ….shall not prevent the normal operation of other input or output field devices in another floor area.

60th

Floor

50th

Floor

40th

Floor

30th

Floor

20th

Floor

10th

Floor

DCC

DCL -C

Primary

Wiring

Circuit DCL-C

Alternate

Wiring

Circuit

TRANSPONDER

TRANSPONDER

TRANSPONDER

TRANSPONDER

TRANSPONDER

TRANSPONDER

TRANSPONDER

70 STOREY

OFFICE

TOWER

Page 12: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006 Glossary Update

DELETED TERMS • Output Circuit

• Redundant Wiring Circuit

• Spacing

Page 13: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006 Requirements Update

– Requirements of Fire Alarm Systems

2006

Page 14: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006 Power Supply Update

2006

Page 15: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006 Plans and Specifications Update

2006

– Fire alarm plans and specifications shall include a

complete and detailed description of the following

Page 16: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006 Plans and Specifications Update

2006

Page 17: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006 Electrical Supervision Update Items G, H & J 2006

Page 18: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006 Electrical Supervision Update

2006

– Conventional Two Stage Systems • Input circuits for first stage and second stage shall not share conductors

Page 19: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006 Separation of Wiring Update

2006

– Class A Wiring Circuit, DCL Style A, DCL Style C • Defines the distance between the primary and alternate wiring circuit paths

Page 20: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006 Separation of Wiring Update – Class A Wiring Circuit, DCL Style A, DCL Style C

• Defines the distance between the primary and alternate wiring circuit paths

2006

Page 21: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006 Separation of Wiring Update – Class A Wiring Circuit, DCL Style A, DCL Style C

• Defines the distance between the primary and alternate wiring circuit paths

2006

Page 22: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006 Separation of Wiring Update

2006

– Class A Wiring Circuit, DCL Style A, DCL Style C

Page 23: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006 Separation of Wiring Update

– Class A Wiring Circuit, DCL Style A, DCL Style C

2006

Page 24: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006 Separation of Wiring Update

2006

Page 25: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006 Installation Of Fire Alarm

Equipment Update

2006 – Height of Control Units and Transponders

1800 mm

Page 26: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

• Manual stations shall be installed on both sides of a

series of doors exceeding 12 m in total width, and within

1500 mm of each side of the opening.

Manual Stations

Exceeding 12 m

Page 27: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006

6.4 m

= 0.7 x 9.1 m

2006 Installation Of Fire Alarm

Fire Detection SMOKE DETECTON

Irregular shaped rooms

Maximum Distance 6.4 m

Page 28: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006

2006 Installation Of Fire Alarm

Fire Detection

HEAT DETECTON

HIGH CEILINGS

Page 29: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

RETURN

SUPPLY FILTER COOLING HEATING COIL

DUCT SMOKE DETECTOR

2006 Installation Of Fire Alarm

Duct Smoke Detection

Page 30: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006 Installation Of Fire Alarm

Duct Smoke Detection

RETURN

SUPPLY FILTER COOLING HEATING COIL

DUCT SMOKE DETECTORS

Page 31: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

Audible and Visible Signal Devices

CEILING

FLOOR

2300 mm

Page 32: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

Audible Signal Devices for Use in Suites of

Residential Occupancy

Where silencing means are separately installed or incorporated in the audible

signal device, the silencing means shall be clearly identified and located not

less than1200 mm and not more than 1400 mm above the finished floor level

measured from the centre of the silencing means.

Touch to

Silence

Page 33: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006 Audible and Visible Signal Devices

• Visible signal devices

that are used to advise occupants that a fire emergency exists

• Two or more visible signal devices in corridors or rooms located in the same field of view shall flash in synchronization

Page 34: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

Audible and Visible Signal Devices

CEILING

FLOOR

2000 mm 2400 mm

• Wall-mounted visible signal devices shall be installed such that

the entire lens is not less than 2000 mm and not more than 2400 mm above the finished floor.

Page 35: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006 Audible and Visible Signal Devices

Page 36: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

Incorrect

Spacing

6.1m 12.2m

Room Spacing Allocation - Incorrect

• Four 15 cd strobes in 12.2m x 12.2m room

Visible

Appliance

(Typical)

15cd

Page 37: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

Room Spacing Allocation - Correct

• CAN/ULC-S524-06 clause 5.4.5.8

– Subdivide the room into multiple

squares

– Install four 15 candela appliances

12.2m

12.2m

6.1m

6.1m

6.1m

6.1m

Page 38: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

System Survivability

• There is an expectation that life safety systems should continue to provide some level of performance in a fire or a disaster.

• Survivability of the fire alarm system during a fire is the new concern.

• Data Communications Links (DCLs) in new fire alarm systems are at the heart of the issue of

the reliability and survivability. • .

Page 39: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

• 2 Fore2st Laneway

2 Forest Laneway

North York

Page 40: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

System survivability what is it?

Fatal fire in a Toronto high-rise fire

six people died, the issue of the early failure of life safety systems during the fire was examined.

• Failure of the exit lighting

• Failure of the emergency lighting

• Failure of the fire alarm annunciation

• Failure of the fire alarm signalling

• Failure of the voice communication system

Page 41: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

What is a DCL?

DATA COMMUMICATIONS LINK

• The data channel between control units and/or

transponders and annunciators

The fire alarm network

____________________________________

• Active field devices

Addressable fire alarm devices

Page 42: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006

Data Communication Link Table 3

Addressable fire alarm devices

Page 43: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

ADDRESSABLE MANUAL STATION

ADDRESSABLE SMOKE DETECTOR

ADDRESSABLE HEAT DETECTOR

Capacity of addressable devices

DCLA

300 Device Limit per loop

2 loops shown

Data Communication Link Table 3

Addressable Devices 2006

Zone 1

Page 44: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

ADDRESSABLE MANUAL STATION

ADDRESSABLE SMOKE DETECTOR

ADDRESSABLE HEAT DETECTOR

Capacity of addressable devices

DCLB

200 Device Limit per loop

2 loops shown

Data Communication Link Table 3

Addressable Devices 2006

Zone 1

Page 45: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

ADDRESSABLE MANUAL STATION

ADDRESSABLE SMOKE DETECTOR

ADDRESSABLE HEAT DETECTOR

Capacity of addressable devices

DCLC

300 Device Limit per loop

Isolators used

2 loops shown

Data Communication Link Table 3

Addressable Devices 2006

Multiple

Zones

Page 46: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

4.2.7

When a data loop serves more than one

floor area,

a fault within one floor area cannot affect

normal operation of devices in another

floor area.

Addressable Devices DCLs

Page 47: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

FIRE ALARM

CONTROL PANEL

OR TRANSPONDER

FIRST FLOOR

FOURTH FLOOR

THIRD FLOOR

SECOND FLOOR

ADDRESSABLE MANUAL STATION

ADDRESSABLE SMOKE DETECTOR

ADDRESSABLE HEAT DETECTOR

FAULT ISOLATION MODULE

DATA COMMUNICATION

LINK

Fault isolation

module pairs

Addressable devices

Data Communication Link Table 3

Addressable Devices 2006

300 Device Limit

Page 48: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

How to install fault isolation

modules

Do not install the fault isolation modules back to back

5.14.6

Page 49: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

400mm

How to install fault isolation

modules

Offset the fault isolation modules

5.14.6

Page 50: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

How to install fault isolation

modules

Fault isolation modules serving a single device in an exit

5.14.8

ZONE 1

ZONE 2

STAIR

Page 51: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

Data Communication Link Table 3

Network Data Communications Link 2006

Only DCLC permitted

Fire Alarm

Control Unit

Fire Alarm

Control Unit

Fire Alarm

Control Unit

Fire Alarm

Control Unit

One fault

does not disable the system Data communications

1000 Addressable device limit for entire system

Fire Alarm

Annunciator

DCLA or DLCB

Data communication

Permitted here

Page 52: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

Data Communication Link Table 3

Network Data Communications Link 2006

Must meet Large Scale Network and only DCLC permitted

Fire Alarm

Control Unit

Fire Alarm

Control Unit

Fire Alarm

Control Unit

Fire Alarm

Control Unit

Data communications

More than1000 Addressable device limit for entire system

Fire Alarm

Annunciator

DCLA or DLCB

Data communication

Permitted here

Page 53: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006

Data Communication Link Table 3

Network Data Communications Link

• More than1000 Addressable device limit

for entire system

• Must meet Large Scale Network

• Only DCLC permitted

Page 54: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

2006

Data Communication Link

Network Data Communications Link

Large Scale Network

• Each transponder has STAND ALONE capability

• Degraded mode capability

• Each transponder must have • Signal silence

• Reset

• Trouble silence

• Stand alone indicator

• In high buildings per NBC

• At least one ADDITIONAL transponder with

– Full annunciation per NBC

– Means to transmit voice communication with “ ALL CALL” capability

• Transponders must be in an electrical room with a 1 hour fire separation

Page 55: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

INTERCONNECTION TO THE FIRE

SIGNAL RECEIVING CENTRE

• The interconnection wiring from the fire alarm control unit

or transponder to the fire signal receiving centre shall

comply with CAN/ULC-S561, Installation and Services for

Fire Signal Receiving Centres and Systems.

Page 56: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

INTERCONNECTION TO THE FIRE

SIGNAL RECEIVING CENTRE

End of Line Device for supervision

Independent Terminal Cabinet Conductors in raceway

for mechanical

protection

Page 57: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems
Page 58: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

Dave Goodyear D. GOODYEAR FIRE CONSULTING

Page 59: Canadian Fire Alarm Association (CFAA) PRESENTATIONS/CAN UL… · Installation of Fire Alarm Systems An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems

Installation of Fire Alarm Systems

D. GOODYEAR FIRE CONSULTING

Installation of

Fire Alarm Systems

CAN/ULC-S524-06

Canadian Fire Alarm Association (CFAA)

D. GOODYEAR FIRE CONSULTING