canalis busbar trunking product range · of joints, mounting and tap-offs means that canalis busbar...

9
Canalis ® Busbar trunking product range

Upload: others

Post on 02-Feb-2020

45 views

Category:

Documents


0 download

TRANSCRIPT

Canalis®

Busbar trunkingproduct range

MV/LV transformers

KDPKBAKBB

KNA

KSA KVC

KHFKTAKTC

KSR

Lighting distribution

Low power distribution

Medium power transport and distribution

Medium power rising main

High power transformer-switchboard & switchboard-switchboard interconnection transport & distribution

Canalis Busbar trunking provides the interconnection for Schneider Electric total solutions

20 and 40A

KDPKBAKBB

KSA

KVC

KVC

KDPKBAKBB

KSA

KNA

KTAKTC

KTAKTC

KSR

KHF

40 to 100A

100 and 800A

1000 and 5000A

400 to 800A

1

4

7

6

2

3

4

1

5

Canalis® From transformer to loadsbusbar trunking meets all low voltage electrical distribution needs

Masterpact air circuit breakers

3

Compact NS moulded case circuit breakers

4

Multi 9 miniaturecircuit breakers

Control & commandproducts

5

Okken switchboards

Multi-Formswitchboards

2

Prisma ‘P&G’,Powerpact 4panelboards

I-Line panelboards

6

Isobar 4 Evofinal distributionboards

LoadCentre KQ+final distributionboards

7

100A 5m & 3m 3 or 4 + PE 1m or 0.5m 13.6 kA 660V 25 to 250A • Tap-off units160A 22 kA for modular250A 28 kA circuit breakers or fuses400A 1m or 0.5m 49.2 kA 25 to 400A500A 55 kA630A 67.5 kA800A 78.7 kA

100 to 800AIP52, IP54

Straight lengths Tap-off units Other items

Rated Length Number of Distance Peak Rated Rated Accessoriescurrent of conductors between short-circuit voltage current or options trunking tap-off outlets current

20A 24m 2 or 4 1.5m 3.6 kA 660V 10 &16A • Fixing 192m 3m devices • Modular prefabricated leads

20AIP54

KBA:25A 3m & 2m 2 or 4 1m or 0.5m 4.4 kA 500V 10 &16A • Flexible length40A 9.6 kA 500V 10 &16A • Metal cable duct • Painted white

KBB:25A 3m & 2m 2 or 4 1m 4.4kA 500V 10 &16A • Flexible length40A (double 9.6 kA 500V 10 &16A • Metal circuit) cable duct 2 + 2 • Painted 2 + 4 white 4 + 4

25 & 40AIP54

40A 2m & 3m 4 + PE 1m or 0.5m 6 kA 500V 16A Tap-off units 63A 11 kA 25A for modular100A Additional 14 kA 32A circuit remote 40A breakers control bus or fuses on option

40 to 100AIP41, IP54

Lighting distribution: Canalis KBA & KBB

Electrical distribution: Canalis KSA

Lighting distribution: Canalis KDP

Electrical distribution: Canalis KNA

Lighting & electrical distribution offer

Straight lengths Tap-off units Other itemsStraight lengths Tap-off units Other items

Rated Length Number of Distance Peak Rated Rated Accessoriescurrent of conductors between short-circuit voltage current or options trunking tap-off outlets current

200 1m 2m 3 or 4 + PE At the 24 to 84 kA 1000V Mono-circuit • Tap-off unitsto 800A 3m 4m & trunking joints and for compact made to multi-circuits NS circuit measure 32 to 400 A breakers or fuses

200 to 800AIP31/IP54

400 to 800AIP54

1000 4m & 3 or 4 + PE 1m or 2m 84 to 209 kA 1000V 25 to 1250 A • Tap-off unitsto 5000A made to for Compact measure NS or circuit breakers or fuses

1000 to 5000AIP52/IP54

1000 5m & 3m 3 or 4 + PE At the 58 to 310kA 750V 63 to 1000A • Tap-off units to 4500A trunking joints for Compact and/or NS or C every metre circuit breakers or fuses

1000 to 4500AIP31

400A 2.5m 4 + PE 0.5m 49.2 kA 660V 25 to 400A • Tap-off units 630A 2m 4m 67.5 kA for modular 800A 3m 78.7 kA circuit breakers or fuses • Made to measure fire barriers

Canalis®

Power transport & distribution offer

CANALIS KCANALIS KH

elemecanique

elemecanique

T

Transport, distribution & Rising main:Canalis KVA/KVC

Transport, distribution & Rising main:Canalis KTA/KTC

Distribution: Canalis KHF

Prefabricated and reliable systems that guaranteethe total quality of the installation.

Rising main: Canalis KSR

Canalis®

Using Fast track is easy and quick

■ The lengths are easy to join. The mechanical and electricalassembly is completed by simply pushing together the lengthsand tightening with a locking screw

■ Easy to mount with a single bracket every 3 metres

■ Silver copper contacts and a foolproof locking deviceguarantee the quality and reliability of your connections

Safety built in

Silver copper contacts and a foolproof locking device ensure allconnections with Fast track are safe and secure. All live parts areinaccessible for complete safety and the installed busbar trunkingautomatically complies with current regulations.

Perfect for a wide range of applications

Applications that benefit from CanalisFast track include:

■ Small and medium sized factories

■ Retail buildings

■ Storage buildings

■ Workshops

■ Leisure facilities

■ University and college buildings

Future upgrades are easy

When there is a need to upgrade an installation, the ‘click’ systemof joints, mounting and tap-offs means that Canalis Busbartrunking is easier to work with than traditional cable.

Save time & reduce costsThe installation of Canalis Busbar trunking iseasy and because of this it is quick. This majorreduction in labour time means you can make atotal cost saving of up to 34% compared withusing cable for the same installation.

Total cost savingof up to 34%compared withusing cable

High levels of safety and is easy toupgrade for future requirements

Fast track

Easy and quick joining of lengths

Simple fixing of trunking

Safe and reliable connection of tap-off units

Cable Canalis Busbardistribution trunking

Estimated time to install (hrs) 35.44 7.25

Estimated material cost (£) 148.56 288.86

Estimated labour cost (£) 354.40 72.50

Estimated total installed cost (£) 502.96 361.36

Total cost saving (£) 141.60

Time saving (hrs) 28.19

Time balance value (£) 281.90

The saving will vary depending on your own labour and material rates.

Available nowThe Canalis Fast track product range is readily available from anybranch of the national network of Canalis authorised distributors.

Tel: 0870 608 8 608

Canalis can save you time and money

CLICK!

CLICK!

CLICK!

Canalis versus cable: cost comparison

For many applications, Canalis not only provides a cost saving forthe initial project, but when compared with conduit or cabletrunking, the time saving obtained effectively offers many hours offree labour.

For example - on a 20m lighting run, with lighting every 2m, basedon an average installation time per metre, Canalis versus metalconduit and cable produces the following results (component ratesbased upon typical 2000 levels. Labour is given at estimated £10per hour).

KBA 25A for lighting distribution

Clic !

Clic !

������ ���

������ ��

Clic !

Clic !

• The straight lengths are self-carrying and support lighting devices.• The electrical and mechanical connections are made quickly.• Tightening the screw completes assembly.

• Two types of feed units are available for mounting on the left or right.• The connection system is identical to straight elements.• The run always ends with an end cover supplied with each feed unit.• The feed units can be adapted to single-phase and 3 phase distribution.

• C -shaped brackets are attached to the building structure using a threaded rod, a chain or a cable.

• The recommended fixing centre distance is 3m.• The max. weight allowed per C-shaped bracket is 60kg.• The luminaire suspension brackets are mounted quickly and straight

onto trunking. Preparation of the luminaires is carried out before mounting.

• The maximum weight per suspension bracket is 20kg.

• Pre-wired tap-off connectors enable instant connection of lighting equipment to the Canalis KBA run.

• They can be handled whilst live and on load.• The fixed polarity versions are equipped with a cable of a diameter of

1.5mm 2 and a length of 0.8m. • The universal versions come with phase selection and enable you to

connect the desired length of cable.

Type of Rating Length Number of Referencetrunking A m tap-off units

Single-phase 25 3 2 KBA-25EB203L + N + PE

3 phase 25 3 2 KBA-25EB4033L + N + PE

3 phase* 25 2 2 KBA-25EA4023L + N + PE

* Use for 2m Single-phase applications

Mounting Rating Supply Connection Referenceterminals PE/Ø max. A number mm2

On the left 25 10 PG21/19 mm KBA-25AA4

On the right 25 10 PG21/19 mm KBA-40SL4

Fixing brackets Description Referencefor

Trunking C- shaped bracket KBA-40ZSUc/w 3m Gripple wire system

Luminaire Suspension bracket KBA-40ZU& Trunking

Pigtail hook KBB-40ZC

Description Rating Distribution Protection ReferenceA

Connectors 16 single-phase – KBC-10CB20with L + N + PEphaseselection single-phase – KBC-10CC211

L + N + PE (Pre-wired)

single-phase cylindrical KBC-16CF21L + N + PE fuse NF

*Not supplied 8.5 x 31.5*

Polarity 10 single-phase – KBC-10CS101connectors L1 + N + PEwithphase single-phase – KBC-10CS201selection L2 + N + PEpre-wired

single-phase – KBC-10CS301L3 + N + PE

Rated insulation voltage 660VRated frequency 50/60HzDegree of protection IP54

Straight lengths Feed units Fixing devices Tap-off connectors

Canalis KBA

KBA-25EB203KBA-25EB403KBA-25EA402

KBC-10CC211KBC-10CB20

KBA-40ZU

KBC-10CS101

KBC-10CS201

KBC-10CS301

KBA-40SL4

KBA-40ZSU

KBA-40ZU

KBC-16CF21

KBA-25AA4

123

!

KNA-10LF4

KNA-06AB4KNA-10AB4

KNA-10ZA1

KNA-06LF4

KNA-03SM47

KNA-01CD2H

KNA-02CG5

KNA-01CG2

KNA-03SG4

KNA-02CM54

KNA-04EA430KNA-06EA430KNA-06ED420KNA-10EA430KNA-10ED420

KNA 40A to 100A for low power distributionRated insulation voltage 660VRated frequency 50/60HzDegree of protection IP52

• The straight lengths carry the current and supply power loads.• Electrical and mechanical connections are made quickly.• The protective earth conduction is guaranteed.• The tap-off outlets are equipped with shutters that can be operated

automatically when a tap-off connector is plugged in.

• The feed units can be mounted on the left or the right of the trunking. • The run always ends with an end cover that is supplied with the

feed unit.

• The universal fixing brackets are suitable for all fixing methods: - suspended by a threaded rod,- wall

• The recommended fixing centre distance is 3m.

• A wide range allows instant connection of loads.• The connectors and tap-off units with isolator can be operated

whilst live.• For the tap-off units, isolation is achieved by opening the cover of

the unit.

Type of Rating Length Number of Referencetrunking A m tap-off units

3 phase 40 3 3 KNA-04EA4303L + N + PE 63 3 3 KNA-06EA430

40/63 2 4 KNA-06ED420100 3 3 KNA-10EA430

2 4 KNA-10ED420

Description Rating Mounting ReferenceA

Flexible 40/63 Edgewise KNA-06LF4elbows (for internal

100 or external angle KNA-10LF4from 80° to 180°)

Mounting Rating Supply Connection ReferenceA terminals mm2 PE/Ø max.

On left 40 16 PG29/25 mm KNA-06AB4or right 63

100 35 PG48/40 mm KNA-10AB4

Fixing brackets Description Referencefor

Trunking Universal fixing bracket KNA-10ZA1

Description Rating Distribution Protection ReferenceA

Connectors 16 Single-phase with KNA-01CD2HL+N+PE with circuit-breaker phase selection (C60 N)

16 Single-phase For BS fuse* KNA-01CG2L+N+PE with

phase selection25 3 phase For BS fuse* KNA-02CG5

3L+N+PE

25 4 modules KNA-02CM54of 18 mm

Tap-off 32 3 phase For BS fuse* KNA-03SG4units 3L+N+PE

40 7 modules KNA-03SM47of 18 mm

* Not supplied

Straight lengths Feed units Fixing devices Tap-off connectors

Canalis® Fast track

KSA-10AB451

KSA-10EA430KSA-16EA430KSA-25EA430KSA-25ED420

KSA-25LC40

KSA-10DB40030

KSA-02DA50010

KSA-02CF5

KSA-05SF41KSA-10SF41KSA-16SF41

KSA-16DB411

KSA-25AB42

KSB-25FA3

KSA-25EZ1

KSA-05DA40010

KSA 100A to 250A for medium power distributionRated insulation voltage 500VRated frequency 50/60HzDegree of protection IP41

��

��

��

��

��

��

��

��

• The straight lengths carry the current and supply power loads.• Electrical and mechanical connections are made quickly.• Protective earth conduction is guaranteed.• The tap-off outlets on both sides of the trunking are fitted with shutters

that can be operated automatically when a tap-off unit or connector is plugged in.

• The feed units can be mounted on the left or the right of the trunking.• The run always ends with an end cover to be ordered separately.

• The universal fixing brackets are suitable for all mounting methods: - suspended by a threaded rod,- wall-mounted

• The recommended fixing centre distance is 3 m.

• A wide range ensures instant connection of loads.• The connectors and tap-off units with isolator switches can be

operated whilst live and off-load.• For the tap-off units, isolation is achieved by opening the cover of

the unit.• The degree of protection for the connectors and tap-off units is IP40. • An IP54 offer is available in the general catalogue.

Type of Rating Length Number of Referencetrunking A m tap-off units

3 phase 100 3 6 KSA-10EA4303L + N + PE

160 3 6 KSA-16EA430

250 3 6 KSA-25EA430

100/250 2 8 KSA-25ED420

Description Rating Mounting ReferenceA

Elbow 100 Edgewise KSA-25LC40160250

Mounting Rating Supply Connection Referenceterminals PE/Ø max. A number mm2

On left 100 5 x 16 PG29/25 mm KSA-10AB451or right Suitable for

PVC/PVCcables only

160 Lug (drilling KSA-25AB42250 240 plate)

(M10 screw)

End 100 – – KSB-25FA3cover 160

250

Fixing brackets Description Referencefor

Trunking Universal fixing bracket KSA-25EZ1

Description Rating Distribution Protection ReferenceA

Connectors 25 3 phase For BS fuse* KSE-02CG53L+N+PE

25 4 modules KSA-02DA50010of 18 mm

Tap-off 32 3 phase For BS fuse* KSE-03SG41units 3L+N+PE

50 7.5 modules KSA-05DA40010of 18 mm

80 For BS fuse* KSE-08SG41100 11 modules KSA-10DB40030

of 18 mm

100/160 compact NS* KSA-16DB411160 For BS fuse* KSE-16SG41

* Not supplied

Straight lengths Feed units Fixing devices Tap-off connectors

Merlin Gerin is a world leader in the manufacture and supply of high, medium and low voltage products for the distribution, protection, control and management of electrical systems. Its quality products, solutions and services are focused on the needs of both the commercialand industrial sectors.

Square D is a total quality organisation and its business is to put electricity to work productively and effectively, protecting people, buildings and equipment. Its low voltageelectrical distribution equipment, systems and services areused extensively in residential and commercial applications.

Telemecanique is a UK market leader and world expert inautomation and control. It provides complete solutions, withit's range of components, Modicon range of high technologyprogrammable controllers (PLCs), multiple fieldbus andethernet communication networks, HMI, motion controlsystems, variable speed drives and communicationssoftware. In addition, it offers power distribution throughprefabricated busbar trunking.

Schneider Electric’s local supportSchneider Electric is committed to supporting its customers at every stage of a project. Our 180 sales engineers, the largestdedicated sales force in the UK electrical industry, operate from 4 customer support centres.

Our sales engineers are skilled at assessing individual requirements and combined with the expert support of our product specialists, will develop the most effective and economical answer taking relevant regulations and standards fully into account.

To access the expertise of the Schneider Electric group, please call 0870 608 8 608. Each customer support centre includesfacilities for demonstrations and training, and presentation rooms fully equipped with audio visual and video, providing excellent meeting facilities.

www.schneider.co.uk

ScotlandSchneider Electric LtdUnit 11000Academy Business ParkGower StreetGlasgow G51 [email protected]

South WestSchneider Electric Ltd190 Aztec WestPark AvenueAlmondsburyBristol BS32 [email protected]

North WestSchneider Electric Ltd8 Brindley RoadCity Park Business VillageCornbrook Manchester M16 [email protected]

Greater LondonSchneider Electric Ltd2nd Floor408 StrandLondon WC2R [email protected]

Industrial systems and solutions product showroomSchneider Electric Ltd, University of Warwick Science Park, Sir William Lyons Road, Coventry CV4 7EZ

Building systems and solutions product showroomSchneider Electric Ltd, Stafford Park 5, Telford, Shropshire TF3 3BL

Energy and Infrastructure systems and solutions product showroomSchneider Electric Ltd, 123 Jack Lane, Hunslet, Leeds LS10 1BS

Product showrooms

Local customer support centres

Fax 0870 608 8 6060870 608 8 608Nationwide support on one number - call the Customer Information Centre on

member of

.co.uk

JUN 2003CAN 5309