case study for dresser rand ethylene compressor

18
Sustain.Ability. 2012 Honeywell Users Group Americas 1 Ethylene Gas Compressor Control Craig Sedelmyer

Upload: duongthuan

Post on 13-Feb-2017

259 views

Category:

Documents


7 download

TRANSCRIPT

Page 1: Case Study for Dresser Rand Ethylene Compressor

Sustain.Ability.

2012 Honeywell Users Group Americas

1

Ethylene Gas Compressor ControlCraig Sedelmyer

Page 2: Case Study for Dresser Rand Ethylene Compressor

2

Dresser-Rand Control Systems

• Integrated control and condition monitoring solutions for industrial rotating equipment since 1959.

• Advanced OEM knowledge of engine, turbine and compressor control requirements.

• More than 3000 systems installed on all makes of rotating equipment.

• Engineering and Manufacturing in US and Norway. ISO 9001-2008 Quality Certified.

• 100 employees Houston, 20 employees Kongsberg.

Headquartered in Houston Texas

Page 3: Case Study for Dresser Rand Ethylene Compressor

3

Dresser-Rand Control Systems

Established 1959ISO 9001 Certified 1995

Kongsberg Norway

Houston, Texas

Established 1966

ISO 9001 Certified 1992

Page 4: Case Study for Dresser Rand Ethylene Compressor

4

Dresser-Rand Control Systems• Complete Controls Solutions for critical, complex

rotating equipment:• Aeroderivative Gas Turbines• Industrial Gas Turbines• Steam Turbines• Centrifugal Compressors• Reciprocating Compressors• Generator Control

• Compressor anti-surge, capacity and load sharing• Generator control• Advanced Condition Monitoring• Station Control Systems• Safety Shutdown Systems• SCADA• Instrumentation and accessories• Turnkey project management

Page 5: Case Study for Dresser Rand Ethylene Compressor

5

Dresser-Rand Control Systems - Flexibility

• Numerous PLC and controllers supported

• Simplex, Redundant, TMR• The right system for each customer

and application• Control platforms that meet

customer’s individual needs• Designed to easily integrate with

existing plant equipment and information systems

• Simplifies operator training and maintenance requirements

• Custom packaged with various accessories

Page 6: Case Study for Dresser Rand Ethylene Compressor

6

Envision TM Condition Monitoring

• Integrate operations, performance & diagnostics

• Homogenous HMI combining:• Process mimics• Surge maps• Compressor Performance• Gas Turbine Performance • Vibration Diagnostics• Alarms • Trending• Consolidated Reports• Client specific screens

• WWW Remote Access for a “Local Experience”• Predictive Diagnostics• Lowered Operating Costs

Page 7: Case Study for Dresser Rand Ethylene Compressor

7

Dresser- Rand Controls / Chemtex Project

• New Motor Driven Reciprocating Compressor– Greencol Facility Taiwan Expansion– Eliminate traditional discrete PLC control– Maintain OEM warranty and control schemes– Embed total train control into C300 50 ms Controller

MACCRL 80,000 lbs. (355.9 kN)MACGL 100,000 lbs. (444.8 kN)Maximum HP 8,225 (6133 kW)Standard Strokes 8.5 to 12 inch (216 to 305 mm)Crankshaft Diameter 9.5 inches (241 mm)Main Bearing Length 4.50 inches (114 mm)Piston Rod Diameter 3.25 inches (83 mm)Number of Throws 2, 4, or 6Cylinder Bore Range 5 to 38.5 inches (127 to 902 mm)

Presenter
Presentation Notes
Greencol Taiwan Corporation ( GTC) making 100ktes/ yr of ethylene for bio-ethanol.
Page 8: Case Study for Dresser Rand Ethylene Compressor

8

Dresser- Rand Controls / Chemtex Project

• Compressor Start Permissives– YS-6320A) Auxiliary Lube Oil Pump In AUTO Position – (HS-6330D) DCS Process Ready– (ZS-63100) Barring Device Not Engaged– (ZS-63101) Locking Device Not Engaged– Compressor Unloaded– Compressor Stopped– All Unit Shutdowns Cleared– Capacity Control Unloaded

Page 9: Case Study for Dresser Rand Ethylene Compressor

9

Dresser- Rand Controls / Chemtex Project

Page 10: Case Study for Dresser Rand Ethylene Compressor

10

Dresser- Rand Controls / Chemtex Project

• Compressor Start Sequence – Lube Oil System Pressure and Time– Main Drive Motor (MCC)

Page 11: Case Study for Dresser Rand Ethylene Compressor

11

Dresser- Rand Controls / Chemtex Project

Page 12: Case Study for Dresser Rand Ethylene Compressor

12

Dresser- Rand Controls / Chemtex Project

• Compressor Capacity Control– Load Delay Timers– Increment and Decrement Capacity Control steps– Adherence to Factory Engineered Matrix

Page 13: Case Study for Dresser Rand Ethylene Compressor

13

Dresser- Rand Controls / Chemtex Project

Page 14: Case Study for Dresser Rand Ethylene Compressor

14

Dresser- Rand Controls / Chemtex Project

• Compressor Aux Lube Oil Pump Control – Local HOA Interface – Critical to emergency shutdowns

• Compressor Lube Oil Heater Control– Closed loop control – Interlocked with frame level

Page 15: Case Study for Dresser Rand Ethylene Compressor

15

Dresser- Rand Controls / Chemtex Project

Page 16: Case Study for Dresser Rand Ethylene Compressor

16

Dresser- Rand Controls / Chemtex Project

• Compressor Normal and Emergency Shutdown Sequence

• Compressor Alarm Handling– See attached Cause and Effect Chart

Page 17: Case Study for Dresser Rand Ethylene Compressor

17

• Centrifugal Compressor Surge Control– Dresser-Rand Proprietary Surge

Controller Evaluation (Patented) – Initial Surge Testing Title using C 300

20 ms w/CAB Support – Test Set Up was Simplex Controller &

Simplex I/O. 1 AI, 1 AO 1 DI ,1 DO– Initial results have shown that C 300

20ms can safely execute up to 8 surge loops (no sequence logic)

– Adding logic reduced performance to only six surge loops!

– More formal testing scheduled for July

Dresser- Rand Controls Surge Control

Page 18: Case Study for Dresser Rand Ethylene Compressor

18

Dresser- Rand Controls / Chemtex Project