catalog ha 35.51 fixed-mounted circuit-breaker switchgear nxplus

Upload: bajrica

Post on 24-Feb-2018

254 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    1/64

    siemens.com/medium-voltage-switchgear

    Totally Integrated Power NXPLUS

    Fixed-Mounted Circuit-Breaker Switchgear

    Type NXPLUS up to 40.5 kV, Gas-InsulatedMedium-Voltage Switchgear

    Edition2015

    CatalogHA 35.51

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    2/64

    2 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    R-HA35-090

    eps

    R-HA35-092

    eps

    R-HA35-156 eps

    ApplicationPublic power supplysystem

    ApplicationSteel works

    ApplicationOffshore wind park

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    3/64

    3Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Application Page

    Types, typical uses, ratings 4 and 5

    Requirements

    Features, safety, technology 6 and 7

    Technical Data

    Electrical data 8 and 9

    Room planning 10

    Shipping data, classification 11

    Dimensions

    Front views, sections,

    floor openings, fixing points 12 to 21

    Product Range

    Single-busbar panels 22 and 23

    Double-busbar panels 24 to 27

    Design

    Single-busbar panel design 28

    Double-busbar panel design 29

    Components

    Vacuum circuit-breaker 30 and 31

    Three-position disconnector 32 and 33

    Busbar, module coupling 34

    Current transformers 35

    Voltage transformers 36 to 38

    Horizontal pressure relief duct 39 and 40

    Panel connection with outside cone 41 to 43

    Installation possibilities with outside cone 44 and 45

    Panel connection with inside cone 46 and 47Installation possibilities with inside cone 48 and 49

    Indicating and measuring equipment 50 to 54

    Protection, control, measuring

    and monitoring equipment 55 to 58

    Standards

    Standards, specifications, guidelines 59 and 60

    Fixed-MountedCircuit-Breaker

    SwitchgearType NXPLUS up to40.5 kV, Gas-InsulatedMedium-Voltage Switchgear

    Catalog HA 35.51 2015

    Invalid: Catalog HA 35.51 2013

    www.siemens.com/medium-voltage-switchgear

    Contents

    The products and systems described in this catalog are man-ufactured and sold according to a certified managementsystem (acc. to ISO 9001, ISO 14001 and BS OHSAS 18001).

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    4/64

    4 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Types

    Application

    Panel for

    double busbar

    Panel for

    single busbar

    R-HA35.5

    1-76

    tif R

    -HA

    35.5

    1-77

    tif

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    5/64

    5Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Fixed-mounted circuit-breaker switchgear NXPLUS is

    a factory-assembled, type-tested, metal-enclosed,

    SF6-insulated switchgear with metallic partitions 2)for

    single-busbar and double-busbar applications for indoor

    installation.

    It is used in transformer and switching substations,

    e. g., in: Power supply companies Power stations Cement industry Automobile industry Iron and steel works Rolling mills

    Textile, paper and food industries Chemical industry Petroleum industry Pipeline installations Electrochemical plants

    Petrochemical plants Diesel power plants Emergency power supply installations Traction power supply systems.

    Typical uses, ratings

    Application

    Double-busbar panels

    Rated voltage max. kV 12 24 36

    Rated frequency Hz 50 / 60

    Rated short-duration kVpower-frequency withstand voltage

    28 50 70

    Rated lightning kVimpulse withstand voltage

    75 125 170

    Rated short-circuit max. kAbreaking current

    31.5

    Rated short-time max. kAwithstand current, 3 s

    31.5

    Rated short-circuit max. kAmaking current

    80 / 82

    Rated peak max. kAwithstand current

    80 / 82

    Rated normal current max. Aof the busbar 2500 2500 2500

    Rated normal current max. Aof the feeders

    2500 2500 2500

    Electrical data (maximum values) and dimensions

    Single-busbar panels

    Rated voltage max. kV 12 24 36 40.5

    Rated frequency Hz 50 / 60

    Rated short-duration kVpower-frequency withstand voltage

    28 50 70 85

    Rated lightning kVimpulse withstand voltage

    75 125 170 185

    Rated short-circuit max. kAbreaking current

    31.5

    Rated short-time max. kAwithstand current, 3 s

    31.5

    Rated short-circuit max. kAmaking current

    80 / 82

    Rated peak max. kAwithstand current

    80 / 82

    Rated normal current max. Aof the busbar

    2000 1) 2000 1) 2000 1) 2000

    Rated normal current max. Aof the feeders

    2000 1) 2000 1) 2000 1) 2000

    1) 2500 A on request

    2) Corresponds to metal- clad accordingto former standard IEC 60298

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    6/64

    6 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Requirements

    Environmental independence

    Hermetically tight, welded switchgear vessels made ofstainless steel as well as single-pole solid insulation makethe parts of the primary circuit under high voltage ofNXPLUS switchgear Insensitive to certain aggressive ambient conditions,

    such as: Air humidity Dust Condensation

    Tight to ingress of foreign objects, such as: Dust Pollution Small animals Humidity

    Independent of the site altitude.

    Compact design

    Thanks to the use of SF6insulation, compact dimensions arepossible up to 40.5 kV.Thus:

    Existing switchgear rooms and substation rooms can beused effectively

    New constructions cost little Costly city-area space is saved.

    Maintenance-free design

    Switchgear vessels designed as sealed pressure systems,maintenance-free switching devices and enclosed cableplugs ensure: Maximum supply reliability

    Personnel safety Sealed-for-life design according to IEC 62271-200

    (sealed pressure system) Installation, operation, extension and replacement

    without SF6gas work Reduced operating costs Cost-efficient investment No maintenance cycles.

    Innovation

    The use of digital secondary systems and combinedprotection and control devices ensures:

    Clear integration in process control systems Flexible and highly simplified adaptation to new systemconditions and thus to cost-efficient operation.

    Service life

    Under normal operating conditions, the expected servicelife of gas-insulated switchgear NXPLUS is at least 35 years,probably 40 to 50 years, taking the tightness of the

    hermetically welded switchgear vessel into account. Theservice life is limited by the maximum number of operatingcycles of the switchgear devices installed: For circuit-breakers, according to the endurance class

    defined in IEC 62271-100

    For three-position disconnectors and earthing switches,according to the endurance class defined in IEC 62271-102.

    Personal safety

    Safe-to-touch and hermetically sealed primary enclosure Cable terminations, busbars and voltage transformers are

    surrounded by earthed layers All high-voltage parts including the cable terminations,

    busbars and voltage transformers are metal-enclosed

    Capacitive voltage detecting system to verify safe isolationfrom supply

    Operating mechanisms and auxiliary switches safelyaccessible outside the primary enclosure (switchgearvessel)

    Due to the system design, operation is only possible withclosed switchgear enclosure

    Standard degree of protection IP 65 for all high-voltageparts of the primary circuit, IP 3XD for the switchgearenclosure according to IEC 60529 and VDE 0470-1

    High resistance to internal arcs by logical mechanicalinterlocks and tested switchgear enclosure

    Panels tested for resistance to internal faults up to 31.5 kA

    Logical mechanical interlocks prevent maloperation Make-proof earthing by means of the vacuum

    circuit-breaker.

    Security of operation

    Hermetically sealed primary enclosure independent ofenvironmental effects (pollution, humidity and smallanimals)

    Maintenance-free in an indoor environment (IEC 62271-1and VDE 0671-1)

    Operating mechanisms of switching devices accessibleoutside the primary enclosure (modules)

    Metal-coated or metal-enclosed, plug-in inductive voltagetransformers mounted outside the SF6switchgear vessel Current transformers as ring-core current transformers

    mounted outside the SF6switchgear vessel Complete switchgear interlocking system with logical

    mechanical interlocks Welded switchgear vessels, sealed for life Minimum fire load Type and routine-tested Standardized and manufactured using numerically

    controlled machines

    Quality assurance in accordance with DIN EN ISO 9001 More than 500,000 switchgear panels of Siemens in

    operation worldwide for many years Option: Resistance against earthquakes (single busbar

    only).

    Reliability

    Type and routine-tested Standardized and manufactured using numerically

    controlled machines Quality assurance in accordance with DIN EN ISO 9001 More than 500,000 switchgear panels of Siemens in

    operation worldwide for many years.

    Features Safety

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    7/64

    7Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Technology

    Requirements

    General

    3-pole enclosure of the primary part via modules made ofstainless steel

    Insulating gas SF6 Three-position switch as busbar disconnector and feeder

    earthing switch

    Make-proof earthing by means of the vacuumcircuit-breaker

    Panel spacing of incoming and outgoing feeder panels:600 mm (1200 mm as of 2300 A feeder current)

    Hermetically tight, welded switchgear vessel made ofstainless steel

    1-pole solid-insulated, screened module coupling in boltedtechnology

    Cable connection with inside-cone or outside-cone plug-insystem, or for connection of solid-insulated bars

    Wall-standing or free-standing arrangement Cable connection access from front or rear

    Low-voltage door hinges on the left or on the right Installation and extension of existing switchgear at bothends without gas work and without modification ofexisting panels

    Panel-internal control cables in metallic wiring ducts.

    Interlocks

    According to IEC 62271-200 and VDE 0671-200 Logical mechanical interlocks prevent maloperation Three-position disconnector can only be operated with

    circuit-breaker in OPEN position Circuit-breaker can only be operated with three-position

    switch in end position and operating lever removed

    Three-position disconnector interlocked against thecircuit-breaker in circuit-breaker panels and in bussectionalizers with one panel spacing

    Feeder earthed locking device Locking device for three-position switch

    The following interlocks can be fulfilled by placing thepadlock accordingly: Padlock on the left:Three-position switch DISCONNECTING function cannotbe operated,three-position switch READY-TO-EARTH function can beoperated Padlock in the center:

    Control gate blocked, no switching operations possible Padlock on the right:Three-position switch DISCONNECTING function can beoperated,three-position switch READY-TO-EARTH function cannotbe operated

    Option: Cable compartment cover interlocked against thethree-position switch (circuit-breaker panel, disconnectorpanel)

    Option: Electromagnetic interlocks Option: Actuating openings of the circuit-breaker can be

    padlocked Option: Feeder locking device.

    Modular design

    Replacement of the circuit-breaker module without gaswork

    Low-voltage compartment removable, plug-in bus wires.

    Instrument transformers

    Can be removed without altering the position of thebusbar and circuit-breaker modules (outside the gascompartments)

    Current transformers not subjected to dielectric stress Easy replacement of ring-core current transformers Metal-coated or metal-enclosed, plug-in and disconnect-

    able voltage transformers.

    Vacuum circuit-breaker

    Maintenance-free under normal ambient conditionsaccording to IEC 62271-1 and VDE 0671-1

    No relubrication or readjustment Up to 10,000 operating cycles Vacuum-tight for life.

    Secondary systems

    Customary protection, measuring and control equipment Option: Numerical multifunction protection relay with

    integrated protection, control, communication, operatingand monitoring functions

    Can be integrated in process control systems.

    Standards

    (see page 59)

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    8/64

    8 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Electrical data, filling pressure, temperature for single-busbar switchgear

    Technical Data

    Commonelectricaldata,fillingpressureandtemperature

    Rated insulation level Rated voltage Ur kV 12 24 36 40.5Rated short-duration power-frequency withstand voltageUd: phase-to-phase, phase-to-earth, open contact gap kV across the isolating distance kV

    2832

    5060

    7080

    8590

    Rated lightning impulse withstand voltage Up: phase-to-phase, phase-to-earth, open contact gap kV across the isolating distance kV

    7585

    125145

    170195

    185218

    Rated frequency fr Hz 50 / 60Rated normal current Ir2) for the busbar up to A 2000 1) 2000 1) 2000 1) 2000Rated filling level pre3) Minimum functional level pme3)

    Ambient air temperature

    Data of the switchgear panels

    Circuit-breaker panelOutside cone1250 A

    Rated normal current Ir2) A 1250 1250 1250 Rated short-timewithstand current Ik

    for switchgear with tk= 3 s up to kA 31.5 31.5 31.5

    Rated peak withstand current Ip 50 / 60 Hz up to kA 80 /82 80 /82 80 /82 /

    Rated short-circuit making current Ima 50 /60 Hz up to kA 80 /82 80 /82 80 /82 /Rated short-circuit breaking current Isc up to kA 31.5 31.5 31.5

    Electrical endurance ofvacuum circuit-breakers

    at rated normal currentat rated short-circuit breaking current

    Circuit-breaker paneland bussectionalizerInside cone1250 A1600 A2000 A

    Rated normal current Ir2) A A A

    125016002000

    125016002000

    125016002000

    125016002000

    Rated short-timewithstand current Ik

    for switchgear with tk= 3 s up to kA 31.5 31.5 31.5 31.5

    Rated peak withstand current Ip 50 / 60 Hz up to kA 80 /82 80 /82 80 /82 80 /82Rated short-circuit making current Ima 50 /60 Hz up to kA 80 /82 80 /82 80 /82 80 /82Rated short-circuit breaking current Isc up to kA 31.5 31.5 31.5 31.5

    Electrical endurance ofvacuum circuit-breakers

    at rated normal currentat rated short-circuit breaking current

    Circuit-breaker panelSeparateinside cone1250 A1600 A

    2000 A

    Rated normal current Ir2) A A A

    125016002000

    125016002000

    125016002000

    125016002000

    Rated short-timewithstand current Ik

    for switchgear with tk= 3 s up to kA 31.5 31.5 31.5 31.5

    Rated peak withstand current Ip 50 / 60 Hz up to kA 80 /82 80 /82 80 /82 80 /82

    Rated short-circuit making current Ima 50 /60 Hz up to kA 80 /82 80 /82 80 /82 80 /82Rated short-circuit breaking current Isc up to kA 31.5 31.5 31.5 31.5

    Electrical endurance ofvacuum circuit-breakers

    at rated normal currentat rated short-circuit breaking current

    DisconnectorpanelOutside cone1250 A

    Rated normal current Ir2) A 1250 1250 1250 Rated short-timewithstand current Ik

    for switchgear with tk= 3 s up to kA 31.5 31.5 31.5

    Rated peak withstand current Ip 50 / 60 Hz up to kA 80 /82 80 /82 80 /82 /

    DisconnectorpanelInside cone1250 A1600 A2000 A

    Rated normal current Ir2) A A A

    125016002000

    125016002000

    125016002000

    125016002000

    Rated short-timewithstand current Ik

    for switchgear with tk= 3 s up to kA 31.5 31.5 31.5 31.5

    Rated peak withstand current Ip 50 / 60 Hz up to kA 80 /82 80 /82 80 /82 80 /82

    150 kPa (absolute) at 20 C130 kPa (absolute) at 20 C

    10,000 operating cycles

    10,000 operating cycles

    10,000 operating cycles

    5 C to + 55 C

    50 breaking operations

    50 breaking operations

    50 breaking operations

    1) 2500 A on request

    2) The rated normal currents apply to ambient air temperatures of max. 40 C.

    The 24- hour mean value is max. 35 C (according to IEC 62271-1 / VDE 0671-1)3) Pressure values for gas-insulated switchgear vessels

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    9/64

    9Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Commonelectricaldata,fillingpressureandtemperature

    Rated insulation level Rated voltage Ur kV 12 24 36Rated short-duration power-frequency withstand voltage Ud: phase-to-phase, phase-to-earth, open contact gap kV across the isolating distance kV

    2832

    5060

    7080

    Rated lightning impulse withstand voltage Up: phase-to-phase, phase-to-earth, open contact gap kV across the isolating distance kV

    7585

    125145

    170195

    Rated frequency fr Hz 50 / 60Rated normal current Ir1) for the busbar up to A 2500 2500 2500Rated filling level pre2) Minimum functional level pme2)

    Ambient air temperature

    Data of the switchgear panels

    Circuit-breakerpanelOutside cone1250 A

    Rated normal current Ir1) A 1250 1250 1250Rated short-timewithstand current Ik

    for switchgear with tk= 3 s up to kA 31.5 31.5 31.5

    Rated peak withstand current Ip 50 / 60 Hz up to kA 80 /82 80 /82 80/ 82

    Rated short-circuit making current Ima 50/ 60 Hz up to kA 80 /82 80 /82 80/ 82Rated short-circuit breaking current Isc up to kA 31.5 31.5 31.5

    Electrical endurance ofvacuum circuit-breakers

    at rated normal currentat rated short-circuit breaking current

    Circuit-breakerpanel, buscoupler, bussectionalizerInside cone1250 A1600 A2000 A2300 A2500 A

    Rated normal current Ir2)

    A A A A A

    12501600200023002500

    12501600200023002500

    12501600200023002500

    Rated short-timewithstand current Ik

    for switchgear with tk= 3 s up to kA 31.5 31.5 31.5

    Rated peak withstand current Ip 50 / 60 Hz up to kA 80 /82 80 /82 80/ 82Rated short-circuit making current Ima 50 /60 Hz up to kA 80 /82 80 /82 80/ 82Rated short-circuit breaking current Isc up to kA 31.5 31.5 31.5

    Electrical endurance ofvacuum circuit-breakers

    at rated normal currentat rated short-circuit breaking current

    Circuit-breakerpanelSeparateinside cone

    1250 A1600 A2000 A2300 A2500 A

    Rated normal current Ir2) A A A A A

    12501600200023002500

    12501600200023002500

    12501600200023002500

    Rated short-timewithstand current Ik

    for switchgear with tk= 3 s up to kA 31.5 31.5 31.5

    Rated peak withstand current Ip 50 / 60 Hz up to kA 80 /82 80 /82 80/ 82

    Rated short-circuit making current Ima 50 /60 Hz up to kA 80 /82 80 /82 80/ 82Rated short-circuit breaking current Isc up to kA 31.5 31.5 31.5

    Electrical endurance ofvacuum circuit-breakers

    at rated normal current

    at rated short-circuit breaking current

    150 kPa (absolute) at 20 C130 kPa (absolute) at 20 C

    10,000 operating cycles

    10,000 operating cycles

    10,000 operating cycles

    5 C to +55 C

    50 breaking operations

    50 breaking operations

    50 breaking operations

    Electrical data, filling pressure, temperature for double-busbar switchgear

    Technical Data

    1) The rated normal currents apply to ambient air temperatures of max. 40 C .

    The 24- hour mean value is max. 35 C (according to IEC 62271-1 / VDE 0671-1)2) Pressure values for gas-insulated switchgear vessels

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    10/64

    10 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Room planning

    Technical Data

    Room planning for single-busbar switchgear

    Room planning for double-busbar switchgear

    Switchgear installation

    For single-busbar or double-busbar applications:

    Wall-standing arrangement or

    Free-standing arrangement Face-to-face arrangement

    accordingly.

    Room dimensions

    See opposite dimensiondrawings.

    Room height

    SBB 2950 mm DBB 3100 mm.

    Door dimensions

    The following dimensions are

    recommended as a minimum

    for the door dimensions:

    SBBDoor height: 2750 mm

    Door width: 1200 mm

    DBB

    Door height: 2900 mm

    Door width: 1500 mm.

    Switchgear fixing

    Floor openings and fixingpoints of the switchgear(see pages 12 to 21)

    Foundations: Steel girder construction Steel-reinforced concrete with

    foundation rails, welded orbolted on.

    Panel dimensions

    See pages 12 to 21.

    Weights

    Single-busbar panels 1200 kg.Double-busbar panels 1800 kg.

    Wall-standing arrangement (top view)

    Free-standing arrangement (top view)

    Wall-standing arrangement / free-standing arrangement

    (top view)

    * Aisle width

    ** Free space next to the last panel installed,either on the left or on the right of the switchgear row

    *** Recommendation 500 mm

    1) 1200 mm at 230 0 / 2500 A

    2) 900 mm or 1200 mm at2300 / 2500 A

    Panel width B1(spacing)

    Circuit-breaker panel 600 mmDisconnector panel 600 mm

    Bus sectionalizer panel 900 mm

    Panel width B2(spacing)

    Circuit-breaker panel 1) 600 mm

    Bus coupler panel 1) 600 mm

    Bus sectionalizer panel,system 1 or system 2 2)

    600 mm

    Metering panel 300 mmor600 mm

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    11/64

    11Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Shipping data, classification

    Technical Data

    Transport

    NXPLUS switchgear is deliveredin form of individual panels.Please observe the following: Transport facilities on site Transport dimensions and

    transport weights Size of door openings in

    building.

    Packing

    Means of transport:Rail and truck Panels on pallets Open packing with

    PE protective foil.

    Means of transport:Ship

    Panels on pallets In closed crates with sealedupper and lower PE protectivefoil

    With desiccant bags With sealed wooden base Max. storage time: 6 months.

    1) Average values depending onthe degree to which panels areequipped

    2) Panels with 1100 mm highlow-voltage compartment

    3) Corresponds to metal-clad

    according to former standardIEC 60298

    Transport dimensions, transport weights 1)

    Panel widths Transport dimensionsWidth x Height x Depth

    Transport weightwith packing without packing

    mm mm mm mm approx. kg approx. kg

    Single-busbar switchgear transport by rail or truck

    1 600 1100 2680 (2850)2)

    2100 1300 12001 900 1870 2680 (2850) 2) 2100 1350 1200

    Single-busbar switchgear transport by ship

    1 600 1150 3000 2100 1300 1200

    1 900 1920 3000 2100 1350 1200

    Double-busbar switchgear transport by rail or truck

    1 600 1100 2830 (2850) 2) 2100 1900 1800

    1 900 1870 2830 (2850) 2) 2100 2000 1800

    1 1200 1870 2830 (2850) 2) 2100 2000 1800

    Double-busbar switchgear transport by ship

    1 600 1150 3000 2100 1900 1800

    1 900 1920 3000 2100 2000 1800

    1 1200 1920 3000 2100 2000 1800

    Classification of NXPLUS switchgear according to IEC 62271-200

    Design and construction

    Partition class PM (metallic partition) 3)

    Loss of service continuity category LSC 2

    Accessibility to compartments(enclosure)Busbar compartmentSwitching-device compartmentLow-voltage compartmentCable compartment

    Tool-basedTool-basedTool-basedTool-based

    Internal arc classification

    Designation of the internalarc classification IACIAC class for:Wall-standing arrangementFree-standing arrangement

    IAC A FL 31.5 kA, 1 sIAC A FLR 31.5 kA, 1 s

    Type of accessibility A

    F L R

    Switchgear in closed electrical service location, accessfor authorized personnel only according to IEC 62271-200FrontLateralRear (for free-standing arrangement)

    Arc test current 31.5 kA

    Test duration 1 s

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    12/64

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    13/64

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    14/64

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    15/64

    15Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Front views, sections, floor openings, fixing points for double-busbar switchgear

    Dimensions

    2300 A2500 A

    1250 A1600 A2000 A

    Separate inside cone

    Circuit-breaker panelsSeparate inside cone

    1 Fixing point

    2 Floor opening for high-voltage cables

    3 Floor opening for control cables

    1) 2615 mm for higher low-voltagecompartment

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    16/64

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    17/64

    17Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Front views, sections, floor openings, fixing points for double-busbar switchgear

    Dimensions

    Bus sectionalizersBusbar system 2

    1250 A

    1600 A2000 A

    2300 A2500 A

    1 Fixing point

    3 Floor opening for control cables

    1) 2615 mm for higher low-voltagecompartment

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    18/64

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    19/64

    HA35-2812d

    eps

    19Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Front views, sections, floor openings, fixing points for double-busbar switchgear

    Dimensions

    Bus sectionalizer consiting of circuit-breaker panel + disconnector panel

    1250 A1600 A2000 A

    2300 A2500 A

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    20/64

    20 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    DimensionsFront views, sections, floor openings, fixing points for double-busbar switchgear

    Bus couplers

    1250 A

    1600 A2000 A

    2300 A2500 A

    1 Fixing point

    3 Floor opening for control cables

    1) 2615 mm for higher low-voltagecompartment

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    21/64

    21Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    DimensionsFront views, sections, floor openings, fixing points for double-busbar switchgear

    Metering panels

    1 Fixing point

    3 Floor opening for control cables

    1) 2615 mm for higher low-voltagecompartment

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    22/64

    22 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Product RangeSingle-busbar panels

    Busbar currenttransformer

    Solid-insulatedbar

    Voltage transformer,plug-in type

    Capacitive voltagedetecting system

    Plug-in cable,1-to 4-fold,inside-cone inter-face type 2 or 3(not included in thescope of supply)

    Surge arrester,

    plug-in type

    Current transformer

    Circuit-breaker panel(cable connection as inside cone)

    and 1) or

    or or

    or or

    or

    or

    Circuit-breaker panel(cable connection as outside cone)

    and 1)

    or or

    or

    or

    or

    1) Not possible with busbar voltagetransformer

    2) Requires cable connection with vesselfor separate inside cone

    3) Not possible with horizontal pressure

    relief duct

    HA35-2541b

    eps

    Voltage transformer,disconnectable

    Cable connectionwith outside-coneplug (not includedin the scope ofsupply)

    Capacitive voltagedetecting system

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    23/64

    23Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Single-busbar panels

    Product Range

    Disconnector panel(cable connection as outside cone) Busbar current

    transformer

    Solid-insulatedbar

    Voltage transformer,plug-in type

    Capacitive voltagedetecting system

    Plug-in cable,1-to 4-fold,inside-cone inter-face type 2 or 3(not included in thescope of supply)

    Surge arrester,

    plug-in type

    Cable connectionwith outside-coneplug (not includedin the scope ofsupply)

    Current transformer

    Disconnector panel(cable connection as inside cone)

    and 1) or

    or or

    or or

    or

    or

    and 1)

    or or

    or

    or

    or

    1) Not possible with busbar voltagetransformer

    3) Not possible with horizontal pressure

    relief duct

    Bus sectionalizer

    HA35-2541b

    eps

    Voltage transformer,disconnectable

    Capacitive voltagedetecting system

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    24/64

    24 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Double-busbar panels

    Product Range

    1) Requires cable connection with vesselfor separate inside cone

    2) Ring-core current transformer, ovaldesign, suitable for use as of 1000 A

    Abbreviations

    SS1 = Busbar 1

    SS2 = Busbar 2

    HA35-2541b

    eps

    Voltage transformer,disconnectable

    Busbar currenttransformer

    Solid-insulatedbar

    Voltage transformer,plug-in type

    Capacitive voltagedetecting system

    Plug-in cable,1-to 4-fold,inside-cone inter-face type 2 or 3(not included in thescope of supply)

    Surge arrester,

    plug-in type

    Current transformer

    Cable connectionwith outside-coneplug (not includedin the scope ofsupply)

    Capacitive voltagedetecting system

    Circuit-breaker panel(cable connection as inside cone)

    or

    or

    or

    or

    Circuit-breaker panel(cable connection as outside cone)

    or

    or

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    25/64

    25Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Double-busbar panels

    Product Range

    Abbreviations

    SS1 = Busbar 1

    SS2 = Busbar 2

    HA35-2541b

    eps

    Voltage transformer,disconnectable

    Busbar currenttransformer

    Solid-insulatedbar

    Voltage transformer,plug-in type

    Capacitive voltagedetecting system

    Plug-in cable,1-to 4-fold,inside-cone inter-face type 2 or 3(not included in thescope of supply)

    Surge arrester,

    plug-in type

    Current transformer

    Cable connectionwith outside-coneplug (not includedin the scope ofsupply)

    Capacitive voltagedetecting system

    Bus sectionalizer

    Bus sectionalizer circuit-breaker panel(cable connection as inside cone)

    or or

    or or

    or or

    or or

    Bus sectionalizer disconnector panel(cable connection as inside cone)

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    26/64

    26 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Double-busbar panels

    Product Range

    HA35-2

    541b

    eps

    Current transformer

    Voltage transformer,plug-in type

    Capacitive voltagedetecting system

    Abbreviations

    SS1 = Busbar 1

    SS2 = Busbar 2

    Bus coupler

    Metering panel

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    27/64

    27Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Single-busbar panels, double-busbar panels

    Product Range

    Single-busbar panelsCircuit-breaker panel

    With cable connection as outside cone for Rated voltage up to 36 kV Rated short-circuit breaking current up to 31.5 kA Rated normal currents of busbars up to 2000 A

    (2500 A on request), and of feeders up to 1250 A With cable connection as inside cone for

    Rated voltage up to 40.5 kV Rated short-circuit breaking current up to 31.5 kA Rated normal currents of busbars and feeders up to2000 A (2500 A on request)

    With cable connection as separate inside cone for Rated voltage up to 40.5 kV Rated short-circuit breaking current up to 31.5 kA Rated normal currents of busbars and feeders up to2000 A (2500 A on request).

    Disconnector panel

    With cable connection as outside cone for Rated voltage up to 36 kV Rated short-circuit breaking current up to 31.5 kA Rated normal currents of busbars up to 2000 A(2500 A on request), and of feeders up to 1250 A

    With cable connection as inside cone for Rated voltage up to 40.5 kV Rated short-time withstand current up to 31.5 kA Rated normal currents of busbars and feeders up to2000 A (2500 A on request).

    Bus sectionalizer

    for Rated voltage up to 40.5 kV

    Rated short-circuit breaking current up to 31.5 kA Rated normal currents of busbars up to 2000 A(2500 A on request).

    Double-busbar panelsCircuit-breaker panel

    With cable connection as outside cone for Rated voltage up to 36 kV Rated short-circuit breaking current up to 31.5 kA Rated normal currents of busbars up to 2500 A, and of

    feeders up to 1250 A With cable connection as inside cone for

    Rated voltage up to 36 kV Rated short-circuit breaking current up to 31.5 kA Rated normal currents of busbars and feeders up to2500 A

    With cable connection as separate inside cone for Rated voltage up to 36 kV Rated short-circuit breaking current up to 31.5 kA Rated normal currents of busbars and feeders up to2500 A.

    Bus sectionalizer

    for Rated voltage up to 36 kV Rated short-circuit breaking current up to 31.5 kA Rated normal currents of busbars up to 2500 A.

    Bus sectionalizer

    (circuit-breaker panel and disconnector panel) With cable connection as inside cone for

    Rated voltage up to 36 kV Rated short-circuit breaking current up to 31.5 kA Rated normal currents of busbars and feeders up to2500 A.

    Bus coupler

    for Rated voltage up to 36 kV Rated short-circuit breaking current up to 31.5 kA Rated normal currents of busbars up to 2500 A.

    Metering panel with a panel spacing of 300 mm or600 mm

    for Rated voltage up to 36 kV Rated normal currents of busbars up to 2500 A.

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    28/64

    28 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Single-busbar panel design

    Design

    Insulating system

    Switchgear vessel filled with SF6gas Featurs of SF6gas: Non-toxic Odorless and colorless Non-inflammable

    Chemically neutral Heavier than air Electronegative (high-quality insulator) Pressure of SF6gas in the switchgear

    vessel (absolute values at 20 C): Rated filling level: 150 kPa

    Design pressure: 180 kPa Design temperature of the SF6gas: 80 C Pickup pressure of the bursting disc:

    300 kPa Bursting pressure: 550 kPa Gas leakage rate: < 0.1 % p.a.

    Panel design

    Factory-assembled, type-tested Metal-enclosed, with metallic

    partitions 1)

    Hermetically tight, welded switchgearvessel made of stainless steel

    Electrical connections via cast-resininsulated, screened and bolted modulecouplings

    Maintenance-free Degree of protection IP 65 for all high-voltage parts of the

    primary circuit IP 3XD for the switchgear enclosure

    Vacuum circuit-breaker Three-position disconnector for dis-connecting and earthing by means ofthe circuit-breaker

    Make-proof earthing by means of thevacuum circuit-breaker

    Cable connection with outside-coneplug-in system or inside-cone plug-insystem according to DIN EN 50181

    Wall-standing or free-standingarrangement

    Installation and possible later extensionof existing panels without gas work

    Replacement of the circuit-breakermodule without gas work

    Instrument transformers can beremoved without altering the position ofthe busbar and circuit-breaker modules

    Replacement of instrument transformerswithout gas work, as they are locatedoutside the gas compartments

    Enclosure made of sendzimir-galvanizedsheet steel, front and rear side ofswitchgear as well as end walls powder-coated in color light basic (SN 700)

    Low-voltage compartment removable,plug-in bus wires

    Lateral metallic wiring duct for controlcables.

    HA35-2397geps

    14

    15

    17

    18

    20

    26

    27

    1

    30

    31

    32

    33

    34

    35

    19

    16

    36

    2

    1

    16

    20

    39

    40 35

    38

    36

    30

    Z

    9

    10

    12

    11

    13

    3

    7

    5

    4

    625

    23

    22

    24

    16

    28

    8

    29

    37

    37

    44

    35

    36

    37

    26

    27

    16

    29

    Modular design(example)

    Panel with integrated inside cone up to 36 kV

    Panel with separate inside cone up to 40.5 kV

    Front view

    Detail Z:

    Panel with outside cone up to 36 kV

    Panel with integrated inside cone up to 40.5 kV

    1) Corresponds to metal-cladaccording to former standard

    IEC 60298

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    29/64

    H

    A35-2401heps

    Z

    9

    10

    12

    11

    13

    35

    36

    34

    33

    32

    31

    30

    1

    16

    19

    20

    24

    16

    26

    27

    18

    17

    15

    14

    1

    2

    28

    3

    7

    5

    4

    6

    25

    29

    23

    22

    21

    37

    16

    20

    39

    4035

    36

    38 30

    37

    Panel with outside cone

    29Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Double-busbar panel design

    Design

    Modular design (example)

    Front view

    Detail Z:

    Panel with integrated inside cone

    Panel with separate inside cone

    1 Low-voltage compartment

    2 Multifunction protection relay SIPROTEC 4(example)

    3 Actuating opening for charging the circuit-breaker springs

    4 Position indicator for circuit-breaker

    5 Spring charged indicator

    6 Operations counter for circuit-breaker

    7 Capacitive voltage detecting system

    8 Interrogation lever

    9 Control gate and locking device fordisconnecting / earthing functions ofthree-position switch

    10 Actuating opening for disconnectingfunction of three-position switch

    11 Actuating opening for ready-to-earthfunction of three-position switch

    12 Position indicator for disconnecting functionof three-position switch

    13 Position indicator for ready-to-earth

    function of three-position switch14 Busbar cover

    15 Busbar module, welded,SF6-insulated

    16 Pressure relief (bursting disc)

    17 Three-phase busbar system

    18 Three-position disconnector

    19 Module coupling between busbar moduleand circuit-breaker module

    20 Circuit-breaker module, welded,SF6-insulated

    21 Selector gate for selectingthe three-position disconnectorin double-busbar switchgear

    22 ON pushbutton for circuit-breaker23 OFF pushbutton for circuit-breaker

    24 Vacuum interrupter of circuit-breaker

    25 Feeder locking device (suitable forpadlocking)

    26 Pressure relief duct

    27 Integrated cable connection as inside cone

    28 Cover of cable compartment

    29 Cable connection with inside-cone plugs

    30 Feeder current transformer

    31 Operating mechanism for three-positionswitch

    32 Mechanical control board

    33 Operating mechanism for circuit-breaker

    34 Voltage transformer connection socket asoutside cone

    35 Cable compartment

    36 Feeder voltage transformer

    37 Earthing busbar

    38 Disconnecting facility for feeder voltagetransformer

    39 Bushing for feeder voltage transformer

    40 Cable connection with outside-cone T-plugs

    41 Module coupling between circuit-breakermodule and separate inside-cone module

    42 Separate inside-cone module

    43 Integrated cable connection as inside cone

    44 Voltage transformer connection socket asoutside cone

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    30/64

    30 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Vacuum circuit-breaker

    Components

    Features

    According to IEC 62271-100 and VDE 0671-100(for standards, see page 59)

    Application in hermetically welded switchgear vessel inconformity with the system

    Climate-independent vacuum interrupter poles in the

    SF6-filled switchgear vessel Maintenance-free for indoor installation according to

    IEC 62271-1 and VDE 0671-1

    Individual secondary equipment A metal bellows is used for gasketless separation of the

    SF6insulation and the operat ing mechanism (already usedwith success for over 2 million vacuum interrupters).

    Trip-free mechanism

    The vacuum circuit-breaker is fitted with a trip-freemechanism according to IEC 62271 and VDE 0671.

    Switching duties and operating mechanisms

    The switching duties of the vacuum circuit-breaker are

    dependent, among other factors, on its type of operatingmechanism.Motor operating mechanism Motor operating stored-energy mechanism

    For auto-reclosing (K) For synchronization and rapid load transfer (U).

    Further operating mechanism features Located outside the switchgear vessel in the operating

    mechanism box and behind the control board Stored-energy spring mechanism for 10,000 operating cycles.

    Operating mechanism functions

    Motor operating mechanism 1)(M1 *)

    In the case of motor operating mechanism, the closingspring is charged by means of a motor and latched in thecharged position (spring charged indication is visible).Closing is effected either by means of an ON pushbuttonor a closing solenoid. The closing spring is rechargedautomatically (for auto-reclosing).

    Endurance class of circuit-breaker

    Function Class Standard Property of NXPLUS

    BREAKING M2 IEC 62271-100 10,000 times mechanically withoutmaintenance

    E2 IEC 62271-100 10,000 times rated normal currentwithout maintenance50 times short-circuit breaking currentwithout maintenance

    C2 IEC 62271-100 Very low probability of restrikesOperating times

    Closing time Closing solenoid < 75 ms

    Opening time 1strelease2ndrelease

    < 65 ms< 50 ms

    Arcing time at 50 Hz < 15 ms

    Break time 1strelease2ndrelease

    < 80 ms< 65 ms

    Dead time 300 ms

    Total charging time < 15 s

    1 Gear with motor (M1 *) 2 Position switch (S4 *)

    3Closing spring

    4 Closing spring charged indication

    5 Closing solenoid (Y9 *)

    6Operations counter

    7 Auxiliary switch 6 NO + 6 NC (S1 *), option: 12 NO + 12 NC

    8 CLOSED/OPEN position indicator for circuit-breaker

    9Option: 2nd release (Y2 *), 3rdrelease (Y7 *)

    10 1strelease (Y1 *)

    11 Feeder locking device

    12Fixed terminal

    13 Pole support

    14 Vacuum interrupter

    15 Moving terminal

    16Metal bellows

    17 Switchgear vessel, SF6-insulated, with vacuum interrupter

    18 Operating mechanism box (see figure above)

    19Operating kinematics

    Section through the vacuum circuit-breaker

    R-HA35-126ae

    ps

    Abbreviations for switching duties:U = Synchronization and rapid load transfer (closing time 90 ms)K = Auto-reclosing1) Motor rating at 60 V to 220 V DC: 700 W 100 V up to 230 V DC: 1100 VA* Item designation

    Inside view of the vacuum circuit-breaker

    7

    11

    10

    1

    5

    98

    4

    2

    3

    6

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    31/64

    31Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Vacuum circuit-breaker

    Components

    Secondary equipment

    The scope of the secondary equipment of the vacuum circuit-breaker depends on the type of application and offers a widerange of possible variations, allowing almost every require-ment to be satisfied:

    Closing solenoid

    Type 3AY15 10 (Y9 *) For electrical closing.

    Shunt release

    Types: Standard: 3AY15 10 (Y1 *) Option: 3AX11 01 (Y2 *), with energy store

    Tripping by protection relay or electrical actuation.

    Undervoltage release

    Type 3AX11 03 (Y7 *)

    Consisting of: Energy store and unlatching mechanism Electromagnetic system, which is permanently connected

    to voltage while the vacuum circuit-breaker is closed;

    tripping is initiated when this voltage drops Connection to voltage transformers possible.

    Anti-pumping(mechanical and electrical)

    Function: If constant CLOSE and OPEN commands arepresent at the vacuum circuit-breaker at the same time,the vacuum circuit-breaker will return to the open positionafter closing. It remains in this position until a new CLOSEcommand is given. In this manner, continuous closing andopening (= pumping) is avoided.

    Circuit-breaker tripping signal

    For electrical signaling (as pulse > 10 ms), e. g. to remote con-trol systems, in the case of automatic tripping (e. g. protection)

    Via limit switch (S6 *) and cutout switch (S7 *).

    Varistor module

    To limit overvoltages to approx. 500 V for protect iondevices (when inductive components are mounted in thevacuum circuit-breaker)

    For auxiliary voltages 60 V DC.

    Auxiliary switch

    Type 3SV9 (S1 *)

    Standard: 6 NO + 6 NC, free contacts thereof 1)2 NO + 2 NC

    Option: 12 NO + 12 NC, free contacts thereof 1)8 NO + 8 NC.

    Position switch

    Type 3AX4 (S41, S42, S16 *)

    For signaling closing spring charged

    For signaling circuit-breaker blocked.Mechanical interlocking

    Mechanical interlocking to the three-position disconnector During operation of the three-position switch, the vacuum

    circuit-breaker cannot be operated.

    Switching rate of the vacuum interrupter

    Electrical data

    Curve Curve Curve Curve

    Rated voltage 12 kV 24 kV 24 kV 36 / 40.5 kV

    Rated short-circuit-breaking current 31.5 kA 25 kA 25 kA 31.5 kA

    Rated normal current 1250 A 1250 A 2000 A 2500 A

    Rated operating sequences

    Rapid transfer (U): O-t-CO-t-CO (t0.3 s, t 3 min)

    Auto-reclosing (K): O-t-CO-t-CO (t0.3 s, t 3 min)

    Auto-reclosing (K): O-t-CO-t-CO (t0.3 s, t 15 s)

    O = OPEN operation

    CO = CLOSE operation with subsequent OPEN operation at the shortest

    internal close-open time of the vacuum circuit-breaker

    Possible release combinations

    Release

    1 2 3 4

    1st shunt release type 3AY1510

    2nd shunt release type 3AX1101

    Undervoltage release type 3AX1103

    Release combination

    1) For utilization

    by the customer* Item designation

    Abbreviations:NO = normally open contactNC = normally closed contact

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    32/64

    32 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Three-position disconnector

    Components

    Features of the three-position disconnector

    According to IEC 62271-102 and VDE 0671-102(for standards, see page 59)

    Application in hermetically welded switchgear vessel inconformity with the system

    Climate-independent contacts in the SF6-filled switchgear

    vessel Maintenance-free for indoor installation according to

    IEC 62271-1 and VDE 0671-1 A metal bellows is used for gasketless separation of the

    SF6insulation and the operating mechanism as alreadyused with success in millions of vacuum interrupters

    Compact design due to short contact gaps in SF6gas Operating shaft and contact blades with common center

    of rotation and reliable switch position up to the operatingfront of the panel

    2000 mechanical operating cycles for CLOSED / OPEN 1000 mechanical operating cycles for

    OPEN / READY-TO-EARTH

    Position indication via mechanical coupled indicators Separate operating shafts for the DISCONNECTING and

    READY-TO-EARTH functions Maintenance-free.

    Switch positions of thethree-position disconnector

    Switch positions of the three-position disconnector

    CLOSED

    OPEN

    FeederEARTHED

    Switch positions

    Endurance class of three-position disconnector

    Function Class Standard Property of NXPLUS

    DISCONNECTING M1 IEC 62271-102 2000 times mechanicallywithout maintenance

    READY-TO-EARTH

    M0E0

    IEC 62271-102IEC 62271-102

    1000 times mechanicallywithout maintenanceno making capacity

    EARTHING E2 1) IEC 62271-200IEC 62271-102

    50 times rated short-circuitmaking current Imawithoutmaintenance

    CLOSED

    Closed current path

    between busbar and

    vacuum circuit-breaker

    Contact blades

    connected with fixed

    contacts at the busbar

    bushings

    OPEN

    Open current path

    between busbar and

    vacuum circuit-breaker

    Isolating distances

    withstand prescribed

    test voltages

    READY-TO-EARTH

    Contact blades

    connected with earth

    contact of switchgear

    vessel

    Earthing and short-

    circuiting the cable

    connection possible

    by closing the

    vacuum circuit-

    breaker

    Three-position disconnector(in OPEN position)(view into the laterallyopen switchgear vessel)

    1 Fixed contact at the busbar2Swivel-mounted contact blade3 Fixed contact for feeder EARTHED4 Push rod

    21

    4

    3

    R-HA35-073b eps

    1) The EARTHING function with endurance class E2 is achieved by

    closing the circuit-breaker in combination with the three-positiondisconnector (endurance class E0)

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    33/64

    33Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    ComponentsThree-position disconnector

    Interlocks

    Selection of permissible switching operations by meansof a control gate with mechanically interlocked vacuumcircuit-breaker

    Corresponding operating shafts are not released at theoperating front until they have been pre-selected with the

    control gate Operating lever cannot be removed until switching

    operation has been completed Circuit-breaker cannot be closed until control gate is in

    neutral position again Switchgear interlocking system also possible with electro-

    mechanical interlocks if switchgear is equipped withmotor operating mechanisms (mechanical interlocking formanual operation remains).

    Switch positions

    CLOSED, OPEN, EARTHED or READY-TO-EARTH In circuit-breaker panels, earthing and short-circuiting

    the cable connection is completed by closing the vacuumcircuit-breaker.

    Operating mechanism

    Slow motion mechanism, used in: Circuit-breaker panel Disconnector panel Bus sectionalizer Bus coupler

    Slow motion mechanism actuated via operating lever at theoperating front of the panel

    Separate operating shafts for the DISCONNECTING andEARTHING or READY-TO-EARTH functions

    Option: Motor operating mechanism for theDISCONNECTING and EARTHING or READY-TO-EARTHfunctions

    Maintenance-free due to non-rusting design of partssubjected to mechanical stress

    Bearings which require no lubrication.

    Transmission principle for operating mechanisms(see illustration) Transmission of operating power from outside into the

    gas-filled switchgear vessel by means of a metal bellows Gas-tight Maintenance-free.

    Transmission principle for operating mechanisms

    1 Gas-filledswitchgear vessel

    2 Gas-tightwelded-inmetal bellows

    Three-position disconnector

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    34/64

    HA35-2375me

    ps

    1

    52

    3

    4

    1

    HA35-2411eeps

    1 5

    2

    3

    4

    1

    34 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Busbar, module coupling

    Components

    Busbar

    Designed as module coupling Solid-insulated Interconnects the panels as well

    as the vessels within a panel.

    Module coupling Single-pole, bolted type Consisting of round-bar copper,

    cast-resin insulated Bolted busbar joint, silicone-

    rubber insulated Field control by means of

    electrically conductive layers onthe insulation (inside and outside)

    Screened by earthing the externallayers with the switchgear vessel

    Switchgear installation, extensionor panel replacement without SF6

    gas work.

    Panel interconnectionsin circuit-breaker panel(example)

    Module couplingsfor single-busbar panels

    Module couplingsfor double-busbar panels

    1 Module coupling2 Busbar module

    3 Circuit-breaker module

    4 End wall

    5 Bushing in adjacent panel

    6 Busbar conductor

    7 Silicone sleeve

    8 Earthing clamps

    9 High-quality joint

    10 Cast-resin bushing

    11 Vessel wall

    12 Cast-resin insulation

    13 Conductive layer

    14 Bolted busbar joint15 Pressure ring

    Busbar moduleSF6-insulated

    Busbar moduleSF6-insulated

    Module coupling

    (solid-insulated)

    R-HA35-115

    eps

    Module coupling

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    35/64

    Panel with

    outside cone up to 36 kV

    Panel with

    separate inside cone

    up to 40.5 kV

    Panel with

    integrated inside cone up to 36 kV

    35Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Current transformers

    Components

    Features

    According to IEC 61869-2and VDE 0414-9-2

    Designed as ring-core currenttransformers, single-pole

    Flexibility for selecting the

    mounting location Free of dielectrically stressed

    cast-resin parts (due todesign)

    Insulation class E Inductive type Certifiable Climate-independent Secondary connection by

    means of a terminal strip inthe low-voltage compartmentof the panel.

    Installation Arranged outside the primaryenclosure (switchgear vessel)

    Mounting locations At the busbar (1) Between busbar module and

    circuit-breaker module (2) At the panel connection (3) Between circuit-breaker

    module and cable connectionmodule (4)

    Zero-sequence currenttransformer.

    Current transformer types Busbar current transformer (1):

    Inside diameter oftransformer 120 mm

    Max. usable height 170 mm Current transformer between

    busbar module and circuit-breaker module (2): Inside diameter oftransformer 120 mm

    Max. usable height 170 mm Current transformer at the

    panel connection (3):

    Inside diameter oftransformer 120 mm

    Max. usable height 205 mm Current transformer between

    circuit-breaker module andcable connection module (4): Inside diameter oftransformer 120 mm

    Max. usable height 170 mm Zero-sequence current

    transformer underneaththe panels (included in thescope of supply); on-site

    installation.

    Electrical data

    Designation Type 4MC

    Operating voltage max. 0.8 kVRated short-durationpower-frequencywithstand voltage(winding test)

    3 kV

    Rated frequency 50 / 60 Hz

    Rated continuousthermal current

    max. 1.2 xrated current(primary)

    Rated short-timethermal current,max. 3 s

    max. 31.5 kA

    Rated dynamiccurrent primary

    secondary

    unlimited,40 A to2500 A1 A and 5 A

    Designation Type 4MC

    Multi ratio (secondary) 200 A 100 Ato2500 A 1250 A

    Core data depending on therated primary current:Measuring Ratingcore Class Overcurrent

    factorProtection Ratingcore Class Overcurrent

    factor

    max. 3 cores

    2.5 VA to 30 VA0.2 to 1

    FS 5, FS 102.5 VA to 30 VA5 P or 10 P10 to 30

    Permissible ambient airtemperature

    max. 60 C

    Insulation class E

    Current transformer installation(basic scheme)

    1 Current transformer at the busbar2 Current transformer between busbar module and circuit-breaker module3 Current transformer at the panel connection4 Current transformer between circuit-breaker module and cable connection module

    Panel with

    separate inside cone

    Panel with

    integrated inside cone

    Panel with

    outside cone

    Front view

    Front view

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    36/64

    Voltage transformer installation for single busbar(basic scheme)

    Panel with

    outside cone up to 36 kV

    Panel with

    separate inside cone

    up to 40.5 kV

    Panel with

    integrated inside cone up to 36 kV

    Front view

    Panel with

    integrated inside cone

    up to 40.5 kV

    36 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Voltage transformers

    Components

    Features

    According to IEC 61869-3and VDE 0414-9-3

    Single-pole, plug-in design Connection system with

    plug-in contact

    Inductive type Safe-to-touch due to

    metal enclosure Certifiable Climate-independent Secondary connection by

    means of plugs inside thepanel

    Cast-resin insulated Arranged outside the

    primary enclosure(switchgear vessel)

    Mounting locations: At the busbar on the busbarmodule (1) (single busbar),or in a separate meteringpanel (8) (double busbar)

    At the panel connection(2)(3)(5).

    Voltage transformer types

    Busbar voltage transformer4MT6 (1) on the busbarmodule (single busbar) Pluggable into aninside-cone socket size 2

    No separate meteringpanel required

    Suitable for 80% of therated short-durationpower-frequency withstandvoltage at rated frequency

    Busbar voltage transformer4MT9 (8) in a separate,300 mm or 600 mm widemetering panel (doublebusbar) Connected with the busbarthrough a flexible cable

    with inside-cone plug,for connection to thebusbar and to the voltagetransformer

    Suitable for 80 % of therated short-durationpower-frequency withstandvoltage at rated frequency.

    Voltage transformers

    Feeder voltage transformer

    (metal-coated) 4MT3

    R-HA35.51-82

    eps

    R-HA35-120

    eps

    Busbar voltage transformer

    (metal-enclosed) 4MT6

    Disconnecting facility for feeder

    voltage transformer (detail Z)

    OPEN and EARTHED

    CLOSED

    1 Voltage transformer at the busbar

    2 Voltage transformer at the panel connection(inside-cone connection)

    3 Voltage transformer at the panel connection(outside-cone connection)

    4 Operating lever for disconnecting facility

    5 Voltage transformer at the panel connection(separate inside-cone connection)

    6 Panel connection

    7Switchgear vessel wall (earthed)

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    37/64

    37Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Voltage transformers

    Components

    Voltage transformers 4MU1or 4MT3 (3) at the panelconnection of the panels withoutside-cone connection Pluggable into an outside-cone bushing at the panel

    connection Application of type 4MU1 at36 kV or 24 kV and 31.5 kA

    Application of type 4MT3up to 24 kV

    Disconnectable via adisconnecting facility at thecable connection

    Switchable through anSF6-insulated disconnectingfacility in the switchgearvessel

    Positions: CLOSED and

    Transformer bushingEARTHED

    Operation of thedisconnecting facilityfrom outside through ametal bellows weldedin the switchgear vessel

    Voltage transformers4MU2 or 4MT5 at the panelconnection of the panels withinside-cone connection Connection via an outside-cone bushing at the panel

    connection for type 4MU2 (2) Connection via a flexiblecable between aninside-cone socket at thepanel connection and aninside-cone socket at thevoltage transformer type4MU2 (5)

    Application of type 4MU2up to 36 kV

    Application of type 4MT5up to 40.5 kV.

    HA35-2809aeps

    2

    2 Voltage transformer at the panelconnection(inside-cone connection)

    3 Voltage transformer at the panelconnection (outside-cone connection)

    4 Operating lever for disconnectingfacility

    5 Voltage transformer at the panelconnection (separate inside-coneconnection)

    8 Voltage transformer at the busbar(double-busbar metering panel)

    Voltage transformer installation for double busbar(basic scheme)

    Metering panel 600 mm

    Metering panel 300 mm

    Panel with

    outside cone

    Panel with

    separate inside cone

    Panel with

    integrated inside cone

    Front view

    Front view

    Front view

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    38/64

    38 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Voltage transformers

    Components

    Rated voltage

    kV

    Rated short-durationpower-frequencywithstand voltage

    kV

    Rated lightningimpulse withstandvoltage

    kV

    Standard Operating voltage

    kV

    7.2 20 60 IEC 6.0 / 3; 6.24 / 3; 6.3 / 3;6.6 / 3; 6.9 / 3

    12 28 75 IEC 7.2 / 3; 7.6 / 3; 8.0 / 3;8.3 / 3; 8.4 / 3; 8.9 / 3;10 / 3; 10.5 / 3; 11 / 3;11.4 / 3; 11.5 / 3; 11.6 / 3

    17.5 38 95 IEC 12 / 3; 12.4 / 3; 12.47 / 3;12.5 / 3; 12.8 / 3; 13.2 / 3;13.4 / 3; 13.8 / 3; 14.4 / 3;15 / 3; 15.8 / 3; 16/ 3;17/ 3;

    24 50 125 IEC 17.5 / 3; 18 / 3; 19 / 3;20 / 3; 22 / 3; 23 / 3;

    36 70 170 IEC 24 / 3; 25.0 / 3; 25.8 / 3;27.6 / 3; 30.0 / 3; 33.0 / 3;34.5 / 3; 35.0 / 3;

    40.5 85 185 IEC 38 / 3;

    Electrical data

    Primary data

    For types 4MT3, 4MT5, 4MT6, 4MT9, 4MU1 and 4MU2For operating voltages from 6.0 kV to 38 kV, rated voltage factor Un/ 8h = 1.9; Un/ continuous = 1.2

    Fortype

    Operatingvoltage

    V

    Auxiliarywinding

    V

    Thermallimit current(measuringwinding)

    A

    Rated long-time current8 h

    A

    Rating at accuracy class

    0.2

    VA

    0.5

    VA

    1

    VA

    3

    VA4MT3 100 / 3

    110 / 3120 / 3

    100 / 3110 / 3120 / 3

    6 4 IEC

    10, 15, 20,25, 30

    10, 15, 20,25, 30, 45,50, 60, 75,90

    10, 15, 20,25, 30, 45,50, 60, 75,90, 100, 120,150, 180

    10, 15, 20,25, 30, 45,50, 60, 75,90, 100, 120,150, 180

    4MT5 100 / 3110 / 3120 / 3

    100 / 3110 / 3120 / 3

    6 6 IEC

    5, 10, 15,20, 25

    10, 15, 20,25, 30, 45,50, 60, 75

    10, 15, 20,25, 30, 45,50, 60, 75,90, 100,120, 150

    10, 15, 20,25, 30, 45,50, 60, 75,90, 100,120, 150

    4MT64MT9

    100 / 3110 / 3120 / 3

    100 / 3110 / 3120 / 3

    6 6 IEC

    5, 10, 15,20, 25

    10, 15, 20,25, 30, 45,

    50, 60, 75

    10, 15, 20,25, 30, 45,

    50, 60, 75,90, 100,120, 150

    10, 15, 20,25, 30, 45,

    50, 60, 75,90, 100,120, 150

    4MU14MU2

    100 / 3;110 / 3;120 / 3

    100 / 3;110 / 3;120 / 3

    6 6 IEC

    5, 10.15, 20,25

    10, 15, 20,25, 30, 45

    10, 15, 20,25, 30, 45,50, 60, 75

    10, 15, 20,25, 30, 45,50, 60, 75

    Secondary data

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    39/64

    39Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Components

    Design

    Modular design per panel

    Various elements for flexible

    design of the evacuation

    Pressure flap insertion ele-

    ment for wall penetration

    (masonry opening).

    Dimensions

    Height of switchgear panel

    Single busbar:

    2874 mm

    Double busbar:

    2997 mm

    Minimum room height

    Single busbar:

    2950 mm

    Double busbar:

    3100 mm

    See dimensions of evacua-tion elements on the next

    page.

    Tests

    Type-tested design.

    Installation

    The horizontal pressure relief

    duct on the panel is installed

    on site

    Evacuation elements

    according to constructional

    planning.

    Horizontal pressure relief duct

    NXPLUS with horizontal

    pressure relief duct

    R-

    HA35-184.j

    pg

    NXPLUS SBB with horizontal

    pressure relief duct and evacuation

    Evacuation to the left

    (also possible to the right)

    Evacuation to the rear

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    40/64

    40 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    HA35-2783b

    eps

    HA35-2781b

    eps

    HA35-2784b

    eps

    HA35-2824e

    ps

    Horizontal pressure relief duct, dimensions

    Components

    NXPLUS DBB with horizontal pressure relief duct and evacuation

    Elements for the evacuation duct

    Evacuation to the left (also possible to the right) Evacuation to the rear

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    41/64

    41Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    ComponentsPanel connection with outside cone

    Features

    For circuit-breaker panel1250 A,for disconnector panel1250 A

    Bushings with outside cone

    With bolted contact (M16) asinterface type C accordingto EN 50180 / EN 50181

    Cable connection height591 mm

    Max. connection depth:960 mm with standard cablecompartment cover

    With cable bracket,type C40 according toDIN EN 50024

    Option: Acess to cablecompartment only if the

    feeder is isolated and earthed For thermoplastic-insulated

    cables For shielded cable T-plugs or

    cable elbow plugs with boltedcontact

    For connection cross-sectionsup to 800 mm2

    Larger cross-sections onrequest

    Cable routing downwards,cable connection from thefront

    For rated normal currentsup to 1250 A

    Cable T-plugs are notincluded in the scope ofsupply.

    Surge arresters

    Pluggable on cable T-plug Surge arresters

    recommended if, at the sametime,

    the cable system is directlyconnected to the overhead

    line, the protection zone of the

    surge arrester at the endtower of the overheadline does not cover theswitchgear.

    Surge limiters

    Pluggable on cable T-plug Surge limiters recommended

    when motors with startingcurrents < 600 A areconnected.

    Connectable cablesCable T-plug with coupling insert

    Cable T-plug with coupling T-plug

    Cable compartment

    Connection with1 cable per phase

    Connection with2 cables per phase

    Connection with2 cables per phase

    Connection with3 cables per phase

    Connection with 3 cables per phase

    Panel width 600 mm

    1 Cable T-plug2 Coupling T-plug3 Screw-type coupling insert

    4 End adapter

    Solid-insulated bar

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    42/64

    42 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    ComponentsPanel connection with outside cone (commercially available cable plugs and bar connections)

    Cable type Cable sealing end Comment

    Make Type Cross-sectionmm2

    Thermoplastic-insulated cables 12 kV according to IEC 60502-2 and VDE 0276-620

    1-core cable,PE and XLPE-insulatedN2YSY (Cu) and

    N2XSY (Cu)orNA2YSY (Al) andNA2XSY (Al)

    Euromold 400TB / G430TB / G440TB / G

    484TB / G489TB / G

    35 to 30035 to 300400 to 630

    50 to 630800 to 1200

    EPDM with semi-conductive layerEPDM with semi-conductive layerEPDM with semi-conductive layer

    EPDM with semi-conductive layerEPDM with semi-conductive layer

    nkt cables CB 12-630CB 17.5-630CB 36-630(1250)CB 42-1250-3

    25 to 30025 to 500400 to 630630 to 1000

    Silicone with semi-conductive layer (optionally with metal housing)Silicone with semi-conductive layerSilicone with semi-conductive layerSilicone with semi-conductive layer

    Sdkabel SET 12SEHDT 13

    50 to 300400 to 500

    Silicone with semi-conductive layer (optionally with metal housing)Silicone with semi-conductive layer (optionally with metal housing)

    Tyco ElectronicsRaychem

    RSTI-58xxRSTI-395x

    25 to 300400 to 800

    Silicone with semi-conductive layer (optionally with metal housing)Silicone with semi-conductive layer (optionally with metal housing)

    ABB Kabeldon CSE-A 12630-xx 25 to 630 EPDM with semi-conductive layer

    3-core cable,PE and XLPE-insulated,N2YSY (Cu) andN2XSY (Cu)orNA2YSY (Al) andNA2XSY (Al)

    Euromold 400TB / G430TB / G

    35 to 30035 to 300

    EPDM with semi-conductive layer, in combination with distribution kitEPDM with semi-conductive layer, in combination with distribution kit

    nkt cables CB 12-630

    CB 17.5-630

    25 to 300

    25 to 500

    Silicone with semi-conductive layer (optionally with metal housing),in combination with distribution kitSilicone with semi-conductive layer, in combination with distribution kit

    Sdkabel SET 12

    SEHDT 13

    50 to 300

    400 to 500

    Silicone with semi-conductive layer (optionally with metal housing),

    in combination with distribution kitSilicone with semi-conductive layer (optionally with metal housing),in combination with distribution kit

    Tyco ElectronicsRaychem

    RSTI-58xx 25 to 300 Si li cone with semi-conduct ive layer, wi th capaci tive measur ing point ,in combination with distribution kit RSTI-TRF0x

    ABB Kabeldon CSE-A 12630-xx 25 to 630 EPDM with semi-conductive layer, in combination with distribution kit

    Thermoplastic-insulated cables 24 kV according to IEC 60502-2 and VDE 0276-620

    1-core cable,PE and XLPE-insulated,N2YSY (Cu) andN2XSY (Cu)orNA2YSY (Al) andNA2XSY (Al)

    Euromold K400TB / GK430TB / GK440TB / GK484TB / GK489TB / G

    35 to 30035 to 300400 to 63035 to 630800 to 1200

    EPDM with semi-conductive layerEPDM with semi-conductive layerEPDM with semi-conductive layerEPDM with semi-conductive layerEPDM with semi-conductive layer

    nkt cables CB 24-630CB 36-630(1250)CB 42-1250-3

    25 to 300400 to 630630 to 1000

    Silicone with semi-conductive layer (optionally with metal housing)Silicone with semi-conductive layerSilicone with semi-conductive layer

    Sdkabel SET 24SEHDT 23

    50 to 300400 to 500

    Silicone with semi-conductive layer (optionally with metal housing)Silicone with semi-conductive layer (optionally with metal housing)

    Tyco ElectronicsRaychem

    RSTI-58xxRSTI-595x

    25 to 300400 to 800

    Silicone with semi-conductive layer, with capacitive measuring pointSilicone with semi-conductive layer, with capacitive measuring point

    ABB Kabeldon CSE-A 24630-xx 25 to 630 EPDM with semi-conductive layer

    3-core cable,PE and XLPE-insulated,N2YSY (Cu) andN2XSY (Cu)orNA2YSY (Al) andNA2XSY (Al)

    Euromold K400TB / GK430TB / G

    35 to 30035 to 300

    EPDM with semi-conductive layer, in combination with distribution kitEPDM with semi-conductive layer, in combination with distribution kit

    nkt cables CB 24-630 25 to 300 Silicone with semi-conductive layer (optionally with metal housing),in combination with distribution kit

    Sdkabel SET 24SEHDT 23

    50 to 300400 to 500

    Silicone with semi-conductive layer (optionally with metal housing),in combination with distribution kitSilicone with semi-conductive layer (optionally with metal housing),in combination with distribution kit

    Tyco ElectronicsRaychem

    RSTI-58xx 25 to 300 Si li cone with semi-conduct ive layer, wi th capaci tive measur ing point ,in combination with distribution kit RSTI-TRF0x

    ABB Kabeldon CSE-A 24630-xx 25 to 630 EPDM with semi-conductive layer, in combination with distribution kit

    Thermoplastic-insulated cables 36 kV according to IEC 60502-2 and VDE 0276-620

    1-core cable,

    PE and XLPE-insulatedN2YSY (Cu) andN2XSY (Cu)orNA2YSY (Al) andNA2XSY (Al)

    Euromold M400TB / G

    M430TB / GM440TB / GM484TB / GM489TB / G

    35 to 300

    35 to 300400 to 63035 to 630800 to 1200

    EPDM with semi-conductive layer

    EPDM with semi-conductive layerEPDM with semi-conductive layerEPDM with semi-conductive layerEPDM with semi-conductive layer

    nkt cables CB 36-630CB 36-630(1250)CB 42-1250-3

    25 to 300400 to 630630 to 1000

    Silicone with semi-conductive layer (optionally with metal housing)Silicone with semi-conductive layerSilicone with semi-conductive layer

    Sdkabel SET 36SEHDT 33

    70 to 300300 to 500

    Silicone with semi-conductive layer (optionally with metal housing)Silicone with semi-conductive layer (optionally with metal housing)

    Tyco ElectronicsRaychem

    RSTI-68xxRSTI-695x

    25 to 300400 to 800

    Silicone with semi-conductive layer, with capacitive measuring pointSilicone with semi-conductive layer, with capacitive measuring point

    ABB Kabeldon CSE-A 36630-xx 50 to 630 EPDM with semi-conductive layer

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    43/64

    43Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    ComponentsPanel connection with outside cone(commercially available cable plugs and bar connections)

    Paper-insulated belted cables (non-draining cables) 12 kV according to IEC 60055 and VDE 0255

    3-core cable,paper insulatedNKBA (Cu), NKBY (Cu),NKRA (Cu) and NKFA(Cu)or

    NAKBA (Al), NAKBY (Al),NAKRA (Al) and NAKFA(Al)

    Euromold 400TB / G

    430TB-630A

    35 to 300

    35 to 300

    EPDM with semi-conductive layerin combination with distribution kit MINDEPDM with semi-conductive layerin combination with distribution kit MIND

    nkt cables CB 24-630 25 to 240 Sil icone with semi-conductive layer (optionally with metal housing),in combination with transition sealing end type SEV 10

    Paper-insulated belted cables (non-draining cables) 12 kV according to GOST 18410-73

    3-core cable,paper insulatedASB and ASBL

    Euromold 400TB / G

    430TB-630A

    35 to 300

    35 to 300

    EPDM with semi-conductive layerin combination with distribution kit MINDEPDM with semi-conductive layerin combination with distribution kit MIND

    nkt cables CB 24-630 25 to 240 Sil icone with semi-conductive layer (optionally with metal housing),in combination with transition sealing end type SEV 10

    Paper-insulated belted cables (mass-impregnated cables) 12 kV according to GOST 18410-73

    3-core cable,paper insulatedNKBA (Cu), NKBY (Cu),NKRA (Cu) and NKFA (Cu)orNAKBA (Al), NAKBY (Al),NAKRA (Al) und NAKFA (Al)

    nkt cables CB 24-630 25 to 240 Sil icone with semi-conductive layer (optionally with metal housing),in combination with transition sealing end type SEV 10

    Paper-insulated belted cables (mass-impregnated cables) 12 kV according to GOST 18410-73

    3-core cable,paper insulatedASB and ASBL

    nkt cables CB 24-630 25 to 240 Sil icone with semi-conductive layer (optionally with metal housing),in combination with transition sealing end type SEV 10

    Commercially available bar systems

    Bar type Bar connection Comment

    Make Type Conductormaterial

    Max. ratedcurrent

    Solid-insulated bar MGCMoser Glaser

    Duresca DE Aluminum 1250 A Outer sheath made of polyamide(polyamide tube)Duresca DE Copper 1250 A

    Duresca DG Aluminum 1250 A Outer sheath made of CrNi steel or aluminum(metal sheath)Duresca DG Copper 1250 A

    Preissinger ISOBUS MR Aluminum 1250 A Outer sheath made of heat shrinkable tube;insulated with cast-resin impregnated paper bandage

    ISOBUS MR Copper 1250 A

    Surge-proof caps

    Make Type Size Rated voltage Comment

    Outside-cone plug-insystem according toEN 50181

    3M SP 33SP 33SP 33

    Outside cone type COutside cone type COutside cone type C

    12 kV24 kV36 kV

    Silicone with semi-conductive layer

    NexansEuromold

    400DR-BK400DR-BM400DR-B

    Outside cone type COutside cone type COutside cone type C

    12 kV24 kV36 kV

    EPDM with semi-conductive layer

    nkt cables CBC 40.5-630CBC 40.5-630CBC 40.5-630

    Outside cone type COutside cone type COutside cone type C

    12 kV24 kV36 kV

    Silicone with semi-conductive layer

    Sdkabel SP 33SP 33SP 33

    Outside cone type COutside cone type COutside cone type C

    12 kV24 kV36 kV

    Silicone with semi-conductive layer

    Thermoplastic-insulated cables 36 kV according to IEC 60502-2 and VDE 0276-620

    3-core cable,PE and XLPE-insulatedN2YSY (Cu) and

    N2XSY (Cu)orNA2YSY (Al) andNA2XSY (Al)

    Euromold M400TB / GM430TB / G

    35 to 30035 to 300

    EPDM with semi-conductive layer, in combination with distribution kitEPDM with semi-conductive layer, in combination with distribution kit

    nkt cables CB 36-630 25 to 300 Silicone with semi-conductive layer (optionally with metal housing),in combination with distribution kit

    Sdkabel SET 36SEHDT 33

    50 to 300400 to 500

    Silicone with semi-conductive layer (optionally with metal housing),in combination with distribution kitSilicone with semi-conductive layer (optionally with metal housing),in combination with distribution kit

    Tyco ElectronicsRaychem

    RSTI-66xx

    RSTI-68xx

    25 to 300

    25 to 300

    Silicone with semi-conductive layer, with capacitive measuring point,in combination with distribution kit RSTI-TRF0xSilicone with semi-conductive layer, with capacitive measuring point,in combination with distribution kit RSTI-TRF0x

    ABB Kabeldon CSE-A 36630-xx 25 to 630 EPDM with semi-conductive layer, in combination with distribution kit

    Cable type Cable sealing end Comment

    Make Type Cross-sectionmm2

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    44/64

    44 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Installation possibilities with outside cone for cable connections and surge arresters

    Components

    1) Observe the actual current and short-current carrying capacity of the cables and the sealing ends.

    Numberof cablesper paneland phase

    Make Ratedvolt-age

    Conductorcross-section1)

    Insula-tion

    Cable T-plugs Coupling inserts /coupling plugs

    Surge arresterswith coupling inserts

    According tostandard

    ArrestersCouplinginserts

    kV mm2 bolted bolted additionally

    GOST forRussia & CISGB / DL for China

    Circuit-breaker panel 1250 A Disconnector panel 1250 A1 Nexans

    Euromold122436

    25 to 30035 to 30050 to 240

    EPDM 1x 400TB/G1x K400TB/G1x M400TB/G

    400PB-5(10)-SA-xxx400PB-5(10)-SA-xxx400PB-5(10)-SA-xxx

    IEC

    122436

    25 to 30035 to 30050 to 240

    EPDM 1x 430TB/G1x K430TB/G1x M430TB/G

    300SA-5(10)SA300SA-5(10)SA300SA-5(10)SA

    IEC

    122436

    400 to 630400 to 630300 to 630

    EPDM 1x 440TB/G1x K440TB/G1x M440TB/G

    400PB-5(10)-SA-xxx400PB-5(10)-SA-xxx400PB-5(10)-SA-xxx

    IEC

    122436

    50 to 63035 to 63035 to 630

    EPDM 1x 484TB/G1x K484TB/G1x M484TB/G

    800SA-10-xxx800SA-10-xxx800SA-10-xxx

    IEC

    122436

    800 to 1200800 to 1200800 to 1200

    EPDM 1x 489TB/G1x K489TB/G1x M489TB/G

    800SA-10-xxx800SA-10-xxx800SA-10-xxx

    IEC

    Sdkabel 1224

    36

    50 to 30025 to 240

    70 to 300

    Silicone 1x SET 121x SET 24

    1x SET 36

    MUT 23MUT 23

    MUT 33

    KU 33

    IEC

    122436

    300 to 500300 to 630300 to 500

    Silicone 1x SEHDT 131x SEHDT 231x SEHDT 33

    MUT 23MUT 23MUT 33

    KU 33

    IEC

    nkt cables 122436

    25 to 30025 to 30025 to 300

    Silicone 1x CB 12-6301x CB 24-6301x CB 36-630

    CSA 12-xCSA 24-xCSA 36-x

    IEC

    122436

    400 to 630400 to 630400 to 630

    Silicone 1x CB 36-630(1250)1x CB 36-630(1250)1x CB 36-630(1250)

    CSA 12-xCSA 24-xCSA 36-x

    IEC

    122436

    630 to 1000630 to 1000630 to 1000

    Silicone 1x CB 42-1250-31x CB 42-1250-31x CB 42-1250-3

    CSA 12-xCSA 24-xCSA 36-x

    IEC

    TycoElectronicsRaychem

    122436

    25 to 30025 to 30035 to 300

    Silicone 1x RSTI-58xx1x RSTI-58xx1x RSTI-68xx

    RSTI-CC-58SAxxxxRSTI-CC-58SAxxxx

    IEC

    1224

    36

    400 to 800400 to 800

    400 to 800

    Silicone 1x RSTI-395x1x RSTI-595x

    1x RSTI-695x

    RSTI-CC-58SAxxxxor

    RSTI-CC-68SAxxxx

    IEC

    ABBKabeldon

    122436

    25 to 63025 to 63050 to 630

    EPDM 1x CSE-A 12630-xx1x CSE-A 24630-xx1x CSE-A 36630-xx

    IEC

    2 NexansEuromold

    122436

    25 to 30035 to 30050 to 240

    EPDM 2x 400TB/G2x K400TB/G2x M400TB/G

    1x 400CP1x K400CP1x M400CP

    400PB-5(10)-SA-xxx400PB-5(10)-SA-xxx400PB-5(10)-SA-xxx

    IEC

    122436

    25 to 30035 to 30050 to 240

    EPDM 1x 430TB/G1x K430TB/G1x M430TB/G

    1x 300PB/G1x K300PB/G1x K300PB/G

    300SA-5(10)SA300SA-5(10)SA300SA-5(10)SA

    IEC

    122436

    400 to 630400 to 630300 to 630

    EPDM 2x 440TB/G2x K440TB/G2x M440TB/G

    1x 400CP1x K400CP1x M400CP

    400PB-5(10)-SA-xxx400PB-5(10)-SA-xxx400PB-5(10)-SA-xxx

    IEC

    122436

    50 to 63035 to 63035 to 630

    EPDM 1x 484TB/G1x K484TB/G1x M484TB/G

    1x 804TB/G1x K804TB/G1x M804TB/G

    800SA-10-xxx800SA-10-xxx800SA-10-xxx

    IEC

    12

    2436

    800 to 1200

    800 to 1200800 to 1200

    EPDM 1x 489TB/G

    1x K489TB/G1x M489TB/G

    1x 809PB/G

    1x K809PB/G1x M809PB/G

    800SA-10-xxx

    800SA-10-xxx800SA-10-xxx

    IEC

    Sdkabel 1224

    50 to 30025 to 240

    Silicone 1x SET 121x SET 24

    1x SEHDK 13.11x SEHDK 23.1

    MUT 23MUT 23

    IEC

    1224

    50 to 30025 to 240

    Silicone 2x SET 122x SET 24

    1x KU 23.21x KU 23.2

    MUT 23MUT 23

    IEC

    122436

    300 to 500300 to 630300 to 500

    Silicone 2x SEHDT 132x SEHDT 232x SEHDT 33

    1x KU 331x KU 331x KU 33

    MUT 23MUT 23MUT 33

    KU 33

    IEC

  • 7/25/2019 Catalog HA 35.51 Fixed-Mounted Circuit-Breaker Switchgear NXPLUS

    45/64

    45Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2015

    Installation possibilities with outside cone for cable connections and surge arresters

    Components

    1) Observe the actual current and short-current carrying capacity of the cables and the sealing ends.

    Numberof cablesper paneland phase

    Make Ratedvolt-age

    Conductorcross-section1)

    Insula-tion

    Cable T-plugs Coupling inserts /coupling plugs

    Surge arresterswith coupling inserts

    According tostandard

    ArrestersCouplinginserts

    kV mm2 bolted bolted additionally

    GOST forRussia & CISGB / DL for China

    Circuit-breaker panel 1250 A Disconnector panel 1250 A2 nkt cables 12

    2436

    25 to 30025 to 30025 to 300

    Silicone 1x CB 12-6301x CB 24-6301x CB 36-630

    1x CC 12-6301x CC 24-6301x CC 36-630

    CSA 12-xCSA 24-xCSA 36-x

    IEC

    122436

    25 to 30025 to 30025 to 300

    Silicone 2x CB 12-6302x CB 24-6302x CB 36-630

    1x CP 630-C1x CP 630-C1x CP 630-C

    CSA 12-xCSA 24-xCSA 36-x

    IEC

    122436

    400 to 630400 to 630400 to 630

    Silicone 1x CB 36-630(1250)1x CB 36-630(1250)1x CB 36-630(1250)

    1x CC 36-630(1250)1x CC 36-630(1250)1x CC 36-630(1250)

    CSA 12-xCSA 24-xCSA 36-x

    IEC

    122436

    400 to 630400 to 630400 to 630

    Silicone 2x CB 36-630(1250)2x CB 36-630(1250)2x CB 36-630(1250)

    1x CP 630-M161x CP 630-M161x CP 630-M16

    CSA 12-xCSA 24-xCSA 36-x

    IEC

    122436

    630 to 1000630 to 1000630 to 1000

    Silicone 1x CB 42-1250-31x CB 42-1250-31x CB 42-1250-3

    1x CC 42-2500-31x CC 42-2500-31x CC 42-2500-3

    CSA 12-xCSA 24-xCSA 36-x

    IEC

    TycoElectronics

    Raychem

    1224

    36

    25 to 30025 to 300

    35 to 300

    Silicone 1x RSTI-58xx1x RSTI-58xx

    1x RSTI-68xx

    1x RSTI-CC-58xx1x RSTI-CC-58xx

    1x RSTI-CC-68xx

    RSTI-CC-58SAxxxxRSTI-CC-58SAxxxx

    IEC

    122436

    400 to 800400 to 800400 to 800

    Silicone 1x RSTI-395x1x RSTI-595x1x RSTI-695x

    1x RSTI-CC-395x1x RSTI-CC-595x1x RSTI-CC-695x

    RSTI-CC-58SAxxxxorRSTI-CC-68SAxxxx

    IEC

    ABBKabeldon

    122436

    25 to 63025 to 63050 to 630

    EPDM 2x CSE-A 12630-xx2x CSE-A 24630-xx2x CSE-A-36630-xx

    PC 630-3PC 630-3PC 630-3 L

    IEC

    3 NexansEuromold

    122436

    25 to 30035 to 30050 to 240

    EPDM 3x 400TB/G3x K400TB/G3x M400TB/G

    2x400CP2xK400CP2xM400CP

    IEC

    122436

    25 to 30035 to 30050 to 240

    EPDM 1x 430TB/G1x K430TB/G1x M430TB/G

    x 300PB/G2x K300PB/G2x K300PB/G

    IEC

    122436

    400 to 630400 to 630300 to 630

    EPDM 3x 440TB/G3x K440TB/G3x M440TB/G

    2x400CP2xK400CP2xM400CP

    IEC

    1224

    36

    50 to 63035 to 630

    35 to 630

    EPDM 1x 484TB/G1x K484TB/G

    1x M484TB/G

    2x 804TB/G2x K804TB/G

    2x M804TB/G

    IEC

    122436

    800 to 1200800 to 1200800 to 1200

    EPDM 1x 489TB/G1x K489TB/G1x M489TB/G

    2x 809PB/G2x K809PB/G2x M809PB/G

    IEC

    nkt cables 122436

    25 to 30025 to 30025 to 300

    Silicone 1x CB 12-6301x CB 24-6301x CB 36-630

    2x CC 12-6302x CC 24-6302x CC 36-630

    IEC

    122436

    25 to 30025 to 30025 to 300

    Silicone 3x CB 12-6303x CB 24-6303x CB 36-630

    2x CP 630-C2x CP 630-C2x CP 630-C

    IEC

    122436

    400 to 630400 to 630400 to 630

    Silicone 1x CB 36-630(1250)1x CB 36-630(1250)1x CB 36-630(1250)

    2x CC 36-630(1250)2x CC 36-630(1250)2x CC 36-630(1250)