Catalogue FlowBar www.air-diffusion.co.uk sales@air-diffusion.co.uk High Capacity Slot Diffuser

Upload: others

Post on 24-Feb-2022

6 views

Category:

Documents


0 download

TRANSCRIPT

Catalogue

FlowBar

[email protected]

High Capacity Slot Diffuser

Air Diffusion FlowBar2

ContentIntroduction .............................................................................................. 4

Diffuser Specification ................................................................................. 5

Air Patterns ............................................................................................... 6

Flange Styles ............................................................................................. 7

Curved Sections ........................................................................................ 8

Corner Sections ......................................................................................... 9

Performance Data ............................................................................. 10 - 25

Standard Fixing Details .............................................................................26

Dimensions - Diffuser ......................................................................... 27 - 29

Installation Details .............................................................................30 - 32

Ordering Information - Diffusers ................................................................33

Plenum Boxes ....................................................................................34 - 36

Accessories........................................................................................37 - 38

Order Information - Plenum Boxes.............................................................39

www.air-diffusion.co.uk 3

Swegon R&D AcademyThe Test Centre at Whitstable provides state of the art facilities for testing a complete range of products. It was designed in accordance with BSRIA recommendations and benefits from third party annual assessment. It has a well equipped demonstration area where tests can be witnessed by contractors, consultants and end clients. Third party witnessing by BSRIA is available if required.

The test facility is fitted with the latest equipment and exceeds the requirements of BS EN 12238:2001 (for air terminal devices aerodynamic testing and rating for mixed flow applications) with a test room size of 7.5m long x 5.6m wide x 2.8m high. Ceiling heights and floor voids can also be adjustable depending on the test regime required.

A purpose designed air handling system is able to supply conditioned air across a wide temperature range in both heating and cooling modes with volumes up to the equivalent of 20 air changes per hour being available.

Sophisticated measuring and logging equipment is able to monitor air volumes, velocities, pressures and temperatures as well as airflow pattern visualisation via the use of smoke generation within the test laboratory.

For bespoke testing please get in touch with us.

Air Diffusion FlowBar4

IntroductionFlowBar is an architecturally designed high capacity linear slot diffuser. It is designed to combine a high air handling capacity with maximum flexibility and is suitable for either ceiling or sidewall applications. The flexibility of the system can blend into a design or provide contrast with its striking but simple design.

FlowBar is a flexible system that can provide straight lines or curves to blend with other architectural elements and enhance the overall concept of the project.

Key Features

▸ High capacity single slot diffuser available in five slot widths of 25mm, 38mm, 51mm, 63mm and 76mm

▸ Surface mounted and plaster frame border frames available

▸ Choice of HT (High Throw) series horizontal or JT (Jet Throw) series vertical air patterns

▸ Curved Sections

▸ Ceiling or Sidewall Applications

▸ Modular or Continuous Lengths

▸ Mitred Corner Pieces

▸ Angled End Sections

▸ Adjustable Discharge Pattern

▸ Concealed Fixing

▸ Matching Plenum Boxes

Ceiling Mounted High Throw

Wall Mounted Jet Throw

www.air-diffusion.co.uk 5

FL-10-HT25mm Slot

FL-15-HT38mm Slot

FL-20-HT51mm Slot

FL-25-HT63mm Slot

FL-30-HT76mm Slot

FL-10-JT25mm Slot

FL-15-JT38mm Slot

FL-20-JT51mm Slot

FL-25-JT63mm Slot

FL-30-JT76mm Slot

The High Throw series is primarily designed for ceiling applications and allows the air diffuser to become inconspicuous, whilst fully integrating into the ceiling system.

The FlowBar systems satisfy both architectural and engineering requirements for designing an air distribution system that will maintain optimum room air conditions whilst being efficient yet inconspicuous.

Integral pattern controllers are 600mm in length allowing the airstream to be directed left and right for horizontal and vertical airflow.

The Jet Throw series has pattern flow controllers to allow the airstream to be jetted in a horizontal direction (sidewall mounted) whilst fully integrating into the wall system.The FlowBar systems satisfy both architectural and engineering requirements for designing an air distribution system that will maintain optimum room air conditions whilst being an integral component of the architectural concept of the project.

Integral pattern controllers 600mm in length allow the airstream to be directed vertically left and right (ceiling application) and up and down (sidewall application) at a 45˚ angle.

Specification High Throw (HT) Series

Specification Jet Throw (JT) Series

Standard slot sizes are 25mm, 38mm, 51mm, 63mm and 76mm with single section lengths available up to 2400mm.

Frame styles 66 (surface mounted), 22 and 55 (plaster frame border) and 11 flangeless are available as standard.

Factory engineered plenum boxes are supplied to ensure a trouble free installation and to ensure published performance data is met.

Jet Throw pattern controllers allow extended throws in typical high bay applications for heated and/or cooled air.

Jet Throw pattern controllers are useful along perimeter walls where heated air can be directed downward.

Standard slot sizes are 25mm, 38mm, 51mm, 63mm and 76mm with single section lengths available up to 2400mm.

Frame styles 66 (surface mounted), 22 and 55 (plaster frames) and 11 flangeless are available as standard.

Factory engineered plenum boxes are supplied to ensure a trouble free installation and to ensure published performance data is met.

Air Diffusion FlowBar6

Air Patterns

High Throw (H T) Ceiling Mounted

Horizontal Left Horizontal Right Vertical

Jet Throw (JT) Sidewall Mounted

Horizontal Upward Downward

www.air-diffusion.co.uk 7

Flange Styles

Standard Types 11, 22, 55 & 66

Type 66 Surface Mounting

Type 55 Deep Plaster Frame

Type 22 Shallow Plaster Frame

Type 11 Flangeless

Air Diffusion FlowBar8

Key

Curved Supply

Curving is only possible with the HT model using border types 11/22/66.

B = Overall Width T = Overall Length C = Overall Arc Length L = Slot Width

Please contact our technical team to discuss curved FlowBar in more detail including any special applications not covered in this catalogue.

Curved Sections

Minimum Curve Radius

HT High Throw - Border 22

Slot Width Min Radius (mm)

FL10 25 1700

FL15 38 1700

FL20 51 45000

HT High Throw - Border 11

Slot Width Min Radius (mm)

FL10 25 800

FL15 38 1200

FL20 51 2100

HT High Throw - Border 66

Slot Width Min Radius (mm)

FL10 25 800

FL15 38 1200

FL20 51 2100

www.air-diffusion.co.uk 9

90˚ Mitred Corner Multidirection Supply

Slot/Style Width T BBorder 66 25 200 95Border 22 25 200 107Border 55 25 200 70Border 11 25 200 70Border 66 38 200 121Border 22 38 200 133Border 55 38 200 95Border 11 38 200 95Border 66 51 200 146Border 22 51 200 158Border 55 51 200 121Border 11 51 200 121Border 66 63 300 172Border 22 63 300 172Border 55 63 300 146Border 11 63 300 146Border 66 76 300 197Border 22 76 300 197Border 55 76 300 172Border 11 76 300 172

Slot/Style Width T BBorder 66 25 200 95Border 22 25 200 107Border 55 25 200 70Border 11 25 200 70Border 66 38 200 121Border 22 38 200 133Border 55 38 200 95Border 11 38 200 95Border 66 51 200 146Border 22 51 200 158Border 55 51 200 121Border 11 51 200 121Border 66 63 300 172Border 22 63 300 172Border 55 63 300 146Border 11 63 300 146Border 66 76 300 197Border 22 76 300 197Border 55 76 300 172Border 11 76 300 172

Corner Sections

90˚ Mitred Corner Multidirection Supply

* Specify Angle

Air Diffusion FlowBar10

Performance Data - High Throw (HT)

Continuous Slot Plenum High Throw (HT)

Data based on active section 1200 long

25mm Slot Width

Air Flow, l/s-m 36 58 79 101 122 144 165

Static Pressure, Pa 7 18 34 55 81 112 148

NC (Noise Criteria) <10 16 26 33 39 44 49

Throw, m 1.5 - 2.5 - 4.3 2.8 - 4 - 5.5 3.8 - 4.5 - 6.5 4.3 - 5.3 - 7.3 4.5 - 5.8 - 8.3 5.3 - 6 - 8.8 5.5 - 6.8 - 9.5

FL-10

38mm Slot Width

Air Flow, l/s-m 43 65 86 108 129 151 173

Static Pressure, Pa 8 18 32 51 73 99 129

NC (Noise Criteria) <10 14 24 31 37 42 48

Throw, m 1.8 - 3 - 5 3 - 4.3 - 5.8 4 - 5 - 6.8 4.3 - 5.5 - 7.5 5 - 5.8 - 8.3 5.3 - 6.5 - 8.8 5.5 - 6.8 - 9.8

FL-15

51mm Slot Width

Air Flow, l/s-m 43 72 101 129 158 187 216

Static Pressure, Pa 5 14 28 46 68 95 127

NC (Noise Criteria) <10 11 22 30 36 41 46

Throw, m 1.5 - 2.8 - 5 2.8 - 4.3 - 6 4 - 5.3 - 7.3 5 - 5.8 - 8.3 5.3 - 6.5 - 9.3 5.8 - 7 - 10 6 - 7.5 - 10.8

FL-20

63mm Slot Width

Air Flow, l/s-m 43 79 115 151 187 223 259

Static Pressure, Pa 3 10 22 38 58 82 110

NC (Noise Criteria) <10 11 23 31 38 43 48

Throw, m 1.3 - 2.5 - 5 3 - 4.5 - 6.5 4.3 - 5.5 - 8 5.3 - 6.5 - 8.8 5.8 - 7 - 10 6.5 - 7.5 - 11 6.8 - 8.3 - 12.8

FL-25

76mm Slot Width

Air Flow, l/s-m 43 86 129 173 216 259 302

Static Pressure, Pa 3 11 25 44 69 99 135

NC (Noise Criteria) <10 <10 18 27 34 40 45

Throw, m 1 - 2.3 - 4.5 3 - 4.5 - 6.8 4.5 - 5.8 - 8.3 5.5 - 6.8 - 9.8 6 - 7.5 - 10.8 6.8 - 8.3 - 12 7.3 - 8.8 - 12.8

FL-30

Length, mm 600 1200 1800 2400 3000

Supply -3 0 +2 +3 +5

Return 0 +3 +5 +6 +8

Table A. NC Correction for Length

Length, mm 600 1200 2400 3000 3600

Throw Correction 0.72 1 1.5 1.7 1.8

Table B. Correction Multiplier for Length

• Pressures are given in Pascal (Pa)

• Pressure loss data assumes a duct velocity is less than 4m/sec in the inlet duct

• Isothermal throw values are given for terminal velocities of 0.8, 0.5 and

0.3m/sec respectively

• Throw data is based on 1200mm active section. For a 600mm section the throw values are 0.72 times those shown. For a 3000mm continuous length, the throw values are 1.7 times those shown and 1.8 for 3600mm units

• Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th, with a room absorption of 10dB, re 10-12 watts, for a 1200mm section. (See Table A for other lengths).

• For supply units used as a return, add 3 NC

• The tests were conducted with no Plenum effect for pressure or sound

• Throw values for High Throw units are based on a 1-way discharge from the slot

• Throws listed are for the 1-way air pattern. For divided airflow, select the airflow in each direction according to the number of slots aimed in that direction, with the total airflow apportioned between slot

www.air-diffusion.co.uk 11

Air Diffusion FlowBar12

25mm Slot

Width

Length 600mm

Air Flow, l/s 12 24 35 47 59 71 83

Total Pressure, Pa 2 8 18 32 50 72 98

Static Pressure, Pa 2 7 16 28 44 63 86

NC (Noise Criteria) <10 <10 <10 20 28 35 40

Throw, m 0.3 - 0.5 - 1.8 1 - 1.8 - 3 1.8 - 2.8 - 3.8 2.5 - 3 - 4.3 2.8 - 3.3 - 5 3 - 3.8 - 5.5 3.3 - 4 - 5.8

Length 1200mm

Air Flow, l/s 19 38 57 76 94 113 132

Total Pressure, Pa 2 7 16 28 44 64 87

Static Pressure, Pa 1 4 10 18 28 40 55

NC (Noise Criteria) <10 <10 <10 16 24 31 37

Throw, m 0.3 - 0.5 - 1.8 1 - 1.8 - 4 1.8 - 3 - 5 2.8 - 4 - 5.5 3.3 - 4.3 - 6 4 - 5 - 6.8 4.3 - 5.3 - 7.3

Length 1500mm

Air Flow, l/s 24 47 71 94 118 142 165

Total Pressure, Pa 2 9 19 34 53 77 104

Static Pressure, Pa 1 4 10 18 28 40 55

NC (Noise Criteria) <10 <10 <10 18 26 33 38

Throw, m 0.3 - 0.5 - 2.3 1 - 2.3 - 4.3 2.3 - 3.3 - 5.5 3 - 4.3 - 6 3.8 - 5 - 7 4.3 - 5.5 - 7.5 5 - 5.8 - 8.3

FL-10 with 150mm inlet

38mm Slot

Width

Length 600mm

Air Flow, l/s 19 33 47 61 76 90 104

Total Pressure, Pa 4 13 26 45 68 96 128

Static Pressure, Pa 4 11 22 38 57 81 109

NC (Noise Criteria) <10 <10 16 25 33 40 46

Throw, m 0.5 - 1.5 -2.8 1.5 - 2.5 - 3.8 2.5 - 3 - 4.3 2.8 - 3.8 - 5 3.3 - 4 - 5.5 3.3 - 4.3 - 6 3.8 - 4.5 - 6.5

Length 1200mm

Air Flow, l/s 38 57 76 94 113 132 151

Total Pressure, Pa 6 14 25 39 56 76 99

Static Pressure, Pa 4 8 14 22 32 44 57

NC (Noise Criteria) <10 <10 12 20 27 33 38

Throw, m 1 - 1.8 - 4 1.8 - 3 - 5 2.8 - 4 - 5.5 3.3 - 4.3 - 6 4 - 5 - 6.8 4.3 - 5.3 - 7.3 4.5 - 5.5 - 8

Length 1500mm

Air Flow, l/s 42 66 90 113 137 160 184

Total Pressure, Pa 6 15 28 44 64 88 116

Static Pressure, Pa 3 7 13 21 30 42 55

NC (Noise Criteria) <10 <10 12 20 27 33 39

Throw, m 1 - 1.8 - 4 1.8 - 3 - 5.3 2.8 - 4.3 - 6 3.3 - 5 - 6.8 4.3 - 5.3 - 7.3 4.5 - 5.8 - 8.3 5 - 6 - 8.5

FL-15 with 150mm inlet

51mm Slot

Width

Length 600mm

Air Flow, l/s 24 40 57 73 90 106 123

Total Pressure, Pa 4 11 22 37 56 78 104

Static Pressure, Pa 4 10 20 34 51 71 95

NC (Noise Criteria) <10 <10 12 21 28 35 40

Throw, m 0.5 - 1.5 - 3 1.8 - 2.8 - 4 2.5 - 3.3 - 5 3 - 4 - 5.5 3.3 - 4.3 - 6 3.8 - 4.5 - 6.8 4 - 5 - 7

Length 1200mm

Air Flow, l/s 42 71 99 127 156 184 212

Total Pressure, Pa 4 11 21 35 52 73 97

Static Pressure, Pa 3 8 16 26 38 54 71

NC (Noise Criteria) <10 <10 20 29 36 42 48

Throw, m 1 - 1.8 - 4 2.3 - 3.3 - 5.5 3 - 4.5 - 6.5 4 - 5.3 - 7.3 4.5 - 5.5 - 8 5 - 6 - 8.5 5.5 - 6.8 - 9.5

Length 1500mm

Air Flow, l/s 47 78 109 139 170 201 231

Total Pressure, Pa 4 10 19 31 46 64 85

Static Pressure, Pa 2 6 12 20 29 41 54

NC (Noise Criteria) <10 <10 19 28 36 42 47

Throw, m 0.5 - 1.5 - 4 1.8 - 3 - 5.5 3 - 4.5 - 6.8 4 - 5.3 - 7.5 4.5 - 5.8 - 8.3 5.3 - 6.5 - 9.3 5.5 - 7 - 9.8

FL-20 with 200mm inlet

FlowBar with Air Diffusion Plenum Box - High Throw (HT)

www.air-diffusion.co.uk 13

25mm Slot

Width

Length 600mm

Air Flow, l/s 24 35 47 59 71 83 94

Total Pressure, Pa 7 16 29 46 66 90 117

Static Pressure, Pa 7 16 28 44 63 86 112

NC (Noise Criteria) <10 <10 19 27 34 40 44

Throw, m 1 - 1.8 - 3 1.8 - 2.8 - 3.8 2.5 - 3 - 4.3 2.8 - 3.3 - 5 3 - 3.8 - 5.5 3.3 - 4 - 5.8 3.8 - 4.3 - 6

Length 1200mm

Air Flow, l/s 33 52 71 90 109 127 146

Total Pressure, Pa 4 10 19 30 44 60 80

Static Pressure, Pa 3 8 16 25 37 51 67

NC (Noise Criteria) <10 <10 13 22 29 35 40

Throw, m 0.5 - 1.5 - 3.3 1.8 - 2.8 - 4.5 2.5 - 3.8 - 5.5 3 - 4.3 - 6 3.8 - 4.5 - 6.8 4.3 - 5.3 - 7.3 4.5 - 5.5 - 7.5

Length 1500mm

Air Flow, l/s 38 61 85 109 132 156 179

Total Pressure, Pa 4 10 19 30 45 63 83

Static Pressure, Pa 3 8 15 24 35 49 65

NC (Noise Criteria) <10 <10 13 22 29 35 40

Throw, m 0.5 - 1.5 - 3.8 1.8 - 2.8 - 5 2.8 - 4 - 5.8 3.3 - 4.5 - 6.8 4.3 - 5.3 - 7.3 4.5 - 5.5 - 8 5 - 6 - 8.5

FL-10 with 200mm inlet

38mm Slot

Width

Length 600mm

Air Flow, l/s 19 33 47 61 76 90 104

Total Pressure, Pa 4 12 24 40 61 86 115

Static Pressure, Pa 4 11 22 38 57 81 109

NC (Noise Criteria) <10 <10 14 24 32 38 45

Throw, m 0.5 - 1.5 -2.8 1.5 - 2.5 - 3.8 2.5 - 3 - 4.3 2.8 - 3.8 - 5 3.3 - 4 - 5.5 3.3 - 4.3 - 6 3.8 - 4.5 - 6.5

Length 1200mm

Air Flow, l/s 38 61 85 109 132 156 179

Total Pressure, Pa 4 12 22 36 54 75 99

Static Pressure, Pa 4 9 18 30 44 61 81

NC (Noise Criteria) <10 <10 15 24 32 38 43

Throw, m 1 - 1.8 - 4 2.3 - 3 - 5 3 - 4.3 - 5.8 3.8 - 4.5 - 6.8 4.3 - 5.5 - 7.3 4.5 - 5.5 - 8 5 - 6 - 8.5

Length 1500mm

Air Flow, l/s 42 71 99 127 156 184 212

Total Pressure, Pa 4 11 21 35 53 74 99

Static Pressure, Pa 3 8 16 26 39 55 73

NC (Noise Criteria) <10 <10 14 24 31 37 43

Throw, m 1 - 1.8 - 4 2.3 - 3.3 - 5.5 3 - 4.5 - 6.5 4 - 5.3 - 7.3 4.5 - 5.5 - 8 5 - 6 - 8.5 5.5 - 6.8 - 9.5

FL-15 with 200mm inlet

51mm Slot

Width

Length 600mm

Air Flow, l/s 24 42 61 80 99 118 137

Total Pressure, Pa 4 12 24 41 63 90 121

Static Pressure, Pa 4 11 24 41 62 88 119

NC (Noise Criteria) <10 <10 <10 13 20 27 32

Throw, m 0.5 - 1.5 - 3 1.8 - 2.8 - 4.3 2.8 - 3.8 - 5 3.3 - 4 - 5.8 3.8 - 4.5 - 6.5 4 - 5 - 7 4.3 - 5.3 - 7.3

Length 1200mm

Air Flow, l/s 42 78 113 149 184 219 255

Total Pressure, Pa 3 10 22 37 57 82 110

Static Pressure, Pa 3 10 20 35 54 76 103

NC (Noise Criteria) <10 <10 13 23 31 37 43

Throw, m 1 - 1.8 - 4 2.5 - 3.8 - 5.5 3.3 - 5 - 6.8 4.5 - 5.5 - 8 5 - 6 - 8.5 5.5 - 6.8 - 9.5 5.8 - 7.3 - 10

Length 1500mm

Air Flow, l/s 47 90 132 175 217 260 302

Total Pressure, Pa 3 9 20 34 53 76 103

Static Pressure, Pa 2 8 18 31 48 68 92

NC (Noise Criteria) <10 <10 15 25 33 39 45

Throw, m 0.5 - 1.5 - 4 2.5 - 3.8 - 6 3.8 -.5.3 - 7.3 5 - 6 - 8.5 5.5 - 6.8 - 9.5 5.8 - 7.3 - 10.3 6.5 - 8 - 11

FL-20 with 300mm inlet

FlowBar with Air Diffusion Plenum Box - High Throw (HT)

Air Diffusion FlowBar14

63mm Slot Width

Length 600mm

Air Flow, l/s 47 68 90 111 132 153 175

Total Pressure, Pa 9 19 33 50 71 96 124

Static Pressure, Pa 9 18 31 47 67 90 117

NC (Noise Criteria) <10 <10 17 26 33 39 44

Throw, m 1.8 - 3 -4.3 2.8 - 3.8 - 5.3 3.3 - 4.3 - 6 4 - 5 - 6.8 4.3 - 5.3 - 7.3 4.5 - 5.5 - 8 5 - 6 - 8.5

Length 1200mm

Air Flow, l/s 66 104 142 179 217 255 293

Total Pressure, Pa 5 13 24 38 56 77 102

Static Pressure, Pa 4 10 19 31 45 62 82

NC (Noise Criteria) <10 <10 20 29 37 44 49

Throw, m 1.5 - 2.8 - 5.3 3 - 4.5 - 6.5 4.3 - 5.5 - 7.5 5 - 6 - 8.5 5.5 - 6.8 - 9.5 5.8 - 7.3 - 10 6.5 - 7.5 - 11

Length 1500mm

Air Flow, l/s 71 113 156 198 241 283 326

Total Pressure, Pa 4 11 21 33 49 68 90

Static Pressure, Pa 3 8 15 24 35 49 65

NC (Noise Criteria) <10 <10 18 28 36 43 49

Throw, m 1.3 - 2.8 - 5.5 3 - 4.5 - 6.8 4 - 5.5 - 8 5.3 - 6.5 - 8.8 5.8 - 7 - 9.8 6 - 7.5 - 10.8 6.8 - 8.3 - 11.5

76mm Slot

Width

Length 600mm

Air Flow, l/s 59 80 101 123 144 165 186

Total Pressure, Pa 13 24 38 55 76 100 128

Static Pressure, Pa 12 22 35 52 71 94 119

NC (Noise Criteria) <10 <10 15 23 30 36 41

Throw, m 2.3 - 3.3 - 5 3 - 4 - 5.8 3.8 - 4.5 - 6.5 4 - 5 - 7 4.5 - 5.5 - 7.5 5 - 5.8 - 8.3 5.3 - 6 - 8.8

Length 1200mm

Air Flow, l/s 94 130 165 201 236 271 307

Total Pressure, Pa 10 18 30 44 61 81 103

Static Pressure, Pa 8 14 23 35 48 63 81

NC (Noise Criteria) <10 <10 17 25 32 39 44

Throw, m 2.5 - 4 - 6 3.8 - 5.3 - 7.3 4.5 - 5.8 - 8.3 5.3 - 6.5 - 9.3 5.8 - 7 - 9.8 6 - 7.3 - 10.3 6.5 - 8 - 11.3

Length 1500mm

Air Flow, l/s 104 146 189 231 274 316 359

Total Pressure, Pa 8 17 28 42 59 78 101

Static Pressure, Pa 6 12 20 29 41 55 71

NC (Noise Criteria) <10 <10 17 25 33 40 46

Throw, m 2.5 - 3.8 - 6.5 3.8 - 5.3 - 7.5 4.5 - 6 - 8.8 5.5 - 7 - 9.8 6 - 7.3 - 10.8 6.5 - 8 - 11.3 7 - 8.5 - 12.3

FL-25 with 250mm inlet

FL-30 with 250mm inlet

FlowBar with Air Diffusion Plenum Box - High Throw (HT)

• Pressures are given in Pascal (Pa)

• Isothermal throw values are given for terminal velocities of 0.8, 0.5 and 0.3m/sec respectively

• Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th, with a room absorption of 10dB, re 10-12 watts

• The tests were conducted with the FlowBar and plenums as a composite assembly

• Throw values for High Throw units are based on a 1-way discharge from the slot

• Throws listed are for the 1-way air pattern. For divided air flow, select the airflow in each direction according to the number of slots aimed in that direction, with the total airflow apportioned between slot

• Plenums not provided by Air Diffusion may demonstrate performance variations from the published data and therefore Air Diffusion would not be able to subsequently guarantee that performance matches our data

www.air-diffusion.co.uk 15

63mm Slot

Width

Length 600mm

Air Flow, l/s 47 68 90 111 132 153 175

Total Pressure, Pa 9 18 32 48 69 93 120

Static Pressure, Pa 9 18 31 47 67 90 117

NC (Noise Criteria) <10 <10 12 21 28 34 40

Throw, m 1.8 - 3 -4.3 2.8 - 3.8 - 5.3 3.3 - 4.3 - 6 4 - 5 - 6.8 4.3 - 5.3 - 7.3 4.5 - 5.5 - 8 5 - 6 - 8.5

Length 1200mm

Air Flow, l/s 66 106 146 186 227 267 307

Total Pressure, Pa 5 12 23 37 55 76 101

Static Pressure, Pa 4 11 20 33 49 68 90

NC (Noise Criteria) <10 <10 16 26 34 41 46

Throw, m 1.5 - 2.8 - 5.3 3 - 4.5 - 6.8 4.3 - 5.5 - 7.5 5.3 - 6 - 8.8 5.5 - 6.8 - 9.8 6 - 7.3 - 10.3 6.5 - 8 - 11.3

Length 1500mm

Air Flow, l/s 71 118 165 212 260 307 354

Total Pressure, Pa 4 10 20 33 49 68 91

Static Pressure, Pa 3 9 17 28 41 58 77

NC (Noise Criteria) <10 <10 16 26 34 41 47

Throw, m 1.3 - 2.8 - 5.5 3 - 4.5 - 7 4.3 - 5.8 - 8.3 5.5 - 6.8 - 9.5 5.8 - 7.3 - 10.3 6.5 - 8 - 11.3 7 - 8.5 - 12

76mm Slot

Width

Length 600mm

Air Flow, l/s 59 80 101 123 144 165 186

Total Pressure, Pa 12 23 37 53 74 97 123

Static Pressure, Pa 12 22 35 52 71 94 119

NC (Noise Criteria) <10 <10 11 19 26 32 37

Throw, m 2.3 - 3.3 - 5 3 - 4 - 5.8 3.8 - 4.5 - 6.5 4 - 5 - 7 4.5 - 5.5 - 7.5 5 - 5.8 - 8.3 5.3 - 6 - 8.8

Length 1200mm

Air Flow, l/s 94 137 179 222 264 307 349

Total Pressure, Pa 9 18 31 48 68 92 119

Static Pressure, Pa 8 16 28 42 60 81 105

NC (Noise Criteria) <10 <10 16 26 33 40 45

Throw, m 2.5 - 4 - 6 3.8 - 5.3 - 7.3 5 - 6 - 8.5 5.5 - 6.8 - 9.5 6 - 7.3 - 10.3 6.5 - 8 - 11.3 7 - 8.5 - 12

Length 1500mm

Air Flow, l/s 104 156 208 260 311 363 415

Total Pressure, Pa 7 16 29 45 64 88 114

Static Pressure, Pa 6 13 24 37 53 73 95

NC (Noise Criteria) <10 <10 17 26 34 41 47

Throw, m 2.5 - 3.8 - 6.5 3.8 - 5.5 - 8 5 - 6.5 - 9.3 5.8 - 7.3 - 10.3 6.5 - 8 - 11.3 7 - 8.5 - 12.3 7.5 - 9.3 - 13

FL-25 with 300mm inlet

FL-30 with 300mm inlet

FlowBar with Air Diffusion Plenum Box - High Throw (HT)

• Pressures are given in Pascal (Pa)

• Isothermal throw values are given for terminal velocities of 0.8, 0.5 and 0.3m/sec respectively

• Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th, with a room absorption of 10dB, re 10-12 watts

• The tests were conducted with the FlowBar and plenums as a composite assembly

• Throw values for High Throw units are based on a 1-way discharge from the slot

• Throws listed are for the 1-way air pattern. For divided air flow, select the airflow in each direction according to the number of slots aimed in that direction, with the total air flow apportioned between slot

• Plenums not provided by Air Diffusion may demonstrate performance variations from the published data and therefore Air Diffusion would not be able to subsequently guarantee that performance matches our data

Air Diffusion FlowBar16

www.air-diffusion.co.uk 17

Air Diffusion FlowBar18

Performance Data - Jet Throw (JT)

Continuous Slot Plenum Jet Throw (JT)

Data based on active section 1200 long

25mm Slot Width

Air Flow, l/s-m 31 62 93 124 155 186 217

Static Pressure, Pa 2 7 15 27 42 61 83

NC (Noise Criteria) <10 <10 17 24 28 32 36

Throw, m 0.5 - 1 - 2.3 1.3 - 2.3 - 4 2.3 - 3 - 5.8 2.8 - 4 - 6.8 3.3 - 5.3 - 7.3 4 - 5.8 - 8 4.5 - 6 - 8.8

FL-10

38mm Slot Width

Air Flow, l/s-m 46 93 139 186 232 279 325

Static Pressure, Pa 2 8 18 31 49 70 95

NC (Noise Criteria) <10 <10 17 22 28 34 40

Throw, m 0.5 - 1.3 - 2.3 1.5 - 2.3 - 4.5 2.3 - 3.3 - 6.8 3 - 4.5 - 8 3.8 - 5.5 - 9.3 4.5 - 6.8 - 9.8 5.3 - 7.5 - 10.8

FL-15

51mm Slot Width

Air Flow, l/s-m 54 116 178 240 302 364 426

Static Pressure, Pa 1 7 15 28 44 64 88

NC (Noise Criteria) <10 <10 18 24 29 33 37

Throw, m 0.3 - 1 - 2.3 1.5 - 2.5 - 4.5 2.5 - 3.8 - 7 3 - 5.- 9.3 4 - 6 - 10.3 5 - 7.3 - 11.3 5.5 - 8.5 - 12.3

FL-20

63mm Slot Width

Air Flow, l/s-m 62 147 232 317 402 488 573

Static Pressure, Pa 1 7 17 31 51 74 102

NC (Noise Criteria) <10 <10 18 25 30 35 39

Throw, m 0.3 - 1 - 2.3 1.8 - 2.5 - 5.3 2.8 - 4 - 8 3.8 - 5.5 - 10.8 4.5 - 7 - 12 5.5 - 8.5 - 13 6.8 - 10 - 14

FL-25

76mm Slot Width

Air Flow, l/s-m 77 178 279 379 480 580 681

Static Pressure, Pa 1 7 17 31 50 73 100

NC (Noise Criteria) <10 <10 15 24 30 35 40

Throw, m 0.3 - 1 - 2.5 1.8 - 2.8 - 5.5 2.8 - 4.3 - 8.5 4 - 5.8 - 11.5 5 - 7.3 - 12.8 6 - 8.8 - 14.3 7 - 10.3 - 15.5

FL-30

Table B. Correction Multiplier for Length

Length, mm 600 1200 2400 3000 3600Throw

Correction 0.72 1 1.5 1.7 1.8

Table A. NC Correction for Length

Length, mm 600 1200 1800 2400 3000Supply -3 0 +2 +3 +5Return 0 +3 +5 +6 +8

• Pressures are given in Pascal (Pa)

• Pressure loss data assumes a duct velocity is less than 4m/sec in the inlet duct

• Isothermal throw values are given for terminal velocities of 0.8, 0.5 and

0.3m/sec respectively

• Throw data is based on 1200mm active section. For a 600mm section the throw values are 0.72 times those shown. For a 3000mm continuous length, the throw values are 1.7 times those shown and 1.8 for 3600mm units

• Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th, with a room absorption of 10dB, re 10-12 watts, for a 1200mm section. See Table A for other lengths

• For supply units used as a return, add 3 NC

• The tests were conducted with no Plenum effect for pressure or sound

• Throw values for Jet Throw units are based on the pattern controller set at 0° discharge vertical flow

www.air-diffusion.co.uk 19

Air Diffusion FlowBar20

25mm Slot

Width

Length 600mm

Air Flow, l/s 24 45 66 87 109 130 151

Total Pressure, Pa 3 11 23 41 63 90 121

Static Pressure, Pa 3 10 21 36 56 80 108

NC (Noise Criteria) <10 <10 16 23 29 34 39

Throw, m 0.5 - 1 - 1.8 1.3 - 1.8 - 3.3 1.5 - 2.5 - 4.3 2.3 - 3.3 - 5 2.8 - 4 - 5.5 3.3 - 4.3 - 6 3.8 - 4.5 - 6.8

Length 1200mm

Air Flow, l/s 47 83 118 153 189 224 260

Total Pressure, Pa 4 12 25 41 63 88 119

Static Pressure, Pa 3 8 17 28 42 60 80

NC (Noise Criteria) <10 <10 18 25 30 34 38

Throw, m 1 - 1.3 - 2.5 1.5 - 2.3 - 4.3 2.3 - 3 - 5.8 2.8 - 4 - 6.8 3.3 - 5.3 - 7.3 4 - 5.8 - 8 4.5 - 6 - 8.5

Length 1500mm

Air Flow, l/s 52 92 132 172 212 252 293

Total Pressure, Pa 4 11 23 40 60 85 114

Static Pressure, Pa 2 6 13 23 34 48 65

NC (Noise Criteria) <10 <10 17 24 29 33 37

Throw, m 1 - 1.3 - 2.5 1.5 - 2.3 - 4.3 2.3 - 3 - 6 2.8 - 4 - 7 3.3 - 5.3 - 8 4 - 6 - 8.5 4.5 - 6.5 - 9.3

38mm Slot

Width

Length 600mm

Air Flow, l/s 28 52 76 99 123 146 170

Total Pressure, Pa 3 11 24 42 64 91 122

Static Pressure, Pa 2 7 14 24 37 52 70

NC (Noise Criteria) <10 <10 <10 16 24 31 37

Throw, m 0.3 - 1 -1.5 1 - 1.5 - 2.8 1.5 - 2.3 - 4.3 1.8 - 2.8 - 5.3 2.3 - 3.3 - 5.8 2.8 - 4 - 6.5 3 - 4.5 - 7

Length 1200mm

Air Flow, l/s 57 85 113 142 170 198 227

Total Pressure, Pa 8 17 31 48 70 95 124

Static Pressure, Pa 2 4 8 12 18 24 31

NC (Noise Criteria) <10 <10 <10 <10 16 22 27

Throw, m 0.5 - 1.3 - 2.3 1.3 - 1.5 - 3.3 1.5 - 2.3 - 4.5 1.8 - 2.8 - 5.5 2.3 - 3.3 - 6.8 2.5 - 4 - 7.5 3 - 4.5 - 8

Length 1500mm

Air Flow, l/s 66 94 123 151 179 208 236

Total Pressure, Pa 10 20 33 50 71 95 122

Static Pressure, Pa 2 3 6 9 13 17 22

NC (Noise Criteria) <10 <10 <10 <10 12 17 22

Throw, m 0.5 - 1.3 - 2.5 1.3 - 1.5 - 3.3 1.5 - 2.3 - 4.3 1.8 - 2.8 - 5.3 2.3 - 3 - 6.5 2.5 - 3.8 - 7.3 2.8 - 4.3 - 8.3

51mm Slot

Width

Length 600mm

Air Flow, l/s 33 66 99 132 165 198 231

Total Pressure, Pa 2 8 18 33 51 74 100

Static Pressure, Pa 1 6 13 23 36 51 70

NC (Noise Criteria) <10 <10 14 21 27 33 38

Throw, m 0.3 - 0.5 - 1.5 1 - 1.5 - 3 1.5 - 2.3 - 4.5 2.3 - 3 - 6 2.5 - 3.8 - 7 3 - 4.5 - 7.5 3.8 - 5.3 - 8.3

Length 1200mm

Air Flow, l/s 66 113 160 208 255 302 349

Total Pressure, Pa 4 12 23 39 58 82 110

Static Pressure, Pa 1 4 8 14 21 30 40

NC (Noise Criteria) <10 12 21 27 32 36 40

Throw, m 0.3 - 1 - 2.3 1.3 - 1.8 - 3.8 1.8 - 2.8 - 5.3 2.3 - 3.3 - 6.8 2.8 - 4.3 - 8.3 3.3 - 5 - 9.3 3.8 - 5.8 - 10

Length 1500mm

Air Flow, l/s 71 123 175 227 278 330 382

Total Pressure, Pa 4 12 24 40 61 85 114

Static Pressure, Pa 1 3 6 11 16 23 30

NC (Noise Criteria) <10 13 21 27 32 36 40

Throw, m 0.3 - 1 - 2.3 1 - 1.8 - 3.8 1.8 - 2.5 - 5.3 2.3 - 3.3 - 6.8 2.8 - 4 - 8.3 3 - 5 - 9.5 3.8 - 5.5 - 10.3

FL-10 with 200mm inlet

FL-15 with 200mm inlet

FL-20 with 200mm inlet

FlowBar with Air Diffusion Plenum Box - Jet Throw (JT)

www.air-diffusion.co.uk 21

25mm Slot

Width

Length 600mm

Air Flow, l/s 24 45 66 87 109 130 151

Total Pressure, Pa 3 10 22 38 59 84 114

Static Pressure, Pa 3 10 21 36 56 80 108

NC (Noise Criteria) <10 <10 16 22 28 33 38

Throw, m 0.5 - 1 - 1.8 1.3 - 1.8 - 3.3 1.5 - 2.5 - 4.3 2.3 - 3.3 - 5 2.8 - 4 - 5.5 3.3 - 4.3 - 6 3.8 - 4.5 - 6.8

Length 1200mm

Air Flow, l/s 47 85 123 160 198 236 274

Total Pressure, Pa 3 10 21 37 56 79 107

Static Pressure, Pa 3 9 18 31 47 66 89

NC (Noise Criteria) <10 <10 18 25 30 35 39

Throw, m 1 - 1.3 - 2.5 1.5 - 2.3 - 4.5 2.3 - 3.3 - 5.8 2.8 - 4.3 - 6.8 3.8 - 5.3 - 7.5 4.3 - 5.8 - 8.3 5 - 6.5 - 8.8

Length 1500mm

Air Flow, l/s 52 99 146 193 241 288 335

Total Pressure, Pa 3 10 21 37 58 82 112

Static Pressure, Pa 2 7 16 28 44 63 85

NC (Noise Criteria) <10 <10 19 26 31 35 40

Throw, m 1 - 1.3 - 2.5 1.5 - 2.5 - 5 2.5 - 3.3 - 6.5 3 - 4.5 - 7.3 4 - 5.8 - 8.3 4.5 - 6.5 - 9.3 5.5 - 7 - 9.8

38mm Slot

Width

Length 600mm

Air Flow, l/s 28 59 90 120 151 182 212

Total Pressure, Pa 2 9 20 37 58 84 115

Static Pressure, Pa 2 8 20 35 55 80 110

NC (Noise Criteria) <10 <10 <10 18 27 35 43

Throw, m 0.3 - 1 -1.5 1.3 - 1.5 - 3.3 1.5 - 2.5 - 5 2.3 - 3.3 - 5.8 2.8 - 4.3 - 6.8 3.3 - 5.3 - 7.3 4 - 5.5 - 8

Length 1200mm

Air Flow, l/s 57 113 170 227 283 340 396

Total Pressure, Pa 2 9 21 37 58 83 113

Static Pressure, Pa 2 8 18 31 49 70 95

NC (Noise Criteria) <10 <10 10 21 30 37 45

Throw, m 0.5 - 1.3 - 2.3 1.5 - 2.3 - 4.5 2.3 - 3.3 - 6.8 3 - 4.5 - 8 3.8 - 5.5 - 9.3 4.8 - 6.8 - 9.8 5.3 - 7.5 - 10.8

Length 1500mm

Air Flow, l/s 66 132 198 264 330 396 463

Total Pressure, Pa 2 9 20 35 55 79 107

Static Pressure, Pa 2 7 15 27 42 61 83

NC (Noise Criteria) <10 <10 10 21 29 36 43

Throw, m 0.5 - 1.3 - 2.5 1.5 - 2.5 - 4.5 2.5 - 3.3 - 7 3 - 4.5 - 8.8 4 - 5.8 - 9.8 4.5 - 7 - 10.8 5.5 - 8.3 - 11.5

51mm Slot

Width

Length 600mm

Air Flow, l/s 33 76 118 160 203 245 288

Total Pressure, Pa 2 8 20 36 58 85 117

Static Pressure, Pa 1 7 8 34 54 79 108

NC (Noise Criteria) <10 <10 <10 17 25 31 36

Throw, m 0.3 - 0.5 - 1.5 1.3 - 1.8 - 3.3 1.8 - 2.8 - 5.5 2.5 - 3.8 - 6.8 3 - 4.5 - 7.5 3.8 - 5.5 - 8.3 4.3 - 6.5 - 9.3

Length 1200mm

Air Flow, l/s 66 137 208 278 349 420 491

Total Pressure, Pa 2 8 19 34 54 77 106

Static Pressure, Pa 1 6 14 25 40 58 79

NC (Noise Criteria) <10 <10 17 24 31 37 41

Throw, m 0.3 - 1 - 2.3 1.5 - 2.3 - 4.5 2.3 - 3.3 - 6.8 3 - 4.5 - 8.8 3.8 - 5.8 - 10 4.5 - 6.8 - 11 5.3 - 8 - 12

Length 1500mm

Air Flow, l/s 71 156 241 326 411 496 580

Total Pressure, Pa 2 8 19 34 54 79 108

Static Pressure, Pa 1 5 12 22 35 51 70

NC (Noise Criteria) <10 <10 19 26 32 38 43

Throw, m 0.3 - 1 - 2.3 1.5 - 2.3 - 4.5 2.5 -3.3 - 7 3 - 5 - 9.5 4 - 6 - 11 5 - 7.3 - 12 5.5 - 8.5 - 12.8

FL-10 with 250mm inlet

FL-15 with 300mm inlet

FL-20 with 300mm inlet

FlowBar with Air Diffusion Plenum Box - Jet Throw (JT)

Air Diffusion FlowBar22

63mm Slot Width

Length 600mm

Air Flow, l/s 38 85 132 179 227 274 321

Total Pressure, Pa 2 8 19 35 55 81 111

Static Pressure, Pa 1 6 15 27 43 63 87

NC (Noise Criteria) <10 <10 <10 13 21 28 34

Throw, m 0.3 - 0.5 -1.5 1.3 - 1.8 - 3.3 1.8 - 2.8 - 5.3 2.5 - 3.8 - 7 3 - 4.5 - 8 3.8 - 5.5 - 8.8 4.3 - 6.5 - 9.5

Length 1200mm

Air Flow, l/s 71 142 212 283 354 425 496

Total Pressure, Pa 2 9 20 36 56 80 109

Static Pressure, Pa 1 4 9 17 26 38 52

NC (Noise Criteria) <10 <10 <10 17 24 30 36

Throw, m 0.3 - 0.5 - 2.3 1.3 - 2.3 - 4 2.3 - 3 - 6 2.8 - 4 - 8 3.3 - 5 - 10 4 - 6 - 11 4.5 - 7 - 12

Length 1500mm

Air Flow, l/s 76 156 236 316 396 477 557

Total Pressure, Pa 2 9 21 37 58 84 114

Static Pressure, Pa 1 3 7 13 21 31 42

NC (Noise Criteria) <10 <10 <10 16 24 30 36

Throw, m 0.3 - 0.5 - 1.8 1.3 - 1.8 - 4 2.3 - 3 - 6 2.8 - 4 - 8 3.3 - 5.3 - 10 4 - 6 - 11.5 4.5 - 7 - 12.5

76mm Slot Width

Length 600mm

Air Flow, l/s 47 101 156 210 264 319 373

Total Pressure, Pa 2 8 20 36 57 83 113

Static Pressure, Pa 1 6 14 26 41 59 81

NC (Noise Criteria) <10 <10 <10 <10 15 24 31

Throw, m 0.3 - 0.5 - 1.8 1.3 - 1.8 - 3.8 1.8 - 2.8 - 5.5 2.5 - 3.8 - 7.5 3 - 5 - 8.8 3.8 - 5.8 - 9.5 4.5 - 6.8 - 10.3

Length 1200mm

Air Flow, l/s 94 170 245 321 396 472 547

Total Pressure, Pa 3 11 23 39 60 85 114

Static Pressure, Pa 1 4 9 15 23 32 44

NC (Noise Criteria) <10 <10 <10 <10 13 21 27

Throw, m 0.3 - 1 - 2.5 1.3 - 2.3 - 4.3 2.3 - 3 - 6 2.8 - 4 - 8.3 3.3 - 5 - 10 4 - 6 - 11.5 4.5 - 7 - 12.5

Length 1500mm

Air Flow, l/s 113 193 274 354 434 514 595

Total Pressure, Pa 4 12 25 41 62 87 116

Static Pressure, Pa 1 3 7 12 18 25 33

NC (Noise Criteria) <10 <10 <10 <10 10 18 24

Throw, m 0.3 - 1 - 2.5 1.3 - 2.3 - 4.3 2.3 - 3 - 6 2.8 - 4 - 8 3.3 - 5 - 9.8 4 - 5.8 - 11.5 4.5 - 6.8 - 13

FL-25 with 250mm inlet

FL-30 with 250mm inlet

FlowBar with Air Diffusion Plenum Box - Jet Throw (JT)

• Pressures are given in Pascal (Pa)

• Isothermal throw values are given for terminal velocities of 0.8, 0.5 and 0.3m/sec respectively

• Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th, with a room absorption of 10dB, re 10-12 watts

• The tests were conducted with the FlowBar and plenums as a composite assembly

• Plenums not provided by Air Diffusion may demonstrate performance variations from the published data and therefore Air Diffusion would not be able to subsequently guarantee that performance matches our data

www.air-diffusion.co.uk 23

63mm Slot Width

Length 600mm

Air Flow, l/s 38 90 142 193 245 297 349

Total Pressure, Pa 1 8 19 36 57 84 116

Static Pressure, Pa 1 7 17 31 51 74 102

NC (Noise Criteria) <10 <10 <10 12 20 26 33

Throw, m 0.3 - 0.5 -1.5 1.3 - 1.8 - 3.8 1.8 - 2.8 - 5.8 2.8 - 4 - 7.3 3.3 - 5 - 8.3 4 - 6 - 9.3 4.5 - 7 - 10

Length 1200mm

Air Flow, l/s 71 158 245 333 420 507 595

Total Pressure, Pa 2 8 19 36 57 83 114

Static Pressure, Pa 1 5 13 23 37 54 74

NC (Noise Criteria) <10 <10 <10 18 26 32 38

Throw, m 0.3 - 0.5 - 2.3 1.5 - 2.3 - 4.5 2.5 - 3.3 - 7 3 - 5 - 9.5 4 - 6 - 11 5 - 7.3 - 12.3 5.5 - 8.5 - 13

Length 1500mm

Air Flow, l/s 76 175 274 373 472 571 670

Total Pressure, Pa 1 8 19 34 55 81 111

Static Pressure, Pa 1 4 10 19 30 44 60

NC (Noise Criteria) <10 <10 <10 18 26 32 38

Throw, m 0.3 - 0.5 - 1.8 1.5 - 2.3 - 4.5 2.5 - 3.3 - 7 3 - 5 - 9.5 4 - 6 - 11.5 5 - 7.3 - 12.8 5.8 - 8.5 - 13.8

76mm Slot Width

Length 600mm

Air Flow, l/s 47 106 165 224 283 342 401

Total Pressure, Pa 2 8 19 35 56 81 112

Static Pressure, Pa 1 7 16 29 47 68 94

NC (Noise Criteria) <10 <10 <10 <10 15 24 31

Throw, m 0.3 - 0.5 - 1.8 1.3 - 1.8 - 3.8 1.8 - 3 - 5.8 2.8 - 4 - 8 3.3 - 5.3 - 9.3 4 - 6 - 9.8 5 - 7.3 - 10.8

Length 1200mm

Air Flow, l/s 94 189 283 378 472 566 661

Total Pressure, Pa 2 9 21 37 58 83 113

Static Pressure, Pa 1 5 12 21 32 47 63

NC (Noise Criteria) <10 <10 <10 <10 17 25 32

Throw, m 0.3 - 1 - 2.5 1.5 - 2.5 - 5 2.5 - 3.8 - 7.3 3 - 5 - 9.5 4 - 6 - 11.5 5 - 7.3 - 12.8 5.5 - 8.3 - 13.8

Length 1500mm

Air Flow, l/s 113 217 321 425 529 632 736

Total Pressure, Pa 3 10 21 37 58 82 112

Static Pressure, Pa 1 4 10 17 26 37 50

NC (Noise Criteria) <10 <10 <10 <10 15 24 30

Throw, m 0.3 - 1 - 2.5 1.5 - 2.5 - 5 2.5 - 3.8 - 7.3 3.3 - 5 - 9.8 4 - 6 - 12 5 - 7 - 13.5 5.5 - 8.3 - 14.8

FL-25 with 300mm inlet

FL-30 with 300mm inlet

FlowBar with Air Diffusion Plenum Box - Jet Throw (JT)

• Pressures are given in Pascal (Pa)

• Isothermal throw values are given for terminal velocities of 0.8, 0.5 and 0.3m/sec respectively

• Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th, with a room absorption of 10dB, re 10-12 watts

• The tests were conducted with the FlowBar and plenums as a composite assembly

• Plenums not provided by Air Diffusion may demonstrate performance variations from the published data and therefore Air Diffusion would not be able to subsequently guarantee that performance matches our data

Air Diffusion FlowBar24

www.air-diffusion.co.uk 25

Air Diffusion FlowBar26

Standard Fixing Details

Jet Throw (JT) Details

Dimensions FL-10-HT (25mm)

W = 70mm

Dimensions FL-10-HT (25mm)

W = 78mm

Dimensions FL-10-JT (25mm)

W = 78mm

Dimensions FL-25-JT (63mm)

W = 154mm

Flowbar Border 66Installation Detail

Flowbar Border 66Installation Detail

Dimensions FL-30-JT (76mm)

W = 179mm

Dimensions FL-20-JT (51mm)

W = 129mm

Dimensions FL-25-HT (63.5mm)

W = 146mm

Dimensions FL-25-HT (63mm)

W = 154mm

Dimensions FL-30-HT (76mm)

W = 171mm

Dimensions FL-30-HT (76mm)

W = 179mm

Dimensions FL-15-HT (38mm)

W = 95mm

Dimensions FL-15-HT (38mm)

W = 103mm

Dimensions FL-20-HT (51mm)

W = 121mm

Dimensions FL-20-HT (51mm)

W = 129mm

Dimensions FL-15-JT (38mm)

W = 103mm

High Throw (HT) Details

Optional F6 Fixing (HT) Details

M gg

� 0

Dimensions FL-10-HT (25mm) W=78mm

Dimensions FL-15-HT (38mm) W= 103mm

Dimensions FL-20-HT (51 mm) W= 129mm

E E

0 0

+ � 0

1•1 ______ N_om_i _na _l _Le _n_g _th _____ _,

1•1Plenum Length

Dimensions FL-25-HT (63.5mm) W = 154mm

Dimensions FL-30-HT (76mm) W = 179mm

Flowbar Border 66 Install ation Detail

www.air-diffusion.co.uk 27

Dimensions & Details - High Throw (HT)

Type 66 FL-10/15/20/25/30

Type 22 FL-10/15/20/25/30

FL-10/15/20/25/30 - HT Border Type 66

F S W H

1 Slot (25mm) 35 25 70 43

1 Slot (38mm) 41 38 95 43

1 Slot (51mm) 48 51 121 43

1 Slot (63mm) 54 63 146 59

1 Slot (76mm) 60 76 171 59

FL-10/15/20/25/30 - HT Border Type 22

F S W H

1 Slot (25mm) 41 25 70 43

1 Slot (38mm) 48 38 95 43

1 Slot (51mm) 54 51 121 43

1 Slot (63mm) 54 63 146 61

1 Slot (76mm) 60 76 171 61

Type 11 FL-10/15/20/25/30

Type 55 FL-10/15/20/25/30

FL-10/15/20/25/30 - HT Border Type 11

F S W H

1 Slot (25mm) 22 25 70 43

1 Slot (38mm) 28.5 38 95 43

1 Slot (51mm) 35 51 121 43

1 Slot (63mm) 41 63 146 58.5

1 Slot (76mm) 47.5 76 171 58.5

FL-10/15/20/25/30 - HT Border Type 55

F S W H

1 Slot (25mm) 14 25 70 61.5

1 Slot (38mm) 21 38 95 61.5

1 Slot (51mm) 27 51 121 61.5

1 Slot (63mm) 31 63 146 61.5

1 Slot (76mm) 38 76 171 61.5

Air Diffusion FlowBar28

Dimensions & Details - Jet Throw (JT)

FL-10/15/20/25/30 - JT Border Type 66F S W H O

1 Slot (25mm) 35 25 70 43 76

1 Slot (38mm) 41 38 95 43 102

1 Slot (51mm) 48 51 121 43 127

1 Slot (63mm) 54 63 146 59 152

1 Slot (76mm) 60 76 171 59 178

FL-10/15/20/25/30 - JT Border Type 22F S W H

1 Slot (25mm) 41 25 70 43

1 Slot (38mm) 48 38 95 43

1 Slot (51mm) 54 51 121 43

1 Slot (63mm) 54 63 146 61

1 Slot (76mm) 60 76 171 61

Border Type 11, 66 Slot Run Border Type 11, 22 & 55 Slot Run

H

Type 66 FL-10/15/20/25/30 Type 22 FL-10/15/20/25/30

Dimensions & Details - Slot Runs

www.air-diffusion.co.uk 29

Dimension & Details - End Border Configurations

Border Type 11 & 66

Optional Blanking Plates - FBBO Blank-off

Optional Return Light Shield Painted Black

FBBO - 10 (25mm Slot) FBBO - 15 (38mm Slot) FBBO - 20 (51mm Slot) FBBO - 25 (63mm Slot) FBBO - 30 (76mm Slot)

FBR - 10 (25mm Slot) FBR - 15 (38mm Slot) FBR - 20 (51mm Slot) FBR - 25 (63mm Slot) FBR - 30 (76mm Slot)

Border Type 11, 22 & 55

Air Diffusion FlowBar30

Standard Installation Details - High Throw (HT) & Jet Throw (JT)

UHC Upper Hanger ClipThe upper hanger clip is used to suspend the FlowBar assembly from the structure. The clip is designed to utilize standard ceiling hanger wire. UHC is for 1 slot only and FL-10, 15 and 20.

H2 Hard Ceiling ClipThe H2 hard ceiling clip is used to mount the FlowBar assembly with border type 55 when 25mm thick plasterboard ceiling is required.

H3 Hard Ceiling ClipThe H3 hard ceiling clip can be used to mount the FlowBar assembly with border type 22 when a standard plasterboard ceiling is required.

Spline Support ClipThe SS1 spline clip is also used to adjoin multiple sections of FlowBar when continuous lengths are desired.

www.air-diffusion.co.uk 31

Standard Types 22 Plaster Frame Installation

Standard Installation for Suspended Ceiling Systems

Standard Installation for Solid (Plasterboard) Type Ceiling Systems

Standard Plenum Box Installation System (HT Only)

Air Diffusion FlowBar32

Diffuser Installation with plenum

FlowBar Model

Ceiling Opening dimensions for border type 66

1-Slot

FL - 10 76

FL - 15 102

FL - 20 127

FL - 25 152

FL - 30 178

Ceiling

Di�user Flange

Mounting Bracket

Attach Hanger Wire/Rods to Plenum Support Brackets Ceiling

Hemmed Edge of Plenum

Mounting bracket catches in HemmedEdge of Plenum

Di�user �ange overlaps ceiling opening

Opening

Plenum

Concealed Fastening Plenum Installation Diffuser Installation with PlenumAttach Hanger Wire/Rods to Plenum Support Brackets Ceiling

Hemmed Edge of Plenum

Mounting bracket catches in HemmedEdge of Plenum

Di�user �ange overlaps ceiling opening

Opening

Plenum

Concealed Fastening Plenum Installation Diffuser Installation with Plenum

Diffuser Installation without plenum

Concealed Fastening Plenum Installation

Standard Installation Details - Jet Throw (JT) only

Bracket Diffuser Assembly

www.air-diffusion.co.uk 33

The model described in the example above would be: 66 - HT -1 - 15 - E1 - F6 - 3 - 4

Ordering Information - FlowBar Slot Diffuser

Example

Frame Diffuser Model

No. of Slots

Slot Width

End Flanges

Fix Optional Fix

Frame Finish

Blade Finish

66

66 Surface Mounting

22 Plaster frame

55 Plaster frame (deep)

11 Flangeless

HT

JT

1

1

15

10

15

20

25

30

E1

E0 Open End

E1 End border one end

E2 End border two ends

EP1 End plate one end

EP2 End Plate two ends

ME Mitred End

F6 SP

F6 ‘U’ Bracket fixing

F9 Toggle Fix

SP Special Fixing

H2 Hard Ceiling clip (25mm)

H3 Hard Ceiling clip (12.5mm)

UHC Upper hanger clip (Border Type 66)

3

3 Standard White matt. Type 66 border

4 Standard Black Type 22, 55 & 11 Border

6 Other colours available to special order

4

4 Standard Black

6 Other colours available to special order

FlowBar Installation ManualFor the comprehensive installation, operation and maintenance (IOM) manual, please visit our website: www.air-diffusion.co.uk where the manual can be downloaded as a PDF file.

Air Diffusion FlowBar34

Specifications

Material/FinishStandard is a minimum of 0.7mm thick galvanised steel.

ConstructionPlenum boxes are generally fabricated in 3 sections, which are either mechanically joined or spot welded to form an airtight seal. As standard, spigots are side entry and located centrally. All boxes are supplied with stepped edges. F9 (HT) or hemmed edges F6 (JT) as standard.

Installation OptionsFixing lugs can be factory fitted if preferred or special fixing methods (by others) may be used. For plenum boxes having flush ends separate hanging brackets/fixing lugs need to be fitted to allow independent support of diffuser and plenum box.

Accessories ▸ Joggled style plenum boxes or

pan adapters

▸ Spigot dampers include manual quadrant or cord operated

▸ Options for: Unlined; 6mm or 12mm thick Class ‘O’ internal lining

▸ Equalising grids (50% free area perforated mesh)

▸ Fixing lugs or special fixings (by others)

Plenum BoxesSupplied with 6mm lining as standard with side entry spigot. Plenum boxes can be supplied without lining or with 12mm lining as an option. Apply to sales office for price.

High Throw (HT) Plenum

Jet Throw (JT) Plenum

www.air-diffusion.co.uk 35

Pressure Drops & Sound RatingThe pressure drop given is for supply diffuser with damper fully open. When the diffuser is installed with plenum box, the pressure loss of the box has to be added to the diffuser.

Plenum Box Spigot Volumes (l/s)

Spigot Velocity m/s1.5 2.0 2.5 3.0 3.5 4.0

Pressure Drop Pa* 2 4 6 8 12 16Sound Power Level NR* - - 25 30 35 40

*The figures given are approximate - dependent upon spigot entry conditions.

Spigot Velocity m/sDiameter (mm) 1.5 2.0 2.5 3.0 3.5 4.0

100 10 15 19 22 26 30125 18 24 30 35 41 47150 25 34 42 51 60 68175 35 46 58 70 82 94200 45 60 75 91 109 121225 58 77 96 117 137 151250 71 95 120 142 170 191275 86 115 145 172 205 230300 103 139 172 208 240 275325 120 160 200 240 280 320350 140 188 235 280 328 375400 185 245 310 370 430 495

Air Diffusion FlowBar36

Type PBL-1

Angle Bracket fixing available if required.

Optional rectangular or flat oval spigots* available (minimum height 100mm).

Type PBL-1 for F6 fixing

Plenum Box Dimensions

Order DetailsC

H L W D LH RH X- - - - - - -

Order DetailsC

H L W D LH RH X- - - - - - -

www.air-diffusion.co.uk 37

AccessoriesManual Quadrant Control Damper

Model Ref Nominal Duct Diameter*

Open Blade Protrusion (mm)

DW144 Casing Leakage Class Weight (Kg)

CB 100 – C 0.56

CB 125 – C 0.71

CB 150 – C 0.85

CB 160 C 0.91

CB 200 C 1.17

CB 250 20.5 C 1.53

CB 300 45.5 C 1.92

CB 315 53 C 2.05

CB 350 70.5 C 2.35

CB 355 73 C 2.40

* NDD: Nominal duct diameter. Actual sizes are in accordance with BS EN 1506.

200

5050

75

50

50

60

NDD

Air Diffusion FlowBar38

Type PBL-1

Plenum Box Detail Lever Operated Damper Option

6565

Accessories

www.air-diffusion.co.uk 39

Ordering Information - Plenum Boxes

Example

Dimensions PBL-1, PBL-2, Example

Model

PBL-1

y PBL-1 Linear Plenum Box with either a circular or square side entry spigot

y PBL-2 Linear Plenum Box having either a circular or square top entry spigot

y PBL-3 Linear Plenum Box with joggle section having either a circular or square side entry spigot

y PBL-4 Linear Plenum Box with joggle section having either a circular or square top entry spigot

Internal Lining

U

y U Standard Unlined Plenum Box

y L 6mm Class ‘O’ Internal Lining

Spigot Damper

N

y N Plain spigot no damper

y Q Quadrant damper

y Z Lever operated opposed blade damper

y C Cord operated damper fitted to spigot

Options

0

y 0 No options

y 2 Equalising grid

y 3 Fixing lugs fitted to side of plenum

y 4 Profile ends on each end of plenum

y 5 Hemmed Edge for concealed strap fixing

y 6 Plenum retaining clips (HT Only)

Dimensions

See example below

Neck Size

L x W

1000 x 95

Plenum Height

H

350

Circular Spigot Diameter

Diameter

250

OR (Sq./Rect. Spigot Width x Height)

0

Centre Line of Spigot

G

0

C x E

Stourbridge Rd, Bridgnorth,WV15 5BB, Shropshire, UK

Tel: +44 (0)1746 761921 Email: [email protected] Website: air-diffusion.co.uk

The statements made in this brochure or by our representatives in consequence of any enquires arising out of this document are given for information purposes only. They are not intended to have any legal effect and the company is not to be regarded as bound thereby. The company will only accept obligations, which are expressly negotiated for and agreed and incorporated into a written agreement made with its customers.

Due to a policy of continuous product development the specification and details contained herein are subject to alteration without prior notice.

actionair | air diffusion | airfiltrera | airolution | naco

LNNN00394 (1.4 - 05.19)