G:\Library/CCEC Product Data/CCEC PDS RotaSec MD Site Prep UK 1.1 - 1 - 04.2006 RotaSec MD120 IMPORTANT Any horizontal pipe or conduit runs below the RotaSec must be at least 140mm below FFL. It is the customers responsibility to ensure the structural integrity and strength of the installation location. Concrete Base to BS 5328:1997 specification. Base to be flat and level to +/- 5mm over footprint area. Dimensions to be > 1800 x 3300 x 150 deep min. Floor Anchors to be drilled during installation, 12mm dia x 100mm deep. Stator bar ‘dead area’ barrier Straight bar rotor Bottom entry conduit location Fixing locations Site Preparation RotaSec MD120 (Shown with straight bar rotor)

Upload: others

Post on 17-Apr-2020

14 views

Category:

Documents


0 download

TRANSCRIPT

G:\Library/CCEC Product Data/CCEC PDS RotaSec MD Site Prep UK 1.1 - 1 - 04.2006

RotaSec MD120

IMPORTANT

• Any horizontal pipe or conduit runs below the RotaSec must be at least 140mm below FFL.

• It is the customers responsibility to ensure the structural integrity and strength of the installation location.

Concrete Base to BS 5328:1997 specification. Base to be flat and level to +/- 5mm over footprint area. Dimensions to be > 1800 x 3300 x 150 deep min.

Floor Anchors to be drilled during installation, 12mm dia x 100mm deep.

Stator bar ‘dead area’ barrier

Straight bar rotor

Bottom entry conduit location

Fixing locations

Site Preparation RotaSec MD120 (Shown with straight bar rotor)

G:\Library/CCEC Product Data/CCEC PDS RotaSec MD Site Prep UK 1.1 - 2 - 04.2006

Concrete Base to BS 5328:1997 specification. Base to be flat and level to +/- 5mm over footprint area. Dimensions to be > 1800 x 3300 x 150 deep min.

Floor Anchors to be drilled during installation, 12mm dia x 100mm deep.

Stator bar ‘dead area’ barrier

Straight bar rotor

Site Preparation RotaSec MD90 (Shown with straight bar rotor)

IMPORTANT

• Any horizontal pipe or conduit runs below the RotaSec must be at least 140mm below FFL.

• It is the customers responsibility to ensure the structural integrity and strength of the installation location.

G:\Library/CCEC Product Data/CCEC PDS RotaSec MD Site Prep UK 1.1 - 3 - 04.2006

IMPORTANT

• Any horizontal pipe or conduit runs below the RotaSec must be at least 140mm below FFL.

• It is the customers responsibility to ensure the structural integrity and strength of the installation location.

Concrete Base to BS 5328:1997 specification. Base to be flat and level to +/- 5mm over footprint area. Dimensions to be > 1800 x 3300 x 150 deep min.

Floor Anchors to be drilled during installation, 12mm dia x 100mm deep.

Stator bar ‘dead area’ barrier

Straight bar rotor

Site Preparation RotaSec MD90 (Shown with straight bar rotor)

Bottom entry conduit location

Fixing locations

G:\Library/CCEC Product Data/CCEC PDS RotaSec MD Site Prep UK 1.1 - 4 - 04.2006

IMPORTANT

• Any horizontal pipe or conduit runs below the RotaSec must be at least 140mm below FFL.

• It is the customers responsibility to ensure the structural integrity and strength of the installation location.

Bottom entry conduit location

Stator bar ‘dead area’ barrier

Fixing locations

Straight bar rotor

Floor Anchors to be drilled during installation, 12mm dia x 100mm deep.

Concrete Base to BS 5328:1997 specification. Base to be flat and level to +/- 5mm over footprint area. Dimensions to be > 1800 x 3300 x 150 deep min.

Site Preparation RotaSec MD120F (Shown with straight bar rotor)

G:\Library/CCEC Product Data/CCEC PDS RotaSec MD Site Prep UK 1.1 - 5 - 04.2006

IMPORTANT

• Any horizontal pipe or conduit runs below the RotaSec must be at least 140mm below FFL.

• It is the customers responsibility to ensure the structural integrity and strength of the installation location.

Concrete Base to BS 5328:1997 specification. Base to be flat and level to +/- 5mm over footprint area. Dimensions to be > 1800 x 3300 x 150 deep min.

Floor Anchors to be drilled during installation, 12mm dia x 100mm deep.

Straight bar rotor

Bottom entry conduit location

Fixing locations

Site Preparation RotaSec MD120FI (Shown with straight bar rotor)

G:\Library/CCEC Product Data/CCEC PDS RotaSec MD Site Prep UK 1.1 - 6 - 04.2006

IMPORTANT

• Any horizontal pipe or conduit runs below the RotaSec must be at least 140mm below FFL.

• It is the customers responsibility to ensure the structural integrity and strength of the installation location.

Site Preparation RotaSec MD90FI (Shown with straight bar rotor)

Floor Anchors to be drilled during installation, 12mm dia x 100mm deep.

Concrete Base to BS 5328:1997 specification. Base to be flat and level to +/- 5mm over footprint area. Dimensions to be > 1800 x 3300 x 150 deep min.

Stator bar ‘dead area’ barrier

Bottom entry conduit location

Fixing locations

Straight bar rotor

G:\Library/CCEC Product Data/CCEC PDS RotaSec MD Site Prep UK 1.1 - 7 - 04.2006

Site Preparation RotaSec MD120R (Shown with straight bar rotor)

IMPORTANT

• Any horizontal pipe or conduit runs below the RotaSec must be at least 140mm below FFL.

• It is the customers responsibility to ensure the structural integrity and strength of the installation location.

Bottom entry conduit location

Stator bar ‘dead area’ barrier

Fixing locations

Straight bar rotor

Floor Anchors to be drilled during installation, 12mm dia x 100mm deep.

GRP canopy

Walkway down lights

Rain water down pipe

Concrete Base to BS 5328:1997 specification. Base to be flat and level to +/- 5mm over footprint area. Dimensions to be > 1800 x 3300 x 150 deep min.

G:\Library/CCEC Product Data/CCEC PDS RotaSec MD Site Prep UK 1.1 - 8 - 04.2006

IMPORTANT

• Any horizontal pipe or conduit runs below the RotaSec must be at least 140mm below FFL.

• It is the customers responsibility to ensure the structural integrity and strength of the installation location.

Site Preparation RotaSec MD120RI (Shown with straight bar rotor)

Concrete Base to BS 5328:1997 specification. Base to be flat and level to +/- 5mm over footprint area. Dimensions to be > 1800 x 3300 x 150 deep min.

Floor Anchors to be drilled during installation, 12mm dia x 100mm deep.

Rain water down pipe

GRP canopy

Stator bar ‘dead area’ barrier

Bottom entry conduit location

Fixing locations

Straight bar rotor

Walkway down lights

G:\Library/CCEC Product Data/CCEC PDS RotaSec MD Site Prep UK 1.1 - 9 - 04.2006

Site Preparation RotaSec MD90R (Shown with straight bar rotor)

IMPORTANT

• Any horizontal pipe or conduit runs below the RotaSec must be at least 140mm below FFL.

• It is the customers responsibility to ensure the structural integrity and strength of the installation location.

Bottom entry conduit location

Fixing locations

Straight bar rotor

Floor Anchors to be drilled during installation, 12mm dia x 100mm deep.

Concrete Base to BS 5328:1997 specification. Base to be flat and level to +/- 5mm over footprint area. Dimensions to be > 1800 x 3300 x 150 deep min.

GRP canopy

Walkway down lights

Rain water down pipe

Stator bar ‘dead area’ barrier

G:\Library/CCEC Product Data/CCEC PDS RotaSec MD Site Prep UK 1.1 - 10 - 04.2006

Site Preparation RotaSec MD90RI (Shown with straight bar rotor)

IMPORTANT

• Any horizontal pipe or conduit runs below the RotaSec must be at least 140mm below FFL.

• It is the customers responsibility to ensure the structural integrity and strength of the installation location.

Concrete Base to BS 5328:1997 specification. Base to be flat and level to +/- 5mm over footprint area. Dimensions to be > 1800 x 3300 x 150 deep min.

Floor Anchors to be drilled during installation, 12mm dia x 100mm deep.

Fixing locations

Bottom entry conduit location

Walkway down lights

Straight bar rotor Rain water down pipe

GRP canopy

G:\Library/CCEC Product Data/CCEC PDS RotaSec MD Site Prep UK 1.1 - 11 - 04.2006

Site Preparation RotaSec MD120SI (Shown with straight bar rotor)

IMPORTANT

• Any horizontal pipe or conduit runs below the RotaSec must be at least 140mm below FFL.

• It is the customers responsibility to ensure the structural integrity and strength of the installation location.

Floor Anchors to be drilled during installation, 12mm dia x 100mm deep.

Stator bar ‘dead area’ barrier

Concrete Base to BS 5328:1997 specification. Base to be flat and level to +/- 5mm over footprint area. Dimensions to be > 1800 x 3300 x 150 deep min.

Fixing locations

GRP canopy

Bottom entry conduit location

Rain water down pipe

Straight bar rotor

Walkway down lights

GRP side cabinets

G:\Library/CCEC Product Data/CCEC PDS RotaSec MD Site Prep UK 1.1 - 12 - 04.2006

Site Preparation RotaSec MD90S (Shown with straight bar rotor)

IMPORTANT

• Any horizontal pipe or conduit runs below the RotaSec must be at least 140mm below FFL.

• It is the customers responsibility to ensure the structural integrity and strength of the installation location.

Bottom entry conduit location

Stator bar ‘dead area’ barrier

Fixing locations

Straight bar rotor

Floor Anchors to be drilled during installation, 12mm dia x 100mm deep.

Concrete Base to BS 5328:1997 specification. Base to be flat and level to +/- 5mm over footprint area. Dimensions to be > 1800 x 3300 x 150 deep min.

GRP canopy

Walkway down lights

Rain water down pipe

GRP side cabinets

G:\Library/CCEC Product Data/CCEC PDS RotaSec MD Site Prep UK 1.1 - 13 - 04.2006

Site Preparation RotaSec MD90SI (Shown with straight bar rotor)

IMPORTANT

• Any horizontal pipe or conduit runs below the RotaSec must be at least 140mm below FFL.

• It is the customers responsibility to ensure the structural integrity and strength of the installation location.

Concrete Base to BS 5328:1997 specification. Base to be flat and level to +/- 5mm over footprint area. Dimensions to be > 1800 x 3300 x 150 deep min.

Bottom entry conduit location

Fixing locations

Stator bar ‘dead area’ barrier

Straight bar rotor

GRP side cabinets GRP canopy

G:\Library/CCEC Product Data/CCEC PDS RotaSec MD Site Prep UK 1.1 - 14 - 04.2006

A COMPANY WITHIN THE GUNNEBO

HEAD OFFICE SWEDEN Gunnebo AB, Box 5181, SE-402 26 Goteborg, SWEDEN. Tel +46-31 83 68 00, Fax +46-31 83 68 10

www.gunnebo.com

Note: In pursuit of its policy of continuous refinement and improvement, Gunnebo Entrance Control Ltd reserves the right to modify design and details.