cdv fan-coil units high-performance, · pdf filecdv fan-coil units high-performance, vertical....

16
catalog CDV Fan-Coil Units High-Performance, Vertical

Upload: buithu

Post on 25-Mar-2018

246 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: CDV Fan-Coil Units High-Performance, · PDF fileCDV Fan-Coil Units High-Performance, Vertical. 2 ENVIRO ... The ENVIRO-TEC® CDV Series B vertical fan coil unit ... , three winding,

catalog

CDV Fan-Coil Units High-Performance, Vertical

Page 2: CDV Fan-Coil Units High-Performance, · PDF fileCDV Fan-Coil Units High-Performance, Vertical. 2 ENVIRO ... The ENVIRO-TEC® CDV Series B vertical fan coil unit ... , three winding,

2 ENVIRO-TEC

Catalog: ET115.26-EG8 (415) CDV Fan-Coil Units High-Performance, Vertical

Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Construction Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Standard and Optional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Coils, Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Fan Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Fan Performance Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Motor, Fan and Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

TABLE OF CONTENTS

NOTES:• Aweb-basedComputerSelectionProgram,“Web-Select”,isavailabletofacilitatetheselectionprocess. Contactyourrepresentativetoobtainaccesstothispowerfulandtime-savingprogram.• Alldatahereinissubjecttochangewithoutnotice.Somedrawingsarenotshowninthiscatalog.• Drawingsnotforinstallationpurposes;refertoIOMmanual.• ETLReportNumber524615.• MEANumberMEA54-98-EappliestoallunitswithanycombinationofchilledwaterorR-22directexpan-sioncoilsandeitherhotwatercoils,steamcoils,orelectricheat.

Page 3: CDV Fan-Coil Units High-Performance, · PDF fileCDV Fan-Coil Units High-Performance, Vertical. 2 ENVIRO ... The ENVIRO-TEC® CDV Series B vertical fan coil unit ... , three winding,

ENVIRO-TEC 3

CDV Fan-Coil Units High-Performance, Vertical Catalog: ET115.26-EG8 (415)

FEATURES AND BENEFITS

HIGH PERFORMANCE

The ENVIRO-TEC® CDV Series B vertical fan coil unit is designed to maximize flexibility of selection and installation .

The units are also designed to exceed the stringentquality standards of the institutional market, whileremainingcostcompetitiveinthelightcommercialseg-ment of the market .

ENVIRO-TEC®verticalfancoilunitssetthenewstan-dardsforquality,flexibility,andcompetitivepricing.

DESIGN FLEXIBILITY TheextensivevarietyofstandardoptionsavailableonCDVunitsarewhereyoufindtheversatilitytofitanyHVACsystemdesigner’sneeds.

Options include:mixingboxwithout linkage, rearorbottomreturn,bottomreturnplenum,singlewallstain-less steel drain pans, foil faced or elastomeric closed cellfoaminsulation,andelectricheatwithsinglepowerconnection.AllelectricheatunitsarelistedwithETLasanassemblyandcarrythecETLlabel.

AllunitscomplywiththelatesteditionofAHRIStandard440 for testingand rating fancoilunits,arecertified,anddisplaytheAHRIsymbol.Sizes16and20exceedthemaximumairflowrateinAHRI440andarethereforenot certified .

High efficiency motors, fan relays, disconnects andfusingmeaneasiercoordinationbetweenmechanicaland electrical trades .

Coiloptionsallowforthreeorfourrowcoolingcoils.One or two row hot water coils are placed in thereheat position .

CONVENIENT INSTALLATION

AllCDVSeries fancoilunitsareshippedcompletelyassembled, reducing field installation timeand labor.Allunitsare thoroughly inspectedand testedprior to shipment, eliminating potential problems at startup.Motorwiringisbroughttoajunctionboxontheoutsideoftheunitcasing,reducingelectricalhook-uptime.

AllCDVSeriesfancoilunitshaveafrontaccesselec-tricalenclosure,allowingeasyaccesstoallelectricalcomponents,terminalblocksandwiring.

Available factory installed control packages cangreatlyreducefieldlaborandsetuptime.Consistingof control transformer and all needed relays, these packages integrate seamlessly with either factoryprovided thermostats or field installed thermostats and controllers .

QUALITY PRODUCT

CDVSeriesfancoilunitsarebuiltfromgalvanizedsteel.Thismetal surpasses theASTM125hour salt spraytest for corrosion and rust .

Standardinsulationis1/2inchthick,fiberglassinsula-tion which is glued and pin spotted for maximum positiveadhesion.InsulationcomplieswithUL181andNFPA90A.

Allunits,withorwithoutelectricheat,arecETLlistedandlabeled.AllwiringisincompliancewithNEC,assur-ingsafetyandqualityfortheowner.

CDVSeriesfancoilunitshavearemovablefanassem-bly.Theentirefanassemblycanberemovedfromtheunitandservicedeasilyonaworkbench.

Page 4: CDV Fan-Coil Units High-Performance, · PDF fileCDV Fan-Coil Units High-Performance, Vertical. 2 ENVIRO ... The ENVIRO-TEC® CDV Series B vertical fan coil unit ... , three winding,

4 ENVIRO-TEC

Catalog: ET115.26-EG8 (415) CDV Fan-Coil Units High-Performance, Vertical

CONSTRUCTION FEATURES

MODEL CDVManystandardfeaturesontheCDVfancoilunitareexpensiveadd-onsforothermanufacturers.

Galvanizedsteelcasingwith-standing125hoursaltsprayspecificationsperASTMB-117

Integraldischargecollar for simple field installation

Statically and dynamically balanceddirectdrivefanassembly(seepage5)

Galvanizedforwardlycurvedfanwheelingalvanizedhousing

Permanentlylubricatedthreespeed(H.P.)fanmotorsavailablein115,208-230or277volt,singlephase60Hz

ODP,PSCmotorswithinherent thermal overload protection

Productlabelingincludingtagging,airflowandelectricalinformation

Singlepointpowerconnectionfor simpleinstallationandwiring

Allhotwater,chilledwater,andDXcoilsareAHRI410listedandbear

theAHRIlabel(seepage7)

Galvanizedsteeldrainpanwith3/4" MPT connection

Drain connection at front of unit — side access not required

1"glassfiberthrowawayfilter

Allaccessfromthefrontpanels—unitscanbemounted in a pipe chase (ductedunitsrequireoption-alreturnplenumforaccess)

Bottom (shown)or front

return air connection

1/2"thick,fiberglassinsulation(stan-dard)complyingwithUL181and

NFPA90A(optionalfoilfacedinsula-tionshown)Elastomericclosedcell

foamisalsoavailable.

Insulation mechanically fastenedforaddedstrength

Pipingandsupplyductconnectionsarefromtopofunit,eliminatingtheneed

forsideorbackaccess

Rightorlefthandconfigurations forcoil(sameendonly)and

electrical connections

Removableaccesspanelssizedforeasyhandlingandmaintenance

Small footprint

Allunitconfigurations listedwithETLforsafetycompliance

OPTIONAL CONSTRUCTION FEATURES• ScrimreinforcedfoilfacedinsulationtomeetASTMC665andC1136isavailableformold,mildew,andhumidityresistance—alledgesaresealed to prevent erosion

• Elastomericclosedcellfoaminsula-tiontomeetASTMG-21forfungiresistanceandUL181formoldgrowth/humidityandairerosion.

• Integraldischargeairplenumwithadjustabledoubledeflectionsupplygrille

• Stainlesssteelcoilcasings• Autoairventsonhydroniccoils• Quickopenaccesspanels• Stainlesssteeldrainpanwith3/4"

MPT connection• Drainpanfloatswitch• ElectricresistanceheatsectionmeetsNECcoderequirements(seepage9).AllunitsETLlistedwithintegralelectricheatasanassembly.

• 2"filterrack

• Integralinductionairmixingboxsec-tion for precise ventilation air blending

• Threepositionmotorspeedswitch• Lowvoltagecontrols• Toggletypesinglephasedisconnectswitchforservice

• Unitstart/stoprelayforflexibilityof control

• SCRelectronicfanspeedcontrollerforfiniteairflowadjustment

Page 5: CDV Fan-Coil Units High-Performance, · PDF fileCDV Fan-Coil Units High-Performance, Vertical. 2 ENVIRO ... The ENVIRO-TEC® CDV Series B vertical fan coil unit ... , three winding,

ENVIRO-TEC 5

CDV Fan-Coil Units High-Performance, Vertical Catalog: ET115.26-EG8 (415)

CONSTRUCTION FEATURES

QUIET, ENERGY EFFICIENT FAN ASSEMBLY

AkeytocomfortistheENVIRO-TEC®extraquietfanassembly.Eachassemblyisspecificallydesignedandbuiltforquiet,energyefficientairdelivery.

WhatmakesENVIRO-TEC®fanassembliesefficientistheuseofthreespeed,threewinding,permanentsplitcapacitor fan motors . The three speed motors are capableofdelivering threeseparatehorsepowerout-puts.Forexample,anominal1/2HPmotoratmediumandlowspeedswilldeliver1/3HPand1/4HPrespec-tively. This is the most efficient means of handlingreduced fan capacities .

Aquickselect terminalstrip isprovided forswitchingbetween motor speeds. An optional three positionrotaryswitchisalsoavailableforsimplifiedmotorspeedselection. Additional air balance of the fan can beachieved through field adjustment of an electronic(SCR)fanspeedcontroller.Theelectronic(SCR)fan

speedcontroller isofferedbyENVIRO-TECandhasbeenspecificallydesignedforcompatibilitywiththefanmotors.EachSCRalsoincludesaminimumvoltagelimiter for stall protection .

Thecombinationofathreespeedfanmotor,andelec-tronic SCR provides the most flexible and energy efficientmeansofbalancingfancapacitieswithvaryingfield conditions. This combination is preferred oversinglespeedmotorandSCRcombinationswhichcauseexcessivepowerconsumptionandhighmotorwindingtemperatures .

Each fan housing is specifically designed for com- patibility with the fan motors and internal pressure losses of the CDV cabinets. This design providesproper motor loading and maximizes fan performance .

Motorplugforquick, convenient change-out

Vibrationdampeningmount-ingbracketswithrubber

grommetedfeet

Highefficiencypermanentlylubri-catedPSCthreespeed(HP)fanmotorwiththermaloverloadpro-tection—mediumandlowmotorspeeds are used most often, allowingsubstantialpowersavings Dynamically balanced,

galvanizedfanwheel

Galvanizedhousing

Page 6: CDV Fan-Coil Units High-Performance, · PDF fileCDV Fan-Coil Units High-Performance, Vertical. 2 ENVIRO ... The ENVIRO-TEC® CDV Series B vertical fan coil unit ... , three winding,

6 ENVIRO-TEC

Catalog: ET115.26-EG8 (415) CDV Fan-Coil Units High-Performance, Vertical

STANDARD AND OPTIONAL FEATURES

STANDARD FEATURESConstruction• AHRI440certifiedandlabeled• Heavygaugegalvanizedsteelconstruction• 1/2"thickfiberglassinsulation• 1"ductdischargecollar• Removableaccesspanelssizedforeasyhandling

Coils• AHRI410certifiedandlabeled• Cooling-3or4rowchilledwaterorDX,heat pumpcompatible

• Heating-1or2rowhotwater–reheatposition• 6totalrowsofcoolingandheatingcoilsmaximum• 1/2"O.D.seamlesscoppertubes• 0.016"tubewallthickness• Leftorrighthandconnections• 300PSIGworkingpressureat200°F• Removableforservice• Manualairvents

Filter Rack and Filters• 1"flatfilterrack• 1"nominalthrowawayfilters

Drain Pans• Singlewall,galvanizedsteel,externallyinsulated–fireretardantandantimicrobial

• Positivelyslopedtodrainconnection• 3/4"MPTgalvanizeddrainconnection

Fan Assemblies• Forwardcurved,DWDIcentrifugaltype• 115volt,singlephase,threetapPSCmotors• Quickdisconnectmotorconnections• Removablefan(s)/motor(s)forservice

Electrical• cETLlistedforsafetycompliance• Electricaljunctionboxforfieldwiringterminations• Terminalblockforfieldconnections

Electric Heat• cETLlistedasanassemblyforsafetycompliance• Integralelectricheatassemblywithremovable

elements for easy service• Automaticresetprimaryandback-up

secondary thermal limits• Singlepointpowerconnection• Hingedelectricalenclosure

OPTIONAL FEATURESConstruction• Scrimreinforcedfoilfacedfiberglassinsulation• Elastomericclosedcellfoaminsulation• Doubledeflectiondischargegrille• Quarterturnquickopenaccesspanelfasteners• Returnandsupplyplenums

Coils• Automaticairvents• Stainlesssteelcoilcasings• 0.025"tubewallthickness

Filter Rack and Filters• 2"flatfilterrack• Sparethrowawayfilters

Inlet Damper Section• Factoryassembledandinstalled• Heavygaugegalvanizedsteelformedblade

dampers• Low-leakdamperswithextrudedvinylbladesealsandflexiblemetaljambseals

• Parallelbladeoperation

Drain Pans• Singlewall,stainlesssteelwithexternal

insulation

Fan Assemblies• 208-230&277volt,singlephase,threetapPSC

motors

Electrical• Frontaccesselectricalenclosure• SCRfanspeedcontroller• Fanrelaypackages• Toggledisconnectswitch• Condensateoverflowswitch(drainpan)• Mainfusing• Unitandremotemountedthreespeedfanswitches

Electric Heat• Doorinterlockingdisconnectswitches• Mainfusing• Manualresetsecondarythermallimits

Thermostats• Remotemountedanalog,digitaldisplayor programmable

• 2and4pipecontrolsequences• Automaticandmanualchangeover• Integralthreespeedfanswitches

Page 7: CDV Fan-Coil Units High-Performance, · PDF fileCDV Fan-Coil Units High-Performance, Vertical. 2 ENVIRO ... The ENVIRO-TEC® CDV Series B vertical fan coil unit ... , three winding,

ENVIRO-TEC 7

CDV Fan-Coil Units High-Performance, Vertical Catalog: ET115.26-EG8 (415)

COILS, PHYSICAL DATA

COILSENVIRO-TEC®offershotwater,chilledwater,anddirectexpansion(DX)coilsforspecificapplicationwithallCDVdirectdrivefancoils.AHRI410certifiedandlabeled,andstricton-siteinspectionbefore,during,andafterinstal-lationguaranteesthehighestqualityandperformanceavailable.

STANDARD FEATURES• Designed,manufacturedandtestedbyENVIRO-TEC®

• AHRI410certifiedandlabeled• 1/2"O.D.seamlesscoppertubes• Highefficiencyaluminumfinsurfaceforoptimizingheattrans-

fer, pressure drop and carryover .• Mechanically expanded copper tubes leak tested to a minimum450PSIGairpressureunderwater

• Manualairventplugonallwatercoils• CopperODMsweatconnections• 300PSIGworkingpressureat200°F• Evaporatorcoilsarefactorysealedandchargedwithminimumof5PSIGnitrogenorrefrigerateddryair

• Refrigerant coils are providedwith a fixed orificemeteringdevice(distributor-eliminator)

• 0.016"tubewallthickness

OPTIONAL FEATURES• Automaticairventsonwatercoils• Stainlesssteelcoilcasings• 0.025"tubewallthickness• DXcoilsareheatpumpcompatible

NOTES:1. Standardfiltersare1"throwaway;optionalfiltersare2"throwaway.2 . Coil face areas are measured in square feet [square meters] .3. Filtersizesaremeasuredininches[millimeters].

COIL FACE AREA AND FILTER DATA

UNIT SIZE

AUXILIARY HEATING COIL

COOLING COIL NOMINAL FILTER SIZES

FACE AREA FACE AREA WITH FRONT RETURN WITH BOTTOM RETURN

04 0 .9 [0 .08] 1 .3 [0 .12] 16x22x1[406x559x25] (2)14x10.5x1[356x267x25]

06 0 .9 [0 .08] 1 .6 [0 .15] 16x22x1[406x559x25] (2)14x10.5x1[356x267x25]

08 1 .2 [0 .11] 1 .8 [0 .17] 16x22x1[406x559x25] (2)14x10.5x1[356x267x25]

10 2 .0 [0 .19] 2 .6 [0 .24] 16x29x1[406x737x25] (2)14x17x1[356x432x25]

12 2 .0 [0 .19] 2 .9 [0 .27] 16x29x1[406x737x25] (2)14x17x1[356x432x25]

16 3 .3 [0 .31] 4 .0 [0 .37] (2)16x23x1[406x584x25] (2)17x22.5x1[432x572x25]

20 3 .3 [0 .31] 5 .1 [0 .47] (2)16x23x1[406x584x25] (2)17x22.5x1[432x572x25]

Page 8: CDV Fan-Coil Units High-Performance, · PDF fileCDV Fan-Coil Units High-Performance, Vertical. 2 ENVIRO ... The ENVIRO-TEC® CDV Series B vertical fan coil unit ... , three winding,

8 ENVIRO-TEC

Catalog: ET115.26-EG8 (415) CDV Fan-Coil Units High-Performance, Vertical

PHYSICAL DATA

UNIT WEIGHT DATA

COMPONENTUNIT SIZE

04 06 08 10 12 16 20BASE UNIT 81 [37] 81 [37] 103 [47] 103 [47] 106 [48] 128 [58] 134 [61]

MIXING BOX 24 [11] 24 [11] 24 [11] 37 [17] 37 [17] 54 [24] 54 [24]DISCHARGE PLENUM 21 [10] 21 [10] 21 [10] 33 [15] 33 [15] 48 [22] 48 [22]

RETURN PLENUM 17 [8] 17 [8] 17 [8] 25 [11] 25 [11] 33 [15] 33 [15]

COILROWS

1 ROW - DRY 7 [3] 7 [3] 8 [4] 11 [5] 11 [5] 16 [7] 16 [7]1 ROW - WET 8 [4] 8 [4] 9 [4] 14 [6] 14 [6] 19 [9] 19 [9]2 ROW - DRY 10 [5] 10 [5] 12 [5] 17 [8] 17 [8] 25 [11] 25 [11]2 ROW - WET 12 [5] 12 [5] 14 [6] 21 [10] 21 [10] 31 [14] 31 [14]3 ROW - DRY 16 [7] 19 [9] 21 [10] 27 [12] 29 [13] 38 [17] 46 [21]3 ROW - WET 20 [9] 23 [10] 26 [12] 35 [16] 38 [17] 49 [22] 60 [27]4 ROW - DRY 20 [9] 23 [10] 26 [12] 34 [15] 37 [17] 49 [22] 59 [27]4 ROW - WET 25 [11] 29 [13] 34 [15] 44 [20] 48 [22] 64 [29] 77 [35]

HEATING CAPACITYUNIT SIZE NOMINAL CFM

1 ROW 2 ROWQS (MBH) GPM WPD QS (MBH) GPM WPD

04 400 12 .5 1 .3 1 .5 21 .2 2 .2 1 .506 600 14 .9 1 .5 2 .1 26 .4 2 .7 2 .208 800 20 .5 2 .1 4 .9 36 .3 3 .7 4 .910 1000 30 .7 3 .2 2 .9 52 .9 5 .4 4 .312 1200 33 .5 3 .4 3 .4 58 .5 6 .0 5 .216 1600 50 .4 5 .2 4 .4 89 .0 9 .1 12 .320 2000 56 .0 5 .7 5 .4 100 .9 10 .3 15 .7

AHRI STANDARD RATINGS

UNIT SIZE AHRI 440 CERTIFIED

COILAIRFLOW

CFM (Dry Flow)

COOLING CAPACITY WATERPOWERINPUT

(WATTS)Rows FPI QT(BTUH)

QS(BTUH)

Flow Rate GPM

WPDft-wg

04 • 4 10 400 13 .6 9 .4 2 .7 3 .2 25006 • 4 10 600 18 .0 12 .9 3 .6 3 .6 27508 • 4 10 800 24 .3 17 .2 4 .9 4 .8 42510 • 4 10 1000 33 .6 23 .0 6 .7 5 .8 45012 • 4 10 1200 40 .4 27 .5 8 .1 8 .2 85016 4 10 1600 57 .6 38 .4 11 .5 9 .8 85020 4 10 2000 66 .4 45 .7 13 .3 4 .3 900

NOTES: 1. Basedon80°FDBand67°FWBEAT,45°FEWT,10°Ftemperaturerise,highfanspeed.Motor type isPSCandmotor

voltageis115/1/60.Airflowunderdrycoilconditions.Allmodelstestedat0.05"externalstaticpressure.2. AirflowrateCFMonsizes16and20exceedmaximumratingsinAHRI440andarethereforenotcertified.3. Forotherselections,refertoWeb-Select® .

NOTES:1. Basedon70°FEAT,180°FEWT,20°Ftemperaturedrop,highfanspeed.2. Forotherselections,refertoWeb-Select® .

NOTE:Unitweightdataisshippingweightinpounds[kilograms].

Page 9: CDV Fan-Coil Units High-Performance, · PDF fileCDV Fan-Coil Units High-Performance, Vertical. 2 ENVIRO ... The ENVIRO-TEC® CDV Series B vertical fan coil unit ... , three winding,

ENVIRO-TEC 9

CDV Fan-Coil Units High-Performance, Vertical Catalog: ET115.26-EG8 (415)

ELECTRIC HEAT

STANDARD FEATURES• ETLlistedasanassembly for safety compliance• Singlepointpowerconnection• Mountedinreheatposition• Automaticresetprimaryandback-up

secondary thermal limits• Internalwiringratedat105°C• Integralelectricheatassemblywith removableelementforeasyservice

OPTIONAL FEATURES• Silentsolidstaterelays• Doorinterlockingdisconnectswitch• Mainfusing• Manualresetsecondarylimits

USEFUL FORMULASkW* = CFMx∆Tx1.085** 34131ØAMPs = kWx1000 Volts* 1kW=3413BTU/H** CapacityatsealevelAltitude Considerations:Reduceby0.034foreach1000ft.ofaltitudeabovesealevel. Example:5000ft./1000ft.=5 5x0.034=0.17 1.085-0.17=0.915

ELECTRICAL CALCULATIONS INFORMATION1.RefertoMCA/MOPcalculatoratwww.enviro-tec.comforMCAand/orMOPcalculations.2.Non-FusedDoorInterlockDisconnectSwitchshallbesizedaccordingtoMCA.3.FusedDoorInterlockDisconnectSwitchandMainFusingshallbesizedaccordingtoMOP.

ELECTRIC HEAT SELECTION CHART (AMPS)

UNITSIZE

MBH 6.83 8.53 10.24 11.95 13.65 17.07 20.48 23.89 27.30 30.72 34.13 37.54 40.96 44.37KW 2.0 2.5 3.0 3.5 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0

VOLTS AMPS

04115 17 .4 21 .8 26 .1 30 .5 34 .8 43 .5208 9 .6 12 .0 14 .4 16 .8 19 .2 24 .1230 8 .7 10 .9 13 .1 15 .2 17 .4 21 .8277 7 .2 9 .0 10 .8 12 .6 14 .4 18 .1

06115 17 .4 21 .8 26 .1 30 .5 34 .8 43 .5208 9 .6 12 .0 14 .4 16 .8 19 .2 24 .1 28 .9 33 .7 38 .5230 8 .7 10 .9 13 .1 15 .2 17 .4 21 .8 26 .1 30 .5 34 .8277 7 .2 9 .0 10 .8 12 .6 14 .4 18 .1 21 .7 25 .3 28 .9

08115 17 .4 21 .8 26 .1 30 .5 34 .8 43 .5208 9 .6 12 .0 14 .4 16 .8 19 .2 24 .1 28 .9 33 .7 38 .5 43 .3230 8 .7 10 .9 13 .1 15 .2 17 .4 21 .8 26 .1 30 .5 34 .8 39 .2 43 .5277 7 .2 9 .0 10 .8 12 .6 14 .4 18 .1 21 .7 25 .3 28 .9 32 .5 36 .1 39 .7

10115 17 .4 21 .8 26 .1 30 .5 34 .8 43 .5208 9 .6 12 .0 14 .4 16 .8 19 .2 24 .1 28 .9 33 .7 38 .5 43 .3230 8 .7 10 .9 13 .1 15 .2 17 .4 21 .8 26 .1 30 .5 34 .8 39 .2 43 .5277 7 .2 9 .0 10 .8 12 .6 14 .4 18 .1 21 .7 25 .3 28 .9 32 .5 36 .1 39 .7 43 .3 46 .9

12115 34 .8 43 .5208 19 .2 24 .1 28 .9 33 .7 38 .5 43 .3230 17 .4 21 .8 26 .1 30 .5 34 .8 39 .2 43 .5277 14 .4 18 .1 21 .7 25 .3 28 .9 32 .5 36 .1 39 .7 43 .3 46 .9

16115 34 .8 43 .5208 19 .2 24 .1 28 .9 33 .7 38 .5 43 .3230 17 .4 21 .8 26 .1 30 .5 34 .8 39 .2 43 .5277 14 .4 18 .1 21 .7 25 .3 28 .9 32 .5 36 .1 39 .7 43 .3 46 .9

20115 34 .8 43 .5208 19 .2 24 .1 28 .9 33 .7 38 .5 43 .3230 17 .4 21 .8 26 .1 30 .5 34 .8 39 .2 43 .5277 14 .4 18 .1 21 .7 25 .3 28 .9 32 .5 36 .1 39 .7 43 .3 46 .9

NOTES:1.ShadedareasindicatekWandvoltageoptionsnotavailable.2.Availablevoltagesaresinglephase,60hertz.

Page 10: CDV Fan-Coil Units High-Performance, · PDF fileCDV Fan-Coil Units High-Performance, Vertical. 2 ENVIRO ... The ENVIRO-TEC® CDV Series B vertical fan coil unit ... , three winding,

10 ENVIRO-TEC

Catalog: ET115.26-EG8 (415) CDV Fan-Coil Units High-Performance, Vertical

FAN PERFORMANCE

GENERAL FAN NOTES1. Fancurvesdepictactualperformanceofeachmotortapwithoutanyadditionalfanbalanceadjustment.Actualcapacities

whichfallbeloweachcurvecanbeobtainedbyaddinganadjustmentdevice.Unitsshouldnotberunpriortoinstallationofdownstreamductwork;otherwise,damagetothemotormayresult.Theminimumexternalstaticpressurerequiredis0.1inchesw.g.

2 . ENVIRO-TEC®fancoilunitsareequippedwithpermanentsplit-capacitor(PSC)motorswiththreeseparatespeeds(High,MediumandLow)whichprovidesvariablehorsepoweroutputs.Mostoften,sizeselectionsareconservativeandactualCFMrequirementsand/orexternalstaticpressurerequirementsarelowerthanthosespecified.Inthiscase,theunitfanmotorcanberunatlowormediumtap,substantiallyreducingtheoperatingcostoftheunit.

3. Allfancurvesarefor115/1/60motorsandincludelossesforcabinet,electricheater,3or4rowcoil,andclean1"throwawayfilter. Forotherconfigurations,adjustperformancecurvesbasedonpressure losses for individualcomponents foundonpage7.

4. Seepage12forfanmotorelectricaldata.

CDV 04 • 3 and 4 Row Coils

0.1

0.0

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1.1

1.2

0 100 200 300 400 500 600 700

CFM

ESP

(IN. W

.G.)

3 ROW COIL4 ROW COIL

CDV 06 • 3 and 4 Row Coils

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0 100 200 300 400 500 600 800700

CFM

ESP

(IN. W

.G.)

3 ROW COIL4 ROW COIL

CDV 08 • 3 and 4 Row Coils

0.1

0

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1.1

0 200 400 600 800 1000 1200

CFM

ESP

(IN. W

.G.)

3 ROW COIL4 ROW COIL

CDV 10 • 3 and 4 Row Coils

0.1

0

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0 200 400 600 800 1000 1200 1400

CFM

ESP

(IN. W

.G.)

3 ROW COIL4 ROW COIL

HIGH

MED.LOW

HIGH

MED.

LOW

HIGH

MED.LOW

HIGH

MED.LOW

Page 11: CDV Fan-Coil Units High-Performance, · PDF fileCDV Fan-Coil Units High-Performance, Vertical. 2 ENVIRO ... The ENVIRO-TEC® CDV Series B vertical fan coil unit ... , three winding,

ENVIRO-TEC 11

CDV Fan-Coil Units High-Performance, Vertical Catalog: ET115.26-EG8 (415)

FAN PERFORMANCE CURVES

Aweb-basedComputerSelectionProgram,“Web-Select”,isavailabletofacilitatetheselectionprocess.Contactyourrepresentativetoobtainaccesstothispowerfulandtime-savingprogram.

0

20451935182016951555140012251015800000

16001550150014251330121010509008000

CDV 16 • 3 and 4 Row Coils

0 .0

0 .2

0 .4

0 .6

0 .8

1 .0

1 .2

0 500 1000 1500 2000 2500

CFM

ESP

(IN.W

.G.)

3ROWCOIL4ROWCOIL

HIGH

MED.LOW

0

1405136213281267121611631108102998095000

131512721254120311711122107010049500

CDV 12 • 3 and 4 Row Coils

0 .0

0 .2

0 .4

0 .6

0 .8

1 .0

1 .2

0 200 400 600 800 1000 1200 1400 1600

CFM

ESP

(IN.W

.G.)

3ROWCOIL4ROWCOIL

HIGH

MED.

LOW

19951900184117821657154314261300116780000

15851548150014501400135013001250115010008000

2375

CDV 20 • 3 and 4 Row Coils

0 .0

0 .1

0 .2

0 .3

0 .4

0 .5

0 .6

0 .7

0 .8

0 .9

1 .0

0 500 1000 1500 2000 2500CFM

ESP

(IN.W

.G.)

3ROWCOIL4ROWCOIL

HIGH

MED.LOW

Page 12: CDV Fan-Coil Units High-Performance, · PDF fileCDV Fan-Coil Units High-Performance, Vertical. 2 ENVIRO ... The ENVIRO-TEC® CDV Series B vertical fan coil unit ... , three winding,

12 ENVIRO-TEC

Catalog: ET115.26-EG8 (415) CDV Fan-Coil Units High-Performance, Vertical

MOTOR, FAN AND SOUND DATAMOTOR AND FAN DATA

SOUND DATA

UNIT SIZE MOTOR TAP MOTOR (QTY.) HP

NUMBER OF FANS

AMPS115V 208V 230V 277V

04HI (1)1/6

12 .7 1 .4 1 .4 1 .0

MED (1)1/8 2 .4 0 .9 0 .9 0 .9LOW (1)1/10 2 .2 0 .6 0 .6 0 .8

06HI (1)1/6

12 .7 1 .4 1 .4 1 .0

MED (1)1/8 2 .4 0 .9 0 .9 0 .9LOW (1)1/10 2 .2 0 .6 0 .6 0 .8

08HI (1)1/4

14 .9 2 .2 2 .2 2 .0

MED (1)1/5 4 .1 1 .5 1 .5 1 .7LOW (1)1/8 3 .2 1 .1 1 .1 1 .4

10HI (1)1/4

14 .9 2 .2 2 .2 2 .0

MED (1)1/5 4 .1 1 .5 1 .5 1 .7LOW (1)1/8 3 .2 1 .1 1 .1 1 .4

12HI (1)1/2

19 .6 4 .0 4 .0 3 .6

MED (1)1/3 9 .3 2 .7 2 .7 2 .9LOW (1)1/4 8 .8 2 .0 2 .0 2 .8

16HI (2)1/4

29 .8 4 .4 4 .4 4 .0

MED (2)1/5 8 .2 3 .0 3 .0 3 .4LOW (2)1/8 6 .4 2 .2 2 .2 2 .8

20HI (2)1/4

29 .8 4 .4 4 .4 4 .0

MED (2)1/5 8 .2 3 .0 3 .0 3 .4LOW (2)1/8 6 .4 2 .2 2 .2 2 .8

UNIT SIZE FAN SPEED CFM RPMTOTAL SOUND POWER LEVEL

OCTAVE BAND / CENTER FREQUENCY (HZ)2/125 3/250 4/500 5/1000 6/2000 7/4000 8/8000

04HI 610 1107 70 62 57 53 51 49 42

MED 570 1040 69 61 55 51 49 49 42LOW 515 949 69 63 58 53 50 49 42

06HI 750 1050 78 71 63 59 57 56 49

MED 650 895 73 66 59 55 53 51 47LOW 540 735 68 61 54 50 48 45 41

08HI 1050 1114 75 70 64 59 57 56 49

MED 1000 1023 72 68 62 57 55 54 46LOW 895 877 69 64 58 53 51 48 40

10HI 1275 1051 74 70 64 64 62 61 53

MED 1050 849 70 64 60 59 56 55 47LOW 825 671 65 58 54 53 50 48 40

12HI 1490 1089 77 72 67 68 68 67 62

MED 1420 1035 76 71 66 67 66 65 60LOW 1320 964 74 69 64 65 64 63 58

16HI 2300 1099 77 71 67 65 64 63 57

MED 2030 988 75 69 65 63 61 60 54LOW 1600 785 71 63 59 57 55 54 46

20HI 2290 1088 77 73 68 66 64 64 58

MED 1970 941 76 69 65 63 61 60 54LOW 1590 769 71 64 60 57 56 53 46

NOTES:1.Motorelectricaldataisnameplatedata.Actualdatawillvarywithapplication.2.230voltmotorisnameplatedfor208-230/1/60.Use230voltmotordatafor208voltapplications.

NOTES:1.SounddatatestedinaccordancewithAHRI350-86.2.Soundlevelsareexpressedindecibels,dBRE:1x10-12watts.3.Totalsoundpower leveldatabasedonfanCFMatcorrespondingmotor tapwith115/1/60voltmotor,0.0"externalstatic

pressure and standard rated internal pressure losses .

Page 13: CDV Fan-Coil Units High-Performance, · PDF fileCDV Fan-Coil Units High-Performance, Vertical. 2 ENVIRO ... The ENVIRO-TEC® CDV Series B vertical fan coil unit ... , three winding,

ENVIRO-TEC 13

CDV Fan-Coil Units High-Performance, Vertical Catalog: ET115.26-EG8 (415)

DIMENSIONAL DATA

MODEL CDV VERTICAL UNITSDrawingsarenottoscaleandnotforsubmittalorinstallationpurposes.

NOTES:1.Alldimensionsareinches[millimeters]+/-1/4"[6mm].Metricvaluesaresoftconversion.2 . Front access only is required for installation and service .3.Righthandunitshown,lefthandunitopposite.

WITH ELECTRIC HEATFront View Side View

Front View Side View

WITHOUT ELECTRIC HEAT

DIMENSIONS

Page 14: CDV Fan-Coil Units High-Performance, · PDF fileCDV Fan-Coil Units High-Performance, Vertical. 2 ENVIRO ... The ENVIRO-TEC® CDV Series B vertical fan coil unit ... , three winding,

14 ENVIRO-TEC

Catalog: ET115.26-EG8 (415) CDV Fan-Coil Units High-Performance, Vertical

DIMENSIONAL DATA

SUPPLY PLENUM WITH DOUBLE DEFLECTION GRILLEDrawingsarenottoscaleandnotforsubmittalorinstallationpurposes.

NOTES:1. Alldimensionsareinches[millimeters]+/-1/4"[6mm].Metricvaluesaresoftconversion.2. C-dimensionaddstobasicunitheight.

UNIT SIZE A B C SUPPLY GRILLEW x H

04-08 15" [381] 22" [559] 15" [381] 18" x 8" [457 x 203]10-12 18" [457] 29" [737] 18" [457] 24" x 12" [610 x 305]16-20 18" [457] 46" [1168] 18" [457] 40" x 12" [1016 x 305]

MIXING BOX SECTIONDrawingsarenottoscaleandnotforsubmittalorinstallationpurposes.

NOTES:1. Alldimensionsareinches[millimeters]+/-1/4"[6mm].Metricvaluesaresoftconversion.2. Returnairplenum(oneinlet,nodampers)isavailableinlieuofmixingboxsection.3. C-dimensionaddstobasicunitheight.4. Linkageandactuatorfordampercontrolshallbeprovided/installedbyothers.

UNIT SIZE A B EDC

04-08 22" [559] 15" [381] 3 1/2" [89]15" [381]15" [381]

10-12 29" [737] 18" [457] 4 1/2" [114]20" [508]18" [457]

16-20 46" [1168] 18" [457] 5" [127]36" [914]18" [457]

End View Side View

Page 15: CDV Fan-Coil Units High-Performance, · PDF fileCDV Fan-Coil Units High-Performance, Vertical. 2 ENVIRO ... The ENVIRO-TEC® CDV Series B vertical fan coil unit ... , three winding,

ENVIRO-TEC 15

CDV Fan-Coil Units High-Performance, Vertical Catalog: ET115.26-EG8 (415)

GUIDE SPECIFICATIONS

GENERAL

Furnish and install ENVIRO-TEC® Model CDV Vertical ConcealedDirectDriveFanCoilUnitwhereindicatedon the plans and specifications.Units shall be com-pletelyfactoryassembled,testedandshippedasonepieceexceptwherenoted.

Allunitsshallbecapableofmeetingorexceedingthescheduled capacities for cooling, heating, and airdelivery.Allunitdimensionsforeachmodelandsizeshallbeconsideredmaximums. UnitsshallbeETLlistedincompliancewithUL/ANSIStandard1995,andbecertifiedascomplyingwiththelatesteditionofAHRIStandard 440 .

CONSTRUCTION

Allunitsshallbefabricatedofheavygaugegalvanizedsteel,abletomeet125hoursaltspraytestperASTMB-117.Allexteriorpanelsshallbeinsulatedwith1/2"thickfiberglassinsulationratedforamaximumairveloc-ity of 5000 f.p.m. In addition to using adhesivecomplyingwithNFPA90Aand90B,theinsulationshallincorporate a secondary mechanical fastener attached totheunitcasingwall(weldpin).Adhesiveastheonlymethodoffasteningtheinsulationtothecasingisnotacceptable.InsulationshallconformtoUL181forero-sion,ASTMC-1071for thermalandsoundabsorbingmaterial,NFPA90Aand90Bfor fireandsmoke,andcarry a 25/50 Flame Spread and Smoke Developed RatingperASTME-84andUL723.

All units shall have aminimum1" duct collar on thedischarge. All accesspanels shall be fully insulatedandattachedwithstandard fastenersonat least twooppositesides.Nocoil,drainpiping,orelectricalcon-nectionsshallpassthroughanyaccesspanel.

Option: Provide foil faced insulation in lieu of matt faced insulation. Foil insulation shall meet or exceed therequirementsstatedabove,andinadditionmeetASTMStandards C-665 and C-1136 for mold, mildew, andhumidityresistance.Insulationshallbelinedwithalu-minumfoil,fiberglassscrimreinforcement,and#30kraftpaperlaminatedtogetherwithaflameresistantadhe-sive.Allexposededgesshallbesealedtopreventanyfibersfromreachingtheairstream.

Option: Provide elastomeric closed cell foam insulation in lieu of standard . Insulation shall meet all require-ments of NFPA 90-A flame and smoke spread andmeltingpoint,aswellasASTMG-21forbacterialand fungi resistance. Polyethylene insulation is notacceptable.

Each unit shall be furnishedwith a one-piece heavygaugegalvanizedsteeldrainpanwithweldedcornerconstruction .

Option:Provideasinglewallprimarydrainpancon-structed entirely of heavy gauge stainless steel forsuperior corrosion resistance . Stainless steel drain pans shall meet or exceed the requirements statedabove.

SOUND

Units shall have published sound power level datatestedinaccordancewithAHRIStandard350-86.

FAN ASSEMBLY

Unit fan shall be dynamically balanced, forwardlycurved,directdriveDWDIwheelwith18gaugegalva-nizedchromatecoateddoubleinletscroll.Motorshallincludetorsionflexsuspensionmountaffixedtoscrollusing permanently attached mounting studs. MotormountshallbesecuredwithNylock®locknuts.Blowerscrollshallbemountedtofanbulkheadwith18gaugemounting rail inamanner toallownometal-to-metalcontactwithfanbulkhead.

Blowermotorshallbehighefficiency,permanentlylubri-catedsleevebearing,permanentsplit-capacitortypewiththermal overload protection and three separate horse-power taps. Singlespeedmotorsarenotacceptable.Thefanmotorshallbeunpluggablefromtheelectricalleads at the motor case for simplified removal .

Option:Provideanelectronic(SCR)fanspeedcontrol-ler for aid in balancing the fan capacity. The speedcontrollershallhavea turndownstop toprevent thepossibilityofharmingthemotorbearings,andincorpo-rateelectricalnoisesuppressiontominimizenoiseontheincomingpowerlines.

COILS

All unit coils shall be rated in accordance with AHRI410.

Allcoilsshallbe1/2"O.D.seamlesscoppertubesshallbemechanicallyexpandedtoprovideanefficientbondbetweentubeandfin.Allwatercoilsshallbeprovidedwithamanualairvent fittingtoallowforcoilventing.Valvecoretypeventfittingsshallnotbeaccepted.

Allchilledwater,hotwater,anddirectexpansion(DX)coilsshallhave0.016"tubewallthickness.

Page 16: CDV Fan-Coil Units High-Performance, · PDF fileCDV Fan-Coil Units High-Performance, Vertical. 2 ENVIRO ... The ENVIRO-TEC® CDV Series B vertical fan coil unit ... , three winding,

GUIDE SPECIFICATIONS

All coilsshallbehydrostatically testedwithairunderwaterat450PSIGminimumpressureandratedforamaximumof300PSIGworkingpressureat200°F.

DXcoilsshallbetestedto450PSIGpressureandfac-tory sealed and chargedwith aminimum of 5 PSIGnitrogenorrefrigerateddryair.DXcoilsshallbepro-vided with a fixed orifice metering device(distributor-eliminator).

OPTIONS

CoilcasingshallbefabricatedfromStainlessSteel.

Provide automatic air vents, in lieu of manual air vents .

Tubewall thicknessshallbe0.025"onchilledwater,hotwater,anddirectexpansioncoils.

FILTER

Allunitsshallbefurnishedwithaminimum1"nominalthrowawayfilter.Provideoptional2"filterrackwith2"throwawayfilterwhereindicated.Filtersshallbetightfittingtopreventairbypass.

SUPPLY PLENUM SECTION

Provideafullyinsulatedintegralsupplyplenumsection,completewithdoubledeflectionsupplygrille.Supplyplenum sections shipped loose for field installation to theunitsarenotacceptable.

MIXING BOX SECTION

Provide a fully insulated integralmixing box section,completewithreturnandoutsideairdampers.Mixingboxsectionsshippedlooseforfieldinstallationtotheunitsarenotacceptable.

ELECTRICAL

Unitsshallbefurnishedwithasinglepointpowerloca-tion and electrical junction box for motor and otherelectrical terminations .

ELECTRIC HEAT SECTION

Provideanintegralelectricresistanceheatingassemblywiththeheatingcapacity,voltage,kilowatts,andstagesasshownintheschedule.

Theheaterassemblyshallbedesignedandratedforinstallation to theairhandlingunitwithout theuseofductextensionsortransitionsbetweentheunitandtheheaterassembly.Theheatershallbefactoryassem-bled and completely wired for single point powerconnection .

Theheaterandunitassemblyshallbe listedforzeroclearance and shall meet all NEC requirements, and beETLlistedwiththeunitasanassemblyincompli-ancewithUL/ANSIStandard1995.

All heatingelements shall beopen coil designusingNi-Chrome wire mounted in ceramic insulators andhousedinaninsulatedheavygaugegalvanizedsteelhousing. All elements shall terminate in a machinestakedstainlesssteel terminalsecuredwithstainlesssteelhardwareforcorrosionresistance.Theelementsupportbracketsshallbespacednogreaterthan3-1/2"oncenter.All internalwiringshallberatedfor105°Cminimum .

All heaters shall include overtemperature protection,andshallbe interlockedwith the fan. Allheaterele-mentsshallbesinglestageunlessnotedotherwiseonthe plans .

Anincominglinepowerdistributionblockshallbepro-vided.Thepowerdistributionblockshallbedesignedto accept incoming powerwiring capable of carrying125% of the calculated load current .

Option: Provide a manual reset secondary thermal limit .

Option: Devices used to energize and de-energize(switch)electricheatmustbetotallysilent.Magnetic,mercury, and/or quiet relays and/or contactors are not acceptable.

ENVIRO-TECisaregisteredtrademarkofJohnsonControls,Inc.intheUnitedStatesofAmericaandothercountries.Othertrademarksusedhereinmaybetrademarksorregisteredtrademarksofothercompanies.

Catalog:ET115.26-EG8(415)SupersedesET115.26-EG8(909)©2015JohnsonControls,Inc.P.O.Box423,Milwaukee,WI53201PrintedinUSAwww.enviro-tec.com