SA
SA
A
E1.1
1
E1.1
(E)
(E)
EXISTING IN GROUND
JUNCTION BOX
SEE DETIAL
SEE DETIAL
EXISTING
LIGHTING CIRCUIT
(TYP)
C
E
1
.
1
EXISTING
(2) 2-1/2"C(2) 2-1/2"C
TO ROOM #2
EXISTING IN GROUND
JUNCTION BOX
GALEON LED AREA AND ROADWAY
SAMcGRAW - EDISON
MANUFACTURER
LUMINAIRE (2) 70 CRI, 3000k,
DUAL HEAD
1A LIGHTSQUARE WITH 16 LEDS AND
TYPE III OPTICS
DRAWING NOTES:
CONTRACTOR SHALL REMOVE EXISTING FIXTURES, POLE
BASES, CONDUIT AND WIRE IN THEIR ENTIRETY WHERE INDICATED.
CONDUIT AND WIRE SHALL BE REMOVED TO POINT INDICATED WITH
JUNCTION BOX. FIXTURES SHALL BE TURNED OVER TO OWNER. POST
HOLES AND TRENCH SHALL BE FILLED IN TO MATCH SURROUNDING
AREA. COORDINATE WITH SITE CONTRACTOR.
CONTRACTOR SHALL INTERCEPT EXISTING CONDUIT AND CONNECT
TO JUNCTION BOX. EXISTING WIRE SHALL BE SPLICED WITH NEW
WIRE TO NEW POLE. EXISTING CIRCUIT: (3) # 6, (1) # 10GRD-1-1/2"C, AS
PER AS BUILT DRAWING E1.
EXISTING JUNCTION BOX AND CONDUIT LOCATIONS BASED ON AS
BUILT DRAWING E1. CONTRACTOR SHALL FIELD VERIFY.
CONDUITS SHALL BE STUBBED UP TO LEVEL OF FINISHED GRADE AND
CAPPED.
24"
RED MARKER TAPE
WITH METAL TRACER
6" BELOW FINISHED GRADE
6" MINIMUM
STONE DUST
3" DUST OR
SAND BASE
OVER CONDUITS
RED MARKER TAPE
GRADE
SCHEDULE 40
PVC CONDUIT
NOTE:
1. BACKFILL TO BE COMPACTED
IN 6 INCH LAYERS TO AVOID
SETTLING.
NO SCALE
36" U
ND
ER
R
OA
DW
AY
WITH METAL TRACER WIRE.
4"
PROVIDE GASKETED HEAVY DUTY COMPOSITE
COVER WITH "ELECTRIC" LOGO
CRUSHER RUN
SUMP AREA
2"
2"
COMPACTED EARTH
3000 PSI CONCRETE
AROUND BOX
NO SCALE
NOTES:
1. SEE SITE PLAN FOR QUANTITIES & SIZES
OF ELECTRICAL CONDUITS.
POLE
HANDHOLE W/COVER
GROUND LUG
BOLT COVER
1" CHAMFER
30"
6'-0"
FINISHED GRADE/
PAVEMENT
18"
MIN.
PVC CONDUIT
(TYP.)
STEEL ANCHOR
BOLTS QUANT.,
LENGTH, DIA.,
& PROJECTION
FROM CONC.
PER MANUF.
RECOMMENDATIONS.
24"Ø CONC.
VERTICAL REINF.
#5 REBAR @
6" O.C.
#4 REBAR @
12" O.C.
2'-0"
GROUND ROD
5/8"Ø x 10'-0"
CADWELD
CONNECTION
NO SCALE
(3) #6, (1) #10 GRD- 1-1/2"C
GLEON-AE-01-LED-E1-
T3-GM-MA
W/ 30' POLE, COOPER; SSS-6-M-30-S-G-4-2
24"
RED MARKER TAPE
WITH METAL TRACER
6" BELOW FINISHED GRADE
6" MINIMUM
STONE DUST
3" DUST OR
SAND BASE
OVER CONDUITS
RED MARKER TAPE
GRADE
SCHEDULE 40
PVC CONDUIT
NOTES:
1. BACKFILL TO BE COMPACTED
IN 6 INCH LAYERS TO AVOID
SETTLING.
CONDUITS ARE TO HAVE 2
INCHES OF HORIZONTAL
SEPARATION.
2.
NO SCALE
36" U
ND
ER
R
OA
DW
AY
24"
RED MARKER TAPE
WITH METAL TRACER
6" BELOW FINISHED GRADE
6" MINIMUM
STONE DUST
3" DUST OR
SAND BASE
OVER CONDUITS
RED MARKER TAPE
GRADE
SCHEDULE 40
PVC CONDUIT
NOTE:
1. BACKFILL TO BE COMPACTED
IN 6 INCH LAYERS TO AVOID
SETTLING.
NO SCALE
36" U
ND
ER
R
OA
DW
AY
WITH METAL TRACER WIRE.
2-1/2"C
2-1/2"C
2-1/2"C