CGVision with BACnet server(only for ZB-S and CG2000!)

04-04-2011

7.2

Page 2: CGVision with BACnet server (only for ZB-S and CG2000!) 04-04-2011 7.2

04.04.2011 - A.Klepper 2

LAN

(RJ45)

BMSwith BACnet-Technology

PC workplace withCGVision

LAN (RJ45)

Visualisation of

BACnet objects(event orientated)

IP-RouterConfig-server

ZB-S

CG-S Bus / FTT10A

ZB-S or CG2000 Systems

ZB-S

IP-RouterClient 1

ZB-S

CG-S Bus / FTT10A

ZB-S or CG2000 Systems

ZB-S

ZB-S

TCP/IP connection – CGVision via CG-S/IP-Router

BACnet/IP – BMS on CGVisionBMS has access to the BACnet Server !Visualisation of BACnet Objects

Schema: BACnet-connection via OPC-Client/BACnet Server

OPC-ClientSNVT

BACnet Server

BACnet Objects

EthernetBACnet /IP

TCP/IP

CG2000

CG2000 CG2000

Page 3: CGVision with BACnet server (only for ZB-S and CG2000!) 04-04-2011 7.2

04.04.2011 - A.Klepper 3

BACnet status informations 22 pcs. Status informations each device (ZB-S / CG2000)1) Device in normal operation2) Sum failure with luminaire failure3) Sum failure without luminaire failure4) Communication error CG-S bus5) Device in battery mode6) Battery duration test is activ7) Device is blocked8) Bettery failure (e.g. interruption)9) Sum failure in a circuit (e.g.:fuse)10) Mains failure (sum)11) Deep discharge protection is activ12) Interruption of the battery circuit13) Charging failure battery14) Isolation failure battery, battery + or – against protection earth15) Rated duration test time not reached16) General luminaire failure17) Functionstest is activ18) Battery voltage to high19) Charging unit failure20) Charging booster failure21) Mains failure - device22) Mains failure – sub distribution board

Page 4: CGVision with BACnet server (only for ZB-S and CG2000!) 04-04-2011 7.2

04.04.2011 - A.Klepper 4

BACnet analogue datas and switch commandos 4 pcs. Analogue values each device1) Battery current (Charging- discharging current)

2) Battery voltage

3) Battery temperature

4) Battery capacity

16 (ZB-S) or 30 (CG2000) pcs. switch commandos each device 1) LON-Switch 1

2) LON-Switch 2

16) LON-Switch 16 (ZB-S)

…..

30) LON-Switch 30 (only CG2000)

3 pcs. status informations e. device (mirror of relay outputs)1) Emergency operation

2) Normal operation

3) Sum failure

6 pcs. control comandos each device1) Block device

2) Release device

3) Start functiontest

4) Start battery duration test

5) Stop battery duration test

6) Quit deep discharge protection

Page 5: CGVision with BACnet server (only for ZB-S and CG2000!) 04-04-2011 7.2

04.04.2011 - A.Klepper 5

Example of status informations via BACnetScreenshot of a BACnet OPC-Server:

Page 6: CGVision with BACnet server (only for ZB-S and CG2000!) 04-04-2011 7.2

04.04.2011 - A.Klepper 6

Example of switch commandos via BACnet

Screenshot of a BACnet OPC-Server: