chapter4 trans

Upload: abdul-shukor

Post on 07-Apr-2018

255 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/6/2019 Chapter4 Trans

    1/104

    1

    Chapter 4.Transformer

  • 8/6/2019 Chapter4 Trans

    2/104

    2

    Transformer- Introduction Two winding transformers Construction and principles

    Equivalent circuit Determination of equivalent circuit

    parameters Voltage regulation

    Efficiency Auto transformer 3 phase transformer

  • 8/6/2019 Chapter4 Trans

    3/104

    3

    Transformer- Introduction

    Varieties of transformers

  • 8/6/2019 Chapter4 Trans

    4/104

    4

    Transformer- Introduction

  • 8/6/2019 Chapter4 Trans

    5/104

    5

    Transformer- Introduction

    Transformer is a device that makes use of themagnetically coupled coils to transfer energy

    It is typically consists of one primary windingcoil and one or more secondary windings

    The primary winding and its circuit is called

    the Primary Side of the transformer The secondary winding and its circuit is called

    the Secondary Side of the transformer

  • 8/6/2019 Chapter4 Trans

    6/104

    6

    Transformer- Introduction

    If one of those winding, the primary, isconnected to an alternating voltagesource, an alternating flux will beproduced. The mutual flux will link theother winding, the secondary, and will

    induced a voltage in it.

  • 8/6/2019 Chapter4 Trans

    7/104

    7

    Transformer- Introduction Transformers are adapted to numerous engineering

    applications and may be classified in many ways:

    Power level (from fraction of a volt-ampere (VA) to over athousand MVA),

    Application (power supply, impedance matching, circuitisolation),

    Frequency range (power, audio, radio frequency (RF)) Voltage class (a few volts to about750 kilovolts) Cooling type (air cooled, oil filled, fan cooled, water

    cooled, etc.) Purpose (distribution, rectifier, arc furnace, amplifier

    output, etc.).

  • 8/6/2019 Chapter4 Trans

    8/104

    8

    Transformer- Introduction

    Power transmission

  • 8/6/2019 Chapter4 Trans

    9/104

    9

    Transformer- Introduction

    Power transmission

  • 8/6/2019 Chapter4 Trans

    10/104

    10

    Transformer

    4.1 Construction

  • 8/6/2019 Chapter4 Trans

    11/104

    11

    Transformer- construction

    Basic components of single phase transformer

  • 8/6/2019 Chapter4 Trans

    12/104

    12

    Transformer- construction

    Single phase transformer construction

    A) re ty e B ) S ell ty e

  • 8/6/2019 Chapter4 Trans

    13/104

    13

    Transformer- construction

  • 8/6/2019 Chapter4 Trans

    14/104

    14

    Transformer- constructionPrimar

    Winding

    econdarWinding

    Multi-la er

    Laminated

    Iron Core

    X1

    X2H

    1 H2

    WindingTerminals

  • 8/6/2019 Chapter4 Trans

    15/104

    15

    4.2 Ideal Transformer

    Transformer

  • 8/6/2019 Chapter4 Trans

    16/104

    16

    Transformer

    i

    e1

    v1 v2

    e2

    The emf which induced in

    transformer primary winding is

    known as self induction emf asthe emf is induced due to to flux

    which produced by the winding

    itself.

    While the emf which induced in

    transformer secondary winding

    is known as mutual induction

    emf as the emf is induced due

    to to flux which produced by the

    other winding.

  • 8/6/2019 Chapter4 Trans

    17/104

    17

    Transformer

    i

    e1

    v1 v2

    e2

    Acording to Faradays Law,theemf which induced in

    the primary winding is,

    e1 =dt

    dN

    J1

    Since theflux is analternating flux,

    tmak [sin!e1 = dt

    tdN ak

    )sin(1

    [J

    tmak [[ cos1!

  • 8/6/2019 Chapter4 Trans

    18/104

    18

    Transformer

    i

    e1

    v1 v2

    e2

    e1

    where,

    tfmak [T cos21!

    tE [cosmax1

    !

    max1E fN TJ 2max1=

    2

    max1

    1

    EErms ! fmax144.4 J!

  • 8/6/2019 Chapter4 Trans

    19/104

    19

    Transformer

    i

    e1

    v1 v2

    e2

    e2 =

    Similarly it can be shownthat,

    dt

    dN

    J2

    E2 rms fN max244.4 J

    kf

    f

    E

    E

    1

    2

    max1

    max2

    1

    2

    44.4

    44.4

    J

    Jk is transformation ratio

  • 8/6/2019 Chapter4 Trans

    20/104

    20

    Transformer

    The voltage ratio ofinduced voltages on the secondary toprimary windings is equal to the turn ratio of the winding turn

    number of the secondary winding to the winding turn numberof the primary winding. Therefore the transformers can beused to step up or step down voltage levels by choosingappropriate number their winding turns. In power system itsnecessary to step up the outputvoltage of a generator which

    less than 30kV to up 500kV for long distance transmission.High voltage for long distance power transmission can reducecurrentflow in the transmission lines, thus line losses andvoltage drop can be reduced.

  • 8/6/2019 Chapter4 Trans

    21/104

    21

    2

    NE m11

    [*!

    2

    m22

    [*!

    Current, voltages and flux in an unloaded ideal transformer

    Transformer- Ideal Transformer Winding resistances are zero, no leakage

    inductance and iron loss

    Magnetization current generates a flux thatinduces voltage in both windings

  • 8/6/2019 Chapter4 Trans

    22/104

    2222

    Transformer

    i

    e1

    v1 v2

    e2

    Transformer on no load.

  • 8/6/2019 Chapter4 Trans

    23/104

    23

    Transformer- Ideal Transformer Loaded transformer

    i

    V1

    E2E1

    V2Z

    L

    I2

    2

    N1 N

    2

    1

    W

    he

    n aload is conn

    ect

    ed to th

    es

    econdary output t

    er

    mina

    ls o

    fa transformer as shown in Figure 4.5, a current I2flows into the

    load and into transformer secondary winding N2. The current I2which flowing in N2produces flux 2which opposite by Lenzslaw- to themain magnetic flux in the transformer core. Thiswill weaken or slightly reduce themain flux to .

  • 8/6/2019 Chapter4 Trans

    24/104

    24

    Transformer- Ideal Transformer Loaded transformer

    i

    V1

    E2E1

    V2Z

    L

    I2

    2

    N1 N

    2

    1

    The reduction ofmain flux by Faradays law- could alsoreduce the induced voltage in primary winding E1.Consequently E1is now smaller than the supply voltage V1,then the primary current would be increased due to thatpotential differences. Therefore on loaded transformer, theprimary current has an additional current of I1.

  • 8/6/2019 Chapter4 Trans

    25/104

    25

    Transformer- Ideal Transformer Loaded transformer

    i

    V1

    E2E1

    V2Z

    L

    I2

    2

    N1 N

    2

    1

    Theextra current I1which flowing in the primary winding N1produces flux 1which naturally react according to Lenzslaw, demagnetize theflux 2. Therefore the net magneticflux in the core is always maintained at original value, it isthemain flux (theflux which produced by themagnetizingcurrent).

  • 8/6/2019 Chapter4 Trans

    26/104

    26

    Transformer- Ideal Transformer Loaded transformer

    i

    V1

    E2E1

    V2Z

    L

    I2

    2

    N1 N

    2

    1

    Themagneto motiveforce (mmf) source N2I

    2at the

    secondary winding produces flux 2, while themmf N1I1produces flux 1. Since themagnitude of 1equal tomagnitude of2and the reluctance seen by these two mmfsources areequal, thus

    N1I1 = N2I2

  • 8/6/2019 Chapter4 Trans

    27/104

    27

    Currents and fluxes in a loaded ideal transformer

    Transformer- Ideal Transformer Loaded transformer

  • 8/6/2019 Chapter4 Trans

    28/104

    28

    Transformer- Ideal Transformer Turn ratio

    Ifthe primary winding has N1 turns and

    secondary winding has N2 turns, then:

    The inputand outputcomplex powers are equal

    1

    2

    2

    1

    2

    1

    I

    I

    E

    E

    N

    Na !!!

    **IESSIE 222111 !!!

  • 8/6/2019 Chapter4 Trans

    29/104

    29

    Transformer- Ideal Transformer Functional description of a transformer:

    When a = 1 Isolation Transformer

    When | a | < 1 Step-Up Transformer Voltageis increased from Primary

    side to secondary side

    When | a | > 1 Step-Down TransformerVoltage is decreased fromPrimary side to secondary

    side

  • 8/6/2019 Chapter4 Trans

    30/104

    30

    Transformer- Ideal Transformer Transformer Rating

    Practical transformers are usually rated

    based on:Voltage Ratio (V1/V2) which gives us the

    turns-ratio

    Power Rating, small transformers are

    given in Watts (real power) and Largerones (Power Transformers) are given inkVA (apparentpower)

  • 8/6/2019 Chapter4 Trans

    31/104

    31

    Transformer- Ideal Transformer

    Example 4.1

    Determine the turns-ratio of a 5 kVA2400V/120V Power Transformer

    Turns-Ratio = a = V1/V2 = 2400/120 =20/1 = 20

    This means itis a Step-Down transformer

  • 8/6/2019 Chapter4 Trans

    32/104

    32

    Transformer- Ideal Transformer

    Example 4.2

    A 480/2400 V (r.m.s) step-up idealtransformer delivers 50 kW to a resistiveload. Calculate:

    (a) the turns ratio, (0.2)

    (b) the primary current, (104.17A)(c) the secondary current. (20.83A)

  • 8/6/2019 Chapter4 Trans

    33/104

    33

    Transformer- IdealTransformer Nameplate oftransformer

  • 8/6/2019 Chapter4 Trans

    34/104

    34

    Transformer- IdealTransformer Equivalentcircuit

    Equivalent circuit of an ideal transformer

  • 8/6/2019 Chapter4 Trans

    35/104

    35

    Transformer- IdealTransformer Transferring impedances through a transformer

    2

    22

    2

    2

    1

    11

    I

    V

    I

    V

    I

    VZ a

    a

    a!

    !!

    Equivalent circuit of an ideal transformer

    load

    a2

    1

    !

  • 8/6/2019 Chapter4 Trans

    36/104

    36

    a) Equivalent circuit when

    secondary impedance istransferred to primary side and

    ideal transformer eliminated

    b) Equivalent circuit when

    primary source is transferred tosecondary side and ideal

    transformer eliminated

    Thvenin equivalents of transformer circuit

    Transformer- IdealTransformer

  • 8/6/2019 Chapter4 Trans

    37/104

    37

    Transformer- practical transformer PracticalTransformer

  • 8/6/2019 Chapter4 Trans

    38/104

    38

    4.3 Equivalent Circuits

    Transformer

  • 8/6/2019 Chapter4 Trans

    39/104

    39

    Transformer- equivalent circuit

  • 8/6/2019 Chapter4 Trans

    40/104

    40

    Transformer- equivalent circuitDevelopment of the transformer equivalent circuits

    The effects of winding resistance and leakage flux are

    respectively accounted for by resistance R and leakagereactance X (2fL).

  • 8/6/2019 Chapter4 Trans

    41/104

    41

    In a practical magneticcore having finitepermeability, a magnetizing currentIm is

    requiredto establish a flux in the core. This effectcan be represented by a

    magnetizing inductance Lm. The core loss canbe represented by a resistance Rc.

    Transformer- practical equivalentcircuit

  • 8/6/2019 Chapter4 Trans

    42/104

    42

    Rc :core loss component,

    Xm : magnetization component,

    R1 and X1 are resistance and reactance of the primary winding

    R2 and X2 are resistance and reactance of the secondary winding

    Transformer- practical equivalent circuit

  • 8/6/2019 Chapter4 Trans

    43/104

    43

    Transformer- practical equivalent circuit The impedances of secondary side such

    as R2, X2 and Z2 can be moved to

    primary side and also the impedancesof primary side can be moved to thesecondary side, base on the principle

    of:The power before transferred = The

    power after transferred.

  • 8/6/2019 Chapter4 Trans

    44/104

    44

    Transformer- practical equivalent circuitThe power before transferred = The power

    after transferred.

    I22R2 = I1

    2R2

    Therefore R2= (I2/ I1) 2 R2

    = a2R2

  • 8/6/2019 Chapter4 Trans

    45/104

    45

    Transformer- practical equivalent circuitThe turns can be moved to the right or left by referring

    all quantities to the primary or secondary side.

    The equivalent circuit with secondary side moved to the primary.

  • 8/6/2019 Chapter4 Trans

    46/104

    46

    Transformer- Approximate equivalentcircuit

    For convenience, the turns is usually notshown and the equivalent circuit is drawn

    with allquantities (voltages, currents, andimpedances) referred to one side.

  • 8/6/2019 Chapter4 Trans

    47/104

    47

    Transformer- equivalent circuit Example 4.3

    A 100

    kVA transformer has400

    turns on the primaryand80 turns on the secondary. The primary andsecondary resistance are 0.3 ohm and0.01 ohmrespectively and the corresponding leakagereactances are 1.1 ohm and0.035 ohm respectively.The supply voltage is 2200V. Calculate:

    (a) the equivalent impedance referred to the primarycircuit(2.05 ohm)(b) the equivalent impedance referred to thesecondary circuit

  • 8/6/2019 Chapter4 Trans

    48/104

    48

    4.4D

    etermination ofEquivalent Circuit

    Parameter

    Transformer

  • 8/6/2019 Chapter4 Trans

    49/104

    49

    1. No-load test (or open-circuit test).

    2. Short-circuit test.

    Transformer- o/c-s/c tests The equivalentcircuit model for the actual

    transformer can be usedto predictthe behavior ofthe transformer.

    The parameters R1, X1, Rc, Xm, R2, X2 and N1/N2mustbe known so thatthe equivalentcircuit modelcan be used.

    These parameters can be directly and more easily

    determined by performing tests:

  • 8/6/2019 Chapter4 Trans

    50/104

    50

    No load/Open circuit test

    Provides magnetizing reactance (Xm) and core

    loss resistance (RC) Obtain components are connected in parallel

    Short circuit test

    Provides combined leakage reactance and

    winding resistance

    Obtain components are connected in series

    Transformer- o/c-s/c tests

  • 8/6/2019 Chapter4 Trans

    51/104

    51

    Transformer- open circuit test No load/Open circuit test

    Equivalent circuit for open circuit test, measurement at the primary side.

    Simplified equivalent

    circuit

  • 8/6/2019 Chapter4 Trans

    52/104

    52

    Transformer- open circuit test Open circuit test evaluation

    Q

    V

    XP

    V

    R

    IVQIV

    P

    oc

    m

    oc

    oc

    c

    ococ

    ococ

    oc

    22

    0

    1

    0 sincos

    !!

    !

    ! UU

  • 8/6/2019 Chapter4 Trans

    53/104

    53

    Transformer- short circuit test Short circuit test

    Secondary (normally the LV winding) is shorted,that means there is no voltage across secondary

    terminals; but a large current flows in thesecondary.

    Test is done at reduced voltage (about5% ofrated voltage) with full-load current in the

    secondary. So, the ammeter reads the full-loadcurrent; the wattmeter reads the winding losses,and the voltmeter reads the applied primaryvoltage.

  • 8/6/2019 Chapter4 Trans

    54/104

    54

    Transformer- short circuit test Short circuit test

    Equivalent circuit for short circuit test, measurement at the primary side

    Simplified equivalent circuit for short circuit test

  • 8/6/2019 Chapter4 Trans

    55/104

  • 8/6/2019 Chapter4 Trans

    56/104

    56

    Transformer- short circuit test Short circuit test evaluation

    21211

    121

    eee

    sc

    sce

    sc

    sce

    RZX

    I

    VZ

    I

    PR

    !

    !!

  • 8/6/2019 Chapter4 Trans

    57/104

    57

    Transformer- o/c-s/c tests Equivalentcircuit obtained by measurement

    Equivalent circuit for a real transformer resulting from the

    open and short circuit tests.

  • 8/6/2019 Chapter4 Trans

    58/104

    58

    Transformer- o/c-s/c tests Example 4.4

    Obtain the equivalentcircuit of a 200/400V, 50Hz

    1-phase transformer from the following test data:-

    O/C test : 200V, 0.7A, 70W - on L.V. side

    S/C test : 15V, 10A, 85W - on H.V. side

    (Rc =571.4 ohm, Xm=330 ohm, Re=0.21ohm,Xe=0.31 ohm)

  • 8/6/2019 Chapter4 Trans

    59/104

    59

    Transformer voltage regulation Voltage Regulation

    Mostloads connected to the secondary of a transformer are

    designed to operate at essentially constant voltage. However,as the current is drawn through the transformer, the loadterminalvoltage changes because of voltage drop in theinternal impedance.

    To reduce the magnitude of the voltage change, thetransformer should be designed for a low value of theinternal impedance Zeq

    The voltage regulation is defined as the change inmagnitude of the secondary voltage as the loadcurrentchanges from the no-load to the loadedcondition.

  • 8/6/2019 Chapter4 Trans

    60/104

    60

    ZV2

    I2 I2

    V12=V20

    R1 R2

    Ze2

    X1

    Rc Xm

    X2

    Ze2 = R1 + R2 + jX1 + jX2

    = Re2 + jXe2

    Transformer voltage regulation

  • 8/6/2019 Chapter4 Trans

    61/104

    61

    ZV2

    I2 I2

    V12=V20

    R1 R2

    Ze2

    X1

    Rc Xm

    X2

    Applying KVL, V20= I2 (Ze2 ) + V2 = I2 (Re2 + jXe2 ) + V2

    Transformer voltage regulation

    Or V2= V20 - I2(Ze2)

  • 8/6/2019 Chapter4 Trans

    62/104

    62

    I2Xe2

    I2Re2

    I2

    V2

    OA

    2

    Transformer voltage regulation

  • 8/6/2019 Chapter4 Trans

    63/104

    63

    I2Xe2

    I2Re2

    I2

    V2

    O

    V20

    I2Re2

    I2Xe2

    A

    B

    2

    Transformer voltage regulation

    V20= I2 (Ze2 ) + V2 = I2 (Re2 + jXe2 ) + V2

  • 8/6/2019 Chapter4 Trans

    64/104

    64

    I2Xe2

    I2Re2

    I2

    V2

    O

    V20

    I2Re2

    I2Xe2

    C

    MNDA

    B

    2

    L

    2

    2

    Transformer voltage regulation

    Voltage drop = AM = OM OA

    = AD + DN + NM

  • 8/6/2019 Chapter4 Trans

    65/104

    65

    I2Xe2

    I2Re2

    I2

    V2

    O

    V20

    I2Re2

    I2Xe2

    C

    MNDA

    B

    2

    L

    2

    2

    Transformer voltage regulation

    AD = I2 Re2 cos2

    DN=BL= I2 Xe2 sin2

  • 8/6/2019 Chapter4 Trans

    66/104

    66

    I2Xe2

    I2Re2

    I2

    V2

    O

    V20

    I2Re2

    I2Xe2

    C

    MNDA

    B

    2

    L

    2

    2

    Transformer voltage regulation

    Applying Phytogrus theorem to OCN triangle.

    (NC)2 = (OC)2 (ON)2

    = (OC + ON)(OC - ON) 2(OC)(NM)

  • 8/6/2019 Chapter4 Trans

    67/104

    67

    I2Xe2

    I2Re2

    I2

    V2

    O

    V20

    I2Re2

    I2Xe2

    C

    MNDA

    B

    2

    L

    2

    2

    Transformer voltage regulation

    Therefore NM = (NC)2/2(OC)

    NC = LC LN = LC BD

    = I2

    Xe2

    cos2

    - I2

    Re2

    sin2

  • 8/6/2019 Chapter4 Trans

    68/104

    68

    I2Xe2

    I2Re2

    I2

    V2

    O

    V20

    I2Re2

    I2Xe2

    C

    MNDA

    B

    2

    L

    2

    2

    20

    2

    222222

    2

    sincos

    V

    RIXIee

    UU

    20

    2

    222222

    2

    sincos

    V

    RIXIee

    UU

    NM =

    AM = AD + DN + NM

    = I2Recos

    2 + I2Xe2sin

    2 +

    Transformer voltage regulation

  • 8/6/2019 Chapter4 Trans

    69/104

    69

    I2Xe2

    I2Re2

    I2

    V2

    O

    V20

    I2Re2

    I2Xe2

    C

    MNDA

    B

    2

    L

    2

    2

    Transformer voltage regulation

    thus,votage regulation = (AM)/V20 per unit

    In actual practice the term NM is negligible since its value isvery small compared with V 2. Thus the votage regulation

    formula can be reduced to:

  • 8/6/2019 Chapter4 Trans

    70/104

    70

    I2Xe2

    I2Re2

    I2

    V2

    O

    V20

    I2Re2

    I2Xe2

    C

    MNDA

    B

    2

    L

    2

    2

    Transformer voltage regulation

    Voltage regulation =

    20

    222222 sincos

    V

    XIRIee

    UU s

  • 8/6/2019 Chapter4 Trans

    71/104

    71

    Transformer- voltage regulation The voltage regulation is expressed as

    follows:

    NL

    LNL

    V

    VVregulationVoltage

    2

    22 !

    V2 L= secondar voltage (no-load condition)

    V2L = secondar voltage (full-load condition)

  • 8/6/2019 Chapter4 Trans

    72/104

    72

    Transformer- voltage regulation For the equivalentcircuit referred to the

    primary:

    1

    21

    V

    VVregulationVoltage

    '!

    V1 = no-load voltage

    V2 = secondar voltage referred to the primar (full-load condition)

  • 8/6/2019 Chapter4 Trans

    73/104

    73

    Transformer- voltage regulation Consider the equivalentcircuit referred to the

    secondary,

    Re2

    Xe2

    NL

    ee

    V

    sinXIcosIregulationVoltage

    2

    222222 UsU!

    (-) : power factor leading

    (+) : power factor lagging

  • 8/6/2019 Chapter4 Trans

    74/104

    74

    Transformer- voltage regulation Consider the equivalentcircuit referred to the primary,

    1

    211211

    V

    sinXIcosIregulationVoltage ee

    UsU!

    Re1

    Xe1

    (-) : power factor leading

    (+) : power factor lagging

  • 8/6/2019 Chapter4 Trans

    75/104

    75

    Transformer- voltage regulation Example 4.5

    Based on Example 4.3 calculate thevoltage regulation and the secondaryterminalvoltage for fullload having apower factor of

    (i) 0.8lagging (0.0336pu,14.8V)(ii) 0.8leading (-0.0154pu,447V)

  • 8/6/2019 Chapter4 Trans

    76/104

    76

    Transformer- Efficiency Losses in a transformer

    Copper losses in primary and secondary

    windings Core losses due to hysteresis and eddy

    current. Itdepends on maximum value offlux density, supply frequencyand core

    dimension. It is assumedto be constantforall loads

  • 8/6/2019 Chapter4 Trans

    77/104

    77

    Transformer- Efficiency As always, efficiency is defined as power outputto

    power input ratio

    The losses in the transformer are the core loss(Pc) and copper loss (Pcu).

    lossesP

    P

    )P(powerinput)P(powe

    routput

    out

    out

    in

    out

    !

    !L

    222222

    222

    ec IPcosIV

    cosIV

    U

    U!L

  • 8/6/2019 Chapter4 Trans

    78/104

    78

    Transformer- Efficiency Efficiencyon full load

    where S is the apparentpower (in voltamperes)

    scocFLFL

    FLFL

    PPSS

    ! U UL cos

    cos

  • 8/6/2019 Chapter4 Trans

    79/104

    79

    Transformer- Efficiency Efficiency for any load equal to n x f ull load

    where corresponding total loss =

    scocFLFL

    FLFL

    PnPSn

    Sn

    vv

    v!2cos

    cosU

    UL

    scoc PnP v2

  • 8/6/2019 Chapter4 Trans

    80/104

    80

    Transformer- Efficiency Example 4.6

    The following results were obtained on a 50 kVA

    transformer: open circuittest primaryvoltage,3300 V; secondaryvoltage, 400 V; primarypower,430W.Shortcircuittest primaryvoltage,124V;primarycurrent, 15.3 A; primarypower,525W; secondarycurrent, full load value. Calculatethe efficiency at full load and half load for 0.7power factor.

    (97.3%, 96.9%)

  • 8/6/2019 Chapter4 Trans

    81/104

    81

    Transformer- Efficiency For constantvalues ofthe terminal voltage V2 and

    load power factor angle 2 , the maximum efficiencyoccurs when

    Ifthis condition is applied, the condition for

    maximum efficiency is

    thatis, core loss = copper loss.

    0

    2

    !LdI

    d

    222 ec IP !

  • 8/6/2019 Chapter4 Trans

    82/104

    82

    Transformer- Efficiency

  • 8/6/2019 Chapter4 Trans

    83/104

  • 8/6/2019 Chapter4 Trans

    84/104

    84

    Transformer- Auto transformer Same operation as two windings

    transformer

    Physical connection from primary tosecondary

    Sliding connection allows for variablevoltage

    Higher kVA delivery than two windingsconnection

  • 8/6/2019 Chapter4 Trans

    85/104

    85

    Transformer- Auto transformer Advantages:

    A tap between primary and secondary sides which

    may be adjustable to provide step-up/downcapability

    Able to transfer larger S apparent power than thetwo winding transformer

    Smaller and lighter than an equivalent two-

    winding transformer Disadvantage:

    Lacks electrical isolation

  • 8/6/2019 Chapter4 Trans

    86/104

    86

    Transformer- Auto transformerA Step Down Autotransformer:

    and

  • 8/6/2019 Chapter4 Trans

    87/104

    87

    Transformer- Auto transformerA Step Up Autotransformer:

    and

  • 8/6/2019 Chapter4 Trans

    88/104

    88

    Transformer- Auto transformer Example 4.7

    An autotransformer with a 40% tap is supplied by a

    400-V, 60-Hz source andis used for step-downoperation. A5-kVA load operating at unity powerfactor is connected to the secondary terminals.

    Find:

    (a) the secondary voltage,(b) the secondary current,(c) the primary current.

  • 8/6/2019 Chapter4 Trans

    89/104

    89

    Transformer- Auto transformer Solution

  • 8/6/2019 Chapter4 Trans

    90/104

  • 8/6/2019 Chapter4 Trans

    91/104

    91

    Transformer -3 phase transformer Analyses of the grounded wye / delta transformer

    Each leg has a

    primary and a

    secondary winding.

    The voltages and

    currents are in phase

    in the windings

    located on the same

    leg.

    The primary phase-to-

    line voltage generates

    the secondary line-to-

    line voltage. These

    voltages are in phase

    A B C

    VAN VBN VCN

    Vab Vbc Vca

    N

    a b c

  • 8/6/2019 Chapter4 Trans

    92/104

    92

    Transformer -3 phase transformer Analyses of the grounded wye / delta transformer

    IA

    IB

    IC

    N

    IAN

    ICNIBN

    Iab

    Ibc

    Ica

    Ib

    Ia

    Ic

  • 8/6/2019 Chapter4 Trans

    93/104

    93

    Transformer -3 phase transformer Analyses of the grounded wye / delta transformer

    VCA

    VAB

    N

    VAN

    VCN

    VBN

    Vbc

    Vbc

    Vab

    Vca

    Vab

    A

    C

    B

    a

    c

    b

    VB C Vbc

  • 8/6/2019 Chapter4 Trans

    94/104

    94

    Three phase transformerTransformer -3 phase transformer

  • 8/6/2019 Chapter4 Trans

    95/104

    95

    Three phase transformerTransformer

  • 8/6/2019 Chapter4 Trans

    96/104

    96

    Three phase transformerTransformer

  • 8/6/2019 Chapter4 Trans

    97/104

    97

    Three phase transformerTransformer

  • 8/6/2019 Chapter4 Trans

    98/104

    98

    Three phase transformerTransformer

  • 8/6/2019 Chapter4 Trans

    99/104

    99

    Transformer Three phase transformer

    TransformerConstruction

    Iron Core

    The iron core is made of thin

    laminated silicon steel (2-3 %

    silicon)

    Pre-cut insulated sheets are

    cut or pressed in form and

    placed on the top of eachother .

    The sheets are overlap each

    others to avoid (reduce) air

    gaps.

    The core is pressed together

    by insulated yokes.

  • 8/6/2019 Chapter4 Trans

    100/104

    100

    Transformer Three phase transformer

    TransformerConstruction Winding

    The winding is made of copper or

    aluminum conductor, insulated withpaper or synthetic insulating material

    (kevlar, maylard).

    The windings are manufactured in

    several layers, and insulation is

    placed between windings.

    The primary and secondary windingsare placed on top of each others but

    insulated by several layers of

    insulating sheets.

    The windings are dried in vacuum

    and impregnated to eliminate

    moisture.

    Small transformer winding

  • 8/6/2019 Chapter4 Trans

    101/104

    101

    Transformer Three phase transformer

    TransformerConstruction

    Iron Cores

    The three phase transformer iron

    core has three legs.

    A phase winding is placed in

    each leg.

    The high voltage and low voltage

    windings are placed on top ofeach other and insulated by

    layers or tubes.

    Larger transformer use layered

    construction shown in the

    previous slides.

    A B C

    Three phase transformer iron core

  • 8/6/2019 Chapter4 Trans

    102/104

    102

    Transformer Three phase transformer

    TransformerConstruction

    The dried and treated

    transformer is placed in a steeltank.

    The tank is filled, under vacuum,

    with heated transformer oil.

    The end of the windings are

    connected to bushings.

    The oil is circulated by pumps

    and forced through the radiators.

    Three phase oil transformer

  • 8/6/2019 Chapter4 Trans

    103/104

    103

    Transformer Three phase transformer

    TransformerConstruction

    The transformer is equipped with

    cooling radiators which arecooled by forced ventilation.

    Cooling fans are installed under

    the radiators.

    Large bushings connect the

    windings to the electrical system.

    The oil is circulated by pumps

    and forced through the radiators.

    The oil temperature, pressure

    are monitored to predict

    transformer performance.

    Three phase oil transformer

  • 8/6/2019 Chapter4 Trans

    104/104

    Transformer Three phase transformer

    TransformerConstruction

    Dry type transformers are used

    at medium and low voltage.

    The winding is vacuumed and

    dried before the molding.

    The winding is insulated by

    epoxy resin

    The slide shows a three phase,

    dry type transformer.

    Dry type transformer